Observium_CE/mibs/carel/CAREL-uchiller-MIB

1385 lines
50 KiB
Plaintext
Raw Permalink Blame History

--
-- CAREL-uchiller.MIB
-- MIB generated by CAREL
-- Friday, 14 March 2003
--
CAREL-uchiller-MIB DEFINITIONS ::= BEGIN
IMPORTS
OBJECT-GROUP
FROM SNMPv2-CONF
sysContact, sysName, sysLocation
FROM SNMPv2-MIB
enterprises, MODULE-IDENTITY
FROM SNMPv2-SMI;
uchillerMIB MODULE-IDENTITY
LAST-UPDATED "200303141725Z" -- March 14, 2003 at 17:25 GMT
ORGANIZATION "CAREL SpA"
CONTACT-INFO
"
Simone Ravazzolo
Carel SpA
Via dell'Industria, 11
35020 Brugine (PD) Italy
Tel: +39 049 9716611
E-mail: simone.ravazzolo@carel.com
"
DESCRIPTION
"This is the MIB module for the uchiller device."
::= { instruments 1 }
--
-- Node definitions
--
-- 1.3.6.1.4.1.9839
carel OBJECT IDENTIFIER ::= { enterprises 9839 }
-- 1.3.6.1.4.1.9839.1
systm OBJECT IDENTIFIER ::= { carel 1 }
-- 1.3.6.1.4.1.9839.1.1
agentRelease OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Release of the Agent."
::= { systm 1 }
-- 1.3.6.1.4.1.9839.1.2
agentCode OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Code of the Agent. 1=WebGate"
::= { systm 2 }
-- 1.3.6.1.4.1.9839.2
instruments OBJECT IDENTIFIER ::= { carel 2 }
-- 1.3.6.1.4.1.9839.2.0
webGateInfo OBJECT IDENTIFIER ::= { instruments 0 }
-- 1.3.6.1.4.1.9839.2.0.1
agentParameters OBJECT IDENTIFIER ::= { webGateInfo 1 }
-- 1.3.6.1.4.1.9839.2.0.1.1
netSize OBJECT-TYPE
SYNTAX Integer32 (1..16)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Network size. It corresponds to the number of units connected to the WebGate. "
::= { agentParameters 1 }
-- 1.3.6.1.4.1.9839.2.0.1.2
baudRate OBJECT-TYPE
SYNTAX Integer32 (1200 | 2400 |4800 |9600 | 19200)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Baudrate of the Carel network. "
::= { agentParameters 2 }
-- 1.3.6.1.4.1.9839.2.0.2
unitTypeGroup OBJECT IDENTIFIER ::= { webGateInfo 2 }
-- 1.3.6.1.4.1.9839.2.0.2.1
unit1-Type OBJECT-TYPE
SYNTAX DisplayString
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of the unit having serial address 1. "
::= { unitTypeGroup 1 }
-- ... You will have how many unitX-Type objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.0.3
unitCodeGroup OBJECT IDENTIFIER ::= { webGateInfo 3 }
-- 1.3.6.1.4.1.9839.2.0.3.1
unit1-Code OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Code of the unit having serial address 1. "
::= { unitCodeGroup 1 }
-- ... You will have how many unitX-Code objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.0.4
unitSoftwareReleaseGroup OBJECT IDENTIFIER ::= { webGateInfo 4 }
-- 1.3.6.1.4.1.9839.2.0.3.1
unit1-SoftwareRelease OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Software release of the unit having serial address 1. "
::= { unitSoftwareReleaseGroup 1 }
-- ... You will have how many unitX-SoftwareRelease objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.0.5
unitMinSoftwareReleaseGroup OBJECT IDENTIFIER ::= { webGateInfo 5 }
-- 1.3.6.1.4.1.9839.2.0.5.1
unit1-MinSoftwareRelease OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Minimum software release of the unit having serial address 1. "
::= { unitMinSoftwareReleaseGroup 1 }
-- ... You will have how many unitX-MinSoftwareRelease objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.0.6
unitMaxSoftwareReleaseGroup OBJECT IDENTIFIER ::= { webGateInfo 6 }
-- 1.3.6.1.4.1.9839.2.0.6.1
unit1-MaxSoftwareRelease OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Maximum software release of the unit having serial address 1. "
::= { unitMaxSoftwareReleaseGroup 1 }
-- ... You will have how many unitX-MaxSoftwareRelease objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.0.7
unitNoAnswerCounterGroup OBJECT IDENTIFIER ::= { webGateInfo 7 }
-- 1.3.6.1.4.1.9839.2.0.7.1
unit1-NoAnswerCounter OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "No answer counter of the unit having serial address 1. "
::= { unitNoAnswerCounterGroup 1 }
-- ... You will have how many unitX-NoAnswerCounter objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.0.8
unitErrorChecksumCounterGroup OBJECT IDENTIFIER ::= { webGateInfo 8 }
-- 1.3.6.1.4.1.9839.2.0.8.1
unit1-ErrorChecksumCounter OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Error checksum counter of the unit having serial address 1. "
::= { unitErrorChecksumCounterGroup 1 }
-- ... You will have how many unitX-ErrorChecksumCounter objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.0.9
unitTimeoutCounterGroup OBJECT IDENTIFIER ::= { webGateInfo 9 }
-- 1.3.6.1.4.1.9839.2.0.9.1
unit1-TimeoutCounter OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timeout counter of the unit having serial address 1. "
::= { unitTimeoutCounterGroup 1 }
-- ... You will have how many unitX-TimeoutCounter objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.0.10
unitOnLineStatusGroup OBJECT IDENTIFIER ::= { webGateInfo 10 }
-- 1.3.6.1.4.1.9839.2.0.10.1
unit1-OnLineStatus OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "On line status of the unit having serial address 1. "
::= { unitOnLineStatusGroup 1 }
-- ... You will have how many unitX-OnLineStatus objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.1
-- uchillerMIB OBJECT IDENTIFIER ::= { instruments 1 }
-- 1.3.6.1.4.1.9839.2.1.1
digitalObjects OBJECT IDENTIFIER ::= { uchillerMIB 1 }
-- 1.3.6.1.4.1.9839.2.1.1.1
res_antig_c1 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "C1 resistence"
::= { digitalObjects 1 }
-- 1.3.6.1.4.1.9839.2.1.1.3
valv_inv_c1 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "C1 valve"
::= { digitalObjects 3 }
-- 1.3.6.1.4.1.9839.2.1.1.5
allarme OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm state"
::= { digitalObjects 5 }
-- 1.3.6.1.4.1.9839.2.1.1.6
antifreeze_resist_c2 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "State antifreeze resistence (circuit n.2)"
DEFVAL { 0 }
::= { digitalObjects 6 }
-- 1.3.6.1.4.1.9839.2.1.1.7
compressore_c2 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of compressors (circuit n.2)"
DEFVAL { 0 }
::= { digitalObjects 7 }
-- 1.3.6.1.4.1.9839.2.1.1.8
valv_inv_c2 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of evaporations (circuit n.2)"
DEFVAL { 0 }
::= { digitalObjects 8 }
-- 1.3.6.1.4.1.9839.2.1.1.9
err_sonda_s1 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Probe s1 faulty or not connected"
::= { digitalObjects 9 }
-- 1.3.6.1.4.1.9839.2.1.1.10
err_sonda_s2 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Probe s2 faulty or not connected"
::= { digitalObjects 10 }
-- 1.3.6.1.4.1.9839.2.1.1.11
err_sonda_s3 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Probe s3 faulty or not connected"
::= { digitalObjects 11 }
-- 1.3.6.1.4.1.9839.2.1.1.12
err_sonda_s4 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Probe s4 faulty or not connected"
::= { digitalObjects 12 }
-- 1.3.6.1.4.1.9839.2.1.1.13
err_sonda_s5 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Probe s5 faulty or not connected"
::= { digitalObjects 13 }
-- 1.3.6.1.4.1.9839.2.1.1.14
err_eeprom OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Eeprom memory error"
::= { digitalObjects 14 }
-- 1.3.6.1.4.1.9839.2.1.1.15
freq_rete OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Zero crossing alarm error"
::= { digitalObjects 15 }
-- 1.3.6.1.4.1.9839.2.1.1.16
allarme_terminale_disconnesso OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Disconnect terminal alarm"
::= { digitalObjects 16 }
-- 1.3.6.1.4.1.9839.2.1.1.17
defrost_st_1 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Executing C1 defrost"
::= { digitalObjects 17 }
-- 1.3.6.1.4.1.9839.2.1.1.19
defrost_st_2 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Executing C2 defrost"
::= { digitalObjects 19 }
-- 1.3.6.1.4.1.9839.2.1.1.20
all_h_press_c1 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "High pressure alarm circuit 1"
::= { digitalObjects 20 }
-- 1.3.6.1.4.1.9839.2.1.1.21
all_l_press_c1 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Low pressure alarm circuit 1"
::= { digitalObjects 21 }
-- 1.3.6.1.4.1.9839.2.1.1.22
all_term_compc1 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compressor circuit 1 overload"
::= { digitalObjects 22 }
-- 1.3.6.1.4.1.9839.2.1.1.23
all_term_fanc1 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Fan circuit 1 overload"
::= { digitalObjects 23 }
-- 1.3.6.1.4.1.9839.2.1.1.24
all_flusso OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Circuit 1 flowswitch alarm"
::= { digitalObjects 24 }
-- 1.3.6.1.4.1.9839.2.1.1.26
est_inv OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "<22>C/<2F>F"
MAX-ACCESS read-only
STATUS current
DESCRIPTION ""
DEFVAL { 0 }
::= { digitalObjects 26 }
-- 1.3.6.1.4.1.9839.2.1.1.27
all_h_press_c2 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "High pressure alarm circuit 2"
::= { digitalObjects 27 }
-- 1.3.6.1.4.1.9839.2.1.1.28
all_l_press_c2 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Low pressure alarm circuit 2"
::= { digitalObjects 28 }
-- 1.3.6.1.4.1.9839.2.1.1.29
all_term_compc2 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compressor circuit 2 overload"
::= { digitalObjects 29 }
-- 1.3.6.1.4.1.9839.2.1.1.30
all_term_fanc2 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Fan circuit 2 overload"
::= { digitalObjects 30 }
-- 1.3.6.1.4.1.9839.2.1.1.32
rich_manut_c2 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Maintenance compressor 2 required"
::= { digitalObjects 32 }
-- 1.3.6.1.4.1.9839.2.1.1.33
all_antigelo_c1 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Circuit 1 antifreeze alarm"
::= { digitalObjects 33 }
-- 1.3.6.1.4.1.9839.2.1.1.34
all_antigelo_c2 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Circuit 2 antifreeze alarm"
::= { digitalObjects 34 }
-- 1.3.6.1.4.1.9839.2.1.1.35
all_defrost_c1 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Circuit 1 defrost termination alarm"
::= { digitalObjects 35 }
-- 1.3.6.1.4.1.9839.2.1.1.36
all_defrost_c2 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Circuit 2 defrost termination alarm"
::= { digitalObjects 36 }
-- 1.3.6.1.4.1.9839.2.1.1.37
tsonda_inev__1 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Type of probe at evaporator inlet, B1"
DEFVAL { 1 }
::= { digitalObjects 37 }
-- 1.3.6.1.4.1.9839.2.1.1.38
tsonda_outev__2 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Type of probe at 1st and 2nd evap. outlet, B2,B4"
DEFVAL { 1 }
::= { digitalObjects 38 }
-- 1.3.6.1.4.1.9839.2.1.1.40
out_per_fan_f1 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Fans output"
DEFVAL { 0 }
::= { digitalObjects 40 }
-- 1.3.6.1.4.1.9839.2.1.1.41
defr_antig_d1 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "min"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Defrosting cycle / condensation antifreeze"
DEFVAL { 0 }
::= { digitalObjects 41 }
-- 1.3.6.1.4.1.9839.2.1.1.43
num_fan_h2 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of ventilating circuits"
DEFVAL { 1 }
::= { digitalObjects 43 }
-- 1.3.6.1.4.1.9839.2.1.1.44
num_evap_h3 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Number of evaporators"
DEFVAL { 0 }
::= { digitalObjects 44 }
-- 1.3.6.1.4.1.9839.2.1.1.45
compr_parz_h4 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Capacity-controllid/compressor in parallele mode."
DEFVAL { 0 }
::= { digitalObjects 45 }
-- 1.3.6.1.4.1.9839.2.1.1.46
en_din_e_i_h6 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Cooling/heating digital input with P8/P9 = 8, 9"
DEFVAL { 0 }
::= { digitalObjects 46 }
-- 1.3.6.1.4.1.9839.2.1.1.47
en_din_a_s_h7 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "ON/OFF digital input"
DEFVAL { 0 }
::= { digitalObjects 47 }
-- 1.3.6.1.4.1.9839.2.1.1.48
num_termin_h8 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Number of terminals"
::= { digitalObjects 48 }
-- 1.3.6.1.4.1.9839.2.1.1.49
num_compressori OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Second set of param."
DEFVAL { 0 }
::= { digitalObjects 49 }
-- 1.3.6.1.4.1.9839.2.1.1.50
comp_rot_r5 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compressor rotation"
DEFVAL { 0 }
::= { digitalObjects 50 }
-- 1.3.6.1.4.1.9839.2.1.1.51
def_ext_da OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Defrost end by external contact"
DEFVAL { 1 }
::= { digitalObjects 51 }
-- 1.3.6.1.4.1.9839.2.1.1.52
anti_def_db OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Antifreeze heaters activated while defrosting"
DEFVAL { 0 }
::= { digitalObjects 52 }
-- 1.3.6.1.4.1.9839.2.1.1.53
end_def_de OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "End defrost.with two gas circuits and 1 rem. Fan"
DEFVAL { 0 }
::= { digitalObjects 53 }
-- 1.3.6.1.4.1.9839.2.1.1.54
sup_probe_a6 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Support heaters probe"
DEFVAL { 0 }
::= { digitalObjects 54 }
-- 1.3.6.1.4.1.9839.2.1.1.55
reset_alarm_p5 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Reset of allarm"
DEFVAL { 0 }
::= { digitalObjects 55 }
-- 1.3.6.1.4.1.9839.2.1.1.56
set_2_param_p6 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "2nd set of param."
DEFVAL { 0 }
::= { digitalObjects 56 }
-- 1.3.6.1.4.1.9839.2.1.1.57
low_press_alarm_p7 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Low pressure alarm with pressure probes"
DEFVAL { 0 }
::= { digitalObjects 57 }
-- 1.3.6.1.4.1.9839.2.1.2
analogObjects OBJECT IDENTIFIER ::= { uchillerMIB 2 }
-- 1.3.6.1.4.1.9839.2.1.2.1
sonda_s1 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "<22>C x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Room or Inlet Evap.Temp."
::= { analogObjects 1 }
-- 1.3.6.1.4.1.9839.2.1.2.2
sonda_s2_r6 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Water temper. at evaporator output circuit n.1, B2"
::= { analogObjects 2 }
-- 1.3.6.1.4.1.9839.2.1.2.3
sonda_s3_r7 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Water temper. at evaporator output circuit n. 2, B4"
::= { analogObjects 3 }
-- 1.3.6.1.4.1.9839.2.1.2.4
sonda_s4_r8 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "bar x10"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Temperature/pressure defrosting 1,B3"
::= { analogObjects 4 }
-- 1.3.6.1.4.1.9839.2.1.2.5
sonda_s5_r9 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "bar x10"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Temperature/pressure defrosting 2,B5"
DEFVAL { 0 }
::= { analogObjects 5 }
-- 1.3.6.1.4.1.9839.2.1.2.6
calibra_s1__6 OBJECT-TYPE
SYNTAX Integer32 (-60..60)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Probe inlet B1 calibation"
DEFVAL { 0 }
::= { analogObjects 6 }
-- 1.3.6.1.4.1.9839.2.1.2.7
calibra_s2__7 OBJECT-TYPE
SYNTAX Integer32 (-60..60)
UNITS "<22>C x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Probe outlet B2 calibration"
DEFVAL { 300 }
::= { analogObjects 7 }
-- 1.3.6.1.4.1.9839.2.1.2.8
calibra_s3__8 OBJECT-TYPE
SYNTAX Integer32 (-60..60)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Defrosting probe B3 calibration"
DEFVAL { 0 }
::= { analogObjects 8 }
-- 1.3.6.1.4.1.9839.2.1.2.9
calibra_s4__9 OBJECT-TYPE
SYNTAX Integer32 (-60..60)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Calibration for elaboration outlet waterprobe at circuit no.2, B4"
DEFVAL { 0 }
::= { analogObjects 9 }
-- 1.3.6.1.4.1.9839.2.1.2.10
calibra_s5__a OBJECT-TYPE
SYNTAX Integer32 (-60..90)
UNITS "<22>C/<2F>F bar x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Condensing probe circuit 2 B5 calibration"
DEFVAL { 0 }
::= { analogObjects 10 }
-- 1.3.6.1.4.1.9839.2.1.2.11
setp_est_r1 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Cooling Set-point"
DEFVAL { 400 }
::= { analogObjects 11 }
-- 1.3.6.1.4.1.9839.2.1.2.12
differ_est_r2 OBJECT-TYPE
SYNTAX Integer32 (1..198)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Cooling differential"
DEFVAL { 30 }
::= { analogObjects 12 }
-- 1.3.6.1.4.1.9839.2.1.2.13
setp_inv_r3 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Heating set-point"
DEFVAL { 30 }
::= { analogObjects 13 }
-- 1.3.6.1.4.1.9839.2.1.2.14
differ_inv_r4 OBJECT-TYPE
SYNTAX Integer32 (1..198)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Heating differential"
DEFVAL { 30 }
::= { analogObjects 14 }
-- 1.3.6.1.4.1.9839.2.1.2.15
set_min_est_ra OBJECT-TYPE
SYNTAX Integer32 (-400..32767)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Min. Cooling set-point"
DEFVAL { -400 }
::= { analogObjects 15 }
-- 1.3.6.1.4.1.9839.2.1.2.16
set_max_est_rb OBJECT-TYPE
SYNTAX Integer32 (-32767..1940)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Max. Cooling set-point"
DEFVAL { 900 }
::= { analogObjects 16 }
-- 1.3.6.1.4.1.9839.2.1.2.17
set_min_inv_rc OBJECT-TYPE
SYNTAX Integer32 (-400..32767)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Min. Heating set-point"
DEFVAL { -400 }
::= { analogObjects 17 }
-- 1.3.6.1.4.1.9839.2.1.2.18
set_max_inv_rd OBJECT-TYPE
SYNTAX Integer32 (-32767..1940)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Max. Heating set-point"
DEFVAL { 900 }
::= { analogObjects 18 }
-- 1.3.6.1.4.1.9839.2.1.2.19
tmin_vel_est_f5 OBJECT-TYPE
SYNTAX Integer32 (0..32767)
UNITS "bar x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Temp.value for min Cooling speed .Pressure"
DEFVAL { 130 }
::= { analogObjects 19 }
-- 1.3.6.1.4.1.9839.2.1.2.20
tmax_vel_est_f6 OBJECT-TYPE
SYNTAX Integer32 (-32767..500)
UNITS "bar x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Temperature value for max Cooling speed. Pressure"
DEFVAL { 160 }
::= { analogObjects 20 }
-- 1.3.6.1.4.1.9839.2.1.2.21
tmin_vel_inv_f7 OBJECT-TYPE
SYNTAX Integer32 (-32767..500)
UNITS "bar x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Temperature value for min Heating speed. pressure"
DEFVAL { 130 }
::= { analogObjects 21 }
-- 1.3.6.1.4.1.9839.2.1.2.22
tmax_vel_inv_f8 OBJECT-TYPE
SYNTAX Integer32 (0..32767)
UNITS "bar x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Temperature value for max Heating speed. pressure"
DEFVAL { 90 }
::= { analogObjects 22 }
-- 1.3.6.1.4.1.9839.2.1.2.23
toff_fan_est_f9 OBJECT-TYPE
SYNTAX Integer32 (0..32767)
UNITS "bar x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Temp.to turn OFF the fan in Cooling .Pressure"
DEFVAL { 80 }
::= { analogObjects 23 }
-- 1.3.6.1.4.1.9839.2.1.2.24
toff_fan_inv_fa OBJECT-TYPE
SYNTAX Integer32 (-32767..500)
UNITS "bar x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Temp.to turn OFF the fan in Winter. Pressure"
DEFVAL { 160 }
::= { analogObjects 24 }
-- 1.3.6.1.4.1.9839.2.1.2.25
tp_start_def_d3 OBJECT-TYPE
SYNTAX Integer32 (-300..32767)
UNITS "bar x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Temperat./pressure starting the defrost.cycle"
DEFVAL { 35 }
::= { analogObjects 25 }
-- 1.3.6.1.4.1.9839.2.1.2.26
tp_end_def_d4 OBJECT-TYPE
SYNTAX Integer32 (-32767..500)
UNITS "bar x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "End-defrosting temperature/pressure"
DEFVAL { 140 }
::= { analogObjects 26 }
-- 1.3.6.1.4.1.9839.2.1.2.27
set_al_agelo_a1 OBJECT-TYPE
SYNTAX Integer32 (-300..32767)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Antifreeze / Low ambient temp alarm set-point"
DEFVAL { 30 }
::= { analogObjects 27 }
-- 1.3.6.1.4.1.9839.2.1.2.28
dif_al_agelo_a2 OBJECT-TYPE
SYNTAX Integer32 (1..198)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Differential for antifreeze / low ambient temperature"
DEFVAL { 50 }
::= { analogObjects 28 }
-- 1.3.6.1.4.1.9839.2.1.2.29
set_res_gelo_a4 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Setpoint for the activation of antifreeze supp. He"
DEFVAL { 50 }
::= { analogObjects 29 }
-- 1.3.6.1.4.1.9839.2.1.2.30
dif_res_gelo_a5 OBJECT-TYPE
SYNTAX Integer32 (1..1220)
UNITS "<22>C/<2F>F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Set point for the activation of antifreeze"
DEFVAL { 10 }
::= { analogObjects 30 }
-- 1.3.6.1.4.1.9839.2.1.3
integerObjects OBJECT IDENTIFIER ::= { uchillerMIB 3 }
-- 1.3.6.1.4.1.9839.2.1.3.1
tipo_sonda__3 OBJECT-TYPE
SYNTAX Integer32 (0..2)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Type of condensation probe"
DEFVAL { 1 }
::= { integerObjects 1 }
-- 1.3.6.1.4.1.9839.2.1.3.2
min_in_corr__4 OBJECT-TYPE
SYNTAX Integer32 (0..32767)
UNITS "bar"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Min. value current input"
DEFVAL { 0 }
::= { integerObjects 2 }
-- 1.3.6.1.4.1.9839.2.1.3.3
max_in_corr__5 OBJECT-TYPE
SYNTAX Integer32 (-32767..35)
UNITS "bar"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Max value current input"
DEFVAL { 35 }
::= { integerObjects 3 }
-- 1.3.6.1.4.1.9839.2.1.3.4
filtro_dig__b OBJECT-TYPE
SYNTAX Integer32 (1..15)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Digital filter"
DEFVAL { 4 }
::= { integerObjects 4 }
-- 1.3.6.1.4.1.9839.2.1.3.5
limitaz_in__c OBJECT-TYPE
SYNTAX Integer32 (1..15)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Input limitation"
DEFVAL { 8 }
::= { integerObjects 5 }
-- 1.3.6.1.4.1.9839.2.1.3.6
tmin_on_comp_c1 OBJECT-TYPE
SYNTAX Integer32 (0..150)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "c1: Minimum ON time"
DEFVAL { 4 }
::= { integerObjects 6 }
-- 1.3.6.1.4.1.9839.2.1.3.8
time_2_acc_c3 OBJECT-TYPE
SYNTAX Integer32 (0..90)
UNITS "10 sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Time-interv.between two successive on routine"
DEFVAL { 36 }
::= { integerObjects 8 }
-- 1.3.6.1.4.1.9839.2.1.3.10
rit_off_2c_c5 OBJECT-TYPE
SYNTAX Integer32 (0..15)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Stop delay between the two compressors"
DEFVAL { 0 }
::= { integerObjects 10 }
-- 1.3.6.1.4.1.9839.2.1.3.11
rit_on_comp_c6 OBJECT-TYPE
SYNTAX Integer32 (0..150)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Delay at start-up"
DEFVAL { 0 }
::= { integerObjects 11 }
-- 1.3.6.1.4.1.9839.2.1.3.12
rit_c_on_pmp_c7 OBJECT-TYPE
SYNTAX Integer32 (0..150)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Delay in switching on compressor after switchi. On`"
DEFVAL { 20 }
::= { integerObjects 12 }
-- 1.3.6.1.4.1.9839.2.1.3.13
off_p_off_c_c8 OBJECT-TYPE
SYNTAX Integer32 (0..150)
UNITS "min"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Delay in switching off compress. After switc.off"
DEFVAL { 20 }
::= { integerObjects 13 }
-- 1.3.6.1.4.1.9839.2.1.3.14
ore_comp1_c9 OBJECT-TYPE
SYNTAX Integer32 (0..19900)
UNITS "hours"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Hour counter comp. 1"
DEFVAL { 0 }
::= { integerObjects 14 }
-- 1.3.6.1.4.1.9839.2.1.3.17
ore_comp2_ca OBJECT-TYPE
SYNTAX Integer32 (0..19900)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Timer compressor"
DEFVAL { 0 }
::= { integerObjects 17 }
-- 1.3.6.1.4.1.9839.2.1.3.18
max_ore_comp_cb OBJECT-TYPE
SYNTAX Integer32 (0..100)
UNITS "step"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Timer threshold for maintenance alarm"
DEFVAL { 0 }
::= { integerObjects 18 }
-- 1.3.6.1.4.1.9839.2.1.3.19
ore_pompa_cc OBJECT-TYPE
SYNTAX Integer32 (0..19900)
UNITS "ore"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Pump/inlet fan timer"
DEFVAL { 0 }
::= { integerObjects 19 }
-- 1.3.6.1.4.1.9839.2.1.3.20
rit_c_f_cond_cd OBJECT-TYPE
SYNTAX Integer32 (0..15)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Starting time of fans"
DEFVAL { 0 }
::= { integerObjects 20 }
-- 1.3.6.1.4.1.9839.2.1.3.21
modo_fan_f2 OBJECT-TYPE
SYNTAX Integer32 (0..15)
UNITS "msec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Triac impulse duration"
DEFVAL { 2 }
::= { integerObjects 21 }
-- 1.3.6.1.4.1.9839.2.1.3.22
min_volt_f3 OBJECT-TYPE
SYNTAX Integer32 (10..150)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Minimum time interval before starting a defr. cycle"
DEFVAL { 10 }
::= { integerObjects 22 }
-- 1.3.6.1.4.1.9839.2.1.3.23
max_volt_f4 OBJECT-TYPE
SYNTAX Integer32 (0..150)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION ""
DEFVAL { 0 }
::= { integerObjects 23 }
-- 1.3.6.1.4.1.9839.2.1.3.24
t_spunto_f_fb OBJECT-TYPE
SYNTAX Integer32 (1..15)
UNITS "min"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Defrost max duration"
DEFVAL { 5 }
::= { integerObjects 24 }
-- 1.3.6.1.4.1.9839.2.1.3.25
t_min_on_def_d5 OBJECT-TYPE
SYNTAX Integer32 (10..150)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Min time to start a defrosting cycle"
DEFVAL { 10 }
::= { integerObjects 25 }
-- 1.3.6.1.4.1.9839.2.1.3.26
t_min_def_d6 OBJECT-TYPE
SYNTAX Integer32 (0..150)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Min. duration of a defrosting cycle"
DEFVAL { 0 }
::= { integerObjects 26 }
-- 1.3.6.1.4.1.9839.2.1.3.27
t_max_def_d7 OBJECT-TYPE
SYNTAX Integer32 (1..15)
UNITS "min"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Max. duration of a defrosting cycle"
DEFVAL { 5 }
::= { integerObjects 27 }
-- 1.3.6.1.4.1.9839.2.1.3.28
rit_2def_1c_d8 OBJECT-TYPE
SYNTAX Integer32 (10..150)
UNITS "min"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Min time-delay between 2defrosting cycle"
DEFVAL { 30 }
::= { integerObjects 28 }
-- 1.3.6.1.4.1.9839.2.1.3.29
rit_def_2c_d9 OBJECT-TYPE
SYNTAX Integer32 (0..150)
UNITS "min"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Defrosting time interval between the 2 circuits"
DEFVAL { 10 }
::= { integerObjects 29 }
-- 1.3.6.1.4.1.9839.2.1.3.30
rit_all_ag_a3 OBJECT-TYPE
SYNTAX Integer32 (0..90)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Bypass time for antifreeze alarm/Low ambient temp"
DEFVAL { 5 }
::= { integerObjects 30 }
-- 1.3.6.1.4.1.9839.2.1.3.31
rall_on_flux_p1 OBJECT-TYPE
SYNTAX Integer32 (0..150)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Flowswitch alarm delayed when starting the punp"
DEFVAL { 20 }
::= { integerObjects 31 }
-- 1.3.6.1.4.1.9839.2.1.3.32
rall_rg_flux_p2 OBJECT-TYPE
SYNTAX Integer32 (0..90)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Flowswitch alarm delayed during normal operating"
DEFVAL { 5 }
::= { integerObjects 32 }
-- 1.3.6.1.4.1.9839.2.1.3.33
rit_all_bp_p3 OBJECT-TYPE
SYNTAX Integer32 (0..150)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Low pressure alarm delayed at compr. start-up"
DEFVAL { 40 }
::= { integerObjects 33 }
-- 1.3.6.1.4.1.9839.2.1.3.34
buzzer_p4 OBJECT-TYPE
SYNTAX Integer32 (0..15)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Buzzer ON"
DEFVAL { 0 }
::= { integerObjects 34 }
-- 1.3.6.1.4.1.9839.2.1.3.35
modello_h1 OBJECT-TYPE
SYNTAX Integer32 (0..6)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Unit model"
DEFVAL { 2 }
::= { integerObjects 35 }
-- 1.3.6.1.4.1.9839.2.1.3.36
modo_pompa_h5 OBJECT-TYPE
SYNTAX Integer32 (0..2)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Working logic of pump/inlet fan"
DEFVAL { 1 }
::= { integerObjects 36 }
-- 1.3.6.1.4.1.9839.2.1.3.37
blocca_tasti_h9 OBJECT-TYPE
SYNTAX Integer32 (0..3)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Keyboard key-up"
DEFVAL { 1 }
::= { integerObjects 37 }
-- 1.3.6.1.4.1.9839.2.1.3.39
delay_def_dc OBJECT-TYPE
SYNTAX Integer32 (0..3)
UNITS "min"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Delay before defrosting"
DEFVAL { 0 }
::= { integerObjects 39 }
-- 1.3.6.1.4.1.9839.2.1.3.40
time_wait_def_dd OBJECT-TYPE
SYNTAX Integer32 (0..3)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Delay after defrosting"
DEFVAL { 0 }
::= { integerObjects 40 }
-- 1.3.6.1.4.1.9839.2.1.3.41
valve_status OBJECT-TYPE
SYNTAX Integer32 (0..2)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Valve status cooling"
DEFVAL { 0 }
::= { integerObjects 41 }
-- 1.3.6.1.4.1.9839.2.1.3.50
machine_config OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Machine configuration"
::= { integerObjects 50 }
-- 1.3.6.1.4.1.9839.2.1.3.51
swrel OBJECT-TYPE
SYNTAX Integer32 (0..255)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "SW Release"
DEFVAL { 1 }
::= { integerObjects 51 }
END
--