Files
Observium_CE/mibs/webgraph/WebGraph-AnalogIn-57644-US-MIB

2534 lines
82 KiB
Plaintext

WebGraph-AnalogIn-57644-US-MIB DEFINITIONS ::= BEGIN
----------------------------------------------------------------
-- Revison: 1.29
----------------------------------------------------------------
-- 22.06.2010 Webio
-- Syntax correction
----------------------------------------------------------------
-- Revison: 1.28
----------------------------------------------------------------
-- 02.12.2008 Webio
-- New Graphics java script base parameter
----------------------------------------------------------------
-- Revison: 1.27
----------------------------------------------------------------
-- 09.11.2006 Webio
-- DHCP enable
----------------------------------------------------------------
-- Revison: 1.26
----------------------------------------------------------------
-- 28.06.2006 New: Community String Trap
--
----------------------------------------------------------------
-- Revison: 1.25
----------------------------------------------------------------
-- 25.11.2005 #57644, WebGraph AnalogIn 2x 0..10V
--
----------------------------------------------------------------
-- Revison: 1.24
----------------------------------------------------------------
-- 26.07.2005 #57644, WebGraph AnalogIn
-- CRON timer function
----------------------------------------------------------------
-- Revison: 1.23
----------------------------------------------------------------
-- 14.07.2005 #57644, WebGraph AnalogIn
-- FTP functions
----------------------------------------------------------------
-- Revison: 1.22
----------------------------------------------------------------
-- 17.05.2005 #57644, WebGraph AnalogIn
-- Trap NMS annotations
----------------------------------------------------------------
-- Revison: 1.21
----------------------------------------------------------------
-- 19.04.2005 #57605, WebGraph Themometer
-- Mail Authentication
----------------------------------------------------------------
-- Revison: 1.20
----------------------------------------------------------------
-- 05.11.2004 #57606, WebGraph Thermo-Hygrometer
-- New: Syslog
--
----------------------------------------------------------------
-- Revison: 1.19
----------------------------------------------------------------
-- 08.09.2004 #57606 WebGraph Thermo-Hygrometer
-- New:
-- wtWebGraphThermHygroAlarmRHMin
-- wtWebGraphThermHygroAlarmRHMax
-- wtWebGraphThermHygroAlarmRHHysteresis
-- wtWebGraphThermHygroPortSensorSelect
-- wtWebGraphThermHygroAlarmDeltaTemp
-- wtWebGraphThermHygroAlarmAHMin
-- wtWebGraphThermHygroAlarmAHMax
----------------------------------------------------------------
-- Revison: 1.18
----------------------------------------------------------------
-- 21.07.2004 #57601/3/4, Webio Anx
-- New:
-- Diagnosis
----------------------------------------------------------------
-- Revison: 1.17
----------------------------------------------------------------
-- 28.06.2004 #57630/1/2, Webio Digital
-- Neu: Puls Mode
----------------------------------------------------------------
-- Revison: 1.16
----------------------------------------------------------------
-- 16.04.2004 New: #57632, Webio Digital EA24x24
--
-- #57630/1, Webio Digital EA12x12
-- New:
-- wtWebioEA12x12InputCounterClear
----------------------------------------------------------------
-- Revison: 1.15
----------------------------------------------------------------
-- 27.02.2004 #57630/1, Webio Digital EA12x12
-- New:
-- Length changed to 32 Bit:
-- wtWebioEA12x12InputValue
-- wtWebioEA12x12OutputValue
-- wtWebioEA12x12LoadControlView
-- wtWebioEA12x12LCShutDownView
-- wtWebioEA12x12SetOutput
-- wtWebioEA12x12AlarmInputTrigger
-- wtWebioEA12x12AlarmOutputTrigger
-- wtWebioEA12x12PortOutputSafetyState
----------------------------------------------------------------
-- Revison: 1.14
----------------------------------------------------------------
-- 16.02.2004 #57630/1, Webio Digital EA12x12
-- New:
-- Text: Location, Contact
-- SNMP: ColdStart, WarmStart, ComunityString Read/RW
-- Alarm: ColdStart / WarmStart trigger
--
-- #57601, 1xWebThermometer
-- #57603, 2xWebThermometer
-- #57604, 8xWebThermometer
-- New:
-- Alarm Hysteresis
-- Alarm Clear Traps and Mails
----------------------------------------------------------------
-- Revison: 1.13
----------------------------------------------------------------
-- 05.02.2004 #57601, 1xWebThermometer
-- #57603, 2xWebThermometer
-- #57604, 8xWebThermometer
-- New:
-- Text: Location, Contact
-- SNMP: ColdStart, WarmStart, ComunityString Read/RW
-- Alarm: ColdStart / WarmStart trigger
----------------------------------------------------------------
-- Revison: 1.12
----------------------------------------------------------------
-- 05.11.2003 #57601, 1xWebThermometer
-- #57603, 2xWebThermometer
-- #57604, 8xWebThermometer
-- New features:
-- Mail : Option CSV attachment
-- Port : Offset calibration
-- Alarm : TCP Client mode
----------------------------------------------------------------
-- Revison: 1.11
----------------------------------------------------------------
-- 28.10.2003 #57630/1, Webio Digital EA12x12
-- New features:
-- Alarm : TCP Client mode
-- Inputs: Puls filter
----------------------------------------------------------------
-- Revison: 1.10
----------------------------------------------------------------
-- 22.07.2003 #57630, Webio Digital EA12x12
-- New navigation tree, new binary modes
--
----------------------------------------------------------------
-- Revison: 1.09
----------------------------------------------------------------
-- 24.03.2003 Trap Enterprise (Type 1, 2) corrected
----------------------------------------------------------------
-- Revison: 1.08
----------------------------------------------------------------
-- 04.03.2003 reconciled the language versions DE/US
----------------------------------------------------------------
-- Revison: 1.07
----------------------------------------------------------------
-- 25.02.2003 Correction: wtWebioEA12x12LoadControl
----------------------------------------------------------------
-- Revison: 1.06
----------------------------------------------------------------
-- 24.02.2003 New:
-- #57630, Webio EA12x12, LoadControl Group
-- Correction: Trap variable names
----------------------------------------------------------------
-- Revison: 1.05
----------------------------------------------------------------
-- 21.01.2003 New:
-- #57630, Webio EA12x12
----------------------------------------------------------------
-- Revison: 1.04
----------------------------------------------------------------
-- 02.01.2003 New:
-- #57601, 1xWebThermometer
-- #57603, 2xWebThermometer, 8 alarms
----------------------------------------------------------------
-- Revison: 1.03
----------------------------------------------------------------
-- 21.11.2002 New:
-- #57604, 2xWebThermometer, BOOTP, StartupSite
-- #57603, 8xWebThermometer, BOOTP, StartupSite
----------------------------------------------------------------
-- Revison: 1.02
----------------------------------------------------------------
-- 26.07.2002 New:
-- #57604, 2xWebThermometer
-- #57603, 8xWebThermometer
--
IMPORTS
OBJECT-TYPE FROM RFC-1212
TRAP-TYPE FROM RFC-1215
DisplayString, PhysAddress FROM RFC1213-MIB
enterprises, TimeTicks, IpAddress, NetworkAddress FROM RFC1155-SMI;
-- IpAddress ::=
-- [APPLICATION 0]
-- IMPLICIT OCTET STRING (SIZE (4))
-- Counter ::=
-- [APPLICATION 1]
-- IMPLICIT INTEGER (0..4294967295)
-- Gauge ::=
-- [APPLICATION 2]
-- IMPLICIT INTEGER (0..4294967295)
-- TimeTicks ::=
-- [APPLICATION 3]
-- IMPLICIT INTEGER (0..4294967295)
-- DisplayString ::= OCTET STRING
-- PhysAddress ::= OCTET STRING
-- internet OBJECT IDENTIFIER ::= { iso org(3) dod(6) 1 }
-- privat OBJECT IDENTIFIER ::= { internet 4 }
-- enterprises OBJECT IDENTIFIER ::= { privat 1 }
-- Wiesemann & Theis Com-Server MIB
wut OBJECT IDENTIFIER ::= { enterprises 5040 }
wtComServer OBJECT IDENTIFIER ::= { wut 1 }
wtWebio OBJECT IDENTIFIER ::= { wtComServer 2 }
-- wtWebGraph Tree
wtWebGraphAnalogIn57644 OBJECT IDENTIFIER ::= { wtWebio 12 }
-- wtWebGraphAnalogIn57644 Tree
wtWebGraphAnalogIn57644Inventory OBJECT IDENTIFIER ::= { wtWebGraphAnalogIn57644 1 }
wtWebGraphAnalogIn57644SessCntrl OBJECT IDENTIFIER ::= { wtWebGraphAnalogIn57644 2 }
wtWebGraphAnalogIn57644Config OBJECT IDENTIFIER ::= { wtWebGraphAnalogIn57644 3 }
wtWebGraphAnalogIn57644Diag OBJECT IDENTIFIER ::= { wtWebGraphAnalogIn57644 4 }
-- wtWebGraphAnalogIn57644Config Tree
wtWebGraphAnalogIn57644Device OBJECT IDENTIFIER ::= { wtWebGraphAnalogIn57644Config 1 }
wtWebGraphAnalogIn57644Ports OBJECT IDENTIFIER ::= { wtWebGraphAnalogIn57644Config 2 }
wtWebGraphAnalogIn57644Manufact OBJECT IDENTIFIER ::= { wtWebGraphAnalogIn57644Config 3 }
-- wtWebGraphAnalogIn57644Device Tree
wtWebGraphAnalogIn57644Text OBJECT IDENTIFIER ::= { wtWebGraphAnalogIn57644Device 1 }
wtWebGraphAnalogIn57644TimeDate OBJECT IDENTIFIER ::= { wtWebGraphAnalogIn57644Device 2 }
wtWebGraphAnalogIn57644Basic OBJECT IDENTIFIER ::= { wtWebGraphAnalogIn57644Device 3 }
wtWebGraphAnalogIn57644Datalogger OBJECT IDENTIFIER ::= { wtWebGraphAnalogIn57644Device 4 }
wtWebGraphAnalogIn57644Alarm OBJECT IDENTIFIER ::= { wtWebGraphAnalogIn57644Device 5 }
wtWebGraphAnalogIn57644Graphics OBJECT IDENTIFIER ::= { wtWebGraphAnalogIn57644Device 6 }
-- wtWebGraphAnalogIn57644TimeDate Tree
wtWebGraphAnalogIn57644TimeZone OBJECT IDENTIFIER ::= { wtWebGraphAnalogIn57644TimeDate 1 }
wtWebGraphAnalogIn57644TimeServer OBJECT IDENTIFIER ::= { wtWebGraphAnalogIn57644TimeDate 2 }
wtWebGraphAnalogIn57644DeviceClock OBJECT IDENTIFIER ::= { wtWebGraphAnalogIn57644TimeDate 3 }
-- wtWebGraphAnalogIn57644Basic Tree
wtWebGraphAnalogIn57644Network OBJECT IDENTIFIER ::= { wtWebGraphAnalogIn57644Basic 1 }
wtWebGraphAnalogIn57644HTTP OBJECT IDENTIFIER ::= { wtWebGraphAnalogIn57644Basic 2 }
wtWebGraphAnalogIn57644Mail OBJECT IDENTIFIER ::= { wtWebGraphAnalogIn57644Basic 3 }
wtWebGraphAnalogIn57644SNMP OBJECT IDENTIFIER ::= { wtWebGraphAnalogIn57644Basic 4 }
wtWebGraphAnalogIn57644UDP OBJECT IDENTIFIER ::= { wtWebGraphAnalogIn57644Basic 5 }
wtWebGraphAnalogIn57644Syslog OBJECT IDENTIFIER ::= { wtWebGraphAnalogIn57644Basic 6 }
wtWebGraphAnalogIn57644FTP OBJECT IDENTIFIER ::= { wtWebGraphAnalogIn57644Basic 7 }
-- wtWebGraphAnalogIn57644Graphics Tree
wtWebGraphAnalogIn57644GraphicsBase OBJECT IDENTIFIER ::= { wtWebGraphAnalogIn57644Graphics 1 }
wtWebGraphAnalogIn57644GraphicsSelect OBJECT IDENTIFIER ::= { wtWebGraphAnalogIn57644Graphics 2 }
wtWebGraphAnalogIn57644GraphicsScale OBJECT IDENTIFIER ::= { wtWebGraphAnalogIn57644Graphics 3 }
-- wtWebGraphAnalogIn57644Inventory Group
------------------------
wtWebGraphAnalogIn57644Sensors OBJECT-TYPE
SYNTAX INTEGER (1..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of sensors"
::= { wtWebGraphAnalogIn57644Inventory 1 }
-- Interface Table
wtWebGraphAnalogIn57644SensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebGraphAnalogIn57644SensorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"List of sensors."
::= { wtWebGraphAnalogIn57644Inventory 2 }
wtWebGraphAnalogIn57644SensorEntry OBJECT-TYPE
SYNTAX WtWebGraphAnalogIn57644SensorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"List of sensor numbers."
INDEX { wtWebGraphAnalogIn57644SensorNo }
::= { wtWebGraphAnalogIn57644SensorTable 1 }
WtWebGraphAnalogIn57644SensorEntry ::= SEQUENCE {
wtWebGraphAnalogIn57644SensorNo INTEGER
}
wtWebGraphAnalogIn57644SensorNo OBJECT-TYPE
SYNTAX INTEGER (1..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Sensor number."
::= { wtWebGraphAnalogIn57644SensorEntry 1 }
-- wtWebGraphAnalogIn57644Values Table
wtWebGraphAnalogIn57644ValuesTable OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebGraphAnalogIn57644ValuesEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"List of measurement values corresponding to the channel numbers."
::= { wtWebGraphAnalogIn57644Inventory 3 }
wtWebGraphAnalogIn57644ValuesEntry OBJECT-TYPE
SYNTAX WtWebGraphAnalogIn57644ValuesEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Measurement values of the sensors."
INDEX { wtWebGraphAnalogIn57644SensorNo }
::= { wtWebGraphAnalogIn57644ValuesTable 1 }
WtWebGraphAnalogIn57644ValuesEntry ::= SEQUENCE{
wtWebGraphAnalogIn57644Values OCTET STRING
}
wtWebGraphAnalogIn57644Values OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (5))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Measurement value of the sensor, ASCII, 7 characters in length."
::= { wtWebGraphAnalogIn57644ValuesEntry 1 }
-- wtWebGraphAnalogIn57644BinaryValues Table
wtWebGraphAnalogIn57644BinaryValuesTable OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebGraphAnalogIn57644BinaryValuesEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"List of binary measurement values corresponding to the channel numbers."
::= { wtWebGraphAnalogIn57644Inventory 4 }
wtWebGraphAnalogIn57644BinaryValuesEntry OBJECT-TYPE
SYNTAX WtWebGraphAnalogIn57644BinaryValuesEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Binary measurement values of the sensors."
INDEX { wtWebGraphAnalogIn57644SensorNo }
::= { wtWebGraphAnalogIn57644BinaryValuesTable 1 }
WtWebGraphAnalogIn57644BinaryValuesEntry ::= SEQUENCE{
wtWebGraphAnalogIn57644BinaryValues INTEGER
}
wtWebGraphAnalogIn57644BinaryValues OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Binary measurement value of the sensor in 1/10 degrees Celsius or 1/10 per cent,
signed number, 0x4FFF6 indicates an
invalid measured value."
::= { wtWebGraphAnalogIn57644BinaryValuesEntry 1 }
-- wtWebGraphAnalogIn57644SessCntrl Group
--------------------------------
wtWebGraphAnalogIn57644SessCntrlPassword OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Entering this password opens a session which is ended by writing a 1 to
wtWebGraphAnalogIn57644SessCntrlLogout. When read this variable provides a string of
length zero."
::= { wtWebGraphAnalogIn57644SessCntrl 1 }
wtWebGraphAnalogIn57644SessCntrlConfigMode OBJECT-TYPE
SYNTAX INTEGER {
wtWebGraphAnalogIn57644SessCntrl-NoSession(0),
wtWebGraphAnalogIn57644SessCntrl-Session(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"When the device is in SNMP configuration mode, the value 1 is
returned, otherwise 0. If the read value is 0 even though the
password was written, the device is already in config mode and the
variables can only be read."
::= { wtWebGraphAnalogIn57644SessCntrl 2 }
wtWebGraphAnalogIn57644SessCntrlLogout OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"If the device is in configuration mode and the session was opened by
this SNMP Manager, writing a 1 to this variable will end the session
and all parameters are stored.
Writing a 2 discards all entries again.
When read this variable provides the value 0."
::= { wtWebGraphAnalogIn57644SessCntrl 3 }
wtWebGraphAnalogIn57644SessCntrlAdminPassword OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This password protects access to the variables with administrator rights.
It can only be changed by the administrator. If no password was assigned,
the valid password is public."
::= { wtWebGraphAnalogIn57644SessCntrl 4 }
wtWebGraphAnalogIn57644SessCntrlConfigPassword OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This password protects access to the variables with configurator rights. It can
be changed by the administrator and by the configurator. If no password was assigned,
the valid password is public. When read this variable provides a null-pointer."
::= { wtWebGraphAnalogIn57644SessCntrl 5 }
-- wtWebGraphAnalogIn57644Text Group
------------------------
wtWebGraphAnalogIn57644DeviceName OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name of the Webio, which is user definable."
::= { wtWebGraphAnalogIn57644Text 1 }
wtWebGraphAnalogIn57644DeviceText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Description of the Webio, which is user definable."
::= { wtWebGraphAnalogIn57644Text 2 }
wtWebGraphAnalogIn57644DeviceLocation OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Description of the location of the Webio, which is user definable."
::= { wtWebGraphAnalogIn57644Text 3 }
wtWebGraphAnalogIn57644DeviceContact OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Contact address of the system operator of the Webio, which is user definable."
::= { wtWebGraphAnalogIn57644Text 4 }
-- wtWebGraphAnalogIn57644TimeZone Group
----------------------------
wtWebGraphAnalogIn57644TzOffsetHrs OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset hours for the time zone (winter time) with respect to UTC."
::= { wtWebGraphAnalogIn57644TimeZone 1 }
wtWebGraphAnalogIn57644TzOffsetMin OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset minutes for the time zone (winter time) with respect to UTC."
::= { wtWebGraphAnalogIn57644TimeZone 2 }
wtWebGraphAnalogIn57644TzEnable OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded conditions:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : Apply Timezone"
::= { wtWebGraphAnalogIn57644TimeZone 3 }
wtWebGraphAnalogIn57644StTzOffsetHrs OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset hours of the time zone (summer time) with respect to UTC."
::= { wtWebGraphAnalogIn57644TimeZone 4 }
wtWebGraphAnalogIn57644StTzOffsetMin OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset minutes of the time zone (summer time) with respect to UTC."
::= { wtWebGraphAnalogIn57644TimeZone 5 }
wtWebGraphAnalogIn57644StTzEnable OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded conditions:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : Apply Summertime"
::= { wtWebGraphAnalogIn57644TimeZone 6 }
wtWebGraphAnalogIn57644StTzStartMonth OBJECT-TYPE
SYNTAX INTEGER {
wtWebGraphAnalogIn57644StartMonth-January(1),
wtWebGraphAnalogIn57644StartMonth-February(2),
wtWebGraphAnalogIn57644StartMonth-March(3),
wtWebGraphAnalogIn57644StartMonth-April(4),
wtWebGraphAnalogIn57644StartMonth-May(5),
wtWebGraphAnalogIn57644StartMonth-June(6),
wtWebGraphAnalogIn57644StartMonth-July(7),
wtWebGraphAnalogIn57644StartMonth-August(8),
wtWebGraphAnalogIn57644StartMonth-September(9),
wtWebGraphAnalogIn57644StartMonth-October(10),
wtWebGraphAnalogIn57644StartMonth-November(11),
wtWebGraphAnalogIn57644StartMonth-December(12)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Month in which the change is made from winter time to summer time."
::= { wtWebGraphAnalogIn57644TimeZone 7 }
wtWebGraphAnalogIn57644StTzStartMode OBJECT-TYPE
SYNTAX INTEGER {
wtWebGraphAnalogIn57644StartMode-first(1),
wtWebGraphAnalogIn57644StartMode-second(2),
wtWebGraphAnalogIn57644StartMode-third(3),
wtWebGraphAnalogIn57644StartMode-fourth(4),
wtWebGraphAnalogIn57644StartMode-last(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Mode of the day of the week for which the change is made from winter time to summer time."
::= { wtWebGraphAnalogIn57644TimeZone 8 }
wtWebGraphAnalogIn57644StTzStartWday OBJECT-TYPE
SYNTAX INTEGER {
wtWebGraphAnalogIn57644StartWday-Sunday(1),
wtWebGraphAnalogIn57644StartWday-Monday(2),
wtWebGraphAnalogIn57644StartWday-Tuesday(3),
wtWebGraphAnalogIn57644StartWday-Thursday(4),
wtWebGraphAnalogIn57644StartWday-Wednesday(5),
wtWebGraphAnalogIn57644StartWday-Friday(6),
wtWebGraphAnalogIn57644StartWday-Saturday(7)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Day of the week on which the change is made from winter time to summer time"
::= { wtWebGraphAnalogIn57644TimeZone 9 }
wtWebGraphAnalogIn57644StTzStartHrs OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Hour in which the time zone is changed from winter to summer time with
respect to UTC."
::= { wtWebGraphAnalogIn57644TimeZone 10 }
wtWebGraphAnalogIn57644StTzStartMin OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Minute in which the time zone is changed from winter to summer time with
respect to UTC."
::= { wtWebGraphAnalogIn57644TimeZone 11 }
wtWebGraphAnalogIn57644StTzStopMonth OBJECT-TYPE
SYNTAX INTEGER {
wtWebGraphAnalogIn57644StopMonth-January(1),
wtWebGraphAnalogIn57644StopMonth-February(2),
wtWebGraphAnalogIn57644StopMonth-March(3),
wtWebGraphAnalogIn57644StopMonth-April(4),
wtWebGraphAnalogIn57644StopMonth-May(5),
wtWebGraphAnalogIn57644StopMonth-June(6),
wtWebGraphAnalogIn57644StopMonth-July(7),
wtWebGraphAnalogIn57644StopMonth-August(8),
wtWebGraphAnalogIn57644StopMonth-September(9),
wtWebGraphAnalogIn57644StopMonth-October(10),
wtWebGraphAnalogIn57644StopMonth-November(11),
wtWebGraphAnalogIn57644StopMonth-December(12)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Month in which the change is made from summer time to winter time."
::= { wtWebGraphAnalogIn57644TimeZone 12 }
wtWebGraphAnalogIn57644StTzStopMode OBJECT-TYPE
SYNTAX INTEGER {
wtWebGraphAnalogIn57644StopMode-first(1),
wtWebGraphAnalogIn57644StopMode-second(2),
wtWebGraphAnalogIn57644StopMode-third(3),
wtWebGraphAnalogIn57644StopMode-fourth(4),
wtWebGraphAnalogIn57644StopMode-last(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Mode of the week day on which the change is made from summer time to winter time."
::= { wtWebGraphAnalogIn57644TimeZone 13 }
wtWebGraphAnalogIn57644StTzStopWday OBJECT-TYPE
SYNTAX INTEGER {
wtWebGraphAnalogIn57644StopWday-Sunday(1),
wtWebGraphAnalogIn57644StopWday-Monday(2),
wtWebGraphAnalogIn57644StopWday-Tuesday(3),
wtWebGraphAnalogIn57644StopWday-Thursday(4),
wtWebGraphAnalogIn57644StopWday-Wednesday(5),
wtWebGraphAnalogIn57644StopWday-Friday(6),
wtWebGraphAnalogIn57644StopWday-Saturday(7)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Day of the week on which the change is made from summer time to winter time."
::= { wtWebGraphAnalogIn57644TimeZone 14 }
wtWebGraphAnalogIn57644StTzStopHrs OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Hour at which the time zone is changed from summer to winter time with
respect to UTC."
::= { wtWebGraphAnalogIn57644TimeZone 15 }
wtWebGraphAnalogIn57644StTzStopMin OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Minute at which the time zone is changed from summer to winter time with
respect to UTC."
::= { wtWebGraphAnalogIn57644TimeZone 16 }
-- wtWebGraphAnalogIn57644TimeServer Group
----------------------------
wtWebGraphAnalogIn57644TimeServer1 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"IP address or name of the 1st time server in ASCII"
::= { wtWebGraphAnalogIn57644TimeServer 1 }
wtWebGraphAnalogIn57644TimeServer2 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"IP address or name of the 2nd time server in ASCII"
::= { wtWebGraphAnalogIn57644TimeServer 2 }
wtWebGraphAnalogIn57644TsEnable OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded conditions:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : Apply Time Server"
::= { wtWebGraphAnalogIn57644TimeServer 3 }
wtWebGraphAnalogIn57644TsSyncTime OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Daily synchronisation time with the time server (hour: 0-23)."
::= { wtWebGraphAnalogIn57644TimeServer 4 }
-- wtWebGraphAnalogIn57644DeviceClock Group
----------------------------
wtWebGraphAnalogIn57644ClockHrs OBJECT-TYPE
SYNTAX INTEGER (0..23)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Clock hours taking into account the time zone settings."
::= { wtWebGraphAnalogIn57644DeviceClock 1 }
wtWebGraphAnalogIn57644ClockMin OBJECT-TYPE
SYNTAX INTEGER (0..59)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Clock minutes taking into account the time zone settings."
::= { wtWebGraphAnalogIn57644DeviceClock 2 }
wtWebGraphAnalogIn57644ClockDay OBJECT-TYPE
SYNTAX INTEGER (1..31)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Date: Day of the month, taking into account the time zone settings."
::= { wtWebGraphAnalogIn57644DeviceClock 3 }
wtWebGraphAnalogIn57644ClockMonth OBJECT-TYPE
SYNTAX INTEGER {
wtWebGraphAnalogIn57644ClockMonth-January(1),
wtWebGraphAnalogIn57644ClockMonth-February(2),
wtWebGraphAnalogIn57644ClockMonth-March(3),
wtWebGraphAnalogIn57644ClockMonth-April(4),
wtWebGraphAnalogIn57644ClockMonth-May(5),
wtWebGraphAnalogIn57644ClockMonth-June(6),
wtWebGraphAnalogIn57644ClockMonth-July(7),
wtWebGraphAnalogIn57644ClockMonth-August(8),
wtWebGraphAnalogIn57644ClockMonth-September(9),
wtWebGraphAnalogIn57644ClockMonth-October(10),
wtWebGraphAnalogIn57644ClockMonth-November(11),
wtWebGraphAnalogIn57644ClockMonth-December(12)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Date: Month, taking into account the time zone settings."
::= { wtWebGraphAnalogIn57644DeviceClock 4 }
wtWebGraphAnalogIn57644ClockYear OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Date: Year, taking into account the time zone settings."
::= { wtWebGraphAnalogIn57644DeviceClock 5 }
-- wtWebGraphAnalogIn57644Network Group
------------------------
wtWebGraphAnalogIn57644IpAddress OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"IP address of the Webio"
::= { wtWebGraphAnalogIn57644Network 1 }
wtWebGraphAnalogIn57644SubnetMask OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Subnet mask of the Webio"
::= { wtWebGraphAnalogIn57644Network 2 }
wtWebGraphAnalogIn57644Gateway OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Gateway of the Webio"
::= { wtWebGraphAnalogIn57644Network 3 }
wtWebGraphAnalogIn57644DnsServer1 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"IP address of the 1st DNS server in ASCII"
::= { wtWebGraphAnalogIn57644Network 4 }
wtWebGraphAnalogIn57644DnsServer2 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"IP address of the 2nd DNS server in ASCII"
::= { wtWebGraphAnalogIn57644Network 5 }
wtWebGraphAnalogIn57644AddConfig OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Additional configuration (1=ON):
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1: DHCP disable
Bit 0: BOOTP disable
"
::= { wtWebGraphAnalogIn57644Network 6 }
-- wtWebGraphAnalogIn57644HTTP Group
--------------------------------
wtWebGraphAnalogIn57644Startup OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded start page:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1: Index.htm
Bit 2: Home.htm
Bit 3: User.htm
Only one page may be selected at a time."
::= { wtWebGraphAnalogIn57644HTTP 1 }
wtWebGraphAnalogIn57644GetHeaderEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"If these bits are set, every answer of a short form GET question will be lead
by the IP-address and name of the device and/or a HTTP header:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-6: unused
Bit 1 : GET HTTP enable
Bit 0 : GET Header enable"
::= { wtWebGraphAnalogIn57644HTTP 2 }
wtWebGraphAnalogIn57644HttpPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Definition of the standard HTML port (Default: 80)."
::= { wtWebGraphAnalogIn57644HTTP 3 }
-- wtWebGraphAnalogIn57644Mail Group
--------------------------------
wtWebGraphAnalogIn57644MailAdName OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Device name for mail administration."
::= { wtWebGraphAnalogIn57644Mail 1 }
wtWebGraphAnalogIn57644MailReply OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Reply address for the mail server."
::= { wtWebGraphAnalogIn57644Mail 2 }
wtWebGraphAnalogIn57644MailServer OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name or IP address of the mail server."
::= { wtWebGraphAnalogIn57644Mail 3 }
wtWebioAn1MailEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set this bit to enable the sending of mails:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : Mail enable"
::= { wtWebGraphAnalogIn57644Mail 4 }
wtWebGraphAnalogIn57644MailAuthentication OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Selection of the authentication modi:
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output.
Bit 0 corresponds to the LSB.
OCTET 1: unused
OCTET 2: unused
OCTET 3: unused
OCTET 4: Bit 3-7: unused
Bit 2 : POP3 before SMTP
Bit 1 : ESMTP, authentication
Bit 0 : SMTP, no authentication"
::= { wtWebGraphAnalogIn57644Mail 5 }
wtWebGraphAnalogIn57644MailAuthUser OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name of the user to be authenticated."
::= { wtWebGraphAnalogIn57644Mail 6 }
wtWebGraphAnalogIn57644MailAuthPassword OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Authentication password."
::= { wtWebGraphAnalogIn57644Mail 7 }
wtWebGraphAnalogIn57644MailPop3Server OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name or Ip-address of the POP3 Servers."
::= { wtWebGraphAnalogIn57644Mail 8 }
-- wtWebGraphAnalogIn57644SNMP Group
--------------------------------
wtWebGraphAnalogIn57644SnmpCommunityStringRead OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Community string read only"
::= { wtWebGraphAnalogIn57644SNMP 1 }
wtWebGraphAnalogIn57644SnmpCommunityStringReadWrite OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Community string read / write"
::= { wtWebGraphAnalogIn57644SNMP 2 }
wtWebGraphAnalogIn57644SystemTrapManagerIP OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name or IP address of the TCP server which accepts the system trap."
::= { wtWebGraphAnalogIn57644SNMP 3 }
wtWebGraphAnalogIn57644SystemTrapEnable OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded trigger conditions:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: ColdStart
Bit 1: WarmStart
Bit 2-7: unused"
::= { wtWebGraphAnalogIn57644SNMP 4 }
wtWebGraphAnalogIn57644SnmpEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set bit 0 to enable SNMP.
If disabled, the device did not respond to any SNMP requests.
Bit 1 decided wether the community string of read operations
is compared with the system password or not:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : SNMP enable"
::= { wtWebGraphAnalogIn57644SNMP 5 }
wtWebGraphAnalogIn57644SnmpCommunityStringTrap OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Community string send within traps."
::= { wtWebGraphAnalogIn57644SNMP 6 }
-- wtWebGraphAnalogIn57644UDP Group
--------------------------------
wtWebGraphAnalogIn57644UdpPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Udp port to which the Udp queries ( short form GET requests) can be sent. This
port number must be unique within the device."
::= { wtWebGraphAnalogIn57644UDP 1 }
wtWebGraphAnalogIn57644UdpEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set this bit to enable UDP support:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : UDP enable"
::= { wtWebGraphAnalogIn57644UDP 2 }
-- wtWebGraphAnalogIn57644Syslog Group
--------------------------------
wtWebGraphAnalogIn57644SyslogServerIP OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name or IP address of the Syslog server, which accepts the Syslog messgaes."
::= { wtWebGraphAnalogIn57644Syslog 1 }
wtWebGraphAnalogIn57644SyslogServerPort OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Portnumber of the Syslog servers, default 514."
::= { wtWebGraphAnalogIn57644Syslog 2 }
wtWebGraphAnalogIn57644SyslogSystemMessagesEnable OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded trigger conditions:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: ColdStart
Bit 1: WarmStart
Bit 2: Diag Messages
Bit 3-7: unused"
::= { wtWebGraphAnalogIn57644Syslog 3 }
wtWebGraphAnalogIn57644SyslogEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set bit 0to enable Syslog:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : Syslog enable"
::= { wtWebGraphAnalogIn57644Syslog 4 }
-- wtWebGraphAnalogIn57644FTP Group
--------------------------------
wtWebGraphAnalogIn57644FTPServerIP OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name or IP address of the FTP server, which accepts the FTP messages."
::= { wtWebGraphAnalogIn57644FTP 1 }
wtWebGraphAnalogIn57644FTPServerControlPort OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Portnumber of the control port of the FTP server, default 21."
::= { wtWebGraphAnalogIn57644FTP 2 }
wtWebGraphAnalogIn57644FTPUserName OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"FTP Loggin: user name."
::= { wtWebGraphAnalogIn57644FTP 3 }
wtWebGraphAnalogIn57644FTPPassword OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"FTP Loggin: user password."
::= { wtWebGraphAnalogIn57644FTP 4 }
wtWebGraphAnalogIn57644FTPAccount OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"FTP Loggin: name of account."
::= { wtWebGraphAnalogIn57644FTP 5 }
wtWebGraphAnalogIn57644FTPOption OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Bit 0 switches the FTP Server in Passiv-Mode,
the Client controls the data connection on its own:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : PASV enable"
::= { wtWebGraphAnalogIn57644FTP 6 }
wtWebGraphAnalogIn57644FTPEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set Bit 0 to enable FTP:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : FTP enable"
::= { wtWebGraphAnalogIn57644FTP 7 }
-- wtWebGraphAnalogIn57644Datalogger Group
--------------------------------
wtWebGraphAnalogIn57644LoggerTimebase OBJECT-TYPE
SYNTAX INTEGER {
wtWebGraphAnalogIn57644Datalogger-1Min(1),
wtWebGraphAnalogIn57644Datalogger-5Min(2),
wtWebGraphAnalogIn57644Datalogger-15Min(3),
wtWebGraphAnalogIn57644Datalogger-60Min(4)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Time base of the data logger"
::= { wtWebGraphAnalogIn57644Datalogger 1 }
wtWebGraphAnalogIn57644LoggerSensorSel OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded trigger conditions:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: Sensor 1
Bit 1: Sensor 2
Bit 2-7: unused"
::= { wtWebGraphAnalogIn57644Datalogger 2 }
wtWebGraphAnalogIn57644DisplaySensorSel OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded sensor selection:
only selected sensors will be shown in the graphical presentation:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: Sensor 1
Bit 1: Sensor 2
Bit 2-7: unused"
::= { wtWebGraphAnalogIn57644Datalogger 3 }
-- Graph Sensor Color Table
wtWebGraphAnalogIn57644SensorColorTable OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebGraphAnalogIn57644SensorColorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"List of sensor colors for the praphical presentation."
::= { wtWebGraphAnalogIn57644Datalogger 4 }
wtWebGraphAnalogIn57644SensorColorEntry OBJECT-TYPE
SYNTAX WtWebGraphAnalogIn57644SensorColorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Index numbers of the sensors."
INDEX { wtWebGraphAnalogIn57644SensorNo }
::= { wtWebGraphAnalogIn57644SensorColorTable 1 }
WtWebGraphAnalogIn57644SensorColorEntry ::= SEQUENCE {
wtWebGraphAnalogIn57644SensorColor OCTET STRING
}
wtWebGraphAnalogIn57644SensorColor OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(3))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Color of the sensors at the praphical presention."
::= { wtWebGraphAnalogIn57644SensorColorEntry 1 }
wtWebGraphAnalogIn57644AutoScaleEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"If bit 0 is set, vertical auto scale is enabled:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : Auto Scale enable"
::= { wtWebGraphAnalogIn57644Datalogger 5 }
wtWebGraphAnalogIn57644VerticalUpperLimit OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This value defines the maximum temperature shown in the graphical presentation,
if no auto scaling is selected.
Temperature in degrees with maximum 2 decimal places."
::= { wtWebGraphAnalogIn57644Datalogger 6 }
wtWebGraphAnalogIn57644VerticalLowerLimit OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This value defines the minimum temperature shown in the graphical presentation,
if no auto scaling is selected.
Temperature in degrees with maximum 2 decimal places."
::= { wtWebGraphAnalogIn57644Datalogger 7 }
wtWebGraphAnalogIn57644HorizontalZoom OBJECT-TYPE
SYNTAX INTEGER {
wtWebGraphAnalogIn57644Zoom-25min(1),
wtWebGraphAnalogIn57644Zoom-75min(2),
wtWebGraphAnalogIn57644Zoom-5hrs(3),
wtWebGraphAnalogIn57644Zoom-30hrs(4),
wtWebGraphAnalogIn57644Zoom-5days(5),
wtWebGraphAnalogIn57644Zoom-25days(6)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Defines the default zoom stage, if no auto scaling is selected."
::= { wtWebGraphAnalogIn57644Datalogger 8 }
-- wtWebGraphAnalogIn57644Alarm Group
----------------------------
wtWebGraphAnalogIn57644AlarmCount OBJECT-TYPE
SYNTAX INTEGER (1..8)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of independent alarms."
::= { wtWebGraphAnalogIn57644Alarm 1 }
-- Alarm Interface Table
wtWebGraphAnalogIn57644AlarmIfTable OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebGraphAnalogIn57644AlarmIfEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"List of alarm indices."
::= { wtWebGraphAnalogIn57644Alarm 2 }
wtWebGraphAnalogIn57644AlarmIfEntry OBJECT-TYPE
SYNTAX WtWebGraphAnalogIn57644AlarmIfEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Numbers of the alarms."
INDEX { wtWebGraphAnalogIn57644AlarmNo }
::= { wtWebGraphAnalogIn57644AlarmIfTable 1 }
WtWebGraphAnalogIn57644AlarmIfEntry ::= SEQUENCE {
wtWebGraphAnalogIn57644AlarmNo INTEGER
}
wtWebGraphAnalogIn57644AlarmNo OBJECT-TYPE
SYNTAX INTEGER (1..8)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Alarm number."
::= { wtWebGraphAnalogIn57644AlarmIfEntry 1 }
-- Alarm Table
wtWebGraphAnalogIn57644AlarmTable OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebGraphAnalogIn57644AlarmEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"List of settings depending on the alarm number."
::= { wtWebGraphAnalogIn57644Alarm 3 }
wtWebGraphAnalogIn57644AlarmEntry OBJECT-TYPE
SYNTAX WtWebGraphAnalogIn57644AlarmEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Alarm parameters of the individual alarms."
INDEX { wtWebGraphAnalogIn57644AlarmNo }
::= { wtWebGraphAnalogIn57644AlarmTable 1 }
WtWebGraphAnalogIn57644AlarmEntry ::= SEQUENCE {
wtWebGraphAnalogIn57644AlarmTrigger OCTET STRING,
wtWebGraphAnalogIn57644AlarmMin OCTET STRING,
wtWebGraphAnalogIn57644AlarmMax OCTET STRING,
wtWebGraphAnalogIn57644AlarmHysteresis OCTET STRING,
wtWebGraphAnalogIn57644AlarmDelay OCTET STRING,
wtWebGraphAnalogIn57644AlarmInterval OCTET STRING,
wtWebGraphAnalogIn57644AlarmEnable OCTET STRING,
wtWebGraphAnalogIn57644AlarmEMailAddr OCTET STRING,
wtWebGraphAnalogIn57644AlarmMailSubject OCTET STRING,
wtWebGraphAnalogIn57644AlarmMailText OCTET STRING,
wtWebGraphAnalogIn57644AlarmManagerIP OCTET STRING,
wtWebGraphAnalogIn57644AlarmTrapText OCTET STRING,
wtWebGraphAnalogIn57644AlarmMailOptions OCTET STRING,
wtWebGraphAnalogIn57644AlarmTcpIpAddr OCTET STRING,
wtWebGraphAnalogIn57644AlarmTcpPort INTEGER,
wtWebGraphAnalogIn57644AlarmTcpText OCTET STRING,
wtWebGraphAnalogIn57644AlarmClearMailSubject OCTET STRING,
wtWebGraphAnalogIn57644AlarmClearMailText OCTET STRING,
wtWebGraphAnalogIn57644AlarmClearTrapText OCTET STRING,
wtWebGraphAnalogIn57644AlarmClearTcpText OCTET STRING,
wtWebGraphAnalogIn57644Alarm2Min OCTET STRING,
wtWebGraphAnalogIn57644Alarm2Max OCTET STRING,
wtWebGraphAnalogIn57644Alarm2Hysteresis OCTET STRING,
wtWebGraphAnalogIn57644AlarmSyslogIpAddr OCTET STRING,
wtWebGraphAnalogIn57644AlarmSyslogPort INTEGER,
wtWebGraphAnalogIn57644AlarmSyslogText OCTET STRING,
wtWebGraphAnalogIn57644AlarmSyslogClearText OCTET STRING,
wtWebGraphAnalogIn57644AlarmFtpDataPort OCTET STRING,
wtWebGraphAnalogIn57644AlarmFtpFileName OCTET STRING,
wtWebGraphAnalogIn57644AlarmFtpText OCTET STRING,
wtWebGraphAnalogIn57644AlarmFtpClearText OCTET STRING,
wtWebGraphAnalogIn57644AlarmFtpOption OCTET STRING,
wtWebGraphAnalogIn57644AlarmTimerCron OCTET STRING
}
wtWebGraphAnalogIn57644AlarmTrigger OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded trigger conditions:
Octet 1: unused
Octet 2: unused
Octet 3:
Bit 0: Timer
Bit 1: ColdStart
Bit 2: WarmStart
Octet 4:
Bit 0: Sensor 1
Bit 1: Sensor 2
Bit 2-7: unused"
::= { wtWebGraphAnalogIn57644AlarmEntry 1 }
wtWebGraphAnalogIn57644AlarmMin OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Minimum temperature in degrees with maximum 2 decimal places."
::= { wtWebGraphAnalogIn57644AlarmEntry 2 }
wtWebGraphAnalogIn57644AlarmMax OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Maximum temperature in degrees with maximum 2 decimal places."
::= { wtWebGraphAnalogIn57644AlarmEntry 3 }
wtWebGraphAnalogIn57644AlarmHysteresis OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Temperature changes of this size clears the alarm state (MAX-hyst, MIN+hyst.)
, in degrees with maximum 2 decimal places."
::= { wtWebGraphAnalogIn57644AlarmEntry 4 }
wtWebGraphAnalogIn57644AlarmDelay OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alarm will be delayed by setting this time while stable alarm
condition occur (time in minutes)."
::= { wtWebGraphAnalogIn57644AlarmEntry 5 }
wtWebGraphAnalogIn57644AlarmInterval OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Send interval for alarm messages."
::= { wtWebGraphAnalogIn57644AlarmEntry 6 }
wtWebGraphAnalogIn57644AlarmEnable OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded alarm enable:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: Mail Enable
Bit 1: SNMP Trap enable
Bit 2: TCP Client enable"
::= { wtWebGraphAnalogIn57644AlarmEntry 7 }
wtWebGraphAnalogIn57644AlarmEMailAddr OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"E-Mail address for sending the alarm mail to."
::= { wtWebGraphAnalogIn57644AlarmEntry 8 }
wtWebGraphAnalogIn57644AlarmMailSubject OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Subject line for alarm mail."
::= { wtWebGraphAnalogIn57644AlarmEntry 9 }
wtWebGraphAnalogIn57644AlarmMailText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alarm mail text: <Tn> provides the current temperature; n = 1..8.
<Z> provides the current time."
::= { wtWebGraphAnalogIn57644AlarmEntry 10 }
wtWebGraphAnalogIn57644AlarmManagerIP OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name or IP address of the SNMP Manager which accepts the trap."
::= { wtWebGraphAnalogIn57644AlarmEntry 11 }
wtWebGraphAnalogIn57644AlarmTrapText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This text is sent in the trap body."
::= { wtWebGraphAnalogIn57644AlarmEntry 12 }
wtWebGraphAnalogIn57644AlarmMailOptions OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded options:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : Attach Thermo.csv Enable
Bit 1 : CSV-Data_since_last_report
Bit 2-7: unused"
::= { wtWebGraphAnalogIn57644AlarmEntry 13 }
wtWebGraphAnalogIn57644AlarmTcpIpAddr OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name or IP address of the TCP server which accepts the trap."
::= { wtWebGraphAnalogIn57644AlarmEntry 14 }
wtWebGraphAnalogIn57644AlarmTcpPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Port number of the TCP server which accepts the trap."
::= { wtWebGraphAnalogIn57644AlarmEntry 15 }
wtWebGraphAnalogIn57644AlarmTcpText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This text is sent in the TCP trap body."
::= { wtWebGraphAnalogIn57644AlarmEntry 16 }
wtWebGraphAnalogIn57644AlarmClearMailSubject OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Subject line for alarm clear mail."
::= { wtWebGraphAnalogIn57644AlarmEntry 17 }
wtWebGraphAnalogIn57644AlarmClearMailText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alarm clear mail text: <Tn> provides the current temperature; n = 1..8.
<Z> provides the current time."
::= { wtWebGraphAnalogIn57644AlarmEntry 18 }
wtWebGraphAnalogIn57644AlarmClearTrapText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This text is sent in the trap body."
::= { wtWebGraphAnalogIn57644AlarmEntry 19 }
wtWebGraphAnalogIn57644AlarmClearTcpText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This text is sent in the TCP trap body."
::= { wtWebGraphAnalogIn57644AlarmEntry 20 }
wtWebGraphAnalogIn57644Alarm2Min OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Minimum rel. Humidity in percent with maximum 2 decimal places."
::= { wtWebGraphAnalogIn57644AlarmEntry 21 }
wtWebGraphAnalogIn57644Alarm2Max OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Maximum rel.Humidity in percent with maximum 2 decimal places."
::= { wtWebGraphAnalogIn57644AlarmEntry 22 }
wtWebGraphAnalogIn57644Alarm2Hysteresis OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Hysterese rel. Humidity in percent with maximum 2 decimal places."
::= { wtWebGraphAnalogIn57644AlarmEntry 23 }
wtWebGraphAnalogIn57644AlarmSyslogIpAddr OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"IP address of the syslog server to which the Webio device should send syslog messages."
::= { wtWebGraphAnalogIn57644AlarmEntry 24 }
wtWebGraphAnalogIn57644AlarmSyslogPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Port number of the syslog server to which the Webio device should send syslog messages."
::= { wtWebGraphAnalogIn57644AlarmEntry 25 }
wtWebGraphAnalogIn57644AlarmSyslogText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body."
::= { wtWebGraphAnalogIn57644AlarmEntry 26 }
wtWebGraphAnalogIn57644AlarmSyslogClearText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body of a alarm clear message."
::= { wtWebGraphAnalogIn57644AlarmEntry 27 }
wtWebGraphAnalogIn57644AlarmFtpDataPort OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Local data port: 1..65535 or AUTO: the next free port will be assigned."
::= { wtWebGraphAnalogIn57644AlarmEntry 28 }
wtWebGraphAnalogIn57644AlarmFtpFileName OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name of the file including path informations."
::= { wtWebGraphAnalogIn57644AlarmEntry 29 }
wtWebGraphAnalogIn57644AlarmFtpText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Message text to store on the FTP server."
::= { wtWebGraphAnalogIn57644AlarmEntry 30 }
wtWebGraphAnalogIn57644AlarmFtpClearText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alarm clear message to store on the FTP server."
::= { wtWebGraphAnalogIn57644AlarmEntry 31 }
wtWebGraphAnalogIn57644AlarmFtpOption OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded options, select only one option at the same time:
STORE = replace file
APPEND = append message at the end of the file
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : STORE
Bit 1 : APPEND
Bit 2-7: unused"
::= { wtWebGraphAnalogIn57644AlarmEntry 32 }
wtWebGraphAnalogIn57644AlarmTimerCron OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This entry contains 5 space or tab seperated text fields for time trigger definition.
Each field must match with the actual time to trigger a message, weekday and day of month
are interpreted separatley.
1: Minutes Range 0-59
2. Hours Range 0-23, 0 is midnight
3: Day of month Range 1-31
4: Month Range 1-12
5: Weekday Range 0-6, 0 is sunday
Syntax for every field:
- an asterix (*) enables every possible setting of a field
- single numbers seperated by commas
- a partition within the allowed range (1-5)
- step size within an partition of the allowed range (0-59/2: every second minute)."
::= { wtWebGraphAnalogIn57644AlarmEntry 33 }
-- wtWebGraphAnalogIn57644GraphicsBase Group
----------------------------
wtWebGraphAnalogIn57644GraphicsBaseEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Defines the viewing options of the graphic:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : Auto scroll enable
Bit 1 : Show table
Bit 2 : Show graph
Bit 3 : Show control buttons
Bit 4 : Show config menu
Bit 5-7: unused"
::= { wtWebGraphAnalogIn57644GraphicsBase 1 }
wtWebGraphAnalogIn57644GraphicsBaseWidth OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Defines the width of the graphic in pixels."
::= { wtWebGraphAnalogIn57644GraphicsBase 2 }
wtWebGraphAnalogIn57644GraphicsBaseHeight OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Defines the height of the graphic in pixels."
::= { wtWebGraphAnalogIn57644GraphicsBase 3 }
wtWebGraphAnalogIn57644GraphicsBaseFrameColor OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(3))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Frame color definition in RGB."
::= { wtWebGraphAnalogIn57644GraphicsBase 4 }
wtWebGraphAnalogIn57644GraphicsBaseBackgroundColor OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(3))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Background color definition in RGB."
::= { wtWebGraphAnalogIn57644GraphicsBase 5 }
wtWebGraphAnalogIn57644GraphicsBasePollingrate OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Defines the pollingrate in seconds,
which defines the refreshing intervall of the graphic."
::= { wtWebGraphAnalogIn57644GraphicsBase 6 }
-- wtWebGraphAnalogIn57644GraphicsSelect Group
----------------------------
wtWebGraphAnalogIn57644GraphicsSelectDisplaySensorSel OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded sensor selection:
only selected sensors will be shown in the graphical presentation:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: Sensor 1
Bit 1: Sensor 2
Bit 2: Sensor 3
Bit 3: Sensor 4
Bit 4: Sensor 5
Bit 5: Sensor 6
Bit 6: Sensor 7
Bit 7: Sensor 8"
::= { wtWebGraphAnalogIn57644GraphicsSelect 1 }
wtWebGraphAnalogIn57644GraphicsSelectDisplayShowExtrem OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded sensor selection:
only selected sensors will be shown with minima and maxima:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: Sensor 1
Bit 1: Sensor 2
Bit 2: Sensor 3
Bit 3: Sensor 4
Bit 4: Sensor 5
Bit 5: Sensor 6
Bit 6: Sensor 7
Bit 7: Sensor 8"
::= { wtWebGraphAnalogIn57644GraphicsSelect 2 }
-- Graph Sensor Color Table
wtWebGraphAnalogIn57644SensorColor2Table OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebGraphAnalogIn57644SensorColor2Entry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"List of sensor colors for the praphical presentation."
::= { wtWebGraphAnalogIn57644GraphicsSelect 3 }
wtWebGraphAnalogIn57644SensorColor2Entry OBJECT-TYPE
SYNTAX WtWebGraphAnalogIn57644SensorColor2Entry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Numbers of the sensors."
INDEX { wtWebGraphAnalogIn57644SensorNo }
::= { wtWebGraphAnalogIn57644SensorColor2Table 1 }
WtWebGraphAnalogIn57644SensorColor2Entry ::= SEQUENCE {
wtWebGraphAnalogIn57644GraphicsSensorColor OCTET STRING,
wtWebGraphAnalogIn57644GraphicsSelectScale OCTET STRING
}
wtWebGraphAnalogIn57644GraphicsSensorColor OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(3))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Color of the sensors at the praphical presention."
::= { wtWebGraphAnalogIn57644SensorColor2Entry 1 }
wtWebGraphAnalogIn57644GraphicsSelectScale OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Assignes one of 4 scales to a sensor:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : Use Scale 1
Bit 1 : Use Scale 2
Bit 2 : Use Scale 3
Bit 3 : Use Scale 4
Bit 4-7: unused"
::= { wtWebGraphAnalogIn57644SensorColor2Entry 2 }
-- wtWebGraphAnalogIn57644GraphicsScale Group
----------------------------
wtWebGraphAnalogIn57644GraphicsScaleAutoScaleEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Select the Auto Scale Mode:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : Scale 1 Auto scale enable
Bit 1 : Scale 2 Auto scale enable
Bit 2 : Scale 3 Auto scale enable
Bit 3 : Scale 4 Auto scale enable
Bit 4-7: unused"
::= { wtWebGraphAnalogIn57644GraphicsScale 1 }
wtWebGraphAnalogIn57644GraphicsScaleAutoFitEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Select the Auto Fit Mode::
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : Scale 1 Auto fit enable
Bit 1 : Scale 2 Auto fit enable
Bit 2 : Scale 3 Auto fit enable
Bit 3 : Scale 4 Auto fit enable
Bit 4-7: unused"
::= { wtWebGraphAnalogIn57644GraphicsScale 2 }
wtWebGraphAnalogIn57644GraphicsScale1Min OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Scale 1: Minimum."
::= { wtWebGraphAnalogIn57644GraphicsScale 3 }
wtWebGraphAnalogIn57644GraphicsScale2Min OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Scale 2: Minimum."
::= { wtWebGraphAnalogIn57644GraphicsScale 4 }
wtWebGraphAnalogIn57644GraphicsScale3Min OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Scale 3: Minimum."
::= { wtWebGraphAnalogIn57644GraphicsScale 5 }
wtWebGraphAnalogIn57644GraphicsScale4Min OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Scale 4: Minimum."
::= { wtWebGraphAnalogIn57644GraphicsScale 6 }
wtWebGraphAnalogIn57644GraphicsScale1Max OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Scale 1: Maximum."
::= { wtWebGraphAnalogIn57644GraphicsScale 7 }
wtWebGraphAnalogIn57644GraphicsScale2Max OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Scale 2: Maximum."
::= { wtWebGraphAnalogIn57644GraphicsScale 8 }
wtWebGraphAnalogIn57644GraphicsScale3Max OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Scale 3: Maximum."
::= { wtWebGraphAnalogIn57644GraphicsScale 9 }
wtWebGraphAnalogIn57644GraphicsScale4Max OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Scale 4: Maximum."
::= { wtWebGraphAnalogIn57644GraphicsScale 10 }
wtWebGraphAnalogIn57644GraphicsScale1Unit OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Scale 1: Unit."
::= { wtWebGraphAnalogIn57644GraphicsScale 11 }
wtWebGraphAnalogIn57644GraphicsScale2Unit OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Scale 2: Unit."
::= { wtWebGraphAnalogIn57644GraphicsScale 12 }
wtWebGraphAnalogIn57644GraphicsScale3Unit OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Scale 3: Unit."
::= { wtWebGraphAnalogIn57644GraphicsScale 13 }
wtWebGraphAnalogIn57644GraphicsScale4Unit OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Scale 4: Unit."
::= { wtWebGraphAnalogIn57644GraphicsScale 14 }
-- wtWebGraphAnalogIn57644Ports Group
----------------------------
-- Table
wtWebGraphAnalogIn57644PortTable OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebGraphAnalogIn57644PortEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"List of settings depending on the sensor number."
::= { wtWebGraphAnalogIn57644Ports 1 }
wtWebGraphAnalogIn57644PortEntry OBJECT-TYPE
SYNTAX WtWebGraphAnalogIn57644PortEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Sensor parameters for the individual sensors."
INDEX { wtWebGraphAnalogIn57644SensorNo }
::= { wtWebGraphAnalogIn57644PortTable 1 }
WtWebGraphAnalogIn57644PortEntry ::= SEQUENCE {
wtWebGraphAnalogIn57644PortName OCTET STRING,
wtWebGraphAnalogIn57644PortText OCTET STRING,
wtWebGraphAnalogIn57644PortOffset1 OCTET STRING,
wtWebGraphAnalogIn57644SetPoint1 OCTET STRING,
wtWebGraphAnalogIn57644PortOffset2 OCTET STRING,
wtWebGraphAnalogIn57644SetPoint2 OCTET STRING,
wtWebGraphAnalogIn57644PortComment OCTET STRING,
wtWebGraphAnalogIn57644PortSensorSelect OCTET STRING,
wtWebGraphAnalogIn57644PortUnit OCTET STRING,
wtWebGraphAnalogIn57644PortScale0 OCTET STRING,
wtWebGraphAnalogIn57644PortScale100 OCTET STRING
}
wtWebGraphAnalogIn57644PortName OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name of the sensor."
::= { wtWebGraphAnalogIn57644PortEntry 1 }
wtWebGraphAnalogIn57644PortText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Description of the sensor."
::= { wtWebGraphAnalogIn57644PortEntry 2 }
wtWebGraphAnalogIn57644PortOffset1 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset calibration: Offset in degrees with maximum 2 decimal places at set point 1."
::= { wtWebGraphAnalogIn57644PortEntry 3 }
wtWebGraphAnalogIn57644SetPoint1 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset calibration: set point 1 in degrees with maximum 2 decimal places."
::= { wtWebGraphAnalogIn57644PortEntry 4 }
wtWebGraphAnalogIn57644PortOffset2 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset calibration: Offset in degrees with maximum 2 decimal places at set point 2."
::= { wtWebGraphAnalogIn57644PortEntry 5 }
wtWebGraphAnalogIn57644SetPoint2 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset calibration: set point 2 in degrees with maximum 2 decimal places."
::= { wtWebGraphAnalogIn57644PortEntry 6 }
wtWebGraphAnalogIn57644PortComment OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset calibration: informations of date, name of operator, reference devices."
::= { wtWebGraphAnalogIn57644PortEntry 7 }
wtWebGraphAnalogIn57644PortSensorSelect OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded options for sensor 1:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : 0-10V (default)
Bit 1 : Disconnect
Bit 2-7: unused
Binary coded options for sensor 2:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : 0-10V (default)
Bit 1 : Disconnect
Bit 2-7: unused"
::= { wtWebGraphAnalogIn57644PortEntry 8 }
wtWebGraphAnalogIn57644PortUnit OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"User scale: displayed unit."
::= { wtWebGraphAnalogIn57644PortEntry 9 }
wtWebGraphAnalogIn57644PortScale0 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"User scale: displayed value in 1/1000 at 0% full scale range.
Range: -999999.999 to 999999.999"
::= { wtWebGraphAnalogIn57644PortEntry 10 }
wtWebGraphAnalogIn57644PortScale100 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"User scale: displayed value in 1/1000 at 100% full scale range.
Range: -999999.999 to 999999.999"
::= { wtWebGraphAnalogIn57644PortEntry 11 }
-- wtWebGraphAnalogIn57644Manufact Group
----------------------------
wtWebGraphAnalogIn57644MfName OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Manufacturer company name"
::= { wtWebGraphAnalogIn57644Manufact 1 }
wtWebGraphAnalogIn57644MfAddr OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Manufacturer address."
::= { wtWebGraphAnalogIn57644Manufact 2 }
wtWebGraphAnalogIn57644MfHotline OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Manufacturer hotline."
::= { wtWebGraphAnalogIn57644Manufact 3 }
wtWebGraphAnalogIn57644MfInternet OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Manufacturer Internet address."
::= { wtWebGraphAnalogIn57644Manufact 4 }
wtWebGraphAnalogIn57644MfDeviceTyp OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Manufacturer device name (model number)."
::= { wtWebGraphAnalogIn57644Manufact 5 }
wtWebGraphAnalogIn57644MfOrderNo OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Manufacturer part number."
::= { wtWebGraphAnalogIn57644Manufact 6 }
-- wtWebGraphAnalogIn57644Diag Group
----------------------------
wtWebGraphAnalogIn57644DiagErrorCount OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of entries in the error memory."
::= { wtWebGraphAnalogIn57644Diag 1 }
wtWebGraphAnalogIn57644DiagBinaryError OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Error causes coded bit-by-bit."
::= { wtWebGraphAnalogIn57644Diag 2 }
wtWebGraphAnalogIn57644DiagErrorIndex OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The value of this variable is used as an index to read
an error massege from wtWebGraphAnalogIn57644DiagErrorMessage.
Errors are numbered from 1 to wtWebGraphAnalogIn57644DiagErrorCount.
Writing a valid value into this variable, making the appropriate
message readable from wtWebGraphAnalogIn57644DiagErrorMessage."
::= { wtWebGraphAnalogIn57644Diag 3 }
wtWebGraphAnalogIn57644DiagErrorMessage OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Using wtWebGraphAnalogIn57644DiagErrorIndex as an index, the appropriate message is available."
::= { wtWebGraphAnalogIn57644Diag 4 }
wtWebGraphAnalogIn57644DiagErrorClear OBJECT-TYPE
SYNTAX INTEGER
ACCESS write-only
STATUS mandatory
DESCRIPTION
"Writing 1 into this variable clears all diagnosis messages."
::= { wtWebGraphAnalogIn57644Diag 5 }
-- TRAP DEFINITIONS
-- Diese SNMP-Traps werden gesendet, wenn die Alarmtriggerbedingungen zutreffen
wtWebGraphAnalogIn57644Alert1 TRAP-TYPE
ENTERPRISE wtWebGraphAnalogIn57644
VARIABLES { wtWebGraphAnalogIn57644AlarmTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 1 was triggered,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Thermo-Hygrometer Alarm 1"
--#SUMMARY "Alarm 1: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 31
wtWebGraphAnalogIn57644Alert2 TRAP-TYPE
ENTERPRISE wtWebGraphAnalogIn57644
VARIABLES { wtWebGraphAnalogIn57644AlarmTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 2 was triggered,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Thermo-Hygrometer Alarm 2"
--#SUMMARY "Alarm 2: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 32
wtWebGraphAnalogIn57644Alert3 TRAP-TYPE
ENTERPRISE wtWebGraphAnalogIn57644
VARIABLES { wtWebGraphAnalogIn57644AlarmTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 3 was triggered,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Thermo-Hygrometer Alarm 3"
--#SUMMARY "Alarm 3: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 33
wtWebGraphAnalogIn57644Alert4 TRAP-TYPE
ENTERPRISE wtWebGraphAnalogIn57644
VARIABLES { wtWebGraphAnalogIn57644AlarmTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 4 was triggered,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Thermo-Hygrometer Alarm 4"
--#SUMMARY "Alarm 4: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 34
wtWebGraphAnalogIn57644Alert5 TRAP-TYPE
ENTERPRISE wtWebGraphAnalogIn57644
VARIABLES { wtWebGraphAnalogIn57644AlarmTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 5 was triggered,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Thermo-Hygrometer Alarm 5"
--#SUMMARY "Alarm 5: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 35
wtWebGraphAnalogIn57644Alert6 TRAP-TYPE
ENTERPRISE wtWebGraphAnalogIn57644
VARIABLES { wtWebGraphAnalogIn57644AlarmTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 6 was triggered,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Thermo-Hygrometer Alarm 6"
--#SUMMARY "Alarm 6: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 36
wtWebGraphAnalogIn57644Alert7 TRAP-TYPE
ENTERPRISE wtWebGraphAnalogIn57644
VARIABLES { wtWebGraphAnalogIn57644AlarmTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 7 was triggered,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Thermo-Hygrometer Alarm 7"
--#SUMMARY "Alarm 7: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 37
wtWebGraphAnalogIn57644Alert8 TRAP-TYPE
ENTERPRISE wtWebGraphAnalogIn57644
VARIABLES { wtWebGraphAnalogIn57644AlarmTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 8 was triggered,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Thermo-Hygrometer Alarm 8"
--#SUMMARY "Alarm 8: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 38
wtWebGraphAnalogIn57644Alert9 TRAP-TYPE
ENTERPRISE wtWebGraphAnalogIn57644
VARIABLES { wtWebGraphAnalogIn57644AlarmClearTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 1 was cleared,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Thermo-Hygrometer Release Alarm 1"
--#SUMMARY "Release Alarm 1: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 91
wtWebGraphAnalogIn57644Alert10 TRAP-TYPE
ENTERPRISE wtWebGraphAnalogIn57644
VARIABLES { wtWebGraphAnalogIn57644AlarmClearTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 2 was cleared,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Thermo-Hygrometer Release Alarm 2"
--#SUMMARY "Release Alarm 2: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 92
wtWebGraphAnalogIn57644Alert11 TRAP-TYPE
ENTERPRISE wtWebGraphAnalogIn57644
VARIABLES { wtWebGraphAnalogIn57644AlarmClearTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 3 was cleared,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Thermo-Hygrometer Release Alarm 3"
--#SUMMARY "Release Alarm 3: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 93
wtWebGraphAnalogIn57644Alert12 TRAP-TYPE
ENTERPRISE wtWebGraphAnalogIn57644
VARIABLES { wtWebGraphAnalogIn57644AlarmClearTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 4 was cleared,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Thermo-Hygrometer Release Alarm 4"
--#SUMMARY "Release Alarm 4: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 94
wtWebGraphAnalogIn57644Alert13 TRAP-TYPE
ENTERPRISE wtWebGraphAnalogIn57644
VARIABLES { wtWebGraphAnalogIn57644AlarmClearTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 5 was cleared,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Thermo-Hygrometer Release Alarm 5"
--#SUMMARY "Release Alarm 5: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 95
wtWebGraphAnalogIn57644Alert14 TRAP-TYPE
ENTERPRISE wtWebGraphAnalogIn57644
VARIABLES { wtWebGraphAnalogIn57644AlarmClearTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 6 was cleared,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Thermo-Hygrometer Release Alarm 6"
--#SUMMARY "Release Alarm 6: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 96
wtWebGraphAnalogIn57644Alert15 TRAP-TYPE
ENTERPRISE wtWebGraphAnalogIn57644
VARIABLES { wtWebGraphAnalogIn57644AlarmClearTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 7 was cleared,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Thermo-Hygrometer Release Alarm 7"
--#SUMMARY "Release Alarm 7: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 97
wtWebGraphAnalogIn57644Alert16 TRAP-TYPE
ENTERPRISE wtWebGraphAnalogIn57644
VARIABLES { wtWebGraphAnalogIn57644AlarmClearTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 8 was cleared,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Thermo-Hygrometer Release Alarm 8"
--#SUMMARY "Release Alarm 8: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 98
wtWebGraphAnalogIn57644AlertDiag TRAP-TYPE
ENTERPRISE wtWebGraphAnalogIn57644
VARIABLES {
wtWebGraphAnalogIn57644DiagErrorIndex,
wtWebGraphAnalogIn57644DiagErrorMessage
}
DESCRIPTION
"This SNMP trap is generated when a diagnosis/error message was triggered,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Thermo-Hygrometer Diagnose Error"
--#SUMMARY "Diagnose error index: %d, Message: %s."
--#ARGUMENTS {0,1}
--#SEVERITY MAJOR
--#TIMEINDEX 99
--#STATE DEGRADED
::= 110
END