355 lines
12 KiB
Plaintext
355 lines
12 KiB
Plaintext
RUGGEDCOM-IRIGB-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
MODULE-IDENTITY,
|
|
OBJECT-TYPE, Integer32, NOTIFICATION-TYPE FROM SNMPv2-SMI
|
|
TEXTUAL-CONVENTION FROM SNMPv2-TC
|
|
OBJECT-GROUP FROM SNMPv2-CONF
|
|
ruggedcomMgmt, ruggedcomTraps FROM RUGGEDCOM-MIB
|
|
RcTimeSyncStatus FROM RUGGEDCOM-TIMECONFIG-MIB;
|
|
|
|
rcIrigb MODULE-IDENTITY
|
|
LAST-UPDATED "201510301700Z" -- Oct 30, 17:00 EST 2015
|
|
ORGANIZATION "Siemens Canada Limited"
|
|
CONTACT-INFO
|
|
"Postal: Siemens Canada Limited
|
|
300 Applewood Crescent
|
|
Concord, Ontario,
|
|
L4K 5C7 Canada
|
|
Tel: 1-905-856-5288
|
|
E-Mail: support@ruggedcom.com"
|
|
DESCRIPTION
|
|
"Siemens - RuggedCom proprietary to control and monitor IRIGB module."
|
|
REVISION "201510301700Z" -- Oct 30, 17:00 EST 2015
|
|
DESCRIPTION
|
|
"Added objects to configure and monitor IRIGB in RuggedCom devices."
|
|
|
|
REVISION "201412011700Z" -- Dec 01, 17:00 EST 2014
|
|
DESCRIPTION
|
|
"Initial version of Siemens - RuggedCom proprietary MIB to control and
|
|
monitor IRIGB module."
|
|
|
|
::= { ruggedcomMgmt 10 }
|
|
|
|
---------------------------------------------------------------
|
|
-- Textual Conventions
|
|
---------------------------------------------------------------
|
|
RcTimeStamp ::= TEXTUAL-CONVENTION
|
|
DISPLAY-HINT "4d.4d"
|
|
STATUS current
|
|
DESCRIPTION "Timestamps are represented as a 64-bit unsigned
|
|
fixed-point number in seconds relative to
|
|
00:00 on 1 January 1970. The integer part is in the
|
|
first 32 bits and the fraction part is in the last
|
|
32 bits."
|
|
SYNTAX OCTET STRING (SIZE (8))
|
|
|
|
-- ---------------------------------------------------------- --
|
|
-- rcIrigb subtrees
|
|
-- ---------------------------------------------------------- --
|
|
rcIrigbBase OBJECT IDENTIFIER ::= { rcIrigb 1 }
|
|
rcIrigbConformance OBJECT IDENTIFIER ::= { rcIrigb 2 }
|
|
rcIrigbGroups OBJECT IDENTIFIER ::= { rcIrigbConformance 2 }
|
|
|
|
-- ---------------------------------------------------------------------- --
|
|
-- Base subtree
|
|
-- ---------------------------------------------------------------------- --
|
|
rcIrigbStatus OBJECT-TYPE
|
|
SYNTAX RcTimeSyncStatus
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system synchronization status when IRIGB is a primary
|
|
time source.
|
|
|
|
If value of this object is changed, rcIrigbStatusChange notification
|
|
will be sent."
|
|
::= { rcIrigbBase 1}
|
|
|
|
rcIrigbAMOutput OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(1),
|
|
am(4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Selects AM (Amplitude Modulation) mode of IRIGB port."
|
|
REFERENCE
|
|
"AM mode complies with IRIG Standard 200-04."
|
|
::= { rcIrigbBase 2}
|
|
|
|
rcIrigbTimeCode OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
bxx0(1),
|
|
bxx1(2),
|
|
bxx2(3),
|
|
bxx3(4),
|
|
bxx4(5),
|
|
bxx5(6),
|
|
bxx6(7),
|
|
bxx7(8)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This device uses the following convention to decode the IRIGB time code:
|
|
letter [B] represents IRIG-B format, [xx] represents [00] for PWM/TTL mode
|
|
of operation and [12] for AM operation. For example, Bxx7 represents B007
|
|
for PWM/TTL operation and B127 for AM operation. Please note that only Bxx0,
|
|
Bxx1, Bxx4 and Bxx5 time codes support IRIGB extensions."
|
|
::= { rcIrigbBase 3}
|
|
|
|
rcIrigbExt OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(1),
|
|
ieee1344(2),
|
|
c37-118-2005(3),
|
|
c37-118-2011(4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"IRIGB extensions use extra bits of the Control Functions (CF) portion of the
|
|
IRIGB time code. Within this portion of the time code, bits are designated for
|
|
additional features, including: Calendar Year, Leap seconds, leap seconds pending,
|
|
Daylight Saving Time (DST), DST pending, local time offset and time quality.
|
|
Please note that only Bxx0, Bxx1, Bxx4 and Bxx5 time codes support IRIGB extensions."
|
|
::= { rcIrigbBase 4}
|
|
|
|
rcIrigbInput OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(1),
|
|
pwm(2),
|
|
pps(3),
|
|
am(4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Selects operational mode of IRIGB input port. IRIGB module is capable of interpreting
|
|
IRIGB extensions such as C37.118-2011, C37.118-2005 and IEEE1344."
|
|
REFERENCE
|
|
"C37.118-2011, C37.118-2005 and IEEE1344."
|
|
::= { rcIrigbBase 5}
|
|
|
|
rcIrigbLockInt OBJECT-TYPE
|
|
SYNTAX Integer32(1..120)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"To set time interval in minute with in which IRIGB receiver
|
|
should acquire lock to the time source.
|
|
Normally IRIGB receiver needs couple of minutes to lock
|
|
the signal.
|
|
User should set reasonable time interval. If time interval expire
|
|
with out acquire the lock then system start distributing the time
|
|
using local clock."
|
|
::= { rcIrigbBase 6}
|
|
|
|
rcIrigbCableComp OBJECT-TYPE
|
|
SYNTAX Integer32(0..50000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Cable compensation in ns may be desired to compensate for a long
|
|
cable run in order to minimize the timing inaccuracy."
|
|
::= { rcIrigbBase 7}
|
|
|
|
rcIrigbOFM OBJECT-TYPE
|
|
SYNTAX Integer32(-2147483647..2147483647)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current time offset between system and reference clocks."
|
|
::= { rcIrigbBase 8}
|
|
|
|
rcIrigbFreqAdj OBJECT-TYPE
|
|
SYNTAX Integer32(-2147483647..2147483647)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current amount of discipline applied to the local frequency reference (TCXO)."
|
|
::= { rcIrigbBase 9}
|
|
|
|
rcIrigbOutputPWM1 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(1),
|
|
pwm(2),
|
|
pps(3),
|
|
ppx(5)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Selects Operational mode of TTL output port. PWM mode complies with IRIG
|
|
Standard 200-04. PPx provides generic pulse per x second interface to
|
|
synchronize external devices."
|
|
::= { rcIrigbBase 10}
|
|
|
|
rcIrigbPulseInterval1 OBJECT-TYPE
|
|
SYNTAX Integer32(1..86400)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Selects Pulse Interval in s for TTL output port. This parameter is used
|
|
in conjunction with PPx in order to provides generic pulse per x second
|
|
interface to synchronize external devices."
|
|
::= { rcIrigbBase 11}
|
|
|
|
rcIrigbPulseWidth1 OBJECT-TYPE
|
|
SYNTAX Integer32(1..200)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Selects Pulse Width in ms for TTL output port. This parameter is used in
|
|
conjunction with PPx to control the width of the pulse."
|
|
::= { rcIrigbBase 12}
|
|
|
|
rcIrigbStartTime1 OBJECT-TYPE
|
|
SYNTAX RcTimeStamp
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This parameter is used in conjunction with PPx to set the starting time of
|
|
first PPx event. Note that this parameter must be set at least 15 seconds
|
|
before the start of desired PPx otherwise first PPx event might be lost."
|
|
::= { rcIrigbBase 13}
|
|
|
|
rcIrigbOutputPWM2 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(1),
|
|
pwm(2),
|
|
pps(3),
|
|
ppx(5)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Selects Operational mode of TTL output port2. PWM mode complies with IRIG
|
|
Standard 200-04. PPx provides generic pulse per x second interface to
|
|
synchronize external devices."
|
|
REFERENCE
|
|
"IRIGB Standard 200-04."
|
|
::= { rcIrigbBase 14}
|
|
|
|
rcIrigbPulseInterval2 OBJECT-TYPE
|
|
SYNTAX Integer32(1..86400)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Selects Pulse Interval in s for TTL output port2. This parameter is used
|
|
in conjunction with PPx in order to provides generic pulse per x second
|
|
interface to synchronize external devices."
|
|
::= { rcIrigbBase 15}
|
|
|
|
rcIrigbPulseWidth2 OBJECT-TYPE
|
|
SYNTAX Integer32(1..200)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Selects Pulse Width in ms for TTL output port2. This parameter is used in
|
|
conjunction with PPx to control the width of the pulse."
|
|
::= { rcIrigbBase 16}
|
|
|
|
rcIrigbStartTime2 OBJECT-TYPE
|
|
SYNTAX RcTimeStamp
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This parameter is used in conjunction with PPx to set the starting time of
|
|
first PPx event. Note that this parameter must be set at least 15 seconds
|
|
before the start of desired PPx otherwise first PPx event might be lost."
|
|
::= { rcIrigbBase 17}
|
|
-- ---------------------------------------------------------------------- --
|
|
-- Traps
|
|
-- ---------------------------------------------------------------------- --
|
|
rcIrigbStatusChange NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
rcIrigbStatus
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Notification generated if status of the IRIGB module is changed."
|
|
::= { ruggedcomTraps 35 }
|
|
|
|
-- ---------------------------------------------------------------------- --
|
|
-- Conformance Groups
|
|
-- ---------------------------------------------------------------------- --
|
|
rcIrigbBaseGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
rcIrigbStatus
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A group of objects providing ability ability to monitor and configure IRIGB status."
|
|
::= { rcIrigbGroups 1 }
|
|
|
|
rcIrigbNotifyGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
rcIrigbStatusChange
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A group of objects that define trap."
|
|
::= { rcIrigbGroups 2 }
|
|
|
|
|
|
rcIrigbCommonGroup OBJECT-GROUP
|
|
OBJECTS { rcIrigbStatus,
|
|
rcIrigbTimeCode,
|
|
rcIrigbExt,
|
|
rcIrigbLockInt,
|
|
rcIrigbCableComp,
|
|
rcIrigbOFM,
|
|
rcIrigbFreqAdj
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A group of objects providing ability to monitor and configure IRIGB device."
|
|
::= { rcIrigbGroups 3 }
|
|
|
|
rcIrigbAMOutGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
rcIrigbAMOutput
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A group of objects providing ability to configure IRIGB AM output interface."
|
|
::= { rcIrigbGroups 4 }
|
|
|
|
rcIrigbInputGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
rcIrigbInput
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This parameter covers both AM and PWM inputs."
|
|
::= { rcIrigbGroups 5 }
|
|
|
|
rcIrigbTTLOutput01Group OBJECT-GROUP
|
|
OBJECTS {
|
|
rcIrigbOutputPWM1,
|
|
rcIrigbPulseInterval1,
|
|
rcIrigbPulseWidth1,
|
|
rcIrigbStartTime1
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A group of objects providing ability to configure IRIGB TTL output interface01."
|
|
::= { rcIrigbGroups 6 }
|
|
|
|
rcIrigbTTLOutput02Group OBJECT-GROUP
|
|
OBJECTS {
|
|
rcIrigbOutputPWM2,
|
|
rcIrigbPulseInterval2,
|
|
rcIrigbPulseWidth2,
|
|
rcIrigbStartTime2
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A group of objects providing ability to configure IRIGB TTL output interface02."
|
|
::= { rcIrigbGroups 7 }
|
|
|
|
END
|