-- -- CAREL-uchiller.MIB -- MIB generated by CAREL -- Friday, 14 March 2003 -- CAREL-uchiller-MIB DEFINITIONS ::= BEGIN IMPORTS OBJECT-GROUP FROM SNMPv2-CONF sysContact, sysName, sysLocation FROM SNMPv2-MIB enterprises, MODULE-IDENTITY FROM SNMPv2-SMI; uchillerMIB MODULE-IDENTITY LAST-UPDATED "200303141725Z" -- March 14, 2003 at 17:25 GMT ORGANIZATION "CAREL SpA" CONTACT-INFO " Simone Ravazzolo Carel SpA Via dell'Industria, 11 35020 Brugine (PD) Italy Tel: +39 049 9716611 E-mail: simone.ravazzolo@carel.com " DESCRIPTION "This is the MIB module for the uchiller device." ::= { instruments 1 } -- -- Node definitions -- -- 1.3.6.1.4.1.9839 carel OBJECT IDENTIFIER ::= { enterprises 9839 } -- 1.3.6.1.4.1.9839.1 systm OBJECT IDENTIFIER ::= { carel 1 } -- 1.3.6.1.4.1.9839.1.1 agentRelease OBJECT-TYPE SYNTAX Integer32 UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Release of the Agent." ::= { systm 1 } -- 1.3.6.1.4.1.9839.1.2 agentCode OBJECT-TYPE SYNTAX Integer32 UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Code of the Agent. 1=WebGate" ::= { systm 2 } -- 1.3.6.1.4.1.9839.2 instruments OBJECT IDENTIFIER ::= { carel 2 } -- 1.3.6.1.4.1.9839.2.0 webGateInfo OBJECT IDENTIFIER ::= { instruments 0 } -- 1.3.6.1.4.1.9839.2.0.1 agentParameters OBJECT IDENTIFIER ::= { webGateInfo 1 } -- 1.3.6.1.4.1.9839.2.0.1.1 netSize OBJECT-TYPE SYNTAX Integer32 (1..16) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Network size. It corresponds to the number of units connected to the WebGate. " ::= { agentParameters 1 } -- 1.3.6.1.4.1.9839.2.0.1.2 baudRate OBJECT-TYPE SYNTAX Integer32 (1200 | 2400 |4800 |9600 | 19200) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Baudrate of the Carel network. " ::= { agentParameters 2 } -- 1.3.6.1.4.1.9839.2.0.2 unitTypeGroup OBJECT IDENTIFIER ::= { webGateInfo 2 } -- 1.3.6.1.4.1.9839.2.0.2.1 unit1-Type OBJECT-TYPE SYNTAX DisplayString UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Type of the unit having serial address 1. " ::= { unitTypeGroup 1 } -- ... You will have how many unitX-Type objects as the value of netSize is -- 1.3.6.1.4.1.9839.2.0.3 unitCodeGroup OBJECT IDENTIFIER ::= { webGateInfo 3 } -- 1.3.6.1.4.1.9839.2.0.3.1 unit1-Code OBJECT-TYPE SYNTAX Integer32 UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Code of the unit having serial address 1. " ::= { unitCodeGroup 1 } -- ... You will have how many unitX-Code objects as the value of netSize is -- 1.3.6.1.4.1.9839.2.0.4 unitSoftwareReleaseGroup OBJECT IDENTIFIER ::= { webGateInfo 4 } -- 1.3.6.1.4.1.9839.2.0.3.1 unit1-SoftwareRelease OBJECT-TYPE SYNTAX Integer32 UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Software release of the unit having serial address 1. " ::= { unitSoftwareReleaseGroup 1 } -- ... You will have how many unitX-SoftwareRelease objects as the value of netSize is -- 1.3.6.1.4.1.9839.2.0.5 unitMinSoftwareReleaseGroup OBJECT IDENTIFIER ::= { webGateInfo 5 } -- 1.3.6.1.4.1.9839.2.0.5.1 unit1-MinSoftwareRelease OBJECT-TYPE SYNTAX Integer32 UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Minimum software release of the unit having serial address 1. " ::= { unitMinSoftwareReleaseGroup 1 } -- ... You will have how many unitX-MinSoftwareRelease objects as the value of netSize is -- 1.3.6.1.4.1.9839.2.0.6 unitMaxSoftwareReleaseGroup OBJECT IDENTIFIER ::= { webGateInfo 6 } -- 1.3.6.1.4.1.9839.2.0.6.1 unit1-MaxSoftwareRelease OBJECT-TYPE SYNTAX Integer32 UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Maximum software release of the unit having serial address 1. " ::= { unitMaxSoftwareReleaseGroup 1 } -- ... You will have how many unitX-MaxSoftwareRelease objects as the value of netSize is -- 1.3.6.1.4.1.9839.2.0.7 unitNoAnswerCounterGroup OBJECT IDENTIFIER ::= { webGateInfo 7 } -- 1.3.6.1.4.1.9839.2.0.7.1 unit1-NoAnswerCounter OBJECT-TYPE SYNTAX Integer32 UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "No answer counter of the unit having serial address 1. " ::= { unitNoAnswerCounterGroup 1 } -- ... You will have how many unitX-NoAnswerCounter objects as the value of netSize is -- 1.3.6.1.4.1.9839.2.0.8 unitErrorChecksumCounterGroup OBJECT IDENTIFIER ::= { webGateInfo 8 } -- 1.3.6.1.4.1.9839.2.0.8.1 unit1-ErrorChecksumCounter OBJECT-TYPE SYNTAX Integer32 UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Error checksum counter of the unit having serial address 1. " ::= { unitErrorChecksumCounterGroup 1 } -- ... You will have how many unitX-ErrorChecksumCounter objects as the value of netSize is -- 1.3.6.1.4.1.9839.2.0.9 unitTimeoutCounterGroup OBJECT IDENTIFIER ::= { webGateInfo 9 } -- 1.3.6.1.4.1.9839.2.0.9.1 unit1-TimeoutCounter OBJECT-TYPE SYNTAX Integer32 UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Timeout counter of the unit having serial address 1. " ::= { unitTimeoutCounterGroup 1 } -- ... You will have how many unitX-TimeoutCounter objects as the value of netSize is -- 1.3.6.1.4.1.9839.2.0.10 unitOnLineStatusGroup OBJECT IDENTIFIER ::= { webGateInfo 10 } -- 1.3.6.1.4.1.9839.2.0.10.1 unit1-OnLineStatus OBJECT-TYPE SYNTAX Integer32 UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "On line status of the unit having serial address 1. " ::= { unitOnLineStatusGroup 1 } -- ... You will have how many unitX-OnLineStatus objects as the value of netSize is -- 1.3.6.1.4.1.9839.2.1 -- uchillerMIB OBJECT IDENTIFIER ::= { instruments 1 } -- 1.3.6.1.4.1.9839.2.1.1 digitalObjects OBJECT IDENTIFIER ::= { uchillerMIB 1 } -- 1.3.6.1.4.1.9839.2.1.1.1 res_antig_c1 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "C1 resistence" ::= { digitalObjects 1 } -- 1.3.6.1.4.1.9839.2.1.1.3 valv_inv_c1 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "C1 valve" ::= { digitalObjects 3 } -- 1.3.6.1.4.1.9839.2.1.1.5 allarme OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Alarm state" ::= { digitalObjects 5 } -- 1.3.6.1.4.1.9839.2.1.1.6 antifreeze_resist_c2 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "flag" MAX-ACCESS read-only STATUS current DESCRIPTION "State antifreeze resistence (circuit n.2)" DEFVAL { 0 } ::= { digitalObjects 6 } -- 1.3.6.1.4.1.9839.2.1.1.7 compressore_c2 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "flag" MAX-ACCESS read-only STATUS current DESCRIPTION "Number of compressors (circuit n.2)" DEFVAL { 0 } ::= { digitalObjects 7 } -- 1.3.6.1.4.1.9839.2.1.1.8 valv_inv_c2 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "flag" MAX-ACCESS read-only STATUS current DESCRIPTION "Number of evaporations (circuit n.2)" DEFVAL { 0 } ::= { digitalObjects 8 } -- 1.3.6.1.4.1.9839.2.1.1.9 err_sonda_s1 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Probe s1 faulty or not connected" ::= { digitalObjects 9 } -- 1.3.6.1.4.1.9839.2.1.1.10 err_sonda_s2 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Probe s2 faulty or not connected" ::= { digitalObjects 10 } -- 1.3.6.1.4.1.9839.2.1.1.11 err_sonda_s3 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Probe s3 faulty or not connected" ::= { digitalObjects 11 } -- 1.3.6.1.4.1.9839.2.1.1.12 err_sonda_s4 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Probe s4 faulty or not connected" ::= { digitalObjects 12 } -- 1.3.6.1.4.1.9839.2.1.1.13 err_sonda_s5 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Probe s5 faulty or not connected" ::= { digitalObjects 13 } -- 1.3.6.1.4.1.9839.2.1.1.14 err_eeprom OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Eeprom memory error" ::= { digitalObjects 14 } -- 1.3.6.1.4.1.9839.2.1.1.15 freq_rete OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Zero crossing alarm error" ::= { digitalObjects 15 } -- 1.3.6.1.4.1.9839.2.1.1.16 allarme_terminale_disconnesso OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Disconnect terminal alarm" ::= { digitalObjects 16 } -- 1.3.6.1.4.1.9839.2.1.1.17 defrost_st_1 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Executing C1 defrost" ::= { digitalObjects 17 } -- 1.3.6.1.4.1.9839.2.1.1.19 defrost_st_2 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Executing C2 defrost" ::= { digitalObjects 19 } -- 1.3.6.1.4.1.9839.2.1.1.20 all_h_press_c1 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "High pressure alarm circuit 1" ::= { digitalObjects 20 } -- 1.3.6.1.4.1.9839.2.1.1.21 all_l_press_c1 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Low pressure alarm circuit 1" ::= { digitalObjects 21 } -- 1.3.6.1.4.1.9839.2.1.1.22 all_term_compc1 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor circuit 1 overload" ::= { digitalObjects 22 } -- 1.3.6.1.4.1.9839.2.1.1.23 all_term_fanc1 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Fan circuit 1 overload" ::= { digitalObjects 23 } -- 1.3.6.1.4.1.9839.2.1.1.24 all_flusso OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Circuit 1 flowswitch alarm" ::= { digitalObjects 24 } -- 1.3.6.1.4.1.9839.2.1.1.26 est_inv OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "°C/°F" MAX-ACCESS read-only STATUS current DESCRIPTION "" DEFVAL { 0 } ::= { digitalObjects 26 } -- 1.3.6.1.4.1.9839.2.1.1.27 all_h_press_c2 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "High pressure alarm circuit 2" ::= { digitalObjects 27 } -- 1.3.6.1.4.1.9839.2.1.1.28 all_l_press_c2 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Low pressure alarm circuit 2" ::= { digitalObjects 28 } -- 1.3.6.1.4.1.9839.2.1.1.29 all_term_compc2 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor circuit 2 overload" ::= { digitalObjects 29 } -- 1.3.6.1.4.1.9839.2.1.1.30 all_term_fanc2 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Fan circuit 2 overload" ::= { digitalObjects 30 } -- 1.3.6.1.4.1.9839.2.1.1.32 rich_manut_c2 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Maintenance compressor 2 required" ::= { digitalObjects 32 } -- 1.3.6.1.4.1.9839.2.1.1.33 all_antigelo_c1 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Circuit 1 antifreeze alarm" ::= { digitalObjects 33 } -- 1.3.6.1.4.1.9839.2.1.1.34 all_antigelo_c2 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Circuit 2 antifreeze alarm" ::= { digitalObjects 34 } -- 1.3.6.1.4.1.9839.2.1.1.35 all_defrost_c1 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Circuit 1 defrost termination alarm" ::= { digitalObjects 35 } -- 1.3.6.1.4.1.9839.2.1.1.36 all_defrost_c2 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Circuit 2 defrost termination alarm" ::= { digitalObjects 36 } -- 1.3.6.1.4.1.9839.2.1.1.37 tsonda_inev__1 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "Type of probe at evaporator inlet, B1" DEFVAL { 1 } ::= { digitalObjects 37 } -- 1.3.6.1.4.1.9839.2.1.1.38 tsonda_outev__2 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "Type of probe at 1st and 2nd evap. outlet, B2,B4" DEFVAL { 1 } ::= { digitalObjects 38 } -- 1.3.6.1.4.1.9839.2.1.1.40 out_per_fan_f1 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Fans output" DEFVAL { 0 } ::= { digitalObjects 40 } -- 1.3.6.1.4.1.9839.2.1.1.41 defr_antig_d1 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "min" MAX-ACCESS read-write STATUS current DESCRIPTION "Defrosting cycle / condensation antifreeze" DEFVAL { 0 } ::= { digitalObjects 41 } -- 1.3.6.1.4.1.9839.2.1.1.43 num_fan_h2 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "flag" MAX-ACCESS read-only STATUS current DESCRIPTION "Number of ventilating circuits" DEFVAL { 1 } ::= { digitalObjects 43 } -- 1.3.6.1.4.1.9839.2.1.1.44 num_evap_h3 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Number of evaporators" DEFVAL { 0 } ::= { digitalObjects 44 } -- 1.3.6.1.4.1.9839.2.1.1.45 compr_parz_h4 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "Capacity-controllid/compressor in parallele mode." DEFVAL { 0 } ::= { digitalObjects 45 } -- 1.3.6.1.4.1.9839.2.1.1.46 en_din_e_i_h6 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Cooling/heating digital input with P8/P9 = 8, 9" DEFVAL { 0 } ::= { digitalObjects 46 } -- 1.3.6.1.4.1.9839.2.1.1.47 en_din_a_s_h7 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF digital input" DEFVAL { 0 } ::= { digitalObjects 47 } -- 1.3.6.1.4.1.9839.2.1.1.48 num_termin_h8 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "Number of terminals" ::= { digitalObjects 48 } -- 1.3.6.1.4.1.9839.2.1.1.49 num_compressori OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "Second set of param." DEFVAL { 0 } ::= { digitalObjects 49 } -- 1.3.6.1.4.1.9839.2.1.1.50 comp_rot_r5 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "Compressor rotation" DEFVAL { 0 } ::= { digitalObjects 50 } -- 1.3.6.1.4.1.9839.2.1.1.51 def_ext_da OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "Defrost end by external contact" DEFVAL { 1 } ::= { digitalObjects 51 } -- 1.3.6.1.4.1.9839.2.1.1.52 anti_def_db OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "Antifreeze heaters activated while defrosting" DEFVAL { 0 } ::= { digitalObjects 52 } -- 1.3.6.1.4.1.9839.2.1.1.53 end_def_de OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "End defrost.with two gas circuits and 1 rem. Fan" DEFVAL { 0 } ::= { digitalObjects 53 } -- 1.3.6.1.4.1.9839.2.1.1.54 sup_probe_a6 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "Support heaters probe" DEFVAL { 0 } ::= { digitalObjects 54 } -- 1.3.6.1.4.1.9839.2.1.1.55 reset_alarm_p5 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "Reset of allarm" DEFVAL { 0 } ::= { digitalObjects 55 } -- 1.3.6.1.4.1.9839.2.1.1.56 set_2_param_p6 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "2nd set of param." DEFVAL { 0 } ::= { digitalObjects 56 } -- 1.3.6.1.4.1.9839.2.1.1.57 low_press_alarm_p7 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "flag" MAX-ACCESS read-only STATUS current DESCRIPTION "Low pressure alarm with pressure probes" DEFVAL { 0 } ::= { digitalObjects 57 } -- 1.3.6.1.4.1.9839.2.1.2 analogObjects OBJECT IDENTIFIER ::= { uchillerMIB 2 } -- 1.3.6.1.4.1.9839.2.1.2.1 sonda_s1 OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "°C x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Room or Inlet Evap.Temp." ::= { analogObjects 1 } -- 1.3.6.1.4.1.9839.2.1.2.2 sonda_s2_r6 OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "°C/°F x10" MAX-ACCESS read-only STATUS current DESCRIPTION "Water temper. at evaporator output circuit n.1, B2" ::= { analogObjects 2 } -- 1.3.6.1.4.1.9839.2.1.2.3 sonda_s3_r7 OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "°C/°F x10" MAX-ACCESS read-only STATUS current DESCRIPTION "Water temper. at evaporator output circuit n. 2, B4" ::= { analogObjects 3 } -- 1.3.6.1.4.1.9839.2.1.2.4 sonda_s4_r8 OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "bar x10" MAX-ACCESS read-only STATUS current DESCRIPTION "Temperature/pressure defrosting 1,B3" ::= { analogObjects 4 } -- 1.3.6.1.4.1.9839.2.1.2.5 sonda_s5_r9 OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "bar x10" MAX-ACCESS read-only STATUS current DESCRIPTION "Temperature/pressure defrosting 2,B5" DEFVAL { 0 } ::= { analogObjects 5 } -- 1.3.6.1.4.1.9839.2.1.2.6 calibra_s1__6 OBJECT-TYPE SYNTAX Integer32 (-60..60) UNITS "°C/°F x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Probe inlet B1 calibation" DEFVAL { 0 } ::= { analogObjects 6 } -- 1.3.6.1.4.1.9839.2.1.2.7 calibra_s2__7 OBJECT-TYPE SYNTAX Integer32 (-60..60) UNITS "°C x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Probe outlet B2 calibration" DEFVAL { 300 } ::= { analogObjects 7 } -- 1.3.6.1.4.1.9839.2.1.2.8 calibra_s3__8 OBJECT-TYPE SYNTAX Integer32 (-60..60) UNITS "°C/°F x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Defrosting probe B3 calibration" DEFVAL { 0 } ::= { analogObjects 8 } -- 1.3.6.1.4.1.9839.2.1.2.9 calibra_s4__9 OBJECT-TYPE SYNTAX Integer32 (-60..60) UNITS "°C/°F x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Calibration for elaboration outlet waterprobe at circuit no.2, B4" DEFVAL { 0 } ::= { analogObjects 9 } -- 1.3.6.1.4.1.9839.2.1.2.10 calibra_s5__a OBJECT-TYPE SYNTAX Integer32 (-60..90) UNITS "°C/°F bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Condensing probe circuit 2 B5 calibration" DEFVAL { 0 } ::= { analogObjects 10 } -- 1.3.6.1.4.1.9839.2.1.2.11 setp_est_r1 OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "°C/°F x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Cooling Set-point" DEFVAL { 400 } ::= { analogObjects 11 } -- 1.3.6.1.4.1.9839.2.1.2.12 differ_est_r2 OBJECT-TYPE SYNTAX Integer32 (1..198) UNITS "°C/°F x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Cooling differential" DEFVAL { 30 } ::= { analogObjects 12 } -- 1.3.6.1.4.1.9839.2.1.2.13 setp_inv_r3 OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "°C/°F x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Heating set-point" DEFVAL { 30 } ::= { analogObjects 13 } -- 1.3.6.1.4.1.9839.2.1.2.14 differ_inv_r4 OBJECT-TYPE SYNTAX Integer32 (1..198) UNITS "°C/°F x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Heating differential" DEFVAL { 30 } ::= { analogObjects 14 } -- 1.3.6.1.4.1.9839.2.1.2.15 set_min_est_ra OBJECT-TYPE SYNTAX Integer32 (-400..32767) UNITS "°C/°F x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Min. Cooling set-point" DEFVAL { -400 } ::= { analogObjects 15 } -- 1.3.6.1.4.1.9839.2.1.2.16 set_max_est_rb OBJECT-TYPE SYNTAX Integer32 (-32767..1940) UNITS "°C/°F x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Max. Cooling set-point" DEFVAL { 900 } ::= { analogObjects 16 } -- 1.3.6.1.4.1.9839.2.1.2.17 set_min_inv_rc OBJECT-TYPE SYNTAX Integer32 (-400..32767) UNITS "°C/°F x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Min. Heating set-point" DEFVAL { -400 } ::= { analogObjects 17 } -- 1.3.6.1.4.1.9839.2.1.2.18 set_max_inv_rd OBJECT-TYPE SYNTAX Integer32 (-32767..1940) UNITS "°C/°F x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Max. Heating set-point" DEFVAL { 900 } ::= { analogObjects 18 } -- 1.3.6.1.4.1.9839.2.1.2.19 tmin_vel_est_f5 OBJECT-TYPE SYNTAX Integer32 (0..32767) UNITS "bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Temp.value for min Cooling speed .Pressure" DEFVAL { 130 } ::= { analogObjects 19 } -- 1.3.6.1.4.1.9839.2.1.2.20 tmax_vel_est_f6 OBJECT-TYPE SYNTAX Integer32 (-32767..500) UNITS "bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Temperature value for max Cooling speed. Pressure" DEFVAL { 160 } ::= { analogObjects 20 } -- 1.3.6.1.4.1.9839.2.1.2.21 tmin_vel_inv_f7 OBJECT-TYPE SYNTAX Integer32 (-32767..500) UNITS "bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Temperature value for min Heating speed. pressure" DEFVAL { 130 } ::= { analogObjects 21 } -- 1.3.6.1.4.1.9839.2.1.2.22 tmax_vel_inv_f8 OBJECT-TYPE SYNTAX Integer32 (0..32767) UNITS "bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Temperature value for max Heating speed. pressure" DEFVAL { 90 } ::= { analogObjects 22 } -- 1.3.6.1.4.1.9839.2.1.2.23 toff_fan_est_f9 OBJECT-TYPE SYNTAX Integer32 (0..32767) UNITS "bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Temp.to turn OFF the fan in Cooling .Pressure" DEFVAL { 80 } ::= { analogObjects 23 } -- 1.3.6.1.4.1.9839.2.1.2.24 toff_fan_inv_fa OBJECT-TYPE SYNTAX Integer32 (-32767..500) UNITS "bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Temp.to turn OFF the fan in Winter. Pressure" DEFVAL { 160 } ::= { analogObjects 24 } -- 1.3.6.1.4.1.9839.2.1.2.25 tp_start_def_d3 OBJECT-TYPE SYNTAX Integer32 (-300..32767) UNITS "bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Temperat./pressure starting the defrost.cycle" DEFVAL { 35 } ::= { analogObjects 25 } -- 1.3.6.1.4.1.9839.2.1.2.26 tp_end_def_d4 OBJECT-TYPE SYNTAX Integer32 (-32767..500) UNITS "bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "End-defrosting temperature/pressure" DEFVAL { 140 } ::= { analogObjects 26 } -- 1.3.6.1.4.1.9839.2.1.2.27 set_al_agelo_a1 OBJECT-TYPE SYNTAX Integer32 (-300..32767) UNITS "°C/°F x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Antifreeze / Low ambient temp alarm set-point" DEFVAL { 30 } ::= { analogObjects 27 } -- 1.3.6.1.4.1.9839.2.1.2.28 dif_al_agelo_a2 OBJECT-TYPE SYNTAX Integer32 (1..198) UNITS "°C/°F x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Differential for antifreeze / low ambient temperature" DEFVAL { 50 } ::= { analogObjects 28 } -- 1.3.6.1.4.1.9839.2.1.2.29 set_res_gelo_a4 OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "°C/°F x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Setpoint for the activation of antifreeze supp. He" DEFVAL { 50 } ::= { analogObjects 29 } -- 1.3.6.1.4.1.9839.2.1.2.30 dif_res_gelo_a5 OBJECT-TYPE SYNTAX Integer32 (1..1220) UNITS "°C/°F x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Set point for the activation of antifreeze" DEFVAL { 10 } ::= { analogObjects 30 } -- 1.3.6.1.4.1.9839.2.1.3 integerObjects OBJECT IDENTIFIER ::= { uchillerMIB 3 } -- 1.3.6.1.4.1.9839.2.1.3.1 tipo_sonda__3 OBJECT-TYPE SYNTAX Integer32 (0..2) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "Type of condensation probe" DEFVAL { 1 } ::= { integerObjects 1 } -- 1.3.6.1.4.1.9839.2.1.3.2 min_in_corr__4 OBJECT-TYPE SYNTAX Integer32 (0..32767) UNITS "bar" MAX-ACCESS read-write STATUS current DESCRIPTION "Min. value current input" DEFVAL { 0 } ::= { integerObjects 2 } -- 1.3.6.1.4.1.9839.2.1.3.3 max_in_corr__5 OBJECT-TYPE SYNTAX Integer32 (-32767..35) UNITS "bar" MAX-ACCESS read-write STATUS current DESCRIPTION "Max value current input" DEFVAL { 35 } ::= { integerObjects 3 } -- 1.3.6.1.4.1.9839.2.1.3.4 filtro_dig__b OBJECT-TYPE SYNTAX Integer32 (1..15) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Digital filter" DEFVAL { 4 } ::= { integerObjects 4 } -- 1.3.6.1.4.1.9839.2.1.3.5 limitaz_in__c OBJECT-TYPE SYNTAX Integer32 (1..15) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Input limitation" DEFVAL { 8 } ::= { integerObjects 5 } -- 1.3.6.1.4.1.9839.2.1.3.6 tmin_on_comp_c1 OBJECT-TYPE SYNTAX Integer32 (0..150) UNITS "sec" MAX-ACCESS read-write STATUS current DESCRIPTION "c1: Minimum ON time" DEFVAL { 4 } ::= { integerObjects 6 } -- 1.3.6.1.4.1.9839.2.1.3.8 time_2_acc_c3 OBJECT-TYPE SYNTAX Integer32 (0..90) UNITS "10 sec" MAX-ACCESS read-write STATUS current DESCRIPTION "Time-interv.between two successive on routine" DEFVAL { 36 } ::= { integerObjects 8 } -- 1.3.6.1.4.1.9839.2.1.3.10 rit_off_2c_c5 OBJECT-TYPE SYNTAX Integer32 (0..15) UNITS "sec" MAX-ACCESS read-write STATUS current DESCRIPTION "Stop delay between the two compressors" DEFVAL { 0 } ::= { integerObjects 10 } -- 1.3.6.1.4.1.9839.2.1.3.11 rit_on_comp_c6 OBJECT-TYPE SYNTAX Integer32 (0..150) UNITS "sec" MAX-ACCESS read-write STATUS current DESCRIPTION "Delay at start-up" DEFVAL { 0 } ::= { integerObjects 11 } -- 1.3.6.1.4.1.9839.2.1.3.12 rit_c_on_pmp_c7 OBJECT-TYPE SYNTAX Integer32 (0..150) UNITS "sec" MAX-ACCESS read-write STATUS current DESCRIPTION "Delay in switching on compressor after switchi. On`" DEFVAL { 20 } ::= { integerObjects 12 } -- 1.3.6.1.4.1.9839.2.1.3.13 off_p_off_c_c8 OBJECT-TYPE SYNTAX Integer32 (0..150) UNITS "min" MAX-ACCESS read-write STATUS current DESCRIPTION "Delay in switching off compress. After switc.off" DEFVAL { 20 } ::= { integerObjects 13 } -- 1.3.6.1.4.1.9839.2.1.3.14 ore_comp1_c9 OBJECT-TYPE SYNTAX Integer32 (0..19900) UNITS "hours" MAX-ACCESS read-write STATUS current DESCRIPTION "Hour counter comp. 1" DEFVAL { 0 } ::= { integerObjects 14 } -- 1.3.6.1.4.1.9839.2.1.3.17 ore_comp2_ca OBJECT-TYPE SYNTAX Integer32 (0..19900) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Timer compressor" DEFVAL { 0 } ::= { integerObjects 17 } -- 1.3.6.1.4.1.9839.2.1.3.18 max_ore_comp_cb OBJECT-TYPE SYNTAX Integer32 (0..100) UNITS "step" MAX-ACCESS read-write STATUS current DESCRIPTION "Timer threshold for maintenance alarm" DEFVAL { 0 } ::= { integerObjects 18 } -- 1.3.6.1.4.1.9839.2.1.3.19 ore_pompa_cc OBJECT-TYPE SYNTAX Integer32 (0..19900) UNITS "ore" MAX-ACCESS read-write STATUS current DESCRIPTION "Pump/inlet fan timer" DEFVAL { 0 } ::= { integerObjects 19 } -- 1.3.6.1.4.1.9839.2.1.3.20 rit_c_f_cond_cd OBJECT-TYPE SYNTAX Integer32 (0..15) UNITS "sec" MAX-ACCESS read-write STATUS current DESCRIPTION "Starting time of fans" DEFVAL { 0 } ::= { integerObjects 20 } -- 1.3.6.1.4.1.9839.2.1.3.21 modo_fan_f2 OBJECT-TYPE SYNTAX Integer32 (0..15) UNITS "msec" MAX-ACCESS read-write STATUS current DESCRIPTION "Triac impulse duration" DEFVAL { 2 } ::= { integerObjects 21 } -- 1.3.6.1.4.1.9839.2.1.3.22 min_volt_f3 OBJECT-TYPE SYNTAX Integer32 (10..150) UNITS "sec" MAX-ACCESS read-write STATUS current DESCRIPTION "Minimum time interval before starting a defr. cycle" DEFVAL { 10 } ::= { integerObjects 22 } -- 1.3.6.1.4.1.9839.2.1.3.23 max_volt_f4 OBJECT-TYPE SYNTAX Integer32 (0..150) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "" DEFVAL { 0 } ::= { integerObjects 23 } -- 1.3.6.1.4.1.9839.2.1.3.24 t_spunto_f_fb OBJECT-TYPE SYNTAX Integer32 (1..15) UNITS "min" MAX-ACCESS read-write STATUS current DESCRIPTION "Defrost max duration" DEFVAL { 5 } ::= { integerObjects 24 } -- 1.3.6.1.4.1.9839.2.1.3.25 t_min_on_def_d5 OBJECT-TYPE SYNTAX Integer32 (10..150) UNITS "sec" MAX-ACCESS read-write STATUS current DESCRIPTION "Min time to start a defrosting cycle" DEFVAL { 10 } ::= { integerObjects 25 } -- 1.3.6.1.4.1.9839.2.1.3.26 t_min_def_d6 OBJECT-TYPE SYNTAX Integer32 (0..150) UNITS "sec" MAX-ACCESS read-write STATUS current DESCRIPTION "Min. duration of a defrosting cycle" DEFVAL { 0 } ::= { integerObjects 26 } -- 1.3.6.1.4.1.9839.2.1.3.27 t_max_def_d7 OBJECT-TYPE SYNTAX Integer32 (1..15) UNITS "min" MAX-ACCESS read-write STATUS current DESCRIPTION "Max. duration of a defrosting cycle" DEFVAL { 5 } ::= { integerObjects 27 } -- 1.3.6.1.4.1.9839.2.1.3.28 rit_2def_1c_d8 OBJECT-TYPE SYNTAX Integer32 (10..150) UNITS "min" MAX-ACCESS read-write STATUS current DESCRIPTION "Min time-delay between 2defrosting cycle" DEFVAL { 30 } ::= { integerObjects 28 } -- 1.3.6.1.4.1.9839.2.1.3.29 rit_def_2c_d9 OBJECT-TYPE SYNTAX Integer32 (0..150) UNITS "min" MAX-ACCESS read-write STATUS current DESCRIPTION "Defrosting time interval between the 2 circuits" DEFVAL { 10 } ::= { integerObjects 29 } -- 1.3.6.1.4.1.9839.2.1.3.30 rit_all_ag_a3 OBJECT-TYPE SYNTAX Integer32 (0..90) UNITS "sec" MAX-ACCESS read-write STATUS current DESCRIPTION "Bypass time for antifreeze alarm/Low ambient temp" DEFVAL { 5 } ::= { integerObjects 30 } -- 1.3.6.1.4.1.9839.2.1.3.31 rall_on_flux_p1 OBJECT-TYPE SYNTAX Integer32 (0..150) UNITS "sec" MAX-ACCESS read-write STATUS current DESCRIPTION "Flowswitch alarm delayed when starting the punp" DEFVAL { 20 } ::= { integerObjects 31 } -- 1.3.6.1.4.1.9839.2.1.3.32 rall_rg_flux_p2 OBJECT-TYPE SYNTAX Integer32 (0..90) UNITS "sec" MAX-ACCESS read-write STATUS current DESCRIPTION "Flowswitch alarm delayed during normal operating" DEFVAL { 5 } ::= { integerObjects 32 } -- 1.3.6.1.4.1.9839.2.1.3.33 rit_all_bp_p3 OBJECT-TYPE SYNTAX Integer32 (0..150) UNITS "sec" MAX-ACCESS read-write STATUS current DESCRIPTION "Low pressure alarm delayed at compr. start-up" DEFVAL { 40 } ::= { integerObjects 33 } -- 1.3.6.1.4.1.9839.2.1.3.34 buzzer_p4 OBJECT-TYPE SYNTAX Integer32 (0..15) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Buzzer ON" DEFVAL { 0 } ::= { integerObjects 34 } -- 1.3.6.1.4.1.9839.2.1.3.35 modello_h1 OBJECT-TYPE SYNTAX Integer32 (0..6) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Unit model" DEFVAL { 2 } ::= { integerObjects 35 } -- 1.3.6.1.4.1.9839.2.1.3.36 modo_pompa_h5 OBJECT-TYPE SYNTAX Integer32 (0..2) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "Working logic of pump/inlet fan" DEFVAL { 1 } ::= { integerObjects 36 } -- 1.3.6.1.4.1.9839.2.1.3.37 blocca_tasti_h9 OBJECT-TYPE SYNTAX Integer32 (0..3) UNITS "flag" MAX-ACCESS read-write STATUS current DESCRIPTION "Keyboard key-up" DEFVAL { 1 } ::= { integerObjects 37 } -- 1.3.6.1.4.1.9839.2.1.3.39 delay_def_dc OBJECT-TYPE SYNTAX Integer32 (0..3) UNITS "min" MAX-ACCESS read-write STATUS current DESCRIPTION "Delay before defrosting" DEFVAL { 0 } ::= { integerObjects 39 } -- 1.3.6.1.4.1.9839.2.1.3.40 time_wait_def_dd OBJECT-TYPE SYNTAX Integer32 (0..3) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Delay after defrosting" DEFVAL { 0 } ::= { integerObjects 40 } -- 1.3.6.1.4.1.9839.2.1.3.41 valve_status OBJECT-TYPE SYNTAX Integer32 (0..2) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Valve status cooling" DEFVAL { 0 } ::= { integerObjects 41 } -- 1.3.6.1.4.1.9839.2.1.3.50 machine_config OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Machine configuration" ::= { integerObjects 50 } -- 1.3.6.1.4.1.9839.2.1.3.51 swrel OBJECT-TYPE SYNTAX Integer32 (0..255) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "SW Release" DEFVAL { 1 } ::= { integerObjects 51 } END -- -- CAREL-uchiller.MIB --