HUAWEI-UPS-MIB DEFINITIONS ::= BEGIN
IMPORTS
huaweiUtility
FROM HUAWEI-MIB
OBJECT-GROUP, NOTIFICATION-GROUP
FROM SNMPv2-CONF
Integer32, Unsigned32, OBJECT-TYPE, MODULE-IDENTITY, NOTIFICATION-TYPE
FROM SNMPv2-SMI
TEXTUAL-CONVENTION
FROM SNMPv2-TC;
hwUpsMIB MODULE-IDENTITY
LAST-UPDATED "201210240000Z"
ORGANIZATION
"Huawei Technologies Co., Ltd."
CONTACT-INFO
"Floor 5, Block 4, R&D Building,
Huawei Longgang Production Base,
Shenzhen, P.R.C.
http: // www.huawei.com
Zip: 518129."
DESCRIPTION
"EMAP MIB defines MIB objects which provides load and backup management, patch management NMS interfaces.
The current version is v1.01"
REVISION "201210240000Z"
DESCRIPTION
"Huawei emap mib v1.00"
::= { huaweiUtility 174 }
DisplayString ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Description."
SYNTAX OCTET STRING (SIZE (1..64))
RowStatus ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Description."
SYNTAX INTEGER
{
active(1),
notInService(2),
notReady(3),
createAndGo(4),
createAndWait(5),
destroy(6)
}
DateAndTime ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Description."
SYNTAX OCTET STRING (SIZE (8..11))
RunStatus ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"This integer value represents running status of the system.
Depending on situation there may be limits on allowed values.
Operational values:
(1) unknown - status has not yet been defined
(2) normal - there are no activated alarms
(3) alarm - alarm status
"
SYNTAX INTEGER
{
unknow(1),
normal(2),
alarm(3)
}
MeasuresRange ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Description."
SYNTAX Integer32
TruthValue ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Description."
SYNTAX INTEGER
{
true(1),
false(2)
}
hwUpsMIBObjects OBJECT IDENTIFIER ::= { hwUpsMIB 1 }
hwUpsSystem OBJECT IDENTIFIER ::= { hwUpsMIBObjects 1 }
hwUpsSysIdent OBJECT IDENTIFIER ::= { hwUpsSystem 1 }
hwUpsSystemMainDeviceESN OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..127))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"ESN of the master device used for setting up a NetEco model. A string of characters."
::= { hwUpsSysIdent 1 }
hwUpsSystemType OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..127))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Name of the UPS system. A string of characters. Configurable."
::= { hwUpsSysIdent 2 }
hwUpsSysInerProtVersion OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..127))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Version number of the system interface protocol between the NetEco and NEs.
A string of characters."
::= { hwUpsSysIdent 3 }
hwUpsSysDeviceNum OBJECT-TYPE
SYNTAX Unsigned32 (0..63)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of devices in the system. An integer ranging from 0 to 63."
::= { hwUpsSysIdent 4 }
hwUpsParallelSysNum OBJECT-TYPE
SYNTAX Unsigned32 (0..63)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of parallel systems. An integer ranging from 0 to 63."
::= { hwUpsSysIdent 5 }
hwUpsEnvTemper OBJECT-TYPE
SYNTAX Integer32 ( -500..1200)
UNITS "C"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Ambient temperature. An integer ranging from -50 to 120.
The value is accurate to one decimal place on the NetEco. The unit is C"
::= { hwUpsSysIdent 6 }
hwUpsEnvHumidity OBJECT-TYPE
SYNTAX Unsigned32 (0..1000)
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Ambient humidity. An integer ranging from 0 to 100.
The value is accurate to one decimal place on the NetEco. The unit is %."
::= { hwUpsSysIdent 7 }
hwUpsDevice OBJECT IDENTIFIER ::= { hwUpsMIBObjects 2 }
hwUpsDeviceIdentTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwUpsDeviceIdentEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The device identification table. Use this table to get device ID, and to get device type,
the soft version, the iner prot version, the ESN, the rating power of device,
the parallel system index of device. This table's index is hwUpsDeviceId."
::= { hwUpsDevice 100 }
hwUpsDeviceIdentEntry OBJECT-TYPE
SYNTAX HwUpsDeviceIdentEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The device identification table. Use this table to get device ID, and to get device type,
the soft version, the iner prot version, the ESN, the rating power of device,
the parallel system index of device. This table's index is hwUpsDeviceId."
INDEX { hwUpsDeviceId }
::= { hwUpsDeviceIdentTable 1 }
HwUpsDeviceIdentEntry ::= SEQUENCE {
hwUpsDeviceId
Unsigned32,
hwUpsDeviceType
OCTET STRING,
hwUpsDeviceSoftVersion
OCTET STRING,
hwUpsDeviceInerProtVersion
OCTET STRING,
hwUpsDeviceESN
OCTET STRING,
hwUpsDevicePowerRating
INTEGER,
hwUpsDeviceParaSysIndex
Unsigned32,
hwUpsDeviceSysGrant
Unsigned32,
hwUpsDeviceMonitorSoftVersion
OCTET STRING,
hwUpsDevicePowerSoftVersion
OCTET STRING,
hwUpsDeviceIdentRowStatus
RowStatus
}
hwUpsDeviceId OBJECT-TYPE
SYNTAX Unsigned32 (1..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack ID, ranging from 1 to 100. This node is referenced as an index node
by hwUpsDeviceIdentTable, hwUpsDeviceOperInfoTable, hwUpsInputTable,
hwUpsOutputTable,hwUpsBypassTable, hwUpsBatteryTable, hwUpsControlTable,
and hwUpsBattScheduleTestTable."
::= { hwUpsDeviceIdentEntry 1 }
hwUpsDeviceType OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..127))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Device model. A string of characters."
::= { hwUpsDeviceIdentEntry 2 }
hwUpsDeviceSoftVersion OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..127))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Device software version number. A string of characters."
::= { hwUpsDeviceIdentEntry 3 }
hwUpsDeviceInerProtVersion OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..127))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Interface protocol version number for the current device. A string of characters."
::= { hwUpsDeviceIdentEntry 4 }
hwUpsDeviceESN OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..127))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"ESN. A string of characters."
::= { hwUpsDeviceIdentEntry 5 }
hwUpsDevicePowerRating OBJECT-TYPE
SYNTAX INTEGER
{
level80(1),
level100(2),
level120(3),
level160(4),
level200(5),
level30(6),
level40(7),
level60(8),
level240(9),
level250(10),
level280(11),
level300(12)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System capacity. Enumeration type. The default value is 5. The unit is kVA.
Value 1 indicates 80 kVA
Value 2 indicates 100 kVA.
Value 3 indicates 120 kVA.
Value 4 indicates 160 kVA.
Value 5 indicates 200 kVA."
::= { hwUpsDeviceIdentEntry 6 }
hwUpsDeviceParaSysIndex OBJECT-TYPE
SYNTAX Unsigned32 (0..63)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"ID of the parallel system that the current device belongs to. An integer ranging from 0 to 63."
::= { hwUpsDeviceIdentEntry 7 }
hwUpsDeviceSysGrant OBJECT-TYPE
SYNTAX Unsigned32 (0..10000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System grant.An integer ranging from 0 to 10000."
::= { hwUpsDeviceIdentEntry 8 }
hwUpsDeviceMonitorSoftVersion OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..127))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Monitor software version number. A string of characters."
::= { hwUpsDeviceIdentEntry 9 }
hwUpsDevicePowerSoftVersion OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..127))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Power software version number A string of characters."
::= { hwUpsDeviceIdentEntry 10 }
hwUpsDeviceIdentRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RowStatus of UPS device Identification table."
::= { hwUpsDeviceIdentEntry 100 }
hwUpsDeviceOperInfoTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwUpsDeviceOperInfoEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Device running information table. It's index is hwUpsDeviceId"
::= { hwUpsDevice 101 }
hwUpsDeviceOperInfoEntry OBJECT-TYPE
SYNTAX HwUpsDeviceOperInfoEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Device running information table. It's index is hwUpsDeviceId"
INDEX { hwUpsDeviceId }
::= { hwUpsDeviceOperInfoTable 1 }
HwUpsDeviceOperInfoEntry ::= SEQUENCE {
hwUpsDevicePowerSupplyMethod
INTEGER,
hwUpsDeviceRunningStatus
INTEGER,
hwUpsDeviceBatteryState
INTEGER,
hwUpsDeviceTemperature
Unsigned32,
hwUpsDeviceEnergyFloatState
Unsigned32,
hwUpsDeviceRedundantNumber
Unsigned32,
hwUpsDeviceDelayShutdownState
Unsigned32,
hwUpsDeviceDelayShutdownOrder
INTEGER,
hwUpsDeviceWorkMode
INTEGER,
hwUpsDeviceSmartPowerMode
INTEGER,
hwUpsDeviceBSCState
INTEGER,
hwUpsDeviceOperInfoRowStatus
RowStatus
}
hwUpsDevicePowerSupplyMethod OBJECT-TYPE
SYNTAX INTEGER
{
noOutput(1),
bypass(2),
normal(3),
battery(4),
sourceShare(5),
normalECO(6),
batteryECO(7)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Device power supply mode. Enumeration type.
Value 1 indicates no power supply.
Value 2 indicates bypass mode.
Value 3 indicates normal mode.
Value 4 indicates battery mode.
Value 5 indicates combined mode.
Value 6 indicates mains ECO mode.
Value 7 indicates battery ECO mode."
::= { hwUpsDeviceOperInfoEntry 1 }
hwUpsDeviceRunningStatus OBJECT-TYPE
SYNTAX INTEGER
{
single(1),
parallel(2),
singleECO(3),
parallelECO(4),
aging(5)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"UPS operating status. Enumeration type.
Value 1 indicates that a single UPS is operating.
Value 2 indicates that the parallel system is operating.
Value 3 indicates that a single UPS is operating in ECO mode.
Value 4 indicates that the parallel system is operating in ECO mode.
Value 5 indicates aging."
::= { hwUpsDeviceOperInfoEntry 2 }
hwUpsDeviceBatteryState OBJECT-TYPE
SYNTAX INTEGER
{
notExist(1),
temperaryMode(2),
sleep(3),
floatCharge(4),
boostCharge(5),
discharge(6)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery status. Enumeration type.
Value 1 indicates that no battery is connected.
Value 2 indicates that the battery is not charging or discharging.
Value 3 indicates hibernation.
Value 4 indicates float charging.
Value 5 indicates equalized charging.
Value 6 indicates discharging."
::= { hwUpsDeviceOperInfoEntry 3 }
hwUpsDeviceTemperature OBJECT-TYPE
SYNTAX Unsigned32 (0..3000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Maximum temperature of the modules in the current device. An integer ranging from 0 to 300."
::= { hwUpsDeviceOperInfoEntry 4 }
hwUpsDeviceEnergyFloatState OBJECT-TYPE
SYNTAX Unsigned32 (0..70000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current flow status. An integer ranging from 0 to 70000. "
::= { hwUpsDeviceOperInfoEntry 5 }
hwUpsDeviceRedundantNumber OBJECT-TYPE
SYNTAX Unsigned32 (0..3)
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Redundant number of the parallel system. An integer ranging from 0 to 3."
::= { hwUpsDeviceOperInfoEntry 6 }
hwUpsDeviceDelayShutdownState OBJECT-TYPE
SYNTAX Unsigned32 (0..4294967295)
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Delay to shutdown state. An integer ranging from 0 to 4294967295"
::= { hwUpsDeviceOperInfoEntry 7 }
hwUpsDeviceDelayShutdownOrder OBJECT-TYPE
SYNTAX INTEGER
{
invalid(1),
valid(2)
}
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Delay to shutdown state. Enumeration type.
Value 1 indicates invalid.
Value 2 indicates valid."
::= { hwUpsDeviceOperInfoEntry 8 }
hwUpsDeviceWorkMode OBJECT-TYPE
SYNTAX INTEGER
{
normalMode(1),
ecoMode(2),
selfloadMode(3),
converterMode(4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Work Mode. Enumeration type.
Value 1 indicates that normal mode.
Value 2 indicates that eco mode.
Value 3 indicates that self load mode.
Value 4 indicates that converter mode.
"
::= { hwUpsDeviceOperInfoEntry 9 }
hwUpsDeviceSmartPowerMode OBJECT-TYPE
SYNTAX INTEGER
{
disable(1),
enable(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Smart Power Mode.Enumeration type.
Value 1 indicates that disable.
Value 2 indicates that enable.
"
::= { hwUpsDeviceOperInfoEntry 10 }
hwUpsDeviceBSCState OBJECT-TYPE
SYNTAX INTEGER
{
notExist(1),
masterMode(2),
slaveMode(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"BSC system status. Enumeration type.
Value 1: Not activated
Value 2: BSC master mode
Value 3: BSC slave mode"
::= { hwUpsDeviceOperInfoEntry 11 }
hwUpsDeviceOperInfoRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RowStatus of UPS device running information table."
::= { hwUpsDeviceOperInfoEntry 101 }
hwUpsInput OBJECT IDENTIFIER ::= { hwUpsMIBObjects 3 }
hwUpsInputTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwUpsInputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"UPS input information table. It's index is hwUpsDeviceId"
::= { hwUpsInput 100 }
hwUpsInputEntry OBJECT-TYPE
SYNTAX HwUpsInputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"UPS input information table. It's index is hwUpsDeviceId"
INDEX { hwUpsDeviceId }
::= { hwUpsInputTable 1 }
HwUpsInputEntry ::= SEQUENCE {
hwUpsInputVoltageA
Unsigned32,
hwUpsInputVoltageB
Unsigned32,
hwUpsInputVoltageC
Unsigned32,
hwUpsInputFrequency
Unsigned32,
hwUpsInputCurrentA
Unsigned32,
hwUpsInputCurrentB
Unsigned32,
hwUpsInputCurrentC
Unsigned32,
hwUpsInputPowerFactorA
Integer32,
hwUpsInputPowerFactorB
Integer32,
hwUpsInputPowerFactorC
Integer32,
hwUpsInputLineVoltageAB
Unsigned32,
hwUpsInputLineVoltageBC
Unsigned32,
hwUpsInputLineVoltageCA
Unsigned32,
hwUpsInputRowStatus
RowStatus
}
hwUpsInputVoltageA OBJECT-TYPE
SYNTAX Unsigned32 (0..10000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Input voltage phase A. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. The unit is V."
::= { hwUpsInputEntry 1 }
hwUpsInputVoltageB OBJECT-TYPE
SYNTAX Unsigned32 (0..10000)
UNITS "V"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Input voltage phase B. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. The unit is V."
::= { hwUpsInputEntry 2 }
hwUpsInputVoltageC OBJECT-TYPE
SYNTAX Unsigned32 (0..10000)
UNITS "V"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Input voltage phase C. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. The unit is V."
::= { hwUpsInputEntry 3 }
hwUpsInputFrequency OBJECT-TYPE
SYNTAX Unsigned32 (0..10000)
UNITS "Hz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Input frequency. The value ranges from 0 to 10000.
The value is accurate to two decimal place on the NetEco. The unit is Hz."
::= { hwUpsInputEntry 4 }
hwUpsInputCurrentA OBJECT-TYPE
SYNTAX Unsigned32 (0..10000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Input current phase A. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. The unit is A."
::= { hwUpsInputEntry 5 }
hwUpsInputCurrentB OBJECT-TYPE
SYNTAX Unsigned32 (0..10000)
UNITS "A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Input current phase B. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. The unit is A."
::= { hwUpsInputEntry 6 }
hwUpsInputCurrentC OBJECT-TYPE
SYNTAX Unsigned32 (0..10000)
UNITS "A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Input current phase C. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. The unit is A."
::= { hwUpsInputEntry 7 }
hwUpsInputPowerFactorA OBJECT-TYPE
SYNTAX Integer32 ( -100..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase A input power factor. The value ranges from -100 to 100.
The value is accurate to one decimal place on the NetEco."
::= { hwUpsInputEntry 8 }
hwUpsInputPowerFactorB OBJECT-TYPE
SYNTAX Integer32 ( -100..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase B input power factor. The value ranges from -100 to 100.
The value is accurate to one decimal place on the NetEco."
::= { hwUpsInputEntry 9 }
hwUpsInputPowerFactorC OBJECT-TYPE
SYNTAX Integer32 ( -100..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase C input power factor. The value ranges from -100 to 100.
The value is accurate to one decimal place on the NetEco."
::= { hwUpsInputEntry 10 }
hwUpsInputLineVoltageAB OBJECT-TYPE
SYNTAX Unsigned32 (0..20000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Input Line voltage AB. The value ranges from 0 to 20000.
The value is accurate to one decimal place on the NetEco. The unit is V."
::= { hwUpsInputEntry 11 }
hwUpsInputLineVoltageBC OBJECT-TYPE
SYNTAX Unsigned32 (0..20000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Input Line voltage BC. The value ranges from 0 to 20000.
The value is accurate to one decimal place on the NetEco. The unit is V."
::= { hwUpsInputEntry 12 }
hwUpsInputLineVoltageCA OBJECT-TYPE
SYNTAX Unsigned32 (0..20000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Input Line voltage CA. The value ranges from 0 to 20000.
The value is accurate to one decimal place on the NetEco. The unit is V."
::= { hwUpsInputEntry 13 }
hwUpsInputRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RowStatus of UPS input information table."
::= { hwUpsInputEntry 100 }
hwUpsOutput OBJECT IDENTIFIER ::= { hwUpsMIBObjects 4 }
hwUpsOutputTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwUpsOutputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"UPS output information table. It's index is hwUpsDeviceId."
::= { hwUpsOutput 100 }
hwUpsOutputEntry OBJECT-TYPE
SYNTAX HwUpsOutputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"UPS output information table. It's index is hwUpsDeviceId.
"
INDEX { hwUpsDeviceId }
::= { hwUpsOutputTable 1 }
HwUpsOutputEntry ::= SEQUENCE {
hwUpsOutputVoltageA
Unsigned32,
hwUpsOutputVoltageB
Unsigned32,
hwUpsOutputVoltageC
Unsigned32,
hwUpsOutputCurrentA
Unsigned32,
hwUpsOutputCurrentB
Unsigned32,
hwUpsOutputCurrentC
Unsigned32,
hwUpsOutputFrequency
Unsigned32,
hwUpsOutputActivePowerA
Integer32,
hwUpsOutputActivePowerB
Integer32,
hwUpsOutputActivePowerC
Integer32,
hwUpsOutputAppearancePowerA
Integer32,
hwUpsOutputAppearancePowerB
Integer32,
hwUpsOutputAppearancePowerC
Integer32,
hwUpsOutputLoadA
Unsigned32,
hwUpsOutputLoadB
Unsigned32,
hwUpsOutputLoadC
Unsigned32,
hwUpsOutputPowerRating
INTEGER,
hwUpsOutputFrequencyRating
INTEGER,
hwUpsOutputPowerFactorA
Integer32,
hwUpsOutputPowerFactorB
Integer32,
hwUpsOutputPowerFactorC
Integer32,
hwUpsOutputLineVoltageAB
Unsigned32,
hwUpsOutputLineVoltageBC
Unsigned32,
hwUpsOutputLineVoltageCA
Unsigned32,
hwUpsRackOutputPeakRatioA
Unsigned32,
hwUpsRackOutputPeakRatioB
Unsigned32,
hwUpsRackOutputPeakRatioC
Unsigned32,
hwUpsOutputRowStatus
RowStatus
}
hwUpsOutputVoltageA OBJECT-TYPE
SYNTAX Unsigned32 ( 0..10000)
UNITS "V"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack phase A output voltage. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. The unit is V.
"
::= { hwUpsOutputEntry 1 }
hwUpsOutputVoltageB OBJECT-TYPE
SYNTAX Unsigned32 ( 0..10000)
UNITS "V"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack phase B output voltage. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. The unit is V."
::= { hwUpsOutputEntry 2 }
hwUpsOutputVoltageC OBJECT-TYPE
SYNTAX Unsigned32 ( 0..10000)
UNITS "V"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack phase C output voltage. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. The unit is V."
::= { hwUpsOutputEntry 3 }
hwUpsOutputCurrentA OBJECT-TYPE
SYNTAX Unsigned32 ( 0..10000)
UNITS "A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack phase A output current. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. The unit is A."
::= { hwUpsOutputEntry 4 }
hwUpsOutputCurrentB OBJECT-TYPE
SYNTAX Unsigned32 ( 0..10000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack phase B output current. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. The unit is A."
::= { hwUpsOutputEntry 5 }
hwUpsOutputCurrentC OBJECT-TYPE
SYNTAX Unsigned32 ( 0..10000)
UNITS "A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack phase C output current. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. The unit is A."
::= { hwUpsOutputEntry 6 }
hwUpsOutputFrequency OBJECT-TYPE
SYNTAX Unsigned32 ( 0..10000)
UNITS "Hz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack output frequency. The value ranges from 0 to 10000.
The value is accurate to two decimal place on the NetEco. The unit is Hz."
::= { hwUpsOutputEntry 7 }
hwUpsOutputActivePowerA OBJECT-TYPE
SYNTAX Integer32 ( -12000..12000)
UNITS "kW"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack phase A output active power. The value ranges from -12000 to 12000.
The value is accurate to one decimal place on the NetEco. The unit is kW."
::= { hwUpsOutputEntry 8 }
hwUpsOutputActivePowerB OBJECT-TYPE
SYNTAX Integer32 ( -12000..12000)
UNITS "kW"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack phase B output active power. The value ranges from -12000 to 12000.
The value is accurate to one decimal place on the NetEco. The unit is kW."
::= { hwUpsOutputEntry 9 }
hwUpsOutputActivePowerC OBJECT-TYPE
SYNTAX Integer32 ( -12000..12000)
UNITS "kW"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack phase C output active power. The value ranges from -12000 to 12000.
The value is accurate to one decimal place on the NetEco. The unit is kW."
::= { hwUpsOutputEntry 10 }
hwUpsOutputAppearancePowerA OBJECT-TYPE
SYNTAX Integer32 ( -12000..12000)
UNITS "kVA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack phase A output apparent power. The value ranges from -12000 to 12000.
The value is accurate to one decimal place on the NetEco. The unit is kVA."
::= { hwUpsOutputEntry 11 }
hwUpsOutputAppearancePowerB OBJECT-TYPE
SYNTAX Integer32 ( -12000..12000)
UNITS "kVA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack phase B output apparent power. The value ranges from -12000 to 12000.
The value is accurate to one decimal place on the NetEco. The unit is kVA."
::= { hwUpsOutputEntry 12 }
hwUpsOutputAppearancePowerC OBJECT-TYPE
SYNTAX Integer32 ( -12000..12000)
UNITS "kVA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack phase C output apparent power. The value ranges from -12000 to 12000.
The value is accurate to one decimal place on the NetEco. The unit is kVA."
::= { hwUpsOutputEntry 13 }
hwUpsOutputLoadA OBJECT-TYPE
SYNTAX Unsigned32 (0..999)
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack phase A output load ratio. The value ranges from 0 to 5000 The value is accurate to one decimal place on the NetEco."
::= { hwUpsOutputEntry 14 }
hwUpsOutputLoadB OBJECT-TYPE
SYNTAX Unsigned32 (0..999)
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack phase B output load ratio. The value ranges from 0 to 5000 The value is accurate to one decimal place on the NetEco."
::= { hwUpsOutputEntry 15 }
hwUpsOutputLoadC OBJECT-TYPE
SYNTAX Unsigned32 (0..999)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack phase C output load ratio. The value ranges from 0 to 5000 The value is accurate to one decimal place on the NetEco."
::= { hwUpsOutputEntry 16 }
hwUpsOutputPowerRating OBJECT-TYPE
SYNTAX INTEGER
{
level200(1),
level208(2),
level220(3),
level380(4),
level400(5),
level415(6),
level480(7),
level600(8),
level690(9)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rated output voltage (system voltage level). Enumeration type. The default value is 6. The unit is V.
Value 1 indicates 200 V.
Value 2 indicates 208 V.
Value 3 indicates 220 V.
Value 4 indicates 380 V.
Value 5 indicates 400 V.
Value 6 indicates 415 V.
Value 7 indicates 480 V.
Value 8 indicates 600 V.
Value 9 indicates 690 V."
::= { hwUpsOutputEntry 17 }
hwUpsOutputFrequencyRating OBJECT-TYPE
SYNTAX INTEGER
{
level50(1),
level60(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rated output frequency. Enumeration type. The default value is 2. The unit is Hz.
Value 1 indicates 50 Hz.
Value 2 indicates 60 Hz."
::= { hwUpsOutputEntry 18 }
hwUpsOutputPowerFactorA OBJECT-TYPE
SYNTAX Integer32 ( -100..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack phase A output power factor.
The value ranges from -100 to 100 The value is accurate to two decimal place on the NetEco."
::= { hwUpsOutputEntry 19 }
hwUpsOutputPowerFactorB OBJECT-TYPE
SYNTAX Integer32 ( -100..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack phase B output power factor.
The value ranges from -100 to 100 The value is accurate to two decimal place on the NetEco.
"
::= { hwUpsOutputEntry 20 }
hwUpsOutputPowerFactorC OBJECT-TYPE
SYNTAX Integer32 ( -100..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack phase C output power factor.
The value ranges from -100 to 100 The value is accurate to two decimal place on the NetEco."
::= { hwUpsOutputEntry 21 }
hwUpsOutputLineVoltageAB OBJECT-TYPE
SYNTAX Unsigned32 (0..20000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack Line AB output voltage. The value ranges from 0 to 20000.
The value is accurate to one decimal place on the NetEco. The unit is V."
::= { hwUpsOutputEntry 22 }
hwUpsOutputLineVoltageBC OBJECT-TYPE
SYNTAX Unsigned32 (0..20000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack Line BC output voltage. The value ranges from 0 to 20000.
The value is accurate to one decimal place on the NetEco. The unit is V."
::= { hwUpsOutputEntry 23 }
hwUpsOutputLineVoltageCA OBJECT-TYPE
SYNTAX Unsigned32 (0..20000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack Line CA output voltage. The value ranges from 0 to 20000.
The value is accurate to one decimal place on the NetEco. The unit is V."
::= { hwUpsOutputEntry 24 }
hwUpsRackOutputPeakRatioA OBJECT-TYPE
SYNTAX Unsigned32 (0..1000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack A Out Peak Ratio. The value ranges from 0 to 1000.
The value is accurate to one decimal place on the NetEco. The unit is %."
::= { hwUpsOutputEntry 25 }
hwUpsRackOutputPeakRatioB OBJECT-TYPE
SYNTAX Unsigned32 (0..1000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack B Out Peak Ratio. The value ranges from 0 to 1000.
The value is accurate to one decimal place on the NetEco. The unit is %."
::= { hwUpsOutputEntry 26 }
hwUpsRackOutputPeakRatioC OBJECT-TYPE
SYNTAX Unsigned32 (0..1000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack C Out Peak Ratio. The value ranges from 0 to 1000.
The value is accurate to one decimal place on the NetEco. The unit is %."
::= { hwUpsOutputEntry 27 }
hwUpsOutputRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RowStatus of UPS output information table."
::= { hwUpsOutputEntry 100 }
hwUpsBypass OBJECT IDENTIFIER ::= { hwUpsMIBObjects 5 }
hwUpsBypassTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwUpsBypassEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"UPS bypass information table. It's index is hwUpsDeviceId."
::= { hwUpsBypass 100 }
hwUpsBypassEntry OBJECT-TYPE
SYNTAX HwUpsBypassEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"UPS bypass information table. It's index is hwUpsDeviceId."
INDEX { hwUpsDeviceId }
::= { hwUpsBypassTable 1 }
HwUpsBypassEntry ::= SEQUENCE {
hwUpsBypassInputVoltageA
Unsigned32,
hwUpsBypassInputVoltageB
Unsigned32,
hwUpsBypassInputVoltageC
Unsigned32,
hwUpsBypassInputFrequency
Unsigned32,
hwUpsBypassInputCurrentA
Unsigned32,
hwUpsBypassInputCurrentB
Unsigned32,
hwUpsBypassInputCurrentC
Unsigned32,
hwUpsBypassInputLineVoltageAB
Unsigned32,
hwUpsBypassInputLineVoltageBC
Unsigned32,
hwUpsBypassInputLineVoltageCA
Unsigned32,
hwUpsBypassRowStatus
RowStatus
}
hwUpsBypassInputVoltageA OBJECT-TYPE
SYNTAX Unsigned32 ( 0..10000)
UNITS "V"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Bypass input voltage phase A. The value ranges from 0 to 10000
The value is accurate to one decimal place on the NetEco. The unit is V."
::= { hwUpsBypassEntry 1 }
hwUpsBypassInputVoltageB OBJECT-TYPE
SYNTAX Unsigned32 ( 0..10000)
UNITS "V"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Bypass input voltage phase B. The value ranges from 0 to 10000
The value is accurate to one decimal place on the NetEco. The unit is V."
::= { hwUpsBypassEntry 2 }
hwUpsBypassInputVoltageC OBJECT-TYPE
SYNTAX Unsigned32 ( 0..10000)
UNITS "V"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Bypass input voltage phase C. The value ranges from 0 to 10000
The value is accurate to one decimal place on the NetEco. The unit is V."
::= { hwUpsBypassEntry 3 }
hwUpsBypassInputFrequency OBJECT-TYPE
SYNTAX Unsigned32 ( 0..10000)
UNITS "Hz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Bypass input frequency. The value ranges from 0 to 10000
The value is accurate to two decimal place on the NetEco. The unit is Hz."
::= { hwUpsBypassEntry 4 }
hwUpsBypassInputCurrentA OBJECT-TYPE
SYNTAX Unsigned32 (0..60000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Bypass input current phase A. The value ranges from 0 to 60000
The value is accurate to one decimal place on the NetEco. The unit is A."
::= { hwUpsBypassEntry 5 }
hwUpsBypassInputCurrentB OBJECT-TYPE
SYNTAX Unsigned32 (0..60000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Bypass input current phase B. The value ranges from 0 to 60000
The value is accurate to one decimal place on the NetEco. The unit is A."
::= { hwUpsBypassEntry 6 }
hwUpsBypassInputCurrentC OBJECT-TYPE
SYNTAX Unsigned32 (0..60000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Bypass input current phase C. The value ranges from 0 to 60000
The value is accurate to one decimal place on the NetEco. The unit is A."
::= { hwUpsBypassEntry 7 }
hwUpsBypassInputLineVoltageAB OBJECT-TYPE
SYNTAX Unsigned32 (0..20000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Bypass Input Line voltage AB. The value ranges from 0 to 20000.
The value is accurate to one decimal place on the NetEco. The unit is V."
::= { hwUpsBypassEntry 8 }
hwUpsBypassInputLineVoltageBC OBJECT-TYPE
SYNTAX Unsigned32 (0..20000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Bypass Input Line voltage BC. The value ranges from 0 to 20000.
The value is accurate to one decimal place on the NetEco. The unit is V."
::= { hwUpsBypassEntry 9 }
hwUpsBypassInputLineVoltageCA OBJECT-TYPE
SYNTAX Unsigned32 (0..20000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Bypass Input Line voltage CA. The value ranges from 0 to 20000.
The value is accurate to one decimal place on the NetEco. The unit is V."
::= { hwUpsBypassEntry 10 }
hwUpsBypassRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RowStatus of UPS bypass information table."
::= { hwUpsBypassEntry 100 }
hwUpsBattery OBJECT IDENTIFIER ::= { hwUpsMIBObjects 6 }
hwUpsBatteryTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwUpsBatteryEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"UPS battery information table. It's index is hwUpsDeviceId."
::= { hwUpsBattery 100 }
hwUpsBatteryEntry OBJECT-TYPE
SYNTAX HwUpsBatteryEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"UPS battery information table. It's index is hwUpsDeviceId."
INDEX { hwUpsDeviceId }
::= { hwUpsBatteryTable 1 }
HwUpsBatteryEntry ::= SEQUENCE {
hwUpsBatteryVoltage
Unsigned32,
hwUpsBatteryCurrent
Integer32,
hwUpsBatteryCapacityLeft
Unsigned32,
hwUpsBatteryBackupTime
Unsigned32,
hwUpsBatteryNumber
Unsigned32,
hwUpsBatterytemperature
Unsigned32,
hwUpsBatterySoh
INTEGER,
hwUpsBatteryRowStatus
RowStatus
}
hwUpsBatteryVoltage OBJECT-TYPE
SYNTAX Unsigned32 (0..10000)
UNITS "V"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery Voltage. It is a real-time analog parameter.
Value range: 0 to 20000, Unit: V, and the value is accurate to one decimal place (.1)."
::= { hwUpsBatteryEntry 1 }
hwUpsBatteryCurrent OBJECT-TYPE
SYNTAX Integer32 (-60000..60000)
UNITS "A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery Total Current. It is a real-time analog parameter.
Value range: -60000 to 60000, Unit: A, and the value is accurate to one decimal place (.1)."
::= { hwUpsBatteryEntry 2 }
hwUpsBatteryCapacityLeft OBJECT-TYPE
SYNTAX Unsigned32 (0..100)
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery Capacity Left. Value range: 0 to 100, Unit: %, and the value is an integer."
::= { hwUpsBatteryEntry 3 }
hwUpsBatteryBackupTime OBJECT-TYPE
SYNTAX Unsigned32 (0..172800)
UNITS "S"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery Backup Time. Value range: 0 to 172800, Unit: S, and the value is an integer."
::= { hwUpsBatteryEntry 4 }
hwUpsBatteryNumber OBJECT-TYPE
SYNTAX Unsigned32 (1..240)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery group number.Value range: 1 to 240,and the value is an integer."
::= { hwUpsBatteryEntry 5 }
hwUpsBatterytemperature OBJECT-TYPE
SYNTAX Unsigned32 (-200..800)
UNITS "C"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery temperature.Value range: -20 to 80, Unit:C, and the value is accurate to one decimal place (.1)"
::= { hwUpsBatteryEntry 6 }
hwUpsBatterySoh OBJECT-TYPE
SYNTAX INTEGER
{
good(1),
requiringMaintenance(2),
repalceBatt(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Description."
::= { hwUpsBatteryEntry 7 }
hwUpsBatteryRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RowStatus of UPS battery information table."
::= { hwUpsBatteryEntry 100 }
-- 1.3.6.1.4.1.2011.6.174.1.10
hwUpsParallelSystem OBJECT IDENTIFIER ::= { hwUpsMIBObjects 10 }
-- 1.3.6.1.4.1.2011.6.174.1.10.1
hwUpsParaSysTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwUpsParaSysEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"UPS parallel system table. Its index is hwUpsDeviceId."
::= { hwUpsParallelSystem 1 }
-- 1.3.6.1.4.1.2011.6.174.1.10.1.1
hwUpsParaSysEntry OBJECT-TYPE
SYNTAX HwUpsParaSysEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"UPS parallel system table entry."
INDEX { hwUpsDeviceId }
::= { hwUpsParaSysTable 1 }
HwUpsParaSysEntry ::=
SEQUENCE {
hwUpsParaSysId
Unsigned32,
hwUpsParaSysOutActivePowA
Integer32,
hwUpsParaSysOutActivePowB
Integer32,
hwUpsParaSysOutActivePowC
Integer32,
hwUpsParaSysOutAppearPowA
Integer32,
hwUpsParaSysOutAppearPowB
Integer32,
hwUpsParaSysOutAppearPowC
Integer32,
hwUpsParaSysOutLoadFactorA
Unsigned32,
hwUpsParaSysOutLoadFactorB
Unsigned32,
hwUpsParaSysOutLoadFactorC
Unsigned32,
hwUpsParallelSystemRowStatus
RowStatus
}
-- 1.3.6.1.4.1.2011.6.174.1.10.1.1.1
hwUpsParaSysId OBJECT-TYPE
SYNTAX Unsigned32 (0..127)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"ID of the parallel system that the current rack belongs to. "
::= { hwUpsParaSysEntry 1 }
-- 1.3.6.1.4.1.2011.6.174.1.10.1.1.2
hwUpsParaSysOutActivePowA OBJECT-TYPE
SYNTAX Integer32 (-120000..120000)
UNITS "kW"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System phase A output active power.The value ranges from -12000 to 12000,
The value is accurate to one decimal place on the NetEco. The unit is kW."
::= { hwUpsParaSysEntry 2 }
-- 1.3.6.1.4.1.2011.6.174.1.10.1.1.3
hwUpsParaSysOutActivePowB OBJECT-TYPE
SYNTAX Integer32 (-120000..120000)
UNITS "kW"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System phase B output active power.The value ranges from -12000 to 12000,
The value is accurate to one decimal place on the NetEco. The unit is kW."
::= { hwUpsParaSysEntry 3 }
-- 1.3.6.1.4.1.2011.6.174.1.10.1.1.4
hwUpsParaSysOutActivePowC OBJECT-TYPE
SYNTAX Integer32 (-120000..120000)
UNITS "kW"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System phase C output active power.The value ranges from -12000 to 12000,
The value is accurate to one decimal place on the NetEco. The unit is kW."
::= { hwUpsParaSysEntry 4 }
-- 1.3.6.1.4.1.2011.6.174.1.10.1.1.5
hwUpsParaSysOutAppearPowA OBJECT-TYPE
SYNTAX Integer32 (-120000..120000)
UNITS "kVA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System phase A output apparent power.The value ranges from -12000 to 12000,
The value is accurate to one decimal place on the NetEco. The unit is kVA."
::= { hwUpsParaSysEntry 5 }
-- 1.3.6.1.4.1.2011.6.174.1.10.1.1.6
hwUpsParaSysOutAppearPowB OBJECT-TYPE
SYNTAX Integer32 (-120000..120000)
UNITS "kVA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System phase B output apparent power.The value ranges from -12000 to 12000,
The value is accurate to one decimal place on the NetEco. The unit is kVA."
::= { hwUpsParaSysEntry 6 }
-- 1.3.6.1.4.1.2011.6.174.1.10.1.1.7
hwUpsParaSysOutAppearPowC OBJECT-TYPE
SYNTAX Integer32 (-120000..120000)
UNITS "kVA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System phase C output apparent power.The value ranges from -12000 to 12000,
The value is accurate to one decimal place on the NetEco. The unit is kVA."
::= { hwUpsParaSysEntry 7 }
-- 1.3.6.1.4.1.2011.6.174.1.10.1.1.8
hwUpsParaSysOutLoadFactorA OBJECT-TYPE
SYNTAX Unsigned32 (0..5000)
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System phase A output reactive power.The value ranges from 0 to 500,
The value is accurate to one decimal place on the NetEco. The unit is %."
::= { hwUpsParaSysEntry 8 }
-- 1.3.6.1.4.1.2011.6.174.1.10.1.1.9
hwUpsParaSysOutLoadFactorB OBJECT-TYPE
SYNTAX Unsigned32 (0..5000)
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System phase B output reactive power.The value ranges from 0 to 500,
The value is accurate to one decimal place on the NetEco. The unit is %."
::= { hwUpsParaSysEntry 9 }
-- 1.3.6.1.4.1.2011.6.174.1.10.1.1.10
hwUpsParaSysOutLoadFactorC OBJECT-TYPE
SYNTAX Unsigned32 (0..5000)
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System phase C output reactive power.The value ranges from 0 to 500,
The value is accurate to one decimal place on the NetEco. The unit is %."
::= { hwUpsParaSysEntry 10 }
-- 1.3.6.1.4.1.2011.6.174.1.10.1.1.100
hwUpsParallelSystemRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RowStatus of ups parallel System Identification table."
::= { hwUpsParaSysEntry 100 }
hwUpsSiteTime OBJECT IDENTIFIER ::= { hwUpsMIBObjects 11 }
hwUpsSiteTimeUTC OBJECT-TYPE
SYNTAX Unsigned32 (0..4294967295)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"UTC time, ranging from 0 to 4294967295. The unit is seconds."
::= { hwUpsSiteTime 1 }
hwUpsSiteTimeZone OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"UTC time zone that the current rack belongs to."
::= { hwUpsSiteTime 2 }
hwUpsAlarm OBJECT IDENTIFIER ::= { hwUpsMIBObjects 12 }
hwUpsAlarmSynchronNum OBJECT-TYPE
SYNTAX Unsigned32 (0..4294967295)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Alarm synchronization ID. The value ranges from 0 to 4294967295.
This value is used by the NetEco to obtain the active alarm synchronization ID and synchronize alarms."
::= { hwUpsAlarm 1 }
hwUpsAlarmCurrActiveNum OBJECT-TYPE
SYNTAX Unsigned32 (0..8000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of active alarms, ranging from 0 to 8000."
::= { hwUpsAlarm 2 }
hwUpsAlarmCurrCriticalNum OBJECT-TYPE
SYNTAX Unsigned32 (0..8000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of critical active alarms, ranging from 0 to 8000."
::= { hwUpsAlarm 3 }
hwUpsAlarmCurrMajorNum OBJECT-TYPE
SYNTAX Unsigned32 (0..8000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of major active alarms, ranging from 0 to 8000."
::= { hwUpsAlarm 4 }
hwUpsAlarmCurrMinorNum OBJECT-TYPE
SYNTAX Unsigned32 (0..8000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of minor active alarms, ranging from 0 to 8000."
::= { hwUpsAlarm 5 }
hwUpsAlarmCurrWarningNum OBJECT-TYPE
SYNTAX Unsigned32 (0..8000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of warning active alarms, ranging from 0 to 8000."
::= { hwUpsAlarm 6 }
hwUpsActiveAlarm OBJECT IDENTIFIER ::= { hwUpsMIBObjects 13 }
hwUpsActiveAlarmTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwUpsActiveAlarmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"UPS active alarm table. It's indexs are hwUpsActiveAlarmDeviceId and hwUpsActiveAlarmSeqId"
::= { hwUpsActiveAlarm 1 }
hwUpsActiveAlarmEntry OBJECT-TYPE
SYNTAX HwUpsActiveAlarmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"UPS active alarm table. It's indexs are hwUpsActiveAlarmDeviceId and hwUpsActiveAlarmSeqId"
INDEX { hwUpsActiveAlarmDeviceId, hwUpsActiveAlarmSeqId }
::= { hwUpsActiveAlarmTable 1 }
HwUpsActiveAlarmEntry ::= SEQUENCE {
hwUpsActiveAlarmDeviceId
Unsigned32,
hwUpsActiveAlarmSeqId
Unsigned32,
hwUpsActiveAlarmEquipID
Unsigned32,
hwUpsActiveAlarmID
Unsigned32,
hwUpsActiveAlarmReasonId
Unsigned32,
hwUpsActiveAlarmText
OCTET STRING,
hwUpsActiveAlarmLevel
INTEGER,
hwUpsActiveAlarmFlag
INTEGER,
hwUpsActiveAlarmSynchronNum
Unsigned32,
hwUpsActiveAlarmTime
Unsigned32,
hwUpsActiveAlarmRowStatus
RowStatus
}
hwUpsActiveAlarmDeviceId OBJECT-TYPE
SYNTAX Unsigned32 (1..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"ID of the device on which the active alarm is generated. An integer ranging from 1 to 100."
::= { hwUpsActiveAlarmEntry 1 }
hwUpsActiveAlarmSeqId OBJECT-TYPE
SYNTAX Unsigned32 (1..4294967295)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Sequence number of an active alarm, ranging from 1 to 4294967295."
::= { hwUpsActiveAlarmEntry 2 }
hwUpsActiveAlarmEquipID OBJECT-TYPE
SYNTAX Unsigned32 (0..10000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Active alarm module ID, ranging from 1 to 10000."
::= { hwUpsActiveAlarmEntry 3 }
hwUpsActiveAlarmID OBJECT-TYPE
SYNTAX Unsigned32 (0..4294967295)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"ID of an active alarm, ranging from 0 to 4294967295."
::= { hwUpsActiveAlarmEntry 4 }
hwUpsActiveAlarmReasonId OBJECT-TYPE
SYNTAX Unsigned32 (0..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Reason ID of an active alarm, ranging from 1 to 100."
::= { hwUpsActiveAlarmEntry 5 }
hwUpsActiveAlarmText OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..127))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"English name of an active alarm. A string of characters. "
::= { hwUpsActiveAlarmEntry 6 }
hwUpsActiveAlarmLevel OBJECT-TYPE
SYNTAX INTEGER
{
critical(1),
major(2),
minor(3),
warning(4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Severity of an active alarm. Enumeration type.
Value 1 indicates a critical alarm.
Value 2 indicates a major alarm.
Value 3 indicates a minor alarm.
Value 4 indicates a warning."
::= { hwUpsActiveAlarmEntry 7 }
hwUpsActiveAlarmFlag OBJECT-TYPE
SYNTAX INTEGER
{
occur(1),
resume(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Flag bit of an active alarm. Enumeration type.
Value 1 indicates that an active alarm is generated.
Value 2 indicates that an active alarm is cleared."
::= { hwUpsActiveAlarmEntry 8 }
hwUpsActiveAlarmSynchronNum OBJECT-TYPE
SYNTAX Unsigned32 (0..4294967295)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Active alarm synchronization ID, ranging from 0 to 4294967295."
::= { hwUpsActiveAlarmEntry 9 }
hwUpsActiveAlarmTime OBJECT-TYPE
SYNTAX Unsigned32 (0..4294967295)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Time when an active alarm is generated, ranging from 0 to 4294967295. The unit is seconds.
"
::= { hwUpsActiveAlarmEntry 10 }
hwUpsActiveAlarmRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RowStatus of ups active alarm table."
::= { hwUpsActiveAlarmEntry 11 }
hwUpsModule OBJECT IDENTIFIER ::= { hwUpsMIBObjects 107 }
hwUpsModuleTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwUpsModuleEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Description."
::= { hwUpsModule 1 }
hwUpsModuleEntry OBJECT-TYPE
SYNTAX HwUpsModuleEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Description."
INDEX { hwUpsModuleRackId }
::= { hwUpsModuleTable 1 }
HwUpsModuleEntry ::= SEQUENCE {
hwUpsModuleRackId
Unsigned32,
hwUpsPowerModuleId
Unsigned32,
hwUpsBusCapacitorLife
Unsigned32,
hwUpsInvACur
Unsigned32,
hwUpsInvBCur
Unsigned32,
hwUpsInvCCur
Unsigned32,
hwUpsModuleAUnevenFlow
Unsigned32,
hwUpsModuleBUnevenFlow
Unsigned32,
hwUpsModuleCUnevenFlow
Unsigned32,
hwUpsInvPowerStat
INTEGER,
hwUpsModuleUnevneCurValueTag
Unsigned32,
hwUpsModuleSleepState
Unsigned32,
hwUpsModuleRowStatus
RowStatus
}
hwUpsModuleRackId OBJECT-TYPE
SYNTAX Unsigned32 (1..6)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Ups Rack Id.Range from 1 to 6.This node is referenced as an index node
by hwUpsModuleTable."
::= { hwUpsModuleEntry 1 }
hwUpsPowerModuleId OBJECT-TYPE
SYNTAX Unsigned32 (1..20)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Ups Power Module Id.Range from 1 to 20.This node is referenced as an index node
by hwUpsModuleTable."
::= { hwUpsModuleEntry 2 }
hwUpsBusCapacitorLife OBJECT-TYPE
SYNTAX Unsigned32 (0..10000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Inv C Cap Life.Value range: 0 to 10000, Unit: Y, and the value is accurate to one decimal place (.1)."
::= { hwUpsModuleEntry 3 }
hwUpsInvACur OBJECT-TYPE
SYNTAX Unsigned32 (0..10000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Inv A Current.Value range: 0 to 10000.The value is accurate to one decimal place (.1).The unit is A."
::= { hwUpsModuleEntry 4 }
hwUpsInvBCur OBJECT-TYPE
SYNTAX Unsigned32 (0..10000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Inv B Current.Value range: 0 to 10000.The value is accurate to one decimal place (.1).The unit is A."
::= { hwUpsModuleEntry 5 }
hwUpsInvCCur OBJECT-TYPE
SYNTAX Unsigned32 (0..10000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Inv C Current.Value range: 0 to 10000.The value is accurate to one decimal place (.1).The unit is A."
::= { hwUpsModuleEntry 6 }
hwUpsModuleAUnevenFlow OBJECT-TYPE
SYNTAX Unsigned32 (0..10000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Module A Uneven Flow.Value range: 0 to 10000,and the value is accurate to one decimal place (.1)."
::= { hwUpsModuleEntry 7 }
hwUpsModuleBUnevenFlow OBJECT-TYPE
SYNTAX Unsigned32 (0..10000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Module B Uneven Flow.Value range: 0 to 10000,and the value is accurate to one decimal place (.1)."
::= { hwUpsModuleEntry 8 }
hwUpsModuleCUnevenFlow OBJECT-TYPE
SYNTAX Unsigned32 (0..1000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Module C Uneven Flow.Value range: 0 to 10000,and the value is accurate to one decimal place (.1)."
::= { hwUpsModuleEntry 9 }
hwUpsInvPowerStat OBJECT-TYPE
SYNTAX INTEGER
{
noOutput(1),
bypass(2),
normal(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Inv Power Stat.Enumeration type.
Value 0 indicates no power supply.
Value 1 indicates bypass mode.
Value 2 indicates normal mode."
::= { hwUpsModuleEntry 10 }
hwUpsModuleUnevneCurValueTag OBJECT-TYPE
SYNTAX Unsigned32 (0..1)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Module uneven current value tag.range 0 to 1,0 indicates invalid,1 indicates valid."
::= { hwUpsModuleEntry 11 }
hwUpsModuleSleepState OBJECT-TYPE
SYNTAX Unsigned32 (0..1)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Module Sleep State.Range 0 to 1,0 indicates not sleep,1 indicates sleep."
::= { hwUpsModuleEntry 12 }
hwUpsModuleRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RowStatus of UPS module information table."
::= { hwUpsModuleEntry 100 }
hwUpsControl OBJECT IDENTIFIER ::= { hwUpsMIBObjects 102 }
hwUpsControlTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwUpsControlEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"UPS control table. It's index is hwUpsRackId."
::= { hwUpsControl 100 }
hwUpsControlEntry OBJECT-TYPE
SYNTAX HwUpsControlEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"UPS control table. It's index is hwUpsRackId."
INDEX { hwUpsDeviceId }
::= { hwUpsControlTable 1 }
HwUpsControlEntry ::= SEQUENCE {
hwUpsCtrlECOSwitch
INTEGER,
hwUpsCtrlPowerOn
INTEGER,
hwUpsCtrlPowerOff
INTEGER,
hwUpsCtrlPowerOffDelay
Unsigned32,
hwUpsCtrlPowerBatCapacity
Unsigned32,
hwUpsCtrlPowerBatType
INTEGER,
hwUpsCtrlModelType
INTEGER,
hwUpsCtrlInputStandard
INTEGER,
hwUpsCtrlOutputStandard
INTEGER,
hwUpsCtrlPowerOnState
INTEGER,
hwUpsCtrlBatteryToBoostState
INTEGER,
hwUpsCtrlBatteryToFloatState
INTEGER,
hwUpsCtrlBatteryToTestState
INTEGER,
hwUpsCtrlBatteryStopTestState
INTEGER,
hwUpsCtrlBatteryManualBoostCharge
INTEGER,
hwUpsCtrlBatteryManualFloatCharge
INTEGER,
hwUpsCtrlBatteryShallowTest
INTEGER,
hwUpsCtrlBatteryVerifyCapTest
INTEGER,
hwUpsCtrlBatteryEndTest
INTEGER,
hwUpsCtrlModelCapacity
Unsigned32,
hwUpsCtrlEPO
INTEGER,
hwUpsSmartParallelSleepMode
INTEGER,
hwUpsCtrlRowStatus
RowStatus
}
hwUpsCtrlECOSwitch OBJECT-TYPE
SYNTAX INTEGER
{
noECO(1),
eco(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"ECO settings. Enumeration type. The default value is 1.
Value 1 indicates ECO mode.
Value 2 indicates Non ECO mode."
::= { hwUpsControlEntry 1 }
hwUpsCtrlPowerOn OBJECT-TYPE
SYNTAX INTEGER
{
powerOn(1),
unknown(255)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Power on settings. Enumeration type.
Value 1 indicates power on .
Value 2 indicates unknow."
::= { hwUpsControlEntry 2 }
hwUpsCtrlPowerOff OBJECT-TYPE
SYNTAX INTEGER
{
powerOff(1),
unknown(255)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Power off settings. Enumeration type.
Value 1 indicates power off .
Value 2 indicates unknow."
::= { hwUpsControlEntry 3 }
hwUpsCtrlPowerOffDelay OBJECT-TYPE
SYNTAX Unsigned32 (0..120000000)
UNITS "S"
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Delay power off.The value ranges from 0 to 120000000 . The unit is S."
::= { hwUpsControlEntry 4 }
hwUpsCtrlPowerBatCapacity OBJECT-TYPE
SYNTAX Unsigned32 (5..3000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery capacity, ranging from 5 to 3000.
"
::= { hwUpsControlEntry 5 }
hwUpsCtrlPowerBatType OBJECT-TYPE
SYNTAX INTEGER
{
vrla(1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery type.ECO settings. Enumeration type. The default value is 1.
Value 1 indicates VRLA batteries."
::= { hwUpsControlEntry 6 }
hwUpsCtrlModelType OBJECT-TYPE
SYNTAX INTEGER
{
model6K(17),
mode110K(33),
model20K(65)
}
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Model type,Enumeration type.
Value 17 indicates 6K.
Value 33 indicates 10K.
Value 65 indicates 20K."
::= { hwUpsControlEntry 7 }
hwUpsCtrlInputStandard OBJECT-TYPE
SYNTAX INTEGER
{
singlePhase(1),
threePhase(2)
}
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Input Standard,Enumeration type.
Value 1 indicates single phase.
Value 2 indicates three phase."
::= { hwUpsControlEntry 8 }
hwUpsCtrlOutputStandard OBJECT-TYPE
SYNTAX INTEGER
{
singlePhase(1)
threePhase(2)
}
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Output Standard,Enumeration type.
Value 1 indicates single phase.
Value 2 indicates three phase."
::= { hwUpsControlEntry 9 }
hwUpsCtrlPowerOnState OBJECT-TYPE
SYNTAX INTEGER
{
powerOff(1),
powerOn(2),
powerOnFail(3),
powerOnComplete(4)
}
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Power On State,Enumeration type.
Value 1 indicates power off.
Value 2 indicates booting.
Value 3 indicates failed to power on.
Value 4 indicates succeed tp power on."
::= { hwUpsControlEntry 10 }
hwUpsCtrlBatteryToBoostState OBJECT-TYPE
SYNTAX INTEGER
{
enable(1),
disable(2)
}
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Battery Change to Boost Charge State,Enumeration type.
Value 1 indicates enabled.
Value 2 indicates disabled."
::= { hwUpsControlEntry 11 }
hwUpsCtrlBatteryToFloatState OBJECT-TYPE
SYNTAX INTEGER
{
enable(1),
disable(2)
}
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Battery Change to Float Charge State,Enumeration type.
Value 1 indicates enabled.
Value 2 indicates disabled."
::= { hwUpsControlEntry 12 }
hwUpsCtrlBatteryToTestState OBJECT-TYPE
SYNTAX INTEGER
{
enable(1),
disable(2),
shallow(3)
}
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Battery Change to Test State,Enumeration type.
Value 1 indicates enabled.
Value 2 indicates disabled."
::= { hwUpsControlEntry 13 }
hwUpsCtrlBatteryStopTestState OBJECT-TYPE
SYNTAX INTEGER
{
enable(1),
disable(2)
}
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Battery Stop Test State,Enumeration type.
Value 1 indicates enabled.
Value 2 indicates disabled."
::= { hwUpsControlEntry 14 }
hwUpsCtrlBatteryManualBoostCharge OBJECT-TYPE
SYNTAX INTEGER
{
toBoostCharge(1),
unknown(255)
}
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Battery Manual to Boost Charge,Enumeration type.
Value 1 indicates enabled.
Value 2 indicates disabled."
::= { hwUpsControlEntry 15 }
hwUpsCtrlBatteryManualFloatCharge OBJECT-TYPE
SYNTAX INTEGER
{
toFloatCharge(1),
unknown(255)
}
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Battery Manual to Float Charge,Enumeration type.
Value 1 indicates enabled.
Value 2 indicates unknown"
::= { hwUpsControlEntry 16 }
hwUpsCtrlBatteryShallowTest OBJECT-TYPE
SYNTAX INTEGER
{
toShallowTest(1),
unknown(255)
}
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Battery Shallow Test,Enumeration type.
Value 1 indicates enabled.
Value 2 indicates unknown"
::= { hwUpsControlEntry 17 }
hwUpsCtrlBatteryVerifyCapTest OBJECT-TYPE
SYNTAX INTEGER
{
toVerifyCapTest(1),
unknown(255)
}
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Battery Verify Cap Test,Enumeration type.
Value 1 indicates enabled.
Value 2 indicates unknown"
::= { hwUpsControlEntry 18 }
hwUpsCtrlBatteryEndTest OBJECT-TYPE
SYNTAX INTEGER
{
toEndTest(1),
unknown(255)
}
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Battery End Test,Enumeration type.
Value 1 indicates enabled.
Value 2 indicates unknown"
::= { hwUpsControlEntry 19 }
hwUpsCtrlModelCapacity OBJECT-TYPE
SYNTAX Unsigned32 (0..200)
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Model Capacity.The value ranges from 0 to 200, The value is accurate to one decimal place on the NetEco. The unit is kVA."
::= { hwUpsControlEntry 20 }
hwUpsCtrlEPO OBJECT-TYPE
SYNTAX INTEGER
{
epo(1),
unknown(2)
}
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"EPO. Enumeration type.
Value 1 indicates EPO .
Value 255 indicates unknown."
::= { hwUpsControlEntry 21 }
hwUpsSmartParallelSleepMode OBJECT-TYPE
SYNTAX INTEGER
{
disable(1),
enable(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Smart Parallel Sleep Mode.Enumeration type.The default value is 0.
Value 0 indicates disable.
Value 1 indicates enable."
::= { hwUpsControlEntry 22 }
hwUpsCtrlRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RowStatus of UPS rack control table."
::= { hwUpsControlEntry 100 }
hwUpsTest OBJECT IDENTIFIER ::= { hwUpsMIBObjects 103 }
hwUpsBattScheduleTestTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwUpsBattScheduleTestEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Battery schedule test table. It's index is hwUpsDeviceId."
::= { hwUpsTest 101 }
hwUpsBattScheduleTestEntry OBJECT-TYPE
SYNTAX HwUpsBattScheduleTestEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Battery schedule test table. It's index is hwUpsDeviceId."
INDEX { hwUpsDeviceId }
::= { hwUpsBattScheduleTestTable 1 }
HwUpsBattScheduleTestEntry ::= SEQUENCE {
hwUpsBattAutoTest
INTEGER,
hwUpsBattAutoTestTimeLimit
INTEGER,
hwUpsBattAutoTestTimeInterval
Unsigned32,
hwUpsBattAutoTestDischargeRate
Unsigned32,
hwUpsBattAutoTestEndVol
Unsigned32,
hwUpsBattTest
INTEGER,
hwUpsBattScheduleTestRowStatus
RowStatus
}
hwUpsBattAutoTest OBJECT-TYPE
SYNTAX INTEGER
{
disable(1),
enalbe(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Scheduled shallow discharge test enabled or disabled. Enumeration value.
The value 1 indicates that the test is disabled.
The value 2 indicates that the test is enabled."
::= { hwUpsBattScheduleTestEntry 1 }
hwUpsBattAutoTestTimeLimit OBJECT-TYPE
SYNTAX INTEGER
{
from0to6(1),
from6to12(2),
from12to18(3),
from18to24(4)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Scheduled shallow discharge test time. Enumeration value.
Value 1 indicates 00:00 to 06:00.
Value 2 indicates 06:00 to 12:00.
Value 3 indicates 12:00 to 18:00.
Value 4 indicates 18:00 to 00:00."
::= { hwUpsBattScheduleTestEntry 2 }
hwUpsBattAutoTestTimeInterval OBJECT-TYPE
SYNTAX Unsigned32 (30..90)
UNITS "Day"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Scheduled shallow discharge test interval. An integer ranging from 30 to 90. The unit is days."
::= { hwUpsBattScheduleTestEntry 3 }
hwUpsBattAutoTestDischargeRate OBJECT-TYPE
SYNTAX Unsigned32 (10..50)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Shallow discharge test discharge ratio. An integer ranging from 10 to 50. .
"
::= { hwUpsBattScheduleTestEntry 4 }
hwUpsBattAutoTestEndVol OBJECT-TYPE
SYNTAX Unsigned32 (160..195)
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum battery discharge time. An integer ranging from 160 to 195. The value is accurate to one decimal place on the NetEco. The unit is V/Cell.
"
::= { hwUpsBattScheduleTestEntry 5 }
hwUpsBattTest OBJECT-TYPE
SYNTAX INTEGER
{
noTestInit(1),
stopTest(2),
scheduleTest(3),
shallowDsgTest(4),
verufyDsgTest(5)
}
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"If you set the value to shallowDsgTest(4), you can perform a shallow discharge test; if you set the value to verifyDsgTest(5), you can perform a capacity test; if you set the value to stopTest(2), you can stop the test. Other settings are invalid. If you start a test when other tests are in progress, error code 4 is returned.
During test, you can use this node to obtain the current or previous test type.
If you have never started the battery test sheduleTest(3), shallowDsgTest(4), or verifyDsgTest(5), this node returns noTestInit(1)."
::= { hwUpsBattScheduleTestEntry 6 }
hwUpsBattScheduleTestRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RowStatus of UPS Battery control table. "
::= { hwUpsBattScheduleTestEntry 100 }
hwUpsiBOX OBJECT IDENTIFIER ::= { hwUpsMIBObjects 110 }
hwUpsBatteryGroupNum OBJECT-TYPE
SYNTAX Unsigned32 (0..4)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of battery group in UPS,ranging from 0 to 4.
"
::= { hwUpsiBOX 1 }
hwUpsBatteryNumInBatteryGroup OBJECT-TYPE
SYNTAX Unsigned32 (0..300)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of battery in one battery group,ranging from 0 to 300.
"
::= { hwUpsiBOX 2 }
hwUpsiBOXNum OBJECT-TYPE
SYNTAX Unsigned32 (0..4)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of iBOX in UPS,ranging from 0 to 4."
::= { hwUpsiBOX 3 }
hwUpsBatteryGroupTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwUpsBatteryGroupEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"UPS battery group table. It's index is hwUpsBatteryGroupNo.
"
::= { hwUpsiBOX 4 }
hwUpsBatteryGroupEntry OBJECT-TYPE
SYNTAX HwUpsBatteryGroupEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"UPS battery group table. It's index is hwUpsBatteryGroupNo.
"
INDEX { hwUpsBatteryGroupNo }
::= { hwUpsBatteryGroupTable 1 }
HwUpsBatteryGroupEntry ::= SEQUENCE {
hwUpsBatteryGroupNo
Unsigned32,
hwUpsBatteryGroupVolt
Unsigned32,
hwUpsBatteryGroupCur
Integer32,
hwUpsBatteryGroupSOC
Unsigned32,
hwUpsBatteryGroupBackupTime
Unsigned32,
hwUpsBatteryGroupSOH
INTEGER,
hwUpsBatteryGroupRowStatus
RowStatus
}
hwUpsBatteryGroupNo OBJECT-TYPE
SYNTAX Unsigned32 (1..4)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"No of battery group,ranging from 1 to 4.This node is referenced as an index node
by hwUpsBatteryGroupTable.
"
::= { hwUpsBatteryGroupEntry 1 }
hwUpsBatteryGroupVolt OBJECT-TYPE
SYNTAX Unsigned32 (0..10000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The Voltage of battery group,ranging from 0 to 10000.
The value is accurate to one decimal place on the NetEco. The unit is V."
::= { hwUpsBatteryGroupEntry 2 }
hwUpsBatteryGroupCur OBJECT-TYPE
SYNTAX Integer32 (-30000..30000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The Current of battery group,ranging from -30000 to 30000.
The value is accurate to one decimal place on the NetEco. The unit is A."
::= { hwUpsBatteryGroupEntry 3 }
hwUpsBatteryGroupSOC OBJECT-TYPE
SYNTAX Unsigned32 (0..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The SOC of battery group,ranging from 0 to 100.The unit is %."
::= { hwUpsBatteryGroupEntry 4 }
hwUpsBatteryGroupBackupTime OBJECT-TYPE
SYNTAX Unsigned32 ( 0..999)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The Backup Time of battery group,ranging from 0 to 999.The unit is min.
"
::= { hwUpsBatteryGroupEntry 5 }
hwUpsBatteryGroupSOH OBJECT-TYPE
SYNTAX INTEGER
{
good(1),
requiringMaintenance(2),
needReplaceBatt(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The SOH of battery group. Enumeration type.
Value 0 indicates good.
Value 1 indicates requiring maintenance.
Value 2 indicates need replace batt.
"
::= { hwUpsBatteryGroupEntry 6 }
hwUpsBatteryGroupRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Row status of hwUpsBatteryGroupTable."
::= { hwUpsBatteryGroupEntry 100 }
hwUpsiBOXTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwUpsiBOXEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"CIM table. It's index is hwUpsCIMNo."
::= { hwUpsiBOX 5 }
hwUpsiBOXEntry OBJECT-TYPE
SYNTAX HwUpsiBOXEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"CIM table. It's index is hwUpsCIMNo."
INDEX { hwUpsiBOXNo }
::= { hwUpsiBOXTable 1 }
HwUpsiBOXEntry ::= SEQUENCE {
hwUpsiBOXNo
Unsigned32,
hwUpsiBOXSoftVersion
Unsigned32,
hwUpsiBOXiBATNum
Unsigned32,
hwUpsiBOXRowStatus
RowStatus
}
hwUpsiBOXNo OBJECT-TYPE
SYNTAX Unsigned32 (1..4)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"No of iBOX,ranging from 1 to 4.This node is referenced as an index node by hwUpsiBOXTable."
::= { hwUpsiBOXEntry 1 }
hwUpsiBOXSoftVersion OBJECT-TYPE
SYNTAX Unsigned32 (0..4294967295)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The software version of iBOX,ranging from 0 to 4294967295."
::= { hwUpsiBOXEntry 2 }
hwUpsiBOXiBATNum OBJECT-TYPE
SYNTAX Unsigned32 (0..300)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"iBAT number of one iBOX,ranging from 0 to 300."
::= { hwUpsiBOXEntry 3 }
hwUpsiBOXRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Row status of hwUpsiBOXTable."
::= { hwUpsiBOXEntry 100 }
hwUpsBattGroupRelaiBOXTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwUpsBattGroupRelaiBOXEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"UPS battery group related CIM Table. It's index is hwUpsBattGrpNo and hwUpsBattGroupRelaCIMNo.
"
::= { hwUpsiBOX 6 }
hwUpsBattGroupRelaiBOXEntry OBJECT-TYPE
SYNTAX HwUpsBattGroupRelaiBOXEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"UPS battery group related CIM Table. It's index is hwUpsBattGrpNo and hwUpsBattGroupRelaCIMNo.
"
INDEX { hwUpsBattGrpNo }
::= { hwUpsBattGroupRelaiBOXTable 1 }
HwUpsBattGroupRelaiBOXEntry ::= SEQUENCE {
hwUpsBattGrpNo
Unsigned32,
hwUpsBattGroupRelaiBOXNo
Unsigned32,
hwUpsBattGroupRelaiBATStartNo
Unsigned32,
hwUpsBattGroupRelaiBATEndNo
Unsigned32,
hwUpsBattGroupRelaiBOXRowStatus
RowStatus
}
hwUpsBattGrpNo OBJECT-TYPE
SYNTAX Unsigned32 (1..4)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"No of battery group,ranging from 1 to 4.This node is referenced as an index node
by hwUpsBattGrpRelaiBOXTable."
::= { hwUpsBattGroupRelaiBOXEntry 1 }
hwUpsBattGroupRelaiBOXNo OBJECT-TYPE
SYNTAX Unsigned32 (1..4)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"No of iBOX,ranging from 1 to 4.This node is referenced as an index node
by hwUpsBattGrpRelaiBOXTable."
::= { hwUpsBattGroupRelaiBOXEntry 2 }
hwUpsBattGroupRelaiBATStartNo OBJECT-TYPE
SYNTAX Unsigned32 (1..300)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Ups Battery Group related iBAT start no,ranging from 1 to 300."
::= { hwUpsBattGroupRelaiBOXEntry 3 }
hwUpsBattGroupRelaiBATEndNo OBJECT-TYPE
SYNTAX Unsigned32 (1..300)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Ups Battery Group related iBAT end no,ranging from 1 to 300.
"
::= { hwUpsBattGroupRelaiBOXEntry 4 }
hwUpsBattGroupRelaiBOXRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Row status of hwUpsBattGroupRelaiBOXTable."
::= { hwUpsBattGroupRelaiBOXEntry 100 }
hwUpsiBATTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwUpsiBATEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"BIM table. It's index is hwUpsBIMCIMNo and hwUpsBIMNo."
::= { hwUpsiBOX 7 }
hwUpsiBATEntry OBJECT-TYPE
SYNTAX HwUpsiBATEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"BIM table. It's index is hwUpsBIMCIMNo and hwUpsBIMNo."
INDEX { hwUpsiBATiBOXNo }
::= { hwUpsiBATTable 1 }
HwUpsiBATEntry ::= SEQUENCE {
hwUpsiBATiBOXNo
Unsigned32,
hwUpsiBATNo
Unsigned32,
hwUpsiBATTemp
Integer32,
hwUpsiBATVoltMulThousand
Unsigned32,
hwUpsiBATResMulHundred
Unsigned32,
hwUpsiBATCur
Integer32,
hwUpsiBATSOC
Unsigned32,
hwUpsiBATSOH
INTEGER,
hwUpsiBATVolt
Unsigned32,
hwUpsiBATRes
Unsigned32,
hwUpsiBATRowStatus
RowStatus
}
hwUpsiBATiBOXNo OBJECT-TYPE
SYNTAX Unsigned32 (1..4)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"No of iBOX,ranging from 1 to 4.This node is referenced as an index node
by hwUpsBIMTable."
::= { hwUpsiBATEntry 1 }
hwUpsiBATNo OBJECT-TYPE
SYNTAX Unsigned32 (1..300)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"No of iBAT,ranging from 1 to 300.
This node is referenced as an index node by hwUpsBIMTable."
::= { hwUpsiBATEntry 2 }
hwUpsiBATTemp OBJECT-TYPE
SYNTAX Integer32 (-200..800)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Ups iBAT Temperature.The value ranges from -200 to 800.
The value is accurate to one decimal place on the NetEco. The unit is <20><>."
::= { hwUpsiBATEntry 3 }
hwUpsiBATVoltMulThousand OBJECT-TYPE
SYNTAX Unsigned32 (0..300)
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Ups iBAT Volt.The value ranges from 0 to 300.
The value is accurate to one decimal place on the NetEco. The unit is V."
::= { hwUpsiBATEntry 4 }
hwUpsiBATResMulHundred OBJECT-TYPE
SYNTAX Unsigned32 (0..3000)
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Ups iBAT Resistance.The value ranges from 0 to 3000.
The value is accurate to one decimal place on the NetEco. The unit is m<><6D>."
::= { hwUpsiBATEntry 5 }
hwUpsiBATCur OBJECT-TYPE
SYNTAX Integer32 (-30000..30000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Ups iBAT Current.The value ranges from -30000 to 30000.
The value is accurate to one decimal place on the NetEco. The unit is A.
"
::= { hwUpsiBATEntry 6 }
hwUpsiBATSOC OBJECT-TYPE
SYNTAX Unsigned32 (0..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The SOC of iBAT,ranging from 0 to 100.The unit is %.
"
::= { hwUpsiBATEntry 7 }
hwUpsiBATSOH OBJECT-TYPE
SYNTAX INTEGER
{
good(1),
requiringMaintenance(2),
needReplaceBatt(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The SOH of iBAT. Enumeration type.
Value 0 indicates good.
Value 1 indicates requiring maintenance.
Value 2 indicates need replace batt.
"
::= { hwUpsiBATEntry 8 }
hwUpsiBATVolt OBJECT-TYPE
SYNTAX Unsigned32 (0..30000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Ups iBAT Volt.The value ranges from 0 to 30000.
The value is accurate to two decimal place on the NetEco. The unit is V."
::= { hwUpsiBATEntry 9 }
hwUpsiBATRes OBJECT-TYPE
SYNTAX Unsigned32 (0..30000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Ups iBAT Resistance.The value ranges from 0 to 30000.
The value is accurate to two decimal place on the NetEco. The unit is m<><6D>."
::= { hwUpsiBATEntry 10 }
hwUpsiBATRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Row status of hwUpsiBATTable."
::= { hwUpsiBATEntry 100 }
hwUpsParallelSystem OBJECT IDENTIFIER ::= { hwUpsMIBObjects 10 }
hwUpsParaSysTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwUpsParaSysEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"/"
::= { hwUpsParallelSystem 1 }
hwUpsParaSysEntry OBJECT-TYPE
SYNTAX HwUpsParaSysEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"/"
INDEX { hwUpsParaSysId }
::= { hwUpsParaSysTable 1 }
HwUpsParaSysEntry ::= SEQUENCE {
hwUpsParaSysId
Unsigned32,
hwUpsParaSysOutActivePowA
Integer32,
hwUpsParaSysOutActivePowB
Integer32,
hwUpsParaSysOutActivePowC
Integer32,
hwUpsParaSysOutAppearPowA
Integer32,
hwUpsParaSysOutAppearPowB
Integer32,
hwUpsParaSysOutAppearPowC
Integer32,
hwUpsParaSysOutLoadFactorA
Unsigned32,
hwUpsParaSysOutLoadFactorB
Unsigned32,
hwUpsParaSysOutLoadFactorC
Unsigned32,
hwUpsParallelSystemRowStatus
RowStatus
}
hwUpsParaSysId OBJECT-TYPE
SYNTAX Unsigned32 (0..127)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"ID of the parallel system that the current rack belongs to."
::= { hwUpsParaSysEntry 1 }
hwUpsParaSysOutActivePowA OBJECT-TYPE
SYNTAX Integer32 (-120000..120000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System phase A output active power.The value ranges from -12000 to 12000,
The value is accurate to one decimal place on the NetEco. The unit is kW.
"
::= { hwUpsParaSysEntry 2 }
hwUpsParaSysOutActivePowB OBJECT-TYPE
SYNTAX Integer32 (-120000..120000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System phase B output active power.The value ranges from -12000 to 12000,
The value is accurate to one decimal place on the NetEco. The unit is kW.
"
::= { hwUpsParaSysEntry 3 }
hwUpsParaSysOutActivePowC OBJECT-TYPE
SYNTAX Integer32 (-120000..120000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System phase C output active power.The value ranges from -12000 to 12000,
The value is accurate to one decimal place on the NetEco. The unit is kW.
"
::= { hwUpsParaSysEntry 4 }
hwUpsParaSysOutAppearPowA OBJECT-TYPE
SYNTAX Integer32 (-120000..120000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System phase A output apparent power.The value ranges from -12000 to 12000,
The value is accurate to one decimal place on the NetEco. The unit is kVA.
"
::= { hwUpsParaSysEntry 5 }
hwUpsParaSysOutAppearPowB OBJECT-TYPE
SYNTAX Integer32 (-120000..120000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System phase B output apparent power.The value ranges from -12000 to 12000,
The value is accurate to one decimal place on the NetEco. The unit is kVA.
"
::= { hwUpsParaSysEntry 6 }
hwUpsParaSysOutAppearPowC OBJECT-TYPE
SYNTAX Integer32 (-120000..120000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System phase C output apparent power.The value ranges from -12000 to 12000,
The value is accurate to one decimal place on the NetEco. The unit is kVA.
"
::= { hwUpsParaSysEntry 7 }
hwUpsParaSysOutLoadFactorA OBJECT-TYPE
SYNTAX Unsigned32 (0..5000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System A output load factor.The value ranges from 0 to 500,
The value is accurate to one decimal place on the NetEco. The unit is %"
::= { hwUpsParaSysEntry 8 }
hwUpsParaSysOutLoadFactorB OBJECT-TYPE
SYNTAX Unsigned32 (0..5000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System B output load factor.The value ranges from 0 to 500,
The value is accurate to one decimal place on the NetEco. The unit is %."
::= { hwUpsParaSysEntry 9 }
hwUpsParaSysOutLoadFactorC OBJECT-TYPE
SYNTAX Unsigned32 (0..5000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System C output load factor.The value ranges from 0 to 500,
The value is accurate to one decimal place on the NetEco. The unit is %."
::= { hwUpsParaSysEntry 10 }
hwUpsParallelSystemRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RowStatus of ups parallel System Identification table."
::= { hwUpsParaSysEntry 100 }
hwUpsRackUnevenCur OBJECT IDENTIFIER ::= { hwUpsMIBObjects 108 }
hwUpsRackUnevenCurTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwUpsRackUnevenCurEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
""
::= { hwUpsRackUnevenCur 1 }
hwUpsRackUnevenCurEntry OBJECT-TYPE
SYNTAX HwUpsRackUnevenCurEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
""
INDEX { hwUpsRackUnevenCurRackId }
::= { hwUpsRackUnevenCurTable 1 }
HwUpsRackUnevenCurEntry ::= SEQUENCE {
hwUpsRackUnevenCurRackId
Unsigned32,
hwUpsRackUnevenCurSysGrant
Unsigned32,
hwUpsRackUnevenCurPowerSupplyMode
INTEGER,
hwUpsRackUnevenCurPowerOnModNum
Unsigned32,
hwUpsRackUnevenCurSleepModNum
Unsigned32,
hwUpsRackOutputCurrentA
Unsigned32,
hwUpsRackOutputCurrentB
Unsigned32,
hwUpsRackOutputCurrentC
Unsigned32,
hwUpsRackUnevenCurA
Unsigned32,
hwUpsRackUnevenCurB
Unsigned32,
hwUpsRackUnevenCurC
Unsigned32,
hwUpsRackUnevenCurValueTag
Unsigned32,
hwUpsRackUnevenCurRowStatus
RowStatus
}
hwUpsRackUnevenCurRackId OBJECT-TYPE
SYNTAX Unsigned32 (1..6)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Ups Rack Id.Range from 1 to 6.This node is referenced as an index node
by hwUpsRackUnevenCurTable"
::= { hwUpsRackUnevenCurEntry 1 }
hwUpsRackUnevenCurSysGrant OBJECT-TYPE
SYNTAX Unsigned32 (0..10000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System grant.An integer ranging from 0 to 10000."
::= { hwUpsRackUnevenCurEntry 2 }
hwUpsRackUnevenCurPowerSupplyMode OBJECT-TYPE
SYNTAX INTEGER
{
noOutput(1),
bypass(2),
normal(3),
battery(4),
sourceShare(5),
normalECO(6),
batteryECO(7)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Device power supply mode. Enumeration type.
Value 1 indicates no power supply.
Value 2 indicates bypass mode.
Value 3 indicates normal mode.
Value 4 indicates battery mode.
Value 5 indicates combined mode.
Value 6 indicates mains ECO mode.
Value 7 indicates battery ECO mode."
::= { hwUpsRackUnevenCurEntry 3 }
hwUpsRackUnevenCurPowerOnModNum OBJECT-TYPE
SYNTAX Unsigned32 (0..20)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack PowerOn Module Num.Range from 0 to 20."
::= { hwUpsRackUnevenCurEntry 4 }
hwUpsRackUnevenCurSleepModNum OBJECT-TYPE
SYNTAX Unsigned32 (0..20)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack Sleep Module Num.Range from 0 to 20."
::= { hwUpsRackUnevenCurEntry 5 }
hwUpsRackOutputCurrentA OBJECT-TYPE
SYNTAX Unsigned32 (0..10000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack phase A output current. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. The unit is A."
::= { hwUpsRackUnevenCurEntry 6 }
hwUpsRackOutputCurrentB OBJECT-TYPE
SYNTAX Unsigned32 (0..10000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack phase B output current. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. The unit is A."
::= { hwUpsRackUnevenCurEntry 7 }
hwUpsRackOutputCurrentC OBJECT-TYPE
SYNTAX Unsigned32 (0..10000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack phase C output current. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. The unit is A."
::= { hwUpsRackUnevenCurEntry 8 }
hwUpsRackUnevenCurA OBJECT-TYPE
SYNTAX Unsigned32 (0..10000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack phase A uneven current. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. "
::= { hwUpsRackUnevenCurEntry 9 }
hwUpsRackUnevenCurB OBJECT-TYPE
SYNTAX Unsigned32 (0..10000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack phase B uneven current. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. "
::= { hwUpsRackUnevenCurEntry 10 }
hwUpsRackUnevenCurC OBJECT-TYPE
SYNTAX Unsigned32 (0..10000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack phase C uneven current. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. "
::= { hwUpsRackUnevenCurEntry 11 }
hwUpsRackUnevenCurValueTag OBJECT-TYPE
SYNTAX Unsigned32 (0..1)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rack uneven current value tag.range 0 to 1,0 indicates invalid,1 indicates valid."
::= { hwUpsRackUnevenCurEntry 12 }
hwUpsRackUnevenCurRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RowStatus of UPS Rack Uneven Current table."
::= { hwUpsRackUnevenCurEntry 100 }
hwUpsMIBTraps OBJECT IDENTIFIER ::= { hwUpsMIB 2 }
hwUpsTrapsVbOids OBJECT IDENTIFIER ::= { hwUpsMIBTraps 1 }
hwUpsTrapsDeviceId OBJECT-TYPE
SYNTAX Unsigned32 (1..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"ID of the device on which the active alarm is generated. An integer ranging from 1 to 100."
::= { hwUpsTrapsVbOids 1 }
hwUpsTrapsModuleSeqId OBJECT-TYPE
SYNTAX Unsigned32 (1..4294967295)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The alarm module name, which produces alarm.
This name may be one of Monitor module name,Bypass module name,ECU module name and Power module name.
If it's value is empty, it indicates the alarm is a synthetical alarm and not belong to any module device."
::= { hwUpsTrapsVbOids 2 }
hwUpsTrapsEquipID OBJECT-TYPE
SYNTAX Unsigned32 (0..154)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Active alarm module ID, ranging from 1 to 154."
::= { hwUpsTrapsVbOids 3 }
hwUpsTrapsID OBJECT-TYPE
SYNTAX Unsigned32 (0..4294967295)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"ID of an active alarm, ranging from 0 to 4294967295."
::= { hwUpsTrapsVbOids 4 }
hwUpsTrapsReasonId OBJECT-TYPE
SYNTAX Unsigned32 (0..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Alarm reason ID. Value range: 0 to 100, and the value is an integer (.0)."
::= { hwUpsTrapsVbOids 5 }
hwUpsTrapsText OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..127))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Alarm name. It is of the character string type, and used to specify the content of a specific alarm."
::= { hwUpsTrapsVbOids 6 }
hwUpsTrapsLevel OBJECT-TYPE
SYNTAX INTEGER
{
critical(1),
major(2),
minor(3),
warning(4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Alarm level, which users can configure the alarm severity, is an enumeration type:
If the enumeration value is 1, it indicates a critical alarm;
If the enumeration value is 2, it indicates a major alarm;
If the enumeration value is 3, it indicates a minor alarm;
If the enumeration value is 4, it indicates a warning."
::= { hwUpsTrapsVbOids 7 }
hwUpsTrapsFlag OBJECT-TYPE
SYNTAX INTEGER
{
occur(1),
resume(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Flag bit of an active alarm. Enumeration type.
Value 1 indicates that an active alarm is generated.
Value 2 indicates that an active alarm is cleared."
::= { hwUpsTrapsVbOids 8 }
hwUpsTrapsSynchronNum OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Active alarm synchronization ID, ranging from 0 to 4294967295"
::= { hwUpsTrapsVbOids 9 }
hwUpsTrapsTime OBJECT-TYPE
SYNTAX Unsigned32 (0..4294967295)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Time when an active alarm is generated, ranging from 0 to 4294967295. The unit is seconds."
::= { hwUpsTrapsVbOids 10 }
hwUpsCommonTraps OBJECT IDENTIFIER ::= { hwUpsMIBTraps 2 }
hwUpsCommonTrapsPrefix OBJECT IDENTIFIER ::= { hwUpsCommonTraps 0 }
-- 1.3.6.1.4.1.2011.6.174.2.2.0.1
-- 1.3.6.1.4.1.2011.6.174.2.2.0.1
-- 1.3.6.1.4.1.2011.6.174.2.2.0.1
hwUpsSummaryAlarmTrap NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"UPS Summary Alarm status changed. Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time.
Additionally, in order to identify the status, UPS system operate status are also include in VB(variable bondings):
If the enumeration value is Normal(2), it indicates that UPS system resumes form alarm.
If the enumeration value is Alarm(3), it indicates that a new alarm occurs on the UPS sytem."
::= { hwUpsCommonTrapsPrefix 1 }
-- 1.3.6.1.4.1.2011.6.174.2.2.0.2
-- 1.3.6.1.4.1.2011.6.174.2.2.0.2
-- 1.3.6.1.4.1.2011.6.174.2.2.0.2
hwUpsPowerModInslotChangeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
}
STATUS current
DESCRIPTION
"Power module inslot status changed.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time.
Additionally, in order to identify the operation, power module operate status are also include in VB(variable bondings):
If the enumeration value is Normal(2), it indicates that a new power module is inserted in slot;
If the enumeration value is Alarm(3), it indicates that communication of the power module module fails or module is not in slot. "
::= { hwUpsCommonTrapsPrefix 2 }
hwUpsPowerStatusWarnTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"When UPS Power Status changed, a warn trap will be send.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsCommonTrapsPrefix 3 }
hwUpsPowerStatusWarnResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"UPS Power Status warn resume trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsCommonTrapsPrefix 4 }
hwUpsSwitchStatusWarnTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"When contactor or switch status changed, a warn trap will be send.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsCommonTrapsPrefix 5 }
hwUpsSwitchStatusWarnResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Contactor or switch warn resume trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsCommonTrapsPrefix 6 }
hwUpsModCommFailedTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"When module communicates failed, a trap will be send.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsCommonTrapsPrefix 7 }
hwUpsModCommFailedResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Module communication failed Resume.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsCommonTrapsPrefix 8 }
hwUpsModConfigWarnTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"When module config status changed, a warn trap will be send.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsCommonTrapsPrefix 9 }
hwUpsModConfigWarnResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Module config warn resume trap.
Its correlation binding parameters:Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsCommonTrapsPrefix 10 }
hwUpsRecWarnTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"When rectifier status changed, a warn trap will be send.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsCommonTrapsPrefix 11 }
hwUpsRecWarnResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Rectifier warn resume trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsCommonTrapsPrefix 12 }
hwUpsChargerPowerWarnTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"When charger power status changed, a warn trap will be send.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsCommonTrapsPrefix 13 }
hwUpsChargerPowerWarnResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Charger power warn resume trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
::= { hwUpsCommonTrapsPrefix 14 }
hwUpsGeneratorWarnTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"When generator status changed, a warn trap will be send.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsCommonTrapsPrefix 15 }
hwUpsGeneratorWarnResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Generator warn resume trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsCommonTrapsPrefix 16 }
hwUpsInvWarnTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"When inverter status changed, a warn trap will be send.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsCommonTrapsPrefix 17 }
hwUpsInvWarnResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Inverter warn resume trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsCommonTrapsPrefix 18 }
hwUpsLBSWarnTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"When LBS status changed, a warn trap will be send.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsCommonTrapsPrefix 19 }
hwUpsLBSWarnResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"LBS warn resume trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsCommonTrapsPrefix 20 }
hwUpsSwitchTipWarnTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"When switch method changed or there is a switch tip, a warn trap will be send.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsCommonTrapsPrefix 21 }
hwUpsSwitchTipWarnResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Switch method or switch tip warn resume trap.
Its correlation binding parameters:Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsCommonTrapsPrefix 22 }
-- 1.3.6.1.4.1.2011.6.174.2.2.0.23
-- 1.3.6.1.4.1.2011.6.174.2.2.0.23
-- 1.3.6.1.4.1.2011.6.174.2.2.0.23
hwUpsBattDetachWarnTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
}
STATUS current
DESCRIPTION
"When battery detach, a warn trap will be send.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsCommonTrapsPrefix 23 }
-- 1.3.6.1.4.1.2011.6.174.2.2.0.24
-- 1.3.6.1.4.1.2011.6.174.2.2.0.24
-- 1.3.6.1.4.1.2011.6.174.2.2.0.24
hwUpsBattDetachWarnResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
}
STATUS current
DESCRIPTION
"Battery detach warn resume trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsCommonTrapsPrefix 24 }
hwUpsBattStatusWarnTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"When battery status abnormal, a warn trap will be send through this OID.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsCommonTrapsPrefix 25 }
hwUpsBattStatusWarnResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"When battery status abnormal resume, a trap will be send through this OID.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsCommonTrapsPrefix 26 }
hwUpsBatteryTestWarnTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"When battery test start, a warn trap will be send through this OID.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time.
"
::= { hwUpsCommonTrapsPrefix 27 }
hwUpsBatteryTestWarnResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"When battery test end, a trap will be send through this OID.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsCommonTrapsPrefix 28 }
hwUpsRackComFailedTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"When Rack communication fail happen, a alarm trap will be send.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time.
"
::= { hwUpsCommonTrapsPrefix 29 }
hwUpsRackComFaiedResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Rack communication fail alarm resume.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsCommonTrapsPrefix 30 }
hwUpsRackMasterConflictTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"When Rack Master Conflict alarm happen, a alarm trap will be send.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsCommonTrapsPrefix 31 }
hwUpsRackMasterConflictResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Rack Master Conflict alarm resume.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsCommonTrapsPrefix 32 }
hwUpsRackNumNoMatchTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"UPS Rack num dismatch warn. Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time.
Additionally, in order to identify the status, UPS system operate status are also include in VB(variable bondings):
If the enumeration value is Normal(2), it indicates that UPS system resumes form alarm.
If the enumeration value is Alarm(3), it indicates that a new alarm occurs on the UPS sytem."
::= { hwUpsCommonTrapsPrefix 33 }
hwUpsRackNumNoMatchResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"UPS Rack num dismatch warn resume. Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time.
Additionally, in order to identify the status, UPS system operate status are also include in VB(variable bondings):
If the enumeration value is Normal(2), it indicates that UPS system resumes form alarm.
If the enumeration value is Alarm(3), it indicates that a new alarm occurs on the UPS sytem.
"
::= { hwUpsCommonTrapsPrefix 34 }
-- 1.3.6.1.4.1.2011.6.174.2.2.1
hwUpsCommonStateTrapsPrefix OBJECT IDENTIFIER ::= { hwUpsCommonTraps 1 }
-- 1.3.6.1.4.1.2011.6.174.2.2.0.35
-- 1.3.6.1.4.1.2011.6.174.2.2.0.35
-- 1.3.6.1.4.1.2011.6.174.2.2.1.1
hwUpsRackOnlineStateChangeTrap NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"Ups Rack Online State Change Trap. Its correlation binding parameters: NULL"
::= { hwUpsCommonStateTrapsPrefix 1 }
-- 1.3.6.1.4.1.2011.6.174.2.2.0.36
-- 1.3.6.1.4.1.2011.6.174.2.2.0.36
-- 1.3.6.1.4.1.2011.6.174.2.2.1.2
hwUpsRackConfigChangeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId }
STATUS current
DESCRIPTION
"Ups Rack Config Change.Its correlation binding parameters: Device ID"
::= { hwUpsCommonStateTrapsPrefix 2 }
-- 1.3.6.1.4.1.2011.6.174.2.2.0.37
-- 1.3.6.1.4.1.2011.6.174.2.2.0.37
-- 1.3.6.1.4.1.2011.6.174.2.2.1.3
hwUpsRackRunningStateChangeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsDeviceRunningStatus, hwUpsTrapsDeviceId }
STATUS current
DESCRIPTION
"Ups Rack Running State Change.Its correlation binding parameters: Device ID and Device running state."
::= { hwUpsCommonStateTrapsPrefix 3 }
-- 1.3.6.1.4.1.2011.6.174.2.2.0.38
-- 1.3.6.1.4.1.2011.6.174.2.2.0.38
-- 1.3.6.1.4.1.2011.6.174.2.2.1.4
hwUpsBatteryRunningStateChangeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsDeviceBatteryState, hwUpsTrapsDeviceId }
STATUS current
DESCRIPTION
"Ups Battery Running State Change,Its correlation binding parameters: Device ID and Battery Running State"
::= { hwUpsCommonStateTrapsPrefix 4 }
-- 1.3.6.1.4.1.2011.6.174.2.2.1.5
hwUpsEnergyFloatChangeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsDeviceEnergyFloatState, hwUpsTrapsDeviceId }
STATUS current
DESCRIPTION
"Ups Energy Float Change,Its correlation binding parameters: Device ID and The Energy Float State"
::= { hwUpsCommonStateTrapsPrefix 5 }
-- 1.3.6.1.4.1.2011.6.174.2.2.1.6
hwUpsVersionChangeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId }
STATUS current
DESCRIPTION
"Ups Version Change,Its correlation binding parameters: Device ID"
::= { hwUpsCommonStateTrapsPrefix 6 }
hwUpsAlarmTraps OBJECT IDENTIFIER ::= { hwUpsMIBTraps 3 }
hwUpsAlarmTrapsPrefix OBJECT IDENTIFIER ::= { hwUpsAlarmTraps 0 }
hwUpsModNumAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"When power module number dismatch, a alarm trap will be send.
Its correlation binding parameters:Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 1 }
hwUpsModNumAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Power module number dismatch alarm resume trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 2 }
hwUpsBypassUnitAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Bypass Unit Abnormal Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 3 }
hwUpsBypassUnitAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Bypass Unit Abnormal Resume Trap.
Its correlation binding parameters:Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 4 }
hwUpsInRackParallelLineAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"In-Rack Parallel Line Abnormal Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time.
"
::= { hwUpsAlarmTrapsPrefix 5 }
hwUpsInRackParallelLineAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Description: In-Rack Parallel Line Abnormal Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 6 }
hwUpsBetweenRackParallelLineAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Between-Rack Parallel Line Abnormal Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 7 }
hwUpsBetweenRackParallelLineAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Between-Rack Parallel Line Abnormal Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 8 }
hwUpsFanAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Fan Abnormal Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 9 }
hwUpsFanAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Fan Abnormal Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 10 }
hwUpsAuxiliaryPowerAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Auxiliary Power Abnormal Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 11 }
hwUpsAuxiliaryPowerAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Auxiliary Power Abnormal Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 12 }
hwUpsVersionMismatchAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"when version mismatch alarms happen, a alarm trap will be send.
Its correlation binding parameters:Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 13 }
hwUpsVersionMatchAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Version mismatch Abnormal Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 14 }
hwUpsAddrConflictAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Address Conflict Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 15 }
hwUpsAddrConflictAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Address Conflict Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 16 }
hwUpsEmergencyPowerOffAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Emergency Power Off Abnormal Trap.
Its correlation binding parameters:Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 17 }
hwUpsEmergencyPowerOffAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Emergency Power Off Abnormal Resume Trap.
Its correlation binding parameters:Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 18 }
hwUpsBypassInputAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Bypass Input Abnormal Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 19 }
hwUpsBypassInputAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Bypass Input Abnormal Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 20 }
-- 1.3.6.1.4.1.2011.6.174.2.3.0.21
-- 1.3.6.1.4.1.2011.6.174.2.3.0.21
-- 1.3.6.1.4.1.2011.6.174.2.3.0.21
hwUpsInputIsolatingTransAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
}
STATUS current
DESCRIPTION
"Transformer Abnormal Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 21 }
-- 1.3.6.1.4.1.2011.6.174.2.3.0.22
-- 1.3.6.1.4.1.2011.6.174.2.3.0.22
-- 1.3.6.1.4.1.2011.6.174.2.3.0.22
hwUpsInputIsolatingTransAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
}
STATUS current
DESCRIPTION
"Transformer Abnormal Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 22 }
hwUpsInternalAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Supervision Unit Internal Fault Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 23 }
hwUpsInternalAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Supervision Unit Internal Fault Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 24 }
hwUpsRectifierAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Rectifier Abnormal Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 25 }
hwUpsRectifierAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Rectifier Abnormal Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 26 }
hwUpsChargerAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Charger Abnormal Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 27 }
hwUpsChargerAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Charger Abnormal Resume Trap.
Its correlation binding parameters:Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 28 }
hwUpsDischargerAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Discharger Abnormal Trap.
Its correlation binding parameters:Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 29 }
hwUpsDischargerAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Discharger Abnormal Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 30 }
hwUpsACAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"AC Abnormal Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 31 }
hwUpsACAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"AC Abnormal Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 32 }
hwUpsModuleNotReadyAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Module Not Ready Abnormal Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 33 }
hwUpsModuleNotReadyAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Module Not Ready Abnormal Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 34 }
hwUpsInverterAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Inverter Abnormal Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 35 }
hwUpsInverterAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Inverter Abnormal Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 36 }
hwUpsECUAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"ECU Abnormal Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 37 }
hwUpsECUAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"ECU Abnormal Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 38 }
hwUpsSPDAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"SPD Abnormal Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 39 }
hwUpsSPDAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"SPD Abnormal Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 40 }
hwUpsOperationFaultAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Operation Fault Abnormal Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 41 }
hwUpsOperationFaultAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Operation Fault Abnormal Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 42 }
hwUpsOverLoadAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Over Load Abnormal Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 43 }
hwUpsOverLoadAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Over Load Abnormal Resume Trap.
Its correlation binding parameters:Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 44 }
hwUpsOverLoadOverTimeAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Over-Load Overtime Abnormal Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 45 }
hwUpsOverLoadOverTimeAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Over-Load Overtime Abnormal Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 46 }
hwUpsLBSAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"LBS Abnormal Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 47 }
hwUpsLBSAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"LBS Abnormal Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 48 }
hwUpsBypSwitchAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Bypass Switch Abnormal Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 49 }
hwUpsBypSwitchAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Bypass Switch Abnormal Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 50 }
hwUpsBatteryFault1AlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"When battery reversed, no Battery, battery earth fault or battery stop discharge abnormal happen, an alarm trap will be send through this OID.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 51 }
hwUpsBatteryFault1AlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"When battery reversed, no Battery, battery earth fault or battery stop discharge abnormal resume, a trap will be send through this OID.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 52 }
hwUpsBatteryFault2AlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"When battery over temperature, battery need maintenance, or battery voltage low abnormal happen, an alarm trap will be send through this OID.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 53 }
hwUpsBatteryFault2AlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"When battery over temperature, battery need maintenance, or battery voltage low abnormal resume, a trap will be send through this OID.
Its correlation binding parameters:Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 54 }
hwUpsBatteryChangeLimitAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Battery Change Limit Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 55 }
hwUpsBatteryChangeLimitAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Battery Change Limit Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 56 }
-- 1.3.6.1.4.1.2011.6.174.2.3.0.57
hwUpsRectifierStartLimitAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
}
STATUS current
DESCRIPTION
"Rectifier Start Limit Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 57 }
-- 1.3.6.1.4.1.2011.6.174.2.3.0.58
hwUpsRectifierStartLimitAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
}
STATUS current
DESCRIPTION
"Rectifier Start Limit Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 58 }
-- 1.3.6.1.4.1.2011.6.174.2.3.0.59
hwUpsMainLoadCapicityAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
}
STATUS current
DESCRIPTION
"Main Load Capicity Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 59 }
-- 1.3.6.1.4.1.2011.6.174.2.3.0.60
hwUpsMainLoadCapicityAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
}
STATUS current
DESCRIPTION
"Main Load Capicity Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 60 }
-- 1.3.6.1.4.1.2011.6.174.2.3.0.61
hwUpsBatteryChangeAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
}
STATUS current
DESCRIPTION
"Batterry Change Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 61 }
-- 1.3.6.1.4.1.2011.6.174.2.3.0.62
hwUpsBatteryChangeAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
}
STATUS current
DESCRIPTION
"Batterry Change Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 62 }
hwUpsBatteryMaintainAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Batterry Maintain Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 63 }
hwUpsBatteryMaintainAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Batterry Maintain Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 64 }
-- 1.3.6.1.4.1.2011.6.174.2.3.0.65
hwUpsMinorLoadOffAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
}
STATUS current
DESCRIPTION
"Minor Load Off Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 65 }
-- 1.3.6.1.4.1.2011.6.174.2.3.0.66
hwUpsMinorLoadOffAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
}
STATUS current
DESCRIPTION
"Minor Load Off Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 66 }
-- 1.3.6.1.4.1.2011.6.174.2.3.0.67
hwUpsParaStatusSetAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
}
STATUS current
DESCRIPTION
"Parallel Status Set Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 67 }
-- 1.3.6.1.4.1.2011.6.174.2.3.0.68
hwUpsParaStatusSetAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
}
STATUS current
DESCRIPTION
"Parallel Status Set Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 68 }
hwUpsRemainCapacityAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Remain Capacity Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 69 }
hwUpsRemainCapacityAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Remain Capacity Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 70 }
hwUpsParParaAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Parallel Parameter Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time. "
::= { hwUpsAlarmTrapsPrefix 71 }
hwUpsParParaAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Parallel Parameter Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the tim"
::= { hwUpsAlarmTrapsPrefix 72 }
-- 1.3.6.1.4.1.2011.6.174.2.3.0.73
hwUpsFlashAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
}
STATUS current
DESCRIPTION
"Flash Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
::= { hwUpsAlarmTrapsPrefix 73 }
-- 1.3.6.1.4.1.2011.6.174.2.3.0.74
hwUpsFlashAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId, hwUpsTrapsModuleSeqId, hwUpsTrapsEquipID, hwUpsTrapsID, hwUpsTrapsReasonId,
hwUpsTrapsText, hwUpsTrapsLevel, hwUpsTrapsFlag, hwUpsTrapsSynchronNum, hwUpsTrapsTime
}
STATUS current
DESCRIPTION
"Flash Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
::= { hwUpsAlarmTrapsPrefix 74 }
hwUpsManulPowerOnOffTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Manul Power On Off Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 75 }
hwUpsManulPowerOnOffResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Manul Power On Off Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
::= { hwUpsAlarmTrapsPrefix 76 }
hwUpsIOAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"IO signal Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
::= { hwUpsAlarmTrapsPrefix 77 }
hwUpsIOAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"IO Signal Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
::= { hwUpsAlarmTrapsPrefix 78 }
hwUpsEnvironmentDataAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Environment Date Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
::= { hwUpsAlarmTrapsPrefix 79 }
hwUpsEnvironmentDataAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Environment Date Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
::= { hwUpsAlarmTrapsPrefix 80 }
hwUpsUpdatingAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Updating Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
::= { hwUpsAlarmTrapsPrefix 81 }
hwUpsUpdatingAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Updating Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
::= { hwUpsAlarmTrapsPrefix 82 }
hwUpsProgramAbnormalTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Program Abnormal Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
::= { hwUpsAlarmTrapsPrefix 83 }
hwUpsProgramAbnormalResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Program Abnormal Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
::= { hwUpsAlarmTrapsPrefix 84 }
hwUpsBcbFaultAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Bcb Fault Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
::= { hwUpsAlarmTrapsPrefix 85 }
hwUpsBcbFaultAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Bcb Fault Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
::= { hwUpsAlarmTrapsPrefix 86 }
hwUpsEcoRangeAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"ECO Range Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
::= { hwUpsAlarmTrapsPrefix 87 }
hwUpsEcoRangeAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"ECO Range Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
::= { hwUpsAlarmTrapsPrefix 88 }
hwUpsBMUAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Bmu Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
::= { hwUpsAlarmTrapsPrefix 89 }
hwUpsBMUAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Bmu Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
::= { hwUpsAlarmTrapsPrefix 90 }
hwUpsElableFailedAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Elable Failed Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
::= { hwUpsAlarmTrapsPrefix 91 }
hwUpsElableFailedAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Elable Failed Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time"
::= { hwUpsAlarmTrapsPrefix 92 }
hwUpsDIPConflictAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"DIP Conflict Trap"
::= { hwUpsAlarmTrapsPrefix 93 }
hwUpsDIPConflictAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"DIP Conflict Resume Trap."
::= { hwUpsAlarmTrapsPrefix 94 }
hwUpsSystemStatusTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Ups System Status Trap."
::= { hwUpsAlarmTrapsPrefix 95 }
hwUpsSystemStatusResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Ups System Status Resume Trap."
::= { hwUpsAlarmTrapsPrefix 96 }
hwUpsIBOXAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Ups IBOX Alarm Trap."
::= { hwUpsAlarmTrapsPrefix 97 }
hwUpsIBOXAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Ups IBOX Alarm Resume Trap"
::= { hwUpsAlarmTrapsPrefix 98 }
hwUpsBattRackAlarmTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Expand Borad Alarm Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 99 }
hwUpsBattRackAlarmResumeTrap NOTIFICATION-TYPE
OBJECTS { hwUpsTrapsDeviceId,hwUpsTrapsModuleSeqId,hwUpsTrapsEquipID,hwUpsTrapsID,hwUpsTrapsReasonId,hwUpsTrapsText,hwUpsTrapsLevel,hwUpsTrapsFlag,hwUpsTrapsSynchronNum,hwUpsTrapsTime }
STATUS current
DESCRIPTION
"Expand Borad Alarm Resume Trap.
Its correlation binding parameters: Device ID, Sequence ID, Equip ID, Trap ID,
Trap Reason ID, Trap Text, Trap Level, Trap Flag, Synchron NO and the time."
::= { hwUpsAlarmTrapsPrefix 100 }
END