uchiller_cmpMIB MODULE-IDENTITY
LAST-UPDATED "200303141725Z" -- March 14, 2003 at 17:25 GMT
ORGANIZATION "CAREL SpA"
CONTACT-INFO
"
Simone Ravazzolo
Carel SpA
Via dell'Industria, 11
35020 Brugine (PD) Italy
Tel: +39 049 9716611
E-mail: simone.ravazzolo@carel.com
"
DESCRIPTION
"This is the MIB module for the uchiller_cmp device."
::= { instruments 1 }
--
-- Node definitions
--
-- 1.3.6.1.4.1.9839
carel OBJECT IDENTIFIER ::= { enterprises 9839 }
-- 1.3.6.1.4.1.9839.1
systm OBJECT IDENTIFIER ::= { carel 1 }
-- 1.3.6.1.4.1.9839.1.1
agentRelease OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Release of the Agent."
::= { systm 1 }
-- 1.3.6.1.4.1.9839.1.2
agentCode OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Code of the Agent. 1=WebGate"
::= { systm 2 }
-- 1.3.6.1.4.1.9839.2
instruments OBJECT IDENTIFIER ::= { carel 2 }
-- 1.3.6.1.4.1.9839.2.0
webGateInfo OBJECT IDENTIFIER ::= { instruments 0 }
-- 1.3.6.1.4.1.9839.2.0.1
agentParameters OBJECT IDENTIFIER ::= { webGateInfo 1 }
-- 1.3.6.1.4.1.9839.2.0.1.1
netSize OBJECT-TYPE
SYNTAX Integer32 (1..16)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Network size. It corresponds to the number of units connected to the WebGate. "
::= { agentParameters 1 }
-- 1.3.6.1.4.1.9839.2.0.1.2
baudRate OBJECT-TYPE
SYNTAX Integer32 (1200 | 2400 |4800 |9600 | 19200)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Baudrate of the Carel network. "
::= { agentParameters 2 }
-- 1.3.6.1.4.1.9839.2.0.2
unitTypeGroup OBJECT IDENTIFIER ::= { webGateInfo 2 }
-- 1.3.6.1.4.1.9839.2.0.2.1
unit1-Type OBJECT-TYPE
SYNTAX DisplayString
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of the unit having serial address 1. "
::= { unitTypeGroup 1 }
-- ... You will have how many unitX-Type objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.0.3
unitCodeGroup OBJECT IDENTIFIER ::= { webGateInfo 3 }
-- 1.3.6.1.4.1.9839.2.0.3.1
unit1-Code OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Code of the unit having serial address 1. "
::= { unitCodeGroup 1 }
-- ... You will have how many unitX-Code objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.0.4
unitSoftwareReleaseGroup OBJECT IDENTIFIER ::= { webGateInfo 4 }
-- 1.3.6.1.4.1.9839.2.0.3.1
unit1-SoftwareRelease OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Software release of the unit having serial address 1. "
::= { unitSoftwareReleaseGroup 1 }
-- ... You will have how many unitX-SoftwareRelease objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.0.5
unitMinSoftwareReleaseGroup OBJECT IDENTIFIER ::= { webGateInfo 5 }
-- 1.3.6.1.4.1.9839.2.0.5.1
unit1-MinSoftwareRelease OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Minimum software release of the unit having serial address 1. "
::= { unitMinSoftwareReleaseGroup 1 }
-- ... You will have how many unitX-MinSoftwareRelease objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.0.6
unitMaxSoftwareReleaseGroup OBJECT IDENTIFIER ::= { webGateInfo 6 }
-- 1.3.6.1.4.1.9839.2.0.6.1
unit1-MaxSoftwareRelease OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Maximum software release of the unit having serial address 1. "
::= { unitMaxSoftwareReleaseGroup 1 }
-- ... You will have how many unitX-MaxSoftwareRelease objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.0.7
unitNoAnswerCounterGroup OBJECT IDENTIFIER ::= { webGateInfo 7 }
-- 1.3.6.1.4.1.9839.2.0.7.1
unit1-NoAnswerCounter OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "No answer counter of the unit having serial address 1. "
::= { unitNoAnswerCounterGroup 1 }
-- ... You will have how many unitX-NoAnswerCounter objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.0.8
unitErrorChecksumCounterGroup OBJECT IDENTIFIER ::= { webGateInfo 8 }
-- 1.3.6.1.4.1.9839.2.0.8.1
unit1-ErrorChecksumCounter OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Error checksum counter of the unit having serial address 1. "
::= { unitErrorChecksumCounterGroup 1 }
-- ... You will have how many unitX-ErrorChecksumCounter objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.0.9
unitTimeoutCounterGroup OBJECT IDENTIFIER ::= { webGateInfo 9 }
-- 1.3.6.1.4.1.9839.2.0.9.1
unit1-TimeoutCounter OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timeout counter of the unit having serial address 1. "
::= { unitTimeoutCounterGroup 1 }
-- ... You will have how many unitX-TimeoutCounter objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.0.10
unitOnLineStatusGroup OBJECT IDENTIFIER ::= { webGateInfo 10 }
-- 1.3.6.1.4.1.9839.2.0.10.1
unit1-OnLineStatus OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "On line status of the unit having serial address 1. "
::= { unitOnLineStatusGroup 1 }
-- ... You will have how many unitX-OnLineStatus objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.1
-- uchiller_cmpMIB OBJECT IDENTIFIER ::= { instruments 1 }
-- 1.3.6.1.4.1.9839.2.1.1
digitalObjects OBJECT IDENTIFIER ::= { uchiller_cmpMIB 1 }
-- 1.3.6.1.4.1.9839.2.1.1.1
est_inv OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Cooling - Heating"
::= { digitalObjects 1 }
-- 1.3.6.1.4.1.9839.2.1.1.2
on_off_unita OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "On-Off if remote On/Off is disabled"
::= { digitalObjects 2 }
-- 1.3.6.1.4.1.9839.2.1.1.5
allarme_hp OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "High pressure alarm"
::= { digitalObjects 5 }
-- 1.3.6.1.4.1.9839.2.1.1.6
allarme_lp OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Low pressure alarm"
::= { digitalObjects 6 }
-- 1.3.6.1.4.1.9839.2.1.1.8
all_flusso OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Flowmeter alarm"
::= { digitalObjects 8 }
-- 1.3.6.1.4.1.9839.2.1.1.9
err_sonda_b3 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Probe b3 faulty or not connected"
::= { digitalObjects 9 }
-- 1.3.6.1.4.1.9839.2.1.1.10
err_sonda_b2 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Probe b2 faulty or not connected"
::= { digitalObjects 10 }
-- 1.3.6.1.4.1.9839.2.1.1.11
err_sonda_b1 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Probe b1 faulty or not connected"
::= { digitalObjects 11 }
-- 1.3.6.1.4.1.9839.2.1.1.13
err_eeprom_s OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Faulty eeprom alarm"
::= { digitalObjects 13 }
-- 1.3.6.1.4.1.9839.2.1.1.16
all_termin_off OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm in the communic. with the remote terminal"
::= { digitalObjects 16 }
-- 1.3.6.1.4.1.9839.2.1.1.17
sbrinamento_on OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Defrost in progress"
::= { digitalObjects 17 }
-- 1.3.6.1.4.1.9839.2.1.1.18
all_sbrinamento OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Defrost timeout"
::= { digitalObjects 18 }
-- 1.3.6.1.4.1.9839.2.1.1.19
all_antigelo OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Freezing alarm"
::= { digitalObjects 19 }
-- 1.3.6.1.4.1.9839.2.1.1.20
all_agelo_sonda OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Low temperature alarm"
::= { digitalObjects 20 }
-- 1.3.6.1.4.1.9839.2.1.1.21
all_sovratens OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Overvoltage alarm"
::= { digitalObjects 21 }
-- 1.3.6.1.4.1.9839.2.1.1.22
all_sottotens OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Undervoltage alarm"
::= { digitalObjects 22 }
-- 1.3.6.1.4.1.9839.2.1.1.25
stato_pompa OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Pump status"
::= { digitalObjects 25 }
-- 1.3.6.1.4.1.9839.2.1.1.26
stato_compress OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Comp. 1 status"
::= { digitalObjects 26 }
-- 1.3.6.1.4.1.9839.2.1.1.27
stato_resists OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Resist. status"
::= { digitalObjects 27 }
-- 1.3.6.1.4.1.9839.2.1.1.28
stato_valvola OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Valve status"
::= { digitalObjects 28 }
-- 1.3.6.1.4.1.9839.2.1.1.30
stato_ventils OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Fan status"
::= { digitalObjects 30 }
-- 1.3.6.1.4.1.9839.2.1.1.40
unita_misura OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Measurement Unit"
DEFVAL { 0 }
::= { digitalObjects 40 }
-- 1.3.6.1.4.1.9839.2.1.1.41
out_per_fan_f1 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flags"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Fans Output"
DEFVAL { 0 }
::= { digitalObjects 41 }
-- 1.3.6.1.4.1.9839.2.1.1.42
esecuz_sbrin_d1 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Defrosting cycle / condensation antifreeze"
DEFVAL { 1 }
::= { digitalObjects 42 }
-- 1.3.6.1.4.1.9839.2.1.1.43
def_time_tmp_d2 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Timed or temperature-based defrosting"
DEFVAL { 0 }
::= { digitalObjects 43 }
-- 1.3.6.1.4.1.9839.2.1.1.44
res_gelo_sbr_db OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Antifreeze heaters activated while defrosting"
DEFVAL { 0 }
::= { digitalObjects 44 }
-- 1.3.6.1.4.1.9839.2.1.1.45
en_sonda_res_a6 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Support heaters probe"
DEFVAL { 0 }
::= { digitalObjects 45 }
-- 1.3.6.1.4.1.9839.2.1.1.46
all_lp_sonda_p7 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Low pressure alarm with pressure probes"
DEFVAL { 0 }
::= { digitalObjects 46 }
-- 1.3.6.1.4.1.9839.2.1.1.47
en_id_on_off_h7 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "ON/OFF digital input"
DEFVAL { 0 }
::= { digitalObjects 47 }
-- 1.3.6.1.4.1.9839.2.1.1.48
all_lp_comp_pa OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Low pressure alarm selection"
DEFVAL { 0 }
::= { digitalObjects 48 }
-- 1.3.6.1.4.1.9839.2.1.1.49
en_set2_hc OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Second set of param."
DEFVAL { 0 }
::= { digitalObjects 49 }
-- 1.3.6.1.4.1.9839.2.1.1.50
inv_est_inv_hd OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Logic inversion cooling/heating"
DEFVAL { 0 }
::= { digitalObjects 50 }
-- 1.3.6.1.4.1.9839.2.1.1.51
sel_rele_all_hf OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Alarm relay status without alarm condition"
DEFVAL { 1 }
::= { digitalObjects 51 }
-- 1.3.6.1.4.1.9839.2.1.1.55
ab_estate_inv_h6 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Cooling/heating digital input with P8/P9 = 8, 9"
DEFVAL { 0 }
::= { digitalObjects 55 }
-- 1.3.6.1.4.1.9839.2.1.1.56
rotaz_compr_r5 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compressor rotation"
DEFVAL { 3 }
::= { digitalObjects 56 }
-- 1.3.6.1.4.1.9839.2.1.2
analogObjects OBJECT IDENTIFIER ::= { uchiller_cmpMIB 2 }
-- 1.3.6.1.4.1.9839.2.1.2.1
sonda_b1 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Inlet probe"
::= { analogObjects 1 }
-- 1.3.6.1.4.1.9839.2.1.2.2
sonda_b2 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Water temperaturte at evaporator output B2"
::= { analogObjects 2 }
-- 1.3.6.1.4.1.9839.2.1.2.3
sonda_b3 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Temperature/pressure defrosting B3"
::= { analogObjects 3 }
-- 1.3.6.1.4.1.9839.2.1.2.5
i_scala_press OBJECT-TYPE
SYNTAX Integer32 (0..32767)
UNITS "bar x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Min. value current input"
DEFVAL { 0 }
::= { analogObjects 5 }
-- 1.3.6.1.4.1.9839.2.1.2.6
f_scala_press OBJECT-TYPE
SYNTAX Integer32 (-32767..400)
UNITS "bar x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Max value current input"
DEFVAL { 300 }
::= { analogObjects 6 }
-- 1.3.6.1.4.1.9839.2.1.2.7
calibra_b1 OBJECT-TYPE
SYNTAX Integer32 (-120..120)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Probe B1 calibration"
DEFVAL { 0 }
::= { analogObjects 7 }
-- 1.3.6.1.4.1.9839.2.1.2.8
calibra_b2 OBJECT-TYPE
SYNTAX Integer32 (-120..120)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Probe outlet B2 calibration"
DEFVAL { 0 }
::= { analogObjects 8 }
-- 1.3.6.1.4.1.9839.2.1.2.9
calibra_b3 OBJECT-TYPE
SYNTAX Integer32 (-120..120)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Defrosting probe B3 calibration"
DEFVAL { 0 }
::= { analogObjects 9 }
-- 1.3.6.1.4.1.9839.2.1.2.10
setp_estate OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Cooling Set-Point"
DEFVAL { 120 }
::= { analogObjects 10 }
-- 1.3.6.1.4.1.9839.2.1.2.11
diff_estate OBJECT-TYPE
SYNTAX Integer32 (3..199)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Cooling differential"
DEFVAL { 30 }
::= { analogObjects 11 }
-- 1.3.6.1.4.1.9839.2.1.2.12
setp_inverno OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Heating set-point"
DEFVAL { 400 }
::= { analogObjects 12 }
-- 1.3.6.1.4.1.9839.2.1.2.13
diff_inverno OBJECT-TYPE
SYNTAX Integer32 (3..199)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Heating differential"
DEFVAL { 30 }
::= { analogObjects 13 }
-- 1.3.6.1.4.1.9839.2.1.2.14
min_set_est OBJECT-TYPE
SYNTAX Integer32 (-400..32767)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Min. Cooling set-point"
DEFVAL { -400 }
::= { analogObjects 14 }
-- 1.3.6.1.4.1.9839.2.1.2.15
max_set_est OBJECT-TYPE
SYNTAX Integer32 (-32767..1990)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Max. Cooling set-point"
DEFVAL { 900 }
::= { analogObjects 15 }
-- 1.3.6.1.4.1.9839.2.1.2.16
min_set_inv OBJECT-TYPE
SYNTAX Integer32 (-400..32767)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Min. Heating set-point"
DEFVAL { -400 }
::= { analogObjects 16 }
-- 1.3.6.1.4.1.9839.2.1.2.17
max_set_inv OBJECT-TYPE
SYNTAX Integer32 (-32767..1990)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Max. Heating set-point"
DEFVAL { 900 }
::= { analogObjects 17 }
-- 1.3.6.1.4.1.9839.2.1.2.18
tmin_vel_est_f5 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "<22>C/<2F>F bar x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Temperature value for min Cooling speed .Pressure"
DEFVAL { 130 }
::= { analogObjects 18 }
-- 1.3.6.1.4.1.9839.2.1.2.19
tmax_vel_est_f6 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "<22>C/<2F>F bar x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Temperature value for max Cooling speed. Pressure"
DEFVAL { 160 }
::= { analogObjects 19 }
-- 1.3.6.1.4.1.9839.2.1.2.20
tmin_vel_inv_f7 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "<22>C/<2F>F bar x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Temperature value for min Heating speed. Pressure"
DEFVAL { 130 }
::= { analogObjects 20 }
-- 1.3.6.1.4.1.9839.2.1.2.21
tmax_vel_inv_f8 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "<22>C/<2F>F bar x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Temperature value for max Heating speed.Pressure"
DEFVAL { 90 }
::= { analogObjects 21 }
-- 1.3.6.1.4.1.9839.2.1.2.22
toff_fan_est_f9 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "<22>C/<2F>F bar x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Temperature to turn OFF the fan in Cooling .Pressure"
DEFVAL { 80 }
::= { analogObjects 22 }
-- 1.3.6.1.4.1.9839.2.1.2.23
toff_fan_inv_fa OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "<22>C/<2F>F bar x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Temperature to turn OFF the fan in Winter. Pressure"
DEFVAL { 160 }
::= { analogObjects 23 }
-- 1.3.6.1.4.1.9839.2.1.2.24
parametro_d3 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "<22>C/<2F>F bar x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Temperat./pressure starting the defrost.cycle"
DEFVAL { 35 }
::= { analogObjects 24 }
-- 1.3.6.1.4.1.9839.2.1.2.25
parametro_d4 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "<22>C/<2F>F bar x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "End-defrosting temperature/pressure"
DEFVAL { 140 }
::= { analogObjects 25 }
-- 1.3.6.1.4.1.9839.2.1.2.26
set_al_agelo_a1 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Antifreeze"
DEFVAL { 30 }
::= { analogObjects 26 }
-- 1.3.6.1.4.1.9839.2.1.2.27
dif_al_agelo_a2 OBJECT-TYPE
SYNTAX Integer32 (3..199)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Differential for antifreeze/low ambient temperatur"
DEFVAL { 50 }
::= { analogObjects 27 }
-- 1.3.6.1.4.1.9839.2.1.2.28
set_res_gelo_a4 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Setpoint for the activation of antifreeze supp."
DEFVAL { 50 }
::= { analogObjects 28 }
-- 1.3.6.1.4.1.9839.2.1.2.29
dif_res_gelo_a5 OBJECT-TYPE
SYNTAX Integer32 (3..199)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Antifreeze/Support heaters differential"
DEFVAL { 10 }
::= { analogObjects 29 }
-- 1.3.6.1.4.1.9839.2.1.2.30
lim_set_gelo_a7 OBJECT-TYPE
SYNTAX Integer32 (-400..1220)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Antifreeze-alarm set"
DEFVAL { -400 }
::= { analogObjects 30 }
-- 1.3.6.1.4.1.9839.2.1.2.31
set_res_risc_a8 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Heating support-resistance set"
DEFVAL { 250 }
::= { analogObjects 31 }
-- 1.3.6.1.4.1.9839.2.1.2.32
dif_res_risc_a9 OBJECT-TYPE
SYNTAX Integer32 (3..199)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Heating support-resistance differential"
DEFVAL { 30 }
::= { analogObjects 32 }
-- 1.3.6.1.4.1.9839.2.1.2.33
set_all_at_pb OBJECT-TYPE
SYNTAX Integer32 (-400..1990)
UNITS "/d x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "High temperature alarm set"
DEFVAL { 900 }
::= { analogObjects 33 }
-- 1.3.6.1.4.1.9839.2.1.2.34
sonda_b4 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Probe B4"
::= { analogObjects 34 }
-- 1.3.6.1.4.1.9839.2.1.3
integerObjects OBJECT IDENTIFIER ::= { uchiller_cmpMIB 3 }
-- 1.3.6.1.4.1.9839.2.1.3.1
velocita_vent OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Fan speed 0-100%"
::= { integerObjects 1 }
-- 1.3.6.1.4.1.9839.2.1.3.6
filtro_digitale OBJECT-TYPE
SYNTAX Integer32 (1..15)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Digital filter"
DEFVAL { 4 }
::= { integerObjects 6 }
-- 1.3.6.1.4.1.9839.2.1.3.8
tmin_on_comp_c1 OBJECT-TYPE
SYNTAX Integer32 (0..150)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Min. running time"
DEFVAL { 60 }
::= { integerObjects 8 }
-- 1.3.6.1.4.1.9839.2.1.3.9
tmin_sp_comp_c2 OBJECT-TYPE
SYNTAX Integer32 (0..90)
UNITS "10 sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Min. stopping time"
DEFVAL { 6 }
::= { integerObjects 9 }
-- 1.3.6.1.4.1.9839.2.1.3.10
time_2_acc_c3 OBJECT-TYPE
SYNTAX Integer32 (0..90)
UNITS "10 sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Time interval between 2 starts"
DEFVAL { 36 }
::= { integerObjects 10 }
-- 1.3.6.1.4.1.9839.2.1.3.11
rit_on_comp_c6 OBJECT-TYPE
SYNTAX Integer32 (0..150)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Delay at start-up"
DEFVAL { 0 }
::= { integerObjects 11 }
-- 1.3.6.1.4.1.9839.2.1.3.12
rit_c_on_pmp_c7 OBJECT-TYPE
SYNTAX Integer32 (0..150)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Delay in switching on compressor after switch. On"
DEFVAL { 20 }
::= { integerObjects 12 }
-- 1.3.6.1.4.1.9839.2.1.3.13
off_p_off_v_c8 OBJECT-TYPE
SYNTAX Integer32 (0..150)
UNITS "min"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Delay in switching off compress. After switc.off"
DEFVAL { 20 }
::= { integerObjects 13 }
-- 1.3.6.1.4.1.9839.2.1.3.14
contaore_c1_c9 OBJECT-TYPE
SYNTAX Integer32 (0..19900)
UNITS "hours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Hour counter comp. 1"
DEFVAL { 0 }
::= { integerObjects 14 }
-- 1.3.6.1.4.1.9839.2.1.3.15
max_ore_comp_cb OBJECT-TYPE
SYNTAX Integer32 (0..100)
UNITS "100 hours"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Timer threshold during normal operation"
DEFVAL { 0 }
::= { integerObjects 15 }
-- 1.3.6.1.4.1.9839.2.1.3.16
ore_pmp_vent_cc OBJECT-TYPE
SYNTAX Integer32 (0..19900)
UNITS "hours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Pump/inlet fan timer"
DEFVAL { 0 }
::= { integerObjects 16 }
-- 1.3.6.1.4.1.9839.2.1.3.17
modo_vent_f2 OBJECT-TYPE
SYNTAX Integer32 (0..3)
UNITS "flags"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Operating logic of the fans"
DEFVAL { 0 }
::= { integerObjects 17 }
-- 1.3.6.1.4.1.9839.2.1.3.18
min_volt_f3 OBJECT-TYPE
SYNTAX Integer32 (0..32767)
UNITS "step"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Minimum tension threshold for Triac"
DEFVAL { 35 }
::= { integerObjects 18 }
-- 1.3.6.1.4.1.9839.2.1.3.19
max_volt_f4 OBJECT-TYPE
SYNTAX Integer32 (-32767..100)
UNITS "step"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Max.tension threshold for Triac"
DEFVAL { 75 }
::= { integerObjects 19 }
-- 1.3.6.1.4.1.9839.2.1.3.20
t_spunto_v_fb OBJECT-TYPE
SYNTAX Integer32 (0..99)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Starting time of fans"
DEFVAL { 4 }
::= { integerObjects 20 }
-- 1.3.6.1.4.1.9839.2.1.3.21
t_imp_triac_fc OBJECT-TYPE
SYNTAX Integer32 (0..15)
UNITS "msec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Triac impulse duration"
DEFVAL { 2 }
::= { integerObjects 21 }
-- 1.3.6.1.4.1.9839.2.1.3.22
t_min_on_def_d5 OBJECT-TYPE
SYNTAX Integer32 (10..150)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Minimum time interval before starting a defr. Cycl"
DEFVAL { 10 }
::= { integerObjects 22 }
-- 1.3.6.1.4.1.9839.2.1.3.23
t_min_def_d6 OBJECT-TYPE
SYNTAX Integer32 (0..150)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Min. duration of a defrosting cycle"
DEFVAL { 0 }
::= { integerObjects 23 }
-- 1.3.6.1.4.1.9839.2.1.3.24
t_max_def_d7 OBJECT-TYPE
SYNTAX Integer32 (1..15)
UNITS "min"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Max. duration of a defrosting cycle"
DEFVAL { 5 }
::= { integerObjects 24 }
-- 1.3.6.1.4.1.9839.2.1.3.25
rit_tra_2def_d8 OBJECT-TYPE
SYNTAX Integer32 (10..150)
UNITS "min"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Time-delay between 2 defrosting"
DEFVAL { 30 }
::= { integerObjects 25 }
-- 1.3.6.1.4.1.9839.2.1.3.26
wait_on_def_dc OBJECT-TYPE
SYNTAX Integer32 (0..3)
UNITS "min"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Delay before defrosting"
DEFVAL { 0 }
::= { integerObjects 26 }
-- 1.3.6.1.4.1.9839.2.1.3.27
wait_end_def_dd OBJECT-TYPE
SYNTAX Integer32 (0..3)
UNITS "min"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Delay after defrosting"
DEFVAL { 0 }
::= { integerObjects 27 }
-- 1.3.6.1.4.1.9839.2.1.3.28
rit_all_ag_a3 OBJECT-TYPE
SYNTAX Integer32 (0..150)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Time to bypass the antfreeze/low amb. Temp. allarm"
DEFVAL { 0 }
::= { integerObjects 28 }
-- 1.3.6.1.4.1.9839.2.1.3.29
r_al_on_flux_p1 OBJECT-TYPE
SYNTAX Integer32 (0..150)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Flowmeter down delayed when starting the pump"
DEFVAL { 20 }
::= { integerObjects 29 }
-- 1.3.6.1.4.1.9839.2.1.3.30
r_al_rg_flux_p2 OBJECT-TYPE
SYNTAX Integer32 (0..90)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Flowswitch alarm delayed during normal operating"
DEFVAL { 5 }
::= { integerObjects 30 }
-- 1.3.6.1.4.1.9839.2.1.3.31
rit_all_lp_p3 OBJECT-TYPE
SYNTAX Integer32 (0..199)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Low pressure alarm delayed at compr. start-up"
DEFVAL { 40 }
::= { integerObjects 31 }
-- 1.3.6.1.4.1.9839.2.1.3.32
t_buzzer_p4 OBJECT-TYPE
SYNTAX Integer32 (0..15)
UNITS "min"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Buzzer ON"
DEFVAL { 0 }
::= { integerObjects 32 }
-- 1.3.6.1.4.1.9839.2.1.3.33
riprist_all_p5 OBJECT-TYPE
SYNTAX Integer32 (0..4)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Reset of alarms"
DEFVAL { 0 }
::= { integerObjects 33 }
-- 1.3.6.1.4.1.9839.2.1.3.34
selez_id1_p8 OBJECT-TYPE
SYNTAX Integer32 (0..7)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Sel. of the digital input"
DEFVAL { 0 }
::= { integerObjects 34 }
-- 1.3.6.1.4.1.9839.2.1.3.35
selez_id2_p9 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Sel. of the digital input n.2"
::= { integerObjects 35 }
-- 1.3.6.1.4.1.9839.2.1.3.36
modello_mac_h1 OBJECT-TYPE
SYNTAX Integer32 (0..8)
UNITS "flag"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Unit model"
DEFVAL { 2 }
::= { integerObjects 36 }
-- 1.3.6.1.4.1.9839.2.1.3.37
modo_pmp_vnt_h5 OBJECT-TYPE
SYNTAX Integer32 (0..2)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Operating logic of the Pump/Inlet fan"
DEFVAL { 1 }
::= { integerObjects 37 }
-- 1.3.6.1.4.1.9839.2.1.3.38
blocca_tasti_h9 OBJECT-TYPE
SYNTAX Integer32 (0..3)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Keyboard lock-up"
DEFVAL { 1 }
::= { integerObjects 38 }
-- 1.3.6.1.4.1.9839.2.1.3.39
seradd OBJECT-TYPE
SYNTAX Integer32 (1..199)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Serial address"
DEFVAL { 1 }
::= { integerObjects 39 }
-- 1.3.6.1.4.1.9839.2.1.3.40
passw_telec_hb OBJECT-TYPE
SYNTAX Integer32 (0..15)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Infrared remote unit password"
DEFVAL { 0 }
::= { integerObjects 40 }
-- 1.3.6.1.4.1.9839.2.1.3.41
valv_inv_ch_he OBJECT-TYPE
SYNTAX Integer32 (0..2)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Valve status cooling"
DEFVAL { 0 }
::= { integerObjects 41 }
-- 1.3.6.1.4.1.9839.2.1.3.42
numero_term_h8 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Number of terminals"
DEFVAL { 0 }
::= { integerObjects 42 }
-- 1.3.6.1.4.1.9839.2.1.3.43
high_temp_all_pc OBJECT-TYPE
SYNTAX Integer32 (0..150)
UNITS "min"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "High temperature alarm delayed at start-up"
DEFVAL { 30 }
::= { integerObjects 43 }
-- 1.3.6.1.4.1.9839.2.1.3.51
versione_sw_hg OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "SW Release"
DEFVAL { 13 }
::= { integerObjects 51 }
-- 1.3.6.1.4.1.9839.2.1.3.52
rit_acc_comp OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "sec"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Start delay between the two compressors"
::= { integerObjects 52 }
-- 1.3.6.1.4.1.9839.2.1.3.53
rit_spegn_comp OBJECT-TYPE
SYNTAX Integer32 (0..15)
UNITS "sec"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Stop delay between the two compressors"
DEFVAL { 0 }
::= { integerObjects 53 }
-- 1.3.6.1.4.1.9839.2.1.3.56
tempo_acc_pompa OBJECT-TYPE
SYNTAX Integer32 (1..150)
UNITS "min"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Minimum time between two pump starts"
DEFVAL { 30 }
::= { integerObjects 56 }
END
--