-- -- CAREL-uchiller_cmp.MIB -- MIB generated by CAREL -- Friday, 14 March 2003 -- CAREL-uchiller_cmp-MIB DEFINITIONS ::= BEGIN IMPORTS OBJECT-GROUP FROM SNMPv2-CONF sysContact, sysName, sysLocation FROM SNMPv2-MIB enterprises, MODULE-IDENTITY FROM SNMPv2-SMI; uchiller_cmpMIB MODULE-IDENTITY LAST-UPDATED "200303141725Z" -- March 14, 2003 at 17:25 GMT ORGANIZATION "CAREL SpA" CONTACT-INFO " Simone Ravazzolo Carel SpA Via dell'Industria, 11 35020 Brugine (PD) Italy Tel: +39 049 9716611 E-mail: simone.ravazzolo@carel.com " DESCRIPTION "This is the MIB module for the uchiller_cmp device." ::= { instruments 1 } -- -- Node definitions -- -- 1.3.6.1.4.1.9839 carel OBJECT IDENTIFIER ::= { enterprises 9839 } -- 1.3.6.1.4.1.9839.1 systm OBJECT IDENTIFIER ::= { carel 1 } -- 1.3.6.1.4.1.9839.1.1 agentRelease OBJECT-TYPE SYNTAX Integer32 UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Release of the Agent." ::= { systm 1 } -- 1.3.6.1.4.1.9839.1.2 agentCode OBJECT-TYPE SYNTAX Integer32 UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Code of the Agent. 1=WebGate" ::= { systm 2 } -- 1.3.6.1.4.1.9839.2 instruments OBJECT IDENTIFIER ::= { carel 2 } -- 1.3.6.1.4.1.9839.2.0 webGateInfo OBJECT IDENTIFIER ::= { instruments 0 } -- 1.3.6.1.4.1.9839.2.0.1 agentParameters OBJECT IDENTIFIER ::= { webGateInfo 1 } -- 1.3.6.1.4.1.9839.2.0.1.1 netSize OBJECT-TYPE SYNTAX Integer32 (1..16) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Network size. It corresponds to the number of units connected to the WebGate. " ::= { agentParameters 1 } -- 1.3.6.1.4.1.9839.2.0.1.2 baudRate OBJECT-TYPE SYNTAX Integer32 (1200 | 2400 |4800 |9600 | 19200) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Baudrate of the Carel network. " ::= { agentParameters 2 } -- 1.3.6.1.4.1.9839.2.0.2 unitTypeGroup OBJECT IDENTIFIER ::= { webGateInfo 2 } -- 1.3.6.1.4.1.9839.2.0.2.1 unit1-Type OBJECT-TYPE SYNTAX DisplayString UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Type of the unit having serial address 1. " ::= { unitTypeGroup 1 } -- ... You will have how many unitX-Type objects as the value of netSize is -- 1.3.6.1.4.1.9839.2.0.3 unitCodeGroup OBJECT IDENTIFIER ::= { webGateInfo 3 } -- 1.3.6.1.4.1.9839.2.0.3.1 unit1-Code OBJECT-TYPE SYNTAX Integer32 UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Code of the unit having serial address 1. " ::= { unitCodeGroup 1 } -- ... You will have how many unitX-Code objects as the value of netSize is -- 1.3.6.1.4.1.9839.2.0.4 unitSoftwareReleaseGroup OBJECT IDENTIFIER ::= { webGateInfo 4 } -- 1.3.6.1.4.1.9839.2.0.3.1 unit1-SoftwareRelease OBJECT-TYPE SYNTAX Integer32 UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Software release of the unit having serial address 1. " ::= { unitSoftwareReleaseGroup 1 } -- ... You will have how many unitX-SoftwareRelease objects as the value of netSize is -- 1.3.6.1.4.1.9839.2.0.5 unitMinSoftwareReleaseGroup OBJECT IDENTIFIER ::= { webGateInfo 5 } -- 1.3.6.1.4.1.9839.2.0.5.1 unit1-MinSoftwareRelease OBJECT-TYPE SYNTAX Integer32 UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Minimum software release of the unit having serial address 1. " ::= { unitMinSoftwareReleaseGroup 1 } -- ... You will have how many unitX-MinSoftwareRelease objects as the value of netSize is -- 1.3.6.1.4.1.9839.2.0.6 unitMaxSoftwareReleaseGroup OBJECT IDENTIFIER ::= { webGateInfo 6 } -- 1.3.6.1.4.1.9839.2.0.6.1 unit1-MaxSoftwareRelease OBJECT-TYPE SYNTAX Integer32 UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Maximum software release of the unit having serial address 1. " ::= { unitMaxSoftwareReleaseGroup 1 } -- ... You will have how many unitX-MaxSoftwareRelease objects as the value of netSize is -- 1.3.6.1.4.1.9839.2.0.7 unitNoAnswerCounterGroup OBJECT IDENTIFIER ::= { webGateInfo 7 } -- 1.3.6.1.4.1.9839.2.0.7.1 unit1-NoAnswerCounter OBJECT-TYPE SYNTAX Integer32 UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "No answer counter of the unit having serial address 1. " ::= { unitNoAnswerCounterGroup 1 } -- ... You will have how many unitX-NoAnswerCounter objects as the value of netSize is -- 1.3.6.1.4.1.9839.2.0.8 unitErrorChecksumCounterGroup OBJECT IDENTIFIER ::= { webGateInfo 8 } -- 1.3.6.1.4.1.9839.2.0.8.1 unit1-ErrorChecksumCounter OBJECT-TYPE SYNTAX Integer32 UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Error checksum counter of the unit having serial address 1. " ::= { unitErrorChecksumCounterGroup 1 } -- ... You will have how many unitX-ErrorChecksumCounter objects as the value of netSize is -- 1.3.6.1.4.1.9839.2.0.9 unitTimeoutCounterGroup OBJECT IDENTIFIER ::= { webGateInfo 9 } -- 1.3.6.1.4.1.9839.2.0.9.1 unit1-TimeoutCounter OBJECT-TYPE SYNTAX Integer32 UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Timeout counter of the unit having serial address 1. " ::= { unitTimeoutCounterGroup 1 } -- ... You will have how many unitX-TimeoutCounter objects as the value of netSize is -- 1.3.6.1.4.1.9839.2.0.10 unitOnLineStatusGroup OBJECT IDENTIFIER ::= { webGateInfo 10 } -- 1.3.6.1.4.1.9839.2.0.10.1 unit1-OnLineStatus OBJECT-TYPE SYNTAX Integer32 UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "On line status of the unit having serial address 1. " ::= { unitOnLineStatusGroup 1 } -- ... You will have how many unitX-OnLineStatus objects as the value of netSize is -- 1.3.6.1.4.1.9839.2.1 -- uchiller_cmpMIB OBJECT IDENTIFIER ::= { instruments 1 } -- 1.3.6.1.4.1.9839.2.1.1 digitalObjects OBJECT IDENTIFIER ::= { uchiller_cmpMIB 1 } -- 1.3.6.1.4.1.9839.2.1.1.1 est_inv OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Cooling - Heating" ::= { digitalObjects 1 } -- 1.3.6.1.4.1.9839.2.1.1.2 on_off_unita OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "On-Off if remote On/Off is disabled" ::= { digitalObjects 2 } -- 1.3.6.1.4.1.9839.2.1.1.5 allarme_hp OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "High pressure alarm" ::= { digitalObjects 5 } -- 1.3.6.1.4.1.9839.2.1.1.6 allarme_lp OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Low pressure alarm" ::= { digitalObjects 6 } -- 1.3.6.1.4.1.9839.2.1.1.8 all_flusso OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Flowmeter alarm" ::= { digitalObjects 8 } -- 1.3.6.1.4.1.9839.2.1.1.9 err_sonda_b3 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Probe b3 faulty or not connected" ::= { digitalObjects 9 } -- 1.3.6.1.4.1.9839.2.1.1.10 err_sonda_b2 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Probe b2 faulty or not connected" ::= { digitalObjects 10 } -- 1.3.6.1.4.1.9839.2.1.1.11 err_sonda_b1 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Probe b1 faulty or not connected" ::= { digitalObjects 11 } -- 1.3.6.1.4.1.9839.2.1.1.13 err_eeprom_s OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Faulty eeprom alarm" ::= { digitalObjects 13 } -- 1.3.6.1.4.1.9839.2.1.1.16 all_termin_off OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Alarm in the communic. with the remote terminal" ::= { digitalObjects 16 } -- 1.3.6.1.4.1.9839.2.1.1.17 sbrinamento_on OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Defrost in progress" ::= { digitalObjects 17 } -- 1.3.6.1.4.1.9839.2.1.1.18 all_sbrinamento OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Defrost timeout" ::= { digitalObjects 18 } -- 1.3.6.1.4.1.9839.2.1.1.19 all_antigelo OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Freezing alarm" ::= { digitalObjects 19 } -- 1.3.6.1.4.1.9839.2.1.1.20 all_agelo_sonda OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Low temperature alarm" ::= { digitalObjects 20 } -- 1.3.6.1.4.1.9839.2.1.1.21 all_sovratens OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Overvoltage alarm" ::= { digitalObjects 21 } -- 1.3.6.1.4.1.9839.2.1.1.22 all_sottotens OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Undervoltage alarm" ::= { digitalObjects 22 } -- 1.3.6.1.4.1.9839.2.1.1.25 stato_pompa OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Pump status" ::= { digitalObjects 25 } -- 1.3.6.1.4.1.9839.2.1.1.26 stato_compress OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Comp. 1 status" ::= { digitalObjects 26 } -- 1.3.6.1.4.1.9839.2.1.1.27 stato_resists OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Resist. status" ::= { digitalObjects 27 } -- 1.3.6.1.4.1.9839.2.1.1.28 stato_valvola OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Valve status" ::= { digitalObjects 28 } -- 1.3.6.1.4.1.9839.2.1.1.30 stato_ventils OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Fan status" ::= { digitalObjects 30 } -- 1.3.6.1.4.1.9839.2.1.1.40 unita_misura OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "Measurement Unit" DEFVAL { 0 } ::= { digitalObjects 40 } -- 1.3.6.1.4.1.9839.2.1.1.41 out_per_fan_f1 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "flags" MAX-ACCESS read-write STATUS current DESCRIPTION "Fans Output" DEFVAL { 0 } ::= { digitalObjects 41 } -- 1.3.6.1.4.1.9839.2.1.1.42 esecuz_sbrin_d1 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "Defrosting cycle / condensation antifreeze" DEFVAL { 1 } ::= { digitalObjects 42 } -- 1.3.6.1.4.1.9839.2.1.1.43 def_time_tmp_d2 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "Timed or temperature-based defrosting" DEFVAL { 0 } ::= { digitalObjects 43 } -- 1.3.6.1.4.1.9839.2.1.1.44 res_gelo_sbr_db OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "Antifreeze heaters activated while defrosting" DEFVAL { 0 } ::= { digitalObjects 44 } -- 1.3.6.1.4.1.9839.2.1.1.45 en_sonda_res_a6 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "Support heaters probe" DEFVAL { 0 } ::= { digitalObjects 45 } -- 1.3.6.1.4.1.9839.2.1.1.46 all_lp_sonda_p7 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "Low pressure alarm with pressure probes" DEFVAL { 0 } ::= { digitalObjects 46 } -- 1.3.6.1.4.1.9839.2.1.1.47 en_id_on_off_h7 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF digital input" DEFVAL { 0 } ::= { digitalObjects 47 } -- 1.3.6.1.4.1.9839.2.1.1.48 all_lp_comp_pa OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "Low pressure alarm selection" DEFVAL { 0 } ::= { digitalObjects 48 } -- 1.3.6.1.4.1.9839.2.1.1.49 en_set2_hc OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "Second set of param." DEFVAL { 0 } ::= { digitalObjects 49 } -- 1.3.6.1.4.1.9839.2.1.1.50 inv_est_inv_hd OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "Logic inversion cooling/heating" DEFVAL { 0 } ::= { digitalObjects 50 } -- 1.3.6.1.4.1.9839.2.1.1.51 sel_rele_all_hf OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "Alarm relay status without alarm condition" DEFVAL { 1 } ::= { digitalObjects 51 } -- 1.3.6.1.4.1.9839.2.1.1.55 ab_estate_inv_h6 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "Cooling/heating digital input with P8/P9 = 8, 9" DEFVAL { 0 } ::= { digitalObjects 55 } -- 1.3.6.1.4.1.9839.2.1.1.56 rotaz_compr_r5 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor rotation" DEFVAL { 3 } ::= { digitalObjects 56 } -- 1.3.6.1.4.1.9839.2.1.2 analogObjects OBJECT IDENTIFIER ::= { uchiller_cmpMIB 2 } -- 1.3.6.1.4.1.9839.2.1.2.1 sonda_b1 OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Inlet probe" ::= { analogObjects 1 } -- 1.3.6.1.4.1.9839.2.1.2.2 sonda_b2 OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Water temperaturte at evaporator output B2" ::= { analogObjects 2 } -- 1.3.6.1.4.1.9839.2.1.2.3 sonda_b3 OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Temperature/pressure defrosting B3" ::= { analogObjects 3 } -- 1.3.6.1.4.1.9839.2.1.2.5 i_scala_press OBJECT-TYPE SYNTAX Integer32 (0..32767) UNITS "bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Min. value current input" DEFVAL { 0 } ::= { analogObjects 5 } -- 1.3.6.1.4.1.9839.2.1.2.6 f_scala_press OBJECT-TYPE SYNTAX Integer32 (-32767..400) UNITS "bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Max value current input" DEFVAL { 300 } ::= { analogObjects 6 } -- 1.3.6.1.4.1.9839.2.1.2.7 calibra_b1 OBJECT-TYPE SYNTAX Integer32 (-120..120) UNITS "°C/°F x10" MAX-ACCESS read-only STATUS current DESCRIPTION "Probe B1 calibration" DEFVAL { 0 } ::= { analogObjects 7 } -- 1.3.6.1.4.1.9839.2.1.2.8 calibra_b2 OBJECT-TYPE SYNTAX Integer32 (-120..120) UNITS "°C/°F x10" MAX-ACCESS read-only STATUS current DESCRIPTION "Probe outlet B2 calibration" DEFVAL { 0 } ::= { analogObjects 8 } -- 1.3.6.1.4.1.9839.2.1.2.9 calibra_b3 OBJECT-TYPE SYNTAX Integer32 (-120..120) UNITS "°C/°F x10" MAX-ACCESS read-only STATUS current DESCRIPTION "Defrosting probe B3 calibration" DEFVAL { 0 } ::= { analogObjects 9 } -- 1.3.6.1.4.1.9839.2.1.2.10 setp_estate OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "°C/°F x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Cooling Set-Point" DEFVAL { 120 } ::= { analogObjects 10 } -- 1.3.6.1.4.1.9839.2.1.2.11 diff_estate OBJECT-TYPE SYNTAX Integer32 (3..199) UNITS "°C/°F x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Cooling differential" DEFVAL { 30 } ::= { analogObjects 11 } -- 1.3.6.1.4.1.9839.2.1.2.12 setp_inverno OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "°C/°F x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Heating set-point" DEFVAL { 400 } ::= { analogObjects 12 } -- 1.3.6.1.4.1.9839.2.1.2.13 diff_inverno OBJECT-TYPE SYNTAX Integer32 (3..199) UNITS "°C/°F x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Heating differential" DEFVAL { 30 } ::= { analogObjects 13 } -- 1.3.6.1.4.1.9839.2.1.2.14 min_set_est OBJECT-TYPE SYNTAX Integer32 (-400..32767) UNITS "°C/°F x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Min. Cooling set-point" DEFVAL { -400 } ::= { analogObjects 14 } -- 1.3.6.1.4.1.9839.2.1.2.15 max_set_est OBJECT-TYPE SYNTAX Integer32 (-32767..1990) UNITS "°C/°F x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Max. Cooling set-point" DEFVAL { 900 } ::= { analogObjects 15 } -- 1.3.6.1.4.1.9839.2.1.2.16 min_set_inv OBJECT-TYPE SYNTAX Integer32 (-400..32767) UNITS "°C/°F x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Min. Heating set-point" DEFVAL { -400 } ::= { analogObjects 16 } -- 1.3.6.1.4.1.9839.2.1.2.17 max_set_inv OBJECT-TYPE SYNTAX Integer32 (-32767..1990) UNITS "°C/°F x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Max. Heating set-point" DEFVAL { 900 } ::= { analogObjects 17 } -- 1.3.6.1.4.1.9839.2.1.2.18 tmin_vel_est_f5 OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "°C/°F bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Temperature value for min Cooling speed .Pressure" DEFVAL { 130 } ::= { analogObjects 18 } -- 1.3.6.1.4.1.9839.2.1.2.19 tmax_vel_est_f6 OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "°C/°F bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Temperature value for max Cooling speed. Pressure" DEFVAL { 160 } ::= { analogObjects 19 } -- 1.3.6.1.4.1.9839.2.1.2.20 tmin_vel_inv_f7 OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "°C/°F bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Temperature value for min Heating speed. Pressure" DEFVAL { 130 } ::= { analogObjects 20 } -- 1.3.6.1.4.1.9839.2.1.2.21 tmax_vel_inv_f8 OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "°C/°F bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Temperature value for max Heating speed.Pressure" DEFVAL { 90 } ::= { analogObjects 21 } -- 1.3.6.1.4.1.9839.2.1.2.22 toff_fan_est_f9 OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "°C/°F bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Temperature to turn OFF the fan in Cooling .Pressure" DEFVAL { 80 } ::= { analogObjects 22 } -- 1.3.6.1.4.1.9839.2.1.2.23 toff_fan_inv_fa OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "°C/°F bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Temperature to turn OFF the fan in Winter. Pressure" DEFVAL { 160 } ::= { analogObjects 23 } -- 1.3.6.1.4.1.9839.2.1.2.24 parametro_d3 OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "°C/°F bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Temperat./pressure starting the defrost.cycle" DEFVAL { 35 } ::= { analogObjects 24 } -- 1.3.6.1.4.1.9839.2.1.2.25 parametro_d4 OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "°C/°F bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "End-defrosting temperature/pressure" DEFVAL { 140 } ::= { analogObjects 25 } -- 1.3.6.1.4.1.9839.2.1.2.26 set_al_agelo_a1 OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "°C/°F x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Antifreeze" DEFVAL { 30 } ::= { analogObjects 26 } -- 1.3.6.1.4.1.9839.2.1.2.27 dif_al_agelo_a2 OBJECT-TYPE SYNTAX Integer32 (3..199) UNITS "°C/°F x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Differential for antifreeze/low ambient temperatur" DEFVAL { 50 } ::= { analogObjects 27 } -- 1.3.6.1.4.1.9839.2.1.2.28 set_res_gelo_a4 OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "°C/°F x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Setpoint for the activation of antifreeze supp." DEFVAL { 50 } ::= { analogObjects 28 } -- 1.3.6.1.4.1.9839.2.1.2.29 dif_res_gelo_a5 OBJECT-TYPE SYNTAX Integer32 (3..199) UNITS "°C/°F x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Antifreeze/Support heaters differential" DEFVAL { 10 } ::= { analogObjects 29 } -- 1.3.6.1.4.1.9839.2.1.2.30 lim_set_gelo_a7 OBJECT-TYPE SYNTAX Integer32 (-400..1220) UNITS "°C/°F x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Antifreeze-alarm set" DEFVAL { -400 } ::= { analogObjects 30 } -- 1.3.6.1.4.1.9839.2.1.2.31 set_res_risc_a8 OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "°C/°F x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Heating support-resistance set" DEFVAL { 250 } ::= { analogObjects 31 } -- 1.3.6.1.4.1.9839.2.1.2.32 dif_res_risc_a9 OBJECT-TYPE SYNTAX Integer32 (3..199) UNITS "°C/°F x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Heating support-resistance differential" DEFVAL { 30 } ::= { analogObjects 32 } -- 1.3.6.1.4.1.9839.2.1.2.33 set_all_at_pb OBJECT-TYPE SYNTAX Integer32 (-400..1990) UNITS "/d x10" MAX-ACCESS read-write STATUS current DESCRIPTION "High temperature alarm set" DEFVAL { 900 } ::= { analogObjects 33 } -- 1.3.6.1.4.1.9839.2.1.2.34 sonda_b4 OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Probe B4" ::= { analogObjects 34 } -- 1.3.6.1.4.1.9839.2.1.3 integerObjects OBJECT IDENTIFIER ::= { uchiller_cmpMIB 3 } -- 1.3.6.1.4.1.9839.2.1.3.1 velocita_vent OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Fan speed 0-100%" ::= { integerObjects 1 } -- 1.3.6.1.4.1.9839.2.1.3.6 filtro_digitale OBJECT-TYPE SYNTAX Integer32 (1..15) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Digital filter" DEFVAL { 4 } ::= { integerObjects 6 } -- 1.3.6.1.4.1.9839.2.1.3.8 tmin_on_comp_c1 OBJECT-TYPE SYNTAX Integer32 (0..150) UNITS "sec" MAX-ACCESS read-write STATUS current DESCRIPTION "Min. running time" DEFVAL { 60 } ::= { integerObjects 8 } -- 1.3.6.1.4.1.9839.2.1.3.9 tmin_sp_comp_c2 OBJECT-TYPE SYNTAX Integer32 (0..90) UNITS "10 sec" MAX-ACCESS read-write STATUS current DESCRIPTION "Min. stopping time" DEFVAL { 6 } ::= { integerObjects 9 } -- 1.3.6.1.4.1.9839.2.1.3.10 time_2_acc_c3 OBJECT-TYPE SYNTAX Integer32 (0..90) UNITS "10 sec" MAX-ACCESS read-write STATUS current DESCRIPTION "Time interval between 2 starts" DEFVAL { 36 } ::= { integerObjects 10 } -- 1.3.6.1.4.1.9839.2.1.3.11 rit_on_comp_c6 OBJECT-TYPE SYNTAX Integer32 (0..150) UNITS "sec" MAX-ACCESS read-write STATUS current DESCRIPTION "Delay at start-up" DEFVAL { 0 } ::= { integerObjects 11 } -- 1.3.6.1.4.1.9839.2.1.3.12 rit_c_on_pmp_c7 OBJECT-TYPE SYNTAX Integer32 (0..150) UNITS "sec" MAX-ACCESS read-write STATUS current DESCRIPTION "Delay in switching on compressor after switch. On" DEFVAL { 20 } ::= { integerObjects 12 } -- 1.3.6.1.4.1.9839.2.1.3.13 off_p_off_v_c8 OBJECT-TYPE SYNTAX Integer32 (0..150) UNITS "min" MAX-ACCESS read-write STATUS current DESCRIPTION "Delay in switching off compress. After switc.off" DEFVAL { 20 } ::= { integerObjects 13 } -- 1.3.6.1.4.1.9839.2.1.3.14 contaore_c1_c9 OBJECT-TYPE SYNTAX Integer32 (0..19900) UNITS "hours" MAX-ACCESS read-only STATUS current DESCRIPTION "Hour counter comp. 1" DEFVAL { 0 } ::= { integerObjects 14 } -- 1.3.6.1.4.1.9839.2.1.3.15 max_ore_comp_cb OBJECT-TYPE SYNTAX Integer32 (0..100) UNITS "100 hours" MAX-ACCESS read-write STATUS current DESCRIPTION "Timer threshold during normal operation" DEFVAL { 0 } ::= { integerObjects 15 } -- 1.3.6.1.4.1.9839.2.1.3.16 ore_pmp_vent_cc OBJECT-TYPE SYNTAX Integer32 (0..19900) UNITS "hours" MAX-ACCESS read-only STATUS current DESCRIPTION "Pump/inlet fan timer" DEFVAL { 0 } ::= { integerObjects 16 } -- 1.3.6.1.4.1.9839.2.1.3.17 modo_vent_f2 OBJECT-TYPE SYNTAX Integer32 (0..3) UNITS "flags" MAX-ACCESS read-write STATUS current DESCRIPTION "Operating logic of the fans" DEFVAL { 0 } ::= { integerObjects 17 } -- 1.3.6.1.4.1.9839.2.1.3.18 min_volt_f3 OBJECT-TYPE SYNTAX Integer32 (0..32767) UNITS "step" MAX-ACCESS read-write STATUS current DESCRIPTION "Minimum tension threshold for Triac" DEFVAL { 35 } ::= { integerObjects 18 } -- 1.3.6.1.4.1.9839.2.1.3.19 max_volt_f4 OBJECT-TYPE SYNTAX Integer32 (-32767..100) UNITS "step" MAX-ACCESS read-write STATUS current DESCRIPTION "Max.tension threshold for Triac" DEFVAL { 75 } ::= { integerObjects 19 } -- 1.3.6.1.4.1.9839.2.1.3.20 t_spunto_v_fb OBJECT-TYPE SYNTAX Integer32 (0..99) UNITS "sec" MAX-ACCESS read-write STATUS current DESCRIPTION "Starting time of fans" DEFVAL { 4 } ::= { integerObjects 20 } -- 1.3.6.1.4.1.9839.2.1.3.21 t_imp_triac_fc OBJECT-TYPE SYNTAX Integer32 (0..15) UNITS "msec" MAX-ACCESS read-write STATUS current DESCRIPTION "Triac impulse duration" DEFVAL { 2 } ::= { integerObjects 21 } -- 1.3.6.1.4.1.9839.2.1.3.22 t_min_on_def_d5 OBJECT-TYPE SYNTAX Integer32 (10..150) UNITS "sec" MAX-ACCESS read-write STATUS current DESCRIPTION "Minimum time interval before starting a defr. Cycl" DEFVAL { 10 } ::= { integerObjects 22 } -- 1.3.6.1.4.1.9839.2.1.3.23 t_min_def_d6 OBJECT-TYPE SYNTAX Integer32 (0..150) UNITS "sec" MAX-ACCESS read-write STATUS current DESCRIPTION "Min. duration of a defrosting cycle" DEFVAL { 0 } ::= { integerObjects 23 } -- 1.3.6.1.4.1.9839.2.1.3.24 t_max_def_d7 OBJECT-TYPE SYNTAX Integer32 (1..15) UNITS "min" MAX-ACCESS read-write STATUS current DESCRIPTION "Max. duration of a defrosting cycle" DEFVAL { 5 } ::= { integerObjects 24 } -- 1.3.6.1.4.1.9839.2.1.3.25 rit_tra_2def_d8 OBJECT-TYPE SYNTAX Integer32 (10..150) UNITS "min" MAX-ACCESS read-write STATUS current DESCRIPTION "Time-delay between 2 defrosting" DEFVAL { 30 } ::= { integerObjects 25 } -- 1.3.6.1.4.1.9839.2.1.3.26 wait_on_def_dc OBJECT-TYPE SYNTAX Integer32 (0..3) UNITS "min" MAX-ACCESS read-write STATUS current DESCRIPTION "Delay before defrosting" DEFVAL { 0 } ::= { integerObjects 26 } -- 1.3.6.1.4.1.9839.2.1.3.27 wait_end_def_dd OBJECT-TYPE SYNTAX Integer32 (0..3) UNITS "min" MAX-ACCESS read-write STATUS current DESCRIPTION "Delay after defrosting" DEFVAL { 0 } ::= { integerObjects 27 } -- 1.3.6.1.4.1.9839.2.1.3.28 rit_all_ag_a3 OBJECT-TYPE SYNTAX Integer32 (0..150) UNITS "sec" MAX-ACCESS read-write STATUS current DESCRIPTION "Time to bypass the antfreeze/low amb. Temp. allarm" DEFVAL { 0 } ::= { integerObjects 28 } -- 1.3.6.1.4.1.9839.2.1.3.29 r_al_on_flux_p1 OBJECT-TYPE SYNTAX Integer32 (0..150) UNITS "sec" MAX-ACCESS read-write STATUS current DESCRIPTION "Flowmeter down delayed when starting the pump" DEFVAL { 20 } ::= { integerObjects 29 } -- 1.3.6.1.4.1.9839.2.1.3.30 r_al_rg_flux_p2 OBJECT-TYPE SYNTAX Integer32 (0..90) UNITS "sec" MAX-ACCESS read-write STATUS current DESCRIPTION "Flowswitch alarm delayed during normal operating" DEFVAL { 5 } ::= { integerObjects 30 } -- 1.3.6.1.4.1.9839.2.1.3.31 rit_all_lp_p3 OBJECT-TYPE SYNTAX Integer32 (0..199) UNITS "sec" MAX-ACCESS read-write STATUS current DESCRIPTION "Low pressure alarm delayed at compr. start-up" DEFVAL { 40 } ::= { integerObjects 31 } -- 1.3.6.1.4.1.9839.2.1.3.32 t_buzzer_p4 OBJECT-TYPE SYNTAX Integer32 (0..15) UNITS "min" MAX-ACCESS read-write STATUS current DESCRIPTION "Buzzer ON" DEFVAL { 0 } ::= { integerObjects 32 } -- 1.3.6.1.4.1.9839.2.1.3.33 riprist_all_p5 OBJECT-TYPE SYNTAX Integer32 (0..4) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "Reset of alarms" DEFVAL { 0 } ::= { integerObjects 33 } -- 1.3.6.1.4.1.9839.2.1.3.34 selez_id1_p8 OBJECT-TYPE SYNTAX Integer32 (0..7) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "Sel. of the digital input" DEFVAL { 0 } ::= { integerObjects 34 } -- 1.3.6.1.4.1.9839.2.1.3.35 selez_id2_p9 OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Sel. of the digital input n.2" ::= { integerObjects 35 } -- 1.3.6.1.4.1.9839.2.1.3.36 modello_mac_h1 OBJECT-TYPE SYNTAX Integer32 (0..8) UNITS "flag" MAX-ACCESS read-only STATUS current DESCRIPTION "Unit model" DEFVAL { 2 } ::= { integerObjects 36 } -- 1.3.6.1.4.1.9839.2.1.3.37 modo_pmp_vnt_h5 OBJECT-TYPE SYNTAX Integer32 (0..2) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "Operating logic of the Pump/Inlet fan" DEFVAL { 1 } ::= { integerObjects 37 } -- 1.3.6.1.4.1.9839.2.1.3.38 blocca_tasti_h9 OBJECT-TYPE SYNTAX Integer32 (0..3) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "Keyboard lock-up" DEFVAL { 1 } ::= { integerObjects 38 } -- 1.3.6.1.4.1.9839.2.1.3.39 seradd OBJECT-TYPE SYNTAX Integer32 (1..199) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Serial address" DEFVAL { 1 } ::= { integerObjects 39 } -- 1.3.6.1.4.1.9839.2.1.3.40 passw_telec_hb OBJECT-TYPE SYNTAX Integer32 (0..15) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Infrared remote unit password" DEFVAL { 0 } ::= { integerObjects 40 } -- 1.3.6.1.4.1.9839.2.1.3.41 valv_inv_ch_he OBJECT-TYPE SYNTAX Integer32 (0..2) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "Valve status cooling" DEFVAL { 0 } ::= { integerObjects 41 } -- 1.3.6.1.4.1.9839.2.1.3.42 numero_term_h8 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "Number of terminals" DEFVAL { 0 } ::= { integerObjects 42 } -- 1.3.6.1.4.1.9839.2.1.3.43 high_temp_all_pc OBJECT-TYPE SYNTAX Integer32 (0..150) UNITS "min" MAX-ACCESS read-write STATUS current DESCRIPTION "High temperature alarm delayed at start-up" DEFVAL { 30 } ::= { integerObjects 43 } -- 1.3.6.1.4.1.9839.2.1.3.51 versione_sw_hg OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "SW Release" DEFVAL { 13 } ::= { integerObjects 51 } -- 1.3.6.1.4.1.9839.2.1.3.52 rit_acc_comp OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "sec" MAX-ACCESS read-only STATUS current DESCRIPTION "Start delay between the two compressors" ::= { integerObjects 52 } -- 1.3.6.1.4.1.9839.2.1.3.53 rit_spegn_comp OBJECT-TYPE SYNTAX Integer32 (0..15) UNITS "sec" MAX-ACCESS read-only STATUS current DESCRIPTION "Stop delay between the two compressors" DEFVAL { 0 } ::= { integerObjects 53 } -- 1.3.6.1.4.1.9839.2.1.3.56 tempo_acc_pompa OBJECT-TYPE SYNTAX Integer32 (1..150) UNITS "min" MAX-ACCESS read-only STATUS current DESCRIPTION "Minimum time between two pump starts" DEFVAL { 30 } ::= { integerObjects 56 } END -- -- CAREL-uchiller_cmp.MIB --