WebGraph-Thermometer-US-MIB DEFINITIONS ::= BEGIN
----------------------------------------------------------------
-- Revison: 1.26
----------------------------------------------------------------
-- 28.06.2006 New: Community String Trap
--
----------------------------------------------------------------
-- Revison: 1.25
----------------------------------------------------------------
-- 22.05.2006 Table entry names changed
--
----------------------------------------------------------------
-- Revison: 1.24
----------------------------------------------------------------
-- 26.07.2005 #57605, WebGraph Thermometer
-- CRON timer function
----------------------------------------------------------------
-- Revison: 1.23
----------------------------------------------------------------
-- 14.07.2005 #57605, WebGraph Thermometer
-- FTP functions
----------------------------------------------------------------
-- Revison: 1.22
----------------------------------------------------------------
-- 02.06.2005 #57605, WebGraph Thermometer
-- Trap NMS annotations
----------------------------------------------------------------
-- Revison: 1.21
----------------------------------------------------------------
-- 19.04.2005 #57605, WebGraph Themometer
-- Mail Authentication
----------------------------------------------------------------
-- Revison: 1.20
----------------------------------------------------------------
-- 05.11.2004 #57605, WebGraph
-- New: Syslog
--
----------------------------------------------------------------
-- Revison: 1.19
----------------------------------------------------------------
-- 27.09.2004 #57601/3/4, Webio Digital
-- New:
-- Entry AlarmHysteresis corrected
----------------------------------------------------------------
-- Revison: 1.18
----------------------------------------------------------------
-- 21.07.2004 #57601/3/4, Webio Anx
-- New:
-- Diagnosis
----------------------------------------------------------------
-- Revison: 1.17
----------------------------------------------------------------
-- 28.06.2004 #57630/1/2, Webio Digital
-- Neu: Puls Mode
----------------------------------------------------------------
-- Revison: 1.16
----------------------------------------------------------------
-- 16.04.2004 New: #57632, Webio Digital EA24x24
--
-- #57630/1, Webio Digital EA12x12
-- New:
-- wtWebioAn1GraphInputCounterClear
----------------------------------------------------------------
-- Revison: 1.15
----------------------------------------------------------------
-- 27.02.2004 #57630/1, Webio Digital EA12x12
-- New:
-- Length changed to 32 Bit:
-- wtWebioEA12x12InputValue
-- wtWebioEA12x12OutputValue
-- wtWebioEA12x12LoadControlView
-- wtWebioEA12x12LCShutDownView
-- wtWebioEA12x12SetOutput
-- wtWebioEA12x12AlarmInputTrigger
-- wtWebioEA12x12AlarmOutputTrigger
-- wtWebioEA12x12PortOutputSafetyState
----------------------------------------------------------------
-- Revison: 1.14
----------------------------------------------------------------
-- 16.02.2004 #57630/1, Webio Digital EA12x12
-- New:
-- Text: Location, Contact
-- SNMP: ColdStart, WarmStart, ComunityString Read/RW
-- Alarm: ColdStart / WarmStart trigger
--
-- #57601, 1xWebThermometer
-- #57603, 2xWebThermometer
-- #57604, 8xWebThermometer
-- New:
-- Alarm Hysteresis
-- Alarm Clear Traps and Mails
----------------------------------------------------------------
-- Revison: 1.13
----------------------------------------------------------------
-- 05.02.2004 #57601, 1xWebThermometer
-- #57603, 2xWebThermometer
-- #57604, 8xWebThermometer
-- New:
-- Text: Location, Contact
-- SNMP: ColdStart, WarmStart, ComunityString Read/RW
-- Alarm: ColdStart / WarmStart trigger
----------------------------------------------------------------
-- Revison: 1.12
----------------------------------------------------------------
-- 05.11.2003 #57601, 1xWebThermometer
-- #57603, 2xWebThermometer
-- #57604, 8xWebThermometer
-- New features:
-- Mail : Option CSV attachment
-- Port : Offset calibration
-- Alarm : TCP Client mode
----------------------------------------------------------------
-- Revison: 1.11
----------------------------------------------------------------
-- 28.10.2003 #57630/1, Webio Digital EA12x12
-- New features:
-- Alarm : TCP Client mode
-- Inputs: Puls filter
----------------------------------------------------------------
-- Revison: 1.10
----------------------------------------------------------------
-- 22.07.2003 #57630, Webio Digital EA12x12
-- New navigation tree, new binary modes
--
----------------------------------------------------------------
-- Revison: 1.09
----------------------------------------------------------------
-- 24.03.2003 Trap Enterprise (Type 1, 2) corrected
----------------------------------------------------------------
-- Revison: 1.08
----------------------------------------------------------------
-- 04.03.2003 reconciled the language versions DE/US
----------------------------------------------------------------
-- Revison: 1.07
----------------------------------------------------------------
-- 25.02.2003 Correction: wtWebioEA12x12LoadControl
----------------------------------------------------------------
-- Revison: 1.06
----------------------------------------------------------------
-- 24.02.2003 New:
-- #57630, Webio EA12x12, LoadControl Group
-- Correction: Trap variable names
----------------------------------------------------------------
-- Revison: 1.05
----------------------------------------------------------------
-- 21.01.2003 New:
-- #57630, Webio EA12x12
----------------------------------------------------------------
-- Revison: 1.04
----------------------------------------------------------------
-- 02.01.2003 New:
-- #57601, 1xWebThermometer
-- #57603, 2xWebThermometer, 8 alarms
----------------------------------------------------------------
-- Revison: 1.03
----------------------------------------------------------------
-- 21.11.2002 New:
-- #57604, 2xWebThermometer, BOOTP, StartupSite
-- #57603, 8xWebThermometer, BOOTP, StartupSite
----------------------------------------------------------------
-- Revison: 1.02
----------------------------------------------------------------
-- 26.07.2002 New:
-- #57604, 2xWebThermometer
-- #57603, 8xWebThermometer
--
IMPORTS
OBJECT-TYPE FROM RFC-1212
TRAP-TYPE FROM RFC-1215
DisplayString, PhysAddress FROM RFC1213-MIB
enterprises, TimeTicks, IpAddress, NetworkAddress FROM RFC1155-SMI;
-- IpAddress ::=
-- [APPLICATION 0]
-- IMPLICIT OCTET STRING (SIZE (4))
-- Counter ::=
-- [APPLICATION 1]
-- IMPLICIT INTEGER (0..4294967295)
-- Gauge ::=
-- [APPLICATION 2]
-- IMPLICIT INTEGER (0..4294967295)
-- TimeTicks ::=
-- [APPLICATION 3]
-- IMPLICIT INTEGER (0..4294967295)
-- DisplayString ::= OCTET STRING
-- PhysAddress ::= OCTET STRING
-- internet OBJECT IDENTIFIER ::= { iso org(3) dod(6) 1 }
-- privat OBJECT IDENTIFIER ::= { internet 4 }
-- enterprises OBJECT IDENTIFIER ::= { privat 1 }
-- Wiesemann & Theis Com-Server MIB
wut OBJECT IDENTIFIER ::= { enterprises 5040 }
wtComServer OBJECT IDENTIFIER ::= { wut 1 }
wtWebio OBJECT IDENTIFIER ::= { wtComServer 2 }
-- wtWebio Tree
wtWebioAn1Graph OBJECT IDENTIFIER ::= { wtWebio 8 }
-- wtWebioAn1Graph Tree
wtWebioAn1GraphTemp OBJECT IDENTIFIER ::= { wtWebioAn1Graph 1 }
wtWebioAn1GraphSessCntrl OBJECT IDENTIFIER ::= { wtWebioAn1Graph 2 }
wtWebioAn1GraphConfig OBJECT IDENTIFIER ::= { wtWebioAn1Graph 3 }
-- wtWebioAn1GraphConfig Tree
wtWebioAn1GraphDevice OBJECT IDENTIFIER ::= { wtWebioAn1GraphConfig 1 }
wtWebioAn1GraphPorts OBJECT IDENTIFIER ::= { wtWebioAn1GraphConfig 2 }
wtWebioAn1GraphManufact OBJECT IDENTIFIER ::= { wtWebioAn1GraphConfig 3 }
wtWebioAn1GraphDiag OBJECT IDENTIFIER ::= { wtWebioAn1GraphConfig 4 }
-- wtWebioAn1GraphDevice Tree
wtWebioAn1GraphText OBJECT IDENTIFIER ::= { wtWebioAn1GraphDevice 1 }
wtWebioAn1GraphTimeDate OBJECT IDENTIFIER ::= { wtWebioAn1GraphDevice 2 }
wtWebioAn1GraphBasic OBJECT IDENTIFIER ::= { wtWebioAn1GraphDevice 3 }
wtWebioAn1GraphDatalogger OBJECT IDENTIFIER ::= { wtWebioAn1GraphDevice 4 }
wtWebioAn1GraphAlarm OBJECT IDENTIFIER ::= { wtWebioAn1GraphDevice 5 }
-- wtWebioAn1GraphTimeDate Tree
wtWebioAn1GraphTimeZone OBJECT IDENTIFIER ::= { wtWebioAn1GraphTimeDate 1 }
wtWebioAn1GraphTimeServer OBJECT IDENTIFIER ::= { wtWebioAn1GraphTimeDate 2 }
wtWebioAn1GraphDeviceClock OBJECT IDENTIFIER ::= { wtWebioAn1GraphTimeDate 3 }
-- wtWebioAn1GraphBasic Tree
wtWebioAn1GraphNetwork OBJECT IDENTIFIER ::= { wtWebioAn1GraphBasic 1 }
wtWebioAn1GraphHTML OBJECT IDENTIFIER ::= { wtWebioAn1GraphBasic 2 }
wtWebioAn1GraphMail OBJECT IDENTIFIER ::= { wtWebioAn1GraphBasic 3 }
wtWebioAn1GraphSNMP OBJECT IDENTIFIER ::= { wtWebioAn1GraphBasic 4 }
wtWebioAn1GraphUDP OBJECT IDENTIFIER ::= { wtWebioAn1GraphBasic 5 }
wtWebioAn1GraphSyslog OBJECT IDENTIFIER ::= { wtWebioAn1GraphBasic 6 }
wtWebioAn1GraphFTP OBJECT IDENTIFIER ::= { wtWebioAn1GraphBasic 7 }
wtWebioAn1GraphHTTP OBJECT IDENTIFIER ::= { wtWebioAn1GraphBasic 8 }
-- wtWebioAn1GraphTemp Group
------------------------
wtWebioAn1GraphSensors OBJECT-TYPE
SYNTAX INTEGER (1..8)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of temperature sensors"
::= { wtWebioAn1GraphTemp 1 }
-- Interface Table
wtWebioAn1GraphSensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebioAn1GraphSensorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"List of sensors."
::= { wtWebioAn1GraphTemp 2 }
wtWebioAn1GraphSensorEntry OBJECT-TYPE
SYNTAX WtWebioAn1GraphSensorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Temperature sensor numbers."
INDEX { wtWebioAn1GraphSensorNo }
::= { wtWebioAn1GraphSensorTable 1 }
WtWebioAn1GraphSensorEntry ::= SEQUENCE {
wtWebioAn1GraphSensorNo INTEGER
}
wtWebioAn1GraphSensorNo OBJECT-TYPE
SYNTAX INTEGER (1)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Temperature sensor number."
::= { wtWebioAn1GraphSensorEntry 1 }
-- wtWebioAn1GraphTempValue Table
wtWebioAn1GraphTempValueTable OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebioAn1GraphTempValueEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"List of temperature values corresponding to the channel numbers."
::= { wtWebioAn1GraphTemp 3 }
wtWebioAn1GraphTempValueEntry OBJECT-TYPE
SYNTAX WtWebioAn1GraphTempValueEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Temperatures of the sensors."
INDEX { wtWebioAn1GraphSensorNo }
::= { wtWebioAn1GraphTempValueTable 1 }
WtWebioAn1GraphTempValueEntry ::= SEQUENCE{
wtWebioAn1GraphTempValue OCTET STRING
}
wtWebioAn1GraphTempValue OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (5))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Temperature value of the sensor, ASCII, 5 characters in length."
::= { wtWebioAn1GraphTempValueEntry 1 }
-- wtWebioAn1GraphBinaryTempValue Table
wtWebioAn1GraphBinaryTempValueTable OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebioAn1GraphBinaryTempValueEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"List of binary temperature values corresponding to the channel numbers."
::= { wtWebioAn1GraphTemp 4 }
wtWebioAn1GraphBinaryTempValueEntry OBJECT-TYPE
SYNTAX WtWebioAn1GraphBinaryTempValueEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Binary temperature values of the sensors."
INDEX { wtWebioAn1GraphSensorNo }
::= { wtWebioAn1GraphBinaryTempValueTable 1 }
WtWebioAn1GraphBinaryTempValueEntry ::= SEQUENCE{
wtWebioAn1GraphBinaryTempValue INTEGER
}
wtWebioAn1GraphBinaryTempValue OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Binary temperature value of the sensor in 1/10 degrees Celsius,
signed number, 0x7FFF indicates an
invalid measured value."
::= { wtWebioAn1GraphBinaryTempValueEntry 1 }
-- wtWebioAn1GraphSessCntrl Group
--------------------------------
wtWebioAn1GraphSessCntrlPassword OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Entering this password opens a session which is ended by writing a 1 to
wtWebioAn1GraphSessCntrlLogout. When read this variable provides a string of
length zero."
::= { wtWebioAn1GraphSessCntrl 1 }
wtWebioAn1GraphSessCntrlConfigMode OBJECT-TYPE
SYNTAX INTEGER {
wtWebioAn1GraphSessCntrl-NoSession(0),
wtWebioAn1GraphSessCntrl-Session(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"When the device is in SNMP configuration mode, the value 1 is
returned, otherwise 0. If the read value is 0 even though the
password was written, the device is already in config mode and the
variables can only be read."
::= { wtWebioAn1GraphSessCntrl 2 }
wtWebioAn1GraphSessCntrlLogout OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"If the device is in configuration mode and the session was opened by
this SNMP Manager, writing a 1 to this variable will end the session
and all parameters are stored.
Writing a 2 discards all entries again.
When read this variable provides the value 0."
::= { wtWebioAn1GraphSessCntrl 3 }
wtWebioAn1GraphSessCntrlAdminPassword OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This password protects access to the variables with administrator rights.
It can only be changed by the administrator. If no password was assigned,
the valid password is public."
::= { wtWebioAn1GraphSessCntrl 4 }
wtWebioAn1GraphSessCntrlConfigPassword OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This password protects access to the variables with configurator rights. It can
be changed by the administrator and by the configurator. If no password was assigned,
the valid password is public. When read this variable provides a null-pointer."
::= { wtWebioAn1GraphSessCntrl 5 }
-- wtWebioAn1GraphText Group
------------------------
wtWebioAn1GraphDeviceName OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name of the Webio, which is user definable."
::= { wtWebioAn1GraphText 1 }
wtWebioAn1GraphDeviceText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Description of the Webio, which is user definable."
::= { wtWebioAn1GraphText 2 }
wtWebioAn1GraphDeviceLocation OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Description of the location of the Webio, which is user definable."
::= { wtWebioAn1GraphText 3 }
wtWebioAn1GraphDeviceContact OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Contact address of the system operator of the Webio, which is user definable."
::= { wtWebioAn1GraphText 4 }
-- wtWebioAn1GraphTimeZone Group
----------------------------
wtWebioAn1GraphTzOffsetHrs OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset hours for the time zone (winter time) with respect to UTC."
::= { wtWebioAn1GraphTimeZone 1 }
wtWebioAn1GraphTzOffsetMin OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset minutes for the time zone (winter time) with respect to UTC."
::= { wtWebioAn1GraphTimeZone 2 }
wtWebioAn1GraphTzEnable OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded conditions:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : Apply Timezone"
::= { wtWebioAn1GraphTimeZone 3 }
wtWebioAn1GraphStTzOffsetHrs OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset hours of the time zone (summer time) with respect to UTC."
::= { wtWebioAn1GraphTimeZone 4 }
wtWebioAn1GraphStTzOffsetMin OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset minutes of the time zone (summer time) with respect to UTC."
::= { wtWebioAn1GraphTimeZone 5 }
wtWebioAn1GraphStTzEnable OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded conditions:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : Apply Summertime"
::= { wtWebioAn1GraphTimeZone 6 }
wtWebioAn1GraphStTzStartMonth OBJECT-TYPE
SYNTAX INTEGER {
wtWebioAn1GraphStartMonth-January(1),
wtWebioAn1GraphStartMonth-February(2),
wtWebioAn1GraphStartMonth-March(3),
wtWebioAn1GraphStartMonth-April(4),
wtWebioAn1GraphStartMonth-May(5),
wtWebioAn1GraphStartMonth-June(6),
wtWebioAn1GraphStartMonth-July(7),
wtWebioAn1GraphStartMonth-August(8),
wtWebioAn1GraphStartMonth-September(9),
wtWebioAn1GraphStartMonth-October(10),
wtWebioAn1GraphStartMonth-November(11),
wtWebioAn1GraphStartMonth-December(12)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Month in which the change is made from winter time to summer time."
::= { wtWebioAn1GraphTimeZone 7 }
wtWebioAn1GraphStTzStartMode OBJECT-TYPE
SYNTAX INTEGER {
wtWebioAn1GraphStartMode-first(1),
wtWebioAn1GraphStartMode-second(2),
wtWebioAn1GraphStartMode-third(3),
wtWebioAn1GraphStartMode-fourth(4),
wtWebioAn1GraphStartMode-last(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Mode of the day of the week for which the change is made from winter time to summer time."
::= { wtWebioAn1GraphTimeZone 8 }
wtWebioAn1GraphStTzStartWday OBJECT-TYPE
SYNTAX INTEGER {
wtWebioAn1GraphStartWday-Sunday(1),
wtWebioAn1GraphStartWday-Monday(2),
wtWebioAn1GraphStartWday-Tuesday(3),
wtWebioAn1GraphStartWday-Thursday(4),
wtWebioAn1GraphStartWday-Wednesday(5),
wtWebioAn1GraphStartWday-Friday(6),
wtWebioAn1GraphStartWday-Saturday(7)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Day of the week on which the change is made from winter time to summer time"
::= { wtWebioAn1GraphTimeZone 9 }
wtWebioAn1GraphStTzStartHrs OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Hour in which the time zone is changed from winter to summer time with
respect to UTC."
::= { wtWebioAn1GraphTimeZone 10 }
wtWebioAn1GraphStTzStartMin OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Minute in which the time zone is changed from winter to summer time with
respect to UTC."
::= { wtWebioAn1GraphTimeZone 11 }
wtWebioAn1GraphStTzStopMonth OBJECT-TYPE
SYNTAX INTEGER {
wtWebioAn1GraphStopMonth-January(1),
wtWebioAn1GraphStopMonth-February(2),
wtWebioAn1GraphStopMonth-March(3),
wtWebioAn1GraphStopMonth-April(4),
wtWebioAn1GraphStopMonth-May(5),
wtWebioAn1GraphStopMonth-June(6),
wtWebioAn1GraphStopMonth-July(7),
wtWebioAn1GraphStopMonth-August(8),
wtWebioAn1GraphStopMonth-September(9),
wtWebioAn1GraphStopMonth-October(10),
wtWebioAn1GraphStopMonth-November(11),
wtWebioAn1GraphStopMonth-December(12)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Month in which the change is made from summer time to winter time."
::= { wtWebioAn1GraphTimeZone 12 }
wtWebioAn1GraphStTzStopMode OBJECT-TYPE
SYNTAX INTEGER {
wtWebioAn1GraphStopMode-first(1),
wtWebioAn1GraphStopMode-second(2),
wtWebioAn1GraphStopMode-third(3),
wtWebioAn1GraphStopMode-fourth(4),
wtWebioAn1GraphStopMode-last(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Mode of the week day on which the change is made from summer time to winter time."
::= { wtWebioAn1GraphTimeZone 13 }
wtWebioAn1GraphStTzStopWday OBJECT-TYPE
SYNTAX INTEGER {
wtWebioAn1GraphStopWday-Sunday(1),
wtWebioAn1GraphStopWday-Monday(2),
wtWebioAn1GraphStopWday-Tuesday(3),
wtWebioAn1GraphStopWday-Thursday(4),
wtWebioAn1GraphStopWday-Wednesday(5),
wtWebioAn1GraphStopWday-Friday(6),
wtWebioAn1GraphStopWday-Saturday(7)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Day of the week on which the change is made from summer time to winter time."
::= { wtWebioAn1GraphTimeZone 14 }
wtWebioAn1GraphStTzStopHrs OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Hour at which the time zone is changed from summer to winter time with
respect to UTC."
::= { wtWebioAn1GraphTimeZone 15 }
wtWebioAn1GraphStTzStopMin OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Minute at which the time zone is changed from summer to winter time with
respect to UTC."
::= { wtWebioAn1GraphTimeZone 16 }
-- wtWebioAn1GraphTimeServer Group
----------------------------
wtWebioAn1GraphTimeServer1 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"IP address or name of the 1st time server in ASCII"
::= { wtWebioAn1GraphTimeServer 1 }
wtWebioAn1GraphTimeServer2 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"IP address or name of the 2nd time server in ASCII"
::= { wtWebioAn1GraphTimeServer 2 }
wtWebioAn1GraphTsEnable OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded conditions:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : Apply Time Server"
::= { wtWebioAn1GraphTimeServer 3 }
wtWebioAn1GraphTsSyncTime OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Daily synchronisation time with the time server (hour: 0-23)."
::= { wtWebioAn1GraphTimeServer 4 }
-- wtWebioAn1GraphDeviceClock Group
----------------------------
wtWebioAn1GraphClockHrs OBJECT-TYPE
SYNTAX INTEGER (0..23)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Clock hours taking into account the time zone settings."
::= { wtWebioAn1GraphDeviceClock 1 }
wtWebioAn1GraphClockMin OBJECT-TYPE
SYNTAX INTEGER (0..59)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Clock minutes taking into account the time zone settings."
::= { wtWebioAn1GraphDeviceClock 2 }
wtWebioAn1GraphClockDay OBJECT-TYPE
SYNTAX INTEGER (1..31)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Date: Day of the month, taking into account the time zone settings."
::= { wtWebioAn1GraphDeviceClock 3 }
wtWebioAn1GraphClockMonth OBJECT-TYPE
SYNTAX INTEGER {
wtWebioAn1GraphClockMonth-January(1),
wtWebioAn1GraphClockMonth-February(2),
wtWebioAn1GraphClockMonth-March(3),
wtWebioAn1GraphClockMonth-April(4),
wtWebioAn1GraphClockMonth-May(5),
wtWebioAn1GraphClockMonth-June(6),
wtWebioAn1GraphClockMonth-July(7),
wtWebioAn1GraphClockMonth-August(8),
wtWebioAn1GraphClockMonth-September(9),
wtWebioAn1GraphClockMonth-October(10),
wtWebioAn1GraphClockMonth-November(11),
wtWebioAn1GraphClockMonth-December(12)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Date: Month, taking into account the time zone settings."
::= { wtWebioAn1GraphDeviceClock 4 }
wtWebioAn1GraphClockYear OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Date: Year, taking into account the time zone settings."
::= { wtWebioAn1GraphDeviceClock 5 }
-- wtWebioAn1GraphNetwork Group
------------------------
wtWebioAn1GraphIpAddress OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"IP address of the Webio"
::= { wtWebioAn1GraphNetwork 1 }
wtWebioAn1GraphSubnetMask OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Subnet mask of the Webio"
::= { wtWebioAn1GraphNetwork 2 }
wtWebioAn1GraphGateway OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Gateway of the Webio"
::= { wtWebioAn1GraphNetwork 3 }
wtWebioAn1GraphDnsServer1 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"IP address of the 1st DNS server in ASCII"
::= { wtWebioAn1GraphNetwork 4 }
wtWebioAn1GraphDnsServer2 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"IP address of the 2nd DNS server in ASCII"
::= { wtWebioAn1GraphNetwork 5 }
wtWebioAn1GraphAddConfig OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Additional configuration (1=ON):
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: BOOTP disable
"
::= { wtWebioAn1GraphNetwork 6 }
-- wtWebioAn1GraphHTTP Group
--------------------------------
wtWebioAn1GraphStartup OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded start page:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1: Index.htm
Bit 2: Home.htm
Bit 3: User.htm
Only one page may be selected at a time."
::= { wtWebioAn1GraphHTTP 1 }
wtWebioAn1GraphGetHeaderEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"If this bit is set, every answer of a short form GET question will be lead
by the IP-address and name of the device:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : GET Header enable"
::= { wtWebioAn1GraphHTTP 2 }
wtWebioAn1GraphHttpPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Definition of the standard HTML port (Default: 80)."
::= { wtWebioAn1GraphHTTP 3 }
-- wtWebioAn1GraphMail Group
--------------------------------
wtWebioAn1GraphMailAdName OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Device name for mail administration."
::= { wtWebioAn1GraphMail 1 }
wtWebioAn1GraphMailReply OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Reply address for the mail server."
::= { wtWebioAn1GraphMail 2 }
wtWebioAn1GraphMailServer OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name or IP address of the mail server."
::= { wtWebioAn1GraphMail 3 }
wtWebioAn1MailEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set this bit to enable the sending of mails:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : Mail enable"
::= { wtWebioAn1GraphMail 4 }
wtWebioAn1GraphMailAuthentication OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Selection of the authentication modi:
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output.
Bit 0 corresponds to the LSB.
OCTET 1: unused
OCTET 2: unused
OCTET 3: unused
OCTET 4: Bit 3-7: unused
Bit 2 : POP3 before SMTP
Bit 1 : ESMTP, authentication
Bit 0 : SMTP, no authentication"
::= { wtWebioAn1GraphMail 5 }
wtWebioAn1GraphMailAuthUser OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name of the user to be authenticated."
::= { wtWebioAn1GraphMail 6 }
wtWebioAn1GraphMailAuthPassword OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Authentication password."
::= { wtWebioAn1GraphMail 7 }
wtWebioAn1GraphMailPop3Server OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name or Ip-address of the POP3 Servers."
::= { wtWebioAn1GraphMail 8 }
-- wtWebioAn1GraphSNMP Group
--------------------------------
wtWebioAn1GraphSnmpCommunityStringRead OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Community string read only"
::= { wtWebioAn1GraphSNMP 1 }
wtWebioAn1GraphSnmpCommunityStringReadWrite OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Community string read / write"
::= { wtWebioAn1GraphSNMP 2 }
wtWebioAn1GraphSystemTrapManagerIP OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name or IP address of the TCP server which accepts the system trap."
::= { wtWebioAn1GraphSNMP 3 }
wtWebioAn1GraphSystemTrapEnable OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded trigger conditions:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: ColdStart
Bit 1: WarmStart
Bit 2-7: unused"
::= { wtWebioAn1GraphSNMP 4 }
wtWebioAn1GraphSnmpEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set bit 0 to enable SNMP.
If disabled, the device did not respond to any SNMP requests.
Bit 1 decided wether the community string of read operations
is compared with the system password or not:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : SNMP enable"
::= { wtWebioAn1GraphSNMP 5 }
wtWebioAn1GraphSnmpCommunityStringTrap OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Community string of the traps."
::= { wtWebioAn1GraphSNMP 6 }
-- wtWebioAn1GraphUDP Group
--------------------------------
wtWebioAn1GraphUdpPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Udp port to which the Udp queries ( short form GET requests) can be sent. This
port number must be unique within the device."
::= { wtWebioAn1GraphUDP 1 }
wtWebioAn1GraphUdpEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set this bit to enable UDP support:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : UDP enable"
::= { wtWebioAn1GraphUDP 2 }
-- wtWebioAn1GraphSyslog Group
--------------------------------
wtWebioAn1GraphSyslogServerIP OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name or IP address of the Syslog server, which accepts the Syslog messgaes."
::= { wtWebioAn1GraphSyslog 1 }
wtWebioAn1GraphSyslogServerPort OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Portnumber of the Syslog servers, default 514."
::= { wtWebioAn1GraphSyslog 2 }
wtWebioAn1GraphSyslogSystemMessagesEnable OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded trigger conditions:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: ColdStart
Bit 1: WarmStart
Bit 2: Diag Messages
Bit 3-7: unused"
::= { wtWebioAn1GraphSyslog 3 }
wtWebioAn1GraphSyslogEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set bit 0 to enable Syslog:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : Syslog enable"
::= { wtWebioAn1GraphSyslog 4 }
-- wtWebioAn1GraphFTP Group
--------------------------------
wtWebioAn1GraphFTPServerIP OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name or IP address of the FTP server, which accepts the FTP messages."
::= { wtWebioAn1GraphFTP 1 }
wtWebioAn1GraphFTPServerControlPort OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Portnumber of the control port of the FTP server, default 21."
::= { wtWebioAn1GraphFTP 2 }
wtWebioAn1GraphFTPUserName OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"FTP Loggin: user name."
::= { wtWebioAn1GraphFTP 3 }
wtWebioAn1GraphFTPPassword OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"FTP Loggin: user password."
::= { wtWebioAn1GraphFTP 4 }
wtWebioAn1GraphFTPAccount OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"FTP Loggin: name of account."
::= { wtWebioAn1GraphFTP 5 }
wtWebioAn1GraphFTPOption OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Bit 0 switches the FTP Server in Passiv-Mode,
the Client controls the data connection on its own:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : PASV enable"
::= { wtWebioAn1GraphFTP 6 }
wtWebioAn1GraphFTPEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set Bit 0 to enable FTP:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : FTP enable"
::= { wtWebioAn1GraphFTP 7 }
-- wtWebioAn1GraphDatalogger Group
--------------------------------
wtWebioAn1GraphLoggerTimebase OBJECT-TYPE
SYNTAX INTEGER {
wtWebioAn1GraphDatalogger-1Min(1),
wtWebioAn1GraphDatalogger-5Min(2),
wtWebioAn1GraphDatalogger-15Min(3),
wtWebioAn1GraphDatalogger-60Min(4)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Time base of the data logger"
::= { wtWebioAn1GraphDatalogger 1 }
wtWebioAn1GraphLoggerSensorSel OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded trigger conditions:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: Sensor 1
Bit 1: Sensor 2
Bit 2: Sensor 3
Bit 3: Sensor 4
Bit 4: Sensor 5
Bit 5: Sensor 6
Bit 6: Sensor 7
Bit 7: Sensor 8"
::= { wtWebioAn1GraphDatalogger 2 }
wtWebioAn1GraphDisplaySensorSel OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded sensor selection:
only selected sensors will be shown in the graphical presentation:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: Sensor 1
Bit 1: Sensor 2
Bit 2: Sensor 3
Bit 3: Sensor 4
Bit 4: Sensor 5
Bit 5: Sensor 6
Bit 6: Sensor 7
Bit 7: Sensor 8"
::= { wtWebioAn1GraphDatalogger 3 }
-- Graph Sensor Color Table
wtWebioAn1GraphSensorColorTable OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebioAn1GraphSensorColorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"List of sensor colors for the praphical presentation."
::= { wtWebioAn1GraphDatalogger 4 }
wtWebioAn1GraphSensorColorEntry OBJECT-TYPE
SYNTAX WtWebioAn1GraphSensorColorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Index numbers of the sensors."
INDEX { wtWebioAn1GraphSensorNo }
::= { wtWebioAn1GraphSensorColorTable 1 }
WtWebioAn1GraphSensorColorEntry ::= SEQUENCE {
wtWebioAn1GraphSensorColor OCTET STRING
}
wtWebioAn1GraphSensorColor OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(3))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Color of the sensors at the praphical presention."
::= { wtWebioAn1GraphSensorColorEntry 1 }
wtWebioAn1GraphAutoScaleEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"If bit 0 is set, vertical auto scale is enabled:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : Auto Scale enable"
::= { wtWebioAn1GraphDatalogger 5 }
wtWebioAn1GraphVerticalUpperLimit OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This value defines the maximum temperature shown in the graphical presentation,
if no auto scaling is selected.
Temperature in degrees with maximum 2 decimal places."
::= { wtWebioAn1GraphDatalogger 6 }
wtWebioAn1GraphVerticalLowerLimit OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This value defines the minimum temperature shown in the graphical presentation,
if no auto scaling is selected.
Temperature in degrees with maximum 2 decimal places."
::= { wtWebioAn1GraphDatalogger 7 }
wtWebioAn1GraphHorizontalZoom OBJECT-TYPE
SYNTAX INTEGER {
wtWebioAn1GraphZoom-25min(1),
wtWebioAn1GraphZoom-75min(2),
wtWebioAn1GraphZoom-5hrs(3),
wtWebioAn1GraphZoom-30hrs(4),
wtWebioAn1GraphZoom-5days(5),
wtWebioAn1GraphZoom-25days(6)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Defines the default zoom stage, if no auto scaling is selected."
::= { wtWebioAn1GraphDatalogger 8 }
-- wtWebioAn1GraphAlarm Group
----------------------------
wtWebioAn1GraphAlarmCount OBJECT-TYPE
SYNTAX INTEGER (1..8)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of independent alarms."
::= { wtWebioAn1GraphAlarm 1 }
-- Alarm Interface Table
wtWebioAn1GraphAlarmIfTable OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebioAn1GraphAlarmIfEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"List of alarm indices."
::= { wtWebioAn1GraphAlarm 2 }
wtWebioAn1GraphAlarmIfEntry OBJECT-TYPE
SYNTAX WtWebioAn1GraphAlarmIfEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Numbers of the alarms."
INDEX { wtWebioAn1GraphAlarmNo }
::= { wtWebioAn1GraphAlarmIfTable 1 }
WtWebioAn1GraphAlarmIfEntry ::= SEQUENCE {
wtWebioAn1GraphAlarmNo INTEGER
}
wtWebioAn1GraphAlarmNo OBJECT-TYPE
SYNTAX INTEGER (1..8)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Alarm number."
::= { wtWebioAn1GraphAlarmIfEntry 1 }
-- Alarm Table
wtWebioAn1GraphAlarmTable OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebioAn1GraphAlarmEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"List of settings depending on the alarm number."
::= { wtWebioAn1GraphAlarm 3 }
wtWebioAn1GraphAlarmEntry OBJECT-TYPE
SYNTAX WtWebioAn1GraphAlarmEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Alarm parameters of the individual alarms."
INDEX { wtWebioAn1GraphAlarmNo }
::= { wtWebioAn1GraphAlarmTable 1 }
WtWebioAn1GraphAlarmEntry ::= SEQUENCE {
wtWebioAn1GraphAlarmTrigger OCTET STRING,
wtWebioAn1GraphAlarmMin OCTET STRING,
wtWebioAn1GraphAlarmMax OCTET STRING,
wtWebioAn1GraphAlarmHysteresis OCTET STRING,
wtWebioAn1GraphAlarmDelay OCTET STRING,
wtWebioAn1GraphAlarmInterval OCTET STRING,
wtWebioAn1GraphAlarmEnable OCTET STRING,
wtWebioAn1GraphAlarmEMailAddr OCTET STRING,
wtWebioAn1GraphAlarmMailSubject OCTET STRING,
wtWebioAn1GraphAlarmMailText OCTET STRING,
wtWebioAn1GraphAlarmManagerIP OCTET STRING,
wtWebioAn1GraphAlarmTrapText OCTET STRING,
wtWebioAn1GraphAlarmMailOptions OCTET STRING,
wtWebioAn1GraphAlarmTcpIpAddr OCTET STRING,
wtWebioAn1GraphAlarmTcpPort INTEGER,
wtWebioAn1GraphAlarmTcpText OCTET STRING,
wtWebioAn1GraphAlarmClearMailSubject OCTET STRING,
wtWebioAn1GraphAlarmClearMailText OCTET STRING,
wtWebioAn1GraphAlarmClearTrapText OCTET STRING,
wtWebioAn1GraphAlarmClearTcpText OCTET STRING,
wtWebioAn1GraphAlarmSyslogIpAddr OCTET STRING,
wtWebioAn1GraphAlarmSyslogPort INTEGER,
wtWebioAn1GraphAlarmSyslogText OCTET STRING,
wtWebioAn1GraphAlarmFtpDataPort OCTET STRING,
wtWebioAn1GraphAlarmFtpFileName OCTET STRING,
wtWebioAn1GraphAlarmFtpText OCTET STRING,
wtWebioAn1GraphAlarmFtpClearText OCTET STRING,
wtWebioAn1GraphAlarmFtpOption OCTET STRING,
wtWebioAn1GraphAlarmTimerCron OCTET STRING
}
wtWebioAn1GraphAlarmTrigger OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded trigger conditions:
Octet 1: unused
Octet 2: unused
Octet 3:
Bit 0: Timer
Bit 1: ColdStart
Bit 2: WarmStart
Octet 4:
Bit 0: Sensor 1
Bit 1: Sensor 2
Bit 2: Sensor 3
Bit 3: Sensor 4
Bit 4: Sensor 5
Bit 5: Sensor 6
Bit 6: Sensor 7
Bit 7: Sensor 8"
::= { wtWebioAn1GraphAlarmEntry 1 }
wtWebioAn1GraphAlarmMin OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Minimum temperature in degrees with maximum 2 decimal places."
::= { wtWebioAn1GraphAlarmEntry 2 }
wtWebioAn1GraphAlarmMax OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Maximum temperature in degrees with maximum 2 decimal places."
::= { wtWebioAn1GraphAlarmEntry 3 }
wtWebioAn1GraphAlarmHysteresis OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Temperature changes of this size clears the alarm state (MAX-hyst, MIN+hyst.)
, in degrees with maximum 2 decimal places."
::= { wtWebioAn1GraphAlarmEntry 4 }
wtWebioAn1GraphAlarmDelay OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alarm will be delayed by setting this time while stable alarm
condition occur (time in minutes)."
::= { wtWebioAn1GraphAlarmEntry 5 }
wtWebioAn1GraphAlarmInterval OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Send interval for alarm messages."
::= { wtWebioAn1GraphAlarmEntry 6 }
wtWebioAn1GraphAlarmEnable OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded alarm enable:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: Mail Enable
Bit 1: SNMP Trap enable
Bit 2: TCP Client enable"
::= { wtWebioAn1GraphAlarmEntry 7 }
wtWebioAn1GraphAlarmEMailAddr OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"E-Mail address for sending the alarm mail to."
::= { wtWebioAn1GraphAlarmEntry 8 }
wtWebioAn1GraphAlarmMailSubject OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Subject line for alarm mail."
::= { wtWebioAn1GraphAlarmEntry 9 }
wtWebioAn1GraphAlarmMailText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alarm mail text: <Tn> provides the current temperature; n = 1..8.
<Z> provides the current time."
::= { wtWebioAn1GraphAlarmEntry 10 }
wtWebioAn1GraphAlarmManagerIP OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name or IP address of the SNMP Manager which accepts the trap."
::= { wtWebioAn1GraphAlarmEntry 11 }
wtWebioAn1GraphAlarmTrapText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This text is sent in the trap body."
::= { wtWebioAn1GraphAlarmEntry 12 }
wtWebioAn1GraphAlarmMailOptions OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded options:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : Attach Thermo.csv Enable
Bit 1-7: unused"
::= { wtWebioAn1GraphAlarmEntry 13 }
wtWebioAn1GraphAlarmTcpIpAddr OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name or IP address of the TCP server which accepts the trap."
::= { wtWebioAn1GraphAlarmEntry 14 }
wtWebioAn1GraphAlarmTcpPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Port number of the TCP server which accepts the trap."
::= { wtWebioAn1GraphAlarmEntry 15 }
wtWebioAn1GraphAlarmTcpText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This text is sent in the TCP trap body."
::= { wtWebioAn1GraphAlarmEntry 16 }
wtWebioAn1GraphAlarmClearMailSubject OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Subject line for alarm clear mail."
::= { wtWebioAn1GraphAlarmEntry 17 }
wtWebioAn1GraphAlarmClearMailText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
" Alarm clear mail text: <Tn> provides the current temperature; n = 1..8. <Z> provides the current time."
::= { wtWebioAn1GraphAlarmEntry 18 }
wtWebioAn1GraphAlarmClearTrapText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This text is sent in the trap body."
::= { wtWebioAn1GraphAlarmEntry 19 }
wtWebioAn1GraphAlarmClearTcpText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This text is sent in the TCP trap body."
::= { wtWebioAn1GraphAlarmEntry 20 }
wtWebioAn1GraphAlarmSyslogIpAddr OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"IP address of the syslog server to which the Webio device should send syslog messages."
::= { wtWebioAn1GraphAlarmEntry 21 }
wtWebioAn1GraphAlarmSyslogPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Port number of the syslog server to which the Webio device should send syslog messages."
::= { wtWebioAn1GraphAlarmEntry 22 }
wtWebioAn1GraphAlarmSyslogText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body."
::= { wtWebioAn1GraphAlarmEntry 23 }
wtWebioAn1GraphAlarmSyslogClearText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body."
::= { wtWebioAn1GraphAlarmEntry 24 }
wtWebioAn1GraphAlarmFtpDataPort OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Local data port: 1..65535 or AUTO: the next free port will be assigned."
::= { wtWebioAn1GraphAlarmEntry 25 }
wtWebioAn1GraphAlarmFtpFileName OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name of the file including path informations."
::= { wtWebioAn1GraphAlarmEntry 26 }
wtWebioAn1GraphAlarmFtpText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Message text to store on the FTP server."
::= { wtWebioAn1GraphAlarmEntry 27 }
wtWebioAn1GraphAlarmFtpClearText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alarm clear message to store on the FTP server."
::= { wtWebioAn1GraphAlarmEntry 28 }
wtWebioAn1GraphAlarmFtpOptions OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded options, select only one option at the same time:
STORE = replace file
APPEND = append message at the end of the file
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : STORE
Bit 1 : APPEND
Bit 2-7: unused"
::= { wtWebioAn1GraphAlarmEntry 29 }
wtWebioAn1GraphAlarmTimerCron OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This entry contains 5 text fields space or tab seperated for time trigger definition.
Each field must match with the actual time to trigger a message, weekday and day of month
are interpreted separately.
1: Minutes Range 0-59
2. Hours Range 0-23, 0 is midnight
3: Day of month Range 1-31
4: Month Range 1-12
5: Weekday Range 0-6, 0 is sunday
Syntax for every field:
- an asterix (*) enables every possible setting of a field
- single numbers seperated by commas
- a partition within the allowed range (1-5)
- step size within an partition of the allowed range (0-59/2: every second minute)."
::= { wtWebioAn1GraphAlarmEntry 30 }
-- wtWebioAn1GraphPorts Group
----------------------------
-- Table
wtWebioAn1GraphPortTable OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebioAn1GraphPortEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"List of settings depending on the sensor number."
::= { wtWebioAn1GraphPorts 1 }
wtWebioAn1GraphPortEntry OBJECT-TYPE
SYNTAX WtWebioAn1GraphPortEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Sensor parameters for the individual sensors."
INDEX { wtWebioAn1GraphSensorNo }
::= { wtWebioAn1GraphPortTable 1 }
WtWebioAn1GraphPortEntry ::= SEQUENCE {
wtWebioAn1GraphPortName OCTET STRING,
wtWebioAn1GraphPortText OCTET STRING,
wtWebioAn1GraphPortOffset1 OCTET STRING,
wtWebioAn1GraphPortTemperature1 OCTET STRING,
wtWebioAn1GraphPortOffset2 OCTET STRING,
wtWebioAn1GraphPortTemperature2 OCTET STRING,
wtWebioAn1GraphPortComment OCTET STRING
}
wtWebioAn1GraphPortName OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name of the sensor."
::= { wtWebioAn1GraphPortEntry 1 }
wtWebioAn1GraphPortText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Description of the sensor."
::= { wtWebioAn1GraphPortEntry 2 }
wtWebioAn1GraphPortOffset1 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 1."
::= { wtWebioAn1GraphPortEntry 3 }
wtWebioAn1GraphPortTemperature1 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places."
::= { wtWebioAn1GraphPortEntry 4 }
wtWebioAn1GraphPortOffset2 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 2."
::= { wtWebioAn1GraphPortEntry 5 }
wtWebioAn1GraphPortTemperature2 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places."
::= { wtWebioAn1GraphPortEntry 6 }
wtWebioAn1GraphPortComment OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset calibration: informations of date, name of operator, reference devices."
::= { wtWebioAn1GraphPortEntry 7 }
-- wtWebioAn1GraphManufact Group
----------------------------
wtWebioAn1GraphMfName OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Manufacturer company name"
::= { wtWebioAn1GraphManufact 1 }
wtWebioAn1GraphMfAddr OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Manufacturer address."
::= { wtWebioAn1GraphManufact 2 }
wtWebioAn1GraphMfHotline OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Manufacturer hotline."
::= { wtWebioAn1GraphManufact 3 }
wtWebioAn1GraphMfInternet OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Manufacturer Internet address."
::= { wtWebioAn1GraphManufact 4 }
wtWebioAn1GraphMfDeviceTyp OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Manufacturer device name (model number)."
::= { wtWebioAn1GraphManufact 5 }
wtWebioAn1GraphMfOrderNo OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Manufacturer part number."
::= { wtWebioAn1GraphManufact 6 }
-- wtWebioAn1GraphDiag Group
----------------------------
wtWebioAn1GraphDiagErrorCount OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of entries in the error memory."
::= { wtWebioAn1GraphDiag 1 }
wtWebioAn1GraphDiagBinaryError OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Error causes coded bit-by-bit."
::= { wtWebioAn1GraphDiag 2 }
wtWebioAn1GraphDiagErrorIndex OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The value of this variable is used as an index to read
an error massege from wtWebioAn1GraphDiagErrorMessage.
Errors are numbered from 1 to wtWebioAn1GraphDiagErrorCount.
Writing a valid value into this variable, making the appropriate
message readable from wtWebioAn1GraphDiagErrorMessage."
::= { wtWebioAn1GraphDiag 3 }
wtWebioAn1GraphDiagErrorMessage OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Using wtWebioAn1GraphDiagErrorIndex as an index, the appropriate message is available."
::= { wtWebioAn1GraphDiag 4 }
wtWebioAn1GraphDiagErrorClear OBJECT-TYPE
SYNTAX INTEGER
ACCESS write-only
STATUS mandatory
DESCRIPTION
"Writing 1 into this variable clears all diagnosis messages."
::= { wtWebioAn1GraphDiag 5 }
-- TRAP DEFINITIONS
-- Diese SNMP-Traps werden gesendet, wenn die Alarmtriggerbedingungen zutreffen
wtWebioAn1GraphAlert1 TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES { wtWebioAn1GraphAlarmTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 1 was triggered,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-Thermograph Alarm 1"
--#SUMMARY "Alarm 1: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 31
wtWebioAn1GraphAlert2 TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES { wtWebioAn1GraphAlarmTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 2 was triggered,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-Thermograph Alarm 2"
--#SUMMARY "Alarm 2: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 32
wtWebioAn1GraphAlert3 TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES { wtWebioAn1GraphAlarmTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 3 was triggered,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-Thermograph Alarm 3"
--#SUMMARY "Alarm 3: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 33
wtWebioAn1GraphAlert4 TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES { wtWebioAn1GraphAlarmTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 4 was triggered,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-Thermograph Alarm 4"
--#SUMMARY "Alarm 4: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 34
wtWebioAn1GraphAlert5 TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES { wtWebioAn1GraphAlarmTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 5 was triggered,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-Thermograph Alarm 5"
--#SUMMARY "Alarm 5: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 35
wtWebioAn1GraphAlert6 TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES { wtWebioAn1GraphAlarmTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 6 was triggered,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-Thermograph Alarm 6"
--#SUMMARY "Alarm 6: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 36
wtWebioAn1GraphAlert7 TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES { wtWebioAn1GraphAlarmTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 7 was triggered,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-Thermograph Alarm 7"
--#SUMMARY "Alarm 7: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 37
wtWebioAn1GraphAlert8 TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES { wtWebioAn1GraphAlarmTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 8 was triggered,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-Thermograph Alarm 8"
--#SUMMARY "Alarm 8: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 38
wtWebioAn1GraphAlert9 TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES { wtWebioAn1GraphAlarmClearTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 1 was cleared,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-Thermograph Release Alarm 1"
--#SUMMARY "Release Alarm 1: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 91
wtWebioAn1GraphAlert10 TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES { wtWebioAn1GraphAlarmClearTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 2 was cleared,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-Thermograph Release Alarm 2"
--#SUMMARY "Release Alarm 2: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 92
wtWebioAn1GraphAlert11 TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES { wtWebioAn1GraphAlarmClearTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 3 was cleared,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-Thermograph Release Alarm 3"
--#SUMMARY "Release Alarm 3: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 93
wtWebioAn1GraphAlert12 TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES { wtWebioAn1GraphAlarmClearTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 4 was cleared,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-Thermograph Release Alarm 4"
--#SUMMARY "Release Alarm 4: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 94
wtWebioAn1GraphAlert13 TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES { wtWebioAn1GraphAlarmClearTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 5 was cleared,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-Thermograph Release Alarm 5"
--#SUMMARY "Release Alarm 5: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 95
wtWebioAn1GraphAlert14 TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES { wtWebioAn1GraphAlarmClearTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 6 was cleared,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-Thermograph Release Alarm 6"
--#SUMMARY "Release Alarm 6: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 96
wtWebioAn1GraphAlert15 TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES { wtWebioAn1GraphAlarmClearTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 7 was cleared,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-Thermograph Release Alarm 7"
--#SUMMARY "Release Alarm 7: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 97
wtWebioAn1GraphAlert16 TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES { wtWebioAn1GraphAlarmClearTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 8 was cleared,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-Thermograph Release Alarm 8"
--#SUMMARY "Release Alarm 8: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 98
wtWebioAn1GraphAlertDiag TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES {
wtWebioAn1GraphDiagErrorIndex,
wtWebioAn1GraphDiagErrorMessage
}
DESCRIPTION
"This SNMP trap is generated when a diagnosis/error message was triggered,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-Thermograph Diagnose Error"
--#SUMMARY "Diagnose error index: %d, Message: %s."
--#ARGUMENTS {0,1}
--#SEVERITY MAJOR
--#TIMEINDEX 99
--#STATE DEGRADED
::= 110
END