2053 lines
58 KiB
Plaintext
2053 lines
58 KiB
Plaintext
DKSF-70-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
enterprises,
|
|
MODULE-IDENTITY,
|
|
OBJECT-TYPE,
|
|
Counter32,
|
|
Integer32,
|
|
Unsigned32,
|
|
NOTIFICATION-TYPE
|
|
FROM SNMPv2-SMI
|
|
TEXTUAL-CONVENTION,
|
|
DisplayString
|
|
FROM SNMPv2-TC
|
|
snmpTraps
|
|
FROM SNMPv2-MIB ;
|
|
|
|
|
|
uniPingServerSolutionV3 MODULE-IDENTITY
|
|
|
|
LAST-UPDATED "202008190000Z"
|
|
ORGANIZATION "Alentis Electronics"
|
|
CONTACT-INFO
|
|
"developers@netping.ru"
|
|
DESCRIPTION
|
|
"Generic MIB for NetPing remote sensing and control"
|
|
|
|
REVISION "202207010000Z"
|
|
DESCRIPTION
|
|
"Renamed by Observium Developers for unify"
|
|
|
|
REVISION "202008190000Z"
|
|
DESCRIPTION
|
|
"npExtRelay branch added"
|
|
|
|
REVISION "202006120000Z"
|
|
DESCRIPTION
|
|
"npSmoke branch (.1.3.6.1.4.1.25728.8200) renamed to npInputAnalog
|
|
and repurposed for 1Wire Current Loop Adapter"
|
|
|
|
REVISION "201910130000Z"
|
|
DESCRIPTION
|
|
"npVoltage branch added"
|
|
|
|
REVISION "201807010000Z"
|
|
DESCRIPTION
|
|
"npGsm branch appended (for DKSF70.7)
|
|
npRelayMode values restricted to on, off, flip"
|
|
|
|
REVISION "201608240000Z"
|
|
DESCRIPTION
|
|
"npThermoValuePrecise added
|
|
npGsmSendSms renamed to npGsmSendSmsUtf8
|
|
npGsmSendWin1251 added"
|
|
|
|
REVISION "201507140000Z"
|
|
DESCRIPTION
|
|
"npSmoke branch added, npRelHum branch extended"
|
|
|
|
REVISION "201505290000Z"
|
|
DESCRIPTION
|
|
"npIoTrapLevelLegend added, npIrStatus values redefined"
|
|
|
|
REVISION "201412030000Z"
|
|
DESCRIPTION
|
|
"npRelayMode, npIoLevelOut values changed"
|
|
|
|
REVISION "201411260000Z"
|
|
DESCRIPTION
|
|
"npRelayN, npRelayMode, npIoLineN, npRelHumSensorStatusH, npRelHumSensorStatus values changed"
|
|
|
|
REVISION "201402020000Z"
|
|
DESCRIPTION
|
|
"npRelayMode valid values changed, (3) excluded "
|
|
|
|
REVISION "201401290000Z"
|
|
DESCRIPTION
|
|
"npCurLoop, npRelHumidity, npIr branches has added"
|
|
|
|
REVISION "201401210000Z"
|
|
DESCRIPTION
|
|
"partial rewrite for DKSF 70"
|
|
|
|
REVISION "201304110000Z"
|
|
DESCRIPTION
|
|
"partial rewrite for DKSF 48"
|
|
|
|
REVISION "201205310000Z"
|
|
DESCRIPTION
|
|
"npPwrRelayState branch was added"
|
|
|
|
REVISION "201204170000Z"
|
|
DESCRIPTION
|
|
"npReboot branch was added"
|
|
|
|
REVISION "201203230000Z"
|
|
DESCRIPTION
|
|
"Minor changes to IR module for IRC-TRv2"
|
|
|
|
REVISION "201109230000Z"
|
|
DESCRIPTION
|
|
"4 IO lines,
|
|
Identification is changed from DKSF 52.4 to DKSF 52.5"
|
|
|
|
REVISION "201103240000Z"
|
|
DESCRIPTION
|
|
"npIoPulseCounter, npIoSinglePulseDuration, npIoSinglePulseStart is added
|
|
Identification is changed from DKSF 52.3 to DKSF 52.4"
|
|
|
|
REVISION "201010140000Z"
|
|
DESCRIPTION
|
|
"IR module support"
|
|
|
|
REVISION "201009200000Z"
|
|
DESCRIPTION
|
|
"dksf 52.3 subversion"
|
|
|
|
REVISION "201005310000Z"
|
|
DESCRIPTION
|
|
"dksf 51.3 subversion"
|
|
|
|
REVISION "201004140000Z"
|
|
DESCRIPTION
|
|
"SMIv2-style rewrite"
|
|
|
|
::= { lightcom 70 }
|
|
|
|
|
|
|
|
lightcom OBJECT IDENTIFIER::={enterprises 25728 }
|
|
|
|
FixedPoint1000 ::= TEXTUAL-CONVENTION
|
|
DISPLAY-HINT "d-3"
|
|
STATUS current
|
|
DESCRIPTION "Fixed-point value as Integer, 3 decimal gigits after point (i.e. value*1000 rounded to Integer)"
|
|
SYNTAX INTEGER
|
|
|
|
npTrapInfo OBJECT IDENTIFIER::={lightcom 90}
|
|
|
|
npTrapEmailTo OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "user-specified e-mail for NetPing Trap Forwarding Service"
|
|
::={npTrapInfo 1}
|
|
|
|
|
|
npRelay OBJECT IDENTIFIER::={ lightcom 5500 }
|
|
|
|
npRelayTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF NpRelayEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Watchdog and outlet/relay control table"
|
|
::= { npRelay 5 }
|
|
|
|
npRelayEntry OBJECT-TYPE
|
|
SYNTAX NpRelayEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Relay/outlet table row"
|
|
INDEX { npRelayN }
|
|
::= { npRelayTable 1 }
|
|
|
|
NpRelayEntry ::= SEQUENCE {
|
|
npRelayN INTEGER,
|
|
npRelayMode INTEGER,
|
|
npRelayStartReset INTEGER,
|
|
npRelayMemo DisplayString,
|
|
npRelayFlip INTEGER,
|
|
npRelayState INTEGER
|
|
-- not in dksf70 npRelayPowered INTEGER
|
|
}
|
|
|
|
npRelayN OBJECT-TYPE
|
|
SYNTAX INTEGER (1..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The N of output relay"
|
|
::= { npRelayEntry 1 }
|
|
|
|
npRelayMode OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
flip(-1),
|
|
off(0),
|
|
on(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Control of relay:
|
|
-1 - flip between on(1) and off(0)
|
|
0 - switch off
|
|
1 - switch on"
|
|
::={npRelayEntry 2}
|
|
|
|
npRelayStartReset OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Write 1 to start reset (switch relay off for some time)"
|
|
::={npRelayEntry 3}
|
|
|
|
npRelayMemo OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Relay memo"
|
|
::={npRelayEntry 6}
|
|
|
|
npRelayFlip OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
flip(-1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Write -1 to flip between manual on and manual off states of relay"
|
|
::={npRelayEntry 14}
|
|
|
|
npRelayState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(0),
|
|
on(1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Actual relay state at the moment,
|
|
regardless of source of control.
|
|
0 - relay is off
|
|
1 - relay is on"
|
|
::={npRelayEntry 15}
|
|
|
|
-- npRelayPowered OBJECT-TYPE
|
|
-- SYNTAX INTEGER {
|
|
-- no(0),
|
|
-- yes(1)
|
|
-- }
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION "AC presence on output.
|
|
-- 0 - no AC dew to relay switched off or no ac on input
|
|
-- 1 - AC is present"
|
|
-- ::={npRelayEntry 16}
|
|
|
|
|
|
npRelayTrapData OBJECT IDENTIFIER::={ npRelay 3 }
|
|
|
|
npRelayTrapN OBJECT-TYPE
|
|
SYNTAX INTEGER (1..2)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The N of output relay"
|
|
::= { npRelayTrapData 1 }
|
|
|
|
npRelayTrapMode OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(0),
|
|
on(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Relay position, w/o effect of temporary switch (reset):
|
|
0 - off
|
|
1 - on"
|
|
::={npRelayTrapData 2}
|
|
|
|
npRelayTrapMemo OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Relay memo"
|
|
::={npRelayTrapData 6}
|
|
|
|
npRelayTrapState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(0),
|
|
on(1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Actual relay state at the moment,
|
|
0 - relay is off
|
|
1 - relay is on"
|
|
::={npRelayTrapData 15}
|
|
|
|
npRelayTrapCmdSrc OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown(-1),
|
|
webInterface(1),
|
|
snmp(2),
|
|
sms(3),
|
|
httpApi(4),
|
|
watchdog(5),
|
|
schedule(6),
|
|
logic(7)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Source of command to switch Relay"
|
|
::={npRelayTrapData 18}
|
|
|
|
npRelayTrapDateTime OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Textual timestamp of event"
|
|
::={npRelayTrapData 19}
|
|
|
|
npRelayTrap OBJECT IDENTIFIER::={npRelay 6}
|
|
npRelayTrapAllEvents OBJECT IDENTIFIER::={npRelayTrap 127}
|
|
|
|
npRelayTrapAllChannels NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
npRelayTrapN,
|
|
npRelayTrapMode,
|
|
npRelayTrapMemo,
|
|
npRelayTrapState,
|
|
npRelayTrapCmdSrc,
|
|
npRelayTrapDateTime
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of Humidity has changed!"
|
|
::= { npRelayTrapAllEvents 99 }
|
|
|
|
npRelayTrapOff NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
npRelayTrapN,
|
|
npRelayTrapMode,
|
|
npRelayTrapMemo,
|
|
npRelayTrapState,
|
|
npRelayTrapCmdSrc,
|
|
npRelayTrapDateTime
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Relay switched off"
|
|
::= { npRelayTrap 100 }
|
|
|
|
npRelayTrapOn NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
npRelayTrapN,
|
|
npRelayTrapMode,
|
|
npRelayTrapMemo,
|
|
npRelayTrapState,
|
|
npRelayTrapCmdSrc,
|
|
npRelayTrapDateTime
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Relay switched on"
|
|
::= { npRelayTrap 101 }
|
|
|
|
npRelayTrapModeChange NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
npRelayTrapN,
|
|
npRelayTrapMode,
|
|
npRelayTrapMemo,
|
|
npRelayTrapState,
|
|
npRelayTrapCmdSrc,
|
|
npRelayTrapDateTime
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Relay mode changed"
|
|
::= { npRelayTrap 102 }
|
|
|
|
npRelayTrapReset NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
npRelayTrapN,
|
|
npRelayTrapMode,
|
|
npRelayTrapMemo,
|
|
npRelayTrapState,
|
|
npRelayTrapCmdSrc,
|
|
npRelayTrapDateTime
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Relay reset started"
|
|
::= { npRelayTrap 103 }
|
|
|
|
|
|
|
|
|
|
npExtRelay OBJECT IDENTIFIER::={ lightcom 5600 }
|
|
|
|
npExtRelayTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF NpExtRelayEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Watchdog and outlet/relay control table"
|
|
::= { npExtRelay 5 }
|
|
|
|
npExtRelayEntry OBJECT-TYPE
|
|
SYNTAX NpExtRelayEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Relay/outlet table row"
|
|
INDEX { npExtRelayN }
|
|
::= { npExtRelayTable 1 }
|
|
|
|
NpExtRelayEntry ::= SEQUENCE {
|
|
npExtRelayN INTEGER,
|
|
npExtRelayMode INTEGER,
|
|
npExtRelayStartReset INTEGER,
|
|
npExtRelayMemo DisplayString,
|
|
npExtRelayFlip INTEGER,
|
|
npExtRelayState INTEGER
|
|
}
|
|
|
|
npExtRelayN OBJECT-TYPE
|
|
SYNTAX INTEGER (1..8)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The N of external relay"
|
|
::= { npExtRelayEntry 1 }
|
|
|
|
npExtRelayMode OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
flip(-1),
|
|
off(0),
|
|
on(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Control of relay:
|
|
-1 - flip between on(1) and off(0)
|
|
0 - switch off
|
|
1 - switch on"
|
|
::={npExtRelayEntry 2}
|
|
|
|
npExtRelayStartReset OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Write 1 to start reset (switch relay off for some time)"
|
|
::={npExtRelayEntry 3}
|
|
|
|
npExtRelayMemo OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Relay memo"
|
|
::={npExtRelayEntry 6}
|
|
|
|
npExtRelayFlip OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
flip(-1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Write -1 to flip between manual on and manual off states of relay"
|
|
::={npExtRelayEntry 14}
|
|
|
|
npExtRelayState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(0),
|
|
on(1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Actual relay state at the moment,
|
|
regardless of source of control.
|
|
0 - relay is off
|
|
1 - relay is on"
|
|
::={npExtRelayEntry 15}
|
|
|
|
|
|
npExtRelayTrapData OBJECT IDENTIFIER::={ npExtRelay 3 }
|
|
|
|
npExtRelayTrapN OBJECT-TYPE
|
|
SYNTAX INTEGER (1..8)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The N of output relay"
|
|
::= { npExtRelayTrapData 1 }
|
|
|
|
npExtRelayTrapMode OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(0),
|
|
on(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Relay position, w/o effect of temporary switch (reset):
|
|
0 - off
|
|
1 - on"
|
|
::={npExtRelayTrapData 2}
|
|
|
|
npExtRelayTrapMemo OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Relay memo"
|
|
::={npExtRelayTrapData 6}
|
|
|
|
npExtRelayTrapState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(0),
|
|
on(1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Actual relay state at the moment,
|
|
0 - relay is off
|
|
1 - relay is on"
|
|
::={npExtRelayTrapData 15}
|
|
|
|
npExtRelayTrapCmdSrc OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown(-1),
|
|
webInterface(1),
|
|
snmp(2),
|
|
sms(3),
|
|
httpApi(4),
|
|
watchdog(5),
|
|
schedule(6),
|
|
logic(7),
|
|
button(8)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Source of command to switch Relay"
|
|
::={npExtRelayTrapData 18}
|
|
|
|
npExtRelayTrapDateTime OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Textual timestamp of event"
|
|
::={npExtRelayTrapData 19}
|
|
|
|
npExtRelayTrap OBJECT IDENTIFIER::={npExtRelay 6}
|
|
npExtRelayTrapAllEvents OBJECT IDENTIFIER::={npExtRelayTrap 127}
|
|
|
|
npExtRelayTrapAllChannels NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
npExtRelayTrapN,
|
|
npExtRelayTrapMode,
|
|
npExtRelayTrapMemo,
|
|
npExtRelayTrapState,
|
|
npExtRelayTrapCmdSrc,
|
|
npExtRelayTrapDateTime
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of Humidity has changed!"
|
|
::= { npExtRelayTrapAllEvents 99 }
|
|
|
|
npExtRelayTrapOff NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
npExtRelayTrapN,
|
|
npExtRelayTrapMode,
|
|
npExtRelayTrapMemo,
|
|
npExtRelayTrapState,
|
|
npExtRelayTrapCmdSrc,
|
|
npExtRelayTrapDateTime
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Relay switched off"
|
|
::= { npExtRelayTrap 100 }
|
|
|
|
npExtRelayTrapOn NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
npExtRelayTrapN,
|
|
npExtRelayTrapMode,
|
|
npExtRelayTrapMemo,
|
|
npExtRelayTrapState,
|
|
npExtRelayTrapCmdSrc,
|
|
npExtRelayTrapDateTime
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Relay switched on"
|
|
::= { npExtRelayTrap 101 }
|
|
|
|
npExtRelayTrapModeChange NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
npExtRelayTrapN,
|
|
npExtRelayTrapMode,
|
|
npExtRelayTrapMemo,
|
|
npExtRelayTrapState,
|
|
npExtRelayTrapCmdSrc,
|
|
npExtRelayTrapDateTime
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Relay mode changed"
|
|
::= { npExtRelayTrap 102 }
|
|
|
|
npExtRelayTrapReset NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
npExtRelayTrapN,
|
|
npExtRelayTrapMode,
|
|
npExtRelayTrapMemo,
|
|
npExtRelayTrapState,
|
|
npExtRelayTrapCmdSrc,
|
|
npExtRelayTrapDateTime
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Relay reset started"
|
|
::= { npExtRelayTrap 103 }
|
|
|
|
|
|
npThermo OBJECT IDENTIFIER::={lightcom 8800}
|
|
|
|
npThermoTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF NpThermoEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Thermo Sensors Table"
|
|
::= { npThermo 1 }
|
|
|
|
npThermoEntry OBJECT-TYPE
|
|
SYNTAX NpThermoEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Thermo Sensors Table Row"
|
|
INDEX { npThermoSensorN }
|
|
::= { npThermoTable 1 }
|
|
|
|
NpThermoEntry ::= SEQUENCE {
|
|
npThermoSensorN INTEGER,
|
|
npThermoValue INTEGER,
|
|
npThermoStatus INTEGER,
|
|
npThermoLow INTEGER,
|
|
npThermoHigh INTEGER,
|
|
npThermoMemo DisplayString,
|
|
npThermoValuePrecise FixedPoint1000
|
|
}
|
|
|
|
npThermoSensorN OBJECT-TYPE
|
|
SYNTAX INTEGER (1..8)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The id of temperature sensor, 1 to 8"
|
|
::= { npThermoEntry 1 }
|
|
|
|
npThermoValue OBJECT-TYPE
|
|
SYNTAX INTEGER (-60..280)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Temperature, deg.C"
|
|
::= { npThermoEntry 2 }
|
|
|
|
npThermoStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
failed(0),
|
|
low(1),
|
|
norm(2),
|
|
high(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Temperature status (0=fault, 1=underheat, 2=normal, 3=overheat)"
|
|
::= { npThermoEntry 3 }
|
|
|
|
npThermoLow OBJECT-TYPE
|
|
SYNTAX INTEGER (-60..280)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Bottom margin of normal temperature range, deg.C"
|
|
::= { npThermoEntry 4 }
|
|
|
|
npThermoHigh OBJECT-TYPE
|
|
SYNTAX INTEGER (-60..280)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Top margin of normal temperature range, deg.C"
|
|
::= { npThermoEntry 5 }
|
|
|
|
npThermoMemo OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "T channel memo"
|
|
::= { npThermoEntry 6 }
|
|
|
|
npThermoValuePrecise OBJECT-TYPE
|
|
SYNTAX FixedPoint1000
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Temperature, deg.C, with fractional part 3 digits after point"
|
|
::= { npThermoEntry 7 }
|
|
|
|
npThermoTraps OBJECT IDENTIFIER::={npThermo 2}
|
|
npThermoTrapPrefix OBJECT IDENTIFIER::={npThermoTraps 0}
|
|
|
|
npThermoTrapSensorN OBJECT-TYPE
|
|
SYNTAX INTEGER (1..8)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The id of temperature sensor, 1 to 8"
|
|
::= { npThermoTraps 1 }
|
|
|
|
npThermoTrapValue OBJECT-TYPE
|
|
SYNTAX INTEGER (-60..280)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Temperature, deg.C"
|
|
::= { npThermoTraps 2 }
|
|
|
|
npThermoTrapStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
failed(0),
|
|
low(1),
|
|
norm(2),
|
|
high(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Temperature status (0=fault, 1=underheat, 2=normal, 3=overheat)"
|
|
::= { npThermoTraps 3 }
|
|
|
|
npThermoTrapLow OBJECT-TYPE
|
|
SYNTAX INTEGER (-60..280)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Bottom margin of normal temperature range, deg.C"
|
|
::= { npThermoTraps 4 }
|
|
|
|
npThermoTrapHigh OBJECT-TYPE
|
|
SYNTAX INTEGER (-60..280)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Top margin of normal temperature range, deg.C"
|
|
::= { npThermoTraps 5 }
|
|
|
|
npThermoTrapMemo OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "T channel memo"
|
|
::= { npThermoTraps 6 }
|
|
|
|
npThermoTrap NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
npThermoTrapSensorN,
|
|
npThermoTrapValue,
|
|
npThermoTrapStatus,
|
|
npThermoTrapLow,
|
|
npThermoTrapHigh,
|
|
npThermoTrapMemo
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of Thermo sensor is changed (crossing of normal temp. range)"
|
|
::= { npThermoTrapPrefix 1 }
|
|
|
|
|
|
|
|
npIo OBJECT IDENTIFIER::={lightcom 8900}
|
|
|
|
npIoTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF NpIoEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Digital Input/output Table"
|
|
::= { npIo 1 }
|
|
|
|
npIoEntry OBJECT-TYPE
|
|
SYNTAX NpIoEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Digital Input/output Table Row"
|
|
INDEX { npIoLineN }
|
|
::= { npIoTable 1 }
|
|
|
|
NpIoEntry ::= SEQUENCE {
|
|
npIoLineN INTEGER,
|
|
npIoLevelIn INTEGER,
|
|
npIoLevelOut INTEGER,
|
|
npIoMemo DisplayString,
|
|
npIoPulseCounter Counter32,
|
|
npIoSinglePulseDuration INTEGER,
|
|
npIoSinglePulseStart INTEGER
|
|
}
|
|
|
|
npIoLineN OBJECT-TYPE
|
|
SYNTAX INTEGER (1..8)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of IO line, from 1 to max supported"
|
|
::= { npIoEntry 1 }
|
|
|
|
npIoLevelIn OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Input level, 0 or 1"
|
|
::= { npIoEntry 2 }
|
|
|
|
npIoLevelOut OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
flip(-1),
|
|
low(0),
|
|
high(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Output level, 0 or 1.
|
|
Write -1 to flip output."
|
|
::= { npIoEntry 3 }
|
|
|
|
npIoMemo OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "IO line memo"
|
|
::= { npIoEntry 6 }
|
|
|
|
npIoPulseCounter OBJECT-TYPE
|
|
SYNTAX Counter32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Pulse Counter on IO input line (counts positive fronts)
|
|
Write 0 to reset."
|
|
::= { npIoEntry 9 }
|
|
|
|
npIoSinglePulseDuration OBJECT-TYPE
|
|
SYNTAX INTEGER (100..25500)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Set duration of single pulse on IO output line,
|
|
100ms to 25500ms, min. step is 100ms"
|
|
::= { npIoEntry 12 }
|
|
|
|
npIoSinglePulseStart OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Write 1 to start single pulse on IO output.
|
|
Output will be inverted for time, specified by npIoSinglePulseDuration"
|
|
::= { npIoEntry 13 }
|
|
|
|
npIoTraps OBJECT IDENTIFIER::={npIo 2}
|
|
npIoTrapPrefix OBJECT IDENTIFIER::={npIoTraps 0}
|
|
|
|
npIoTrapLineN OBJECT-TYPE
|
|
SYNTAX INTEGER (1..2)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Trap data, Number of IO line"
|
|
::= { npIoTraps 1 }
|
|
|
|
npIoTrapLevelIn OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Trap data, new Input level, 0 or 1"
|
|
::= { npIoTraps 2 }
|
|
|
|
npIoTrapMemo OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Trap data, IO line memo"
|
|
::= { npIoTraps 6 }
|
|
|
|
npIoTrapLevelLegend OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Legend for current logic level on the IO line"
|
|
::= { npIoTraps 7 }
|
|
|
|
npIoTrap NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
npIoTrapLineN,
|
|
npIoTrapLevelIn,
|
|
npIoTrapMemo,
|
|
npIoTrapLevelLegend
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Input state of IO line is changed"
|
|
::= { npIoTrapPrefix 1 }
|
|
|
|
|
|
|
|
npCurLoop OBJECT IDENTIFIER::={lightcom 8300}
|
|
|
|
npCurLoopTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF NpCurLoopEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Current loop sensors Table"
|
|
::= { npCurLoop 1 }
|
|
|
|
npCurLoopEntry OBJECT-TYPE
|
|
SYNTAX NpCurLoopEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Current loop sensors Table Row"
|
|
INDEX { npCurLoopN }
|
|
::= { npCurLoopTable 1 }
|
|
|
|
NpCurLoopEntry ::= SEQUENCE {
|
|
npCurLoopN INTEGER,
|
|
npCurLoopStatus INTEGER,
|
|
npCurLoopI INTEGER,
|
|
npCurLoopV INTEGER,
|
|
npCurLoopR INTEGER,
|
|
npCurLoopPower INTEGER
|
|
}
|
|
|
|
npCurLoopN OBJECT-TYPE
|
|
SYNTAX INTEGER (1..8)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Index of current loop, 1 to max supported"
|
|
::= { npCurLoopEntry 1 }
|
|
|
|
npCurLoopStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
ok(0),
|
|
alert(1),
|
|
cut(2),
|
|
short(3),
|
|
notPowered(4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Status of the loop
|
|
0=Normal, 1=Alert, 2=Cut, 3=Short, 4=Not Powered"
|
|
::= { npCurLoopEntry 2 }
|
|
|
|
npCurLoopI OBJECT-TYPE
|
|
SYNTAX INTEGER (0..99999)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Loop current, mA"
|
|
::= { npCurLoopEntry 3 }
|
|
|
|
npCurLoopV OBJECT-TYPE
|
|
SYNTAX INTEGER (0..99999)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Voltage drop on the loop, mV"
|
|
::= { npCurLoopEntry 4 }
|
|
|
|
npCurLoopR OBJECT-TYPE
|
|
SYNTAX INTEGER (0..99999)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Resistance of the loop, Ohm"
|
|
::= { npCurLoopEntry 5 }
|
|
|
|
npCurLoopPower OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(0),
|
|
on(1),
|
|
cyclePower(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Control of loop power
|
|
0=Off, 1=On, 2=reset by off/on power"
|
|
::= { npCurLoopEntry 7 }
|
|
|
|
npCurLoopTraps OBJECT IDENTIFIER::={npCurLoop 2}
|
|
npCurLoopTrapPrefix OBJECT IDENTIFIER::={npCurLoopTraps 0}
|
|
|
|
npCurLoopTrapN OBJECT-TYPE
|
|
SYNTAX INTEGER (1..8)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Index of current loop, which status has changed"
|
|
::= { npCurLoopTraps 1 }
|
|
|
|
npCurLoopTrapStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
ok(0),
|
|
alert(1),
|
|
cut(2),
|
|
short(3),
|
|
notPowered(4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Status of the loop
|
|
0=Normal, 1=Alert, 2=Cut, 3=Short, 4=Not Powered"
|
|
::= { npCurLoopTraps 2 }
|
|
|
|
npCurLoopTrapI OBJECT-TYPE
|
|
SYNTAX INTEGER (0..99999)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Loop current, mA"
|
|
::= { npCurLoopTraps 3 }
|
|
|
|
npCurLoopTrapV OBJECT-TYPE
|
|
SYNTAX INTEGER (0..99999)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Voltage drop on the loop, mV"
|
|
::= { npCurLoopTraps 4 }
|
|
|
|
npCurLoopTrapR OBJECT-TYPE
|
|
SYNTAX INTEGER (0..99999)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Resistance of the loop, Ohm"
|
|
::= { npCurLoopTraps 5 }
|
|
|
|
npCurLoopTrapPower OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(0),
|
|
on(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Status of loop power
|
|
0=Off, 1=On"
|
|
::= { npCurLoopTraps 7 }
|
|
|
|
npCurLoopTrap NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
npCurLoopTrapN,
|
|
npCurLoopTrapStatus,
|
|
npCurLoopTrapI,
|
|
npCurLoopTrapV,
|
|
npCurLoopTrapR,
|
|
npCurLoopTrapPower,
|
|
npTrapEmailTo
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of current loop N has changed!"
|
|
::= { npCurLoopTrapPrefix 1 }
|
|
|
|
|
|
|
|
npVoltage OBJECT IDENTIFIER::={lightcom 9000}
|
|
|
|
npVoltageTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF NpVoltageEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Voltage Monitoring Sensors Table"
|
|
::= { npVoltage 1 }
|
|
|
|
npVoltageEntry OBJECT-TYPE
|
|
SYNTAX NpVoltageEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Voltage Monitoring Sensors Table Row"
|
|
INDEX { npVoltageN }
|
|
::= { npVoltageTable 1 }
|
|
|
|
NpVoltageEntry ::= SEQUENCE {
|
|
npVoltageN INTEGER,
|
|
npVoltageRMS INTEGER,
|
|
npVoltageStatus INTEGER,
|
|
npVoltageFreq INTEGER,
|
|
npVoltageFreqStatus INTEGER,
|
|
npVoltageMemo DisplayString,
|
|
npVoltageSagCounter Counter32,
|
|
npVoltageSagStatus INTEGER,
|
|
npVoltageSagSmallThreshold INTEGER,
|
|
npVoltageSagMediumThreshold INTEGER,
|
|
npVoltageSagBigThreshold INTEGER,
|
|
npVoltageStandard INTEGER,
|
|
npVoltagePeak INTEGER,
|
|
npVoltagePeakStatus INTEGER
|
|
}
|
|
|
|
npVoltageN OBJECT-TYPE
|
|
SYNTAX INTEGER (1..3)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The ID of Voltage Monitoring sensor, 1 to 3"
|
|
::= { npVoltageEntry 1 }
|
|
|
|
npVoltageRMS OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Voltage value, V"
|
|
::= { npVoltageEntry 2 }
|
|
|
|
npVoltageStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
sensorFailed(0),
|
|
noVoltage(1),
|
|
bad(2),
|
|
warn(3),
|
|
good(4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Status of voltage"
|
|
::= { npVoltageEntry 3 }
|
|
|
|
npVoltageFreq OBJECT-TYPE
|
|
SYNTAX INTEGER (0..10000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Frequency value in units of .01 Hz"
|
|
::= { npVoltageEntry 4 }
|
|
|
|
npVoltageFreqStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
sensorFailed(0),
|
|
noVoltage(1),
|
|
bad(2),
|
|
warn(3),
|
|
good(4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Status of frequency"
|
|
::= { npVoltageEntry 5 }
|
|
|
|
npVoltageMemo OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Voltage Monitoring sensor memo"
|
|
::= { npVoltageEntry 6 }
|
|
|
|
npVoltageSagCounter OBJECT-TYPE
|
|
SYNTAX Counter32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Counter of voltage sags"
|
|
::= { npVoltageEntry 10 }
|
|
|
|
npVoltageSagStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
sensorFailed(0),
|
|
noVoltage(1),
|
|
high(2),
|
|
medium(3),
|
|
small(4),
|
|
noSags(5)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Status of voltage sag"
|
|
::= { npVoltageEntry 11 }
|
|
|
|
npVoltageSagSmallThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER (0..100)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The margin between No Sags and Small Sags, % of Nominal Voltage
|
|
Usually 90%"
|
|
::= { npVoltageEntry 12 }
|
|
|
|
npVoltageSagMediumThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER (0..100)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The margin between Small Sags and Medium Sags, % of Nominal Voltage
|
|
Usually 70%"
|
|
::= { npVoltageEntry 13 }
|
|
|
|
npVoltageSagBigThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER (0..100)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The margin between Medium Sags and Big Sags, % of Nominal Voltage
|
|
Usually 50%"
|
|
::= { npVoltageEntry 14 }
|
|
|
|
npVoltageStandard OBJECT-TYPE
|
|
SYNTAX INTEGER (100..240)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Nominal voltage, V"
|
|
::= { npVoltageEntry 20 }
|
|
|
|
npVoltagePeak OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Peak voltage, V"
|
|
::= { npVoltageEntry 30 }
|
|
|
|
npVoltagePeakStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
sensorFailed(0),
|
|
noVoltage(1),
|
|
dangerous(2),
|
|
noPeaks(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Status of peak voltage"
|
|
::= { npVoltageEntry 31 }
|
|
|
|
npVoltageTraps OBJECT IDENTIFIER::={npVoltage 2}
|
|
npVoltageTrapPrefix OBJECT IDENTIFIER::={npVoltageTraps 0}
|
|
|
|
npVoltageTrapN OBJECT-TYPE
|
|
SYNTAX INTEGER (1..3)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The ID of Voltage Monitoring sensor, 1 to 3"
|
|
::= { npVoltageTraps 1 }
|
|
|
|
npVoltageTrapRMS OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Voltage value, V"
|
|
::= { npVoltageTraps 2 }
|
|
|
|
npVoltageTrapStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
sensorFailed(0),
|
|
noVoltage(1),
|
|
bad(2),
|
|
warn(3),
|
|
good(4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Status of voltage"
|
|
::= { npVoltageTraps 3 }
|
|
|
|
npVoltageTrapFreq OBJECT-TYPE
|
|
SYNTAX INTEGER (0..10000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Frequency value in units of .01 Hz"
|
|
::= { npVoltageTraps 4 }
|
|
|
|
npVoltageTrapFreqStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
sensorFailed(0),
|
|
noVoltage(1),
|
|
bad(2),
|
|
warn(3),
|
|
good(4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Status of frequency"
|
|
::= { npVoltageTraps 5 }
|
|
|
|
npVoltageTrapMemo OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Voltage Monitoring sensor memo"
|
|
::= { npVoltageTraps 6 }
|
|
|
|
npVoltageTrapSagCounter OBJECT-TYPE
|
|
SYNTAX Counter32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Counter of voltage sags"
|
|
::= { npVoltageTraps 10 }
|
|
|
|
npVoltageTrapSagStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
sensorFailed(0),
|
|
noVoltage(1),
|
|
high(2),
|
|
medium(3),
|
|
small(4),
|
|
noSags(5)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Status of voltage sag"
|
|
::= { npVoltageTraps 11 }
|
|
|
|
npVoltageTrapPeak OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Peak voltage, V"
|
|
::= { npVoltageTraps 30 }
|
|
|
|
npVoltageTrapPeakStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
sensorFailed(0),
|
|
noVoltage(1),
|
|
dangerous(2),
|
|
noPeaks(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Status of peak voltage"
|
|
::= { npVoltageTraps 31 }
|
|
|
|
npVoltageTrap NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
npVoltageTrapN,
|
|
npVoltageTrapRMS,
|
|
npVoltageTrapStatus,
|
|
npVoltageTrapFreq,
|
|
npVoltageTrapFreqStatus,
|
|
npVoltageTrapMemo,
|
|
npVoltageTrapSagCounter,
|
|
npVoltageTrapSagStatus,
|
|
npVoltageTrapPeakStatus
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of Voltage Monitoring sensor is changed"
|
|
::= { npVoltageTrapPrefix 1 }
|
|
|
|
|
|
|
|
npInputAnalog OBJECT IDENTIFIER::={lightcom 8200}
|
|
|
|
npInputAnalogTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF NpInputAnalogEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "1Wire Current Loop Adapters Table"
|
|
::= { npInputAnalog 1 }
|
|
|
|
npInputAnalogEntry OBJECT-TYPE
|
|
SYNTAX NpInputAnalogEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "1Wire Current Loop Adapters Table Row"
|
|
INDEX { npInputAnalogSensorN }
|
|
::= { npInputAnalogTable 1 }
|
|
|
|
NpInputAnalogEntry ::= SEQUENCE {
|
|
npInputAnalogSensorN INTEGER,
|
|
npInputAnalogStatus INTEGER,
|
|
npInputAnalogCurrent Integer32,
|
|
npInputAnalogVoltage Integer32,
|
|
npInputAnalogResistance Unsigned32,
|
|
npInputAnalogMemo DisplayString,
|
|
npInputAnalogPower INTEGER,
|
|
npInputAnalogReset INTEGER,
|
|
npInputAnalogWorkRangeHigh Integer32,
|
|
npInputAnalogSafeRangeHigh Integer32,
|
|
npInputAnalogSafeRangeLow Integer32,
|
|
npInputAnalogWorkRangeLow Integer32
|
|
}
|
|
|
|
npInputAnalogSensorN OBJECT-TYPE
|
|
SYNTAX INTEGER (1..4)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The id of 1Wire Current Loop Adapter, 1 to 4"
|
|
::= { npInputAnalogEntry 1 }
|
|
|
|
npInputAnalogStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
failure1w(0),
|
|
belowSafe(1),
|
|
safe(2),
|
|
aboveSafe(3),
|
|
failureAnalog(5)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Status of Current Loop Signal,
|
|
failure1w = no reply from the adapter on 1wire bus,
|
|
failureAnalog = signal is beyond it's Working Range,
|
|
belowSafe, safe, aboveSafe - status of the signal
|
|
relative to the Safe Range margins"
|
|
::= { npInputAnalogEntry 2 }
|
|
|
|
npInputAnalogCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Current via RS_P, RS_N contacts of Current Loop
|
|
Adapter, uA (microamperes)"
|
|
::= { npInputAnalogEntry 3 }
|
|
|
|
npInputAnalogVoltage OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Voltage on RS_P contact of Current Loop
|
|
Adapter Vs Ground, mV"
|
|
::= { npInputAnalogEntry 4 }
|
|
|
|
npInputAnalogResistance OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Resistance of the Current Loop, Ohm"
|
|
::= { npInputAnalogEntry 5 }
|
|
|
|
npInputAnalogMemo OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Current Loop memo, what's connected"
|
|
::= { npInputAnalogEntry 6 }
|
|
|
|
npInputAnalogPower OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(0),
|
|
on(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Controls power on Current Loop Adapter outputs +24V, +12V"
|
|
::= { npInputAnalogEntry 7 }
|
|
|
|
npInputAnalogReset OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Write duration 1..25s to temporary switch off
|
|
+12V, +24V outputs to reset sensor on the
|
|
current loop by cycling it's power"
|
|
::= { npInputAnalogEntry 8 }
|
|
|
|
npInputAnalogWorkRangeHigh OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Top marging of Working Range, uA or mV or Ohm.
|
|
If monitored value is outide of Working Range, Analog Failure take place.
|
|
If not specified, value is -32768"
|
|
::= { npInputAnalogEntry 11 }
|
|
|
|
npInputAnalogSafeRangeHigh OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Top marging of Safe Range, uA or mV or Ohm.
|
|
If not specified, value is -32768"
|
|
::= { npInputAnalogEntry 12 }
|
|
|
|
npInputAnalogSafeRangeLow OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Bottom marging of Safe Range, uA or mV or Ohm.
|
|
If not specified, value is -32768"
|
|
::= { npInputAnalogEntry 13 }
|
|
|
|
npInputAnalogWorkRangeLow OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Bottom marging of Working Range, uA or mV or Ohm.
|
|
If monitored value is outide of Working Range, Analog Failure take place.
|
|
If not specified, value is -32768"
|
|
::= { npInputAnalogEntry 14 }
|
|
|
|
|
|
npInputAnalogTraps OBJECT IDENTIFIER::={npInputAnalog 2}
|
|
npInputAnalogTrapPrefix OBJECT IDENTIFIER::={npInputAnalogTraps 0}
|
|
|
|
npInputAnalogTrapSensorN OBJECT-TYPE
|
|
SYNTAX INTEGER (1..4)
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION "The id of 1Wire Current Loop Adapter, 1 to 4"
|
|
::= { npInputAnalogTraps 1 }
|
|
|
|
npInputAnalogTrapStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
failure1w(0),
|
|
belowSafe(1),
|
|
safe(2),
|
|
aboveSafe(3),
|
|
failureAnalog(5)
|
|
}
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION "New status of Current Loop Signal,
|
|
failure1w = no reply from the adapter on 1wire bus,
|
|
failureAnalog = signal is beyond it's Working Range,
|
|
belowSafe, safe, aboveSafe - status of the signal
|
|
relative to the Safe Range margins"
|
|
::= { npInputAnalogTraps 2 }
|
|
|
|
npInputAnalogTrapCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION "Current via RS_P, RS_N contacts of Current Loop
|
|
Adapter, uA (microamperes)"
|
|
::= { npInputAnalogTraps 3 }
|
|
|
|
npInputAnalogTrapVoltage OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION "Voltage on RS_P contact of Current Loop
|
|
Adapter Vs Ground, mV"
|
|
::= { npInputAnalogTraps 4 }
|
|
|
|
npInputAnalogTrapResistance OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION "Resistance of the Current Loop, Ohm"
|
|
::= { npInputAnalogTraps 5 }
|
|
|
|
npInputAnalogTrapMemo OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION "Current Loop memo"
|
|
::= { npInputAnalogTraps 6 }
|
|
|
|
npInputAnalogTrapPower OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(0),
|
|
on(1),
|
|
temporaryOff(3)
|
|
}
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION "Status of power outputs +12V, +24V,
|
|
temporary switching off for reset ignored"
|
|
::= { npInputAnalogTraps 7 }
|
|
|
|
npInputAnalogTrapWorkRangeHigh OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION "Top marging of Working Range, uA or mV or Ohm.
|
|
If monitored value is outide of Working Range, Analog Failure take place.
|
|
If not specified, value is -32768"
|
|
::= { npInputAnalogTraps 11 }
|
|
|
|
npInputAnalogTrapSafeRangeHigh OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION "Top marging of Safe Range, uA or mV or Ohm.
|
|
If not specified, value is -32768"
|
|
::= { npInputAnalogTraps 12 }
|
|
|
|
npInputAnalogTrapSafeRangeLow OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION "Bottom marging of Safe Range, uA or mV or Ohm.
|
|
If not specified, value is -32768"
|
|
::= { npInputAnalogTraps 13 }
|
|
|
|
npInputAnalogTrapWorkRangeLow OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION "Bottom marging of Working Range, uA or mV or Ohm.
|
|
If monitored value is outide of Working Range, Analog Failure take place.
|
|
If not specified, value is -32768"
|
|
::= { npInputAnalogTraps 14 }
|
|
|
|
npInputAnalogTrap NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
npInputAnalogTrapSensorN,
|
|
npInputAnalogTrapStatus,
|
|
npInputAnalogTrapCurrent,
|
|
npInputAnalogTrapVoltage,
|
|
npInputAnalogTrapResistance,
|
|
npInputAnalogTrapMemo,
|
|
npInputAnalogTrapPower,
|
|
npInputAnalogTrapWorkRangeHigh,
|
|
npInputAnalogTrapSafeRangeHigh,
|
|
npInputAnalogTrapSafeRangeLow,
|
|
npInputAnalogTrapWorkRangeLow
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of 1W Analog Input Adapter has changed"
|
|
::= { npInputAnalogTrapPrefix 1 }
|
|
|
|
|
|
|
|
npRelHumidity OBJECT IDENTIFIER::={lightcom 8400}
|
|
|
|
npRelHumTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF NpRelHumEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Humidity+Temperature Sensors Table"
|
|
::= { npRelHumidity 1 }
|
|
|
|
npRelHumEntry OBJECT-TYPE
|
|
SYNTAX NpRelHumEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Humidity+Temperature Sensors Table Row"
|
|
INDEX { npRelHumN }
|
|
::= { npRelHumTable 1 }
|
|
|
|
NpRelHumEntry ::= SEQUENCE {
|
|
npRelHumN INTEGER,
|
|
npRelHumValue INTEGER,
|
|
npRelHumStatus INTEGER,
|
|
npRelHumTempValue INTEGER,
|
|
npRelHumTempStatus INTEGER,
|
|
npRelHumMemo DisplayString,
|
|
npRelHumSafeRangeHigh INTEGER,
|
|
npRelHumSafeRangeLow INTEGER,
|
|
npRelHumTempSafeRangeHigh INTEGER,
|
|
npRelHumTempSafeRangeLow INTEGER
|
|
}
|
|
|
|
npRelHumN OBJECT-TYPE
|
|
SYNTAX INTEGER (1..4)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Index of Humidity+Temperature sensor, 1 to max supported"
|
|
::= { npRelHumEntry 1 }
|
|
|
|
npRelHumValue OBJECT-TYPE
|
|
SYNTAX INTEGER (0..100)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Relative humidity value, %"
|
|
::= { npRelHumEntry 2 }
|
|
|
|
npRelHumStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
sensorFailed(0),
|
|
belowSafeRange(1),
|
|
inSafeRange(2),
|
|
aboveSafeRange(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Status of Relative Humiduty"
|
|
::= { npRelHumEntry 3 }
|
|
|
|
npRelHumTempValue OBJECT-TYPE
|
|
SYNTAX INTEGER (-60..200)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Sensor temperature, deg.C"
|
|
::= { npRelHumEntry 4 }
|
|
|
|
npRelHumTempStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
sensorFailed(0),
|
|
belowSafeRange(1),
|
|
inSafeRange(2),
|
|
aboveSafeRange(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Status of Relative Humiduty"
|
|
::= { npRelHumEntry 5 }
|
|
|
|
npRelHumMemo OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Sensor Memo/Location"
|
|
::= { npRelHumEntry 6 }
|
|
|
|
npRelHumSafeRangeHigh OBJECT-TYPE
|
|
SYNTAX INTEGER (0..100)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Relative Humidity safe range, top margin, %RH"
|
|
::= { npRelHumEntry 7 }
|
|
|
|
npRelHumSafeRangeLow OBJECT-TYPE
|
|
SYNTAX INTEGER (0..100)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Relative Humidity safe range, bottom margin, %RH"
|
|
::= { npRelHumEntry 8 }
|
|
|
|
npRelHumTempSafeRangeHigh OBJECT-TYPE
|
|
SYNTAX INTEGER (-55..150)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Temperature safe range, top margin, deg.C"
|
|
::= { npRelHumEntry 9 }
|
|
|
|
npRelHumTempSafeRangeLow OBJECT-TYPE
|
|
SYNTAX INTEGER (-55..150)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Temperature safe range, bottom margin, deg.C"
|
|
::= { npRelHumEntry 10 }
|
|
|
|
npRelHumTrapData OBJECT IDENTIFIER::={npRelHumidity 3}
|
|
|
|
npRelHumTrapDataN OBJECT-TYPE
|
|
SYNTAX INTEGER (1..4)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Index of Humidity+Temperature sensor, 1 to max supported"
|
|
::= { npRelHumTrapData 1 }
|
|
|
|
npRelHumTrapDataValue OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Sensor humidity, %RH, or temperature, deg.C"
|
|
::= { npRelHumTrapData 2 }
|
|
|
|
npRelHumTrapDataStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
sensorFailed(0),
|
|
belowSafeRange(1),
|
|
inSafeRange(2),
|
|
aboveSafeRange(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Status of humidity or temperature"
|
|
::= { npRelHumTrapData 4 }
|
|
|
|
npRelHumTrapDataMemo OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Sensor Memo/Location"
|
|
::= { npRelHumTrapData 6 }
|
|
|
|
npRelHumTrapDataSafeRangeHigh OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Relative Humidity safe range, top margin, %RH or deg.C"
|
|
::= { npRelHumTrapData 7 }
|
|
|
|
npRelHumTrapDataSafeRangeLow OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Relative Humidity safe range, bottom margin, %RH or deg.C"
|
|
::= { npRelHumTrapData 8 }
|
|
|
|
npRelHumTrap OBJECT IDENTIFIER::={npRelHumidity 6}
|
|
npRelHumTrapAllEvents OBJECT IDENTIFIER::={npRelHumTrap 127}
|
|
npRelHumTrapTemp OBJECT IDENTIFIER::={npRelHumidity 7}
|
|
npRelHumTrapTempAllEvents OBJECT IDENTIFIER::={npRelHumTrapTemp 127}
|
|
|
|
npRelHumTrapAllChannels NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
npRelHumTrapDataN,
|
|
npRelHumTrapDataStatus,
|
|
npRelHumTrapDataValue,
|
|
npRelHumTrapDataMemo,
|
|
npRelHumTrapDataSafeRangeHigh,
|
|
npRelHumTrapDataSafeRangeLow
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of Humidity has changed!"
|
|
::= { npRelHumTrapAllEvents 99 }
|
|
|
|
npRelHumTrapAboveSafe NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
npRelHumTrapDataN,
|
|
npRelHumTrapDataStatus,
|
|
npRelHumTrapDataValue,
|
|
npRelHumTrapDataMemo,
|
|
npRelHumTrapDataSafeRangeHigh,
|
|
npRelHumTrapDataSafeRangeLow
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Humidity above the Safe range"
|
|
::= { npRelHumTrap 103 }
|
|
|
|
npRelHumTrapSafe NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
npRelHumTrapDataN,
|
|
npRelHumTrapDataStatus,
|
|
npRelHumTrapDataValue,
|
|
npRelHumTrapDataMemo,
|
|
npRelHumTrapDataSafeRangeHigh,
|
|
npRelHumTrapDataSafeRangeLow
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Humidity in the Safe range"
|
|
::= { npRelHumTrap 102 }
|
|
|
|
npRelHumTrapBelowSafe NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
npRelHumTrapDataN,
|
|
npRelHumTrapDataStatus,
|
|
npRelHumTrapDataValue,
|
|
npRelHumTrapDataMemo,
|
|
npRelHumTrapDataSafeRangeHigh,
|
|
npRelHumTrapDataSafeRangeLow
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Humidity below the Safe range"
|
|
::= { npRelHumTrap 101 }
|
|
|
|
npRelHumTrapFail NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
npRelHumTrapDataN,
|
|
npRelHumTrapDataStatus,
|
|
npRelHumTrapDataValue,
|
|
npRelHumTrapDataMemo,
|
|
npRelHumTrapDataSafeRangeHigh,
|
|
npRelHumTrapDataSafeRangeLow
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rel.Humidity sensor failed!"
|
|
::= { npRelHumTrap 100 }
|
|
|
|
npRelHumTrapTempAllChannels NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
npRelHumTrapDataN,
|
|
npRelHumTrapDataStatus,
|
|
npRelHumTrapDataValue,
|
|
npRelHumTrapDataMemo,
|
|
npRelHumTrapDataSafeRangeHigh,
|
|
npRelHumTrapDataSafeRangeLow
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of Temperature has changed!"
|
|
::= { npRelHumTrapTempAllEvents 99 }
|
|
|
|
npRelHumTrapTempAboveSafe NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
npRelHumTrapDataN,
|
|
npRelHumTrapDataStatus,
|
|
npRelHumTrapDataValue,
|
|
npRelHumTrapDataMemo,
|
|
npRelHumTrapDataSafeRangeHigh,
|
|
npRelHumTrapDataSafeRangeLow
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature above the Safe range"
|
|
::= { npRelHumTrapTemp 103 }
|
|
|
|
npRelHumTrapTempSafe NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
npRelHumTrapDataN,
|
|
npRelHumTrapDataStatus,
|
|
npRelHumTrapDataValue,
|
|
npRelHumTrapDataMemo,
|
|
npRelHumTrapDataSafeRangeHigh,
|
|
npRelHumTrapDataSafeRangeLow
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature in the Safe range"
|
|
::= { npRelHumTrapTemp 102 }
|
|
|
|
npRelHumTrapTempBelowSafe NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
npRelHumTrapDataN,
|
|
npRelHumTrapDataStatus,
|
|
npRelHumTrapDataValue,
|
|
npRelHumTrapDataMemo,
|
|
npRelHumTrapDataSafeRangeHigh,
|
|
npRelHumTrapDataSafeRangeLow
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature below the Safe range"
|
|
::= { npRelHumTrapTemp 101 }
|
|
|
|
npRelHumTrapTempFail NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
npRelHumTrapDataN,
|
|
npRelHumTrapDataStatus,
|
|
npRelHumTrapDataValue,
|
|
npRelHumTrapDataMemo,
|
|
npRelHumTrapDataSafeRangeHigh,
|
|
npRelHumTrapDataSafeRangeLow
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sensor failed!"
|
|
::= { npRelHumTrapTemp 100 }
|
|
|
|
|
|
npGsm OBJECT IDENTIFIER::={lightcom 3800}
|
|
npGsmInfo OBJECT IDENTIFIER::={npGsm 1}
|
|
|
|
npGsmFailed OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
ok (0),
|
|
failed (1),
|
|
fatalError (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Firmware's GSM module status"
|
|
::= { npGsmInfo 1 }
|
|
|
|
npGsmRegistration OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
impossible (0),
|
|
homeNetwork (1),
|
|
searching (2),
|
|
denied (3),
|
|
unknown (4),
|
|
roaming (5),
|
|
infoUpdate (255)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Status of modem registration in GSM network (AT+CREG? result)"
|
|
::= { npGsmInfo 2 }
|
|
|
|
npGsmStrength OBJECT-TYPE
|
|
SYNTAX INTEGER (0..255)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "GSM signal strength.
|
|
0..31 = 0..100%,
|
|
99 = unknown or n/a,
|
|
255 = updating info"
|
|
::= { npGsmInfo 3 }
|
|
|
|
npGsmSendSmsUtf8 OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Send arbitrary SMS.
|
|
Format: [phone_number,phone_number,...] Message
|
|
One to four destination phone numbers
|
|
If [] and numbers omitted, mesagge will be sent to preset numbers from SMS setup
|
|
Cyrillic characters must be in UTF8 encoding."
|
|
::= { npGsmInfo 9 }
|
|
|
|
npGsmSendSmsWin1251 OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Send arbitrary SMS.
|
|
Format: [phone_number,phone_number,...] Message
|
|
One to four destination phone numbers
|
|
If [] and numbers omitted, mesagge will be sent to preset numbers from SMS setup
|
|
Cyrillic characters must be in Win1251 encoding."
|
|
::= { npGsmInfo 10 }
|
|
|
|
npGsmUnparsedRxSmsFrom OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION "Source phone of received unparsed (unknown) Sms"
|
|
::= { npGsmInfo 11 }
|
|
|
|
npGsmUnparsedRxSms OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION "Received unparsed Sms with unknown starting word,
|
|
Encoding Windows-1251"
|
|
::= { npGsmInfo 12 }
|
|
|
|
npGsmUnparsedRxSmsUtf8 OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION "Received unparsed Sms with unknown starting word,
|
|
Encoding UTF-8"
|
|
::= { npGsmInfo 13 }
|
|
|
|
npGsmTrapUnparsedSms NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
npGsmUnparsedRxSmsFrom,
|
|
npGsmUnparsedRxSms,
|
|
npGsmUnparsedRxSmsUtf8
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"forwarding of SMS with wrong starting keyword"
|
|
::= { npGsmTrapPrefix 2 }
|
|
|
|
npGsmTraps OBJECT IDENTIFIER::={npGsm 2}
|
|
npGsmTrapPrefix OBJECT IDENTIFIER::={npGsmTraps 0}
|
|
|
|
npGsmTrap NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
npGsmFailed,
|
|
npGsmRegistration,
|
|
npGsmStrength
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"GSM modem or SMS firmware problems"
|
|
::= { npGsmTrapPrefix 1 }
|
|
|
|
|
|
|
|
npIr OBJECT IDENTIFIER::={lightcom 7900}
|
|
npIrCtrl OBJECT IDENTIFIER::={npIr 1}
|
|
|
|
npIrPlayCmd OBJECT-TYPE
|
|
SYNTAX INTEGER (1..16)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Write IR command number to send IR command"
|
|
::= { npIrCtrl 1 }
|
|
|
|
npIrReset OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Write 1 to reset IR transiever.
|
|
After reset, send IR command and check npIrStatus."
|
|
::= { npIrCtrl 2 }
|
|
|
|
npIrStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
commandCompleted (0),
|
|
protocolError (1),
|
|
commandAccepted (2),
|
|
errorUnknown (16),
|
|
errorBadNumber (17),
|
|
errorEmptyRecord (18),
|
|
errorFlashChip (19),
|
|
errorTimeout (20),
|
|
errorExtBusBusy (21)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "IR transiever status"
|
|
::= { npIrCtrl 3 }
|
|
|
|
|
|
|
|
npReboot OBJECT IDENTIFIER::={ lightcom 911 }
|
|
|
|
npSoftReboot OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Write 1 to reboot device after
|
|
current operations completition"
|
|
::= { npReboot 1 }
|
|
|
|
npResetStack OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Write 1 to re-initialize network
|
|
stack"
|
|
::= { npReboot 2 }
|
|
|
|
npForcedReboot OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Write 1 to immediate forced reboot"
|
|
::= { npReboot 3 }
|
|
|
|
END
|