DKSF-70-MIB DEFINITIONS ::= BEGIN IMPORTS enterprises, MODULE-IDENTITY, OBJECT-TYPE, Counter32, Integer32, Unsigned32, NOTIFICATION-TYPE FROM SNMPv2-SMI TEXTUAL-CONVENTION, DisplayString FROM SNMPv2-TC snmpTraps FROM SNMPv2-MIB ; uniPingServerSolutionV3 MODULE-IDENTITY LAST-UPDATED "202008190000Z" ORGANIZATION "Alentis Electronics" CONTACT-INFO "developers@netping.ru" DESCRIPTION "Generic MIB for NetPing remote sensing and control" REVISION "202207010000Z" DESCRIPTION "Renamed by Observium Developers for unify" REVISION "202008190000Z" DESCRIPTION "npExtRelay branch added" REVISION "202006120000Z" DESCRIPTION "npSmoke branch (.1.3.6.1.4.1.25728.8200) renamed to npInputAnalog and repurposed for 1Wire Current Loop Adapter" REVISION "201910130000Z" DESCRIPTION "npVoltage branch added" REVISION "201807010000Z" DESCRIPTION "npGsm branch appended (for DKSF70.7) npRelayMode values restricted to on, off, flip" REVISION "201608240000Z" DESCRIPTION "npThermoValuePrecise added npGsmSendSms renamed to npGsmSendSmsUtf8 npGsmSendWin1251 added" REVISION "201507140000Z" DESCRIPTION "npSmoke branch added, npRelHum branch extended" REVISION "201505290000Z" DESCRIPTION "npIoTrapLevelLegend added, npIrStatus values redefined" REVISION "201412030000Z" DESCRIPTION "npRelayMode, npIoLevelOut values changed" REVISION "201411260000Z" DESCRIPTION "npRelayN, npRelayMode, npIoLineN, npRelHumSensorStatusH, npRelHumSensorStatus values changed" REVISION "201402020000Z" DESCRIPTION "npRelayMode valid values changed, (3) excluded " REVISION "201401290000Z" DESCRIPTION "npCurLoop, npRelHumidity, npIr branches has added" REVISION "201401210000Z" DESCRIPTION "partial rewrite for DKSF 70" REVISION "201304110000Z" DESCRIPTION "partial rewrite for DKSF 48" REVISION "201205310000Z" DESCRIPTION "npPwrRelayState branch was added" REVISION "201204170000Z" DESCRIPTION "npReboot branch was added" REVISION "201203230000Z" DESCRIPTION "Minor changes to IR module for IRC-TRv2" REVISION "201109230000Z" DESCRIPTION "4 IO lines, Identification is changed from DKSF 52.4 to DKSF 52.5" REVISION "201103240000Z" DESCRIPTION "npIoPulseCounter, npIoSinglePulseDuration, npIoSinglePulseStart is added Identification is changed from DKSF 52.3 to DKSF 52.4" REVISION "201010140000Z" DESCRIPTION "IR module support" REVISION "201009200000Z" DESCRIPTION "dksf 52.3 subversion" REVISION "201005310000Z" DESCRIPTION "dksf 51.3 subversion" REVISION "201004140000Z" DESCRIPTION "SMIv2-style rewrite" ::= { lightcom 70 } lightcom OBJECT IDENTIFIER::={enterprises 25728 } FixedPoint1000 ::= TEXTUAL-CONVENTION DISPLAY-HINT "d-3" STATUS current DESCRIPTION "Fixed-point value as Integer, 3 decimal gigits after point (i.e. value*1000 rounded to Integer)" SYNTAX INTEGER npTrapInfo OBJECT IDENTIFIER::={lightcom 90} npTrapEmailTo OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "user-specified e-mail for NetPing Trap Forwarding Service" ::={npTrapInfo 1} npRelay OBJECT IDENTIFIER::={ lightcom 5500 } npRelayTable OBJECT-TYPE SYNTAX SEQUENCE OF NpRelayEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Watchdog and outlet/relay control table" ::= { npRelay 5 } npRelayEntry OBJECT-TYPE SYNTAX NpRelayEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Relay/outlet table row" INDEX { npRelayN } ::= { npRelayTable 1 } NpRelayEntry ::= SEQUENCE { npRelayN INTEGER, npRelayMode INTEGER, npRelayStartReset INTEGER, npRelayMemo DisplayString, npRelayFlip INTEGER, npRelayState INTEGER -- not in dksf70 npRelayPowered INTEGER } npRelayN OBJECT-TYPE SYNTAX INTEGER (1..1) MAX-ACCESS read-only STATUS current DESCRIPTION "The N of output relay" ::= { npRelayEntry 1 } npRelayMode OBJECT-TYPE SYNTAX INTEGER { flip(-1), off(0), on(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "Control of relay: -1 - flip between on(1) and off(0) 0 - switch off 1 - switch on" ::={npRelayEntry 2} npRelayStartReset OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Write 1 to start reset (switch relay off for some time)" ::={npRelayEntry 3} npRelayMemo OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Relay memo" ::={npRelayEntry 6} npRelayFlip OBJECT-TYPE SYNTAX INTEGER { flip(-1) } MAX-ACCESS read-write STATUS current DESCRIPTION "Write -1 to flip between manual on and manual off states of relay" ::={npRelayEntry 14} npRelayState OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Actual relay state at the moment, regardless of source of control. 0 - relay is off 1 - relay is on" ::={npRelayEntry 15} -- npRelayPowered OBJECT-TYPE -- SYNTAX INTEGER { -- no(0), -- yes(1) -- } -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION "AC presence on output. -- 0 - no AC dew to relay switched off or no ac on input -- 1 - AC is present" -- ::={npRelayEntry 16} npRelayTrapData OBJECT IDENTIFIER::={ npRelay 3 } npRelayTrapN OBJECT-TYPE SYNTAX INTEGER (1..2) MAX-ACCESS read-only STATUS current DESCRIPTION "The N of output relay" ::= { npRelayTrapData 1 } npRelayTrapMode OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "Relay position, w/o effect of temporary switch (reset): 0 - off 1 - on" ::={npRelayTrapData 2} npRelayTrapMemo OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Relay memo" ::={npRelayTrapData 6} npRelayTrapState OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Actual relay state at the moment, 0 - relay is off 1 - relay is on" ::={npRelayTrapData 15} npRelayTrapCmdSrc OBJECT-TYPE SYNTAX INTEGER { unknown(-1), webInterface(1), snmp(2), sms(3), httpApi(4), watchdog(5), schedule(6), logic(7) } MAX-ACCESS read-only STATUS current DESCRIPTION "Source of command to switch Relay" ::={npRelayTrapData 18} npRelayTrapDateTime OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Textual timestamp of event" ::={npRelayTrapData 19} npRelayTrap OBJECT IDENTIFIER::={npRelay 6} npRelayTrapAllEvents OBJECT IDENTIFIER::={npRelayTrap 127} npRelayTrapAllChannels NOTIFICATION-TYPE OBJECTS { npRelayTrapN, npRelayTrapMode, npRelayTrapMemo, npRelayTrapState, npRelayTrapCmdSrc, npRelayTrapDateTime } STATUS current DESCRIPTION "Status of Humidity has changed!" ::= { npRelayTrapAllEvents 99 } npRelayTrapOff NOTIFICATION-TYPE OBJECTS { npRelayTrapN, npRelayTrapMode, npRelayTrapMemo, npRelayTrapState, npRelayTrapCmdSrc, npRelayTrapDateTime } STATUS current DESCRIPTION "Relay switched off" ::= { npRelayTrap 100 } npRelayTrapOn NOTIFICATION-TYPE OBJECTS { npRelayTrapN, npRelayTrapMode, npRelayTrapMemo, npRelayTrapState, npRelayTrapCmdSrc, npRelayTrapDateTime } STATUS current DESCRIPTION "Relay switched on" ::= { npRelayTrap 101 } npRelayTrapModeChange NOTIFICATION-TYPE OBJECTS { npRelayTrapN, npRelayTrapMode, npRelayTrapMemo, npRelayTrapState, npRelayTrapCmdSrc, npRelayTrapDateTime } STATUS current DESCRIPTION "Relay mode changed" ::= { npRelayTrap 102 } npRelayTrapReset NOTIFICATION-TYPE OBJECTS { npRelayTrapN, npRelayTrapMode, npRelayTrapMemo, npRelayTrapState, npRelayTrapCmdSrc, npRelayTrapDateTime } STATUS current DESCRIPTION "Relay reset started" ::= { npRelayTrap 103 } npExtRelay OBJECT IDENTIFIER::={ lightcom 5600 } npExtRelayTable OBJECT-TYPE SYNTAX SEQUENCE OF NpExtRelayEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Watchdog and outlet/relay control table" ::= { npExtRelay 5 } npExtRelayEntry OBJECT-TYPE SYNTAX NpExtRelayEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Relay/outlet table row" INDEX { npExtRelayN } ::= { npExtRelayTable 1 } NpExtRelayEntry ::= SEQUENCE { npExtRelayN INTEGER, npExtRelayMode INTEGER, npExtRelayStartReset INTEGER, npExtRelayMemo DisplayString, npExtRelayFlip INTEGER, npExtRelayState INTEGER } npExtRelayN OBJECT-TYPE SYNTAX INTEGER (1..8) MAX-ACCESS read-only STATUS current DESCRIPTION "The N of external relay" ::= { npExtRelayEntry 1 } npExtRelayMode OBJECT-TYPE SYNTAX INTEGER { flip(-1), off(0), on(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "Control of relay: -1 - flip between on(1) and off(0) 0 - switch off 1 - switch on" ::={npExtRelayEntry 2} npExtRelayStartReset OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Write 1 to start reset (switch relay off for some time)" ::={npExtRelayEntry 3} npExtRelayMemo OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Relay memo" ::={npExtRelayEntry 6} npExtRelayFlip OBJECT-TYPE SYNTAX INTEGER { flip(-1) } MAX-ACCESS read-write STATUS current DESCRIPTION "Write -1 to flip between manual on and manual off states of relay" ::={npExtRelayEntry 14} npExtRelayState OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Actual relay state at the moment, regardless of source of control. 0 - relay is off 1 - relay is on" ::={npExtRelayEntry 15} npExtRelayTrapData OBJECT IDENTIFIER::={ npExtRelay 3 } npExtRelayTrapN OBJECT-TYPE SYNTAX INTEGER (1..8) MAX-ACCESS read-only STATUS current DESCRIPTION "The N of output relay" ::= { npExtRelayTrapData 1 } npExtRelayTrapMode OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "Relay position, w/o effect of temporary switch (reset): 0 - off 1 - on" ::={npExtRelayTrapData 2} npExtRelayTrapMemo OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Relay memo" ::={npExtRelayTrapData 6} npExtRelayTrapState OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Actual relay state at the moment, 0 - relay is off 1 - relay is on" ::={npExtRelayTrapData 15} npExtRelayTrapCmdSrc OBJECT-TYPE SYNTAX INTEGER { unknown(-1), webInterface(1), snmp(2), sms(3), httpApi(4), watchdog(5), schedule(6), logic(7), button(8) } MAX-ACCESS read-only STATUS current DESCRIPTION "Source of command to switch Relay" ::={npExtRelayTrapData 18} npExtRelayTrapDateTime OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Textual timestamp of event" ::={npExtRelayTrapData 19} npExtRelayTrap OBJECT IDENTIFIER::={npExtRelay 6} npExtRelayTrapAllEvents OBJECT IDENTIFIER::={npExtRelayTrap 127} npExtRelayTrapAllChannels NOTIFICATION-TYPE OBJECTS { npExtRelayTrapN, npExtRelayTrapMode, npExtRelayTrapMemo, npExtRelayTrapState, npExtRelayTrapCmdSrc, npExtRelayTrapDateTime } STATUS current DESCRIPTION "Status of Humidity has changed!" ::= { npExtRelayTrapAllEvents 99 } npExtRelayTrapOff NOTIFICATION-TYPE OBJECTS { npExtRelayTrapN, npExtRelayTrapMode, npExtRelayTrapMemo, npExtRelayTrapState, npExtRelayTrapCmdSrc, npExtRelayTrapDateTime } STATUS current DESCRIPTION "Relay switched off" ::= { npExtRelayTrap 100 } npExtRelayTrapOn NOTIFICATION-TYPE OBJECTS { npExtRelayTrapN, npExtRelayTrapMode, npExtRelayTrapMemo, npExtRelayTrapState, npExtRelayTrapCmdSrc, npExtRelayTrapDateTime } STATUS current DESCRIPTION "Relay switched on" ::= { npExtRelayTrap 101 } npExtRelayTrapModeChange NOTIFICATION-TYPE OBJECTS { npExtRelayTrapN, npExtRelayTrapMode, npExtRelayTrapMemo, npExtRelayTrapState, npExtRelayTrapCmdSrc, npExtRelayTrapDateTime } STATUS current DESCRIPTION "Relay mode changed" ::= { npExtRelayTrap 102 } npExtRelayTrapReset NOTIFICATION-TYPE OBJECTS { npExtRelayTrapN, npExtRelayTrapMode, npExtRelayTrapMemo, npExtRelayTrapState, npExtRelayTrapCmdSrc, npExtRelayTrapDateTime } STATUS current DESCRIPTION "Relay reset started" ::= { npExtRelayTrap 103 } npThermo OBJECT IDENTIFIER::={lightcom 8800} npThermoTable OBJECT-TYPE SYNTAX SEQUENCE OF NpThermoEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Thermo Sensors Table" ::= { npThermo 1 } npThermoEntry OBJECT-TYPE SYNTAX NpThermoEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Thermo Sensors Table Row" INDEX { npThermoSensorN } ::= { npThermoTable 1 } NpThermoEntry ::= SEQUENCE { npThermoSensorN INTEGER, npThermoValue INTEGER, npThermoStatus INTEGER, npThermoLow INTEGER, npThermoHigh INTEGER, npThermoMemo DisplayString, npThermoValuePrecise FixedPoint1000 } npThermoSensorN OBJECT-TYPE SYNTAX INTEGER (1..8) MAX-ACCESS read-only STATUS current DESCRIPTION "The id of temperature sensor, 1 to 8" ::= { npThermoEntry 1 } npThermoValue OBJECT-TYPE SYNTAX INTEGER (-60..280) MAX-ACCESS read-only STATUS current DESCRIPTION "Temperature, deg.C" ::= { npThermoEntry 2 } npThermoStatus OBJECT-TYPE SYNTAX INTEGER { failed(0), low(1), norm(2), high(3) } MAX-ACCESS read-only STATUS current DESCRIPTION "Temperature status (0=fault, 1=underheat, 2=normal, 3=overheat)" ::= { npThermoEntry 3 } npThermoLow OBJECT-TYPE SYNTAX INTEGER (-60..280) MAX-ACCESS read-only STATUS current DESCRIPTION "Bottom margin of normal temperature range, deg.C" ::= { npThermoEntry 4 } npThermoHigh OBJECT-TYPE SYNTAX INTEGER (-60..280) MAX-ACCESS read-only STATUS current DESCRIPTION "Top margin of normal temperature range, deg.C" ::= { npThermoEntry 5 } npThermoMemo OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "T channel memo" ::= { npThermoEntry 6 } npThermoValuePrecise OBJECT-TYPE SYNTAX FixedPoint1000 MAX-ACCESS read-only STATUS current DESCRIPTION "Temperature, deg.C, with fractional part 3 digits after point" ::= { npThermoEntry 7 } npThermoTraps OBJECT IDENTIFIER::={npThermo 2} npThermoTrapPrefix OBJECT IDENTIFIER::={npThermoTraps 0} npThermoTrapSensorN OBJECT-TYPE SYNTAX INTEGER (1..8) MAX-ACCESS read-only STATUS current DESCRIPTION "The id of temperature sensor, 1 to 8" ::= { npThermoTraps 1 } npThermoTrapValue OBJECT-TYPE SYNTAX INTEGER (-60..280) MAX-ACCESS read-only STATUS current DESCRIPTION "Temperature, deg.C" ::= { npThermoTraps 2 } npThermoTrapStatus OBJECT-TYPE SYNTAX INTEGER { failed(0), low(1), norm(2), high(3) } MAX-ACCESS read-only STATUS current DESCRIPTION "Temperature status (0=fault, 1=underheat, 2=normal, 3=overheat)" ::= { npThermoTraps 3 } npThermoTrapLow OBJECT-TYPE SYNTAX INTEGER (-60..280) MAX-ACCESS read-only STATUS current DESCRIPTION "Bottom margin of normal temperature range, deg.C" ::= { npThermoTraps 4 } npThermoTrapHigh OBJECT-TYPE SYNTAX INTEGER (-60..280) MAX-ACCESS read-only STATUS current DESCRIPTION "Top margin of normal temperature range, deg.C" ::= { npThermoTraps 5 } npThermoTrapMemo OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "T channel memo" ::= { npThermoTraps 6 } npThermoTrap NOTIFICATION-TYPE OBJECTS { npThermoTrapSensorN, npThermoTrapValue, npThermoTrapStatus, npThermoTrapLow, npThermoTrapHigh, npThermoTrapMemo } STATUS current DESCRIPTION "Status of Thermo sensor is changed (crossing of normal temp. range)" ::= { npThermoTrapPrefix 1 } npIo OBJECT IDENTIFIER::={lightcom 8900} npIoTable OBJECT-TYPE SYNTAX SEQUENCE OF NpIoEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Digital Input/output Table" ::= { npIo 1 } npIoEntry OBJECT-TYPE SYNTAX NpIoEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Digital Input/output Table Row" INDEX { npIoLineN } ::= { npIoTable 1 } NpIoEntry ::= SEQUENCE { npIoLineN INTEGER, npIoLevelIn INTEGER, npIoLevelOut INTEGER, npIoMemo DisplayString, npIoPulseCounter Counter32, npIoSinglePulseDuration INTEGER, npIoSinglePulseStart INTEGER } npIoLineN OBJECT-TYPE SYNTAX INTEGER (1..8) MAX-ACCESS read-only STATUS current DESCRIPTION "Number of IO line, from 1 to max supported" ::= { npIoEntry 1 } npIoLevelIn OBJECT-TYPE SYNTAX INTEGER (0..1) MAX-ACCESS read-only STATUS current DESCRIPTION "Input level, 0 or 1" ::= { npIoEntry 2 } npIoLevelOut OBJECT-TYPE SYNTAX INTEGER { flip(-1), low(0), high(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "Output level, 0 or 1. Write -1 to flip output." ::= { npIoEntry 3 } npIoMemo OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "IO line memo" ::= { npIoEntry 6 } npIoPulseCounter OBJECT-TYPE SYNTAX Counter32 MAX-ACCESS read-write STATUS current DESCRIPTION "Pulse Counter on IO input line (counts positive fronts) Write 0 to reset." ::= { npIoEntry 9 } npIoSinglePulseDuration OBJECT-TYPE SYNTAX INTEGER (100..25500) MAX-ACCESS read-write STATUS current DESCRIPTION "Set duration of single pulse on IO output line, 100ms to 25500ms, min. step is 100ms" ::= { npIoEntry 12 } npIoSinglePulseStart OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Write 1 to start single pulse on IO output. Output will be inverted for time, specified by npIoSinglePulseDuration" ::= { npIoEntry 13 } npIoTraps OBJECT IDENTIFIER::={npIo 2} npIoTrapPrefix OBJECT IDENTIFIER::={npIoTraps 0} npIoTrapLineN OBJECT-TYPE SYNTAX INTEGER (1..2) MAX-ACCESS read-only STATUS current DESCRIPTION "Trap data, Number of IO line" ::= { npIoTraps 1 } npIoTrapLevelIn OBJECT-TYPE SYNTAX INTEGER (0..1) MAX-ACCESS read-only STATUS current DESCRIPTION "Trap data, new Input level, 0 or 1" ::= { npIoTraps 2 } npIoTrapMemo OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Trap data, IO line memo" ::= { npIoTraps 6 } npIoTrapLevelLegend OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Legend for current logic level on the IO line" ::= { npIoTraps 7 } npIoTrap NOTIFICATION-TYPE OBJECTS { npIoTrapLineN, npIoTrapLevelIn, npIoTrapMemo, npIoTrapLevelLegend } STATUS current DESCRIPTION "Input state of IO line is changed" ::= { npIoTrapPrefix 1 } npCurLoop OBJECT IDENTIFIER::={lightcom 8300} npCurLoopTable OBJECT-TYPE SYNTAX SEQUENCE OF NpCurLoopEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Current loop sensors Table" ::= { npCurLoop 1 } npCurLoopEntry OBJECT-TYPE SYNTAX NpCurLoopEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Current loop sensors Table Row" INDEX { npCurLoopN } ::= { npCurLoopTable 1 } NpCurLoopEntry ::= SEQUENCE { npCurLoopN INTEGER, npCurLoopStatus INTEGER, npCurLoopI INTEGER, npCurLoopV INTEGER, npCurLoopR INTEGER, npCurLoopPower INTEGER } npCurLoopN OBJECT-TYPE SYNTAX INTEGER (1..8) MAX-ACCESS read-only STATUS current DESCRIPTION "Index of current loop, 1 to max supported" ::= { npCurLoopEntry 1 } npCurLoopStatus OBJECT-TYPE SYNTAX INTEGER { ok(0), alert(1), cut(2), short(3), notPowered(4) } MAX-ACCESS read-only STATUS current DESCRIPTION "Status of the loop 0=Normal, 1=Alert, 2=Cut, 3=Short, 4=Not Powered" ::= { npCurLoopEntry 2 } npCurLoopI OBJECT-TYPE SYNTAX INTEGER (0..99999) MAX-ACCESS read-only STATUS current DESCRIPTION "Loop current, mA" ::= { npCurLoopEntry 3 } npCurLoopV OBJECT-TYPE SYNTAX INTEGER (0..99999) MAX-ACCESS read-only STATUS current DESCRIPTION "Voltage drop on the loop, mV" ::= { npCurLoopEntry 4 } npCurLoopR OBJECT-TYPE SYNTAX INTEGER (0..99999) MAX-ACCESS read-only STATUS current DESCRIPTION "Resistance of the loop, Ohm" ::= { npCurLoopEntry 5 } npCurLoopPower OBJECT-TYPE SYNTAX INTEGER { off(0), on(1), cyclePower(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Control of loop power 0=Off, 1=On, 2=reset by off/on power" ::= { npCurLoopEntry 7 } npCurLoopTraps OBJECT IDENTIFIER::={npCurLoop 2} npCurLoopTrapPrefix OBJECT IDENTIFIER::={npCurLoopTraps 0} npCurLoopTrapN OBJECT-TYPE SYNTAX INTEGER (1..8) MAX-ACCESS read-only STATUS current DESCRIPTION "Index of current loop, which status has changed" ::= { npCurLoopTraps 1 } npCurLoopTrapStatus OBJECT-TYPE SYNTAX INTEGER { ok(0), alert(1), cut(2), short(3), notPowered(4) } MAX-ACCESS read-only STATUS current DESCRIPTION "Status of the loop 0=Normal, 1=Alert, 2=Cut, 3=Short, 4=Not Powered" ::= { npCurLoopTraps 2 } npCurLoopTrapI OBJECT-TYPE SYNTAX INTEGER (0..99999) MAX-ACCESS read-only STATUS current DESCRIPTION "Loop current, mA" ::= { npCurLoopTraps 3 } npCurLoopTrapV OBJECT-TYPE SYNTAX INTEGER (0..99999) MAX-ACCESS read-only STATUS current DESCRIPTION "Voltage drop on the loop, mV" ::= { npCurLoopTraps 4 } npCurLoopTrapR OBJECT-TYPE SYNTAX INTEGER (0..99999) MAX-ACCESS read-only STATUS current DESCRIPTION "Resistance of the loop, Ohm" ::= { npCurLoopTraps 5 } npCurLoopTrapPower OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "Status of loop power 0=Off, 1=On" ::= { npCurLoopTraps 7 } npCurLoopTrap NOTIFICATION-TYPE OBJECTS { npCurLoopTrapN, npCurLoopTrapStatus, npCurLoopTrapI, npCurLoopTrapV, npCurLoopTrapR, npCurLoopTrapPower, npTrapEmailTo } STATUS current DESCRIPTION "Status of current loop N has changed!" ::= { npCurLoopTrapPrefix 1 } npVoltage OBJECT IDENTIFIER::={lightcom 9000} npVoltageTable OBJECT-TYPE SYNTAX SEQUENCE OF NpVoltageEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Voltage Monitoring Sensors Table" ::= { npVoltage 1 } npVoltageEntry OBJECT-TYPE SYNTAX NpVoltageEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Voltage Monitoring Sensors Table Row" INDEX { npVoltageN } ::= { npVoltageTable 1 } NpVoltageEntry ::= SEQUENCE { npVoltageN INTEGER, npVoltageRMS INTEGER, npVoltageStatus INTEGER, npVoltageFreq INTEGER, npVoltageFreqStatus INTEGER, npVoltageMemo DisplayString, npVoltageSagCounter Counter32, npVoltageSagStatus INTEGER, npVoltageSagSmallThreshold INTEGER, npVoltageSagMediumThreshold INTEGER, npVoltageSagBigThreshold INTEGER, npVoltageStandard INTEGER, npVoltagePeak INTEGER, npVoltagePeakStatus INTEGER } npVoltageN OBJECT-TYPE SYNTAX INTEGER (1..3) MAX-ACCESS read-only STATUS current DESCRIPTION "The ID of Voltage Monitoring sensor, 1 to 3" ::= { npVoltageEntry 1 } npVoltageRMS OBJECT-TYPE SYNTAX INTEGER (0..1000) MAX-ACCESS read-only STATUS current DESCRIPTION "Voltage value, V" ::= { npVoltageEntry 2 } npVoltageStatus OBJECT-TYPE SYNTAX INTEGER { sensorFailed(0), noVoltage(1), bad(2), warn(3), good(4) } MAX-ACCESS read-only STATUS current DESCRIPTION "Status of voltage" ::= { npVoltageEntry 3 } npVoltageFreq OBJECT-TYPE SYNTAX INTEGER (0..10000) MAX-ACCESS read-only STATUS current DESCRIPTION "Frequency value in units of .01 Hz" ::= { npVoltageEntry 4 } npVoltageFreqStatus OBJECT-TYPE SYNTAX INTEGER { sensorFailed(0), noVoltage(1), bad(2), warn(3), good(4) } MAX-ACCESS read-only STATUS current DESCRIPTION "Status of frequency" ::= { npVoltageEntry 5 } npVoltageMemo OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Voltage Monitoring sensor memo" ::= { npVoltageEntry 6 } npVoltageSagCounter OBJECT-TYPE SYNTAX Counter32 MAX-ACCESS read-write STATUS current DESCRIPTION "Counter of voltage sags" ::= { npVoltageEntry 10 } npVoltageSagStatus OBJECT-TYPE SYNTAX INTEGER { sensorFailed(0), noVoltage(1), high(2), medium(3), small(4), noSags(5) } MAX-ACCESS read-only STATUS current DESCRIPTION "Status of voltage sag" ::= { npVoltageEntry 11 } npVoltageSagSmallThreshold OBJECT-TYPE SYNTAX INTEGER (0..100) MAX-ACCESS read-write STATUS current DESCRIPTION "The margin between No Sags and Small Sags, % of Nominal Voltage Usually 90%" ::= { npVoltageEntry 12 } npVoltageSagMediumThreshold OBJECT-TYPE SYNTAX INTEGER (0..100) MAX-ACCESS read-write STATUS current DESCRIPTION "The margin between Small Sags and Medium Sags, % of Nominal Voltage Usually 70%" ::= { npVoltageEntry 13 } npVoltageSagBigThreshold OBJECT-TYPE SYNTAX INTEGER (0..100) MAX-ACCESS read-write STATUS current DESCRIPTION "The margin between Medium Sags and Big Sags, % of Nominal Voltage Usually 50%" ::= { npVoltageEntry 14 } npVoltageStandard OBJECT-TYPE SYNTAX INTEGER (100..240) MAX-ACCESS read-write STATUS current DESCRIPTION "Nominal voltage, V" ::= { npVoltageEntry 20 } npVoltagePeak OBJECT-TYPE SYNTAX INTEGER (0..1000) MAX-ACCESS read-only STATUS current DESCRIPTION "Peak voltage, V" ::= { npVoltageEntry 30 } npVoltagePeakStatus OBJECT-TYPE SYNTAX INTEGER { sensorFailed(0), noVoltage(1), dangerous(2), noPeaks(3) } MAX-ACCESS read-only STATUS current DESCRIPTION "Status of peak voltage" ::= { npVoltageEntry 31 } npVoltageTraps OBJECT IDENTIFIER::={npVoltage 2} npVoltageTrapPrefix OBJECT IDENTIFIER::={npVoltageTraps 0} npVoltageTrapN OBJECT-TYPE SYNTAX INTEGER (1..3) MAX-ACCESS read-only STATUS current DESCRIPTION "The ID of Voltage Monitoring sensor, 1 to 3" ::= { npVoltageTraps 1 } npVoltageTrapRMS OBJECT-TYPE SYNTAX INTEGER (0..1000) MAX-ACCESS read-only STATUS current DESCRIPTION "Voltage value, V" ::= { npVoltageTraps 2 } npVoltageTrapStatus OBJECT-TYPE SYNTAX INTEGER { sensorFailed(0), noVoltage(1), bad(2), warn(3), good(4) } MAX-ACCESS read-only STATUS current DESCRIPTION "Status of voltage" ::= { npVoltageTraps 3 } npVoltageTrapFreq OBJECT-TYPE SYNTAX INTEGER (0..10000) MAX-ACCESS read-only STATUS current DESCRIPTION "Frequency value in units of .01 Hz" ::= { npVoltageTraps 4 } npVoltageTrapFreqStatus OBJECT-TYPE SYNTAX INTEGER { sensorFailed(0), noVoltage(1), bad(2), warn(3), good(4) } MAX-ACCESS read-only STATUS current DESCRIPTION "Status of frequency" ::= { npVoltageTraps 5 } npVoltageTrapMemo OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Voltage Monitoring sensor memo" ::= { npVoltageTraps 6 } npVoltageTrapSagCounter OBJECT-TYPE SYNTAX Counter32 MAX-ACCESS read-only STATUS current DESCRIPTION "Counter of voltage sags" ::= { npVoltageTraps 10 } npVoltageTrapSagStatus OBJECT-TYPE SYNTAX INTEGER { sensorFailed(0), noVoltage(1), high(2), medium(3), small(4), noSags(5) } MAX-ACCESS read-only STATUS current DESCRIPTION "Status of voltage sag" ::= { npVoltageTraps 11 } npVoltageTrapPeak OBJECT-TYPE SYNTAX INTEGER (0..1000) MAX-ACCESS read-only STATUS current DESCRIPTION "Peak voltage, V" ::= { npVoltageTraps 30 } npVoltageTrapPeakStatus OBJECT-TYPE SYNTAX INTEGER { sensorFailed(0), noVoltage(1), dangerous(2), noPeaks(3) } MAX-ACCESS read-only STATUS current DESCRIPTION "Status of peak voltage" ::= { npVoltageTraps 31 } npVoltageTrap NOTIFICATION-TYPE OBJECTS { npVoltageTrapN, npVoltageTrapRMS, npVoltageTrapStatus, npVoltageTrapFreq, npVoltageTrapFreqStatus, npVoltageTrapMemo, npVoltageTrapSagCounter, npVoltageTrapSagStatus, npVoltageTrapPeakStatus } STATUS current DESCRIPTION "Status of Voltage Monitoring sensor is changed" ::= { npVoltageTrapPrefix 1 } npInputAnalog OBJECT IDENTIFIER::={lightcom 8200} npInputAnalogTable OBJECT-TYPE SYNTAX SEQUENCE OF NpInputAnalogEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "1Wire Current Loop Adapters Table" ::= { npInputAnalog 1 } npInputAnalogEntry OBJECT-TYPE SYNTAX NpInputAnalogEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "1Wire Current Loop Adapters Table Row" INDEX { npInputAnalogSensorN } ::= { npInputAnalogTable 1 } NpInputAnalogEntry ::= SEQUENCE { npInputAnalogSensorN INTEGER, npInputAnalogStatus INTEGER, npInputAnalogCurrent Integer32, npInputAnalogVoltage Integer32, npInputAnalogResistance Unsigned32, npInputAnalogMemo DisplayString, npInputAnalogPower INTEGER, npInputAnalogReset INTEGER, npInputAnalogWorkRangeHigh Integer32, npInputAnalogSafeRangeHigh Integer32, npInputAnalogSafeRangeLow Integer32, npInputAnalogWorkRangeLow Integer32 } npInputAnalogSensorN OBJECT-TYPE SYNTAX INTEGER (1..4) MAX-ACCESS read-only STATUS current DESCRIPTION "The id of 1Wire Current Loop Adapter, 1 to 4" ::= { npInputAnalogEntry 1 } npInputAnalogStatus OBJECT-TYPE SYNTAX INTEGER { failure1w(0), belowSafe(1), safe(2), aboveSafe(3), failureAnalog(5) } MAX-ACCESS read-only STATUS current DESCRIPTION "Status of Current Loop Signal, failure1w = no reply from the adapter on 1wire bus, failureAnalog = signal is beyond it's Working Range, belowSafe, safe, aboveSafe - status of the signal relative to the Safe Range margins" ::= { npInputAnalogEntry 2 } npInputAnalogCurrent OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Current via RS_P, RS_N contacts of Current Loop Adapter, uA (microamperes)" ::= { npInputAnalogEntry 3 } npInputAnalogVoltage OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Voltage on RS_P contact of Current Loop Adapter Vs Ground, mV" ::= { npInputAnalogEntry 4 } npInputAnalogResistance OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS read-only STATUS current DESCRIPTION "Resistance of the Current Loop, Ohm" ::= { npInputAnalogEntry 5 } npInputAnalogMemo OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Current Loop memo, what's connected" ::= { npInputAnalogEntry 6 } npInputAnalogPower OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "Controls power on Current Loop Adapter outputs +24V, +12V" ::= { npInputAnalogEntry 7 } npInputAnalogReset OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Write duration 1..25s to temporary switch off +12V, +24V outputs to reset sensor on the current loop by cycling it's power" ::= { npInputAnalogEntry 8 } npInputAnalogWorkRangeHigh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Top marging of Working Range, uA or mV or Ohm. If monitored value is outide of Working Range, Analog Failure take place. If not specified, value is -32768" ::= { npInputAnalogEntry 11 } npInputAnalogSafeRangeHigh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Top marging of Safe Range, uA or mV or Ohm. If not specified, value is -32768" ::= { npInputAnalogEntry 12 } npInputAnalogSafeRangeLow OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Bottom marging of Safe Range, uA or mV or Ohm. If not specified, value is -32768" ::= { npInputAnalogEntry 13 } npInputAnalogWorkRangeLow OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Bottom marging of Working Range, uA or mV or Ohm. If monitored value is outide of Working Range, Analog Failure take place. If not specified, value is -32768" ::= { npInputAnalogEntry 14 } npInputAnalogTraps OBJECT IDENTIFIER::={npInputAnalog 2} npInputAnalogTrapPrefix OBJECT IDENTIFIER::={npInputAnalogTraps 0} npInputAnalogTrapSensorN OBJECT-TYPE SYNTAX INTEGER (1..4) MAX-ACCESS accessible-for-notify STATUS current DESCRIPTION "The id of 1Wire Current Loop Adapter, 1 to 4" ::= { npInputAnalogTraps 1 } npInputAnalogTrapStatus OBJECT-TYPE SYNTAX INTEGER { failure1w(0), belowSafe(1), safe(2), aboveSafe(3), failureAnalog(5) } MAX-ACCESS accessible-for-notify STATUS current DESCRIPTION "New status of Current Loop Signal, failure1w = no reply from the adapter on 1wire bus, failureAnalog = signal is beyond it's Working Range, belowSafe, safe, aboveSafe - status of the signal relative to the Safe Range margins" ::= { npInputAnalogTraps 2 } npInputAnalogTrapCurrent OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS accessible-for-notify STATUS current DESCRIPTION "Current via RS_P, RS_N contacts of Current Loop Adapter, uA (microamperes)" ::= { npInputAnalogTraps 3 } npInputAnalogTrapVoltage OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS accessible-for-notify STATUS current DESCRIPTION "Voltage on RS_P contact of Current Loop Adapter Vs Ground, mV" ::= { npInputAnalogTraps 4 } npInputAnalogTrapResistance OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS accessible-for-notify STATUS current DESCRIPTION "Resistance of the Current Loop, Ohm" ::= { npInputAnalogTraps 5 } npInputAnalogTrapMemo OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS accessible-for-notify STATUS current DESCRIPTION "Current Loop memo" ::= { npInputAnalogTraps 6 } npInputAnalogTrapPower OBJECT-TYPE SYNTAX INTEGER { off(0), on(1), temporaryOff(3) } MAX-ACCESS accessible-for-notify STATUS current DESCRIPTION "Status of power outputs +12V, +24V, temporary switching off for reset ignored" ::= { npInputAnalogTraps 7 } npInputAnalogTrapWorkRangeHigh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS accessible-for-notify STATUS current DESCRIPTION "Top marging of Working Range, uA or mV or Ohm. If monitored value is outide of Working Range, Analog Failure take place. If not specified, value is -32768" ::= { npInputAnalogTraps 11 } npInputAnalogTrapSafeRangeHigh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS accessible-for-notify STATUS current DESCRIPTION "Top marging of Safe Range, uA or mV or Ohm. If not specified, value is -32768" ::= { npInputAnalogTraps 12 } npInputAnalogTrapSafeRangeLow OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS accessible-for-notify STATUS current DESCRIPTION "Bottom marging of Safe Range, uA or mV or Ohm. If not specified, value is -32768" ::= { npInputAnalogTraps 13 } npInputAnalogTrapWorkRangeLow OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS accessible-for-notify STATUS current DESCRIPTION "Bottom marging of Working Range, uA or mV or Ohm. If monitored value is outide of Working Range, Analog Failure take place. If not specified, value is -32768" ::= { npInputAnalogTraps 14 } npInputAnalogTrap NOTIFICATION-TYPE OBJECTS { npInputAnalogTrapSensorN, npInputAnalogTrapStatus, npInputAnalogTrapCurrent, npInputAnalogTrapVoltage, npInputAnalogTrapResistance, npInputAnalogTrapMemo, npInputAnalogTrapPower, npInputAnalogTrapWorkRangeHigh, npInputAnalogTrapSafeRangeHigh, npInputAnalogTrapSafeRangeLow, npInputAnalogTrapWorkRangeLow } STATUS current DESCRIPTION "Status of 1W Analog Input Adapter has changed" ::= { npInputAnalogTrapPrefix 1 } npRelHumidity OBJECT IDENTIFIER::={lightcom 8400} npRelHumTable OBJECT-TYPE SYNTAX SEQUENCE OF NpRelHumEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Humidity+Temperature Sensors Table" ::= { npRelHumidity 1 } npRelHumEntry OBJECT-TYPE SYNTAX NpRelHumEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Humidity+Temperature Sensors Table Row" INDEX { npRelHumN } ::= { npRelHumTable 1 } NpRelHumEntry ::= SEQUENCE { npRelHumN INTEGER, npRelHumValue INTEGER, npRelHumStatus INTEGER, npRelHumTempValue INTEGER, npRelHumTempStatus INTEGER, npRelHumMemo DisplayString, npRelHumSafeRangeHigh INTEGER, npRelHumSafeRangeLow INTEGER, npRelHumTempSafeRangeHigh INTEGER, npRelHumTempSafeRangeLow INTEGER } npRelHumN OBJECT-TYPE SYNTAX INTEGER (1..4) MAX-ACCESS read-only STATUS current DESCRIPTION "Index of Humidity+Temperature sensor, 1 to max supported" ::= { npRelHumEntry 1 } npRelHumValue OBJECT-TYPE SYNTAX INTEGER (0..100) MAX-ACCESS read-only STATUS current DESCRIPTION "Relative humidity value, %" ::= { npRelHumEntry 2 } npRelHumStatus OBJECT-TYPE SYNTAX INTEGER { sensorFailed(0), belowSafeRange(1), inSafeRange(2), aboveSafeRange(3) } MAX-ACCESS read-only STATUS current DESCRIPTION "Status of Relative Humiduty" ::= { npRelHumEntry 3 } npRelHumTempValue OBJECT-TYPE SYNTAX INTEGER (-60..200) MAX-ACCESS read-only STATUS current DESCRIPTION "Sensor temperature, deg.C" ::= { npRelHumEntry 4 } npRelHumTempStatus OBJECT-TYPE SYNTAX INTEGER { sensorFailed(0), belowSafeRange(1), inSafeRange(2), aboveSafeRange(3) } MAX-ACCESS read-only STATUS current DESCRIPTION "Status of Relative Humiduty" ::= { npRelHumEntry 5 } npRelHumMemo OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Sensor Memo/Location" ::= { npRelHumEntry 6 } npRelHumSafeRangeHigh OBJECT-TYPE SYNTAX INTEGER (0..100) MAX-ACCESS read-only STATUS current DESCRIPTION "Relative Humidity safe range, top margin, %RH" ::= { npRelHumEntry 7 } npRelHumSafeRangeLow OBJECT-TYPE SYNTAX INTEGER (0..100) MAX-ACCESS read-only STATUS current DESCRIPTION "Relative Humidity safe range, bottom margin, %RH" ::= { npRelHumEntry 8 } npRelHumTempSafeRangeHigh OBJECT-TYPE SYNTAX INTEGER (-55..150) MAX-ACCESS read-only STATUS current DESCRIPTION "Temperature safe range, top margin, deg.C" ::= { npRelHumEntry 9 } npRelHumTempSafeRangeLow OBJECT-TYPE SYNTAX INTEGER (-55..150) MAX-ACCESS read-only STATUS current DESCRIPTION "Temperature safe range, bottom margin, deg.C" ::= { npRelHumEntry 10 } npRelHumTrapData OBJECT IDENTIFIER::={npRelHumidity 3} npRelHumTrapDataN OBJECT-TYPE SYNTAX INTEGER (1..4) MAX-ACCESS read-only STATUS current DESCRIPTION "Index of Humidity+Temperature sensor, 1 to max supported" ::= { npRelHumTrapData 1 } npRelHumTrapDataValue OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Sensor humidity, %RH, or temperature, deg.C" ::= { npRelHumTrapData 2 } npRelHumTrapDataStatus OBJECT-TYPE SYNTAX INTEGER { sensorFailed(0), belowSafeRange(1), inSafeRange(2), aboveSafeRange(3) } MAX-ACCESS read-only STATUS current DESCRIPTION "Status of humidity or temperature" ::= { npRelHumTrapData 4 } npRelHumTrapDataMemo OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Sensor Memo/Location" ::= { npRelHumTrapData 6 } npRelHumTrapDataSafeRangeHigh OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Relative Humidity safe range, top margin, %RH or deg.C" ::= { npRelHumTrapData 7 } npRelHumTrapDataSafeRangeLow OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Relative Humidity safe range, bottom margin, %RH or deg.C" ::= { npRelHumTrapData 8 } npRelHumTrap OBJECT IDENTIFIER::={npRelHumidity 6} npRelHumTrapAllEvents OBJECT IDENTIFIER::={npRelHumTrap 127} npRelHumTrapTemp OBJECT IDENTIFIER::={npRelHumidity 7} npRelHumTrapTempAllEvents OBJECT IDENTIFIER::={npRelHumTrapTemp 127} npRelHumTrapAllChannels NOTIFICATION-TYPE OBJECTS { npRelHumTrapDataN, npRelHumTrapDataStatus, npRelHumTrapDataValue, npRelHumTrapDataMemo, npRelHumTrapDataSafeRangeHigh, npRelHumTrapDataSafeRangeLow } STATUS current DESCRIPTION "Status of Humidity has changed!" ::= { npRelHumTrapAllEvents 99 } npRelHumTrapAboveSafe NOTIFICATION-TYPE OBJECTS { npRelHumTrapDataN, npRelHumTrapDataStatus, npRelHumTrapDataValue, npRelHumTrapDataMemo, npRelHumTrapDataSafeRangeHigh, npRelHumTrapDataSafeRangeLow } STATUS current DESCRIPTION "Humidity above the Safe range" ::= { npRelHumTrap 103 } npRelHumTrapSafe NOTIFICATION-TYPE OBJECTS { npRelHumTrapDataN, npRelHumTrapDataStatus, npRelHumTrapDataValue, npRelHumTrapDataMemo, npRelHumTrapDataSafeRangeHigh, npRelHumTrapDataSafeRangeLow } STATUS current DESCRIPTION "Humidity in the Safe range" ::= { npRelHumTrap 102 } npRelHumTrapBelowSafe NOTIFICATION-TYPE OBJECTS { npRelHumTrapDataN, npRelHumTrapDataStatus, npRelHumTrapDataValue, npRelHumTrapDataMemo, npRelHumTrapDataSafeRangeHigh, npRelHumTrapDataSafeRangeLow } STATUS current DESCRIPTION "Humidity below the Safe range" ::= { npRelHumTrap 101 } npRelHumTrapFail NOTIFICATION-TYPE OBJECTS { npRelHumTrapDataN, npRelHumTrapDataStatus, npRelHumTrapDataValue, npRelHumTrapDataMemo, npRelHumTrapDataSafeRangeHigh, npRelHumTrapDataSafeRangeLow } STATUS current DESCRIPTION "Rel.Humidity sensor failed!" ::= { npRelHumTrap 100 } npRelHumTrapTempAllChannels NOTIFICATION-TYPE OBJECTS { npRelHumTrapDataN, npRelHumTrapDataStatus, npRelHumTrapDataValue, npRelHumTrapDataMemo, npRelHumTrapDataSafeRangeHigh, npRelHumTrapDataSafeRangeLow } STATUS current DESCRIPTION "Status of Temperature has changed!" ::= { npRelHumTrapTempAllEvents 99 } npRelHumTrapTempAboveSafe NOTIFICATION-TYPE OBJECTS { npRelHumTrapDataN, npRelHumTrapDataStatus, npRelHumTrapDataValue, npRelHumTrapDataMemo, npRelHumTrapDataSafeRangeHigh, npRelHumTrapDataSafeRangeLow } STATUS current DESCRIPTION "Temperature above the Safe range" ::= { npRelHumTrapTemp 103 } npRelHumTrapTempSafe NOTIFICATION-TYPE OBJECTS { npRelHumTrapDataN, npRelHumTrapDataStatus, npRelHumTrapDataValue, npRelHumTrapDataMemo, npRelHumTrapDataSafeRangeHigh, npRelHumTrapDataSafeRangeLow } STATUS current DESCRIPTION "Temperature in the Safe range" ::= { npRelHumTrapTemp 102 } npRelHumTrapTempBelowSafe NOTIFICATION-TYPE OBJECTS { npRelHumTrapDataN, npRelHumTrapDataStatus, npRelHumTrapDataValue, npRelHumTrapDataMemo, npRelHumTrapDataSafeRangeHigh, npRelHumTrapDataSafeRangeLow } STATUS current DESCRIPTION "Temperature below the Safe range" ::= { npRelHumTrapTemp 101 } npRelHumTrapTempFail NOTIFICATION-TYPE OBJECTS { npRelHumTrapDataN, npRelHumTrapDataStatus, npRelHumTrapDataValue, npRelHumTrapDataMemo, npRelHumTrapDataSafeRangeHigh, npRelHumTrapDataSafeRangeLow } STATUS current DESCRIPTION "Sensor failed!" ::= { npRelHumTrapTemp 100 } npGsm OBJECT IDENTIFIER::={lightcom 3800} npGsmInfo OBJECT IDENTIFIER::={npGsm 1} npGsmFailed OBJECT-TYPE SYNTAX INTEGER { ok (0), failed (1), fatalError (2) } MAX-ACCESS read-only STATUS current DESCRIPTION "Firmware's GSM module status" ::= { npGsmInfo 1 } npGsmRegistration OBJECT-TYPE SYNTAX INTEGER { impossible (0), homeNetwork (1), searching (2), denied (3), unknown (4), roaming (5), infoUpdate (255) } MAX-ACCESS read-only STATUS current DESCRIPTION "Status of modem registration in GSM network (AT+CREG? result)" ::= { npGsmInfo 2 } npGsmStrength OBJECT-TYPE SYNTAX INTEGER (0..255) MAX-ACCESS read-only STATUS current DESCRIPTION "GSM signal strength. 0..31 = 0..100%, 99 = unknown or n/a, 255 = updating info" ::= { npGsmInfo 3 } npGsmSendSmsUtf8 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Send arbitrary SMS. Format: [phone_number,phone_number,...] Message One to four destination phone numbers If [] and numbers omitted, mesagge will be sent to preset numbers from SMS setup Cyrillic characters must be in UTF8 encoding." ::= { npGsmInfo 9 } npGsmSendSmsWin1251 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Send arbitrary SMS. Format: [phone_number,phone_number,...] Message One to four destination phone numbers If [] and numbers omitted, mesagge will be sent to preset numbers from SMS setup Cyrillic characters must be in Win1251 encoding." ::= { npGsmInfo 10 } npGsmUnparsedRxSmsFrom OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS accessible-for-notify STATUS current DESCRIPTION "Source phone of received unparsed (unknown) Sms" ::= { npGsmInfo 11 } npGsmUnparsedRxSms OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS accessible-for-notify STATUS current DESCRIPTION "Received unparsed Sms with unknown starting word, Encoding Windows-1251" ::= { npGsmInfo 12 } npGsmUnparsedRxSmsUtf8 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS accessible-for-notify STATUS current DESCRIPTION "Received unparsed Sms with unknown starting word, Encoding UTF-8" ::= { npGsmInfo 13 } npGsmTrapUnparsedSms NOTIFICATION-TYPE OBJECTS { npGsmUnparsedRxSmsFrom, npGsmUnparsedRxSms, npGsmUnparsedRxSmsUtf8 } STATUS current DESCRIPTION "forwarding of SMS with wrong starting keyword" ::= { npGsmTrapPrefix 2 } npGsmTraps OBJECT IDENTIFIER::={npGsm 2} npGsmTrapPrefix OBJECT IDENTIFIER::={npGsmTraps 0} npGsmTrap NOTIFICATION-TYPE OBJECTS { npGsmFailed, npGsmRegistration, npGsmStrength } STATUS current DESCRIPTION "GSM modem or SMS firmware problems" ::= { npGsmTrapPrefix 1 } npIr OBJECT IDENTIFIER::={lightcom 7900} npIrCtrl OBJECT IDENTIFIER::={npIr 1} npIrPlayCmd OBJECT-TYPE SYNTAX INTEGER (1..16) MAX-ACCESS read-write STATUS current DESCRIPTION "Write IR command number to send IR command" ::= { npIrCtrl 1 } npIrReset OBJECT-TYPE SYNTAX INTEGER (0..1) MAX-ACCESS read-write STATUS current DESCRIPTION "Write 1 to reset IR transiever. After reset, send IR command and check npIrStatus." ::= { npIrCtrl 2 } npIrStatus OBJECT-TYPE SYNTAX INTEGER { commandCompleted (0), protocolError (1), commandAccepted (2), errorUnknown (16), errorBadNumber (17), errorEmptyRecord (18), errorFlashChip (19), errorTimeout (20), errorExtBusBusy (21) } MAX-ACCESS read-only STATUS current DESCRIPTION "IR transiever status" ::= { npIrCtrl 3 } npReboot OBJECT IDENTIFIER::={ lightcom 911 } npSoftReboot OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Write 1 to reboot device after current operations completition" ::= { npReboot 1 } npResetStack OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Write 1 to re-initialize network stack" ::= { npReboot 2 } npForcedReboot OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Write 1 to immediate forced reboot" ::= { npReboot 3 } END