KMX-RACK DEFINITIONS ::= BEGIN
IMPORTS
enterprises
FROM RFC1155-SMI
OBJECT-TYPE
FROM RFC-1212
TRAP-TYPE
FROM RFC-1215
DisplayString
FROM RFC1213-MIB;
kentix OBJECT IDENTIFIER ::= { enterprises 37954 }
multisensorRack OBJECT IDENTIFIER ::= { kentix 3 }
-- Kentix KMS-RACK MODULE-IDENTITY
-- LAST-UPDATED "20140611"
-- ORGANIZATION
-- "Kentix GmbH"
-- CONTACT-INFO
-- "info@kentix.de"
-- DESCRIPTION
-- "KMS-RACK MIB module"
--
-- REVISION "20140611REV01"
-- DESCRIPTION
-- "MIB Release version 1.0"
-- ::= { multisensorRack }
datapoints OBJECT IDENTIFIER ::= { multisensorRack 1 }
-- Temperature
temperatureEntry OBJECT IDENTIFIER ::= { datapoints 1 }
temperatureValue OBJECT-TYPE
SYNTAX INTEGER (0..1000)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Temperature on the Kentix KMS-RACK for that datatpoint (Factor 0.1)"
::= { temperatureEntry 1 }
temperatureMin OBJECT-TYPE
SYNTAX INTEGER (0..99)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Temperature Min on the Kentix KMS-RACK for that datatpoint"
::= { temperatureEntry 2 }
temperatureMax OBJECT-TYPE
SYNTAX INTEGER (0..99)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Temperature Max on the Kentix KMS-RACK for that datatpoint"
::= { temperatureEntry 3 }
temperatureAlarm OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Alarm on the Kentix KMS-RACK for that datatpoint"
::= { temperatureEntry 4 }
temperatureAlarmtext OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Alarmmessage on the Kentix KMS-RACK for that datatpoint"
::= { temperatureEntry 5 }
temperatureAlarmArm OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Arm/Disarm TemperatureAlarm on the Kentix KMS-RACK"
::= { temperatureEntry 6 }
-- Humidity
humidityEntry OBJECT IDENTIFIER ::= { datapoints 2 }
humidityValue OBJECT-TYPE
SYNTAX INTEGER (0..1000)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Humidity on the Kentix KMS-RACK for that datatpoint (Factor 0.1)"
::= { humidityEntry 1 }
humidityMin OBJECT-TYPE
SYNTAX INTEGER (0..99)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Humidity Min on the Kentix KMS-RACK for that datatpoint"
::= { humidityEntry 2 }
humidityMax OBJECT-TYPE
SYNTAX INTEGER (0..99)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Humidity Max on the Kentix KMS-RACK for that datatpoint"
::= { humidityEntry 3 }
humidityAlarm OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Alarm on the Kentix KMS-RACK for that datatpoint"
::= { humidityEntry 4 }
humidityAlarmtext OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Alarmmessage on the Kentix KMS-RACK for that datatpoint"
::= { humidityEntry 5 }
humidityAlarmArm OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Arm/Disarm HumidityAlarm on the Kentix KMS-RACK"
::= { humidityEntry 6 }
-- Dewpoint
dewpointEntry OBJECT IDENTIFIER ::= { datapoints 3 }
dewpointValue OBJECT-TYPE
SYNTAX INTEGER (0..1000)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Dewpoint on the Kentix KMS-RACK for that datatpoint (Factor 0.1)"
::= { dewpointEntry 1 }
dewpointMin OBJECT-TYPE
SYNTAX INTEGER (0..99)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Dewpoint Min on the Kentix KMS-RACK for that datatpoint"
::= { dewpointEntry 2 }
dewpointAlarm OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Alarm on the Kentix KMS-RACK for that datatpoint"
::= { dewpointEntry 3 }
dewpointAlarmtext OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Alarmmessage on the Kentix KMS-RACK for that datatpoint"
::= { dewpointEntry 4 }
dewpointAlarmArm OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Arm/Disarm DewpointAlarm on the Kentix KMS-RACK"
::= { dewpointEntry 6 }
-- Carbon Monoxide
coEntry OBJECT IDENTIFIER ::= { datapoints 4 }
coValue OBJECT-TYPE
SYNTAX INTEGER (-100..100)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Carbon Monoxide on the Kentix KMS-RACK for that datatpoint"
::= { coEntry 1 }
coMax OBJECT-TYPE
SYNTAX INTEGER (0..99)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Carbon Monoxide Min on the Kentix KMS-RACK for that datatpoint"
::= { coEntry 2 }
coAlarm OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Alarm on the Kentix KMS-RACK for that datatpoint"
::= { coEntry 3 }
coAlarmtext OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Alarmmessage on the Kentix KMS-RACK for that datatpoint"
::= { coEntry 4 }
coAlarmArm OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Arm/Disarm COAlarm on the Kentix KMS-RACK"
::= { coEntry 6 }
-- Motion
motionEntry OBJECT IDENTIFIER ::= { datapoints 5 }
motionValue OBJECT-TYPE
SYNTAX INTEGER (0..100)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Motion on the Kentix KMS-RACK for that datatpoint"
::= { motionEntry 1 }
motionMax OBJECT-TYPE
SYNTAX INTEGER (0..99)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Motion Min on the Kentix KMS-RACK for that datatpoint"
::= { motionEntry 2 }
motionAlarm OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Alarm on the Kentix KMS-RACK for that datatpoint"
::= { motionEntry 3 }
motionAlarmtext OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Alarmmessage on the Kentix KMS-RACK for that datatpoint"
::= { motionEntry 4 }
motionAlarmArm OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Arm/Disarm MotionAlarm on the Kentix KMS-RACK"
::= { motionEntry 6 }
-- Digital IN 1
digitalIn1 OBJECT IDENTIFIER ::= { datapoints 6 }
digitalIn1Value OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Digital IN 1 on the Kentix KMS-RACK for that datatpoint"
::= { digitalIn1 1 }
digitalIn1Name OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Digital IN 1 on the Kentix KMS-RACK for that datatpoint"
::= { digitalIn1 2 }
-- Digital IN 2
digitalIn2 OBJECT IDENTIFIER ::= { datapoints 7 }
digitalIn2Value OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Digital IN 2 on the Kentix KMS-RACK for that datatpoint"
::= { digitalIn2 1 }
digitalIn2Name OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Digital IN 2 on the Kentix KMS-RACK for that datatpoint"
::= { digitalIn2 2 }
-- Digital OUT 2
digitalOut2 OBJECT IDENTIFIER ::= { datapoints 8 }
digitalOut2Value OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Digital OUT 2 on the Kentix KMS-RACK for that datatpoint"
::= { digitalOut2 1 }
buzzerTime OBJECT IDENTIFIER ::= { datapoints 9 }
buzzerTimeValue OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Buzzer on the Kentix KMS-RACK for that datatpoint"
::= { buzzerTime 1 }
-- RelayTime
relayTime OBJECT IDENTIFIER ::= { datapoints 10 }
relayTimeValue OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Buzzer Time on the Kentix KMS-RACK for that datatpoint"
::= { relayTime 1 }
-- Arm-Disarm Motion
rearmMotion OBJECT IDENTIFIER ::= { datapoints 11 }
rearmMotionValue OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Arm-Disarm Motion on the Kentix KMS-RACK for that datatpoint"
::= { rearmMotion 1 }
-- pdu1
pdu1 OBJECT IDENTIFIER ::= { datapoints 12 }
pdu1activepowerValue OBJECT-TYPE
SYNTAX INTEGER (0..100000)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Active power value of pdu1 on the Kentix KMS-RACK (Factor 0.1)"
::= { pdu1 1 }
pdu1apparentpowerValue OBJECT-TYPE
SYNTAX INTEGER (0..100000)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Apparrnt power value of pdu1 on the Kentix KMS-RACK (Factor 0.1)"
::= { pdu1 2 }
pdu1energyValue OBJECT-TYPE
SYNTAX INTEGER (0..40000000)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Energy value of pdu1 on the Kentix KMS-RACK (Factor 0.1)"
::= { pdu1 3 }
pdu1energycostsValue OBJECT-TYPE
SYNTAX INTEGER (0..40000000)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Energy costs value of pdu1 on the Kentix KMS-RACK (Factor 0.1)"
::= { pdu1 4 }
pdu1currentValue OBJECT-TYPE
SYNTAX INTEGER (0..1000)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Current value of pdu1 on the Kentix KMS-RACK (Factor 0.1)"
::= { pdu1 5 }
pdu1voltageValue OBJECT-TYPE
SYNTAX INTEGER (0..10000)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Voltage value of pdu1 on the Kentix KMS-RACK (Factor 0.1)"
::= { pdu1 6 }
pdu1powerfactorValue OBJECT-TYPE
SYNTAX INTEGER (0..1000)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Power factor of pdu1 on the Kentix KMS-RACK (Factor 0.1)"
::= { pdu1 7 }
pdu1frequencyValue OBJECT-TYPE
SYNTAX INTEGER (0..1000)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Frequency of pdu1 on the Kentix KMS-RACK (Factor 0.1)"
::= { pdu1 8 }
pdu1VoltageFlicker OBJECT IDENTIFIER ::= { pdu1 9 }
pdu1VoltageFlickerValue OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Flicker (low voltage) value of pdu1 on the Kentix KMS-RACK."
::= { pdu1VoltageFlicker 1 }
pdu1VoltageFlickerTime OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Last Flicker (low voltage) time of pdu1 on the Kentix KMS-RACK."
::= { pdu1VoltageFlicker 2 }
pdu1VoltageFlickerState OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Alarmstate Flicker (low voltage) of pdu1 on the Kentix KMS-RACK."
::= { pdu1VoltageFlicker 3 }
pdu1VoltageSwell OBJECT IDENTIFIER ::= { pdu1 10 }
pdu1VoltageSwellValue OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Voltage swell value of pdu1 on the Kentix KMS-RACK."
::= { pdu1VoltageSwell 1 }
pdu1VoltageSwellTime OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Last voltage swell time of pdu1 on the Kentix KMS-RACK."
::= { pdu1VoltageSwell 2 }
pdu1VoltageSwellState OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Alarmstate voltage swell of pdu1 on the Kentix KMS-RACK."
::= { pdu1VoltageSwell 3 }
pdu1VoltagePeak OBJECT IDENTIFIER ::= { pdu1 11 }
pdu1VoltagePeakValue OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"VoltagePeakvoltage value of pdu1 on the Kentix KMS-RACK."
::= { pdu1VoltagePeak 1 }
pdu1VoltagePeakTime OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Last peakvoltage time of pdu1 on the Kentix KMS-RACK."
::= { pdu1VoltagePeak 2 }
pdu1VoltagePeakState OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Alarmstate peakvoltage of pdu1 on the Kentix KMS-RACK."
::= { pdu1VoltagePeak 3 }
-- pdu2
pdu2 OBJECT IDENTIFIER ::= { datapoints 13 }
pdu2activepowerValue OBJECT-TYPE
SYNTAX INTEGER (0..100000)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Active power value of pdu2 on the Kentix KMS-RACK (Factor 0.1)"
::= { pdu2 1 }
pdu2apparentpowerValue OBJECT-TYPE
SYNTAX INTEGER (0..100000)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Apparrnt power value of pdu2 on the Kentix KMS-RACK (Factor 0.1)"
::= { pdu2 2 }
pdu2energyValue OBJECT-TYPE
SYNTAX INTEGER (0..40000000)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Energy value of pdu2 on the Kentix KMS-RACK (Factor 0.1)"
::= { pdu2 3 }
pdu2energycostsValue OBJECT-TYPE
SYNTAX INTEGER (0..40000000)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Energy costs value of pdu2 on the Kentix KMS-RACK (Factor 0.1)"
::= { pdu2 4 }
pdu2currentValue OBJECT-TYPE
SYNTAX INTEGER (0..1000)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Current value of pdu2 on the Kentix KMS-RACK (Factor 0.1)"
::= { pdu2 5 }
pdu2voltageValue OBJECT-TYPE
SYNTAX INTEGER (0..10000)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Voltage value of pdu2 on the Kentix KMS-RACK (Factor 0.1)"
::= { pdu2 6 }
pdu2powerfactorValue OBJECT-TYPE
SYNTAX INTEGER (0..1000)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Power factor of pdu2 on the Kentix KMS-RACK (Factor 0.1)"
::= { pdu2 7 }
pdu2frequencyValue OBJECT-TYPE
SYNTAX INTEGER (0..1000)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Frequency of pdu2 on the Kentix KMS-RACK (Factor 0.1)"
::= { pdu2 8 }
pdu2VoltageFlicker OBJECT IDENTIFIER ::= { pdu2 9 }
pdu2VoltageFlickerValue OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Flicker (low voltage) value of pdu2 on the Kentix KMS-RACK."
::= { pdu2VoltageFlicker 1 }
pdu2VoltageFlickerTime OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Last Flicker (low voltage) time of pdu2 on the Kentix KMS-RACK."
::= { pdu2VoltageFlicker 2 }
pdu2VoltageFlickerState OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Alarmstate Flicker (low voltage) of pdu2 on the Kentix KMS-RACK."
::= { pdu2VoltageFlicker 3 }
pdu2VoltageSwell OBJECT IDENTIFIER ::= { pdu2 10 }
pdu2VoltageSwellValue OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Voltage swell value of pdu2 on the Kentix KMS-RACK."
::= { pdu2VoltageSwell 1 }
pdu2VoltageSwellTime OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Last voltage swell time of pdu2 on the Kentix KMS-RACK."
::= { pdu2VoltageSwell 2 }
pdu2VoltageSwellState OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Alarmstate voltage swell of pdu2 on the Kentix KMS-RACK."
::= { pdu2VoltageSwell 3 }
pdu2VoltagePeak OBJECT IDENTIFIER ::= { pdu2 11 }
pdu2VoltagePeakValue OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Peakvoltage value of pdu2 on the Kentix KMS-RACK."
::= { pdu2VoltagePeak 1 }
pdu2VoltagePeakTime OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Last peakvoltage time of pdu2 on the Kentix KMS-RACK."
::= { pdu2VoltagePeak 2 }
pdu2VoltagePeakState OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Alarmstate peakvoltage of pdu2 on the Kentix KMS-RACK."
::= { pdu2VoltagePeak 3 }
-- pdu1
pdusum OBJECT IDENTIFIER ::= { datapoints 14 }
pdusumactivepowerValue OBJECT-TYPE
SYNTAX INTEGER (0..100000)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Active power value of all pdus the Kentix KMS-RACK (Factor 0.1)"
::= { pdusum 1 }
pdusumapparentpowerValue OBJECT-TYPE
SYNTAX INTEGER (0..100000)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Apparrnt power value of all pdus the Kentix KMS-RACK (Factor 0.1)"
::= { pdusum 2 }
pdusumenergyValue OBJECT-TYPE
SYNTAX INTEGER (0..40000000)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Energy value of all pdus the Kentix KMS-RACK (Factor 0.1)"
::= { pdusum 3 }
pdusumenergycostsValue OBJECT-TYPE
SYNTAX INTEGER (0..40000000)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Energy costs value of all pdus the Kentix KMS-RACK (Factor 0.1)"
::= { pdusum 4 }
pdusumcurrentValue OBJECT-TYPE
SYNTAX INTEGER (0..1000)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Current value of all pdus the Kentix KMS-RACK (Factor 0.1)"
::= { pdusum 5 }
pdusumvoltageValue OBJECT-TYPE
SYNTAX INTEGER (0..10000)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Voltage value of all pdus the Kentix KMS-RACK (Factor 0.1)"
::= { pdusum 6 }
pdusumpowerfactorValue OBJECT-TYPE
SYNTAX INTEGER (0..1000)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Power factor of all pdus the Kentix KMS-RACK (Factor 0.1)"
::= { pdusum 7 }
pdusumfrequencyValue OBJECT-TYPE
SYNTAX INTEGER (0..1000)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Frequency of all pdus the Kentix KMS-RACK (Factor 0.1)"
::= { pdusum 8 }
alarmText OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Alarm Text send to the Manager"
::= { multisensorRack 2 }
wrongLogin TRAP-TYPE
ENTERPRISE kentix
DESCRIPTION
"wrong login of a user"
::= 1
login TRAP-TYPE
ENTERPRISE kentix
DESCRIPTION
"login of user"
::= 2
alarm TRAP-TYPE
ENTERPRISE kentix
VARIABLES { alarmText }
DESCRIPTION
"SNMP Trap for each multisensor alarm"
::= 3
END