Observium_CE/mibs/scte/SCTE-HMS-GEN-MIB

520 lines
15 KiB
Plaintext

-- ****************************************************************************
-- *
-- * Module Name: HMS033R10 (SCTE 38-6-2005)
-- *
-- * Description: Implements SCTE-HMS-GEN-MIB for Outside Plant Generators
-- *
-- * 13-Apr-2005 Altered genVBatIgnition and genEnclosureTemperature to
-- * require an entry in the property table, instead of entries
-- * in the discrete property table. Description of
-- * these objects in R8 was a typographical error.
-- *
-- * 07-Nov-2005 Altered genProtocolVersion per ballot comments
-- * - 'power supply' changed to 'generator'
-- * - value of 0x04 changed to 11 to reflect current document
-- * revision
-- * - Object description now mirrors psProtocolVersion MIB object
-- * in SCTE-HMS-PS-MIB.
-- *
-- ****************************************************************************
SCTE-HMS-GEN-MIB DEFINITIONS ::= BEGIN
IMPORTS
OBJECT-TYPE
FROM RFC-1212
genIdent
FROM SCTE-HMS-ROOTS
;
-- /*************************************
-- * The Generator Group *
-- *************************************/
genNumberOfGenerators OBJECT-TYPE
SYNTAX INTEGER ( 1..8 )
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of generators connected to this NE."
::= { genIdent 1 }
genDeviceTable OBJECT-TYPE
SYNTAX SEQUENCE OF GenDeviceEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Table containing information about the individual
generators being monitored"
::= { genIdent 2 }
genDeviceEntry OBJECT-TYPE
SYNTAX GenDeviceEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"List of information about each generator being monitored."
INDEX { genDeviceAddress }
::= { genDeviceTable 1 }
GenDeviceEntry ::=
SEQUENCE
{
genDeviceAddress
INTEGER,
genProtocolVersion
INTEGER,
genSoftwareVersion
OCTET STRING,
genDeviceId
OCTET STRING,
genGasHazardOption
INTEGER,
genWaterIntrusionOption
INTEGER,
genPadShearOption
INTEGER,
genDoorOption
INTEGER,
genChargerOption
INTEGER,
genFuelOption
INTEGER,
genVBatIgnitionOption
INTEGER,
genTempOption
INTEGER,
genGeneratorStatus
INTEGER,
genGasHazard
INTEGER,
genWaterIntrusion
INTEGER,
genPadShear
INTEGER,
genEnclosureDoor
INTEGER,
genCharger
INTEGER,
genFuel
INTEGER,
genVBatIgnition
INTEGER,
genEnclosureTemperature
INTEGER,
genEquipmentControl
INTEGER,
genOilOption
INTEGER,
genMinorAlarmSupport
INTEGER,
genMajorAlarmSupport
INTEGER,
genOil
INTEGER,
genMinorAlarm
INTEGER,
genMajorAlarm
INTEGER,
genVendorOID
OBJECT IDENTIFIER
}
genDeviceAddress OBJECT-TYPE
SYNTAX INTEGER ( 1..15 )
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Index into the psDeviceTable.
Address of Generator on the RS-485 Path"
::= { genDeviceEntry 1 }
-- * Generator Configuration
genProtocolVersion OBJECT-TYPE
SYNTAX INTEGER ( 0..255 )
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Version of the SCTE HMS protocol implemented in the monitored
equipment. The 'Protocol Version' implementation will comply
with the defined protocol in the SCTE 25-3 (formerly HMS 022)
document with the corresponding revision number.
Example: A generator implementing all commands and responses
defined in the SCTE 25-3 revision 1.1 would return a value
of 11(decimal) in this field, reflecting major revision 1,
minor revision 1."
::= { genDeviceEntry 2 }
genSoftwareVersion OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(8))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The contents of this field are vendor specific. The intent
is to provide a text representation of the power supply or
generator system software version. Any printable ASCII
characters ca be included in this field. NULL (0x00)
characters are non-printable and are used to fill any unused
locations following the text data"
::= { genDeviceEntry 3 }
genDeviceId OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The content of this field is vendor specific. The intent is
to provide manufacturer and/or product specific ASCII text
information that will propagate to the manager's console
verbatim. The following special characters are defined in
association with this field:
'\' Used to cause a new line on the console display.
Example: 'ALPHA\XM2 9015' would appear at the monitoring
station as :
ALPHA
XM2 9015"
::= { genDeviceEntry 4 }
genGasHazardOption OBJECT-TYPE
SYNTAX INTEGER { notInstalled(1), installed(2) }
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Defines if gas hazard sensor is installed."
::= { genDeviceEntry 5 }
genWaterIntrusionOption OBJECT-TYPE
SYNTAX INTEGER { notInstalled(1), installed(2) }
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Defines if water intrusion sensor is installed."
::= { genDeviceEntry 6 }
genPadShearOption OBJECT-TYPE
SYNTAX INTEGER { notInstalled(1), installed(2) }
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Defines if pad shear sensor is installed."
::= { genDeviceEntry 7 }
genDoorOption OBJECT-TYPE
SYNTAX INTEGER { notInstalled(1), installed(2) }
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Defines if separate generator door is installed."
::= { genDeviceEntry 8 }
genChargerOption OBJECT-TYPE
SYNTAX INTEGER { notInstalled(1), installed(2) }
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Defines if charger fail signal is supported."
::= { genDeviceEntry 9 }
genFuelOption OBJECT-TYPE
SYNTAX INTEGER { notInstalled(1), installed(2) }
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Defines if low fuel detection is supported."
::= { genDeviceEntry 10 }
genVBatIgnitionOption OBJECT-TYPE
SYNTAX INTEGER { notInstalled(1), installed(2) }
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Defines if engine ignition battery voltage is monitored."
::= { genDeviceEntry 11 }
genTempOption OBJECT-TYPE
SYNTAX INTEGER { notInstalled(1), installed(2) }
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Defines if engine enclosure temperature is monitored."
::= { genDeviceEntry 12 }
-- * Generator Data
genGeneratorStatus OBJECT-TYPE
SYNTAX INTEGER { off(1), runningTest (2), running(3), fail(4) }
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Defines the current state of generator operation.
1 = Off
2 = Running(test)
3 = Running
4 = Fail (A condition preventing the generator
from functioning)
This item requires entries in the discrete property table."
::= { genDeviceEntry 13 }
genGasHazard OBJECT-TYPE
SYNTAX INTEGER { noAlarm(1), alarm(2) }
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The concentration of hydrocarbon fuel in the
generator enclosure has exceeded safe limits.
Generator operation is suspended. The alarm
is cleared when the sensor is reset via the
'Reset Latched Generator Alarms' command.
This item requires entries in the discrete property table."
::= { genDeviceEntry 14 }
genWaterIntrusion OBJECT-TYPE
SYNTAX INTEGER { noAlarm(1), alarm(2) }
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Water level within the generator or fuel enclosure
has exceeded safe limits for generator operation.
Generator operation is suspended while this alarm
is active. The alarm is reset when the water returns
to a safe level.
This item requires entries in the discrete property table."
::= { genDeviceEntry 15 }
genPadShear OBJECT-TYPE
SYNTAX INTEGER { noAlarm(1), alarm(2) }
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicates that the generator or fuel enclosure
has shifted from its mounting position. Generator
operation is suspended. The alarm is reset when
the unit its returned to its original position.
This item requires entries in the discrete property table."
::= { genDeviceEntry 16 }
genEnclosureDoor OBJECT-TYPE
SYNTAX INTEGER { noAlarm(1), alarm(2) }
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicates current status of the generator
and/or auxiliary fuel enclosure door.
This item requires entries in the discrete property table."
::= { genDeviceEntry 17 }
genCharger OBJECT-TYPE
SYNTAX INTEGER { noAlarm(1), alarm(2) }
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicates if the ignition battery charger is operating.
This item requires entries in the discrete property table."
::= { genDeviceEntry 18 }
genFuel OBJECT-TYPE
SYNTAX INTEGER { noAlarm(1), alarm(2) }
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicates if the engine's fuel supply is sufficient
for extended operation. Alarm is reset when fuel is
replenished.
This item requires entries in the discrete property table."
::= { genDeviceEntry 19 }
genVBatIgnition OBJECT-TYPE
SYNTAX INTEGER ( 0..65535 )
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Scaled representation of the generator's
ignition battery in 1/100 Volts.
This item requires an entry in the property table."
::= { genDeviceEntry 20 }
genEnclosureTemperature OBJECT-TYPE
SYNTAX INTEGER ( -40..80 )
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Temperature inside generator's enclosure in degrees C.
This item requires an entry in the property table."
::= { genDeviceEntry 21 }
genEquipmentControl OBJECT-TYPE
SYNTAX INTEGER {
stopGenerator(1),
startGenerator(2),
resetLatchedAlarms(3) }
ACCESS read-write
STATUS optional
DESCRIPTION
"When written, the appropriate corresponding command action
is sent to the generator.
1 = End generator test
2 = Start generator test
3 = Reset latched generator alarms which
may be preventing a generator start
This object is intentionally simplistic to allow for maximum
flexibility. It IS assumed that the generator has
sufficient intelligence to prevent an overcrank condition.
Example 1: From a single SET and corresponding single
'start' command, the generator may automatically attempt
starting 'n' times before giving up.
Example 2: The transponder may be simple and send only the
single 'start' command, and the EMS/end user is responsible
for making 'n' attempts (by performing additional SETs to
this object.)
The choice between the methods depends on the specific
application and vendor equipment."
::= { genDeviceEntry 22 }
genOilOption OBJECT-TYPE
SYNTAX INTEGER { notInstalled(1), installed(2) }
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Defines if oil pressure is monitored."
::= { genDeviceEntry 23 }
genMinorAlarmSupport OBJECT-TYPE
SYNTAX INTEGER { notInstalled(1), installed(2) }
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Defines if the minor alarm indicator is supported."
::= { genDeviceEntry 24 }
genMajorAlarmSupport OBJECT-TYPE
SYNTAX INTEGER { notInstalled(1), installed(2) }
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Defines if the major alarm indicator is supported."
::= { genDeviceEntry 25 }
genOil OBJECT-TYPE
SYNTAX INTEGER { noAlarm(1), alarm(2) }
ACCESS read-only
STATUS optional
DESCRIPTION
"Indicates if the engine's oil is adequate for safe operation.
Alarm is reset when the condition returns to normal.
This item requires entries in the discrete property table."
::= { genDeviceEntry 26 }
genMinorAlarm OBJECT-TYPE
SYNTAX INTEGER { noAlarm(1), alarm(2) }
ACCESS read-only
STATUS optional
DESCRIPTION
"Indicates if the generator is indicating a minor alarm.
The generator requires attention, but does not require an immediate
visit to the generator.
This item requires entries in the discrete property table."
::= { genDeviceEntry 27 }
genMajorAlarm OBJECT-TYPE
SYNTAX INTEGER { noAlarm(1), alarm(2) }
ACCESS read-only
STATUS optional
DESCRIPTION
"Indicates if the generator is indicating a major alarm.
The generator requires immediate attention, and should be visited
immediately to remedy the situation.
This item requires entries in the discrete property table."
::= { genDeviceEntry 28 }
genVendorOID OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
ACCESS read-only
STATUS optional
DESCRIPTION
"This object provides a means for a vendor to
point to a vendor specific extension of this MIB."
::= { genDeviceEntry 29 }
END