Observium_CE/mibs/carel/CAREL-uac-MIB

1583 lines
56 KiB
Plaintext
Raw Permalink Blame History

--
-- CAREL-uac.MIB
-- MIB generated by CAREL
-- Friday, 14 March 2003
--
CAREL-uac-MIB DEFINITIONS ::= BEGIN
IMPORTS
OBJECT-GROUP
FROM SNMPv2-CONF
sysContact, sysName, sysLocation
FROM SNMPv2-MIB
enterprises, MODULE-IDENTITY
FROM SNMPv2-SMI;
uacMIB MODULE-IDENTITY
LAST-UPDATED "200303141725Z" -- March 14, 2003 at 17:25 GMT
ORGANIZATION "CAREL SpA"
CONTACT-INFO
"
Simone Ravazzolo
Carel SpA
Via dell'Industria, 11
35020 Brugine (PD) Italy
Tel: +39 049 9716611
E-mail: simone.ravazzolo@carel.com
"
DESCRIPTION
"This is the MIB module for the uac device."
::= { instruments 1 }
--
-- Node definitions
--
-- 1.3.6.1.4.1.9839
carel OBJECT IDENTIFIER ::= { enterprises 9839 }
-- 1.3.6.1.4.1.9839.1
systm OBJECT IDENTIFIER ::= { carel 1 }
-- 1.3.6.1.4.1.9839.1.1
agentRelease OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Release of the Agent."
::= { systm 1 }
-- 1.3.6.1.4.1.9839.1.2
agentCode OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Code of the Agent. 1=WebGate"
::= { systm 2 }
-- 1.3.6.1.4.1.9839.2
instruments OBJECT IDENTIFIER ::= { carel 2 }
-- 1.3.6.1.4.1.9839.2.0
webGateInfo OBJECT IDENTIFIER ::= { instruments 0 }
-- 1.3.6.1.4.1.9839.2.0.1
agentParameters OBJECT IDENTIFIER ::= { webGateInfo 1 }
-- 1.3.6.1.4.1.9839.2.0.1.1
netSize OBJECT-TYPE
SYNTAX Integer32 (1..16)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Network size. It corresponds to the number of units connected to the WebGate. "
::= { agentParameters 1 }
-- 1.3.6.1.4.1.9839.2.0.1.2
baudRate OBJECT-TYPE
SYNTAX Integer32 (1200 | 2400 |4800 |9600 | 19200)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Baudrate of the Carel network. "
::= { agentParameters 2 }
-- 1.3.6.1.4.1.9839.2.0.2
unitTypeGroup OBJECT IDENTIFIER ::= { webGateInfo 2 }
-- 1.3.6.1.4.1.9839.2.0.2.1
unit1-Type OBJECT-TYPE
SYNTAX DisplayString
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of the unit having serial address 1. "
::= { unitTypeGroup 1 }
-- ... You will have how many unitX-Type objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.0.3
unitCodeGroup OBJECT IDENTIFIER ::= { webGateInfo 3 }
-- 1.3.6.1.4.1.9839.2.0.3.1
unit1-Code OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Code of the unit having serial address 1. "
::= { unitCodeGroup 1 }
-- ... You will have how many unitX-Code objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.0.4
unitSoftwareReleaseGroup OBJECT IDENTIFIER ::= { webGateInfo 4 }
-- 1.3.6.1.4.1.9839.2.0.3.1
unit1-SoftwareRelease OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Software release of the unit having serial address 1. "
::= { unitSoftwareReleaseGroup 1 }
-- ... You will have how many unitX-SoftwareRelease objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.0.5
unitMinSoftwareReleaseGroup OBJECT IDENTIFIER ::= { webGateInfo 5 }
-- 1.3.6.1.4.1.9839.2.0.5.1
unit1-MinSoftwareRelease OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Minimum software release of the unit having serial address 1. "
::= { unitMinSoftwareReleaseGroup 1 }
-- ... You will have how many unitX-MinSoftwareRelease objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.0.6
unitMaxSoftwareReleaseGroup OBJECT IDENTIFIER ::= { webGateInfo 6 }
-- 1.3.6.1.4.1.9839.2.0.6.1
unit1-MaxSoftwareRelease OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Maximum software release of the unit having serial address 1. "
::= { unitMaxSoftwareReleaseGroup 1 }
-- ... You will have how many unitX-MaxSoftwareRelease objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.0.7
unitNoAnswerCounterGroup OBJECT IDENTIFIER ::= { webGateInfo 7 }
-- 1.3.6.1.4.1.9839.2.0.7.1
unit1-NoAnswerCounter OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "No answer counter of the unit having serial address 1. "
::= { unitNoAnswerCounterGroup 1 }
-- ... You will have how many unitX-NoAnswerCounter objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.0.8
unitErrorChecksumCounterGroup OBJECT IDENTIFIER ::= { webGateInfo 8 }
-- 1.3.6.1.4.1.9839.2.0.8.1
unit1-ErrorChecksumCounter OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Error checksum counter of the unit having serial address 1. "
::= { unitErrorChecksumCounterGroup 1 }
-- ... You will have how many unitX-ErrorChecksumCounter objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.0.9
unitTimeoutCounterGroup OBJECT IDENTIFIER ::= { webGateInfo 9 }
-- 1.3.6.1.4.1.9839.2.0.9.1
unit1-TimeoutCounter OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timeout counter of the unit having serial address 1. "
::= { unitTimeoutCounterGroup 1 }
-- ... You will have how many unitX-TimeoutCounter objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.0.10
unitOnLineStatusGroup OBJECT IDENTIFIER ::= { webGateInfo 10 }
-- 1.3.6.1.4.1.9839.2.0.10.1
unit1-OnLineStatus OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "On line status of the unit having serial address 1. "
::= { unitOnLineStatusGroup 1 }
-- ... You will have how many unitX-OnLineStatus objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.1
uacMIB OBJECT IDENTIFIER ::= { instruments 1 }
-- 1.3.6.1.4.1.9839.2.1.1
digitalObjects OBJECT IDENTIFIER ::= { uacMIB 1 }
-- 1.3.6.1.4.1.9839.2.1.1.3
al_eeprom OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "eeprom error"
::= { digitalObjects 3 }
-- 1.3.6.1.4.1.9839.2.1.1.4
al_b1_ko OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Control sensor faulty or not connected"
::= { digitalObjects 4 }
-- 1.3.6.1.4.1.9839.2.1.1.5
al_b2_ko OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Evaporator sensor faulty or not connected"
::= { digitalObjects 5 }
-- 1.3.6.1.4.1.9839.2.1.1.6
al_b3_ko OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Humidity probe faulty or not connected"
::= { digitalObjects 6 }
-- 1.3.6.1.4.1.9839.2.1.1.7
al_b4_ko OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Supply sensor faulty or not connected"
::= { digitalObjects 7 }
-- 1.3.6.1.4.1.9839.2.1.1.8
al_clock OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "clock board faulty or not connected"
::= { digitalObjects 8 }
-- 1.3.6.1.4.1.9839.2.1.1.9
al_hp_ckt1 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "high pressure on circuit 1"
::= { digitalObjects 9 }
-- 1.3.6.1.4.1.9839.2.1.1.10
al_hp_ckt2 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "high pressure on circuit 2"
::= { digitalObjects 10 }
-- 1.3.6.1.4.1.9839.2.1.1.11
al_lp_ckt1 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "low pressure on circuit 1"
::= { digitalObjects 11 }
-- 1.3.6.1.4.1.9839.2.1.1.12
al_lp_ckt2 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "low pressure on circuit 2"
::= { digitalObjects 12 }
-- 1.3.6.1.4.1.9839.2.1.1.13
al_flow_sw OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Air flow alarm"
::= { digitalObjects 13 }
-- 1.3.6.1.4.1.9839.2.1.1.14
al_clogged_fl OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "clogged filter"
::= { digitalObjects 14 }
-- 1.3.6.1.4.1.9839.2.1.1.15
al_heaters_ol OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Resistors overheat"
::= { digitalObjects 15 }
-- 1.3.6.1.4.1.9839.2.1.1.16
al_fan_ol OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Fan overheat"
::= { digitalObjects 16 }
-- 1.3.6.1.4.1.9839.2.1.1.17
al_comp_ol OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compressor overheat"
::= { digitalObjects 17 }
-- 1.3.6.1.4.1.9839.2.1.1.18
al_freecool OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Cooling alarm"
::= { digitalObjects 18 }
-- 1.3.6.1.4.1.9839.2.1.1.19
al_humidif OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Humidifier alarm"
::= { digitalObjects 19 }
-- 1.3.6.1.4.1.9839.2.1.1.20
al_room_lt OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "room low temperature"
::= { digitalObjects 20 }
-- 1.3.6.1.4.1.9839.2.1.1.21
al_room_ht OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "room high temperature"
::= { digitalObjects 21 }
-- 1.3.6.1.4.1.9839.2.1.1.22
al_room_lh OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "room low humidity"
::= { digitalObjects 22 }
-- 1.3.6.1.4.1.9839.2.1.1.23
al_room_hh OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "room high humidity"
::= { digitalObjects 23 }
-- 1.3.6.1.4.1.9839.2.1.1.24
al_generic_ext OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "External alarm"
::= { digitalObjects 24 }
-- 1.3.6.1.4.1.9839.2.1.1.25
al_fan_maint OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "fan maintenance"
::= { digitalObjects 25 }
-- 1.3.6.1.4.1.9839.2.1.1.26
al_filter_maint OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "air filter maintenance"
::= { digitalObjects 26 }
-- 1.3.6.1.4.1.9839.2.1.1.27
al_comp1_maint OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "compressor n<>1 maintenance"
::= { digitalObjects 27 }
-- 1.3.6.1.4.1.9839.2.1.1.28
al_comp2_maint OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "compressor n<>2 maintenance"
::= { digitalObjects 28 }
-- 1.3.6.1.4.1.9839.2.1.1.29
al_low_c_ee OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "low voltage while eeprom writing"
::= { digitalObjects 29 }
-- 1.3.6.1.4.1.9839.2.1.1.30
al_volt_lack OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "No shelter mains"
::= { digitalObjects 30 }
-- 1.3.6.1.4.1.9839.2.1.1.31
al_smoke_fire OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Smoke/Fire alarm"
::= { digitalObjects 31 }
-- 1.3.6.1.4.1.9839.2.1.1.33
unit_status OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "On status"
::= { digitalObjects 33 }
-- 1.3.6.1.4.1.9839.2.1.1.34
comp1_status OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compressor 1"
::= { digitalObjects 34 }
-- 1.3.6.1.4.1.9839.2.1.1.35
comp2_status OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compressor 2"
::= { digitalObjects 35 }
-- 1.3.6.1.4.1.9839.2.1.1.36
heater1_status OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Heater 1"
::= { digitalObjects 36 }
-- 1.3.6.1.4.1.9839.2.1.1.37
heater2_status OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Heater 2"
::= { digitalObjects 37 }
-- 1.3.6.1.4.1.9839.2.1.1.38
fan_status OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Fan status"
::= { digitalObjects 38 }
-- 1.3.6.1.4.1.9839.2.1.1.39
deshum_status OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Dehumidifier"
::= { digitalObjects 39 }
-- 1.3.6.1.4.1.9839.2.1.1.41
humid_on OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "with HA=4,5 humidifier status"
::= { digitalObjects 41 }
-- 1.3.6.1.4.1.9839.2.1.1.45
al_fan1_ol OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Fan overheat 1"
::= { digitalObjects 45 }
-- 1.3.6.1.4.1.9839.2.1.1.46
al_fan2_ol OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Fan overheat 2"
::= { digitalObjects 46 }
-- 1.3.6.1.4.1.9839.2.1.1.49
on_off OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "On/off command (like press on/off key)"
::= { digitalObjects 49 }
-- 1.3.6.1.4.1.9839.2.1.1.50
measunit OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Measure unit (celsius/Fahrenheit)"
DEFVAL { 0 }
::= { digitalObjects 50 }
-- 1.3.6.1.4.1.9839.2.1.2
analogObjects OBJECT IDENTIFIER ::= { uacMIB 2 }
-- 1.3.6.1.4.1.9839.2.1.2.1
probeb3_rp OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "%RH x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Reading probe B3"
::= { analogObjects 1 }
-- 1.3.6.1.4.1.9839.2.1.2.2
probeb1_rn OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "<22>C x10"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Room temper. B1"
::= { analogObjects 2 }
-- 1.3.6.1.4.1.9839.2.1.2.3
probeb2_ro OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "<22>C x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Reading probe B2"
::= { analogObjects 3 }
-- 1.3.6.1.4.1.9839.2.1.2.4
probeb4_rr OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "<22>C x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Reading probe B4"
::= { analogObjects 4 }
-- 1.3.6.1.4.1.9839.2.1.2.5
real_setp OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "<22>C x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Set point"
DEFVAL { 200 }
::= { analogObjects 5 }
-- 1.3.6.1.4.1.9839.2.1.2.11
sum_setp_r1 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "<22>C x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Temperature set point (cooling)"
DEFVAL { 200 }
::= { analogObjects 11 }
-- 1.3.6.1.4.1.9839.2.1.2.12
win_setp_r9 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "<22>C x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Temperature set point (heating)"
DEFVAL { 180 }
::= { analogObjects 12 }
-- 1.3.6.1.4.1.9839.2.1.2.13
min_setp_t_ra OBJECT-TYPE
SYNTAX Integer32 (-40..32767)
UNITS "<22>C x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Minimum temperature set point"
DEFVAL { 0 }
::= { analogObjects 13 }
-- 1.3.6.1.4.1.9839.2.1.2.14
max_setp_t_rb OBJECT-TYPE
SYNTAX Integer32 (-32767..1400)
UNITS "<22>C x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Maximum temperature set point"
DEFVAL { 500 }
::= { analogObjects 14 }
-- 1.3.6.1.4.1.9839.2.1.2.15
sum_diff_r2 OBJECT-TYPE
SYNTAX Integer32 (1..198)
UNITS "<22>C x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Cooling differential"
DEFVAL { 30 }
::= { analogObjects 15 }
-- 1.3.6.1.4.1.9839.2.1.2.16
win_diff_r3 OBJECT-TYPE
SYNTAX Integer32 (1..198)
UNITS "<22>C x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Heating differential"
DEFVAL { 20 }
::= { analogObjects 16 }
-- 1.3.6.1.4.1.9839.2.1.2.17
n_zone_r4 OBJECT-TYPE
SYNTAX Integer32 (1..360)
UNITS "<22>C x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Temperature dead zone"
DEFVAL { 10 }
::= { analogObjects 17 }
-- 1.3.6.1.4.1.9839.2.1.2.18
hum_setp_r5 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "%RH x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Humidity Set Point"
DEFVAL { 500 }
::= { analogObjects 18 }
-- 1.3.6.1.4.1.9839.2.1.2.19
min_setp_h_rc OBJECT-TYPE
SYNTAX Integer32 (0..32767)
UNITS "%RH x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Minimum humidity set point"
DEFVAL { 0 }
::= { analogObjects 19 }
-- 1.3.6.1.4.1.9839.2.1.2.20
max_setp_h_rd OBJECT-TYPE
SYNTAX Integer32 (-32767..1000)
UNITS "%RH x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Maximum humidity set point"
DEFVAL { 1000 }
::= { analogObjects 20 }
-- 1.3.6.1.4.1.9839.2.1.2.21
diff_hum_r6 OBJECT-TYPE
SYNTAX Integer32 (10..200)
UNITS "%RH x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Humidification differential"
DEFVAL { 40 }
::= { analogObjects 21 }
-- 1.3.6.1.4.1.9839.2.1.2.22
diff_dehum_r7 OBJECT-TYPE
SYNTAX Integer32 (10..200)
UNITS "%RH x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Dehumidification differential"
DEFVAL { 30 }
::= { analogObjects 22 }
-- 1.3.6.1.4.1.9839.2.1.2.23
n_zone_h_r8 OBJECT-TYPE
SYNTAX Integer32 (0..200)
UNITS "%RH x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Humidity control dead zone"
DEFVAL { 20 }
::= { analogObjects 23 }
-- 1.3.6.1.4.1.9839.2.1.2.24
authority_rg OBJECT-TYPE
SYNTAX Integer32 (-20..20)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "rG Authority for compensation"
DEFVAL { 5 }
::= { analogObjects 24 }
-- 1.3.6.1.4.1.9839.2.1.2.25
s_setp_b2_rh OBJECT-TYPE
SYNTAX Integer32 (-40..1400)
UNITS "<22>C x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Cooling set point compensation"
DEFVAL { 250 }
::= { analogObjects 25 }
-- 1.3.6.1.4.1.9839.2.1.2.26
w_setp_b2_ri OBJECT-TYPE
SYNTAX Integer32 (-40..1400)
UNITS "<22>C x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Heating set point compensation"
DEFVAL { 100 }
::= { analogObjects 26 }
-- 1.3.6.1.4.1.9839.2.1.2.27
diff_freec_rl OBJECT-TYPE
SYNTAX Integer32 (0..540)
UNITS "<22>C x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Free cooling differential(only for shelters)"
DEFVAL { 90 }
::= { analogObjects 27 }
-- 1.3.6.1.4.1.9839.2.1.2.28
min_t_freec_rn OBJECT-TYPE
SYNTAX Integer32 (-40..860)
UNITS "<22>C x10"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Lower supply temperature limit during free cooling"
DEFVAL { 50 }
::= { analogObjects 28 }
-- 1.3.6.1.4.1.9839.2.1.2.29
delta_p6 OBJECT-TYPE
SYNTAX Integer32 (0..900)
UNITS "<22>C x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Delta from effective set point for low temperature alarm"
DEFVAL { 100 }
::= { analogObjects 29 }
-- 1.3.6.1.4.1.9839.2.1.2.30
delta_p7 OBJECT-TYPE
SYNTAX Integer32 (0..900)
UNITS "<22>C x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Delta from effective set point for high temperature alarm"
DEFVAL { 100 }
::= { analogObjects 30 }
-- 1.3.6.1.4.1.9839.2.1.2.31
delta_p8 OBJECT-TYPE
SYNTAX Integer32 (0..500)
UNITS "%RH x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Delta from set point for low humidity alarm"
DEFVAL { 200 }
::= { analogObjects 31 }
-- 1.3.6.1.4.1.9839.2.1.2.32
delta_p9 OBJECT-TYPE
SYNTAX Integer32 (0..500)
UNITS "%RH x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Delta from set point for high humidity alarm"
DEFVAL { 200 }
::= { analogObjects 32 }
-- 1.3.6.1.4.1.9839.2.1.2.33
diff_pd OBJECT-TYPE
SYNTAX Integer32 (0..360)
UNITS "<22>C x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Return supply temp. difference for supply temp ala"
DEFVAL { 30 }
::= { analogObjects 33 }
-- 1.3.6.1.4.1.9839.2.1.2.34
min_fan_s_f5 OBJECT-TYPE
SYNTAX Integer32 (0..32767)
UNITS "<22>C x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "% reg. band for min speed or temp./pressure for min speed in condens."
DEFVAL { 200 }
::= { analogObjects 34 }
-- 1.3.6.1.4.1.9839.2.1.2.35
max_fan_s_f6 OBJECT-TYPE
SYNTAX Integer32 (-32767..1580)
UNITS "<22>C x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "% reg. band for max speed or temp./pressure for max speed in condens."
DEFVAL { 1000 }
::= { analogObjects 35 }
-- 1.3.6.1.4.1.9839.2.1.2.36
probeconvl OBJECT-TYPE
SYNTAX Integer32 (0..32767)
UNITS "%RH/bar x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Minimun value of humidity/pressure at 0mA, 4mA or 0Vdc"
DEFVAL { 0 }
::= { analogObjects 36 }
-- 1.3.6.1.4.1.9839.2.1.2.37
probeconvh OBJECT-TYPE
SYNTAX Integer32 (-32767..1000)
UNITS "%RH/bar x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "maximun value of humidity/pressure at 20mA or 1Vdc"
DEFVAL { 1000 }
::= { analogObjects 37 }
-- 1.3.6.1.4.1.9839.2.1.2.38
calibrazione_sonda_b1 OBJECT-TYPE
SYNTAX Integer32 (-108..108)
UNITS "<22>C x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Calibration probe B1"
DEFVAL { 0 }
::= { analogObjects 38 }
-- 1.3.6.1.4.1.9839.2.1.2.39
calibrazione_sonda_b2 OBJECT-TYPE
SYNTAX Integer32 (-108..108)
UNITS "<22>C x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Calibration probe B2"
DEFVAL { 0 }
::= { analogObjects 39 }
-- 1.3.6.1.4.1.9839.2.1.2.40
calibrazione_sonda_b3 OBJECT-TYPE
SYNTAX Integer32 (-100..100)
UNITS "%RH/bar x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Calibration probe B3"
DEFVAL { 0 }
::= { analogObjects 40 }
-- 1.3.6.1.4.1.9839.2.1.2.41
calibrazione_sonda_b4 OBJECT-TYPE
SYNTAX Integer32 (-108..108)
UNITS "<22>C x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Calibration probe B4"
DEFVAL { 0 }
::= { analogObjects 41 }
-- 1.3.6.1.4.1.9839.2.1.3
integerObjects OBJECT IDENTIFIER ::= { uacMIB 3 }
-- 1.3.6.1.4.1.9839.2.1.3.11
fan_h_count_fa OBJECT-TYPE
SYNTAX Integer32 (0..30000)
UNITS "hours"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Supply fan hour counter"
DEFVAL { 0 }
::= { integerObjects 11 }
-- 1.3.6.1.4.1.9839.2.1.3.12
filt_h_count_fc OBJECT-TYPE
SYNTAX Integer32 (0..30000)
UNITS "hours"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Filter hour counter"
DEFVAL { 0 }
::= { integerObjects 12 }
-- 1.3.6.1.4.1.9839.2.1.3.13
cmp1_h_count_c9 OBJECT-TYPE
SYNTAX Integer32 (0..30000)
UNITS "hours"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "compressor 1 hour counter"
DEFVAL { 0 }
::= { integerObjects 13 }
-- 1.3.6.1.4.1.9839.2.1.3.14
cmp2_h_count_ca OBJECT-TYPE
SYNTAX Integer32 (0..30000)
UNITS "hours"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "compressor 2 hour counter"
DEFVAL { 0 }
::= { integerObjects 14 }
-- 1.3.6.1.4.1.9839.2.1.3.15
en_fan_hc_f9 OBJECT-TYPE
SYNTAX Integer32 (0..30000)
UNITS "hours"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Supply fan hour counter threshold"
DEFVAL { 0 }
::= { integerObjects 15 }
-- 1.3.6.1.4.1.9839.2.1.3.16
en_filt_hc_fb OBJECT-TYPE
SYNTAX Integer32 (0..30000)
UNITS "hours"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Filter hour counter threshold"
DEFVAL { 0 }
::= { integerObjects 16 }
-- 1.3.6.1.4.1.9839.2.1.3.17
en_cmps_hc_c8 OBJECT-TYPE
SYNTAX Integer32 (0..30000)
UNITS "hours"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "compressor hour counter threshold"
DEFVAL { 0 }
::= { integerObjects 17 }
-- 1.3.6.1.4.1.9839.2.1.3.18
unit_model_h1 OBJECT-TYPE
SYNTAX Integer32 (0..3)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Machine model"
DEFVAL { 0 }
::= { integerObjects 18 }
-- 1.3.6.1.4.1.9839.2.1.3.19
cool_mode_h5 OBJECT-TYPE
SYNTAX Integer32 (1..5)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Operating mode of the 2 <20>cool<6F> outputs"
DEFVAL { 1 }
::= { integerObjects 19 }
-- 1.3.6.1.4.1.9839.2.1.3.20
heat_mode_h6 OBJECT-TYPE
SYNTAX Integer32 (0..4)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Operating mode of the 2 <20>heat<61> outputs"
DEFVAL { 1 }
::= { integerObjects 20 }
-- 1.3.6.1.4.1.9839.2.1.3.21
en_humidif_h8 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Presence of humidifier"
DEFVAL { 0 }
::= { integerObjects 21 }
-- 1.3.6.1.4.1.9839.2.1.3.22
tempo_di_escursione_valvola_3 OBJECT-TYPE
SYNTAX Integer32 (0..600)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "3P valve or damper excursion time"
DEFVAL { 150 }
::= { integerObjects 22 }
-- 1.3.6.1.4.1.9839.2.1.3.23
prop_pi_re OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Type of temperature regulation"
DEFVAL { 0 }
::= { integerObjects 23 }
-- 1.3.6.1.4.1.9839.2.1.3.24
pi_time_rf OBJECT-TYPE
SYNTAX Integer32 (10..3600)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Integration time for P+I action"
DEFVAL { 600 }
::= { integerObjects 24 }
-- 1.3.6.1.4.1.9839.2.1.3.25
conf_humid_h9 OBJECT-TYPE
SYNTAX Integer32 (0..9)
UNITS "flags"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Type of dehumidification"
DEFVAL { 0 }
::= { integerObjects 25 }
-- 1.3.6.1.4.1.9839.2.1.3.26
conf_b2_hc OBJECT-TYPE
SYNTAX Integer32 (0..3)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Function of probe B2"
DEFVAL { 0 }
::= { integerObjects 26 }
-- 1.3.6.1.4.1.9839.2.1.3.27
conf_b3_hd OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Function of probe B3"
DEFVAL { 0 }
::= { integerObjects 27 }
-- 1.3.6.1.4.1.9839.2.1.3.28
conf_anout2_hb OBJECT-TYPE
SYNTAX Integer32 (0..2)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Function of output Y2"
DEFVAL { 0 }
::= { integerObjects 28 }
-- 1.3.6.1.4.1.9839.2.1.3.29
id_on_off_he OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "ON/OFF digital input"
DEFVAL { 0 }
::= { integerObjects 29 }
-- 1.3.6.1.4.1.9839.2.1.3.30
al_out_lgk_hf OBJECT-TYPE
SYNTAX Integer32 (0..3)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Alarm relay logic"
DEFVAL { 0 }
::= { integerObjects 30 }
-- 1.3.6.1.4.1.9839.2.1.3.31
conf_deshum_ha OBJECT-TYPE
SYNTAX Integer32 (0..7)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Function of the dehumidificat./humidif. Relay"
DEFVAL { 0 }
::= { integerObjects 31 }
-- 1.3.6.1.4.1.9839.2.1.3.32
conf_id_al_pb OBJECT-TYPE
SYNTAX Integer32 (0..6)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Type of management of generic alarm input ID5"
DEFVAL { 1 }
::= { integerObjects 32 }
-- 1.3.6.1.4.1.9839.2.1.3.33
un_rot_num_h2 OBJECT-TYPE
SYNTAX Integer32 (0..6)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "N. of machines in rotation"
DEFVAL { 0 }
::= { integerObjects 33 }
-- 1.3.6.1.4.1.9839.2.1.3.34
un_rot_adr_h3 OBJECT-TYPE
SYNTAX Integer32 (1..6)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Address of unit in rotation"
DEFVAL { 1 }
::= { integerObjects 34 }
-- 1.3.6.1.4.1.9839.2.1.3.35
rot_time_h4 OBJECT-TYPE
SYNTAX Integer32 (0..250)
UNITS "hours"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Rotation time between a series of units"
DEFVAL { 0 }
::= { integerObjects 35 }
-- 1.3.6.1.4.1.9839.2.1.3.36
presenza_sonda_1 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Presence external air probe B2"
DEFVAL { 0 }
::= { integerObjects 36 }
-- 1.3.6.1.4.1.9839.2.1.3.37
tipo_sonda_2 OBJECT-TYPE
SYNTAX Integer32 (0..2)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Type of humidity/press./temp. probe B3"
DEFVAL { 0 }
::= { integerObjects 37 }
-- 1.3.6.1.4.1.9839.2.1.3.38
presenza_sonda_3 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Presence supply air B4"
DEFVAL { 0 }
::= { integerObjects 38 }
-- 1.3.6.1.4.1.9839.2.1.3.39
filtro_digitale OBJECT-TYPE
SYNTAX Integer32 (1..15)
UNITS "<22>C"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Digital filter"
DEFVAL { 4 }
::= { integerObjects 39 }
-- 1.3.6.1.4.1.9839.2.1.3.40
limitazione_ingresso OBJECT-TYPE
SYNTAX Integer32 (1..15)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Input limit"
DEFVAL { 8 }
::= { integerObjects 40 }
-- 1.3.6.1.4.1.9839.2.1.3.41
keyb_lockup_hi OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "inibit parameter modifications"
::= { integerObjects 41 }
-- 1.3.6.1.4.1.9839.2.1.3.42
param_set_hl OBJECT-TYPE
SYNTAX Integer32 (0..3)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Parameter sets"
DEFVAL { 0 }
::= { integerObjects 42 }
-- 1.3.6.1.4.1.9839.2.1.3.43
display_cfg_hn OBJECT-TYPE
SYNTAX Integer32 (0..2)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Select data shown on display"
DEFVAL { 0 }
::= { integerObjects 43 }
-- 1.3.6.1.4.1.9839.2.1.3.44
buzzer_cfg_p4 OBJECT-TYPE
SYNTAX Integer32 (0..15)
UNITS "min"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "P4 Buzzer activation"
DEFVAL { 0 }
::= { integerObjects 44 }
-- 1.3.6.1.4.1.9839.2.1.3.45
alm_reset_p5 OBJECT-TYPE
SYNTAX Integer32 (1..5)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Reset alarms"
DEFVAL { 1 }
::= { integerObjects 45 }
-- 1.3.6.1.4.1.9839.2.1.3.48
user_pw_hh OBJECT-TYPE
SYNTAX Integer32 (0..200)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "USER password"
DEFVAL { 22 }
::= { integerObjects 48 }
-- 1.3.6.1.4.1.9839.2.1.3.49
sw_release_hr OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Software version"
DEFVAL { 13 }
::= { integerObjects 49 }
-- 1.3.6.1.4.1.9839.2.1.3.50
fan_config_f1 OBJECT-TYPE
SYNTAX Integer32 (0..2)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Fan operating mode"
DEFVAL { 1 }
::= { integerObjects 50 }
-- 1.3.6.1.4.1.9839.2.1.3.51
min_volt_f2 OBJECT-TYPE
SYNTAX Integer32 (0..32767)
UNITS "step"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Minimum triac voltage threshold"
DEFVAL { 35 }
::= { integerObjects 51 }
-- 1.3.6.1.4.1.9839.2.1.3.52
max_volt_f3 OBJECT-TYPE
SYNTAX Integer32 (-32767..100)
UNITS "step"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Maximum triac voltage threshold"
DEFVAL { 75 }
::= { integerObjects 52 }
-- 1.3.6.1.4.1.9839.2.1.3.53
triac_durat_f4 OBJECT-TYPE
SYNTAX Integer32 (0..15)
UNITS "ms"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Duration of triac impulse"
DEFVAL { 2 }
::= { integerObjects 53 }
-- 1.3.6.1.4.1.9839.2.1.3.54
min_out_val_f7 OBJECT-TYPE
SYNTAX Integer32 (0..32767)
UNITS "%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Minimum output value"
DEFVAL { 10 }
::= { integerObjects 54 }
-- 1.3.6.1.4.1.9839.2.1.3.55
max_out_val_f8 OBJECT-TYPE
SYNTAX Integer32 (-32767..100)
UNITS "%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Maximum output value"
DEFVAL { 100 }
::= { integerObjects 55 }
-- 1.3.6.1.4.1.9839.2.1.3.56
min_on_time_c1 OBJECT-TYPE
SYNTAX Integer32 (0..300)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Minimum ON time"
DEFVAL { 60 }
::= { integerObjects 56 }
-- 1.3.6.1.4.1.9839.2.1.3.57
min_off_time_c2 OBJECT-TYPE
SYNTAX Integer32 (0..900)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Minimum OFF time"
DEFVAL { 60 }
::= { integerObjects 57 }
-- 1.3.6.1.4.1.9839.2.1.3.58
t_betw_2_on_c3 OBJECT-TYPE
SYNTAX Integer32 (0..900)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Minimum time between two start-ups"
DEFVAL { 360 }
::= { integerObjects 58 }
-- 1.3.6.1.4.1.9839.2.1.3.59
t_comp_2_on_c4 OBJECT-TYPE
SYNTAX Integer32 (0..300)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "ON delay between the 2 compressors"
DEFVAL { 30 }
::= { integerObjects 59 }
-- 1.3.6.1.4.1.9839.2.1.3.60
t_comp_2_off_c5 OBJECT-TYPE
SYNTAX Integer32 (0..300)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "OFF delay between the 2 compressors"
DEFVAL { 0 }
::= { integerObjects 60 }
-- 1.3.6.1.4.1.9839.2.1.3.61
t_comp_fan_c7 OBJECT-TYPE
SYNTAX Integer32 (0..300)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Comp. ON delay from supply fan start-up"
DEFVAL { 20 }
::= { integerObjects 61 }
-- 1.3.6.1.4.1.9839.2.1.3.62
off_fan_d_fd OBJECT-TYPE
SYNTAX Integer32 (0..900)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Supply fan off delay"
DEFVAL { 20 }
::= { integerObjects 62 }
-- 1.3.6.1.4.1.9839.2.1.3.63
on_dalay_hg OBJECT-TYPE
SYNTAX Integer32 (0..300)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Delay on start-up"
DEFVAL { 0 }
::= { integerObjects 63 }
-- 1.3.6.1.4.1.9839.2.1.3.64
en_rotat_c6 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compressor rotation"
DEFVAL { 0 }
::= { integerObjects 64 }
-- 1.3.6.1.4.1.9839.2.1.3.65
d_flow_s_p1 OBJECT-TYPE
SYNTAX Integer32 (0..250)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Flow alarm delay from fan start-up"
DEFVAL { 20 }
::= { integerObjects 65 }
-- 1.3.6.1.4.1.9839.2.1.3.66
d_flow_run_p2 OBJECT-TYPE
SYNTAX Integer32 (0..90)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Flow alarm delay during operation"
DEFVAL { 5 }
::= { integerObjects 66 }
-- 1.3.6.1.4.1.9839.2.1.3.67
lp_delay_p3 OBJECT-TYPE
SYNTAX Integer32 (0..250)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Low pressure alarm delay from compress. Start-up"
DEFVAL { 40 }
::= { integerObjects 67 }
-- 1.3.6.1.4.1.9839.2.1.3.68
al_prb_delay_pa OBJECT-TYPE
SYNTAX Integer32 (0..150)
UNITS "min"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Alarm delay high/low temperature/humidity on start-up"
DEFVAL { 20 }
::= { integerObjects 68 }
-- 1.3.6.1.4.1.9839.2.1.3.69
al_gen_delay_pc OBJECT-TYPE
SYNTAX Integer32 (0..250)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Generic alarm delay"
DEFVAL { 60 }
::= { integerObjects 69 }
-- 1.3.6.1.4.1.9839.2.1.3.70
t_slot_cfg_rt OBJECT-TYPE
SYNTAX Integer32 (0..2)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Time band setting"
DEFVAL { 0 }
::= { integerObjects 70 }
-- 1.3.6.1.4.1.9839.2.1.3.71
fan_time_fe OBJECT-TYPE
SYNTAX Integer32 (0..60)
UNITS "sec"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Fan pick-up time in condensation"
DEFVAL { 4 }
::= { integerObjects 71 }
-- 1.3.6.1.4.1.9839.2.1.3.72
abilitazione_allarme_fumo OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Input selection"
DEFVAL { 0 }
::= { integerObjects 72 }
-- 1.3.6.1.4.1.9839.2.1.3.73
abilitazione_allarme_cf OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Water flow alarm enable"
DEFVAL { 0 }
::= { integerObjects 73 }
-- 1.3.6.1.4.1.9839.2.1.3.74
abilitazione_allarme_ht OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "flag"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "high temperature pre-alarm enable"
DEFVAL { 0 }
::= { integerObjects 74 }
END
--