-- * Module Name: HMS033R10 (SCTE 38-6-2005)
|
|
-- *
|
|
-- * Description: Implements SCTE-HMS-GEN-MIB for Outside Plant Generators
|
|
-- *
|
|
-- * 13-Apr-2005 Altered genVBatIgnition and genEnclosureTemperature to
|
|
-- * require an entry in the property table, instead of entries
|
|
-- * in the discrete property table. Description of
|
|
-- * these objects in R8 was a typographical error.
|
|
-- *
|
|
-- * 07-Nov-2005 Altered genProtocolVersion per ballot comments
|
|
-- * - 'power supply' changed to 'generator'
|
|
-- * - value of 0x04 changed to 11 to reflect current document
|
|
-- * revision
|
|
-- * - Object description now mirrors psProtocolVersion MIB object
|
|
-- * in SCTE-HMS-PS-MIB.
|
|
-- *
|
|
-- ****************************************************************************
|
|
|
|
SCTE-HMS-GEN-MIB DEFINITIONS ::= BEGIN
|
|
|
|
|
|
IMPORTS
|
|
OBJECT-TYPE
|
|
FROM RFC-1212
|
|
genIdent
|
|
FROM SCTE-HMS-ROOTS
|
|
;
|
|
|
|
-- /*************************************
|
|
-- * The Generator Group *
|
|
-- *************************************/
|
|
|
|
|
|
genNumberOfGenerators OBJECT-TYPE
|
|
SYNTAX INTEGER ( 1..8 )
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of generators connected to this NE."
|
|
::= { genIdent 1 }
|
|
|
|
|
|
genDeviceTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF GenDeviceEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Table containing information about the individual
|
|
generators being monitored"
|
|
::= { genIdent 2 }
|
|
|
|
genDeviceEntry OBJECT-TYPE
|
|
SYNTAX GenDeviceEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"List of information about each generator being monitored."
|
|
INDEX { genDeviceAddress }
|
|
::= { genDeviceTable 1 }
|
|
|
|
GenDeviceEntry ::=
|
|
SEQUENCE
|
|
{
|
|
genDeviceAddress
|
|
INTEGER,
|
|
|
|
genProtocolVersion
|
|
INTEGER,
|
|
|
|
genSoftwareVersion
|
|
OCTET STRING,
|
|
|
|
genDeviceId
|
|
OCTET STRING,
|
|
|
|
genGasHazardOption
|
|
INTEGER,
|
|
|
|
genWaterIntrusionOption
|
|
INTEGER,
|
|
|
|
genPadShearOption
|
|
INTEGER,
|
|
|
|
genDoorOption
|
|
INTEGER,
|
|
|
|
genChargerOption
|
|
INTEGER,
|
|
|
|
genFuelOption
|
|
INTEGER,
|
|
|
|
genVBatIgnitionOption
|
|
INTEGER,
|
|
|
|
genTempOption
|
|
INTEGER,
|
|
|
|
genGeneratorStatus
|
|
INTEGER,
|
|
|
|
genGasHazard
|
|
INTEGER,
|
|
|
|
genWaterIntrusion
|
|
INTEGER,
|
|
|
|
genPadShear
|
|
INTEGER,
|
|
|
|
genEnclosureDoor
|
|
INTEGER,
|
|
|
|
genCharger
|
|
INTEGER,
|
|
|
|
genFuel
|
|
INTEGER,
|
|
|
|
genVBatIgnition
|
|
INTEGER,
|
|
|
|
genEnclosureTemperature
|
|
INTEGER,
|
|
|
|
genEquipmentControl
|
|
INTEGER,
|
|
|
|
genOilOption
|
|
INTEGER,
|
|
|
|
genMinorAlarmSupport
|
|
INTEGER,
|
|
|
|
genMajorAlarmSupport
|
|
INTEGER,
|
|
|
|
genOil
|
|
INTEGER,
|
|
|
|
genMinorAlarm
|
|
INTEGER,
|
|
|
|
genMajorAlarm
|
|
INTEGER,
|
|
|
|
genVendorOID
|
|
OBJECT IDENTIFIER
|
|
|
|
}
|
|
|
|
genDeviceAddress OBJECT-TYPE
|
|
SYNTAX INTEGER ( 1..15 )
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Index into the psDeviceTable.
|
|
Address of Generator on the RS-485 Path"
|
|
::= { genDeviceEntry 1 }
|
|
|
|
-- * Generator Configuration
|
|
|
|
genProtocolVersion OBJECT-TYPE
|
|
SYNTAX INTEGER ( 0..255 )
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Version of the SCTE HMS protocol implemented in the monitored
|
|
equipment. The 'Protocol Version' implementation will comply
|
|
with the defined protocol in the SCTE 25-3 (formerly HMS 022)
|
|
document with the corresponding revision number.
|
|
|
|
Example: A generator implementing all commands and responses
|
|
defined in the SCTE 25-3 revision 1.1 would return a value
|
|
of 11(decimal) in this field, reflecting major revision 1,
|
|
minor revision 1."
|
|
|
|
::= { genDeviceEntry 2 }
|
|
|
|
genSoftwareVersion OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The contents of this field are vendor specific. The intent
|
|
is to provide a text representation of the power supply or
|
|
generator system software version. Any printable ASCII
|
|
characters ca be included in this field. NULL (0x00)
|
|
characters are non-printable and are used to fill any unused
|
|
locations following the text data"
|
|
|
|
::= { genDeviceEntry 3 }
|
|
|
|
genDeviceId OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(32))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The content of this field is vendor specific. The intent is
|
|
to provide manufacturer and/or product specific ASCII text
|
|
information that will propagate to the manager's console
|
|
verbatim. The following special characters are defined in
|
|
association with this field:
|
|
|
|
'\' Used to cause a new line on the console display.
|
|
Example: 'ALPHA\XM2 9015' would appear at the monitoring
|
|
station as :
|
|
ALPHA
|
|
XM2 9015"
|
|
::= { genDeviceEntry 4 }
|
|
|
|
genGasHazardOption OBJECT-TYPE
|
|
SYNTAX INTEGER { notInstalled(1), installed(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Defines if gas hazard sensor is installed."
|
|
|
|
::= { genDeviceEntry 5 }
|
|
|
|
genWaterIntrusionOption OBJECT-TYPE
|
|
SYNTAX INTEGER { notInstalled(1), installed(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Defines if water intrusion sensor is installed."
|
|
|
|
::= { genDeviceEntry 6 }
|
|
|
|
genPadShearOption OBJECT-TYPE
|
|
SYNTAX INTEGER { notInstalled(1), installed(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Defines if pad shear sensor is installed."
|
|
|
|
::= { genDeviceEntry 7 }
|
|
|
|
genDoorOption OBJECT-TYPE
|
|
SYNTAX INTEGER { notInstalled(1), installed(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Defines if separate generator door is installed."
|
|
|
|
::= { genDeviceEntry 8 }
|
|
|
|
genChargerOption OBJECT-TYPE
|
|
SYNTAX INTEGER { notInstalled(1), installed(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Defines if charger fail signal is supported."
|
|
|
|
::= { genDeviceEntry 9 }
|
|
|
|
genFuelOption OBJECT-TYPE
|
|
SYNTAX INTEGER { notInstalled(1), installed(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Defines if low fuel detection is supported."
|
|
|
|
::= { genDeviceEntry 10 }
|
|
|
|
genVBatIgnitionOption OBJECT-TYPE
|
|
SYNTAX INTEGER { notInstalled(1), installed(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Defines if engine ignition battery voltage is monitored."
|
|
|
|
::= { genDeviceEntry 11 }
|
|
|
|
genTempOption OBJECT-TYPE
|
|
SYNTAX INTEGER { notInstalled(1), installed(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Defines if engine enclosure temperature is monitored."
|
|
|
|
::= { genDeviceEntry 12 }
|
|
|
|
-- * Generator Data
|
|
|
|
genGeneratorStatus OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), runningTest (2), running(3), fail(4) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Defines the current state of generator operation.
|
|
1 = Off
|
|
2 = Running(test)
|
|
3 = Running
|
|
4 = Fail (A condition preventing the generator
|
|
from functioning)
|
|
|
|
This item requires entries in the discrete property table."
|
|
|
|
::= { genDeviceEntry 13 }
|
|
|
|
|
|
genGasHazard OBJECT-TYPE
|
|
SYNTAX INTEGER { noAlarm(1), alarm(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The concentration of hydrocarbon fuel in the
|
|
generator enclosure has exceeded safe limits.
|
|
Generator operation is suspended. The alarm
|
|
is cleared when the sensor is reset via the
|
|
'Reset Latched Generator Alarms' command.
|
|
|
|
This item requires entries in the discrete property table."
|
|
|
|
::= { genDeviceEntry 14 }
|
|
|
|
genWaterIntrusion OBJECT-TYPE
|
|
SYNTAX INTEGER { noAlarm(1), alarm(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Water level within the generator or fuel enclosure
|
|
has exceeded safe limits for generator operation.
|
|
Generator operation is suspended while this alarm
|
|
is active. The alarm is reset when the water returns
|
|
to a safe level.
|
|
|
|
This item requires entries in the discrete property table."
|
|
|
|
::= { genDeviceEntry 15 }
|
|
|
|
genPadShear OBJECT-TYPE
|
|
SYNTAX INTEGER { noAlarm(1), alarm(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates that the generator or fuel enclosure
|
|
has shifted from its mounting position. Generator
|
|
operation is suspended. The alarm is reset when
|
|
the unit its returned to its original position.
|
|
|
|
This item requires entries in the discrete property table."
|
|
|
|
::= { genDeviceEntry 16 }
|
|
|
|
genEnclosureDoor OBJECT-TYPE
|
|
SYNTAX INTEGER { noAlarm(1), alarm(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates current status of the generator
|
|
and/or auxiliary fuel enclosure door.
|
|
|
|
This item requires entries in the discrete property table."
|
|
|
|
::= { genDeviceEntry 17 }
|
|
|
|
genCharger OBJECT-TYPE
|
|
SYNTAX INTEGER { noAlarm(1), alarm(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates if the ignition battery charger is operating.
|
|
|
|
This item requires entries in the discrete property table."
|
|
|
|
::= { genDeviceEntry 18 }
|
|
|
|
genFuel OBJECT-TYPE
|
|
SYNTAX INTEGER { noAlarm(1), alarm(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates if the engine's fuel supply is sufficient
|
|
for extended operation. Alarm is reset when fuel is
|
|
replenished.
|
|
|
|
This item requires entries in the discrete property table."
|
|
|
|
::= { genDeviceEntry 19 }
|
|
|
|
genVBatIgnition OBJECT-TYPE
|
|
SYNTAX INTEGER ( 0..65535 )
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Scaled representation of the generator's
|
|
ignition battery in 1/100 Volts.
|
|
|
|
This item requires an entry in the property table."
|
|
|
|
::= { genDeviceEntry 20 }
|
|
|
|
genEnclosureTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER ( -40..80 )
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Temperature inside generator's enclosure in degrees C.
|
|
|
|
This item requires an entry in the property table."
|
|
|
|
::= { genDeviceEntry 21 }
|
|
|
|
genEquipmentControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
stopGenerator(1),
|
|
startGenerator(2),
|
|
resetLatchedAlarms(3) }
|
|
ACCESS read-write
|
|
STATUS optional
|
|
DESCRIPTION
|
|
"When written, the appropriate corresponding command action
|
|
is sent to the generator.
|
|
|
|
1 = End generator test
|
|
2 = Start generator test
|
|
3 = Reset latched generator alarms which
|
|
may be preventing a generator start
|
|
|
|
This object is intentionally simplistic to allow for maximum
|
|
flexibility. It IS assumed that the generator has
|
|
sufficient intelligence to prevent an overcrank condition.
|
|
|
|
Example 1: From a single SET and corresponding single
|
|
'start' command, the generator may automatically attempt
|
|
starting 'n' times before giving up.
|
|
|
|
Example 2: The transponder may be simple and send only the
|
|
single 'start' command, and the EMS/end user is responsible
|
|
for making 'n' attempts (by performing additional SETs to
|
|
this object.)
|
|
|
|
The choice between the methods depends on the specific
|
|
application and vendor equipment."
|
|
|
|
::= { genDeviceEntry 22 }
|
|
|
|
genOilOption OBJECT-TYPE
|
|
SYNTAX INTEGER { notInstalled(1), installed(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Defines if oil pressure is monitored."
|
|
|
|
::= { genDeviceEntry 23 }
|
|
|
|
genMinorAlarmSupport OBJECT-TYPE
|
|
SYNTAX INTEGER { notInstalled(1), installed(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Defines if the minor alarm indicator is supported."
|
|
|
|
::= { genDeviceEntry 24 }
|
|
|
|
genMajorAlarmSupport OBJECT-TYPE
|
|
SYNTAX INTEGER { notInstalled(1), installed(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Defines if the major alarm indicator is supported."
|
|
|
|
::= { genDeviceEntry 25 }
|
|
|
|
genOil OBJECT-TYPE
|
|
SYNTAX INTEGER { noAlarm(1), alarm(2) }
|
|
ACCESS read-only
|
|
STATUS optional
|
|
DESCRIPTION
|
|
"Indicates if the engine's oil is adequate for safe operation.
|
|
Alarm is reset when the condition returns to normal.
|
|
|
|
This item requires entries in the discrete property table."
|
|
|
|
::= { genDeviceEntry 26 }
|
|
|
|
genMinorAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER { noAlarm(1), alarm(2) }
|
|
ACCESS read-only
|
|
STATUS optional
|
|
DESCRIPTION
|
|
"Indicates if the generator is indicating a minor alarm.
|
|
The generator requires attention, but does not require an immediate
|
|
visit to the generator.
|
|
|
|
This item requires entries in the discrete property table."
|
|
|
|
::= { genDeviceEntry 27 }
|
|
|
|
genMajorAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER { noAlarm(1), alarm(2) }
|
|
ACCESS read-only
|
|
STATUS optional
|
|
DESCRIPTION
|
|
"Indicates if the generator is indicating a major alarm.
|
|
The generator requires immediate attention, and should be visited
|
|
immediately to remedy the situation.
|
|
|
|
This item requires entries in the discrete property table."
|
|
|
|
::= { genDeviceEntry 28 }
|
|
|
|
genVendorOID OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
ACCESS read-only
|
|
STATUS optional
|
|
DESCRIPTION
|
|
"This object provides a means for a vendor to
|
|
point to a vendor specific extension of this MIB."
|
|
|
|
::= { genDeviceEntry 29 }
|
|
|
|
END
|
|
|