HUAWEI-UPS-MIB DEFINITIONS ::= BEGIN
|
||
IMPORTS
|
||
huaweiUtility
|
||
FROM HUAWEI-MIB
|
||
OBJECT-GROUP, NOTIFICATION-GROUP
|
||
FROM SNMPv2-CONF
|
||
Integer32, Unsigned32, OBJECT-TYPE, MODULE-IDENTITY, NOTIFICATION-TYPE
|
||
FROM SNMPv2-SMI
|
||
TEXTUAL-CONVENTION
|
||
FROM SNMPv2-TC;
|
||
hwUpsMIB MODULE-IDENTITY
|
||
LAST-UPDATED "201210240000Z"
|
||
ORGANIZATION
|
||
"Huawei Technologies Co., Ltd."
|
||
CONTACT-INFO
|
||
"Floor 5, Block 4, R&D Building,
|
||
Huawei Longgang Production Base,
|
||
Shenzhen, P.R.C.
|
||
http: // www.huawei.com
|
||
Zip: 518129."
|
||
DESCRIPTION
|
||
"EMAP MIB defines MIB objects which provides load and backup management, patch management NMS interfaces.
|
||
The current version is v1.01"
|
||
REVISION "201210240000Z"
|
||
DESCRIPTION
|
||
"Huawei emap mib v1.00"
|
||
::= { huaweiUtility 174 }
|
||
|
||
DisplayString ::= TEXTUAL-CONVENTION
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
SYNTAX OCTET STRING (SIZE (1..64))
|
||
|
||
RowStatus ::= TEXTUAL-CONVENTION
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
SYNTAX INTEGER
|
||
{
|
||
active(1),
|
||
notInService(2),
|
||
notReady(3),
|
||
createAndGo(4),
|
||
createAndWait(5),
|
||
destroy(6)
|
||
}
|
||
|
||
DateAndTime ::= TEXTUAL-CONVENTION
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
SYNTAX OCTET STRING (SIZE (8..11))
|
||
|
||
RunStatus ::= TEXTUAL-CONVENTION
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This integer value represents running status of the system.
|
||
Depending on situation there may be limits on allowed values.
|
||
Operational values:
|
||
(1) unknown - status has not yet been defined
|
||
(2) normal - there are no activated alarms
|
||
(3) alarm - alarm status
|
||
"
|
||
SYNTAX INTEGER
|
||
{
|
||
unknow(1),
|
||
normal(2),
|
||
alarm(3)
|
||
}
|
||
|
||
MeasuresRange ::= TEXTUAL-CONVENTION
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
SYNTAX Integer32
|
||
|
||
TruthValue ::= TEXTUAL-CONVENTION
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
SYNTAX INTEGER
|
||
{
|
||
true(1),
|
||
false(2)
|
||
}
|
||
hwUpsMIBObjects OBJECT IDENTIFIER ::= { hwUpsMIB 1 }
|
||
|
||
hwUpsSystem OBJECT IDENTIFIER ::= { hwUpsMIBObjects 1 }
|
||
|
||
hwUpsSysIdent OBJECT IDENTIFIER ::= { hwUpsSystem 1 }
|
||
|
||
hwUpsSystemMainDeviceESN OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..127))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ESN of the master device used for setting up a NetEco model. A string of characters."
|
||
::= { hwUpsSysIdent 1 }
|
||
|
||
hwUpsSystemType OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..127))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Name of the UPS system. A string of characters. Configurable."
|
||
::= { hwUpsSysIdent 2 }
|
||
|
||
hwUpsSysInerProtVersion OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..127))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Version number of the system interface protocol between the NetEco and NEs.
|
||
A string of characters."
|
||
::= { hwUpsSysIdent 3 }
|
||
|
||
hwUpsSysDeviceNum OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..63)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Number of devices in the system. An integer ranging from 0 to 63."
|
||
::= { hwUpsSysIdent 4 }
|
||
|
||
hwUpsParallelSysNum OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..63)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Number of parallel systems. An integer ranging from 0 to 63."
|
||
::= { hwUpsSysIdent 5 }
|
||
|
||
hwUpsEnvTemper OBJECT-TYPE
|
||
SYNTAX Integer32 ( -500..1200)
|
||
UNITS "C"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ambient temperature. An integer ranging from -50 to 120.
|
||
The value is accurate to one decimal place on the NetEco. The unit is C"
|
||
::= { hwUpsSysIdent 6 }
|
||
|
||
hwUpsEnvHumidity OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..1000)
|
||
UNITS "%"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ambient humidity. An integer ranging from 0 to 100.
|
||
The value is accurate to one decimal place on the NetEco. The unit is %."
|
||
::= { hwUpsSysIdent 7 }
|
||
|
||
hwUpsDevice OBJECT IDENTIFIER ::= { hwUpsMIBObjects 2 }
|
||
|
||
hwUpsDeviceIdentTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwUpsDeviceIdentEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The device identification table. Use this table to get device ID, and to get device type,
|
||
the soft version, the iner prot version, the ESN, the rating power of device,
|
||
the parallel system index of device. This table's index is hwUpsDeviceId."
|
||
::= { hwUpsDevice 100 }
|
||
|
||
hwUpsDeviceIdentEntry OBJECT-TYPE
|
||
SYNTAX HwUpsDeviceIdentEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The device identification table. Use this table to get device ID, and to get device type,
|
||
the soft version, the iner prot version, the ESN, the rating power of device,
|
||
the parallel system index of device. This table's index is hwUpsDeviceId."
|
||
INDEX { hwUpsDeviceId }
|
||
::= { hwUpsDeviceIdentTable 1 }
|
||
|
||
HwUpsDeviceIdentEntry ::= SEQUENCE {
|
||
hwUpsDeviceId
|
||
Unsigned32,
|
||
hwUpsDeviceType
|
||
OCTET STRING,
|
||
hwUpsDeviceSoftVersion
|
||
OCTET STRING,
|
||
hwUpsDeviceInerProtVersion
|
||
OCTET STRING,
|
||
hwUpsDeviceESN
|
||
OCTET STRING,
|
||
hwUpsDevicePowerRating
|
||
INTEGER,
|
||
hwUpsDeviceParaSysIndex
|
||
Unsigned32,
|
||
hwUpsDeviceSysGrant
|
||
Unsigned32,
|
||
hwUpsDeviceMonitorSoftVersion
|
||
OCTET STRING,
|
||
hwUpsDevicePowerSoftVersion
|
||
OCTET STRING,
|
||
hwUpsDeviceIdentRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwUpsDeviceId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (1..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack ID, ranging from 1 to 100. This node is referenced as an index node
|
||
by hwUpsDeviceIdentTable, hwUpsDeviceOperInfoTable, hwUpsInputTable,
|
||
hwUpsOutputTable,hwUpsBypassTable, hwUpsBatteryTable, hwUpsControlTable,
|
||
and hwUpsBattScheduleTestTable."
|
||
::= { hwUpsDeviceIdentEntry 1 }
|
||
|
||
hwUpsDeviceType OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..127))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Device model. A string of characters."
|
||
::= { hwUpsDeviceIdentEntry 2 }
|
||
|
||
hwUpsDeviceSoftVersion OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..127))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Device software version number. A string of characters."
|
||
::= { hwUpsDeviceIdentEntry 3 }
|
||
|
||
hwUpsDeviceInerProtVersion OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..127))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Interface protocol version number for the current device. A string of characters."
|
||
::= { hwUpsDeviceIdentEntry 4 }
|
||
|
||
hwUpsDeviceESN OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..127))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ESN. A string of characters."
|
||
::= { hwUpsDeviceIdentEntry 5 }
|
||
|
||
hwUpsDevicePowerRating OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
level80(1),
|
||
level100(2),
|
||
level120(3),
|
||
level160(4),
|
||
level200(5),
|
||
level30(6),
|
||
level40(7),
|
||
level60(8),
|
||
level240(9),
|
||
level250(10),
|
||
level280(11),
|
||
level300(12)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"System capacity. Enumeration type. The default value is 5. The unit is kVA.
|
||
Value 1 indicates 80 kVA
|
||
Value 2 indicates 100 kVA.
|
||
Value 3 indicates 120 kVA.
|
||
Value 4 indicates 160 kVA.
|
||
Value 5 indicates 200 kVA."
|
||
::= { hwUpsDeviceIdentEntry 6 }
|
||
|
||
hwUpsDeviceParaSysIndex OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..63)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ID of the parallel system that the current device belongs to. An integer ranging from 0 to 63."
|
||
::= { hwUpsDeviceIdentEntry 7 }
|
||
|
||
hwUpsDeviceSysGrant OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"System grant.An integer ranging from 0 to 10000."
|
||
::= { hwUpsDeviceIdentEntry 8 }
|
||
|
||
hwUpsDeviceMonitorSoftVersion OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..127))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Monitor software version number. A string of characters."
|
||
::= { hwUpsDeviceIdentEntry 9 }
|
||
|
||
hwUpsDevicePowerSoftVersion OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..127))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Power software version number A string of characters."
|
||
::= { hwUpsDeviceIdentEntry 10 }
|
||
|
||
hwUpsDeviceIdentRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus of UPS device Identification table."
|
||
::= { hwUpsDeviceIdentEntry 100 }
|
||
|
||
hwUpsDeviceOperInfoTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwUpsDeviceOperInfoEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Device running information table. It's index is hwUpsDeviceId"
|
||
::= { hwUpsDevice 101 }
|
||
|
||
hwUpsDeviceOperInfoEntry OBJECT-TYPE
|
||
SYNTAX HwUpsDeviceOperInfoEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Device running information table. It's index is hwUpsDeviceId"
|
||
INDEX { hwUpsDeviceId }
|
||
::= { hwUpsDeviceOperInfoTable 1 }
|
||
|
||
HwUpsDeviceOperInfoEntry ::= SEQUENCE {
|
||
hwUpsDevicePowerSupplyMethod
|
||
INTEGER,
|
||
hwUpsDeviceRunningStatus
|
||
INTEGER,
|
||
hwUpsDeviceBatteryState
|
||
INTEGER,
|
||
hwUpsDeviceTemperature
|
||
Unsigned32,
|
||
hwUpsDeviceEnergyFloatState
|
||
Unsigned32,
|
||
hwUpsDeviceRedundantNumber
|
||
Unsigned32,
|
||
hwUpsDeviceDelayShutdownState
|
||
Unsigned32,
|
||
hwUpsDeviceDelayShutdownOrder
|
||
INTEGER,
|
||
hwUpsDeviceWorkMode
|
||
INTEGER,
|
||
hwUpsDeviceSmartPowerMode
|
||
INTEGER,
|
||
hwUpsDeviceBSCState
|
||
INTEGER,
|
||
hwUpsDeviceOperInfoRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwUpsDevicePowerSupplyMethod OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
noOutput(1),
|
||
bypass(2),
|
||
normal(3),
|
||
battery(4),
|
||
sourceShare(5),
|
||
normalECO(6),
|
||
batteryECO(7)
|
||
|
||
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Device power supply mode. Enumeration type.
|
||
Value 1 indicates no power supply.
|
||
Value 2 indicates bypass mode.
|
||
Value 3 indicates normal mode.
|
||
Value 4 indicates battery mode.
|
||
Value 5 indicates combined mode.
|
||
Value 6 indicates mains ECO mode.
|
||
Value 7 indicates battery ECO mode."
|
||
::= { hwUpsDeviceOperInfoEntry 1 }
|
||
|
||
hwUpsDeviceRunningStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
single(1),
|
||
parallel(2),
|
||
singleECO(3),
|
||
parallelECO(4),
|
||
aging(5)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"UPS operating status. Enumeration type.
|
||
Value 1 indicates that a single UPS is operating.
|
||
Value 2 indicates that the parallel system is operating.
|
||
Value 3 indicates that a single UPS is operating in ECO mode.
|
||
Value 4 indicates that the parallel system is operating in ECO mode.
|
||
Value 5 indicates aging."
|
||
::= { hwUpsDeviceOperInfoEntry 2 }
|
||
|
||
hwUpsDeviceBatteryState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
notExist(1),
|
||
temperaryMode(2),
|
||
sleep(3),
|
||
floatCharge(4),
|
||
boostCharge(5),
|
||
discharge(6)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery status. Enumeration type.
|
||
Value 1 indicates that no battery is connected.
|
||
Value 2 indicates that the battery is not charging or discharging.
|
||
Value 3 indicates hibernation.
|
||
Value 4 indicates float charging.
|
||
Value 5 indicates equalized charging.
|
||
Value 6 indicates discharging."
|
||
::= { hwUpsDeviceOperInfoEntry 3 }
|
||
|
||
hwUpsDeviceTemperature OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..3000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Maximum temperature of the modules in the current device. An integer ranging from 0 to 300."
|
||
::= { hwUpsDeviceOperInfoEntry 4 }
|
||
|
||
hwUpsDeviceEnergyFloatState OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..70000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Current flow status. An integer ranging from 0 to 70000. "
|
||
::= { hwUpsDeviceOperInfoEntry 5 }
|
||
|
||
hwUpsDeviceRedundantNumber OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..3)
|
||
MAX-ACCESS read-only
|
||
STATUS obsolete
|
||
DESCRIPTION
|
||
"Redundant number of the parallel system. An integer ranging from 0 to 3."
|
||
::= { hwUpsDeviceOperInfoEntry 6 }
|
||
|
||
hwUpsDeviceDelayShutdownState OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..4294967295)
|
||
MAX-ACCESS read-only
|
||
STATUS obsolete
|
||
DESCRIPTION
|
||
"Delay to shutdown state. An integer ranging from 0 to 4294967295"
|
||
::= { hwUpsDeviceOperInfoEntry 7 }
|
||
|
||
hwUpsDeviceDelayShutdownOrder OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
invalid(1),
|
||
valid(2)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS obsolete
|
||
DESCRIPTION
|
||
"Delay to shutdown state. Enumeration type.
|
||
Value 1 indicates invalid.
|
||
Value 2 indicates valid."
|
||
::= { hwUpsDeviceOperInfoEntry 8 }
|
||
|
||
hwUpsDeviceWorkMode OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normalMode(1),
|
||
ecoMode(2),
|
||
selfloadMode(3),
|
||
converterMode(4)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Work Mode. Enumeration type.
|
||
Value 1 indicates that normal mode.
|
||
Value 2 indicates that eco mode.
|
||
Value 3 indicates that self load mode.
|
||
Value 4 indicates that converter mode.
|
||
"
|
||
::= { hwUpsDeviceOperInfoEntry 9 }
|
||
|
||
hwUpsDeviceSmartPowerMode OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
disable(1),
|
||
enable(2)
|
||
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Smart Power Mode.Enumeration type.
|
||
Value 1 indicates that disable.
|
||
Value 2 indicates that enable.
|
||
|
||
"
|
||
::= { hwUpsDeviceOperInfoEntry 10 }
|
||
|
||
hwUpsDeviceBSCState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
notExist(1),
|
||
masterMode(2),
|
||
slaveMode(3)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"BSC system status. Enumeration type.
|
||
Value 1: Not activated
|
||
Value 2: BSC master mode
|
||
Value 3: BSC slave mode"
|
||
::= { hwUpsDeviceOperInfoEntry 11 }
|
||
|
||
hwUpsDeviceOperInfoRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus of UPS device running information table."
|
||
::= { hwUpsDeviceOperInfoEntry 101 }
|
||
|
||
hwUpsInput OBJECT IDENTIFIER ::= { hwUpsMIBObjects 3 }
|
||
|
||
hwUpsInputTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwUpsInputEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"UPS input information table. It's index is hwUpsDeviceId"
|
||
::= { hwUpsInput 100 }
|
||
|
||
hwUpsInputEntry OBJECT-TYPE
|
||
SYNTAX HwUpsInputEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"UPS input information table. It's index is hwUpsDeviceId"
|
||
INDEX { hwUpsDeviceId }
|
||
::= { hwUpsInputTable 1 }
|
||
|
||
HwUpsInputEntry ::= SEQUENCE {
|
||
hwUpsInputVoltageA
|
||
Unsigned32,
|
||
hwUpsInputVoltageB
|
||
Unsigned32,
|
||
hwUpsInputVoltageC
|
||
Unsigned32,
|
||
hwUpsInputFrequency
|
||
Unsigned32,
|
||
hwUpsInputCurrentA
|
||
Unsigned32,
|
||
hwUpsInputCurrentB
|
||
Unsigned32,
|
||
hwUpsInputCurrentC
|
||
Unsigned32,
|
||
hwUpsInputPowerFactorA
|
||
Integer32,
|
||
hwUpsInputPowerFactorB
|
||
Integer32,
|
||
hwUpsInputPowerFactorC
|
||
Integer32,
|
||
hwUpsInputLineVoltageAB
|
||
Unsigned32,
|
||
hwUpsInputLineVoltageBC
|
||
Unsigned32,
|
||
hwUpsInputLineVoltageCA
|
||
Unsigned32,
|
||
hwUpsInputRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwUpsInputVoltageA OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Input voltage phase A. The value ranges from 0 to 10000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is V."
|
||
::= { hwUpsInputEntry 1 }
|
||
|
||
hwUpsInputVoltageB OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
UNITS "V"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Input voltage phase B. The value ranges from 0 to 10000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is V."
|
||
::= { hwUpsInputEntry 2 }
|
||
|
||
hwUpsInputVoltageC OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
UNITS "V"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Input voltage phase C. The value ranges from 0 to 10000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is V."
|
||
::= { hwUpsInputEntry 3 }
|
||
|
||
hwUpsInputFrequency OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
UNITS "Hz"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Input frequency. The value ranges from 0 to 10000.
|
||
The value is accurate to two decimal place on the NetEco. The unit is Hz."
|
||
::= { hwUpsInputEntry 4 }
|
||
|
||
hwUpsInputCurrentA OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Input current phase A. The value ranges from 0 to 10000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is A."
|
||
::= { hwUpsInputEntry 5 }
|
||
|
||
hwUpsInputCurrentB OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
UNITS "A"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Input current phase B. The value ranges from 0 to 10000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is A."
|
||
::= { hwUpsInputEntry 6 }
|
||
|
||
hwUpsInputCurrentC OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
UNITS "A"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Input current phase C. The value ranges from 0 to 10000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is A."
|
||
::= { hwUpsInputEntry 7 }
|
||
|
||
hwUpsInputPowerFactorA OBJECT-TYPE
|
||
SYNTAX Integer32 ( -100..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Phase A input power factor. The value ranges from -100 to 100.
|
||
The value is accurate to one decimal place on the NetEco."
|
||
::= { hwUpsInputEntry 8 }
|
||
|
||
hwUpsInputPowerFactorB OBJECT-TYPE
|
||
SYNTAX Integer32 ( -100..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Phase B input power factor. The value ranges from -100 to 100.
|
||
The value is accurate to one decimal place on the NetEco."
|
||
::= { hwUpsInputEntry 9 }
|
||
|
||
hwUpsInputPowerFactorC OBJECT-TYPE
|
||
SYNTAX Integer32 ( -100..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Phase C input power factor. The value ranges from -100 to 100.
|
||
The value is accurate to one decimal place on the NetEco."
|
||
::= { hwUpsInputEntry 10 }
|
||
|
||
hwUpsInputLineVoltageAB OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..20000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Input Line voltage AB. The value ranges from 0 to 20000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is V."
|
||
::= { hwUpsInputEntry 11 }
|
||
|
||
hwUpsInputLineVoltageBC OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..20000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Input Line voltage BC. The value ranges from 0 to 20000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is V."
|
||
::= { hwUpsInputEntry 12 }
|
||
|
||
hwUpsInputLineVoltageCA OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..20000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Input Line voltage CA. The value ranges from 0 to 20000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is V."
|
||
::= { hwUpsInputEntry 13 }
|
||
|
||
hwUpsInputRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus of UPS input information table."
|
||
::= { hwUpsInputEntry 100 }
|
||
|
||
hwUpsOutput OBJECT IDENTIFIER ::= { hwUpsMIBObjects 4 }
|
||
|
||
hwUpsOutputTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwUpsOutputEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"UPS output information table. It's index is hwUpsDeviceId."
|
||
::= { hwUpsOutput 100 }
|
||
|
||
hwUpsOutputEntry OBJECT-TYPE
|
||
SYNTAX HwUpsOutputEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"UPS output information table. It's index is hwUpsDeviceId.
|
||
"
|
||
INDEX { hwUpsDeviceId }
|
||
::= { hwUpsOutputTable 1 }
|
||
|
||
HwUpsOutputEntry ::= SEQUENCE {
|
||
hwUpsOutputVoltageA
|
||
Unsigned32,
|
||
hwUpsOutputVoltageB
|
||
Unsigned32,
|
||
hwUpsOutputVoltageC
|
||
Unsigned32,
|
||
hwUpsOutputCurrentA
|
||
Unsigned32,
|
||
hwUpsOutputCurrentB
|
||
Unsigned32,
|
||
hwUpsOutputCurrentC
|
||
Unsigned32,
|
||
hwUpsOutputFrequency
|
||
Unsigned32,
|
||
hwUpsOutputActivePowerA
|
||
Integer32,
|
||
hwUpsOutputActivePowerB
|
||
Integer32,
|
||
hwUpsOutputActivePowerC
|
||
Integer32,
|
||
hwUpsOutputAppearancePowerA
|
||
Integer32,
|
||
hwUpsOutputAppearancePowerB
|
||
Integer32,
|
||
hwUpsOutputAppearancePowerC
|
||
Integer32,
|
||
hwUpsOutputLoadA
|
||
Unsigned32,
|
||
hwUpsOutputLoadB
|
||
Unsigned32,
|
||
hwUpsOutputLoadC
|
||
Unsigned32,
|
||
hwUpsOutputPowerRating
|
||
INTEGER,
|
||
hwUpsOutputFrequencyRating
|
||
INTEGER,
|
||
hwUpsOutputPowerFactorA
|
||
Integer32,
|
||
hwUpsOutputPowerFactorB
|
||
Integer32,
|
||
hwUpsOutputPowerFactorC
|
||
Integer32,
|
||
hwUpsOutputLineVoltageAB
|
||
Unsigned32,
|
||
hwUpsOutputLineVoltageBC
|
||
Unsigned32,
|
||
hwUpsOutputLineVoltageCA
|
||
Unsigned32,
|
||
hwUpsRackOutputPeakRatioA
|
||
Unsigned32,
|
||
hwUpsRackOutputPeakRatioB
|
||
Unsigned32,
|
||
hwUpsRackOutputPeakRatioC
|
||
Unsigned32,
|
||
hwUpsOutputRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwUpsOutputVoltageA OBJECT-TYPE
|
||
SYNTAX Unsigned32 ( 0..10000)
|
||
UNITS "V"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack phase A output voltage. The value ranges from 0 to 10000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is V.
|
||
"
|
||
::= { hwUpsOutputEntry 1 }
|
||
|
||
hwUpsOutputVoltageB OBJECT-TYPE
|
||
SYNTAX Unsigned32 ( 0..10000)
|
||
UNITS "V"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack phase B output voltage. The value ranges from 0 to 10000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is V."
|
||
::= { hwUpsOutputEntry 2 }
|
||
|
||
hwUpsOutputVoltageC OBJECT-TYPE
|
||
SYNTAX Unsigned32 ( 0..10000)
|
||
UNITS "V"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack phase C output voltage. The value ranges from 0 to 10000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is V."
|
||
::= { hwUpsOutputEntry 3 }
|
||
|
||
hwUpsOutputCurrentA OBJECT-TYPE
|
||
SYNTAX Unsigned32 ( 0..10000)
|
||
UNITS "A"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack phase A output current. The value ranges from 0 to 10000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is A."
|
||
::= { hwUpsOutputEntry 4 }
|
||
|
||
hwUpsOutputCurrentB OBJECT-TYPE
|
||
SYNTAX Unsigned32 ( 0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack phase B output current. The value ranges from 0 to 10000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is A."
|
||
::= { hwUpsOutputEntry 5 }
|
||
|
||
hwUpsOutputCurrentC OBJECT-TYPE
|
||
SYNTAX Unsigned32 ( 0..10000)
|
||
UNITS "A"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack phase C output current. The value ranges from 0 to 10000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is A."
|
||
::= { hwUpsOutputEntry 6 }
|
||
|
||
hwUpsOutputFrequency OBJECT-TYPE
|
||
SYNTAX Unsigned32 ( 0..10000)
|
||
UNITS "Hz"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack output frequency. The value ranges from 0 to 10000.
|
||
The value is accurate to two decimal place on the NetEco. The unit is Hz."
|
||
::= { hwUpsOutputEntry 7 }
|
||
|
||
hwUpsOutputActivePowerA OBJECT-TYPE
|
||
SYNTAX Integer32 ( -12000..12000)
|
||
UNITS "kW"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack phase A output active power. The value ranges from -12000 to 12000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is kW."
|
||
::= { hwUpsOutputEntry 8 }
|
||
|
||
hwUpsOutputActivePowerB OBJECT-TYPE
|
||
SYNTAX Integer32 ( -12000..12000)
|
||
UNITS "kW"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack phase B output active power. The value ranges from -12000 to 12000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is kW."
|
||
::= { hwUpsOutputEntry 9 }
|
||
|
||
hwUpsOutputActivePowerC OBJECT-TYPE
|
||
SYNTAX Integer32 ( -12000..12000)
|
||
UNITS "kW"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack phase C output active power. The value ranges from -12000 to 12000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is kW."
|
||
::= { hwUpsOutputEntry 10 }
|
||
|
||
hwUpsOutputAppearancePowerA OBJECT-TYPE
|
||
SYNTAX Integer32 ( -12000..12000)
|
||
UNITS "kVA"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack phase A output apparent power. The value ranges from -12000 to 12000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is kVA."
|
||
::= { hwUpsOutputEntry 11 }
|
||
|
||
hwUpsOutputAppearancePowerB OBJECT-TYPE
|
||
SYNTAX Integer32 ( -12000..12000)
|
||
UNITS "kVA"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack phase B output apparent power. The value ranges from -12000 to 12000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is kVA."
|
||
::= { hwUpsOutputEntry 12 }
|
||
|
||
hwUpsOutputAppearancePowerC OBJECT-TYPE
|
||
SYNTAX Integer32 ( -12000..12000)
|
||
UNITS "kVA"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack phase C output apparent power. The value ranges from -12000 to 12000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is kVA."
|
||
::= { hwUpsOutputEntry 13 }
|
||
|
||
hwUpsOutputLoadA OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..999)
|
||
UNITS "%"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack phase A output load ratio. The value ranges from 0 to 5000 The value is accurate to one decimal place on the NetEco."
|
||
::= { hwUpsOutputEntry 14 }
|
||
|
||
hwUpsOutputLoadB OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..999)
|
||
UNITS "%"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack phase B output load ratio. The value ranges from 0 to 5000 The value is accurate to one decimal place on the NetEco."
|
||
::= { hwUpsOutputEntry 15 }
|
||
|
||
hwUpsOutputLoadC OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..999)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack phase C output load ratio. The value ranges from 0 to 5000 The value is accurate to one decimal place on the NetEco."
|
||
::= { hwUpsOutputEntry 16 }
|
||
|
||
hwUpsOutputPowerRating OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
level200(1),
|
||
level208(2),
|
||
level220(3),
|
||
level380(4),
|
||
level400(5),
|
||
level415(6),
|
||
level480(7),
|
||
level600(8),
|
||
level690(9)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rated output voltage (system voltage level). Enumeration type. The default value is 6. The unit is V.
|
||
Value 1 indicates 200 V.
|
||
Value 2 indicates 208 V.
|
||
Value 3 indicates 220 V.
|
||
Value 4 indicates 380 V.
|
||
Value 5 indicates 400 V.
|
||
Value 6 indicates 415 V.
|
||
Value 7 indicates 480 V.
|
||
Value 8 indicates 600 V.
|
||
Value 9 indicates 690 V."
|
||
::= { hwUpsOutputEntry 17 }
|
||
|
||
hwUpsOutputFrequencyRating OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
level50(1),
|
||
level60(2)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rated output frequency. Enumeration type. The default value is 2. The unit is Hz.
|
||
Value 1 indicates 50 Hz.
|
||
Value 2 indicates 60 Hz."
|
||
::= { hwUpsOutputEntry 18 }
|
||
|
||
hwUpsOutputPowerFactorA OBJECT-TYPE
|
||
SYNTAX Integer32 ( -100..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack phase A output power factor.
|
||
The value ranges from -100 to 100 The value is accurate to two decimal place on the NetEco."
|
||
::= { hwUpsOutputEntry 19 }
|
||
|
||
hwUpsOutputPowerFactorB OBJECT-TYPE
|
||
SYNTAX Integer32 ( -100..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack phase B output power factor.
|
||
The value ranges from -100 to 100 The value is accurate to two decimal place on the NetEco.
|
||
"
|
||
::= { hwUpsOutputEntry 20 }
|
||
|
||
hwUpsOutputPowerFactorC OBJECT-TYPE
|
||
SYNTAX Integer32 ( -100..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack phase C output power factor.
|
||
The value ranges from -100 to 100 The value is accurate to two decimal place on the NetEco."
|
||
::= { hwUpsOutputEntry 21 }
|
||
|
||
hwUpsOutputLineVoltageAB OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..20000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack Line AB output voltage. The value ranges from 0 to 20000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is V."
|
||
::= { hwUpsOutputEntry 22 }
|
||
|
||
hwUpsOutputLineVoltageBC OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..20000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack Line BC output voltage. The value ranges from 0 to 20000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is V."
|
||
::= { hwUpsOutputEntry 23 }
|
||
|
||
hwUpsOutputLineVoltageCA OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..20000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack Line CA output voltage. The value ranges from 0 to 20000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is V."
|
||
::= { hwUpsOutputEntry 24 }
|
||
|
||
hwUpsRackOutputPeakRatioA OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack A Out Peak Ratio. The value ranges from 0 to 1000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is %."
|
||
::= { hwUpsOutputEntry 25 }
|
||
|
||
hwUpsRackOutputPeakRatioB OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack B Out Peak Ratio. The value ranges from 0 to 1000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is %."
|
||
::= { hwUpsOutputEntry 26 }
|
||
|
||
hwUpsRackOutputPeakRatioC OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack C Out Peak Ratio. The value ranges from 0 to 1000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is %."
|
||
::= { hwUpsOutputEntry 27 }
|
||
|
||
hwUpsOutputRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus of UPS output information table."
|
||
::= { hwUpsOutputEntry 100 }
|
||
|
||
hwUpsBypass OBJECT IDENTIFIER ::= { hwUpsMIBObjects 5 }
|
||
|
||
hwUpsBypassTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwUpsBypassEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"UPS bypass information table. It's index is hwUpsDeviceId."
|
||
::= { hwUpsBypass 100 }
|
||
|
||
hwUpsBypassEntry OBJECT-TYPE
|
||
SYNTAX HwUpsBypassEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"UPS bypass information table. It's index is hwUpsDeviceId."
|
||
INDEX { hwUpsDeviceId }
|
||
::= { hwUpsBypassTable 1 }
|
||
|
||
HwUpsBypassEntry ::= SEQUENCE {
|
||
hwUpsBypassInputVoltageA
|
||
Unsigned32,
|
||
hwUpsBypassInputVoltageB
|
||
Unsigned32,
|
||
hwUpsBypassInputVoltageC
|
||
Unsigned32,
|
||
hwUpsBypassInputFrequency
|
||
Unsigned32,
|
||
hwUpsBypassInputCurrentA
|
||
Unsigned32,
|
||
hwUpsBypassInputCurrentB
|
||
Unsigned32,
|
||
hwUpsBypassInputCurrentC
|
||
Unsigned32,
|
||
hwUpsBypassInputLineVoltageAB
|
||
Unsigned32,
|
||
hwUpsBypassInputLineVoltageBC
|
||
Unsigned32,
|
||
hwUpsBypassInputLineVoltageCA
|
||
Unsigned32,
|
||
hwUpsBypassRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwUpsBypassInputVoltageA OBJECT-TYPE
|
||
SYNTAX Unsigned32 ( 0..10000)
|
||
UNITS "V"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Bypass input voltage phase A. The value ranges from 0 to 10000
|
||
The value is accurate to one decimal place on the NetEco. The unit is V."
|
||
::= { hwUpsBypassEntry 1 }
|
||
|
||
hwUpsBypassInputVoltageB OBJECT-TYPE
|
||
SYNTAX Unsigned32 ( 0..10000)
|
||
UNITS "V"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Bypass input voltage phase B. The value ranges from 0 to 10000
|
||
The value is accurate to one decimal place on the NetEco. The unit is V."
|
||
::= { hwUpsBypassEntry 2 }
|
||
|
||
hwUpsBypassInputVoltageC OBJECT-TYPE
|
||
SYNTAX Unsigned32 ( 0..10000)
|
||
UNITS "V"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Bypass input voltage phase C. The value ranges from 0 to 10000
|
||
The value is accurate to one decimal place on the NetEco. The unit is V."
|
||
::= { hwUpsBypassEntry 3 }
|
||
|
||
hwUpsBypassInputFrequency OBJECT-TYPE
|
||
SYNTAX Unsigned32 ( 0..10000)
|
||
UNITS "Hz"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Bypass input frequency. The value ranges from 0 to 10000
|
||
The value is accurate to two decimal place on the NetEco. The unit is Hz."
|
||
::= { hwUpsBypassEntry 4 }
|
||
|
||
hwUpsBypassInputCurrentA OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..60000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Bypass input current phase A. The value ranges from 0 to 60000
|
||
The value is accurate to one decimal place on the NetEco. The unit is A."
|
||
::= { hwUpsBypassEntry 5 }
|
||
|
||
hwUpsBypassInputCurrentB OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..60000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Bypass input current phase B. The value ranges from 0 to 60000
|
||
The value is accurate to one decimal place on the NetEco. The unit is A."
|
||
::= { hwUpsBypassEntry 6 }
|
||
|
||
hwUpsBypassInputCurrentC OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..60000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Bypass input current phase C. The value ranges from 0 to 60000
|
||
The value is accurate to one decimal place on the NetEco. The unit is A."
|
||
::= { hwUpsBypassEntry 7 }
|
||
|
||
hwUpsBypassInputLineVoltageAB OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..20000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Bypass Input Line voltage AB. The value ranges from 0 to 20000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is V."
|
||
::= { hwUpsBypassEntry 8 }
|
||
|
||
hwUpsBypassInputLineVoltageBC OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..20000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Bypass Input Line voltage BC. The value ranges from 0 to 20000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is V."
|
||
::= { hwUpsBypassEntry 9 }
|
||
|
||
hwUpsBypassInputLineVoltageCA OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..20000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Bypass Input Line voltage CA. The value ranges from 0 to 20000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is V."
|
||
::= { hwUpsBypassEntry 10 }
|
||
|
||
hwUpsBypassRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus of UPS bypass information table."
|
||
::= { hwUpsBypassEntry 100 }
|
||
|
||
hwUpsBattery OBJECT IDENTIFIER ::= { hwUpsMIBObjects 6 }
|
||
|
||
hwUpsBatteryTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwUpsBatteryEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"UPS battery information table. It's index is hwUpsDeviceId."
|
||
::= { hwUpsBattery 100 }
|
||
|
||
hwUpsBatteryEntry OBJECT-TYPE
|
||
SYNTAX HwUpsBatteryEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"UPS battery information table. It's index is hwUpsDeviceId."
|
||
INDEX { hwUpsDeviceId }
|
||
::= { hwUpsBatteryTable 1 }
|
||
|
||
HwUpsBatteryEntry ::= SEQUENCE {
|
||
hwUpsBatteryVoltage
|
||
Unsigned32,
|
||
hwUpsBatteryCurrent
|
||
Integer32,
|
||
hwUpsBatteryCapacityLeft
|
||
Unsigned32,
|
||
hwUpsBatteryBackupTime
|
||
Unsigned32,
|
||
hwUpsBatteryNumber
|
||
Unsigned32,
|
||
hwUpsBatterytemperature
|
||
Unsigned32,
|
||
hwUpsBatterySoh
|
||
INTEGER,
|
||
hwUpsBatteryRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwUpsBatteryVoltage OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
UNITS "V"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery Voltage. It is a real-time analog parameter.
|
||
Value range: 0 to 20000, Unit: V, and the value is accurate to one decimal place (.1)."
|
||
::= { hwUpsBatteryEntry 1 }
|
||
|
||
hwUpsBatteryCurrent OBJECT-TYPE
|
||
SYNTAX Integer32 (-60000..60000)
|
||
UNITS "A"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery Total Current. It is a real-time analog parameter.
|
||
Value range: -60000 to 60000, Unit: A, and the value is accurate to one decimal place (.1)."
|
||
::= { hwUpsBatteryEntry 2 }
|
||
|
||
hwUpsBatteryCapacityLeft OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100)
|
||
UNITS "%"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery Capacity Left. Value range: 0 to 100, Unit: %, and the value is an integer."
|
||
::= { hwUpsBatteryEntry 3 }
|
||
|
||
hwUpsBatteryBackupTime OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..172800)
|
||
UNITS "S"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery Backup Time. Value range: 0 to 172800, Unit: S, and the value is an integer."
|
||
::= { hwUpsBatteryEntry 4 }
|
||
|
||
hwUpsBatteryNumber OBJECT-TYPE
|
||
SYNTAX Unsigned32 (1..240)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery group number.Value range: 1 to 240,and the value is an integer."
|
||
::= { hwUpsBatteryEntry 5 }
|
||
|
||
hwUpsBatterytemperature OBJECT-TYPE
|
||
SYNTAX Unsigned32 (-200..800)
|
||
UNITS "C"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery temperature.Value range: -20 to 80, Unit:C, and the value is accurate to one decimal place (.1)"
|
||
::= { hwUpsBatteryEntry 6 }
|
||
|
||
hwUpsBatterySoh OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
|
||
good(1),
|
||
requiringMaintenance(2),
|
||
repalceBatt(3)
|
||
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwUpsBatteryEntry 7 }
|
||
|
||
hwUpsBatteryRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus of UPS battery information table."
|
||
::= { hwUpsBatteryEntry 100 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.1.10
|
||
hwUpsParallelSystem OBJECT IDENTIFIER ::= { hwUpsMIBObjects 10 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.1.10.1
|
||
hwUpsParaSysTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwUpsParaSysEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"UPS parallel system table. Its index is hwUpsDeviceId."
|
||
::= { hwUpsParallelSystem 1 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.1.10.1.1
|
||
hwUpsParaSysEntry OBJECT-TYPE
|
||
SYNTAX HwUpsParaSysEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"UPS parallel system table entry."
|
||
INDEX { hwUpsDeviceId }
|
||
::= { hwUpsParaSysTable 1 }
|
||
|
||
|
||
HwUpsParaSysEntry ::=
|
||
SEQUENCE {
|
||
hwUpsParaSysId
|
||
Unsigned32,
|
||
hwUpsParaSysOutActivePowA
|
||
Integer32,
|
||
hwUpsParaSysOutActivePowB
|
||
Integer32,
|
||
hwUpsParaSysOutActivePowC
|
||
Integer32,
|
||
hwUpsParaSysOutAppearPowA
|
||
Integer32,
|
||
hwUpsParaSysOutAppearPowB
|
||
Integer32,
|
||
hwUpsParaSysOutAppearPowC
|
||
Integer32,
|
||
hwUpsParaSysOutLoadFactorA
|
||
Unsigned32,
|
||
hwUpsParaSysOutLoadFactorB
|
||
Unsigned32,
|
||
hwUpsParaSysOutLoadFactorC
|
||
Unsigned32,
|
||
hwUpsParallelSystemRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.1.10.1.1.1
|
||
hwUpsParaSysId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..127)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ID of the parallel system that the current rack belongs to. "
|
||
::= { hwUpsParaSysEntry 1 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.1.10.1.1.2
|
||
hwUpsParaSysOutActivePowA OBJECT-TYPE
|
||
SYNTAX Integer32 (-120000..120000)
|
||
UNITS "kW"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"System phase A output active power.The value ranges from -12000 to 12000,
|
||
The value is accurate to one decimal place on the NetEco. The unit is kW."
|
||
::= { hwUpsParaSysEntry 2 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.1.10.1.1.3
|
||
hwUpsParaSysOutActivePowB OBJECT-TYPE
|
||
SYNTAX Integer32 (-120000..120000)
|
||
UNITS "kW"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"System phase B output active power.The value ranges from -12000 to 12000,
|
||
The value is accurate to one decimal place on the NetEco. The unit is kW."
|
||
::= { hwUpsParaSysEntry 3 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.1.10.1.1.4
|
||
hwUpsParaSysOutActivePowC OBJECT-TYPE
|
||
SYNTAX Integer32 (-120000..120000)
|
||
UNITS "kW"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"System phase C output active power.The value ranges from -12000 to 12000,
|
||
The value is accurate to one decimal place on the NetEco. The unit is kW."
|
||
::= { hwUpsParaSysEntry 4 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.1.10.1.1.5
|
||
hwUpsParaSysOutAppearPowA OBJECT-TYPE
|
||
SYNTAX Integer32 (-120000..120000)
|
||
UNITS "kVA"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"System phase A output apparent power.The value ranges from -12000 to 12000,
|
||
The value is accurate to one decimal place on the NetEco. The unit is kVA."
|
||
::= { hwUpsParaSysEntry 5 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.1.10.1.1.6
|
||
hwUpsParaSysOutAppearPowB OBJECT-TYPE
|
||
SYNTAX Integer32 (-120000..120000)
|
||
UNITS "kVA"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"System phase B output apparent power.The value ranges from -12000 to 12000,
|
||
The value is accurate to one decimal place on the NetEco. The unit is kVA."
|
||
::= { hwUpsParaSysEntry 6 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.1.10.1.1.7
|
||
hwUpsParaSysOutAppearPowC OBJECT-TYPE
|
||
SYNTAX Integer32 (-120000..120000)
|
||
UNITS "kVA"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"System phase C output apparent power.The value ranges from -12000 to 12000,
|
||
The value is accurate to one decimal place on the NetEco. The unit is kVA."
|
||
::= { hwUpsParaSysEntry 7 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.1.10.1.1.8
|
||
hwUpsParaSysOutLoadFactorA OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..5000)
|
||
UNITS "%"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"System phase A output reactive power.The value ranges from 0 to 500,
|
||
The value is accurate to one decimal place on the NetEco. The unit is %."
|
||
::= { hwUpsParaSysEntry 8 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.1.10.1.1.9
|
||
hwUpsParaSysOutLoadFactorB OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..5000)
|
||
UNITS "%"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"System phase B output reactive power.The value ranges from 0 to 500,
|
||
The value is accurate to one decimal place on the NetEco. The unit is %."
|
||
::= { hwUpsParaSysEntry 9 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.1.10.1.1.10
|
||
hwUpsParaSysOutLoadFactorC OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..5000)
|
||
UNITS "%"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"System phase C output reactive power.The value ranges from 0 to 500,
|
||
The value is accurate to one decimal place on the NetEco. The unit is %."
|
||
::= { hwUpsParaSysEntry 10 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.1.10.1.1.100
|
||
hwUpsParallelSystemRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus of ups parallel System Identification table."
|
||
::= { hwUpsParaSysEntry 100 }
|
||
|
||
hwUpsSiteTime OBJECT IDENTIFIER ::= { hwUpsMIBObjects 11 }
|
||
|
||
hwUpsSiteTimeUTC OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..4294967295)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"UTC time, ranging from 0 to 4294967295. The unit is seconds."
|
||
::= { hwUpsSiteTime 1 }
|
||
|
||
hwUpsSiteTimeZone OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-write
|
||
STATUS obsolete
|
||
DESCRIPTION
|
||
"UTC time zone that the current rack belongs to."
|
||
::= { hwUpsSiteTime 2 }
|
||
|
||
hwUpsAlarm OBJECT IDENTIFIER ::= { hwUpsMIBObjects 12 }
|
||
|
||
hwUpsAlarmSynchronNum OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..4294967295)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Alarm synchronization ID. The value ranges from 0 to 4294967295.
|
||
This value is used by the NetEco to obtain the active alarm synchronization ID and synchronize alarms."
|
||
::= { hwUpsAlarm 1 }
|
||
|
||
hwUpsAlarmCurrActiveNum OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..8000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Number of active alarms, ranging from 0 to 8000."
|
||
::= { hwUpsAlarm 2 }
|
||
|
||
hwUpsAlarmCurrCriticalNum OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..8000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Number of critical active alarms, ranging from 0 to 8000."
|
||
::= { hwUpsAlarm 3 }
|
||
|
||
hwUpsAlarmCurrMajorNum OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..8000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Number of major active alarms, ranging from 0 to 8000."
|
||
::= { hwUpsAlarm 4 }
|
||
|
||
hwUpsAlarmCurrMinorNum OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..8000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Number of minor active alarms, ranging from 0 to 8000."
|
||
::= { hwUpsAlarm 5 }
|
||
|
||
hwUpsAlarmCurrWarningNum OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..8000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Number of warning active alarms, ranging from 0 to 8000."
|
||
::= { hwUpsAlarm 6 }
|
||
|
||
hwUpsActiveAlarm OBJECT IDENTIFIER ::= { hwUpsMIBObjects 13 }
|
||
|
||
hwUpsActiveAlarmTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwUpsActiveAlarmEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"UPS active alarm table. It's indexs are hwUpsActiveAlarmDeviceId and hwUpsActiveAlarmSeqId"
|
||
::= { hwUpsActiveAlarm 1 }
|
||
|
||
hwUpsActiveAlarmEntry OBJECT-TYPE
|
||
SYNTAX HwUpsActiveAlarmEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"UPS active alarm table. It's indexs are hwUpsActiveAlarmDeviceId and hwUpsActiveAlarmSeqId"
|
||
INDEX { hwUpsActiveAlarmDeviceId, hwUpsActiveAlarmSeqId }
|
||
::= { hwUpsActiveAlarmTable 1 }
|
||
|
||
HwUpsActiveAlarmEntry ::= SEQUENCE {
|
||
hwUpsActiveAlarmDeviceId
|
||
Unsigned32,
|
||
hwUpsActiveAlarmSeqId
|
||
Unsigned32,
|
||
hwUpsActiveAlarmEquipID
|
||
Unsigned32,
|
||
hwUpsActiveAlarmID
|
||
Unsigned32,
|
||
hwUpsActiveAlarmReasonId
|
||
Unsigned32,
|
||
hwUpsActiveAlarmText
|
||
OCTET STRING,
|
||
hwUpsActiveAlarmLevel
|
||
INTEGER,
|
||
hwUpsActiveAlarmFlag
|
||
INTEGER,
|
||
hwUpsActiveAlarmSynchronNum
|
||
Unsigned32,
|
||
hwUpsActiveAlarmTime
|
||
Unsigned32,
|
||
hwUpsActiveAlarmRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwUpsActiveAlarmDeviceId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (1..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ID of the device on which the active alarm is generated. An integer ranging from 1 to 100."
|
||
::= { hwUpsActiveAlarmEntry 1 }
|
||
|
||
hwUpsActiveAlarmSeqId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (1..4294967295)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Sequence number of an active alarm, ranging from 1 to 4294967295."
|
||
::= { hwUpsActiveAlarmEntry 2 }
|
||
|
||
hwUpsActiveAlarmEquipID OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Active alarm module ID, ranging from 1 to 10000."
|
||
::= { hwUpsActiveAlarmEntry 3 }
|
||
|
||
hwUpsActiveAlarmID OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..4294967295)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ID of an active alarm, ranging from 0 to 4294967295."
|
||
::= { hwUpsActiveAlarmEntry 4 }
|
||
|
||
hwUpsActiveAlarmReasonId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Reason ID of an active alarm, ranging from 1 to 100."
|
||
::= { hwUpsActiveAlarmEntry 5 }
|
||
|
||
hwUpsActiveAlarmText OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..127))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"English name of an active alarm. A string of characters. "
|
||
::= { hwUpsActiveAlarmEntry 6 }
|
||
|
||
hwUpsActiveAlarmLevel OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
critical(1),
|
||
major(2),
|
||
minor(3),
|
||
warning(4)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Severity of an active alarm. Enumeration type.
|
||
Value 1 indicates a critical alarm.
|
||
Value 2 indicates a major alarm.
|
||
Value 3 indicates a minor alarm.
|
||
Value 4 indicates a warning."
|
||
::= { hwUpsActiveAlarmEntry 7 }
|
||
|
||
hwUpsActiveAlarmFlag OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
occur(1),
|
||
resume(2)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Flag bit of an active alarm. Enumeration type.
|
||
Value 1 indicates that an active alarm is generated.
|
||
Value 2 indicates that an active alarm is cleared."
|
||
::= { hwUpsActiveAlarmEntry 8 }
|
||
|
||
hwUpsActiveAlarmSynchronNum OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..4294967295)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Active alarm synchronization ID, ranging from 0 to 4294967295."
|
||
::= { hwUpsActiveAlarmEntry 9 }
|
||
|
||
hwUpsActiveAlarmTime OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..4294967295)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Time when an active alarm is generated, ranging from 0 to 4294967295. The unit is seconds.
|
||
"
|
||
::= { hwUpsActiveAlarmEntry 10 }
|
||
|
||
hwUpsActiveAlarmRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus of ups active alarm table."
|
||
::= { hwUpsActiveAlarmEntry 11 }
|
||
|
||
hwUpsModule OBJECT IDENTIFIER ::= { hwUpsMIBObjects 107 }
|
||
|
||
hwUpsModuleTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwUpsModuleEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwUpsModule 1 }
|
||
|
||
hwUpsModuleEntry OBJECT-TYPE
|
||
SYNTAX HwUpsModuleEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
INDEX { hwUpsModuleRackId }
|
||
::= { hwUpsModuleTable 1 }
|
||
|
||
HwUpsModuleEntry ::= SEQUENCE {
|
||
hwUpsModuleRackId
|
||
Unsigned32,
|
||
hwUpsPowerModuleId
|
||
Unsigned32,
|
||
hwUpsBusCapacitorLife
|
||
Unsigned32,
|
||
hwUpsInvACur
|
||
Unsigned32,
|
||
hwUpsInvBCur
|
||
Unsigned32,
|
||
hwUpsInvCCur
|
||
Unsigned32,
|
||
hwUpsModuleAUnevenFlow
|
||
Unsigned32,
|
||
hwUpsModuleBUnevenFlow
|
||
Unsigned32,
|
||
hwUpsModuleCUnevenFlow
|
||
Unsigned32,
|
||
hwUpsInvPowerStat
|
||
INTEGER,
|
||
hwUpsModuleUnevneCurValueTag
|
||
Unsigned32,
|
||
hwUpsModuleSleepState
|
||
Unsigned32,
|
||
hwUpsModuleRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwUpsModuleRackId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (1..6)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ups Rack Id.Range from 1 to 6.This node is referenced as an index node
|
||
by hwUpsModuleTable."
|
||
::= { hwUpsModuleEntry 1 }
|
||
|
||
hwUpsPowerModuleId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (1..20)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ups Power Module Id.Range from 1 to 20.This node is referenced as an index node
|
||
by hwUpsModuleTable."
|
||
::= { hwUpsModuleEntry 2 }
|
||
|
||
hwUpsBusCapacitorLife OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inv C Cap Life.Value range: 0 to 10000, Unit: Y, and the value is accurate to one decimal place (.1)."
|
||
::= { hwUpsModuleEntry 3 }
|
||
|
||
hwUpsInvACur OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inv A Current.Value range: 0 to 10000.The value is accurate to one decimal place (.1).The unit is A."
|
||
::= { hwUpsModuleEntry 4 }
|
||
|
||
hwUpsInvBCur OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inv B Current.Value range: 0 to 10000.The value is accurate to one decimal place (.1).The unit is A."
|
||
::= { hwUpsModuleEntry 5 }
|
||
|
||
hwUpsInvCCur OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inv C Current.Value range: 0 to 10000.The value is accurate to one decimal place (.1).The unit is A."
|
||
::= { hwUpsModuleEntry 6 }
|
||
|
||
hwUpsModuleAUnevenFlow OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Module A Uneven Flow.Value range: 0 to 10000,and the value is accurate to one decimal place (.1)."
|
||
::= { hwUpsModuleEntry 7 }
|
||
|
||
hwUpsModuleBUnevenFlow OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Module B Uneven Flow.Value range: 0 to 10000,and the value is accurate to one decimal place (.1)."
|
||
::= { hwUpsModuleEntry 8 }
|
||
|
||
hwUpsModuleCUnevenFlow OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Module C Uneven Flow.Value range: 0 to 10000,and the value is accurate to one decimal place (.1)."
|
||
::= { hwUpsModuleEntry 9 }
|
||
|
||
hwUpsInvPowerStat OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
noOutput(1),
|
||
bypass(2),
|
||
normal(3)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inv Power Stat.Enumeration type.
|
||
Value 0 indicates no power supply.
|
||
Value 1 indicates bypass mode.
|
||
Value 2 indicates normal mode."
|
||
::= { hwUpsModuleEntry 10 }
|
||
|
||
hwUpsModuleUnevneCurValueTag OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..1)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Module uneven current value tag.range 0 to 1,0 indicates invalid,1 indicates valid."
|
||
::= { hwUpsModuleEntry 11 }
|
||
|
||
hwUpsModuleSleepState OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..1)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Module Sleep State.Range 0 to 1,0 indicates not sleep,1 indicates sleep."
|
||
::= { hwUpsModuleEntry 12 }
|
||
|
||
hwUpsModuleRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus of UPS module information table."
|
||
::= { hwUpsModuleEntry 100 }
|
||
|
||
hwUpsControl OBJECT IDENTIFIER ::= { hwUpsMIBObjects 102 }
|
||
|
||
hwUpsControlTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwUpsControlEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"UPS control table. It's index is hwUpsRackId."
|
||
::= { hwUpsControl 100 }
|
||
|
||
hwUpsControlEntry OBJECT-TYPE
|
||
SYNTAX HwUpsControlEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"UPS control table. It's index is hwUpsRackId."
|
||
INDEX { hwUpsDeviceId }
|
||
::= { hwUpsControlTable 1 }
|
||
|
||
HwUpsControlEntry ::= SEQUENCE {
|
||
hwUpsCtrlECOSwitch
|
||
INTEGER,
|
||
hwUpsCtrlPowerOn
|
||
INTEGER,
|
||
hwUpsCtrlPowerOff
|
||
INTEGER,
|
||
hwUpsCtrlPowerOffDelay
|
||
Unsigned32,
|
||
hwUpsCtrlPowerBatCapacity
|
||
Unsigned32,
|
||
hwUpsCtrlPowerBatType
|
||
INTEGER,
|
||
hwUpsCtrlModelType
|
||
INTEGER,
|
||
hwUpsCtrlInputStandard
|
||
INTEGER,
|
||
hwUpsCtrlOutputStandard
|
||
INTEGER,
|
||
hwUpsCtrlPowerOnState
|
||
INTEGER,
|
||
hwUpsCtrlBatteryToBoostState
|
||
INTEGER,
|
||
hwUpsCtrlBatteryToFloatState
|
||
INTEGER,
|
||
hwUpsCtrlBatteryToTestState
|
||
INTEGER,
|
||
hwUpsCtrlBatteryStopTestState
|
||
INTEGER,
|
||
hwUpsCtrlBatteryManualBoostCharge
|
||
INTEGER,
|
||
hwUpsCtrlBatteryManualFloatCharge
|
||
INTEGER,
|
||
hwUpsCtrlBatteryShallowTest
|
||
INTEGER,
|
||
hwUpsCtrlBatteryVerifyCapTest
|
||
INTEGER,
|
||
hwUpsCtrlBatteryEndTest
|
||
INTEGER,
|
||
hwUpsCtrlModelCapacity
|
||
Unsigned32,
|
||
hwUpsCtrlEPO
|
||
INTEGER,
|
||
hwUpsSmartParallelSleepMode
|
||
INTEGER,
|
||
hwUpsCtrlRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwUpsCtrlECOSwitch OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
noECO(1),
|
||
eco(2)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ECO settings. Enumeration type. The default value is 1.
|
||
Value 1 indicates ECO mode.
|
||
Value 2 indicates Non ECO mode."
|
||
::= { hwUpsControlEntry 1 }
|
||
|
||
hwUpsCtrlPowerOn OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
powerOn(1),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Power on settings. Enumeration type.
|
||
Value 1 indicates power on .
|
||
Value 2 indicates unknow."
|
||
::= { hwUpsControlEntry 2 }
|
||
|
||
hwUpsCtrlPowerOff OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
powerOff(1),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Power off settings. Enumeration type.
|
||
Value 1 indicates power off .
|
||
Value 2 indicates unknow."
|
||
::= { hwUpsControlEntry 3 }
|
||
|
||
hwUpsCtrlPowerOffDelay OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..120000000)
|
||
UNITS "S"
|
||
MAX-ACCESS read-only
|
||
STATUS obsolete
|
||
DESCRIPTION
|
||
"Delay power off.The value ranges from 0 to 120000000 . The unit is S."
|
||
::= { hwUpsControlEntry 4 }
|
||
|
||
hwUpsCtrlPowerBatCapacity OBJECT-TYPE
|
||
SYNTAX Unsigned32 (5..3000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery capacity, ranging from 5 to 3000.
|
||
"
|
||
::= { hwUpsControlEntry 5 }
|
||
|
||
hwUpsCtrlPowerBatType OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
vrla(1)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery type.ECO settings. Enumeration type. The default value is 1.
|
||
Value 1 indicates VRLA batteries."
|
||
::= { hwUpsControlEntry 6 }
|
||
|
||
hwUpsCtrlModelType OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
model6K(17),
|
||
mode110K(33),
|
||
model20K(65)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS obsolete
|
||
DESCRIPTION
|
||
"Model type,Enumeration type.
|
||
Value 17 indicates 6K.
|
||
Value 33 indicates 10K.
|
||
Value 65 indicates 20K."
|
||
::= { hwUpsControlEntry 7 }
|
||
|
||
hwUpsCtrlInputStandard OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
singlePhase(1),
|
||
threePhase(2)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS obsolete
|
||
DESCRIPTION
|
||
"Input Standard,Enumeration type.
|
||
Value 1 indicates single phase.
|
||
Value 2 indicates three phase."
|
||
::= { hwUpsControlEntry 8 }
|
||
|
||
hwUpsCtrlOutputStandard OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
singlePhase(1)
|
||
threePhase(2)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS obsolete
|
||
DESCRIPTION
|
||
"Output Standard,Enumeration type.
|
||
Value 1 indicates single phase.
|
||
Value 2 indicates three phase."
|
||
::= { hwUpsControlEntry 9 }
|
||
|
||
hwUpsCtrlPowerOnState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
powerOff(1),
|
||
powerOn(2),
|
||
powerOnFail(3),
|
||
powerOnComplete(4)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS obsolete
|
||
DESCRIPTION
|
||
"Power On State,Enumeration type.
|
||
Value 1 indicates power off.
|
||
Value 2 indicates booting.
|
||
Value 3 indicates failed to power on.
|
||
Value 4 indicates succeed tp power on."
|
||
::= { hwUpsControlEntry 10 }
|
||
|
||
hwUpsCtrlBatteryToBoostState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
enable(1),
|
||
disable(2)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS obsolete
|
||
DESCRIPTION
|
||
"Battery Change to Boost Charge State,Enumeration type.
|
||
Value 1 indicates enabled.
|
||
Value 2 indicates disabled."
|
||
::= { hwUpsControlEntry 11 }
|
||
|
||
hwUpsCtrlBatteryToFloatState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
enable(1),
|
||
disable(2)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS obsolete
|
||
DESCRIPTION
|
||
"Battery Change to Float Charge State,Enumeration type.
|
||
Value 1 indicates enabled.
|
||
Value 2 indicates disabled."
|
||
::= { hwUpsControlEntry 12 }
|
||
|
||
hwUpsCtrlBatteryToTestState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
enable(1),
|
||
disable(2),
|
||
shallow(3)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS obsolete
|
||
DESCRIPTION
|
||
"Battery Change to Test State,Enumeration type.
|
||
Value 1 indicates enabled.
|
||
Value 2 indicates disabled."
|
||
::= { hwUpsControlEntry 13 }
|
||
|
||
hwUpsCtrlBatteryStopTestState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
enable(1),
|
||
disable(2)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS obsolete
|
||
DESCRIPTION
|
||
"Battery Stop Test State,Enumeration type.
|
||
Value 1 indicates enabled.
|
||
Value 2 indicates disabled."
|
||
::= { hwUpsControlEntry 14 }
|
||
|
||
hwUpsCtrlBatteryManualBoostCharge OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
toBoostCharge(1),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS obsolete
|
||
DESCRIPTION
|
||
"Battery Manual to Boost Charge,Enumeration type.
|
||
Value 1 indicates enabled.
|
||
Value 2 indicates disabled."
|
||
::= { hwUpsControlEntry 15 }
|
||
|
||
hwUpsCtrlBatteryManualFloatCharge OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
toFloatCharge(1),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS obsolete
|
||
DESCRIPTION
|
||
"Battery Manual to Float Charge,Enumeration type.
|
||
Value 1 indicates enabled.
|
||
Value 2 indicates unknown"
|
||
::= { hwUpsControlEntry 16 }
|
||
|
||
hwUpsCtrlBatteryShallowTest OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
toShallowTest(1),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS obsolete
|
||
DESCRIPTION
|
||
"Battery Shallow Test,Enumeration type.
|
||
Value 1 indicates enabled.
|
||
Value 2 indicates unknown"
|
||
::= { hwUpsControlEntry 17 }
|
||
|
||
hwUpsCtrlBatteryVerifyCapTest OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
toVerifyCapTest(1),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS obsolete
|
||
DESCRIPTION
|
||
"Battery Verify Cap Test,Enumeration type.
|
||
Value 1 indicates enabled.
|
||
Value 2 indicates unknown"
|
||
::= { hwUpsControlEntry 18 }
|
||
|
||
hwUpsCtrlBatteryEndTest OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
toEndTest(1),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS obsolete
|
||
DESCRIPTION
|
||
"Battery End Test,Enumeration type.
|
||
Value 1 indicates enabled.
|
||
Value 2 indicates unknown"
|
||
::= { hwUpsControlEntry 19 }
|
||
|
||
hwUpsCtrlModelCapacity OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..200)
|
||
MAX-ACCESS read-only
|
||
STATUS obsolete
|
||
DESCRIPTION
|
||
"Model Capacity.The value ranges from 0 to 200, The value is accurate to one decimal place on the NetEco. The unit is kVA."
|
||
::= { hwUpsControlEntry 20 }
|
||
|
||
hwUpsCtrlEPO OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
epo(1),
|
||
unknown(2)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS obsolete
|
||
DESCRIPTION
|
||
"EPO. Enumeration type.
|
||
Value 1 indicates EPO .
|
||
Value 255 indicates unknown."
|
||
::= { hwUpsControlEntry 21 }
|
||
|
||
hwUpsSmartParallelSleepMode OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
disable(1),
|
||
enable(2)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Smart Parallel Sleep Mode.Enumeration type.The default value is 0.
|
||
Value 0 indicates disable.
|
||
Value 1 indicates enable."
|
||
::= { hwUpsControlEntry 22 }
|
||
|
||
hwUpsCtrlRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus of UPS rack control table."
|
||
::= { hwUpsControlEntry 100 }
|
||
|
||
hwUpsTest OBJECT IDENTIFIER ::= { hwUpsMIBObjects 103 }
|
||
|
||
hwUpsBattScheduleTestTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwUpsBattScheduleTestEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery schedule test table. It's index is hwUpsDeviceId."
|
||
::= { hwUpsTest 101 }
|
||
|
||
hwUpsBattScheduleTestEntry OBJECT-TYPE
|
||
SYNTAX HwUpsBattScheduleTestEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery schedule test table. It's index is hwUpsDeviceId."
|
||
INDEX { hwUpsDeviceId }
|
||
::= { hwUpsBattScheduleTestTable 1 }
|
||
|
||
HwUpsBattScheduleTestEntry ::= SEQUENCE {
|
||
hwUpsBattAutoTest
|
||
INTEGER,
|
||
hwUpsBattAutoTestTimeLimit
|
||
INTEGER,
|
||
hwUpsBattAutoTestTimeInterval
|
||
Unsigned32,
|
||
hwUpsBattAutoTestDischargeRate
|
||
Unsigned32,
|
||
hwUpsBattAutoTestEndVol
|
||
Unsigned32,
|
||
hwUpsBattTest
|
||
INTEGER,
|
||
hwUpsBattScheduleTestRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwUpsBattAutoTest OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
disable(1),
|
||
enalbe(2)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Scheduled shallow discharge test enabled or disabled. Enumeration value.
|
||
The value 1 indicates that the test is disabled.
|
||
The value 2 indicates that the test is enabled."
|
||
::= { hwUpsBattScheduleTestEntry 1 }
|
||
|
||
hwUpsBattAutoTestTimeLimit OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
from0to6(1),
|
||
from6to12(2),
|
||
from12to18(3),
|
||
from18to24(4)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Scheduled shallow discharge test time. Enumeration value.
|
||
Value 1 indicates 00:00 to 06:00.
|
||
Value 2 indicates 06:00 to 12:00.
|
||
Value 3 indicates 12:00 to 18:00.
|
||
Value 4 indicates 18:00 to 00:00."
|
||
::= { hwUpsBattScheduleTestEntry 2 }
|
||
|
||
hwUpsBattAutoTestTimeInterval OBJECT-TYPE
|
||
SYNTAX Unsigned32 (30..90)
|
||
UNITS "Day"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Scheduled shallow discharge test interval. An integer ranging from 30 to 90. The unit is days."
|
||
::= { hwUpsBattScheduleTestEntry 3 }
|
||
|
||
hwUpsBattAutoTestDischargeRate OBJECT-TYPE
|
||
SYNTAX Unsigned32 (10..50)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Shallow discharge test discharge ratio. An integer ranging from 10 to 50. .
|
||
"
|
||
::= { hwUpsBattScheduleTestEntry 4 }
|
||
|
||
hwUpsBattAutoTestEndVol OBJECT-TYPE
|
||
SYNTAX Unsigned32 (160..195)
|
||
MAX-ACCESS read-write
|
||
STATUS obsolete
|
||
DESCRIPTION
|
||
"Maximum battery discharge time. An integer ranging from 160 to 195. The value is accurate to one decimal place on the NetEco. The unit is V/Cell.
|
||
"
|
||
::= { hwUpsBattScheduleTestEntry 5 }
|
||
|
||
hwUpsBattTest OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
noTestInit(1),
|
||
stopTest(2),
|
||
scheduleTest(3),
|
||
shallowDsgTest(4),
|
||
verufyDsgTest(5)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS obsolete
|
||
DESCRIPTION
|
||
"If you set the value to shallowDsgTest(4), you can perform a shallow discharge test; if you set the value to verifyDsgTest(5), you can perform a capacity test; if you set the value to stopTest(2), you can stop the test. Other settings are invalid. If you start a test when other tests are in progress, error code 4 is returned.
|
||
During test, you can use this node to obtain the current or previous test type.
|
||
If you have never started the battery test sheduleTest(3), shallowDsgTest(4), or verifyDsgTest(5), this node returns noTestInit(1)."
|
||
::= { hwUpsBattScheduleTestEntry 6 }
|
||
|
||
hwUpsBattScheduleTestRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus of UPS Battery control table. "
|
||
::= { hwUpsBattScheduleTestEntry 100 }
|
||
|
||
hwUpsiBOX OBJECT IDENTIFIER ::= { hwUpsMIBObjects 110 }
|
||
|
||
hwUpsBatteryGroupNum OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..4)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Number of battery group in UPS,ranging from 0 to 4.
|
||
"
|
||
::= { hwUpsiBOX 1 }
|
||
|
||
hwUpsBatteryNumInBatteryGroup OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..300)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Number of battery in one battery group,ranging from 0 to 300.
|
||
"
|
||
::= { hwUpsiBOX 2 }
|
||
|
||
hwUpsiBOXNum OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..4)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Number of iBOX in UPS,ranging from 0 to 4."
|
||
::= { hwUpsiBOX 3 }
|
||
|
||
hwUpsBatteryGroupTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwUpsBatteryGroupEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"UPS battery group table. It's index is hwUpsBatteryGroupNo.
|
||
"
|
||
::= { hwUpsiBOX 4 }
|
||
|
||
hwUpsBatteryGroupEntry OBJECT-TYPE
|
||
SYNTAX HwUpsBatteryGroupEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"UPS battery group table. It's index is hwUpsBatteryGroupNo.
|
||
"
|
||
INDEX { hwUpsBatteryGroupNo }
|
||
::= { hwUpsBatteryGroupTable 1 }
|
||
|
||
HwUpsBatteryGroupEntry ::= SEQUENCE {
|
||
hwUpsBatteryGroupNo
|
||
Unsigned32,
|
||
hwUpsBatteryGroupVolt
|
||
Unsigned32,
|
||
hwUpsBatteryGroupCur
|
||
Integer32,
|
||
hwUpsBatteryGroupSOC
|
||
Unsigned32,
|
||
hwUpsBatteryGroupBackupTime
|
||
Unsigned32,
|
||
hwUpsBatteryGroupSOH
|
||
INTEGER,
|
||
hwUpsBatteryGroupRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwUpsBatteryGroupNo OBJECT-TYPE
|
||
SYNTAX Unsigned32 (1..4)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"No of battery group,ranging from 1 to 4.This node is referenced as an index node
|
||
by hwUpsBatteryGroupTable.
|
||
"
|
||
::= { hwUpsBatteryGroupEntry 1 }
|
||
|
||
hwUpsBatteryGroupVolt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The Voltage of battery group,ranging from 0 to 10000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is V."
|
||
::= { hwUpsBatteryGroupEntry 2 }
|
||
|
||
hwUpsBatteryGroupCur OBJECT-TYPE
|
||
SYNTAX Integer32 (-30000..30000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The Current of battery group,ranging from -30000 to 30000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is A."
|
||
::= { hwUpsBatteryGroupEntry 3 }
|
||
|
||
hwUpsBatteryGroupSOC OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The SOC of battery group,ranging from 0 to 100.The unit is %."
|
||
::= { hwUpsBatteryGroupEntry 4 }
|
||
|
||
hwUpsBatteryGroupBackupTime OBJECT-TYPE
|
||
SYNTAX Unsigned32 ( 0..999)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The Backup Time of battery group,ranging from 0 to 999.The unit is min.
|
||
"
|
||
::= { hwUpsBatteryGroupEntry 5 }
|
||
|
||
hwUpsBatteryGroupSOH OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
good(1),
|
||
requiringMaintenance(2),
|
||
needReplaceBatt(3)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The SOH of battery group. Enumeration type.
|
||
Value 0 indicates good.
|
||
Value 1 indicates requiring maintenance.
|
||
Value 2 indicates need replace batt.
|
||
"
|
||
::= { hwUpsBatteryGroupEntry 6 }
|
||
|
||
hwUpsBatteryGroupRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Row status of hwUpsBatteryGroupTable."
|
||
::= { hwUpsBatteryGroupEntry 100 }
|
||
|
||
hwUpsiBOXTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwUpsiBOXEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"CIM table. It's index is hwUpsCIMNo."
|
||
::= { hwUpsiBOX 5 }
|
||
|
||
hwUpsiBOXEntry OBJECT-TYPE
|
||
SYNTAX HwUpsiBOXEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"CIM table. It's index is hwUpsCIMNo."
|
||
INDEX { hwUpsiBOXNo }
|
||
::= { hwUpsiBOXTable 1 }
|
||
|
||
HwUpsiBOXEntry ::= SEQUENCE {
|
||
hwUpsiBOXNo
|
||
Unsigned32,
|
||
hwUpsiBOXSoftVersion
|
||
Unsigned32,
|
||
hwUpsiBOXiBATNum
|
||
Unsigned32,
|
||
hwUpsiBOXRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwUpsiBOXNo OBJECT-TYPE
|
||
SYNTAX Unsigned32 (1..4)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"No of iBOX,ranging from 1 to 4.This node is referenced as an index node by hwUpsiBOXTable."
|
||
::= { hwUpsiBOXEntry 1 }
|
||
|
||
hwUpsiBOXSoftVersion OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..4294967295)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The software version of iBOX,ranging from 0 to 4294967295."
|
||
::= { hwUpsiBOXEntry 2 }
|
||
|
||
hwUpsiBOXiBATNum OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..300)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"iBAT number of one iBOX,ranging from 0 to 300."
|
||
::= { hwUpsiBOXEntry 3 }
|
||
|
||
hwUpsiBOXRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Row status of hwUpsiBOXTable."
|
||
::= { hwUpsiBOXEntry 100 }
|
||
|
||
hwUpsBattGroupRelaiBOXTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwUpsBattGroupRelaiBOXEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"UPS battery group related CIM Table. It's index is hwUpsBattGrpNo and hwUpsBattGroupRelaCIMNo.
|
||
"
|
||
::= { hwUpsiBOX 6 }
|
||
|
||
hwUpsBattGroupRelaiBOXEntry OBJECT-TYPE
|
||
SYNTAX HwUpsBattGroupRelaiBOXEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"UPS battery group related CIM Table. It's index is hwUpsBattGrpNo and hwUpsBattGroupRelaCIMNo.
|
||
"
|
||
INDEX { hwUpsBattGrpNo }
|
||
::= { hwUpsBattGroupRelaiBOXTable 1 }
|
||
|
||
HwUpsBattGroupRelaiBOXEntry ::= SEQUENCE {
|
||
hwUpsBattGrpNo
|
||
Unsigned32,
|
||
hwUpsBattGroupRelaiBOXNo
|
||
Unsigned32,
|
||
hwUpsBattGroupRelaiBATStartNo
|
||
Unsigned32,
|
||
hwUpsBattGroupRelaiBATEndNo
|
||
Unsigned32,
|
||
hwUpsBattGroupRelaiBOXRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwUpsBattGrpNo OBJECT-TYPE
|
||
SYNTAX Unsigned32 (1..4)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"No of battery group,ranging from 1 to 4.This node is referenced as an index node
|
||
by hwUpsBattGrpRelaiBOXTable."
|
||
::= { hwUpsBattGroupRelaiBOXEntry 1 }
|
||
|
||
hwUpsBattGroupRelaiBOXNo OBJECT-TYPE
|
||
SYNTAX Unsigned32 (1..4)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"No of iBOX,ranging from 1 to 4.This node is referenced as an index node
|
||
by hwUpsBattGrpRelaiBOXTable."
|
||
::= { hwUpsBattGroupRelaiBOXEntry 2 }
|
||
|
||
hwUpsBattGroupRelaiBATStartNo OBJECT-TYPE
|
||
SYNTAX Unsigned32 (1..300)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ups Battery Group related iBAT start no,ranging from 1 to 300."
|
||
::= { hwUpsBattGroupRelaiBOXEntry 3 }
|
||
|
||
hwUpsBattGroupRelaiBATEndNo OBJECT-TYPE
|
||
SYNTAX Unsigned32 (1..300)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ups Battery Group related iBAT end no,ranging from 1 to 300.
|
||
"
|
||
::= { hwUpsBattGroupRelaiBOXEntry 4 }
|
||
|
||
hwUpsBattGroupRelaiBOXRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Row status of hwUpsBattGroupRelaiBOXTable."
|
||
::= { hwUpsBattGroupRelaiBOXEntry 100 }
|
||
|
||
hwUpsiBATTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwUpsiBATEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"BIM table. It's index is hwUpsBIMCIMNo and hwUpsBIMNo."
|
||
::= { hwUpsiBOX 7 }
|
||
|
||
hwUpsiBATEntry OBJECT-TYPE
|
||
SYNTAX HwUpsiBATEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"BIM table. It's index is hwUpsBIMCIMNo and hwUpsBIMNo."
|
||
INDEX { hwUpsiBATiBOXNo }
|
||
::= { hwUpsiBATTable 1 }
|
||
|
||
HwUpsiBATEntry ::= SEQUENCE {
|
||
hwUpsiBATiBOXNo
|
||
Unsigned32,
|
||
hwUpsiBATNo
|
||
Unsigned32,
|
||
hwUpsiBATTemp
|
||
Integer32,
|
||
hwUpsiBATVoltMulThousand
|
||
Unsigned32,
|
||
hwUpsiBATResMulHundred
|
||
Unsigned32,
|
||
hwUpsiBATCur
|
||
Integer32,
|
||
hwUpsiBATSOC
|
||
Unsigned32,
|
||
hwUpsiBATSOH
|
||
INTEGER,
|
||
hwUpsiBATVolt
|
||
Unsigned32,
|
||
hwUpsiBATRes
|
||
Unsigned32,
|
||
hwUpsiBATRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwUpsiBATiBOXNo OBJECT-TYPE
|
||
SYNTAX Unsigned32 (1..4)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"No of iBOX,ranging from 1 to 4.This node is referenced as an index node
|
||
by hwUpsBIMTable."
|
||
::= { hwUpsiBATEntry 1 }
|
||
|
||
hwUpsiBATNo OBJECT-TYPE
|
||
SYNTAX Unsigned32 (1..300)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"No of iBAT,ranging from 1 to 300.
|
||
This node is referenced as an index node by hwUpsBIMTable."
|
||
::= { hwUpsiBATEntry 2 }
|
||
|
||
hwUpsiBATTemp OBJECT-TYPE
|
||
SYNTAX Integer32 (-200..800)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ups iBAT Temperature.The value ranges from -200 to 800.
|
||
The value is accurate to one decimal place on the NetEco. The unit is <20><>."
|
||
::= { hwUpsiBATEntry 3 }
|
||
|
||
hwUpsiBATVoltMulThousand OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..300)
|
||
MAX-ACCESS read-only
|
||
STATUS obsolete
|
||
DESCRIPTION
|
||
"Ups iBAT Volt.The value ranges from 0 to 300.
|
||
The value is accurate to one decimal place on the NetEco. The unit is V."
|
||
::= { hwUpsiBATEntry 4 }
|
||
|
||
hwUpsiBATResMulHundred OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..3000)
|
||
MAX-ACCESS read-only
|
||
STATUS obsolete
|
||
DESCRIPTION
|
||
"Ups iBAT Resistance.The value ranges from 0 to 3000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is m<><6D>."
|
||
::= { hwUpsiBATEntry 5 }
|
||
|
||
hwUpsiBATCur OBJECT-TYPE
|
||
SYNTAX Integer32 (-30000..30000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ups iBAT Current.The value ranges from -30000 to 30000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is A.
|
||
"
|
||
::= { hwUpsiBATEntry 6 }
|
||
|
||
hwUpsiBATSOC OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The SOC of iBAT,ranging from 0 to 100.The unit is %.
|
||
"
|
||
::= { hwUpsiBATEntry 7 }
|
||
|
||
hwUpsiBATSOH OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
good(1),
|
||
requiringMaintenance(2),
|
||
needReplaceBatt(3)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The SOH of iBAT. Enumeration type.
|
||
Value 0 indicates good.
|
||
Value 1 indicates requiring maintenance.
|
||
Value 2 indicates need replace batt.
|
||
"
|
||
::= { hwUpsiBATEntry 8 }
|
||
|
||
hwUpsiBATVolt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..30000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ups iBAT Volt.The value ranges from 0 to 30000.
|
||
The value is accurate to two decimal place on the NetEco. The unit is V."
|
||
::= { hwUpsiBATEntry 9 }
|
||
|
||
hwUpsiBATRes OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..30000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ups iBAT Resistance.The value ranges from 0 to 30000.
|
||
The value is accurate to two decimal place on the NetEco. The unit is m<><6D>."
|
||
::= { hwUpsiBATEntry 10 }
|
||
|
||
hwUpsiBATRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Row status of hwUpsiBATTable."
|
||
::= { hwUpsiBATEntry 100 }
|
||
|
||
hwUpsParallelSystem OBJECT IDENTIFIER ::= { hwUpsMIBObjects 10 }
|
||
|
||
hwUpsParaSysTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwUpsParaSysEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwUpsParallelSystem 1 }
|
||
|
||
hwUpsParaSysEntry OBJECT-TYPE
|
||
SYNTAX HwUpsParaSysEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
INDEX { hwUpsParaSysId }
|
||
::= { hwUpsParaSysTable 1 }
|
||
|
||
HwUpsParaSysEntry ::= SEQUENCE {
|
||
hwUpsParaSysId
|
||
Unsigned32,
|
||
hwUpsParaSysOutActivePowA
|
||
Integer32,
|
||
hwUpsParaSysOutActivePowB
|
||
Integer32,
|
||
hwUpsParaSysOutActivePowC
|
||
Integer32,
|
||
hwUpsParaSysOutAppearPowA
|
||
Integer32,
|
||
hwUpsParaSysOutAppearPowB
|
||
Integer32,
|
||
hwUpsParaSysOutAppearPowC
|
||
Integer32,
|
||
hwUpsParaSysOutLoadFactorA
|
||
Unsigned32,
|
||
hwUpsParaSysOutLoadFactorB
|
||
Unsigned32,
|
||
hwUpsParaSysOutLoadFactorC
|
||
Unsigned32,
|
||
hwUpsParallelSystemRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwUpsParaSysId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..127)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ID of the parallel system that the current rack belongs to."
|
||
::= { hwUpsParaSysEntry 1 }
|
||
|
||
hwUpsParaSysOutActivePowA OBJECT-TYPE
|
||
SYNTAX Integer32 (-120000..120000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"System phase A output active power.The value ranges from -12000 to 12000,
|
||
The value is accurate to one decimal place on the NetEco. The unit is kW.
|
||
"
|
||
::= { hwUpsParaSysEntry 2 }
|
||
|
||
hwUpsParaSysOutActivePowB OBJECT-TYPE
|
||
SYNTAX Integer32 (-120000..120000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"System phase B output active power.The value ranges from -12000 to 12000,
|
||
The value is accurate to one decimal place on the NetEco. The unit is kW.
|
||
"
|
||
::= { hwUpsParaSysEntry 3 }
|
||
|
||
hwUpsParaSysOutActivePowC OBJECT-TYPE
|
||
SYNTAX Integer32 (-120000..120000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"System phase C output active power.The value ranges from -12000 to 12000,
|
||
The value is accurate to one decimal place on the NetEco. The unit is kW.
|
||
"
|
||
::= { hwUpsParaSysEntry 4 }
|
||
|
||
hwUpsParaSysOutAppearPowA OBJECT-TYPE
|
||
SYNTAX Integer32 (-120000..120000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"System phase A output apparent power.The value ranges from -12000 to 12000,
|
||
The value is accurate to one decimal place on the NetEco. The unit is kVA.
|
||
"
|
||
::= { hwUpsParaSysEntry 5 }
|
||
|
||
hwUpsParaSysOutAppearPowB OBJECT-TYPE
|
||
SYNTAX Integer32 (-120000..120000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"System phase B output apparent power.The value ranges from -12000 to 12000,
|
||
The value is accurate to one decimal place on the NetEco. The unit is kVA.
|
||
"
|
||
::= { hwUpsParaSysEntry 6 }
|
||
|
||
hwUpsParaSysOutAppearPowC OBJECT-TYPE
|
||
SYNTAX Integer32 (-120000..120000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"System phase C output apparent power.The value ranges from -12000 to 12000,
|
||
The value is accurate to one decimal place on the NetEco. The unit is kVA.
|
||
"
|
||
::= { hwUpsParaSysEntry 7 }
|
||
|
||
hwUpsParaSysOutLoadFactorA OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..5000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"System A output load factor.The value ranges from 0 to 500,
|
||
The value is accurate to one decimal place on the NetEco. The unit is %"
|
||
::= { hwUpsParaSysEntry 8 }
|
||
|
||
hwUpsParaSysOutLoadFactorB OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..5000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"System B output load factor.The value ranges from 0 to 500,
|
||
The value is accurate to one decimal place on the NetEco. The unit is %."
|
||
::= { hwUpsParaSysEntry 9 }
|
||
|
||
hwUpsParaSysOutLoadFactorC OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..5000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"System C output load factor.The value ranges from 0 to 500,
|
||
The value is accurate to one decimal place on the NetEco. The unit is %."
|
||
::= { hwUpsParaSysEntry 10 }
|
||
|
||
hwUpsParallelSystemRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus of ups parallel System Identification table."
|
||
::= { hwUpsParaSysEntry 100 }
|
||
|
||
hwUpsRackUnevenCur OBJECT IDENTIFIER ::= { hwUpsMIBObjects 108 }
|
||
|
||
hwUpsRackUnevenCurTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwUpsRackUnevenCurEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
""
|
||
::= { hwUpsRackUnevenCur 1 }
|
||
|
||
hwUpsRackUnevenCurEntry OBJECT-TYPE
|
||
SYNTAX HwUpsRackUnevenCurEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
""
|
||
INDEX { hwUpsRackUnevenCurRackId }
|
||
::= { hwUpsRackUnevenCurTable 1 }
|
||
|
||
HwUpsRackUnevenCurEntry ::= SEQUENCE {
|
||
hwUpsRackUnevenCurRackId
|
||
Unsigned32,
|
||
hwUpsRackUnevenCurSysGrant
|
||
Unsigned32,
|
||
hwUpsRackUnevenCurPowerSupplyMode
|
||
INTEGER,
|
||
hwUpsRackUnevenCurPowerOnModNum
|
||
Unsigned32,
|
||
hwUpsRackUnevenCurSleepModNum
|
||
Unsigned32,
|
||
hwUpsRackOutputCurrentA
|
||
Unsigned32,
|
||
hwUpsRackOutputCurrentB
|
||
Unsigned32,
|
||
hwUpsRackOutputCurrentC
|
||
Unsigned32,
|
||
hwUpsRackUnevenCurA
|
||
Unsigned32,
|
||
hwUpsRackUnevenCurB
|
||
Unsigned32,
|
||
hwUpsRackUnevenCurC
|
||
Unsigned32,
|
||
hwUpsRackUnevenCurValueTag
|
||
Unsigned32,
|
||
hwUpsRackUnevenCurRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwUpsRackUnevenCurRackId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (1..6)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ups Rack Id.Range from 1 to 6.This node is referenced as an index node
|
||
by hwUpsRackUnevenCurTable"
|
||
::= { hwUpsRackUnevenCurEntry 1 }
|
||
|
||
hwUpsRackUnevenCurSysGrant OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"System grant.An integer ranging from 0 to 10000."
|
||
::= { hwUpsRackUnevenCurEntry 2 }
|
||
|
||
hwUpsRackUnevenCurPowerSupplyMode OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
noOutput(1),
|
||
bypass(2),
|
||
normal(3),
|
||
battery(4),
|
||
sourceShare(5),
|
||
normalECO(6),
|
||
batteryECO(7)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Device power supply mode. Enumeration type.
|
||
Value 1 indicates no power supply.
|
||
Value 2 indicates bypass mode.
|
||
Value 3 indicates normal mode.
|
||
Value 4 indicates battery mode.
|
||
Value 5 indicates combined mode.
|
||
Value 6 indicates mains ECO mode.
|
||
Value 7 indicates battery ECO mode."
|
||
::= { hwUpsRackUnevenCurEntry 3 }
|
||
|
||
hwUpsRackUnevenCurPowerOnModNum OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..20)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack PowerOn Module Num.Range from 0 to 20."
|
||
::= { hwUpsRackUnevenCurEntry 4 }
|
||
|
||
hwUpsRackUnevenCurSleepModNum OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..20)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack Sleep Module Num.Range from 0 to 20."
|
||
::= { hwUpsRackUnevenCurEntry 5 }
|
||
|
||
hwUpsRackOutputCurrentA OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack phase A output current. The value ranges from 0 to 10000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is A."
|
||
::= { hwUpsRackUnevenCurEntry 6 }
|
||
|
||
hwUpsRackOutputCurrentB OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack phase B output current. The value ranges from 0 to 10000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is A."
|
||
::= { hwUpsRackUnevenCurEntry 7 }
|
||
|
||
hwUpsRackOutputCurrentC OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack phase C output current. The value ranges from 0 to 10000.
|
||
The value is accurate to one decimal place on the NetEco. The unit is A."
|
||
::= { hwUpsRackUnevenCurEntry 8 }
|
||
|
||
hwUpsRackUnevenCurA OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack phase A uneven current. The value ranges from 0 to 10000.
|
||
The value is accurate to one decimal place on the NetEco. "
|
||
::= { hwUpsRackUnevenCurEntry 9 }
|
||
|
||
hwUpsRackUnevenCurB OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack phase B uneven current. The value ranges from 0 to 10000.
|
||
The value is accurate to one decimal place on the NetEco. "
|
||
::= { hwUpsRackUnevenCurEntry 10 }
|
||
|
||
hwUpsRackUnevenCurC OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack phase C uneven current. The value ranges from 0 to 10000.
|
||
The value is accurate to one decimal place on the NetEco. "
|
||
::= { hwUpsRackUnevenCurEntry 11 }
|
||
|
||
hwUpsRackUnevenCurValueTag OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..1)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack uneven current value tag.range 0 to 1,0 indicates invalid,1 indicates valid."
|
||
::= { hwUpsRackUnevenCurEntry 12 }
|
||
|
||
hwUpsRackUnevenCurRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus of UPS Rack Uneven Current table."
|
||
::= { hwUpsRackUnevenCurEntry 100 }
|
||
|
||
hwUpsMIBTraps OBJECT IDENTIFIER ::= { hwUpsMIB 2 }
|
||
|
||
hwUpsTrapsVbOids OBJECT IDENTIFIER ::= { hwUpsMIBTraps 1 }
|
||
|
||
hwUpsTrapsDeviceId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (1..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ID of the device on which the active alarm is generated. An integer ranging from 1 to 100."
|
||
::= { hwUpsTrapsVbOids 1 }
|
||
|
||
hwUpsTrapsModuleSeqId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (1..4294967295)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The alarm module name, which produces alarm.
|
||
This name may be one of Monitor module name,Bypass module name,ECU module name and Power module name.
|
||
If it's value is empty, it indicates the alarm is a synthetical alarm and not belong to any module device."
|
||
::= { hwUpsTrapsVbOids 2 }
|
||
|
||
hwUpsTrapsEquipID OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..154)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Active alarm module ID, ranging from 1 to 154."
|
||
::= { hwUpsTrapsVbOids 3 }
|
||
|
||
hwUpsTrapsID OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..4294967295)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ID of an active alarm, ranging from 0 to 4294967295."
|
||
::= { hwUpsTrapsVbOids 4 }
|
||
|
||
hwUpsTrapsReasonId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Alarm reason ID. Value range: 0 to 100, and the value is an integer (.0)."
|
||
::= { hwUpsTrapsVbOids 5 }
|
||
|
||
hwUpsTrapsText OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..127))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Alarm name. It is of the character string type, and used to specify the content of a specific alarm."
|
||
::= { hwUpsTrapsVbOids 6 }
|
||
|
||
hwUpsTrapsLevel OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
critical(1),
|
||
major(2),
|
||
minor(3),
|
||
warning(4)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Alarm level, which users can configure the alarm severity, is an enumeration type:
|
||
If the enumeration value is 1, it indicates a critical alarm;
|
||
If the enumeration value is 2, it indicates a major alarm;
|
||
If the enumeration value is 3, it indicates a minor alarm;
|
||
If the enumeration value is 4, it indicates a warning."
|
||
::= { hwUpsTrapsVbOids 7 }
|
||
|
||
hwUpsTrapsFlag OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
occur(1),
|
||
resume(2)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Flag bit of an active alarm. Enumeration type.
|
||
Value 1 indicates that an active alarm is generated.
|
||
Value 2 indicates that an active alarm is cleared."
|
||
::= { hwUpsTrapsVbOids 8 }
|
||
|
||
hwUpsTrapsSynchronNum OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Active alarm synchronization ID, ranging from 0 to 4294967295"
|
||
::= { hwUpsTrapsVbOids 9 }
|
||
|
||
hwUpsTrapsTime OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..4294967295)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Time when an active alarm is generated, ranging from 0 to 4294967295. The unit is seconds."
|
||
::= { hwUpsTrapsVbOids 10 }
|
||
|
||
hwUpsCommonTraps OBJECT IDENTIFIER ::= { hwUpsMIBTraps 2 }
|
||
|
||
hwUpsCommonTrapsPrefix OBJECT IDENTIFIER ::= { hwUpsCommonTraps 0 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.2.2.0.1
|
||
-- 1.3.6.1.4.1.2011.6.174.2.2.0.1
|
||
-- 1.3.6.1.4.1.2011.6.174.2.2.0.1
|
||
hwUpsSummaryAlarmTrap NOTIFICATION-TYPE
|
||
STATUS current
|
||
DESCRIPTION
|
||
"UPS Summary Alarm status changed. Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time.
|
||
Additionally, in order to identify the status, UPS system operate status are also include in VB(variable bondings):
|
||
If the enumeration value is Normal(2), it indicates that UPS system resumes form alarm.
|
||
If the enumeration value is Alarm(3), it indicates that a new alarm occurs on the UPS sytem."
|
||
::= { hwUpsCommonTrapsPrefix 1 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.2.2.0.2
|
||
-- 1.3.6.1.4.1.2011.6.174.2.2.0.2
|
||
-- 1.3.6.1.4.1.2011.6.174.2.2.0.2
|
||
hwUpsPowerModInslotChangeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
|
||
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Power module inslot status changed.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time.
|
||
Additionally, in order to identify the operation, power module operate status are also include in VB(variable bondings):
|
||
If the enumeration value is Normal(2), it indicates that a new power module is inserted in slot;
|
||
If the enumeration value is Alarm(3), it indicates that communication of the power module module fails or module is not in slot. "
|
||
::= { hwUpsCommonTrapsPrefix 2 }
|
||
|
||
hwUpsPowerStatusWarnTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"When UPS Power Status changed, a warn trap will be send.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsCommonTrapsPrefix 3 }
|
||
|
||
hwUpsPowerStatusWarnResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"UPS Power Status warn resume trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsCommonTrapsPrefix 4 }
|
||
|
||
hwUpsSwitchStatusWarnTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"When contactor or switch status changed, a warn trap will be send.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsCommonTrapsPrefix 5 }
|
||
|
||
hwUpsSwitchStatusWarnResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Contactor or switch warn resume trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsCommonTrapsPrefix 6 }
|
||
|
||
hwUpsModCommFailedTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"When module communicates failed, a trap will be send.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsCommonTrapsPrefix 7 }
|
||
|
||
hwUpsModCommFailedResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Module communication failed Resume.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsCommonTrapsPrefix 8 }
|
||
|
||
hwUpsModConfigWarnTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"When module config status changed, a warn trap will be send.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsCommonTrapsPrefix 9 }
|
||
|
||
hwUpsModConfigWarnResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Module config warn resume trap.
|
||
Its correlation binding parameters:Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsCommonTrapsPrefix 10 }
|
||
|
||
hwUpsRecWarnTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"When rectifier status changed, a warn trap will be send.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsCommonTrapsPrefix 11 }
|
||
|
||
hwUpsRecWarnResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rectifier warn resume trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsCommonTrapsPrefix 12 }
|
||
|
||
hwUpsChargerPowerWarnTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"When charger power status changed, a warn trap will be send.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsCommonTrapsPrefix 13 }
|
||
|
||
hwUpsChargerPowerWarnResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Charger power warn resume trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
|
||
::= { hwUpsCommonTrapsPrefix 14 }
|
||
|
||
hwUpsGeneratorWarnTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"When generator status changed, a warn trap will be send.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsCommonTrapsPrefix 15 }
|
||
|
||
hwUpsGeneratorWarnResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Generator warn resume trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsCommonTrapsPrefix 16 }
|
||
|
||
hwUpsInvWarnTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"When inverter status changed, a warn trap will be send.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsCommonTrapsPrefix 17 }
|
||
|
||
hwUpsInvWarnResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inverter warn resume trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsCommonTrapsPrefix 18 }
|
||
|
||
hwUpsLBSWarnTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"When LBS status changed, a warn trap will be send.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsCommonTrapsPrefix 19 }
|
||
|
||
hwUpsLBSWarnResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"LBS warn resume trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsCommonTrapsPrefix 20 }
|
||
|
||
hwUpsSwitchTipWarnTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"When switch method changed or there is a switch tip, a warn trap will be send.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsCommonTrapsPrefix 21 }
|
||
|
||
hwUpsSwitchTipWarnResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Switch method or switch tip warn resume trap.
|
||
Its correlation binding parameters:Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsCommonTrapsPrefix 22 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.2.2.0.23
|
||
-- 1.3.6.1.4.1.2011.6.174.2.2.0.23
|
||
-- 1.3.6.1.4.1.2011.6.174.2.2.0.23
|
||
hwUpsBattDetachWarnTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
|
||
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"When battery detach, a warn trap will be send.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsCommonTrapsPrefix 23 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.2.2.0.24
|
||
-- 1.3.6.1.4.1.2011.6.174.2.2.0.24
|
||
-- 1.3.6.1.4.1.2011.6.174.2.2.0.24
|
||
hwUpsBattDetachWarnResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
|
||
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery detach warn resume trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsCommonTrapsPrefix 24 }
|
||
|
||
hwUpsBattStatusWarnTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"When battery status abnormal, a warn trap will be send through this OID.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsCommonTrapsPrefix 25 }
|
||
|
||
hwUpsBattStatusWarnResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"When battery status abnormal resume, a trap will be send through this OID.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsCommonTrapsPrefix 26 }
|
||
|
||
hwUpsBatteryTestWarnTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"When battery test start, a warn trap will be send through this OID.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time.
|
||
"
|
||
::= { hwUpsCommonTrapsPrefix 27 }
|
||
|
||
hwUpsBatteryTestWarnResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"When battery test end, a trap will be send through this OID.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsCommonTrapsPrefix 28 }
|
||
|
||
hwUpsRackComFailedTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"When Rack communication fail happen, a alarm trap will be send.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time.
|
||
"
|
||
::= { hwUpsCommonTrapsPrefix 29 }
|
||
|
||
hwUpsRackComFaiedResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack communication fail alarm resume.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsCommonTrapsPrefix 30 }
|
||
|
||
hwUpsRackMasterConflictTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"When Rack Master Conflict alarm happen, a alarm trap will be send.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsCommonTrapsPrefix 31 }
|
||
|
||
hwUpsRackMasterConflictResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rack Master Conflict alarm resume.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsCommonTrapsPrefix 32 }
|
||
|
||
hwUpsRackNumNoMatchTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"UPS Rack num dismatch warn. Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time.
|
||
Additionally, in order to identify the status, UPS system operate status are also include in VB(variable bondings):
|
||
If the enumeration value is Normal(2), it indicates that UPS system resumes form alarm.
|
||
If the enumeration value is Alarm(3), it indicates that a new alarm occurs on the UPS sytem."
|
||
::= { hwUpsCommonTrapsPrefix 33 }
|
||
|
||
hwUpsRackNumNoMatchResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"UPS Rack num dismatch warn resume. Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time.
|
||
Additionally, in order to identify the status, UPS system operate status are also include in VB(variable bondings):
|
||
If the enumeration value is Normal(2), it indicates that UPS system resumes form alarm.
|
||
If the enumeration value is Alarm(3), it indicates that a new alarm occurs on the UPS sytem.
|
||
"
|
||
::= { hwUpsCommonTrapsPrefix 34 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.2.2.1
|
||
hwUpsCommonStateTrapsPrefix OBJECT IDENTIFIER ::= { hwUpsCommonTraps 1 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.2.2.0.35
|
||
-- 1.3.6.1.4.1.2011.6.174.2.2.0.35
|
||
-- 1.3.6.1.4.1.2011.6.174.2.2.1.1
|
||
hwUpsRackOnlineStateChangeTrap NOTIFICATION-TYPE
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ups Rack Online State Change Trap. Its correlation binding parameters: NULL"
|
||
::= { hwUpsCommonStateTrapsPrefix 1 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.2.2.0.36
|
||
-- 1.3.6.1.4.1.2011.6.174.2.2.0.36
|
||
-- 1.3.6.1.4.1.2011.6.174.2.2.1.2
|
||
hwUpsRackConfigChangeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ups Rack Config Change.Its correlation binding parameters: Device ID"
|
||
::= { hwUpsCommonStateTrapsPrefix 2 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.2.2.0.37
|
||
-- 1.3.6.1.4.1.2011.6.174.2.2.0.37
|
||
-- 1.3.6.1.4.1.2011.6.174.2.2.1.3
|
||
hwUpsRackRunningStateChangeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsDeviceRunningStatus, hwUpsTrapsDeviceId }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ups Rack Running State Change.Its correlation binding parameters: Device ID and Device running state."
|
||
::= { hwUpsCommonStateTrapsPrefix 3 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.2.2.0.38
|
||
-- 1.3.6.1.4.1.2011.6.174.2.2.0.38
|
||
-- 1.3.6.1.4.1.2011.6.174.2.2.1.4
|
||
hwUpsBatteryRunningStateChangeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsDeviceBatteryState, hwUpsTrapsDeviceId }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ups Battery Running State Change,Its correlation binding parameters: Device ID and Battery Running State"
|
||
::= { hwUpsCommonStateTrapsPrefix 4 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.2.2.1.5
|
||
hwUpsEnergyFloatChangeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsDeviceEnergyFloatState, hwUpsTrapsDeviceId }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ups Energy Float Change,Its correlation binding parameters: Device ID and The Energy Float State"
|
||
::= { hwUpsCommonStateTrapsPrefix 5 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.2.2.1.6
|
||
hwUpsVersionChangeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ups Version Change,Its correlation binding parameters: Device ID"
|
||
::= { hwUpsCommonStateTrapsPrefix 6 }
|
||
|
||
hwUpsAlarmTraps OBJECT IDENTIFIER ::= { hwUpsMIBTraps 3 }
|
||
|
||
hwUpsAlarmTrapsPrefix OBJECT IDENTIFIER ::= { hwUpsAlarmTraps 0 }
|
||
|
||
hwUpsModNumAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"When power module number dismatch, a alarm trap will be send.
|
||
Its correlation binding parameters:Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 1 }
|
||
|
||
hwUpsModNumAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Power module number dismatch alarm resume trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 2 }
|
||
|
||
hwUpsBypassUnitAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Bypass Unit Abnormal Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 3 }
|
||
|
||
hwUpsBypassUnitAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Bypass Unit Abnormal Resume Trap.
|
||
Its correlation binding parameters:Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 4 }
|
||
|
||
hwUpsInRackParallelLineAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"In-Rack Parallel Line Abnormal Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time.
|
||
"
|
||
::= { hwUpsAlarmTrapsPrefix 5 }
|
||
|
||
hwUpsInRackParallelLineAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description: In-Rack Parallel Line Abnormal Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 6 }
|
||
|
||
hwUpsBetweenRackParallelLineAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Between-Rack Parallel Line Abnormal Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 7 }
|
||
|
||
hwUpsBetweenRackParallelLineAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Between-Rack Parallel Line Abnormal Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 8 }
|
||
|
||
hwUpsFanAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Fan Abnormal Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 9 }
|
||
|
||
hwUpsFanAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Fan Abnormal Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 10 }
|
||
|
||
hwUpsAuxiliaryPowerAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Auxiliary Power Abnormal Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 11 }
|
||
|
||
hwUpsAuxiliaryPowerAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Auxiliary Power Abnormal Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 12 }
|
||
|
||
hwUpsVersionMismatchAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"when version mismatch alarms happen, a alarm trap will be send.
|
||
Its correlation binding parameters:Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 13 }
|
||
|
||
hwUpsVersionMatchAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Version mismatch Abnormal Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 14 }
|
||
|
||
hwUpsAddrConflictAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Address Conflict Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 15 }
|
||
|
||
hwUpsAddrConflictAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Address Conflict Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 16 }
|
||
|
||
hwUpsEmergencyPowerOffAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Emergency Power Off Abnormal Trap.
|
||
Its correlation binding parameters:Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 17 }
|
||
|
||
hwUpsEmergencyPowerOffAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Emergency Power Off Abnormal Resume Trap.
|
||
Its correlation binding parameters:Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 18 }
|
||
|
||
hwUpsBypassInputAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Bypass Input Abnormal Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 19 }
|
||
|
||
hwUpsBypassInputAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Bypass Input Abnormal Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 20 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.2.3.0.21
|
||
-- 1.3.6.1.4.1.2011.6.174.2.3.0.21
|
||
-- 1.3.6.1.4.1.2011.6.174.2.3.0.21
|
||
hwUpsInputIsolatingTransAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
|
||
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Transformer Abnormal Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 21 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.2.3.0.22
|
||
-- 1.3.6.1.4.1.2011.6.174.2.3.0.22
|
||
-- 1.3.6.1.4.1.2011.6.174.2.3.0.22
|
||
hwUpsInputIsolatingTransAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
|
||
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Transformer Abnormal Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 22 }
|
||
|
||
|
||
hwUpsInternalAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Supervision Unit Internal Fault Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 23 }
|
||
|
||
hwUpsInternalAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Supervision Unit Internal Fault Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 24 }
|
||
|
||
hwUpsRectifierAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rectifier Abnormal Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 25 }
|
||
|
||
hwUpsRectifierAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rectifier Abnormal Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 26 }
|
||
|
||
hwUpsChargerAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Charger Abnormal Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 27 }
|
||
|
||
hwUpsChargerAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Charger Abnormal Resume Trap.
|
||
Its correlation binding parameters:Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 28 }
|
||
|
||
hwUpsDischargerAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Discharger Abnormal Trap.
|
||
Its correlation binding parameters:Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 29 }
|
||
|
||
hwUpsDischargerAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Discharger Abnormal Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 30 }
|
||
|
||
hwUpsACAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC Abnormal Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 31 }
|
||
|
||
hwUpsACAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC Abnormal Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 32 }
|
||
|
||
hwUpsModuleNotReadyAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Module Not Ready Abnormal Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 33 }
|
||
|
||
hwUpsModuleNotReadyAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Module Not Ready Abnormal Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 34 }
|
||
|
||
hwUpsInverterAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inverter Abnormal Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 35 }
|
||
|
||
hwUpsInverterAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inverter Abnormal Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 36 }
|
||
|
||
hwUpsECUAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ECU Abnormal Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 37 }
|
||
|
||
hwUpsECUAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ECU Abnormal Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 38 }
|
||
|
||
hwUpsSPDAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"SPD Abnormal Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 39 }
|
||
|
||
hwUpsSPDAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"SPD Abnormal Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 40 }
|
||
|
||
hwUpsOperationFaultAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Operation Fault Abnormal Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 41 }
|
||
|
||
hwUpsOperationFaultAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Operation Fault Abnormal Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 42 }
|
||
|
||
hwUpsOverLoadAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Over Load Abnormal Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 43 }
|
||
|
||
hwUpsOverLoadAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Over Load Abnormal Resume Trap.
|
||
Its correlation binding parameters:Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 44 }
|
||
|
||
hwUpsOverLoadOverTimeAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Over-Load Overtime Abnormal Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 45 }
|
||
|
||
hwUpsOverLoadOverTimeAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Over-Load Overtime Abnormal Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 46 }
|
||
|
||
hwUpsLBSAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"LBS Abnormal Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 47 }
|
||
|
||
hwUpsLBSAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"LBS Abnormal Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 48 }
|
||
|
||
hwUpsBypSwitchAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Bypass Switch Abnormal Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 49 }
|
||
|
||
hwUpsBypSwitchAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Bypass Switch Abnormal Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 50 }
|
||
|
||
hwUpsBatteryFault1AlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"When battery reversed, no Battery, battery earth fault or battery stop discharge abnormal happen, an alarm trap will be send through this OID.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 51 }
|
||
|
||
hwUpsBatteryFault1AlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"When battery reversed, no Battery, battery earth fault or battery stop discharge abnormal resume, a trap will be send through this OID.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 52 }
|
||
|
||
hwUpsBatteryFault2AlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"When battery over temperature, battery need maintenance, or battery voltage low abnormal happen, an alarm trap will be send through this OID.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 53 }
|
||
|
||
hwUpsBatteryFault2AlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"When battery over temperature, battery need maintenance, or battery voltage low abnormal resume, a trap will be send through this OID.
|
||
Its correlation binding parameters:Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 54 }
|
||
|
||
hwUpsBatteryChangeLimitAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery Change Limit Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 55 }
|
||
|
||
hwUpsBatteryChangeLimitAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery Change Limit Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 56 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.2.3.0.57
|
||
hwUpsRectifierStartLimitAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
|
||
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rectifier Start Limit Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 57 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.2.3.0.58
|
||
hwUpsRectifierStartLimitAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
|
||
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rectifier Start Limit Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 58 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.2.3.0.59
|
||
hwUpsMainLoadCapicityAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
|
||
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Main Load Capicity Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 59 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.2.3.0.60
|
||
hwUpsMainLoadCapicityAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
|
||
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Main Load Capicity Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 60 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.2.3.0.61
|
||
hwUpsBatteryChangeAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
|
||
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Batterry Change Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 61 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.2.3.0.62
|
||
hwUpsBatteryChangeAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
|
||
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Batterry Change Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 62 }
|
||
|
||
hwUpsBatteryMaintainAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Batterry Maintain Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 63 }
|
||
|
||
hwUpsBatteryMaintainAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Batterry Maintain Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 64 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.2.3.0.65
|
||
hwUpsMinorLoadOffAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
|
||
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Minor Load Off Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 65 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.2.3.0.66
|
||
hwUpsMinorLoadOffAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
|
||
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Minor Load Off Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 66 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.2.3.0.67
|
||
hwUpsParaStatusSetAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
|
||
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Parallel Status Set Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 67 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.2.3.0.68
|
||
hwUpsParaStatusSetAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
|
||
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Parallel Status Set Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 68 }
|
||
|
||
hwUpsRemainCapacityAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Remain Capacity Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 69 }
|
||
|
||
hwUpsRemainCapacityAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Remain Capacity Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 70 }
|
||
|
||
hwUpsParParaAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Parallel Parameter Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
|
||
::= { hwUpsAlarmTrapsPrefix 71 }
|
||
|
||
hwUpsParParaAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Parallel Parameter Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the tim"
|
||
::= { hwUpsAlarmTrapsPrefix 72 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.2.3.0.73
|
||
hwUpsFlashAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
|
||
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Flash Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
|
||
::= { hwUpsAlarmTrapsPrefix 73 }
|
||
|
||
|
||
-- 1.3.6.1.4.1.2011.6.174.2.3.0.74
|
||
hwUpsFlashAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
|
||
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Flash Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
|
||
::= { hwUpsAlarmTrapsPrefix 74 }
|
||
|
||
hwUpsManulPowerOnOffTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Manul Power On Off Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 75 }
|
||
|
||
hwUpsManulPowerOnOffResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Manul Power On Off Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
|
||
::= { hwUpsAlarmTrapsPrefix 76 }
|
||
|
||
hwUpsIOAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"IO signal Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
|
||
::= { hwUpsAlarmTrapsPrefix 77 }
|
||
|
||
hwUpsIOAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"IO Signal Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
|
||
::= { hwUpsAlarmTrapsPrefix 78 }
|
||
|
||
hwUpsEnvironmentDataAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Environment Date Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
|
||
::= { hwUpsAlarmTrapsPrefix 79 }
|
||
|
||
hwUpsEnvironmentDataAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Environment Date Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
|
||
::= { hwUpsAlarmTrapsPrefix 80 }
|
||
|
||
hwUpsUpdatingAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Updating Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
|
||
::= { hwUpsAlarmTrapsPrefix 81 }
|
||
|
||
hwUpsUpdatingAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Updating Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
|
||
::= { hwUpsAlarmTrapsPrefix 82 }
|
||
|
||
hwUpsProgramAbnormalTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Program Abnormal Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
|
||
::= { hwUpsAlarmTrapsPrefix 83 }
|
||
|
||
hwUpsProgramAbnormalResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Program Abnormal Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
|
||
::= { hwUpsAlarmTrapsPrefix 84 }
|
||
|
||
hwUpsBcbFaultAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Bcb Fault Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
|
||
::= { hwUpsAlarmTrapsPrefix 85 }
|
||
|
||
hwUpsBcbFaultAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Bcb Fault Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
|
||
::= { hwUpsAlarmTrapsPrefix 86 }
|
||
|
||
hwUpsEcoRangeAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ECO Range Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
|
||
::= { hwUpsAlarmTrapsPrefix 87 }
|
||
|
||
hwUpsEcoRangeAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ECO Range Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
|
||
::= { hwUpsAlarmTrapsPrefix 88 }
|
||
|
||
hwUpsBMUAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Bmu Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
|
||
::= { hwUpsAlarmTrapsPrefix 89 }
|
||
|
||
hwUpsBMUAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Bmu Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
|
||
::= { hwUpsAlarmTrapsPrefix 90 }
|
||
|
||
hwUpsElableFailedAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Elable Failed Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
|
||
::= { hwUpsAlarmTrapsPrefix 91 }
|
||
|
||
hwUpsElableFailedAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Elable Failed Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
|
||
::= { hwUpsAlarmTrapsPrefix 92 }
|
||
|
||
hwUpsDIPConflictAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DIP Conflict Trap"
|
||
::= { hwUpsAlarmTrapsPrefix 93 }
|
||
|
||
hwUpsDIPConflictAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DIP Conflict Resume Trap."
|
||
::= { hwUpsAlarmTrapsPrefix 94 }
|
||
|
||
hwUpsSystemStatusTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ups System Status Trap."
|
||
::= { hwUpsAlarmTrapsPrefix 95 }
|
||
|
||
hwUpsSystemStatusResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ups System Status Resume Trap."
|
||
::= { hwUpsAlarmTrapsPrefix 96 }
|
||
|
||
hwUpsIBOXAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ups IBOX Alarm Trap."
|
||
::= { hwUpsAlarmTrapsPrefix 97 }
|
||
|
||
hwUpsIBOXAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ups IBOX Alarm Resume Trap"
|
||
::= { hwUpsAlarmTrapsPrefix 98 }
|
||
|
||
hwUpsBattRackAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Expand Borad Alarm Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 99 }
|
||
|
||
hwUpsBattRackAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Expand Borad Alarm Resume Trap.
|
||
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
|
||
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
|
||
::= { hwUpsAlarmTrapsPrefix 100 }
|
||
|
||
END
|