-- Bachmann GmbH, Stuttgart
-- BACHMANN-BLUENET2-MIB Version 1.0
--
-- Management Information Base for SNMP Network Management
--
-- Copyright 2013 Bachmann GmbH.
-- All Rights Reserved.
--
-- *****************************************************************************
-- File : $RCSfile: BACHMANN-BLUENET2-MIB.txt,v $
-- Rev. : $Revision: 1.17 $
-- Date : $Date: 2015/09/22 16:45:34 $
-- Author : $Author: fis $
-- Id : $Id: BACHMANN-BLUENET2-MIB.txt,v 1.17 2015/09/22 16:45:34 fis Exp $
-- *****************************************************************************
BACHMANN-BLUENET2-MIB DEFINITIONS ::= BEGIN
IMPORTS
MODULE-IDENTITY,
NOTIFICATION-TYPE,
OBJECT-TYPE,
Integer32,
Unsigned32,
TimeTicks
FROM SNMPv2-SMI
MODULE-COMPLIANCE,
NOTIFICATION-GROUP,
OBJECT-GROUP
FROM SNMPv2-CONF
DateAndTime,
DisplayString,
RowStatus,
TEXTUAL-CONVENTION
FROM SNMPv2-TC
sysObjectID
FROM SNMPv2-MIB
bachmann
FROM BACHMANN-SMI-MIB;
blueNet2Mib MODULE-IDENTITY
LAST-UPDATED "201507010000Z"
ORGANIZATION "Bachmann GmbH"
CONTACT-INFO "www.bachmann.com
Bachmann GmbH
Ernsthaldenstrasse 33
D-70565 Stuttgart
Germany, Europe
Tel. +49 711 86602-0
Fax +49 711 86602-34
info@bachmann.com"
DESCRIPTION "The MIB module for representing BlueNet2 PDU SNMP agent implementation version v1.01.00."
REVISION "201507010000Z"
DESCRIPTION "The MIB module for representing BlueNet2 PDU SNMP agent implementation version v1.00.00."
REVISION "201506010000Z"
DESCRIPTION "Version 10100 of BlueNet2 PDU MIB."
REVISION "201502010000Z"
DESCRIPTION "Initial Version of BlueNet2 PDU MIB."
-- ::= { iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) bachmann(31770) blueNet2Mib(2) }
::= { bachmann 2 }
-- *****************************************************************************
-- bachmann OBJECT IDENTIFIER ::= { enterprises 31770 }
-- blueNet2Mib OBJECT IDENTIFIER ::= { bachmann 2 }
blueNet2Notifications OBJECT IDENTIFIER ::= { blueNet2Mib 0 }
blueNet2Products OBJECT IDENTIFIER ::= { blueNet2Mib 1 }
blueNet2Objects OBJECT IDENTIFIER ::= { blueNet2Mib 2 }
blueNet2Identification OBJECT IDENTIFIER ::= { blueNet2Objects 1 }
blueNet2Information OBJECT IDENTIFIER ::= { blueNet2Objects 2 }
blueNet2Configuration OBJECT IDENTIFIER ::= { blueNet2Objects 3 }
blueNet2Devices OBJECT IDENTIFIER ::= { blueNet2Objects 4 }
blueNet2Sensors OBJECT IDENTIFIER ::= { blueNet2Objects 5 }
blueNet2Circuits OBJECT IDENTIFIER ::= { blueNet2Objects 6 }
blueNet2SocketGroups OBJECT IDENTIFIER ::= { blueNet2Objects 7 }
blueNet2Variables OBJECT IDENTIFIER ::= { blueNet2Objects 8 }
blueNet2MPStates OBJECT IDENTIFIER ::= { blueNet2Objects 9 }
blueNet2Traps OBJECT IDENTIFIER ::= { blueNet2Mib 3 }
blueNet2Conformance OBJECT IDENTIFIER ::= { blueNet2Mib 4 }
-- blueNet2Capabilities OBJECT IDENTIFIER ::= { blueNet2Mib 5 }
-- *****************************************************************************
BlueNet2ComponentStates ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION "Represents the possible values of component states."
SYNTAX INTEGER {
ok (1),
warning (2),
alarm (3)
}
BlueNet2EntitySources ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION "Represents the possible source of entity variables."
SYNTAX INTEGER {
other (1),
device (2),
sensor (3),
circuit (4),
phase (5),
fuse (6),
socket (7),
socketgroup (8),
rcm (9)
}
BlueNet2EntityStates ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION "Represents the possible values of entity states."
SYNTAX INTEGER {
expected (0),
undefined (1),
ok (2),
errorHigh (3),
errorLow (4),
warningHigh (5),
warningLow (6),
lost (7),
deactivate (8),
onAlarmIdentidy (9),
offAlarmIdentify(10),
onAlarm (11),
offAlarm (12),
onWarningIdentify (13),
offWarningIdentify (14),
onWarning (15),
offWarning (16),
onIdentify (17),
offIdentify (18),
on (19),
off (20),
onChildAlarm (21),
offChildAlarm (22),
onChildWarning (23),
offChildWarning (24),
childAlarm (25),
childWarning (26),
lostChild (27),
updateInProgress (36),
updateError (37),
onGoingSwitch (38),
high (39),
low (40),
alarm (41),
warning (42),
ok (43),
disabled (44),
fwVersionTooNew (45)
}
BlueNet2EntityBits ::= TEXTUAL-CONVENTION
DISPLAY-HINT "1x:"
STATUS current
DESCRIPTION "Each octet within this value specifies a set of
eight BlueNet2EntityStates, with the first octet
specifying 0 through 7, the second octet
specifying states 8 through 15, etc.
Within each octet, the most significant bit
represents the lowest numbered state, and the least
significant bit represents the highest numbered
state. Thus, each state is represented by a single
bit within the value of this object. If that bit
has a value of '1' then that state is included in
the set of states; the states is not included if
its bit has a value of '0'."
SYNTAX OCTET STRING (SIZE (8..8))
BlueNet2DataSourceTypes ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION "Represents the possible values of data sources.
(1) voltage
(2) peak voltage, can be reset by user
(4) current
(5) peak current, can be reset by user
(7) differential current AC
(8) differential current DC
(9) neutral current if more than one phase is present
(16) phase angle
(17) power factor
(18) apparent power
(19) active power
(20) peak active power
(21) peak active power, can be reset by user
(22) reactive power
(23) frequency
(24) peak neutral current
(32) apparent energy accumulated
(33) apparent energy delta
(34) reactive energy accumulated
(35) reactive energy delta
(36) active energy accumulated
(37) active energy delta
(38) active energy accumulated, can be reset by the user
(39) active energy runtime
(40) custom energy runtime, can be reset by the user
(48) fuse state (on, off etc)
(49) orientation as calculated by the gyro sensor
(50) usb
(51) socket state
(52) pdu state
(53) state of an external i2c sensor
(54) circuit state
(55) phase state
(56) rcd state
(57) socketGroup state
(58) global state
(64) (external) sensor type
(65) circuit type
(66) fuse type
(67) socket type
(68) socket color
(69) phase type
(70) pdu type
(71) rcm type
(80) delta voltage 12
(81) delta voltage 23
(82) delta voltage 31
(83) rcm AC peak value
(84) rcm DC peak value
(256) temperature
(257) humidity
(258) general purpose i/o input channel 1
(259) general purpose i/o input channel 2
(260) general purpose i/o input channel 3
(261) general purpose i/o input channel 4
(262) general purpose i/o output channel 1
(263) general purpose i/o output channel 2
(264) general purpose i/o output channel 3
(265) general purpose i/o output channel 4
(266) dew point
(267) pressure
(268) differential pressure
(269) co2 equivalent (air quality)
(270) total volatile organic components (air quality)
(65535) Unspecified"
SYNTAX INTEGER {
voltage (1),
peakVoltage (2),
current (4),
peakCurrent (5),
differentialCurrentAc(7),
differentialCurrentDc(8),
neutralCurrent (9),
phaseAngle (16),
powerFactor (17),
apparentPower (18),
activePower (19),
peakActivePower (20),
peakActivePowerUser(21),
reactivePower (22),
frequency (23),
peakNeutralCurrent(24),
apparentEnergyAccumulated(32),
apparentEnergyDelta(33),
reactiveEnergyAccumulated(34),
reactiveEnergyDelta(35),
activeEnergyAccumulated(36),
activeEnergyDelta(37),
activeEnergyAccumulatedUser(38),
activeEnergyRuntime(39),
customEnergyRuntimeUser(40),
fuseState (48),
orientation (49),
usb (50),
socketState (51),
pduState (52),
sensorState (53),
circuitState (54),
phaseState (55),
rcdState (56),
socketGroupState (57),
globalState (58),
sensorType (64),
circuitType (65),
fuseType (66),
socketType (67),
socketColor (68),
phaseType (69),
pduType (70),
rcmType (71),
deltaVoltage12 (80),
deltaVoltage23 (81),
deltaVoltage31 (82),
rcmACPeak (83),
rcmDCPeak (84),
temperature (256),
humidity (257),
ioInputChannel1 (258),
ioInputChannel2 (259),
ioInputChannel3 (260),
ioInputChannel4 (261),
ioOutputChannel1(262),
ioOutputChannel2(263),
ioOutputChannel3(264),
ioOutputChannel4(265),
dewPoint (266),
pressure (267),
diffPressure (268),
co2Equivalent (269),
tvoc (270),
unspecified (65535)
}
BlueNet2DataSourceUnits ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION "Represents the possible units of data sources.
Definitions according to CiA 2006."
SYNTAX INTEGER {
metre (1),
kilogram (2),
second (3),
ampere (4),
kelvin (5),
mole (6),
candela (7),
radian (16),
steradian (17),
hertz (32),
newton (33),
pascal (34),
joule (35),
watt (36),
coulomb (37),
volt (38),
farad (39),
ohm (40),
siemens (41),
weber (42),
tesla (43),
henry (44),
celsius (45),
lumen (46),
lux (47),
becquerel (48),
gray (49),
sievert (50),
katal (51),
grade (64),
degree (65),
aMinuteAngle (66),
aSecondAngle (67),
litre (68),
are (69),
hectare (70),
minute (71),
hour (72),
day (73),
year (74),
gram (75),
tonne (76),
bar (78),
poise (79),
stokes (80),
electronvolt (81),
atomicMass (82),
astronomic (83),
parsec (84),
metrePerS2 (85),
newtonMetre (86),
s2 (87),
m2 (88),
m3 (89),
pascalSecond (90),
jPerKgK (91),
wPerMK (92),
jPerMoleK (93),
wPerM2Sr (94),
katPerM3 (95),
kiloWattHour (240),
percentage (241),
va (242),
var (243),
kiloVaHour (244),
kiloVarHour (245),
milliAmpere (246),
unit (255)
}
BlueNet2InfoMessageSources ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION "Represents the source of a message."
SYNTAX INTEGER {
other (1),
device (2),
sensor (3),
variable (4)
}
BlueNet2SocketModes ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION "Represents the mode of a socket or socket group or its LEDs.
A socket or socket group can be notSwitchable or switchedOn/Off.
A socket group may also have different sockets switchedOnAndOff.
A socket or socket group can be set using switchedOn/Off only.
A socket group without any socket at all has mode notAvailable."
SYNTAX INTEGER {
switchedOn (1),
switchedOff (2),
switchedOnAndOff(3),
notAvailable (4),
notSwitchable (5)
}
BlueNet2SocketMembers ::= TEXTUAL-CONVENTION
DISPLAY-HINT "1x:"
STATUS current
DESCRIPTION "Each octet within this value specifies a set of eight
sockets, with the first octet specifying sockets 1 through
8, the second octet specifying sockets 9 through 16, etc.
Within each octet, the most significant bit represents
the lowest numbered socket, and the least significant bit
represents the highest numbered socket. Thus, each socket
of the pdu is represented by a single bit within the
value of this object. If that bit has a value of '1'
then that socket is included in the set of sockets; the
socket is not included if its bit has a value of '0'."
SYNTAX OCTET STRING (SIZE (1..255))
BlueNet2GPIOModes ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION "Represents the mode of GPIO input or output."
SYNTAX INTEGER {
disabled (0),
enabled (2),
s0 (6),
undefined (7)
}
BlueNet2GPIOSwitch ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION "Represents the state to switch on/off GPIO output."
SYNTAX INTEGER {
undefined (0),
switchable (3),
notSwitchable (5),
on (1),
off (2)
}
BlueNet2RcmSelftestCommand ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION "Represents RCM self-test commands with or without alarm or selftest notifications."
SYNTAX INTEGER {
selftestWithoutAnyNotification (0),
selftestWithAlarmNotifyOnly (1),
selftestWithSelftestNotifyOnly (2),
selftestWithAlarmAndSelftestNotify (3),
selftestCommand (4)
}
BlueNet2RcmSelftestResult ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION "Represents RCM self-test result values."
SYNTAX INTEGER {
notRun (0),
notReachable (1),
success (2),
failure (3),
partialSuccess (4),
cancelled (5),
notApplicable (255)
}
-- *****************************************************************************
-- Notifications --
blueNet2NotificationPrefix OBJECT IDENTIFIER ::= { blueNet2Notifications 0 }
blueNet2PduStatusOkNotification NOTIFICATION-TYPE
OBJECTS {
blueNet2DeviceGuid,
blueNet2DeviceStatus,
blueNet2DeviceAlarm
}
STATUS current
DESCRIPTION "PDU status ok."
--
-- #CATEGORY "Status Events."
-- #TYPE "PDU status ok."
-- #SUMMARY "Guid %x device status is %i: %s."
-- #ARGUMENTS {0,1,2}
-- #SEVERITY INFORMATIONAL
-- #STATE OPERATIONAL
--
::= { blueNet2NotificationPrefix 1 }
blueNet2PduStatusWarningNotification NOTIFICATION-TYPE
OBJECTS {
blueNet2DeviceGuid,
blueNet2DeviceStatus,
blueNet2DeviceAlarm
}
STATUS current
DESCRIPTION "PDU status warning."
--
-- #CATEGORY "Status Events."
-- #TYPE "PDU status warning."
-- #SUMMARY "Guid %x device status is %i: %s."
-- #ARGUMENTS {0,1,2}
-- #SEVERITY MINOR
-- #STATE OPERATIONAL
--
::= { blueNet2NotificationPrefix 2 }
blueNet2PduStatusAlarmNotification NOTIFICATION-TYPE
OBJECTS {
blueNet2DeviceGuid,
blueNet2DeviceStatus,
blueNet2DeviceAlarm
}
STATUS current
DESCRIPTION "PDU status alarm."
--
-- #CATEGORY "Status Events."
-- #TYPE "PDU status alarm."
-- #SUMMARY "Guid %x device status is %i: %s."
-- #ARGUMENTS {0,1,2}
-- #SEVERITY MAJOR
-- #STATE OPERATIONAL
--
::= { blueNet2NotificationPrefix 3 }
blueNet2SensorStatusOkNotification NOTIFICATION-TYPE
OBJECTS {
blueNet2SensorGuid,
blueNet2SensorStatus,
blueNet2SensorAlarm
}
STATUS current
DESCRIPTION "Sensor status ok."
--
-- #CATEGORY "Status Events."
-- #TYPE "Sensor status ok."
-- #SUMMARY "Guid %x sensor status is %i: %s."
-- #ARGUMENTS {0,1,2}
-- #SEVERITY INFORMATIONAL
-- #STATE OPERATIONAL
--
::= { blueNet2NotificationPrefix 4 }
blueNet2SensorStatusWarningNotification NOTIFICATION-TYPE
OBJECTS {
blueNet2SensorGuid,
blueNet2SensorStatus,
blueNet2SensorAlarm
}
STATUS current
DESCRIPTION "Sensor status warning."
--
-- #CATEGORY "Status Events."
-- #TYPE "Sensor status warning."
-- #SUMMARY "Guid %x sensor status is %i: %s."
-- #ARGUMENTS {0,1,2}
-- #SEVERITY MINOR
-- #STATE OPERATIONAL
--
::= { blueNet2NotificationPrefix 5 }
blueNet2SensorStatusAlarmNotification NOTIFICATION-TYPE
OBJECTS {
blueNet2SensorGuid,
blueNet2SensorStatus,
blueNet2SensorAlarm
}
STATUS current
DESCRIPTION "Sensor status alarm."
--
-- #CATEGORY "Status Events."
-- #TYPE "Sensor status alarm."
-- #SUMMARY "Guid %x sensor status is %i: %s."
-- #ARGUMENTS {0,1,2}
-- #SEVERITY INFORMATIONAL
-- #STATE OPERATIONAL
--
::= { blueNet2NotificationPrefix 6 }
blueNet2VariableStatusOkNotification NOTIFICATION-TYPE
OBJECTS {
blueNet2VariableDataGuid,
blueNet2VariableDataStatus,
blueNet2VariableDataValue,
blueNet2VariableAlarm
}
STATUS current
DESCRIPTION "Variable status ok."
--
-- #CATEGORY "Threshold Events."
-- #TYPE "Variable status ok."
-- #SUMMARY "Guid %x variable value %i is ok (%i), %s."
-- #ARGUMENTS {0,1,2,3}
-- #SEVERITY INFORMATIONAL
-- #STATE OPERATIONAL
--
::= { blueNet2NotificationPrefix 7 }
blueNet2VariableLowerWarningNotification NOTIFICATION-TYPE
OBJECTS {
blueNet2VariableDataGuid,
blueNet2VariableDataStatus,
blueNet2VariableDataValue,
blueNet2VariableSetPointLowerAlarm,
blueNet2VariableAlarm
}
STATUS current
DESCRIPTION "Variable status lower warning."
--
-- #CATEGORY "Threshold Events."
-- #TYPE "Variable status lower warning."
-- #SUMMARY "Guid %x variable value %i deceeds %i (%i), %s."
-- #ARGUMENTS {0,2,1,3,4}
-- #SEVERITY MINOR
-- #STATE OPERATIONAL
--
::= { blueNet2NotificationPrefix 8 }
blueNet2VariableUpperWarningNotification NOTIFICATION-TYPE
OBJECTS {
blueNet2VariableDataGuid,
blueNet2VariableDataStatus,
blueNet2VariableDataValue,
blueNet2VariableSetPointUpperWarning,
blueNet2VariableAlarm
}
STATUS current
DESCRIPTION "Variable status upper warning."
--
-- #CATEGORY "Threshold Events."
-- #TYPE "Variable status upper warning."
-- #SUMMARY "Guid %x variable value %i exceeds %i (%i), %s."
-- #ARGUMENTS {0,2,1,3,4}
-- #SEVERITY MINOR
-- #STATE OPERATIONAL
--
::= { blueNet2NotificationPrefix 9 }
blueNet2VariableLowerAlarmNotification NOTIFICATION-TYPE
OBJECTS {
blueNet2VariableDataGuid,
blueNet2VariableDataStatus,
blueNet2VariableDataValue,
blueNet2VariableSetPointLowerAlarm,
blueNet2VariableAlarm
}
STATUS current
DESCRIPTION "Variable status lower alarm."
--
-- #CATEGORY "Threshold Events."
-- #TYPE "Variable status lower alarm."
-- #SUMMARY "Guid %x variable value %i deceeds %i (%i), %s."
-- #ARGUMENTS {0,2,1,3,4}
-- #SEVERITY MAJOR
-- #STATE OPERATIONAL
--
::= { blueNet2NotificationPrefix 10 }
blueNet2VariableUpperAlarmNotification NOTIFICATION-TYPE
OBJECTS {
blueNet2VariableDataGuid,
blueNet2VariableDataStatus,
blueNet2VariableDataValue,
blueNet2VariableSetPointUpperAlarm,
blueNet2VariableAlarm
}
STATUS current
DESCRIPTION "Variable status upper alarm."
--
-- #CATEGORY "Threshold Events."
-- #TYPE "Variable status upper alarm."
-- #SUMMARY "Guid %x variable value %i exceeds %i (%i), %s."
-- #ARGUMENTS {0,2,1,3,4}
-- #SEVERITY MAJOR
-- #STATE OPERATIONAL
--
::= { blueNet2NotificationPrefix 11 }
blueNet2ReconfigAgentNotification NOTIFICATION-TYPE
OBJECTS {
sysObjectID
}
STATUS current
DESCRIPTION "Agent reconfiguration."
--
-- #CATEGORY "Status Events."
-- #TYPE "Agent status."
-- #SUMMARY "Agent type: %s, Status: configuration has changed."
-- #ARGUMENTS {0}
-- #SEVERITY INFORMATIONAL
-- #TIMEINDEX 6
-- #STATE OPERATIONAL
--
::= { blueNet2NotificationPrefix 98 }
blueNet2ShutdownAgentNotification NOTIFICATION-TYPE
OBJECTS {
sysObjectID
}
STATUS current
DESCRIPTION "Agent shutdown."
--
-- #CATEGORY "Status Events."
-- #TYPE "Agent status."
-- #SUMMARY "Agent type: %s, Status: shutdown."
-- #ARGUMENTS {0}
-- #SEVERITY SEVERE
-- #TIMEINDEX 6
-- #STATE NONOPERATIONAL
--
::= { blueNet2NotificationPrefix 99 }
-- *****************************************************************************
-- Products --
-- please refer to BACHMANN-BLUENET2-PRODUCTS-MIB definitions
-- *****************************************************************************
-- Objects --
-- =============================================================================
-- blueNet2Identification: global BlueNet2 PDU product identification --
blueNet2IdProductVendor OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "BlueNet2 vendor name."
::= { blueNet2Identification 1 }
blueNet2IdProductName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "BlueNet2 product name."
::= { blueNet2Identification 2 }
blueNet2IdProductURI OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "URI of BlueNet2 PDU product."
::= { blueNet2Identification 3 }
blueNet2IdProductPartNr OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Part number of BlueNet2 PDU product."
::= { blueNet2Identification 4 }
blueNet2IdProductSNr OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Unique serial number of BlueNet2 PDU product."
::= { blueNet2Identification 5 }
blueNet2IdProductDate OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Production date of BlueNet2 PDU product."
::= { blueNet2Identification 6 }
blueNet2IdProductFacility OBJECT-TYPE
SYNTAX INTEGER {
neutralCurrent (0),
fuse (1),
rcd (2),
identify (3),
switch (4),
oneInlet (5),
monitoredPerOutlet(6),
monitoredPerPhase(7),
spd (8)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Functional product facility of BlueNet2 PDU product.
0 : number of phases is 3
1 : has real fuses
2 : has any RCMs
3 : has sockets
4 : sockets can be switched
5 : has one inlet
6 : measurement is done on socket layer
7 : measurement is done on phase layer
8 : has any SPDs"
::= { blueNet2Identification 7 }
blueNet2IdProductCaps OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Capabilities of BlueNet2 PDU product as referred in
BACHMANN-BLUENET2-CAPABILITY-MIB blueNet2Capabilities.
e.g. read 10203 as 01 02 03 to get version 1.2.3."
::= { blueNet2Identification 8 }
blueNet2IdProductFwV OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Hardware revision of BlueNet2 PDU."
::= { blueNet2Identification 9 }
blueNet2IdProductHwV OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Hardware revision of BlueNet2 PDU."
::= { blueNet2Identification 10 }
blueNet2IdProductSwV OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Software revision of BlueNet2 PDU."
::= { blueNet2Identification 11 }
blueNet2IdProductOsV OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Operating system revision of BlueNet2 PDU."
::= { blueNet2Identification 12 }
blueNet2IdProductArch OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Operating system cpu architecture of BlueNet2 PDU."
::= { blueNet2Identification 13 }
blueNet2IdProductMAC OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Ethernet MAC address of BlueNet2 PDU."
::= { blueNet2Identification 14 }
-- =============================================================================
-- blueNet2Information: global BlueNet2 PDU information --
blueNet2InfoUpTime OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Uptime of the BlueNet2 PDU operating system in seconds.
This is different to the sysUpTime since agent (re-)start."
::= { blueNet2Information 1 }
blueNet2InfoOverallStatus OBJECT-TYPE
SYNTAX BlueNet2ComponentStates
MAX-ACCESS read-only
STATUS current
DESCRIPTION "General hadware status of BlueNet2 PDU."
::= { blueNet2Information 2 }
blueNet2InfoNumberOfChanges OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The number of global configuration changes."
::= { blueNet2Information 3 }
blueNet2InfoLastChange OBJECT-TYPE
SYNTAX TimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The value of the sysUpTime object at which the
last change in global configuration happened."
::= { blueNet2Information 4 }
blueNet2InfoAccumulatedStatus OBJECT-TYPE
SYNTAX BlueNet2EntityBits
MAX-ACCESS read-only
STATUS current
DESCRIPTION "A bit field of all current states."
::= { blueNet2Information 5 }
blueNet2InfoLoadTable OBJECT-TYPE
SYNTAX SEQUENCE OF BlueNet2InfoLoadEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A list of system load entries."
::= { blueNet2Information 6 }
blueNet2InfoLoadEntry OBJECT-TYPE
SYNTAX BlueNet2InfoLoadEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Entries of system load table."
INDEX { blueNet2InfoLoadIndex }
::= { blueNet2InfoLoadTable 1 }
BlueNet2InfoLoadEntry ::= SEQUENCE {
blueNet2InfoLoadIndex Unsigned32,
blueNet2InfoLoadAverage Unsigned32
}
blueNet2InfoLoadIndex OBJECT-TYPE
SYNTAX Unsigned32 (1..10)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index for the system load table.
These are the past minutes the load is given for."
::= { blueNet2InfoLoadEntry 1 }
blueNet2InfoLoadAverage OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "System load average multiplied by 100."
::= { blueNet2InfoLoadEntry 2 }
blueNet2InfoMessageTable OBJECT-TYPE
SYNTAX SEQUENCE OF BlueNet2InfoMessageEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A table of the last text message per source."
::= { blueNet2Information 7 }
blueNet2InfoMessageEntry OBJECT-TYPE
SYNTAX BlueNet2InfoMessageEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Entries of last message table."
INDEX { blueNet2InfoMessageSource }
::= { blueNet2InfoMessageTable 1 }
BlueNet2InfoMessageEntry ::= SEQUENCE {
blueNet2InfoMessageSource BlueNet2InfoMessageSources,
blueNet2InfoMessageStatus BlueNet2ComponentStates,
blueNet2InfoMessageTime TimeTicks,
blueNet2InfoMessageText DisplayString,
blueNet2InfoMessageNumberOfOks Unsigned32,
blueNet2InfoMessageNumberOfWarnings Unsigned32,
blueNet2InfoMessageNumberOfErrors Unsigned32
}
blueNet2InfoMessageSource OBJECT-TYPE
SYNTAX BlueNet2InfoMessageSources
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Source of the text message."
::= { blueNet2InfoMessageEntry 1 }
blueNet2InfoMessageStatus OBJECT-TYPE
SYNTAX BlueNet2ComponentStates
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Status of the text message source."
::= { blueNet2InfoMessageEntry 2 }
blueNet2InfoMessageTime OBJECT-TYPE
SYNTAX TimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timestamp of last received text message
according to operating time sysUpTime."
::= { blueNet2InfoMessageEntry 3 }
blueNet2InfoMessageText OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Last text message of a source."
::= { blueNet2InfoMessageEntry 4 }
blueNet2InfoMessageNumberOfOks OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The accumulated number of ok messages."
::= { blueNet2InfoMessageEntry 5 }
blueNet2InfoMessageNumberOfWarnings OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The accumulated number of warning messages."
::= { blueNet2InfoMessageEntry 6 }
blueNet2InfoMessageNumberOfErrors OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The accumulated number of error messages."
::= { blueNet2InfoMessageEntry 7 }
-- =============================================================================
-- blueNet2Configuration: global BlueNet2 PDU configuration --
blueNet2Alias OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "BlueNet2 product alias.
This object should be set by the administrator."
::= { blueNet2Configuration 1 }
blueNet2Language OBJECT-TYPE
SYNTAX INTEGER {
other (1),
english (2),
german (3),
french (4)
}
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION "Supported display language."
DEFVAL { english }
::= { blueNet2Configuration 2 }
blueNet2DateTime OBJECT-TYPE
SYNTAX DateAndTime
-- DISPLAY-HINT "2d-1d-1d,1d:1d:1d.1d,1a1d:1d"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Date and time of day as set manually or by NTP."
::= { blueNet2Configuration 3 }
blueNet2Protocols OBJECT IDENTIFIER ::= { blueNet2Configuration 4 }
blueNet2FtpAccess OBJECT-TYPE
SYNTAX INTEGER {
disabled (1),
enabled (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Ftp access status."
DEFVAL { disabled }
::= { blueNet2Protocols 1 }
blueNet2FtpPort OBJECT-TYPE
SYNTAX Unsigned32 (1..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "TCP/IP port of FTP daemon."
DEFVAL { 21 }
::= { blueNet2Protocols 2 }
blueNet2HttpAccess OBJECT-TYPE
SYNTAX BITS {
httpEnabled (0),
httpsEnabled (1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "HTTP/HTTPS access status."
DEFVAL { { httpsEnabled } }
::= { blueNet2Protocols 3 }
blueNet2HttpPort OBJECT-TYPE
SYNTAX Unsigned32 (1..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "TCP/IP port of HTTP daemon."
DEFVAL { 80 }
::= { blueNet2Protocols 4 }
blueNet2HttpsPort OBJECT-TYPE
SYNTAX Unsigned32 (1..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "TCP/IP port of HTTPS daemon."
DEFVAL { 443 }
::= { blueNet2Protocols 5 }
blueNet2SftpAccess OBJECT-TYPE
SYNTAX INTEGER {
disabled (1),
enabled (2)
}
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION "Sftp access status."
DEFVAL { disabled }
::= { blueNet2Protocols 6 }
blueNet2SftpPort OBJECT-TYPE
SYNTAX Unsigned32 (1..65535)
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION "TCP/IP port of SFTP daemon."
DEFVAL { 115 }
::= { blueNet2Protocols 7 }
blueNet2SshAccess OBJECT-TYPE
SYNTAX INTEGER {
disabled (1),
enabled (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Ssh access status."
DEFVAL { enabled }
::= { blueNet2Protocols 8 }
blueNet2SshPort OBJECT-TYPE
SYNTAX Unsigned32 (1..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "TCP/IP port of SSH daemon."
DEFVAL { 22 }
::= { blueNet2Protocols 9 }
blueNet2TelnetAccess OBJECT-TYPE
SYNTAX INTEGER {
disabled (1),
enabled (2)
}
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION "Telnet access status."
DEFVAL { disabled }
::= { blueNet2Protocols 10 }
blueNet2TelnetPort OBJECT-TYPE
SYNTAX Unsigned32 (1..65535)
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION "TCP/IP port of telnet daemon."
DEFVAL { 23 }
::= { blueNet2Protocols 11 }
-- -----------------------------------------------------------------------------
blueNet2Snmp OBJECT IDENTIFIER ::= { blueNet2Protocols 12 }
blueNet2SnmpVersions OBJECT-TYPE
SYNTAX BITS {
snmpv1 (0),
snmpv2c (1),
snmpv3 (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Supported and enabled SNMP versions."
DEFVAL { { snmpv1, snmpv2c, snmpv3 } }
::= { blueNet2Snmp 1 }
blueNet2MaxTrapReceivers OBJECT-TYPE
SYNTAX Unsigned32 (1..256)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The maximum number of entries in blueNet2TrapReceiverTable."
::= { blueNet2Snmp 2 }
blueNet2TrapReceiverTable OBJECT-TYPE
SYNTAX SEQUENCE OF BlueNet2TrapReceiverEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A list of trap receiver entries."
::= { blueNet2Snmp 3 }
blueNet2TrapReceiverEntry OBJECT-TYPE
SYNTAX BlueNet2TrapReceiverEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Entries of trapTable."
INDEX { blueNet2TrapReceiverIndex }
::= { blueNet2TrapReceiverTable 1 }
BlueNet2TrapReceiverEntry ::= SEQUENCE {
blueNet2TrapReceiverIndex Unsigned32,
blueNet2TrapReceiverRowStatus RowStatus,
blueNet2TrapReceiverProtocol INTEGER,
blueNet2TrapReceiverAddress DisplayString,
blueNet2TrapReceiverFriendlyName DisplayString,
blueNet2TrapReceiverDescription DisplayString,
blueNet2TrapReceiverCommunity DisplayString,
blueNet2TrapReceiverUsername DisplayString
}
blueNet2TrapReceiverIndex OBJECT-TYPE
SYNTAX Unsigned32 (1..256)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of the trap receiver table."
::= { blueNet2TrapReceiverEntry 1 }
blueNet2TrapReceiverRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-create
STATUS current
DESCRIPTION "Activate/create/destroy/disable a trap receiver entry."
::= { blueNet2TrapReceiverEntry 2 }
blueNet2TrapReceiverProtocol OBJECT-TYPE
SYNTAX INTEGER {
snmpv1Trap (1),
snmpv2cTrap (2),
snmpv2cInform (3),
snmpv3Trap (4),
snmpv3Inform (5)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Set trap/inform version."
DEFVAL { snmpv1Trap }
::= { blueNet2TrapReceiverEntry 3 }
blueNet2TrapReceiverAddress OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "IPv4/IPv6 address or host name of trap receiver."
::= { blueNet2TrapReceiverEntry 4 }
blueNet2TrapReceiverFriendlyName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..128))
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION "User friendly name to identify a trap receiver.
This is a mnemonic only and will not be used to send traps."
::= { blueNet2TrapReceiverEntry 5 }
blueNet2TrapReceiverDescription OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION "Description to identify a trap receiver.
This is a mnemonic only and will not be used to send traps."
::= { blueNet2TrapReceiverEntry 6 }
blueNet2TrapReceiverCommunity OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Community used by SNMPv1 and SNMPv2c to identify at trap receiver address."
::= { blueNet2TrapReceiverEntry 7 }
blueNet2TrapReceiverUsername OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Username used by SNMPv3 to identify at trap receiver address."
::= { blueNet2TrapReceiverEntry 8 }
-- -----------------------------------------------------------------------------
blueNet2Modbus OBJECT IDENTIFIER ::= { blueNet2Protocols 13 }
blueNet2ModbusVersions OBJECT-TYPE
SYNTAX BITS {
rtu (0),
tcp (1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Supported and enabled modbus version(s)."
DEFVAL { { tcp } }
::= { blueNet2Modbus 1 }
blueNet2ModbusService OBJECT-TYPE
SYNTAX INTEGER {
disabled (1),
readonly (2),
writeonly (3),
readwrite (4)
}
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION "Modbus service status."
DEFVAL { disabled }
::= { blueNet2Modbus 2 }
blueNet2ModbusTcpPort OBJECT-TYPE
SYNTAX Unsigned32 (1..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "TCP/IP port of modbus daemon."
DEFVAL { 502 }
::= { blueNet2Modbus 3 }
blueNet2ModbusSerialMode OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION "Serial mode configuration parameters (baud,data,parity,stop) of modbus daemon."
DEFVAL { "115200,8,N,1" }
::= { blueNet2Modbus 4 }
blueNet2MaxModbusTcpMasters OBJECT-TYPE
SYNTAX Unsigned32 (1..256)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The maximum number of entries in blueNet2ModbusTcpTable."
::= { blueNet2Modbus 5 }
blueNet2ModbusTcpTable OBJECT-TYPE
SYNTAX SEQUENCE OF BlueNet2ModbusTcpEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION "A list of modbus entries."
::= { blueNet2Modbus 6 }
blueNet2ModbusTcpEntry OBJECT-TYPE
SYNTAX BlueNet2ModbusTcpEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION "Entries of modbus table."
INDEX { blueNet2ModbusTcpIndex }
::= { blueNet2ModbusTcpTable 1 }
BlueNet2ModbusTcpEntry ::=
SEQUENCE {
blueNet2ModbusTcpIndex Unsigned32,
blueNet2ModbusTcpRowStatus RowStatus,
blueNet2ModbusTcpAccess INTEGER,
blueNet2ModbusTcpMaster DisplayString,
blueNet2ModbusTcpFriendlyName DisplayString,
blueNet2ModbusTcpDescription DisplayString
}
blueNet2ModbusTcpIndex OBJECT-TYPE
SYNTAX Unsigned32 (1..256)
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION "Index of the modbus TCP access table."
::= { blueNet2ModbusTcpEntry 1 }
blueNet2ModbusTcpRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-create
STATUS deprecated
DESCRIPTION "Activate/create/destroy/disable a modbus TCP entry."
::= { blueNet2ModbusTcpEntry 2 }
blueNet2ModbusTcpAccess OBJECT-TYPE
SYNTAX INTEGER {
noaccess (1),
readonly (2),
writeonly (3),
readwrite (4)
}
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION "Modbus access for this master entry.
This access is inferior to blueNet2ModbusService, e.g.
readwrite access also requires readwrite status."
-- DEFVAL { noaccess }
::= { blueNet2ModbusTcpEntry 3 }
blueNet2ModbusTcpMaster OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION "Source to restrict modbus access.
It can either be a specific hostname,
IP address, or a subnet represented as
IP/MASK (e.g. 10.10.10.0/255.255.255.0),
or IP/BITS (e.g. 10.10.10.0/24),
or the IPv6 equivalents.
The same master can be specified in several separate
entries presumably with different access tokens.
The first combination matching an incoming request
will be selected."
::= { blueNet2ModbusTcpEntry 4 }
blueNet2ModbusTcpFriendlyName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..128))
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION "User friendly name to identify a modbus master.
This is a mnemonic only and will not be used to query data."
::= { blueNet2ModbusTcpEntry 5 }
blueNet2ModbusTcpDescription OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION "Description to identify a modbus master.
This is a mnemonic only and will not be used to query data."
::= { blueNet2ModbusTcpEntry 6 }
-- -----------------------------------------------------------------------------
blueNet2Ntp OBJECT IDENTIFIER ::= { blueNet2Protocols 14 }
blueNet2NtpService OBJECT-TYPE
SYNTAX INTEGER {
disabled (1),
enabled (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "NTP service status."
DEFVAL { disabled }
::= { blueNet2Ntp 1 }
blueNet2NtpPort OBJECT-TYPE
SYNTAX Unsigned32 (1..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "TCP/IP port of NTP server."
DEFVAL { 123 }
::= { blueNet2Ntp 2 }
blueNet2NtpTimeZone OBJECT-TYPE
SYNTAX Integer32 (1..107)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Time Zone, list is sorted once by time offset and once by index
24 : (GMT-12:00) International Date Line West
99 : (GMT-11:00) Coordinated Universal Time-11
39 : (GMT-10:00) Hawaii
2 : (GMT-09:00) Alaska
58 : (GMT-08:00) Pacific Time (US & Canada)
59 : (GMT-08:00) Tijuana, Baja California
75 : (GMT-07:00) Arizona
47 : (GMT-07:00) Mountain Time (US & Canada)
48 : (GMT-07:00) Chihuahua, La Paz, Mazatlan
15 : (GMT-06:00) Central America
21 : (GMT-06:00) Central Time (US & Canada)
22 : (GMT-06:00) Guadalajara, Mexico City, Monterrey
11 : (GMT-06:00) Saskatchewan
106 : (GMT-05:30) Pacific Marquesas
63 : (GMT-05:00) Bogota, Lima, Quito, Rio Branco
29 : (GMT-05:00) Eastern Time (US & Canada)
74 : (GMT-05:00) Indiana (East)
85 : (GMT-04:00) Caracas
95 : (GMT-04:00) Asuncion
6 : (GMT-04:00) Atlantic Time (Canada)
64 : (GMT-04:00) La Paz
17 : (GMT-04:00) Manaus
57 : (GMT-04:00) Santiago
54 : (GMT-03:30) Newfoundland
28 : (GMT-03:00) Brasilia
86 : (GMT-03:00) Buenos Aires
62 : (GMT-03:00) Buenos Aires, Georgetown
36 : (GMT-03:00) Greenland
83 : (GMT-03:00) Montevideo
87 : (GMT-03:00) Salvador
45 : (GMT-02:00) Mid-Atlantic
10 : (GMT-01:00) Azores
12 : (GMT-01:00) Cape Verde Is.
93 : (GMT) Casablanca
89 : (GMT) Coordinated Universal Time
37 : (GMT) Casablanca, Monrovia, Reykjavik
35 : (GMT) Greenwich Mean Time : Dublin, Edinburgh, Lisbon, London
79 : (GMT+01:00) Amsterdam, Berlin, Bern, Rome, Stockholm, Vienna
18 : (GMT+01:00) Belgrade, Bratislava, Budapest, Ljubljana, Prague
60 : (GMT+01:00) Brussels, Copenhagen, Madrid, Paris
19 : (GMT+01:00) Sarajevo, Skopje, Warsaw, Zagreb
101 : (GMT+01:00) Tripoli
78 : (GMT+01:00) West Central Africa
43 : (GMT+02:00) Amman
38 : (GMT+02:00) Athens, Bucharest, Istanbul
46 : (GMT+02:00) Beirut
27 : (GMT+02:00) Minsk
30 : (GMT+02:00) Cairo
96 : (GMT+02:00) Damascus
68 : (GMT+02:00) Harare, Pretoria
33 : (GMT+02:00) Helsinki, Kyiv, Riga, Sofia, Tallinn, Vilnius
98 : (GMT+02:00) Istanbul
42 : (GMT+02:00) Jerusalem
51 : (GMT+02:00) Windhoek
5 : (GMT+03:00) Baghdad
90 : (GMT+03:00) Kaliningrad, Minsk
3 : (GMT+03:00) Kuwait, Riyadh
61 : (GMT+04:00) Moscow, St. Petersburg, Volgograd
92 : (GMT+04:00) Port Louis
25 : (GMT+03:00) Nairobi
34 : (GMT+03:00) Tbilisi
41 : (GMT+03:30) Tehran
4 : (GMT+04:00) Abu Dhabi, Muscat
9 : (GMT+04:00) Baku
84 : (GMT+04:00) Yerevan
13 : (GMT+04:00) Yerevan (Do not use)
1 : (GMT+04:30) Kabul
31 : (GMT+05:00) Ekaterinburg
94 : (GMT+05:00) Islamabad, Karachi
80 : (GMT+05:00) Tashkent
40 : (GMT+05:30) Chennai, Kolkata, Mumbai, New Delhi
69 : (GMT+05:30) Sri Jayawardenepura
52 : (GMT+05:45) Kathmandu
50 : (GMT+06:00) Almaty, Novosibirsk
16 : (GMT+06:00) Astana, Dhaka
88 : (GMT+06:00) Dhaka
49 : (GMT+06:30) Yangon (Rangoon)
66 : (GMT+07:00) Bangkok, Hanoi, Jakarta
56 : (GMT+07:00) Krasnoyarsk
23 : (GMT+08:00) Beijing, Chongqing, Hong Kong, Urumqi
55 : (GMT+08:00) Irkutsk, Ulaan Bataar
97 : (GMT+08:00) Ulaanbaatar
67 : (GMT+08:00) Kuala Lumpur, Singapore
77 : (GMT+08:00) Perth
70 : (GMT+08:00) Taipei
102 : (GMT+08:45) Australia, Eucla
72 : (GMT+09:00) Osaka, Sapporo, Tokyo
44 : (GMT+09:00) Seoul
82 : (GMT+09:00) Yakutsk
14 : (GMT+09:30) Adelaide
7 : (GMT+09:30) Darwin
26 : (GMT+10:00) Brisbane
8 : (GMT+10:00) Canberra, Melbourne, Sydney
81 : (GMT+10:00) Guam, Port Moresby
71 : (GMT+10:00) Hobart
76 : (GMT+10:00) Vladivostok
103 : (GMT+10:30) Australia, Lord Howe
104 : (GMT+11:30) Pacific, Norfolk
91 : (GMT+12:00) Magadan
20 : (GMT+11:00) Magadan, Solomon Is., New Caledonia
53 : (GMT+12:00) Auckland, Wellington
100 : (GMT+12:00) Coordinated Universal Time+12
32 : (GMT+12:00) Fiji, Kamchatka, Marshall Is.
105 : (GMT+12:45) Pacific, Chatham
65 : (GMT+13:00) Samoa
73 : (GMT+13:00) Nuku'alofa
107 : (GMT+14:00) Line Island
1 : (GMT+04:30) Kabul
2 : (GMT-09:00) Alaska
3 : (GMT+03:00) Kuwait, Riyadh
4 : (GMT+04:00) Abu Dhabi, Muscat
5 : (GMT+03:00) Baghdad
6 : (GMT-04:00) Atlantic Time (Canada)
7 : (GMT+09:30) Darwin
8 : (GMT+10:00) Canberra, Melbourne, Sydney
9 : (GMT+04:00) Baku
10 : (GMT-01:00) Azores
11 : (GMT-06:00) Saskatchewan
12 : (GMT-01:00) Cape Verde Is.
13 : (GMT+04:00) Yerevan (Do not use)
14 : (GMT+09:30) Adelaide
15 : (GMT-06:00) Central America
16 : (GMT+06:00) Astana, Dhaka
17 : (GMT-04:00) Manaus
18 : (GMT+01:00) Belgrade, Bratislava, Budapest, Ljubljana, Prague
19 : (GMT+01:00) Sarajevo, Skopje, Warsaw, Zagreb
20 : (GMT+11:00) Magadan, Solomon Is., New Caledonia
21 : (GMT-06:00) Central Time (US & Canada)
22 : (GMT-06:00) Guadalajara, Mexico City, Monterrey
23 : (GMT+08:00) Beijing, Chongqing, Hong Kong, Urumqi
24 : (GMT-12:00) International Date Line West
25 : (GMT+03:00) Nairobi
26 : (GMT+10:00) Brisbane
27 : (GMT+02:00) Minsk
28 : (GMT-03:00) Brasilia
29 : (GMT-05:00) Eastern Time (US & Canada)
30 : (GMT+02:00) Cairo
31 : (GMT+05:00) Ekaterinburg
32 : (GMT+12:00) Fiji, Kamchatka, Marshall Is.
33 : (GMT+02:00) Helsinki, Kyiv, Riga, Sofia, Tallinn, Vilnius
34 : (GMT+03:00) Tbilisi
35 : (GMT) Greenwich Mean Time : Dublin, Edinburgh, Lisbon, London
36 : (GMT-03:00) Greenland
37 : (GMT) Casablanca, Monrovia, Reykjavik
38 : (GMT+02:00) Athens, Bucharest, Istanbul
39 : (GMT-10:00) Hawaii
40 : (GMT+05:30) Chennai, Kolkata, Mumbai, New Delhi
41 : (GMT+03:30) Tehran
42 : (GMT+02:00) Jerusalem
43 : (GMT+02:00) Amman
44 : (GMT+09:00) Seoul
45 : (GMT-02:00) Mid-Atlantic
46 : (GMT+02:00) Beirut
47 : (GMT-07:00) Mountain Time (US & Canada)
48 : (GMT-07:00) Chihuahua, La Paz, Mazatlan
49 : (GMT+06:30) Yangon (Rangoon)
50 : (GMT+06:00) Almaty, Novosibirsk
51 : (GMT+02:00) Windhoek
52 : (GMT+05:45) Kathmandu
53 : (GMT+12:00) Auckland, Wellington
54 : (GMT-03:30) Newfoundland
55 : (GMT+08:00) Irkutsk, Ulaan Bataar
56 : (GMT+07:00) Krasnoyarsk
57 : (GMT-04:00) Santiago
58 : (GMT-08:00) Pacific Time (US & Canada)
59 : (GMT-08:00) Tijuana, Baja California
60 : (GMT+01:00) Brussels, Copenhagen, Madrid, Paris
61 : (GMT+04:00) Moscow, St. Petersburg, Volgograd
62 : (GMT-03:00) Buenos Aires, Georgetown
63 : (GMT-05:00) Bogota, Lima, Quito, Rio Branco
64 : (GMT-04:00) La Paz
65 : (GMT+13:00) Samoa
66 : (GMT+07:00) Bangkok, Hanoi, Jakarta
67 : (GMT+08:00) Kuala Lumpur, Singapore
68 : (GMT+02:00) Harare, Pretoria
69 : (GMT+05:30) Sri Jayawardenepura
70 : (GMT+08:00) Taipei
71 : (GMT+10:00) Hobart
72 : (GMT+09:00) Osaka, Sapporo, Tokyo
73 : (GMT+13:00) Nuku'alofa
74 : (GMT-05:00) Indiana (East)
75 : (GMT-07:00) Arizona
76 : (GMT+10:00) Vladivostok
77 : (GMT+08:00) Perth
78 : (GMT+01:00) West Central Africa
79 : (GMT+01:00) Amsterdam, Berlin, Bern, Rome, Stockholm, Vienna
80 : (GMT+05:00) Tashkent
81 : (GMT+10:00) Guam, Port Moresby
82 : (GMT+09:00) Yakutsk
83 : (GMT-03:00) Montevideo
84 : (GMT+04:00) Yerevan
85 : (GMT-04:00) Caracas
86 : (GMT-03:00) Buenos Aires
87 : (GMT-03:00) Salvador
88 : (GMT+06:00) Dhaka
89 : (GMT) Coordinated Universal Time
90 : (GMT+03:00) Kaliningrad, Minsk
91 : (GMT+12:00) Magadan
92 : (GMT+04:00) Port Louis
93 : (GMT) Casablanca
94 : (GMT+05:00) Islamabad, Karachi
95 : (GMT-04:00) Asuncion
96 : (GMT+02:00) Damascus
97 : (GMT+08:00) Ulaanbaatar
98 : (GMT+02:00) Istanbul
99 : (GMT-11:00) Coordinated Universal Time-11
100 : (GMT+12:00) Coordinated Universal Time+12
101 : (GMT+01:00) Tripoli
102 : (GMT+08:45) Australia, Eucla
103 : (GMT+10:30) Australia, Lord Howe
104 : (GMT+11:30) Pacific, Norfolk
105 : (GMT+12:45) Pacific, Chatham
106 : (GMT-09:30) Pacific Marquesas
107 : (GMT+14:00) Line Island
The operating system may reject any unknown/unsupported timezone.
The timezone may also change to another timezone with the same offset."
DEFVAL { 79 }
::= { blueNet2Ntp 3 }
blueNet2MaxNtpServers OBJECT-TYPE
SYNTAX Unsigned32 (1..3)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The maximum number of entries in blueNet2NtpServerTable."
::= { blueNet2Ntp 4 }
blueNet2NtpServerTable OBJECT-TYPE
SYNTAX SEQUENCE OF BlueNet2NtpServerEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A list of NTP server entries."
::= { blueNet2Ntp 5 }
blueNet2NtpServerEntry OBJECT-TYPE
SYNTAX BlueNet2NtpServerEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Entries of NTP server table."
INDEX { blueNet2NtpServerIndex }
::= { blueNet2NtpServerTable 1 }
BlueNet2NtpServerEntry ::=
SEQUENCE {
blueNet2NtpServerIndex Unsigned32,
blueNet2NtpServerRowStatus RowStatus,
blueNet2NtpServerAddress DisplayString,
blueNet2NtpServerFriendlyName DisplayString,
blueNet2NtpServerDescription DisplayString
}
blueNet2NtpServerIndex OBJECT-TYPE
SYNTAX Unsigned32 (1..3)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of the NTP server table."
::= { blueNet2NtpServerEntry 1 }
blueNet2NtpServerRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-create
STATUS current
DESCRIPTION "Activate/create/destroy/disable a NTP server entry."
::= { blueNet2NtpServerEntry 2 }
blueNet2NtpServerAddress OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "IP address or name of NTP server."
::= { blueNet2NtpServerEntry 3 }
blueNet2NtpServerFriendlyName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..128))
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION "User friendly name to identify a ntp server.
This is a mnemonic only and will not be used to query data."
::= { blueNet2NtpServerEntry 4 }
blueNet2NtpServerDescription OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION "Description to identify a ntp server.
This is a mnemonic only and will not be used to query data."
::= { blueNet2NtpServerEntry 5 }
-- -----------------------------------------------------------------------------
blueNet2Smtp OBJECT IDENTIFIER ::= { blueNet2Protocols 15 }
blueNet2SmtpService OBJECT-TYPE
SYNTAX INTEGER {
disabled (1),
enabled (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "SMTP service status."
DEFVAL { disabled }
::= { blueNet2Smtp 1 }
blueNet2SmtpPort OBJECT-TYPE
SYNTAX Unsigned32 (1..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "TCP/IP port of SMTP server."
DEFVAL { 25 }
::= { blueNet2Smtp 2 }
blueNet2SmtpServer OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "IP address or name of SMTP server."
::= { blueNet2Smtp 3 }
blueNet2SmtpAuth OBJECT-TYPE
SYNTAX INTEGER {
disabled (1),
enabled (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "SMTP authentication mode."
DEFVAL { disabled }
::= { blueNet2Smtp 4 }
blueNet2SmtpUsername OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Username required to authenticate at the SMTP server."
::= { blueNet2Smtp 5 }
blueNet2SmtpPassword OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Password required to authenticate at the SMTP server."
::= { blueNet2Smtp 6 }
blueNet2SmtpFrom OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Sender address of the SMTP message."
::= { blueNet2Smtp 7 }
blueNet2SmtpReply OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Reply address of the SMTP message."
::= { blueNet2Smtp 8 }
blueNet2MaxSmtpReceivers OBJECT-TYPE
SYNTAX Unsigned32 (1..256)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The maximum number of entries in blueNet2SmtpReceiverTable."
::= { blueNet2Smtp 9 }
blueNet2SmtpReceiverTable OBJECT-TYPE
SYNTAX SEQUENCE OF BlueNet2SmtpReceiverEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION "A list of SMTP receiver entries."
::= { blueNet2Smtp 10 }
blueNet2SmtpReceiverEntry OBJECT-TYPE
SYNTAX BlueNet2SmtpReceiverEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION "Entries of SMTP receiver table."
INDEX { blueNet2SmtpReceiverIndex }
::= { blueNet2SmtpReceiverTable 1 }
BlueNet2SmtpReceiverEntry ::=
SEQUENCE {
blueNet2SmtpReceiverIndex Unsigned32,
blueNet2SmtpReceiverRowStatus RowStatus,
blueNet2SmtpReceiverAddress DisplayString,
blueNet2SmtpReceiverFriendlyName DisplayString,
blueNet2SmtpReceiverDescription DisplayString
}
blueNet2SmtpReceiverIndex OBJECT-TYPE
SYNTAX Unsigned32 (1..256)
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION "Index of the SMTP receiver table."
::= { blueNet2SmtpReceiverEntry 1 }
blueNet2SmtpReceiverRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-create
STATUS deprecated
DESCRIPTION "Activate/create/destroy/disable a SMTP receiver entry."
::= { blueNet2SmtpReceiverEntry 2 }
blueNet2SmtpReceiverAddress OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION "IP address or name of SMTP receiver."
::= { blueNet2SmtpReceiverEntry 3 }
blueNet2SmtpReceiverFriendlyName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..128))
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION "User friendly name to identify a smtp server.
This is a mnemonic only and will not be used to send data."
::= { blueNet2SmtpReceiverEntry 4 }
blueNet2SmtpReceiverDescription OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION "Description to identify a smtp server.
This is a mnemonic only and will not be used to send data."
::= { blueNet2SmtpReceiverEntry 5 }
-- -----------------------------------------------------------------------------
blueNet2Syslog OBJECT IDENTIFIER ::= { blueNet2Protocols 16 }
blueNet2SyslogService OBJECT-TYPE
SYNTAX INTEGER {
disabled (1),
enabled (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Syslog service status."
DEFVAL { disabled }
::= { blueNet2Syslog 1 }
blueNet2SyslogFacility OBJECT-TYPE
SYNTAX INTEGER {
local0 (1),
local1 (2),
local2 (3),
local3 (4),
local4 (5),
local5 (6),
local6 (7),
local7 (8)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Syslog facility local0 .. local7."
DEFVAL { local0 }
::= { blueNet2Syslog 2 }
blueNet2MaxSyslogServers OBJECT-TYPE
SYNTAX Unsigned32 (1..3)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The maximum number of entries in blueNet2SyslogServerTable."
::= { blueNet2Syslog 3 }
blueNet2SyslogServerTable OBJECT-TYPE
SYNTAX SEQUENCE OF BlueNet2SyslogServerEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A list of syslog server entries."
::= { blueNet2Syslog 4 }
blueNet2SyslogServerEntry OBJECT-TYPE
SYNTAX BlueNet2SyslogServerEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Entries of syslog server table."
INDEX { blueNet2SyslogServerIndex }
::= { blueNet2SyslogServerTable 1 }
BlueNet2SyslogServerEntry ::=
SEQUENCE {
blueNet2SyslogServerIndex Unsigned32,
blueNet2SyslogServerRowStatus RowStatus,
blueNet2SyslogServerAddress DisplayString,
blueNet2SyslogServerPort Unsigned32,
blueNet2SyslogServerFriendlyName DisplayString,
blueNet2SyslogServerDescription DisplayString,
blueNet2SyslogServerProtocol INTEGER
}
blueNet2SyslogServerIndex OBJECT-TYPE
SYNTAX Unsigned32 (1..3)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of the syslog server table."
::= { blueNet2SyslogServerEntry 1 }
blueNet2SyslogServerRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-create
STATUS current
DESCRIPTION "Activate/create/destroy/disable a syslog server entry."
::= { blueNet2SyslogServerEntry 2 }
blueNet2SyslogServerAddress OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "IP address or name of syslog server."
::= { blueNet2SyslogServerEntry 3 }
blueNet2SyslogServerPort OBJECT-TYPE
SYNTAX Unsigned32 (1..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "TCP/IP port of syslog server."
DEFVAL { 514 }
::= { blueNet2SyslogServerEntry 4 }
blueNet2SyslogServerFriendlyName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..128))
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION "User friendly name to identify a syslog server.
This is a mnemonic only and will not be used to send data."
::= { blueNet2SyslogServerEntry 5 }
blueNet2SyslogServerDescription OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION "Description to identify a syslog server.
This is a mnemonic only and will not be used to send data."
::= { blueNet2SyslogServerEntry 6 }
blueNet2SyslogServerProtocol OBJECT-TYPE
SYNTAX INTEGER {
udp (1),
tcp (2),
relp (3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Set TCP/IP protocol of syslog server."
DEFVAL { udp }
::= { blueNet2SyslogServerEntry 7 }
-- =============================================================================
-- blueNet2Devices: global BlueNet2 PDU devices --
blueNet2DeviceInfo OBJECT IDENTIFIER ::= { blueNet2Devices 1 }
blueNet2OverallDeviceStatus OBJECT-TYPE
SYNTAX BlueNet2ComponentStates
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Overall status of all devices."
::= { blueNet2DeviceInfo 1 }
blueNet2NumberOfDevices OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of devices available."
::= { blueNet2DeviceInfo 2 }
blueNet2LastChangeOverallDeviceStatus OBJECT-TYPE
SYNTAX TimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timestamp of last status change of any device connected to BlueNet2 PDU
according to operating time sysUpTime."
::= { blueNet2DeviceInfo 3 }
blueNet2LastChangeNumberOfDevices OBJECT-TYPE
SYNTAX TimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timestamp of last device number change
according to operating time sysUpTime."
::= { blueNet2DeviceInfo 4 }
blueNet2LastChangeDeviceSettings OBJECT-TYPE
SYNTAX TimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timestamp of last setting change of any device connected to BlueNet2 PDU
according to operating time sysUpTime.
This timestamp will be affected by SNMP settings only!"
::= { blueNet2DeviceInfo 5 }
blueNet2LastChangeDevices OBJECT-TYPE
SYNTAX TimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timestamp of last device change
according to operating time sysUpTime."
::= { blueNet2DeviceInfo 6 }
blueNet2DevicesAccumulatedStatus OBJECT-TYPE
SYNTAX BlueNet2EntityBits
MAX-ACCESS read-only
STATUS current
DESCRIPTION "A bit field of all current device states."
::= { blueNet2DeviceInfo 7 }
-- -----------------------------------------------------------------------------
blueNet2DeviceTable OBJECT-TYPE
SYNTAX SEQUENCE OF BlueNet2DeviceEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Headline of device table."
::= { blueNet2Devices 2 }
blueNet2DeviceEntry OBJECT-TYPE
SYNTAX BlueNet2DeviceEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Entries of device table."
INDEX { blueNet2DeviceIndex }
::= { blueNet2DeviceTable 1 }
BlueNet2DeviceEntry ::=
SEQUENCE {
blueNet2DeviceIndex Unsigned32,
blueNet2DeviceGuid OCTET STRING,
blueNet2DeviceName DisplayString,
blueNet2DeviceFriendlyName DisplayString,
blueNet2DeviceDescription DisplayString,
blueNet2DeviceType OBJECT IDENTIFIER,
blueNet2DeviceStatus BlueNet2EntityStates,
blueNet2DeviceAlarm DisplayString,
blueNet2DeviceLastChange TimeTicks,
blueNet2DeviceEntPhysicalIndex Unsigned32,
blueNet2DevicePartNr DisplayString,
blueNet2DeviceSNr DisplayString,
blueNet2DeviceFwV DisplayString,
blueNet2DeviceHwV DisplayString,
blueNet2DeviceSwV DisplayString,
blueNet2DeviceOsV DisplayString,
blueNet2DeviceMAC DisplayString,
blueNet2DeviceNumberOfSensors Unsigned32,
blueNet2DeviceNumberOfCircuits Unsigned32,
blueNet2DeviceNumberOfPhases Unsigned32,
blueNet2DeviceNumberOfFuses Unsigned32,
blueNet2DeviceNumberOfSockets Unsigned32,
blueNet2DeviceNumberOfRCMs Unsigned32,
blueNet2DeviceNumberOfVars Unsigned32,
blueNet2DeviceLocation DisplayString,
blueNet2DeviceProductDate DisplayString,
blueNet2DeviceModbusAddr Integer32,
blueNet2DeviceNumberOfSPDs Unsigned32
}
blueNet2DeviceIndex OBJECT-TYPE
SYNTAX Unsigned32 (1..11)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of device connected to BlueNet2 PDU."
::= { blueNet2DeviceEntry 1 }
blueNet2DeviceGuid OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (8..8))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "GUID of device connected to BlueNet2 PDU."
::= { blueNet2DeviceEntry 2 }
blueNet2DeviceName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..40))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Name of the device connected to BlueNet2 PDU."
::= { blueNet2DeviceEntry 3 }
blueNet2DeviceFriendlyName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..128))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "User friendlyname of the device connected to BlueNet2 PDU."
::= { blueNet2DeviceEntry 4 }
blueNet2DeviceDescription OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Description of the device connected to BlueNet2 PDU."
::= { blueNet2DeviceEntry 5 }
blueNet2DeviceType OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of device connected to BlueNet2 PDU."
::= { blueNet2DeviceEntry 6 }
blueNet2DeviceStatus OBJECT-TYPE
SYNTAX BlueNet2EntityStates
MAX-ACCESS read-only
STATUS current
DESCRIPTION "General status of device connected to BlueNet2 PDU."
::= { blueNet2DeviceEntry 7 }
blueNet2DeviceAlarm OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION "Alarm text of device connected to BlueNet2 PDU.
This field is deprecated and is not filled."
::= { blueNet2DeviceEntry 8 }
blueNet2DeviceLastChange OBJECT-TYPE
SYNTAX TimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timestamp of last change of device connected to BlueNet2 PDU
according to operating time sysUpTime."
::= { blueNet2DeviceEntry 9 }
blueNet2DeviceEntPhysicalIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Corresponding entPhysicalIndex of this device. 0 if none exists."
::= { blueNet2DeviceEntry 10 }
blueNet2DevicePartNr OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Article part number of device connected to BlueNet2 PDU."
::= { blueNet2DeviceEntry 11 }
blueNet2DeviceSNr OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Serial number of device connected to BlueNet2 PDU."
::= { blueNet2DeviceEntry 12 }
blueNet2DeviceFwV OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Firmware version of device connected to BlueNet2 PDU."
::= { blueNet2DeviceEntry 13 }
blueNet2DeviceHwV OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Hardware version of device connected to BlueNet2 PDU."
::= { blueNet2DeviceEntry 14 }
blueNet2DeviceSwV OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Software version of device connected to BlueNet2 PDU."
::= { blueNet2DeviceEntry 15 }
blueNet2DeviceOsV OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Operating system version of device connected to BlueNet2 PDU."
::= { blueNet2DeviceEntry 16 }
blueNet2DeviceMAC OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "MAC address of device connected to BlueNet2 PDU."
::= { blueNet2DeviceEntry 17 }
blueNet2DeviceNumberOfSensors OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of sensors available on this device.
This variable will give the number of rows of the
sensor table blueNet2SensorTable belonging to this device."
::= { blueNet2DeviceEntry 18 }
blueNet2DeviceNumberOfCircuits OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of circuits available in this device.
This variable will give the number of rows of the circuit
table blueNet2CircuitTable belonging to this device."
::= { blueNet2DeviceEntry 19 }
blueNet2DeviceNumberOfPhases OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of phases available in this device.
This variable will give the number of rows of the phases
table blueNet2PhaseTable belonging to this device."
::= { blueNet2DeviceEntry 20 }
blueNet2DeviceNumberOfFuses OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of fuses available in this device.
This variable will give the number of rows of the fuse
table blueNet2FuseTable belonging to this device."
::= { blueNet2DeviceEntry 21 }
blueNet2DeviceNumberOfSockets OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of sockets available in this device.
This variable will give the number of rows of the socket
table blueNet2SocketTable belonging to this device."
::= { blueNet2DeviceEntry 22 }
blueNet2DeviceNumberOfRCMs OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of RCMs available in this device.
This variable will give the number of rows of the RCM
table blueNet2RcmTable belonging to this device."
::= { blueNet2DeviceEntry 23 }
blueNet2DeviceNumberOfVars OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of variables available in this device.
This variable will give the number of rows of the variable
table blueNet2VariableTable belonging to this device."
::= { blueNet2DeviceEntry 24 }
blueNet2DeviceLocation OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Location of device connected to BlueNet2 PDU."
::= { blueNet2DeviceEntry 25 }
blueNet2DeviceProductDate OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Device Production Date."
::= { blueNet2DeviceEntry 26 }
blueNet2DeviceModbusAddr OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Device Modbus Address."
::= { blueNet2DeviceEntry 27 }
blueNet2DeviceNumberOfSPDs OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of SPDs available in this device.
This variable will give the number of rows of the SPD
table blueNet2SpdTable belonging to this device."
::= { blueNet2DeviceEntry 28 }
-- =============================================================================
-- blueNet2Sensors: BlueNet2 PDU sensors --
blueNet2SensorInfo OBJECT IDENTIFIER ::= { blueNet2Sensors 1 }
blueNet2OverallSensorStatus OBJECT-TYPE
SYNTAX BlueNet2ComponentStates
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Overall status of all sensors."
::= { blueNet2SensorInfo 1 }
blueNet2NumberOfSensors OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of sensors available."
::= { blueNet2SensorInfo 2 }
blueNet2LastChangeOverallSensorStatus OBJECT-TYPE
SYNTAX TimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timestamp of last status change of any sensor connected to BlueNet2 PDU
according to operating time sysUpTime."
::= { blueNet2SensorInfo 3 }
blueNet2LastChangeNumberOfSensors OBJECT-TYPE
SYNTAX TimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timestamp of last sensor number change
according to operating time sysUpTime."
::= { blueNet2SensorInfo 4 }
blueNet2LastChangeSensorSettings OBJECT-TYPE
SYNTAX TimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timestamp of last setting change of any sensor connected to BlueNet2 PDU
according to operating time sysUpTime.
This timestamp will be affected by SNMP settings only!"
::= { blueNet2SensorInfo 5 }
blueNet2LastChangeSensors OBJECT-TYPE
SYNTAX TimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timestamp of last sensor change
according to operating time sysUpTime."
::= { blueNet2SensorInfo 6 }
blueNet2SensorsAccumulatedStatus OBJECT-TYPE
SYNTAX BlueNet2EntityBits
MAX-ACCESS read-only
STATUS current
DESCRIPTION "A bit field of all current sensor states."
::= { blueNet2SensorInfo 7 }
-- -----------------------------------------------------------------------------
blueNet2SensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF BlueNet2SensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Headline of sensor table."
::= { blueNet2Sensors 2 }
blueNet2SensorEntry OBJECT-TYPE
SYNTAX BlueNet2SensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Entries of sensor table."
INDEX { blueNet2SensorDevice,blueNet2SensorIndex }
::= { blueNet2SensorTable 1 }
BlueNet2SensorEntry ::=
SEQUENCE {
blueNet2SensorDevice Unsigned32,
blueNet2SensorIndex Unsigned32,
blueNet2SensorGuid OCTET STRING,
blueNet2SensorName DisplayString,
blueNet2SensorFriendlyName DisplayString,
blueNet2SensorDescription DisplayString,
blueNet2SensorType OBJECT IDENTIFIER,
blueNet2SensorStatus BlueNet2EntityStates,
blueNet2SensorAlarm DisplayString,
blueNet2SensorLastChange TimeTicks,
blueNet2SensorEntPhysicalIndex Unsigned32,
blueNet2SensorNumberOfVars Unsigned32,
blueNet2SensorHwV DisplayString,
blueNet2SensorFwV DisplayString,
blueNet2SensorSNr DisplayString
}
blueNet2SensorDevice OBJECT-TYPE
SYNTAX Unsigned32 (1..11)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of device connected to BlueNet2 PDU."
::= { blueNet2SensorEntry 1 }
blueNet2SensorIndex OBJECT-TYPE
SYNTAX Unsigned32 (1..8)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of sensor connected to BlueNet2 PDU."
::= { blueNet2SensorEntry 2 }
blueNet2SensorGuid OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (8..8))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "GUID of sensor connected to BlueNet2 PDU."
::= { blueNet2SensorEntry 3 }
blueNet2SensorName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..40))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Name of the sensor connected to BlueNet2 PDU."
::= { blueNet2SensorEntry 4 }
blueNet2SensorFriendlyName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..128))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "User friendlyname of the sensor connected to BlueNet2 PDU."
::= { blueNet2SensorEntry 5 }
blueNet2SensorDescription OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Description of the sensor connected to BlueNet2 PDU."
::= { blueNet2SensorEntry 6 }
blueNet2SensorType OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of of sensor connected to BlueNet2 PDU."
::= { blueNet2SensorEntry 7 }
blueNet2SensorStatus OBJECT-TYPE
SYNTAX BlueNet2EntityStates
MAX-ACCESS read-only
STATUS current
DESCRIPTION "General Status of sensor connected to BlueNet2 PDU."
::= { blueNet2SensorEntry 8 }
blueNet2SensorAlarm OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm text of sensor connected to BlueNet2 PDU."
::= { blueNet2SensorEntry 9 }
blueNet2SensorLastChange OBJECT-TYPE
SYNTAX TimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timestamp of last change of sensor connected to BlueNet2 PDU
according to operating time sysUpTime."
::= { blueNet2SensorEntry 10 }
blueNet2SensorEntPhysicalIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Corresponding entPhysicalIndex of this sensor. 0 if none exists."
::= { blueNet2SensorEntry 11 }
blueNet2SensorNumberOfVars OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of variables available on this sensor.
This variable will give the number of rows of the
variable table blueNet2SensorVarTable belonging to this sensor."
::= { blueNet2SensorEntry 12 }
blueNet2SensorHwV OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Hardware version of the sensor."
::= { blueNet2SensorEntry 13 }
blueNet2SensorFwV OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Firmware version of the sensor."
::= { blueNet2SensorEntry 14 }
blueNet2SensorSNr OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Serial number of the sensor."
::= { blueNet2SensorEntry 15 }
-- -----------------------------------------------------------------------------
blueNet2SensorVariableTable OBJECT-TYPE
SYNTAX SEQUENCE OF BlueNet2SensorVariableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Headline of sensor variable table."
::= { blueNet2Sensors 3 }
blueNet2SensorVariableEntry OBJECT-TYPE
SYNTAX BlueNet2SensorVariableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Entries of sensor variable table."
INDEX { blueNet2SensorDeviceIndex,blueNet2SensorSensorIndex,blueNet2SensorVariableIndex }
::= { blueNet2SensorVariableTable 1 }
BlueNet2SensorVariableEntry ::=
SEQUENCE {
blueNet2SensorDeviceIndex Unsigned32,
blueNet2SensorSensorIndex Unsigned32,
blueNet2SensorVariableIndex Unsigned32,
blueNet2SensorVariableGuid OCTET STRING,
blueNet2SensorVariableName DisplayString,
blueNet2SensorVariableFriendlyName DisplayString,
blueNet2SensorVariableDescription DisplayString,
blueNet2SensorVariableGPIOMode BlueNet2GPIOModes,
blueNet2SensorVariableGPIOSwitch BlueNet2GPIOSwitch,
blueNet2SensorVariableGPIOState BlueNet2EntityStates
}
blueNet2SensorDeviceIndex OBJECT-TYPE
SYNTAX Unsigned32 (1..11)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of sensor connected."
::= { blueNet2SensorVariableEntry 1 }
blueNet2SensorSensorIndex OBJECT-TYPE
SYNTAX Unsigned32 (1..8)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of sensor connected."
::= { blueNet2SensorVariableEntry 2 }
blueNet2SensorVariableIndex OBJECT-TYPE
SYNTAX Unsigned32 (1..8)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of sensor variable."
::= { blueNet2SensorVariableEntry 3 }
blueNet2SensorVariableGuid OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (8..8))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "GUID of sensor connected to BlueNet2 PDU."
::= { blueNet2SensorVariableEntry 4 }
blueNet2SensorVariableName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..40))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Name of the sensor variable."
::= { blueNet2SensorVariableEntry 5 }
blueNet2SensorVariableFriendlyName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..128))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "User friendlyname of the sensor variable."
::= { blueNet2SensorVariableEntry 6 }
blueNet2SensorVariableDescription OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Description of the sensor variable."
::= { blueNet2SensorVariableEntry 7 }
blueNet2SensorVariableGPIOMode OBJECT-TYPE
SYNTAX BlueNet2GPIOModes
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Mode of the GPIO sensor connected to BlueNet2 PDU."
::= { blueNet2SensorVariableEntry 8 }
blueNet2SensorVariableGPIOSwitch OBJECT-TYPE
SYNTAX BlueNet2GPIOSwitch
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Switch on/off the GPIO Outputs."
::= { blueNet2SensorVariableEntry 9 }
blueNet2SensorVariableGPIOState OBJECT-TYPE
SYNTAX BlueNet2EntityStates
MAX-ACCESS read-only
STATUS current
DESCRIPTION "State of GPIO inputs/outputs"
::= { blueNet2SensorVariableEntry 10 }
-- =============================================================================
-- blueNet2Circuits: BlueNet2 PDU Circuits --
blueNet2CircuitInfo OBJECT IDENTIFIER ::= { blueNet2Circuits 1 }
blueNet2OverallCircuitStatus OBJECT-TYPE
SYNTAX BlueNet2ComponentStates
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Overall status of all circuits."
::= { blueNet2CircuitInfo 1 }
blueNet2NumberOfCircuits OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of circuits available."
::= { blueNet2CircuitInfo 2 }
blueNet2LastChangeOverallCircuitStatus OBJECT-TYPE
SYNTAX TimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timestamp of last status change of any circuit connected to BlueNet2 PDU
according to operating time sysUpTime."
::= { blueNet2CircuitInfo 3 }
blueNet2LastChangeNumberOfCircuits OBJECT-TYPE
SYNTAX TimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timestamp of last circuit number change
according to operating time sysUpTime."
::= { blueNet2CircuitInfo 4 }
blueNet2LastChangeCircuitSettings OBJECT-TYPE
SYNTAX TimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timestamp of last setting change of any circuit connected to BlueNet2 PDU
according to operating time sysUpTime.
This timestamp will be affected by SNMP settings only!"
::= { blueNet2CircuitInfo 5 }
blueNet2LastChangeCircuits OBJECT-TYPE
SYNTAX TimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timestamp of last circuit change
according to operating time sysUpTime."
::= { blueNet2CircuitInfo 6 }
-- -----------------------------------------------------------------------------
blueNet2CircuitTable OBJECT-TYPE
SYNTAX SEQUENCE OF BlueNet2CircuitEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Headline of circuit table."
::= { blueNet2Circuits 2 }
blueNet2CircuitEntry OBJECT-TYPE
SYNTAX BlueNet2CircuitEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Entries of circuit table."
INDEX { blueNet2CircuitDevice,blueNet2CircuitIndex }
::= { blueNet2CircuitTable 1 }
BlueNet2CircuitEntry ::=
SEQUENCE {
blueNet2CircuitDevice Unsigned32,
blueNet2CircuitIndex Unsigned32,
blueNet2CircuitGuid OCTET STRING,
blueNet2CircuitName DisplayString,
blueNet2CircuitFriendlyName DisplayString,
blueNet2CircuitDescription DisplayString,
blueNet2CircuitType OBJECT IDENTIFIER,
blueNet2CircuitStatus BlueNet2EntityStates,
blueNet2CircuitNumberOfPhases Unsigned32
}
blueNet2CircuitDevice OBJECT-TYPE
SYNTAX Unsigned32 (1..11)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of device connected to BlueNet2 PDU."
::= { blueNet2CircuitEntry 1 }
blueNet2CircuitIndex OBJECT-TYPE
SYNTAX Unsigned32 (1..2)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of circuit connected to BlueNet2 PDU."
::= { blueNet2CircuitEntry 2 }
blueNet2CircuitGuid OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (8..8))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "GUID of circuit connected to BlueNet2 PDU."
::= { blueNet2CircuitEntry 3 }
blueNet2CircuitName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..40))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Name of the circuit connected to BlueNet2 PDU."
::= { blueNet2CircuitEntry 4 }
blueNet2CircuitFriendlyName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..128))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "User friendlyname of the circuit connected to BlueNet2 PDU."
::= { blueNet2CircuitEntry 5 }
blueNet2CircuitDescription OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Description of the circuit connected to BlueNet2 PDU."
::= { blueNet2CircuitEntry 6 }
blueNet2CircuitType OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of circuit connected to BlueNet2 PDU."
::= { blueNet2CircuitEntry 7 }
blueNet2CircuitStatus OBJECT-TYPE
SYNTAX BlueNet2EntityStates
MAX-ACCESS read-only
STATUS current
DESCRIPTION "General status of the entity providing the status of a
circuit connected to BlueNet2 PDU in blueNet2VariableStatus."
::= { blueNet2CircuitEntry 8 }
blueNet2CircuitNumberOfPhases OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of phases of circuit connected to BlueNet2 PDU."
::= { blueNet2CircuitEntry 9 }
-- -----------------------------------------------------------------------------
blueNet2PhaseTable OBJECT-TYPE
SYNTAX SEQUENCE OF BlueNet2PhaseEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Headline of phase table."
::= { blueNet2Circuits 3 }
blueNet2PhaseEntry OBJECT-TYPE
SYNTAX BlueNet2PhaseEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Entries of phase table."
INDEX { blueNet2PhaseDevice,blueNet2PhaseCircuit,blueNet2PhaseIndex }
::= { blueNet2PhaseTable 1 }
BlueNet2PhaseEntry ::=
SEQUENCE {
blueNet2PhaseDevice Unsigned32,
blueNet2PhaseCircuit Unsigned32,
blueNet2PhaseIndex Unsigned32,
blueNet2PhaseGuid OCTET STRING,
blueNet2PhaseName DisplayString,
blueNet2PhaseFriendlyName DisplayString,
blueNet2PhaseDescription DisplayString,
blueNet2PhaseStatus BlueNet2EntityStates,
blueNet2PhaseNumberOfFuses Unsigned32
}
blueNet2PhaseDevice OBJECT-TYPE
SYNTAX Unsigned32 (1..11)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of device connected to BlueNet2 PDU."
::= { blueNet2PhaseEntry 1 }
blueNet2PhaseCircuit OBJECT-TYPE
SYNTAX Unsigned32 (1..2)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of circuit connected to BlueNet2 PDU."
::= { blueNet2PhaseEntry 2 }
blueNet2PhaseIndex OBJECT-TYPE
SYNTAX Unsigned32 (1..3)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of phase connected to BlueNet2 PDU."
::= { blueNet2PhaseEntry 3 }
blueNet2PhaseGuid OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (8..8))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "GUID of phase connected to BlueNet2 PDU."
::= { blueNet2PhaseEntry 4 }
blueNet2PhaseName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..40))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Name of the phase connected to BlueNet2 PDU."
::= { blueNet2PhaseEntry 5 }
blueNet2PhaseFriendlyName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..128))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "User friendlyname of the phase connected to BlueNet2 PDU."
::= { blueNet2PhaseEntry 6 }
blueNet2PhaseDescription OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Description of the phase connected to BlueNet2 PDU."
::= { blueNet2PhaseEntry 7 }
blueNet2PhaseStatus OBJECT-TYPE
SYNTAX BlueNet2EntityStates
MAX-ACCESS read-only
STATUS current
DESCRIPTION "General status of the entity providing the status of a
phase connected to BlueNet2 PDU in blueNet2VariableStatus."
::= { blueNet2PhaseEntry 8 }
blueNet2PhaseNumberOfFuses OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of fuses of phase connected to BlueNet2 PDU."
::= { blueNet2PhaseEntry 9 }
-- -----------------------------------------------------------------------------
blueNet2FuseTable OBJECT-TYPE
SYNTAX SEQUENCE OF BlueNet2FuseEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Headline of fuse table."
::= { blueNet2Circuits 4 }
blueNet2FuseEntry OBJECT-TYPE
SYNTAX BlueNet2FuseEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Entries of fuse table."
INDEX { blueNet2FuseDevice,blueNet2FuseCircuit,blueNet2FusePhase,blueNet2FuseIndex }
::= { blueNet2FuseTable 1 }
BlueNet2FuseEntry ::=
SEQUENCE {
blueNet2FuseDevice Unsigned32,
blueNet2FuseCircuit Unsigned32,
blueNet2FusePhase Unsigned32,
blueNet2FuseIndex Unsigned32,
blueNet2FuseGuid OCTET STRING,
blueNet2FuseName DisplayString,
blueNet2FuseFriendlyName DisplayString,
blueNet2FuseDescription DisplayString,
blueNet2FuseType OBJECT IDENTIFIER,
blueNet2FuseStatus BlueNet2EntityStates,
blueNet2FuseNumberOfSockets Unsigned32
}
blueNet2FuseDevice OBJECT-TYPE
SYNTAX Unsigned32 (1..11)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of device connected to BlueNet2 PDU."
::= { blueNet2FuseEntry 1 }
blueNet2FuseCircuit OBJECT-TYPE
SYNTAX Unsigned32 (1..2)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of circuit connected to BlueNet2 PDU."
::= { blueNet2FuseEntry 2 }
blueNet2FusePhase OBJECT-TYPE
SYNTAX Unsigned32 (1..3)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of phase connected to BlueNet2 PDU."
::= { blueNet2FuseEntry 3 }
blueNet2FuseIndex OBJECT-TYPE
SYNTAX Unsigned32 (1..4)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of phase connected to BlueNet2 PDU."
::= { blueNet2FuseEntry 4 }
blueNet2FuseGuid OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (8..8))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "GUID of fuse connected to BlueNet2 PDU."
::= { blueNet2FuseEntry 5 }
blueNet2FuseName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..40))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Name of the fuse connected to BlueNet2 PDU."
::= { blueNet2FuseEntry 6 }
blueNet2FuseFriendlyName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..128))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "User friendlyname of the fuse connected to BlueNet2 PDU."
::= { blueNet2FuseEntry 7 }
blueNet2FuseDescription OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Description of the fuse connected to BlueNet2 PDU."
::= { blueNet2FuseEntry 8 }
blueNet2FuseType OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of the fuse connected to BlueNet2 PDU."
::= { blueNet2FuseEntry 9 }
blueNet2FuseStatus OBJECT-TYPE
SYNTAX BlueNet2EntityStates
MAX-ACCESS read-only
STATUS current
DESCRIPTION "General status of the entity providing the status of a
fuse connected to BlueNet2 PDU in blueNet2VariableStatus."
::= { blueNet2FuseEntry 10 }
blueNet2FuseNumberOfSockets OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of sockets of fuse connected to BlueNet2 PDU."
::= { blueNet2FuseEntry 11 }
-- -----------------------------------------------------------------------------
blueNet2SocketTable OBJECT-TYPE
SYNTAX SEQUENCE OF BlueNet2SocketEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Headline of socket table."
::= { blueNet2Circuits 5 }
blueNet2SocketEntry OBJECT-TYPE
SYNTAX BlueNet2SocketEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Entries of socket table."
INDEX { blueNet2SocketDevice,blueNet2SocketCircuit,blueNet2SocketPhase,blueNet2SocketIndex }
::= { blueNet2SocketTable 1 }
BlueNet2SocketEntry ::=
SEQUENCE {
blueNet2SocketDevice Unsigned32,
blueNet2SocketCircuit Unsigned32,
blueNet2SocketPhase Unsigned32,
blueNet2SocketFuse Unsigned32,
blueNet2SocketIndex Unsigned32,
blueNet2SocketGuid OCTET STRING,
blueNet2SocketName DisplayString,
blueNet2SocketFriendlyName DisplayString,
blueNet2SocketDescription DisplayString,
blueNet2SocketType OBJECT IDENTIFIER,
blueNet2SocketStatus BlueNet2EntityStates,
blueNet2SocketMode BlueNet2SocketModes,
blueNet2SocketIdentify BlueNet2SocketModes,
blueNet2SocketMemberIndex Unsigned32
}
blueNet2SocketDevice OBJECT-TYPE
SYNTAX Unsigned32 (1..11)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of device connected to BlueNet2 PDU."
::= { blueNet2SocketEntry 1 }
blueNet2SocketCircuit OBJECT-TYPE
SYNTAX Unsigned32 (1..2)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of circuit connected to BlueNet2 PDU."
::= { blueNet2SocketEntry 2 }
blueNet2SocketPhase OBJECT-TYPE
SYNTAX Unsigned32 (0..3)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of phase connected to BlueNet2 PDU."
::= { blueNet2SocketEntry 3 }
blueNet2SocketFuse OBJECT-TYPE
SYNTAX Unsigned32 (1..4)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of fuse connected to BlueNet2 PDU."
::= { blueNet2SocketEntry 4 }
blueNet2SocketIndex OBJECT-TYPE
SYNTAX Unsigned32 (0..24)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of socket connected to BlueNet2 PDU."
::= { blueNet2SocketEntry 5 }
blueNet2SocketGuid OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (8..8))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "GUID of socket connected to BlueNet2 PDU."
::= { blueNet2SocketEntry 6 }
blueNet2SocketName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..40))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Name of the socket connected to BlueNet2 PDU."
::= { blueNet2SocketEntry 7 }
blueNet2SocketFriendlyName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..128))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "User friendlyname of the socket connected to BlueNet2 PDU."
::= { blueNet2SocketEntry 8 }
blueNet2SocketDescription OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Description of the socket connected to BlueNet2 PDU."
::= { blueNet2SocketEntry 9 }
blueNet2SocketType OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of the socket connected to BlueNet2 PDU."
::= { blueNet2SocketEntry 10 }
blueNet2SocketStatus OBJECT-TYPE
SYNTAX BlueNet2EntityStates
MAX-ACCESS read-only
STATUS current
DESCRIPTION "General status of the entity providing the status of a
socket connected to BlueNet2 PDU in blueNet2VariableStatus."
::= { blueNet2SocketEntry 11 }
blueNet2SocketMode OBJECT-TYPE
SYNTAX BlueNet2SocketModes
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Mode of the socket connected to BlueNet2 PDU."
::= { blueNet2SocketEntry 12 }
blueNet2SocketIdentify OBJECT-TYPE
SYNTAX BlueNet2SocketModes
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Mode of the sockets LED connected to BlueNet2 PDU."
::= { blueNet2SocketEntry 13 }
blueNet2SocketMemberIndex OBJECT-TYPE
SYNTAX Unsigned32 (1..2048)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Index of this socket to be used in blueNet2SocketGroupMembers."
::= { blueNet2SocketEntry 14 }
-- -----------------------------------------------------------------------------
blueNet2RcmTable OBJECT-TYPE
SYNTAX SEQUENCE OF BlueNet2RCMEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Headline of rcm table."
::= { blueNet2Circuits 6 }
blueNet2RcmEntry OBJECT-TYPE
SYNTAX BlueNet2RCMEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Entries of rcm table."
INDEX { blueNet2RcmDevice,blueNet2RcmCircuit,blueNet2RcmPhase,blueNet2RcmFuse,blueNet2RcmSocket,blueNet2RcmIndex }
::= { blueNet2RcmTable 1 }
BlueNet2RCMEntry ::=
SEQUENCE {
blueNet2RcmDevice Unsigned32,
blueNet2RcmCircuit Unsigned32,
blueNet2RcmPhase Unsigned32,
blueNet2RcmFuse Unsigned32,
blueNet2RcmSocket Unsigned32,
blueNet2RcmIndex Unsigned32,
blueNet2RcmGuid OCTET STRING,
blueNet2RcmName DisplayString,
blueNet2RcmFriendlyName DisplayString,
blueNet2RcmDescription DisplayString,
blueNet2RcmType OBJECT IDENTIFIER,
blueNet2RcmStatus BlueNet2EntityStates,
blueNet2RcmSelftestCommand BlueNet2RcmSelftestCommand,
blueNet2RcmSelftestResultValue BlueNet2RcmSelftestResult,
blueNet2RcmSelftestResultACvalue BlueNet2RcmSelftestResult,
blueNet2RcmSelftestResultDCvalue BlueNet2RcmSelftestResult,
blueNet2RcmSelftestTimeStamp DateAndTime,
blueNet2RcmSelftestResultStr DisplayString
}
blueNet2RcmDevice OBJECT-TYPE
SYNTAX Unsigned32 (0..11)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of device connected to BlueNet2 PDU."
::= { blueNet2RcmEntry 1 }
blueNet2RcmCircuit OBJECT-TYPE
SYNTAX Unsigned32 (0..2)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of circuit connected to BlueNet2 PDU."
::= { blueNet2RcmEntry 2 }
blueNet2RcmPhase OBJECT-TYPE
SYNTAX Unsigned32 (0..3)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of phase connected to BlueNet2 PDU."
::= { blueNet2RcmEntry 3 }
blueNet2RcmFuse OBJECT-TYPE
SYNTAX Unsigned32 (0..4)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of fuse connected to BlueNet2 PDU."
::= { blueNet2RcmEntry 4 }
blueNet2RcmSocket OBJECT-TYPE
SYNTAX Unsigned32 (0..24)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of socket connected to BlueNet2 PDU."
::= { blueNet2RcmEntry 5 }
blueNet2RcmIndex OBJECT-TYPE
SYNTAX Unsigned32 (0..24)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of RCM connected to BlueNet2 PDU."
::= { blueNet2RcmEntry 6 }
blueNet2RcmGuid OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (8..8))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "GUID of RCM connected to BlueNet2 PDU."
::= { blueNet2RcmEntry 7 }
blueNet2RcmName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..40))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Name of the RCM connected to BlueNet2 PDU."
::= { blueNet2RcmEntry 8 }
blueNet2RcmFriendlyName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..128))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "User friendlyname of the RCM connected to BlueNet2 PDU."
::= { blueNet2RcmEntry 9 }
blueNet2RcmDescription OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Description of the RCM connected to BlueNet2 PDU."
::= { blueNet2RcmEntry 10 }
blueNet2RcmType OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of the rcm connected to BlueNet2 PDU."
::= { blueNet2RcmEntry 11 }
blueNet2RcmStatus OBJECT-TYPE
SYNTAX BlueNet2EntityStates
MAX-ACCESS read-only
STATUS current
DESCRIPTION "General status of the entity providing the status of a
Rcm connected to BlueNet2 PDU in blueNet2VariableStatus."
::= { blueNet2RcmEntry 12 }
blueNet2RcmSelftestCommand OBJECT-TYPE
SYNTAX BlueNet2RcmSelftestCommand
MAX-ACCESS read-write
STATUS current
DESCRIPTION "RCM self-test commands."
::= { blueNet2RcmEntry 13 }
blueNet2RcmSelftestResultValue OBJECT-TYPE
SYNTAX BlueNet2RcmSelftestResult
MAX-ACCESS read-only
STATUS current
DESCRIPTION "RCM self-test result value."
::= { blueNet2RcmEntry 14 }
blueNet2RcmSelftestResultACvalue OBJECT-TYPE
SYNTAX BlueNet2RcmSelftestResult
MAX-ACCESS read-only
STATUS current
DESCRIPTION "RCM self-test AC result value."
::= { blueNet2RcmEntry 15 }
blueNet2RcmSelftestResultDCvalue OBJECT-TYPE
SYNTAX BlueNet2RcmSelftestResult
MAX-ACCESS read-only
STATUS current
DESCRIPTION "RCM self-test DC result value."
::= { blueNet2RcmEntry 16 }
blueNet2RcmSelftestTimeStamp OBJECT-TYPE
SYNTAX DateAndTime
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timestamp of RCM self-test."
::= { blueNet2RcmEntry 17 }
blueNet2RcmSelftestResultStr OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "RCM Selftest result as string."
::= { blueNet2RcmEntry 18 }
-- -----------------------------------------------------------------------------
blueNet2SpdTable OBJECT-TYPE
SYNTAX SEQUENCE OF BlueNet2SpdEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Headline of SPD table."
::= { blueNet2Circuits 7 }
blueNet2SpdEntry OBJECT-TYPE
SYNTAX BlueNet2SpdEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Entries of spd table."
INDEX { blueNet2SpdDevice,blueNet2SpdCircuit,blueNet2SpdPhase,blueNet2SpdFuse,blueNet2SpdSocket,blueNet2SpdIndex }
::= { blueNet2SpdTable 1 }
BlueNet2SpdEntry ::=
SEQUENCE {
blueNet2SpdDevice Unsigned32,
blueNet2SpdCircuit Unsigned32,
blueNet2SpdPhase Unsigned32,
blueNet2SpdFuse Unsigned32,
blueNet2SpdSocket Unsigned32,
blueNet2SpdIndex Unsigned32,
blueNet2SpdGuid OCTET STRING,
blueNet2SpdName DisplayString,
blueNet2SpdFriendlyName DisplayString,
blueNet2SpdDescription DisplayString,
blueNet2SpdType OBJECT IDENTIFIER,
blueNet2SpdStatus BlueNet2EntityStates
}
blueNet2SpdDevice OBJECT-TYPE
SYNTAX Unsigned32 (1..11)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of device connected to BlueNet2 PDU."
::= { blueNet2SpdEntry 1 }
blueNet2SpdCircuit OBJECT-TYPE
SYNTAX Unsigned32 (1..2)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of circuit connected to BlueNet2 PDU."
::= { blueNet2SpdEntry 2 }
blueNet2SpdPhase OBJECT-TYPE
SYNTAX Unsigned32 (0..3)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of phase connected to BlueNet2 PDU."
::= { blueNet2SpdEntry 3 }
blueNet2SpdFuse OBJECT-TYPE
SYNTAX Unsigned32 (0..4)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of fuse connected to BlueNet2 PDU."
::= { blueNet2SpdEntry 4 }
blueNet2SpdSocket OBJECT-TYPE
SYNTAX Unsigned32 (0..48)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of socket connected to BlueNet2 PDU."
::= { blueNet2SpdEntry 5 }
blueNet2SpdIndex OBJECT-TYPE
SYNTAX Unsigned32 (1..3)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of SPD connected to BlueNet2 PDU."
::= { blueNet2SpdEntry 6 }
blueNet2SpdGuid OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (8..8))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "GUID of SPD connected to BlueNet2 PDU."
::= { blueNet2SpdEntry 7 }
blueNet2SpdName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..40))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Name of the SPD connected to BlueNet2 PDU."
::= { blueNet2SpdEntry 8 }
blueNet2SpdFriendlyName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..128))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "User friendlyname of the SPD connected to BlueNet2 PDU."
::= { blueNet2SpdEntry 9 }
blueNet2SpdDescription OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Description of the SPD connected to BlueNet2 PDU."
::= { blueNet2SpdEntry 10 }
blueNet2SpdType OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of the spd connected to BlueNet2 PDU."
::= { blueNet2SpdEntry 11 }
blueNet2SpdStatus OBJECT-TYPE
SYNTAX BlueNet2EntityStates
MAX-ACCESS read-only
STATUS current
DESCRIPTION "General status of the entity providing the status of an
SPD connected to BlueNet2 PDU."
::= { blueNet2SpdEntry 12 }
-- =============================================================================
-- blueNet2SocketGroups: global BlueNet2 PDU SocketGroups --
blueNet2SocketGroupInfo OBJECT IDENTIFIER ::= { blueNet2SocketGroups 1 }
blueNet2OverallSocketGroupStatus OBJECT-TYPE
SYNTAX BlueNet2ComponentStates
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Overall status of all socket groups."
::= { blueNet2SocketGroupInfo 1 }
blueNet2NumberOfSocketGroups OBJECT-TYPE
SYNTAX Unsigned32 (1..128)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of socket groups available."
::= { blueNet2SocketGroupInfo 2 }
blueNet2LastChangeOverallSocketGroupStatus OBJECT-TYPE
SYNTAX TimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timestamp of last status change of any socket group connected to BlueNet2 PDU
according to operating time sysUpTime."
::= { blueNet2SocketGroupInfo 3 }
blueNet2LastChangeNumberOfSocketGroups OBJECT-TYPE
SYNTAX TimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timestamp of last socket group number change
according to operating time sysUpTime."
::= { blueNet2SocketGroupInfo 4 }
blueNet2LastChangeSocketGroupSettings OBJECT-TYPE
SYNTAX TimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timestamp of last setting change of any socket group connected to BlueNet2 PDU
according to operating time sysUpTime.
This timestamp will be affected by SNMP settings only!"
::= { blueNet2SocketGroupInfo 5 }
blueNet2LastChangeSocketGroups OBJECT-TYPE
SYNTAX TimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timestamp of last socket group change
according to operating time sysUpTime."
::= { blueNet2SocketGroupInfo 6 }
blueNet2SocketGroupsAccumulatedStatus OBJECT-TYPE
SYNTAX BlueNet2EntityBits
MAX-ACCESS read-only
STATUS current
DESCRIPTION "A bit field of all current socket group states."
::= { blueNet2SocketGroupInfo 7 }
blueNet2SocketGroupsInUse OBJECT-TYPE
SYNTAX Unsigned32 (1..128)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of socket groups in use."
::= { blueNet2SocketGroupInfo 8 }
blueNet2MaxSocketGroups OBJECT-TYPE
SYNTAX Unsigned32 (1..128)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The maximum number of entries in blueNet2SocketGroupTable."
::= { blueNet2SocketGroupInfo 9 }
-- -----------------------------------------------------------------------------
blueNet2SocketGroupTable OBJECT-TYPE
SYNTAX SEQUENCE OF BlueNet2SocketGroupEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Headline of socket group table."
::= { blueNet2SocketGroups 2 }
blueNet2SocketGroupEntry OBJECT-TYPE
SYNTAX BlueNet2SocketGroupEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Entries of socket group table."
INDEX { blueNet2SocketGroupIndex }
::= { blueNet2SocketGroupTable 1 }
BlueNet2SocketGroupEntry ::=
SEQUENCE {
blueNet2SocketGroupIndex Unsigned32,
blueNet2SocketGroupRowStatus RowStatus,
blueNet2SocketGroupGuid OCTET STRING,
blueNet2SocketGroupName DisplayString,
blueNet2SocketGroupFriendlyName DisplayString,
blueNet2SocketGroupDescription DisplayString,
blueNet2SocketGroupStatus INTEGER,
blueNet2SocketGroupMode BlueNet2SocketModes,
blueNet2SocketGroupIdentify BlueNet2SocketModes,
blueNet2SocketGroupEntPhysicalIndex Unsigned32,
blueNet2SocketGroupAccumulatedStatus BlueNet2EntityBits,
blueNet2SocketGroupMembers BlueNet2SocketMembers
}
blueNet2SocketGroupIndex OBJECT-TYPE
SYNTAX Unsigned32 (1..128)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Index of socket group available on BlueNet2 PDU."
::= { blueNet2SocketGroupEntry 1 }
blueNet2SocketGroupRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-create
STATUS current
DESCRIPTION "Activate/create/destroy/disable a socket group entry."
::= { blueNet2SocketGroupEntry 2 }
blueNet2SocketGroupGuid OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (8..8))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "GUID of socket group on BlueNet2 PDU."
::= { blueNet2SocketGroupEntry 3 }
blueNet2SocketGroupName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..40))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Name of the socket group connected to BlueNet2 PDU."
::= { blueNet2SocketGroupEntry 4 }
blueNet2SocketGroupFriendlyName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..128))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "User friendlyname of the socket group connected to BlueNet2 PDU."
::= { blueNet2SocketGroupEntry 5 }
blueNet2SocketGroupDescription OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Description of the socket group connected to BlueNet2 PDU."
::= { blueNet2SocketGroupEntry 6 }
blueNet2SocketGroupStatus OBJECT-TYPE
SYNTAX BlueNet2EntityStates
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Status of socket group."
::= { blueNet2SocketGroupEntry 7 }
blueNet2SocketGroupMode OBJECT-TYPE
SYNTAX BlueNet2SocketModes
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Mode of all the sockets of a socket group connected to BlueNet2 PDU."
::= { blueNet2SocketGroupEntry 8 }
blueNet2SocketGroupIdentify OBJECT-TYPE
SYNTAX BlueNet2SocketModes
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Mode of all the socket leds of a socket group connected to BlueNet2 PDU."
::= { blueNet2SocketGroupEntry 9 }
blueNet2SocketGroupEntPhysicalIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Corresponding entPhysicalIndex of this socketgroup. 0 if none exists."
::= { blueNet2SocketGroupEntry 10 }
blueNet2SocketGroupAccumulatedStatus OBJECT-TYPE
SYNTAX BlueNet2EntityBits
MAX-ACCESS read-only
STATUS current
DESCRIPTION "A bit field of all current socket group members states."
::= { blueNet2SocketGroupEntry 11 }
blueNet2SocketGroupMembers OBJECT-TYPE
SYNTAX BlueNet2SocketMembers
MAX-ACCESS read-write
STATUS current
DESCRIPTION "The set of sockets which are members of this socket group."
::= { blueNet2SocketGroupEntry 12 }
--- =============================================================================
-- blueNet2Variables: global BlueNet2 PDU Variables --
blueNet2VariableInfo OBJECT IDENTIFIER ::= { blueNet2Variables 1 }
blueNet2OverallVariableStatus OBJECT-TYPE
SYNTAX BlueNet2ComponentStates
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Overall status of all variables."
::= { blueNet2VariableInfo 1 }
blueNet2NumberOfVariables OBJECT-TYPE
SYNTAX Unsigned32 (1..128)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of variables available."
::= { blueNet2VariableInfo 2 }
blueNet2LastChangeOverallVariableStatus OBJECT-TYPE
SYNTAX TimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timestamp of last status change of any variables connected to BlueNet2 PDU
according to operating time sysUpTime."
::= { blueNet2VariableInfo 3 }
blueNet2LastChangeNumberOfVariables OBJECT-TYPE
SYNTAX TimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timestamp of last variables number change
according to operating time sysUpTime."
::= { blueNet2VariableInfo 4 }
blueNet2LastChangeVariableSettings OBJECT-TYPE
SYNTAX TimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timestamp of last setting change of any variables connected to BlueNet2 PDU
according to operating time sysUpTime.
This timestamp will be affected by SNMP settings only!"
::= { blueNet2VariableInfo 5 }
blueNet2LastChangeVariableStatus OBJECT-TYPE
SYNTAX TimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timestamp of last variable status change
according to operating time sysUpTime."
::= { blueNet2VariableInfo 6 }
blueNet2VariablesAccumulatedStatus OBJECT-TYPE
SYNTAX BlueNet2EntityBits
MAX-ACCESS read-only
STATUS current
DESCRIPTION "A bit field of all current variable states."
::= { blueNet2VariableInfo 7 }
blueNet2NumberOfChangesVariableScaling OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of changes in variable scaling due to overrun or reset.
Variables are given most accurate, each using its own scaling.
But some variables are accumulated and may overrun time by time.
In case of overrun or manually reset of a variable its scaling
will be changed and this counter gets incremented."
::= { blueNet2VariableInfo 8 }
blueNet2LastChangeVariableScaling OBJECT-TYPE
SYNTAX TimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timestamp of last variable scaling change
according to operating time sysUpTime."
::= { blueNet2VariableInfo 9 }
blueNet2LastChangeVariableReset OBJECT-TYPE
SYNTAX TimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timestamp of last manually reset of a variable
according to operating time sysUpTime."
::= { blueNet2VariableInfo 10 }
-- -----------------------------------------------------------------------------
blueNet2VariableTable OBJECT-TYPE
SYNTAX SEQUENCE OF BlueNet2VariableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Headline of variable table."
::= { blueNet2Variables 2 }
blueNet2VariableEntry OBJECT-TYPE
SYNTAX BlueNet2VariableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Entries of variable table."
INDEX { blueNet2VariableId }
::= { blueNet2VariableTable 1 }
BlueNet2VariableEntry ::=
SEQUENCE {
blueNet2VariableId OCTET STRING,
blueNet2VariableGuid OCTET STRING,
blueNet2VariableName DisplayString,
blueNet2VariableFriendlyName DisplayString,
blueNet2VariableDescription DisplayString,
blueNet2VariableType BlueNet2DataSourceTypes,
blueNet2VariableStatus BlueNet2EntityStates,
blueNet2VariableAlarm DisplayString,
blueNet2VariableScaling Integer32,
blueNet2VariableUnit BlueNet2DataSourceUnits,
blueNet2VariableSetPoint INTEGER,
blueNet2VariableMode INTEGER,
blueNet2VariableEntPhysicalIndex Unsigned32
}
blueNet2VariableId OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (8..8))
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "GUID of variable."
::= { blueNet2VariableEntry 1 }
blueNet2VariableGuid OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (8..8))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "GUID of variable."
::= { blueNet2VariableEntry 2 }
blueNet2VariableName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..40))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Name of the variable connected to BlueNet2 PDU."
::= { blueNet2VariableEntry 3 }
blueNet2VariableFriendlyName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..128))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "User friendlyname of the variable connected to BlueNet2 PDU."
::= { blueNet2VariableEntry 4 }
blueNet2VariableDescription OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Description of the variable connected to BlueNet2 PDU."
::= { blueNet2VariableEntry 5 }
blueNet2VariableType OBJECT-TYPE
SYNTAX BlueNet2DataSourceTypes
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of variable."
::= { blueNet2VariableEntry 6 }
blueNet2VariableStatus OBJECT-TYPE
SYNTAX BlueNet2EntityStates
MAX-ACCESS read-only
STATUS current
DESCRIPTION "General status of variable connected to BlueNet2 PDU."
::= { blueNet2VariableEntry 7 }
blueNet2VariableAlarm OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm text of variable connected to BlueNet2 PDU."
::= { blueNet2VariableEntry 8 }
blueNet2VariableScaling OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Scaling of variable as 10^x."
::= { blueNet2VariableEntry 9 }
blueNet2VariableUnit OBJECT-TYPE
SYNTAX BlueNet2DataSourceUnits
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Unit of variable."
::= { blueNet2VariableEntry 10 }
blueNet2VariableSetPoint OBJECT-TYPE
SYNTAX INTEGER {
notAvailable (1),
available (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Set point supported for this variable."
::= { blueNet2VariableEntry 11 }
blueNet2VariableMode OBJECT-TYPE
SYNTAX INTEGER {
resettable (0),
reset (1),
noReset (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Reset mode of a variable.
Variables in mode reset(1) can by reset by writing reset(1).
No other values than reset(1) can be written."
::= { blueNet2VariableEntry 12 }
blueNet2VariableEntPhysicalIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Corresponding entPhysicalIndex of this variable. 0 if none exists."
::= { blueNet2VariableEntry 13 }
-- -----------------------------------------------------------------------------
blueNet2VariableSetPointTable OBJECT-TYPE
SYNTAX SEQUENCE OF BlueNet2VariableSetPointEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Headline of variable set point table."
::= { blueNet2Variables 3 }
blueNet2VariableSetPointEntry OBJECT-TYPE
SYNTAX BlueNet2VariableSetPointEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Entries of variable set point table."
INDEX { blueNet2VariableSetPointGuid }
::= { blueNet2VariableSetPointTable 1 }
BlueNet2VariableSetPointEntry ::=
SEQUENCE {
blueNet2VariableSetPointGuid OCTET STRING,
blueNet2VariableSetPointType BITS,
blueNet2VariableSetPointMinValue Integer32,
blueNet2VariableSetPointMaxValue Integer32,
blueNet2VariableSetPointLowerAlarm Integer32,
blueNet2VariableSetPointLowerWarning Integer32,
blueNet2VariableSetPointUpperWarning Integer32,
blueNet2VariableSetPointUpperAlarm Integer32,
blueNet2VariableSetPointHysteresis Unsigned32,
blueNet2VariableSetPointRcmACUpperAlarmThreshold DisplayString,
blueNet2VariableSetPointRcmACUpperAlarmGradient DisplayString,
blueNet2VariableSetPointRcmACUpperWarningThreshold DisplayString,
blueNet2VariableSetPointRcmACUpperWarningGradient DisplayString
}
blueNet2VariableSetPointGuid OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (8..8))
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "GUID of set point."
::= { blueNet2VariableSetPointEntry 1 }
blueNet2VariableSetPointType OBJECT-TYPE
SYNTAX BITS {
highAlarm (0),
lowAlarm (1),
highWarning (2),
lowWarning (3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of setpoint."
::= { blueNet2VariableSetPointEntry 2 }
blueNet2VariableSetPointMinValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Minimum value of setpoint."
::= { blueNet2VariableSetPointEntry 3 }
blueNet2VariableSetPointMaxValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Maximum value of setpoint."
::= { blueNet2VariableSetPointEntry 4 }
blueNet2VariableSetPointLowerAlarm OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Lower threshold of variable."
::= { blueNet2VariableSetPointEntry 5 }
blueNet2VariableSetPointLowerWarning OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Lower Warning of variable."
::= { blueNet2VariableSetPointEntry 6 }
blueNet2VariableSetPointUpperWarning OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Upper warning of variable."
::= { blueNet2VariableSetPointEntry 7 }
blueNet2VariableSetPointUpperAlarm OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Upper threshold of variable."
::= { blueNet2VariableSetPointEntry 8 }
blueNet2VariableSetPointHysteresis OBJECT-TYPE
SYNTAX Unsigned32 (0..100)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Hysteresis of variable."
::= { blueNet2VariableSetPointEntry 9 }
blueNet2VariableSetPointRcmACUpperAlarmThreshold OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Upper Alarm threshold of RCM AC."
::= { blueNet2VariableSetPointEntry 10 }
blueNet2VariableSetPointRcmACUpperAlarmGradient OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Upper Alarm gradient of RCM AC."
::= { blueNet2VariableSetPointEntry 11 }
blueNet2VariableSetPointRcmACUpperWarningThreshold OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Upper Warning threshold of RCM AC."
::= { blueNet2VariableSetPointEntry 12 }
blueNet2VariableSetPointRcmACUpperWarningGradient OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Upper Warning gradient of RCM AC."
::= { blueNet2VariableSetPointEntry 13 }
-- -----------------------------------------------------------------------------
blueNet2VariableDataTable OBJECT-TYPE
SYNTAX SEQUENCE OF BlueNet2VariableDataEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Headline of variable data table.
This table contains a subset of frequently changing variables as
in blueNet2VariableDataTable, like measured values and status."
::= { blueNet2Variables 4 }
blueNet2VariableDataEntry OBJECT-TYPE
SYNTAX BlueNet2VariableDataEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Entries of variable date table."
INDEX { blueNet2VariableGuid }
::= { blueNet2VariableDataTable 1 }
BlueNet2VariableDataEntry ::=
SEQUENCE {
blueNet2VariableDataId OCTET STRING,
blueNet2VariableDataGuid OCTET STRING,
blueNet2VariableDataType BlueNet2DataSourceTypes,
blueNet2VariableDataStatus BlueNet2EntityStates,
blueNet2VariableDataValue Integer32,
blueNet2VariableDataDateTime DateAndTime
}
blueNet2VariableDataId OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (8..8))
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "GUID of variable."
::= { blueNet2VariableDataEntry 1 }
blueNet2VariableDataGuid OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (8..8))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "GUID of variable."
::= { blueNet2VariableDataEntry 2 }
blueNet2VariableDataType OBJECT-TYPE
SYNTAX BlueNet2DataSourceTypes
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of variable."
::= { blueNet2VariableDataEntry 3 }
blueNet2VariableDataStatus OBJECT-TYPE
SYNTAX BlueNet2EntityStates
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Status of variable."
::= { blueNet2VariableDataEntry 4 }
blueNet2VariableDataValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Value of variable."
::= { blueNet2VariableDataEntry 5 }
blueNet2VariableDataDateTime OBJECT-TYPE
SYNTAX DateAndTime
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timestamp of variable."
::= { blueNet2VariableDataEntry 6 }
-- -----------------------------------------------------------------------------
blueNet2VariableDataByTypeTable OBJECT-TYPE
SYNTAX SEQUENCE OF BlueNet2VariableDataByTypeEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Headline of variable data by type table.
This table contains a subset of frequently changing variables as
in blueNet2VariableDataByTypeTable, like measured values and status.
This table is ordered by type of measurement source."
::= { blueNet2Variables 5 }
blueNet2VariableDataByTypeEntry OBJECT-TYPE
SYNTAX BlueNet2VariableDataByTypeEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Entries of variable data by type table."
INDEX { blueNet2VariableDataByType,blueNet2VariableDataByTypeGuid }
::= { blueNet2VariableDataByTypeTable 1 }
BlueNet2VariableDataByTypeEntry ::=
SEQUENCE {
blueNet2VariableDataByType BlueNet2DataSourceTypes,
blueNet2VariableDataByTypeGuid OCTET STRING,
blueNet2VariableDataByTypeType BlueNet2DataSourceTypes,
blueNet2VariableDataByTypeStatus BlueNet2EntityStates,
blueNet2VariableDataByTypeValue Integer32,
blueNet2VariableDataByTypeDateTime DateAndTime
}
blueNet2VariableDataByType OBJECT-TYPE
SYNTAX BlueNet2DataSourceTypes
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Type of variable."
::= { blueNet2VariableDataByTypeEntry 1 }
blueNet2VariableDataByTypeGuid OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (8..8))
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "GUID of variable."
::= { blueNet2VariableDataByTypeEntry 2 }
blueNet2VariableDataByTypeType OBJECT-TYPE
SYNTAX BlueNet2DataSourceTypes
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of variable."
::= { blueNet2VariableDataByTypeEntry 3 }
blueNet2VariableDataByTypeStatus OBJECT-TYPE
SYNTAX BlueNet2EntityStates
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Status of variable."
::= { blueNet2VariableDataByTypeEntry 4 }
blueNet2VariableDataByTypeValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Value of variable."
::= { blueNet2VariableDataByTypeEntry 5 }
blueNet2VariableDataByTypeDateTime OBJECT-TYPE
SYNTAX DateAndTime
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timestamp of variable."
::= { blueNet2VariableDataByTypeEntry 6 }
-- -----------------------------------------------------------------------------
blueNet2VariableDataByStateTable OBJECT-TYPE
SYNTAX SEQUENCE OF BlueNet2VariableDataByStateEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION "Headline of variable data by state table.
This table contains a subset of frequently changing variables as
in blueNet2VariableDataByStateTable, like measured values and status.
This table is ordered by the state of variable.
This table is updated periodically in a 15 seconds intervall!
Therefore a variable state may temporarily not reflect the current state!"
::= { blueNet2Variables 6 }
blueNet2VariableDataByStateEntry OBJECT-TYPE
SYNTAX BlueNet2VariableDataByStateEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION "Entries of variable data by state table."
INDEX { blueNet2VariableDataByState,blueNet2VariableDataByStateGuid }
::= { blueNet2VariableDataByStateTable 1 }
BlueNet2VariableDataByStateEntry ::=
SEQUENCE {
blueNet2VariableDataByState BlueNet2EntityStates,
blueNet2VariableDataByStateGuid OCTET STRING,
blueNet2VariableDataByStateType BlueNet2DataSourceTypes,
blueNet2VariableDataByStateStatus BlueNet2EntityStates,
blueNet2VariableDataByStateValue Integer32,
blueNet2VariableDataByStateDateTime DateAndTime
}
blueNet2VariableDataByState OBJECT-TYPE
SYNTAX BlueNet2EntityStates
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION "Status of variable."
::= { blueNet2VariableDataByStateEntry 1 }
blueNet2VariableDataByStateGuid OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (8..8))
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION "GUID of variable."
::= { blueNet2VariableDataByStateEntry 2 }
blueNet2VariableDataByStateType OBJECT-TYPE
SYNTAX BlueNet2DataSourceTypes
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION "Type of variable."
::= { blueNet2VariableDataByStateEntry 3 }
blueNet2VariableDataByStateStatus OBJECT-TYPE
SYNTAX BlueNet2EntityStates
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION "Status of variable."
::= { blueNet2VariableDataByStateEntry 4 }
blueNet2VariableDataByStateValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION "Value of variable."
::= { blueNet2VariableDataByStateEntry 5 }
blueNet2VariableDataByStateDateTime OBJECT-TYPE
SYNTAX DateAndTime
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION "Timestamp of variable."
::= { blueNet2VariableDataByStateEntry 6 }
-- -----------------------------------------------------------------------------
blueNet2VariableDataBySourceTable OBJECT-TYPE
SYNTAX SEQUENCE OF BlueNet2VariableDataBySourceEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Headline of variable data by state table.
This table contains a subset of frequently changing variables as
in blueNet2VariableDataBySourceTable, like measured values and status.
This table is ordered by the source of variable."
::= { blueNet2Variables 7 }
blueNet2VariableDataBySourceEntry OBJECT-TYPE
SYNTAX BlueNet2VariableDataBySourceEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Entries of variable data by source table."
INDEX { blueNet2VariableDataBySource,blueNet2VariableDataBySourceGuid }
::= { blueNet2VariableDataBySourceTable 1 }
BlueNet2VariableDataBySourceEntry ::=
SEQUENCE {
blueNet2VariableDataBySource BlueNet2EntitySources,
blueNet2VariableDataBySourceGuid OCTET STRING,
blueNet2VariableDataBySourceType BlueNet2DataSourceTypes,
blueNet2VariableDataBySourceStatus BlueNet2EntityStates,
blueNet2VariableDataBySourceValue Integer32,
blueNet2VariableDataBySourceDateTime DateAndTime
}
blueNet2VariableDataBySource OBJECT-TYPE
SYNTAX BlueNet2EntitySources
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Source of variable."
::= { blueNet2VariableDataBySourceEntry 1 }
blueNet2VariableDataBySourceGuid OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (8..8))
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "GUID of variable."
::= { blueNet2VariableDataBySourceEntry 2 }
blueNet2VariableDataBySourceType OBJECT-TYPE
SYNTAX BlueNet2DataSourceTypes
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of variable."
::= { blueNet2VariableDataBySourceEntry 3 }
blueNet2VariableDataBySourceStatus OBJECT-TYPE
SYNTAX BlueNet2EntityStates
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Status of variable."
::= { blueNet2VariableDataBySourceEntry 4 }
blueNet2VariableDataBySourceValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Value of variable."
::= { blueNet2VariableDataBySourceEntry 5 }
blueNet2VariableDataBySourceDateTime OBJECT-TYPE
SYNTAX DateAndTime
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timestamp of variable."
::= { blueNet2VariableDataBySourceEntry 6 }
--- =============================================================================
-- blueNet2MPStates: global BlueNet2 Overview of Measurement Point States --
blueNet2MPTable OBJECT-TYPE
SYNTAX SEQUENCE OF BlueNet2MPEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Headline of MP (Measurement Point) table."
::= { blueNet2MPStates 1 }
blueNet2MPEntry OBJECT-TYPE
SYNTAX BlueNet2MPEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Entries of Measurement Point table."
INDEX { blueNet2MPID }
::= { blueNet2MPTable 1 }
BlueNet2MPEntry ::=
SEQUENCE {
blueNet2MPID OCTET STRING,
blueNet2MPGuid OCTET STRING,
blueNet2MPName DisplayString,
blueNet2MPFriendlyName DisplayString,
blueNet2MPState BlueNet2EntityStates,
blueNet2MPTimeStamp DateAndTime
}
blueNet2MPID OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (8..8))
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "GUID of a Measurement Point."
::= { blueNet2MPEntry 1 }
blueNet2MPGuid OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (8..8))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "GUID of a Measurement Point."
::= { blueNet2MPEntry 2 }
blueNet2MPName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..40))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Name of a Measurement Point."
::= { blueNet2MPEntry 3 }
blueNet2MPFriendlyName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..128))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "User friendlyname of a Measurement Point."
::= { blueNet2MPEntry 4 }
blueNet2MPState OBJECT-TYPE
SYNTAX BlueNet2EntityStates
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Status of a Measurement Point."
::= { blueNet2MPEntry 5 }
blueNet2MPTimeStamp OBJECT-TYPE
SYNTAX DateAndTime
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timestamp of the last change of a Measurement Point."
::= { blueNet2MPEntry 6 }
-- *****************************************************************************
-- Traps --
blueNet2TrapPrefix OBJECT IDENTIFIER ::= { blueNet2Traps 0 }
blueNet2PduStatusOkTrap NOTIFICATION-TYPE
OBJECTS {
blueNet2DeviceGuid,
blueNet2DeviceStatus,
blueNet2DeviceAlarm
}
STATUS current
DESCRIPTION "PDU status ok."
--
-- #CATEGORY "Status Events."
-- #TYPE "PDU status ok."
-- #SUMMARY "Guid %x device status is %i: %s."
-- #ARGUMENTS {0,1,2}
-- #SEVERITY INFORMATIONAL
-- #STATE OPERATIONAL
--
::= { blueNet2TrapPrefix 1 }
blueNet2PduStatusWarningTrap NOTIFICATION-TYPE
OBJECTS {
blueNet2DeviceGuid,
blueNet2DeviceStatus,
blueNet2DeviceAlarm
}
STATUS current
DESCRIPTION "PDU status warning."
--
-- #CATEGORY "Status Events."
-- #TYPE "PDU status warning."
-- #SUMMARY "Guid %x device status is %i: %s."
-- #ARGUMENTS {0,1,2}
-- #SEVERITY MINOR
-- #STATE OPERATIONAL
--
::= { blueNet2TrapPrefix 2 }
blueNet2PduStatusAlarmTrap NOTIFICATION-TYPE
OBJECTS {
blueNet2DeviceGuid,
blueNet2DeviceStatus,
blueNet2DeviceAlarm
}
STATUS current
DESCRIPTION "PDU status alarm."
--
-- #CATEGORY "Status Events."
-- #TYPE "PDU status alarm."
-- #SUMMARY "Guid %x device status is %i: %s."
-- #ARGUMENTS {0,1,2}
-- #SEVERITY MAJOR
-- #STATE OPERATIONAL
--
::= { blueNet2TrapPrefix 3 }
blueNet2SensorStatusOkTrap NOTIFICATION-TYPE
OBJECTS {
blueNet2SensorGuid,
blueNet2SensorStatus,
blueNet2SensorAlarm
}
STATUS current
DESCRIPTION "Sensor status change."
--
-- #CATEGORY "Status Events."
-- #TYPE "Sensor status ok."
-- #SUMMARY "Guid %x sensor status is %i: %s."
-- #ARGUMENTS {0,1,2}
-- #SEVERITY INFORMATIONAL
-- #STATE OPERATIONAL
--
::= { blueNet2TrapPrefix 4 }
blueNet2SensorStatusWarningTrap NOTIFICATION-TYPE
OBJECTS {
blueNet2SensorGuid,
blueNet2SensorStatus,
blueNet2SensorAlarm
}
STATUS current
DESCRIPTION "Sensor status change."
--
-- #CATEGORY "Status Events."
-- #TYPE "Sensor status warning."
-- #SUMMARY "Guid %x sensor status is %i: %s."
-- #ARGUMENTS {0,1,2}
-- #SEVERITY MINOR
-- #STATE OPERATIONAL
--
::= { blueNet2TrapPrefix 5 }
blueNet2SensorStatusAlarmTrap NOTIFICATION-TYPE
OBJECTS {
blueNet2SensorGuid,
blueNet2SensorStatus,
blueNet2SensorAlarm
}
STATUS current
DESCRIPTION "Sensor status change."
--
-- #CATEGORY "Status Events."
-- #TYPE "Sensor status alarm."
-- #SUMMARY "Guid %x sensor status is %i: %s."
-- #ARGUMENTS {0,1,2}
-- #SEVERITY MAJOR
-- #STATE OPERATIONAL
--
::= { blueNet2TrapPrefix 6 }
blueNet2VariableStatusOkTrap NOTIFICATION-TYPE
OBJECTS {
blueNet2VariableDataGuid,
blueNet2VariableDataStatus,
blueNet2VariableDataValue,
blueNet2VariableAlarm
}
STATUS current
DESCRIPTION "Variable status is ok."
--
-- #CATEGORY "Threshold Events."
-- #TYPE "Variable status is ok."
-- #SUMMARY "Guid %x variable value %i is ok (%i), %s."
-- #ARGUMENTS {0,1,2,3}
-- #SEVERITY INFORMATIONAL
-- #STATE OPERATIONAL
--
::= { blueNet2TrapPrefix 7 }
blueNet2VariableLowerWarningTrap NOTIFICATION-TYPE
OBJECTS {
blueNet2VariableDataGuid,
blueNet2VariableDataStatus,
blueNet2VariableDataValue,
blueNet2VariableSetPointLowerAlarm,
blueNet2VariableAlarm
}
STATUS current
DESCRIPTION "Variable status lower warning."
--
-- #CATEGORY "Threshold Events."
-- #TYPE "Variable status lower warning."
-- #SUMMARY "Guid %x variable value %i deceeds %i (%i), %s."
-- #ARGUMENTS {0,2,1,3,4}
-- #SEVERITY MINOR
-- #STATE OPERATIONAL
--
::= { blueNet2TrapPrefix 8 }
blueNet2VariableUpperWarningTrap NOTIFICATION-TYPE
OBJECTS {
blueNet2VariableDataGuid,
blueNet2VariableDataStatus,
blueNet2VariableDataValue,
blueNet2VariableSetPointUpperWarning,
blueNet2VariableAlarm
}
STATUS current
DESCRIPTION "Variable status upper warning."
--
-- #CATEGORY "Threshold Events."
-- #TYPE "Variable status upper warning."
-- #SUMMARY "Guid %x variable value %i exceeds %i (%i), %s."
-- #ARGUMENTS {0,2,1,3,4}
-- #SEVERITY MINOR
-- #STATE OPERATIONAL
--
::= { blueNet2TrapPrefix 9 }
blueNet2VariableLowerAlarmTrap NOTIFICATION-TYPE
OBJECTS {
blueNet2VariableDataGuid,
blueNet2VariableDataStatus,
blueNet2VariableDataValue,
blueNet2VariableSetPointLowerAlarm,
blueNet2VariableAlarm
}
STATUS current
DESCRIPTION "Variable status lower alarm."
--
-- #CATEGORY "Threshold Events."
-- #TYPE "Variable status lower alarm."
-- #SUMMARY "Guid %x variable value %i deceeds %i (%i), %s."
-- #ARGUMENTS {0,2,1,3,4}
-- #SEVERITY MAJOR
-- #STATE OPERATIONAL
--
::= { blueNet2TrapPrefix 10 }
blueNet2VariableUpperAlarmTrap NOTIFICATION-TYPE
OBJECTS {
blueNet2VariableDataGuid,
blueNet2VariableDataStatus,
blueNet2VariableDataValue,
blueNet2VariableSetPointUpperAlarm,
blueNet2VariableAlarm
}
STATUS current
DESCRIPTION "Variable status upper alarm."
--
-- #CATEGORY "Threshold Events."
-- #TYPE "Variable status upper alarm."
-- #SUMMARY "Guid %x variable value %i exceeds %i (%i), %s."
-- #ARGUMENTS {0,2,1,3,4}
-- #SEVERITY MAJOR
-- #STATE OPERATIONAL
--
::= { blueNet2TrapPrefix 11 }
blueNet2RCMSelftestResultTrap NOTIFICATION-TYPE
OBJECTS {
blueNet2RcmSelftestResultStr
}
STATUS current
DESCRIPTION "RCM Selftest result."
--
-- #CATEGORY "Status Events."
-- #TYPE "RCM Selftest result."
-- #SUMMARY "RCM Selftest result: %s."
-- #ARGUMENTS {0}
-- #SEVERITY INFORMATIONAL
-- #STATE OPERATIONAL
--
::= { blueNet2TrapPrefix 12 }
blueNet2ReconfigAgentTrap NOTIFICATION-TYPE
OBJECTS {
sysObjectID
}
STATUS current
DESCRIPTION "Agent reconfiguration."
--
-- #CATEGORY "Status Events."
-- #TYPE "Agent status."
-- #SUMMARY "Agent type: %s, Status: configuration has changed."
-- #ARGUMENTS {0}
-- #SEVERITY INFORMATIONAL
-- #TIMEINDEX 6
-- #STATE OPERATIONAL
--
::= { blueNet2TrapPrefix 98 }
blueNet2ShutdownAgentTrap NOTIFICATION-TYPE
OBJECTS {
sysObjectID
}
STATUS current
DESCRIPTION "Agent shutdown."
--
-- #CATEGORY "Status Events."
-- #TYPE "Agent status."
-- #SUMMARY "Agent type: %s, Status: shutdown."
-- #ARGUMENTS {0}
-- #SEVERITY SEVERE
-- #TIMEINDEX 6
-- #STATE NONOPERATIONAL
--
::= { blueNet2TrapPrefix 99 }
-- *****************************************************************************
-- Compliance Statements --
blueNet2Compliances OBJECT IDENTIFIER ::= { blueNet2Conformance 1 }
blueNet2Groups OBJECT IDENTIFIER ::= { blueNet2Conformance 2 }
blueNet2Compliance MODULE-COMPLIANCE
STATUS current
DESCRIPTION "The core compliance statement for all BlueNet2 PDU implementations."
MODULE MANDATORY-GROUPS {
blueNet2NotificationGroup,
blueNet2TrapGroup,
blueNet2IdentificationGroup,
blueNet2InformationGroup,
blueNet2ConfigurationGroup,
blueNet2RcmGroup,
blueNet2SpdGroup,
blueNet2SmtpGroup,
blueNet2SnmpGroup,
blueNet2NtpGroup,
blueNet2ModbusGroup,
blueNet2DeviceGroup,
blueNet2SensorGroup,
blueNet2CircuitGroup,
blueNet2SocketGroup,
blueNet2VariableGroup,
blueNet2MPGroup
}
GROUP blueNet2NotificationGroup
DESCRIPTION "SNMP notification handling."
GROUP blueNet2TrapGroup
DESCRIPTION "SNMP trap handling."
GROUP blueNet2IdentificationGroup
DESCRIPTION "base identification handling."
GROUP blueNet2InformationGroup
DESCRIPTION "base information handling."
GROUP blueNet2ConfigurationGroup
DESCRIPTION "base configuration handling."
GROUP blueNet2NtpGroup
DESCRIPTION "Simple Network Time Protocol (NTP) handling."
GROUP blueNet2SyslogGroup
DESCRIPTION "System log handling."
GROUP blueNet2SmtpGroup
DESCRIPTION "Simple Mail Transfer Protocol (SMTP) handling."
GROUP blueNet2SnmpGroup
DESCRIPTION "Simple Network Management Protocol (SNMP) handling."
GROUP blueNet2ModbusGroup
DESCRIPTION "Modbus ASCII/RTU/TCP handling."
GROUP blueNet2DeviceGroup
DESCRIPTION "BlueNet2 PDU device handling."
GROUP blueNet2SensorGroup
DESCRIPTION "BlueNet2 PDU sensor handling."
GROUP blueNet2CircuitGroup
DESCRIPTION "BlueNet2 PDU circuit handling."
GROUP blueNet2PhaseGroup
DESCRIPTION "BlueNet2 PDU phase handling."
GROUP blueNet2FuseGroup
DESCRIPTION "BlueNet2 PDU fuse handling."
GROUP blueNet2SocketGroup
DESCRIPTION "BlueNet2 PDU socket handling."
GROUP blueNet2SocketGroupGroup
DESCRIPTION "BlueNet2 PDU socket group handling."
GROUP blueNet2VariableGroup
DESCRIPTION "BlueNet2 PDU variable handling."
GROUP blueNet2MPGroup
DESCRIPTION "BlueNet2 Measurement Point handling."
::= { blueNet2Compliances 1 }
-- *****************************************************************************
-- Conformance Groups --
blueNet2TrapGroup OBJECT-GROUP
OBJECTS {
blueNet2DeviceGuid,
blueNet2DeviceStatus,
blueNet2DeviceAlarm,
blueNet2SensorGuid,
blueNet2SensorStatus,
blueNet2SensorAlarm,
blueNet2VariableDataGuid,
blueNet2VariableDataStatus,
blueNet2VariableDataValue,
blueNet2VariableSetPointLowerAlarm,
blueNet2VariableSetPointLowerWarning,
blueNet2VariableSetPointUpperWarning,
blueNet2VariableSetPointUpperAlarm,
blueNet2VariableAlarm
}
STATUS current
DESCRIPTION "Conformance group for all objects contained in BlueNet2 PDU traps."
::= { blueNet2Groups 1 }
blueNet2NotificationGroup NOTIFICATION-GROUP
NOTIFICATIONS {
blueNet2PduStatusOkNotification,
blueNet2PduStatusWarningNotification,
blueNet2PduStatusAlarmNotification,
blueNet2SensorStatusOkNotification,
blueNet2SensorStatusWarningNotification,
blueNet2SensorStatusAlarmNotification,
blueNet2VariableStatusOkNotification,
blueNet2VariableLowerWarningNotification,
blueNet2VariableUpperWarningNotification,
blueNet2VariableLowerAlarmNotification,
blueNet2VariableUpperAlarmNotification,
blueNet2ReconfigAgentNotification,
blueNet2ShutdownAgentNotification,
blueNet2PduStatusOkTrap,
blueNet2PduStatusWarningTrap,
blueNet2PduStatusAlarmTrap,
blueNet2SensorStatusOkTrap,
blueNet2SensorStatusWarningTrap,
blueNet2SensorStatusAlarmTrap,
blueNet2VariableStatusOkTrap,
blueNet2VariableLowerWarningTrap,
blueNet2VariableUpperWarningTrap,
blueNet2VariableLowerAlarmTrap,
blueNet2VariableUpperAlarmTrap,
blueNet2RCMSelftestResultTrap,
blueNet2ReconfigAgentTrap,
blueNet2ShutdownAgentTrap
}
STATUS current
DESCRIPTION "Conformance group for BlueNet2 PDU notifications."
::= { blueNet2Groups 2 }
blueNet2IdentificationGroup OBJECT-GROUP
OBJECTS {
blueNet2IdProductVendor,
blueNet2IdProductURI,
blueNet2IdProductName,
blueNet2IdProductPartNr,
blueNet2IdProductSNr,
blueNet2IdProductDate,
blueNet2IdProductFacility,
blueNet2IdProductCaps,
blueNet2IdProductFwV,
blueNet2IdProductHwV,
blueNet2IdProductSwV,
blueNet2IdProductOsV,
blueNet2IdProductArch,
blueNet2IdProductMAC
}
STATUS current
DESCRIPTION "Conformance group for BlueNet2 PDU base identfication."
::= { blueNet2Groups 3 }
blueNet2InformationGroup OBJECT-GROUP
OBJECTS {
blueNet2InfoUpTime,
blueNet2InfoOverallStatus,
blueNet2InfoNumberOfChanges,
blueNet2InfoLastChange,
blueNet2InfoAccumulatedStatus,
blueNet2InfoLoadAverage,
blueNet2InfoMessageStatus,
blueNet2InfoMessageTime,
blueNet2InfoMessageText,
blueNet2InfoMessageNumberOfOks,
blueNet2InfoMessageNumberOfWarnings,
blueNet2InfoMessageNumberOfErrors
}
STATUS current
DESCRIPTION "Conformance group for BlueNet2 PDU base information."
::= { blueNet2Groups 4 }
blueNet2ConfigurationGroup OBJECT-GROUP
OBJECTS {
blueNet2Alias,
blueNet2Language,
blueNet2FtpAccess,
blueNet2FtpPort,
blueNet2HttpAccess,
blueNet2HttpPort,
blueNet2HttpsPort,
blueNet2SftpAccess,
blueNet2SftpPort,
blueNet2SshAccess,
blueNet2SshPort,
blueNet2TelnetAccess,
blueNet2TelnetPort
}
STATUS current
DESCRIPTION "Conformance group for BlueNet2 PDU base configuration."
::= { blueNet2Groups 5 }
blueNet2SnmpGroup OBJECT-GROUP
OBJECTS {
blueNet2SnmpVersions,
blueNet2MaxTrapReceivers,
blueNet2TrapReceiverRowStatus,
blueNet2TrapReceiverProtocol,
blueNet2TrapReceiverAddress,
blueNet2TrapReceiverFriendlyName,
blueNet2TrapReceiverDescription,
blueNet2TrapReceiverCommunity,
blueNet2TrapReceiverUsername
}
STATUS current
DESCRIPTION "Conformance group for BlueNet2 PDU SNMP configuration."
::= { blueNet2Groups 6 }
blueNet2ModbusGroup OBJECT-GROUP
OBJECTS {
blueNet2ModbusVersions,
blueNet2ModbusService,
blueNet2ModbusTcpPort,
blueNet2ModbusSerialMode,
blueNet2MaxModbusTcpMasters,
blueNet2ModbusTcpRowStatus,
blueNet2ModbusTcpAccess,
blueNet2ModbusTcpMaster,
blueNet2ModbusTcpFriendlyName,
blueNet2ModbusTcpDescription
}
STATUS current
DESCRIPTION "Conformance group for blueNet2 PDU modbus configuration."
::= { blueNet2Groups 7 }
blueNet2NtpGroup OBJECT-GROUP
OBJECTS {
blueNet2DateTime,
blueNet2NtpService,
blueNet2NtpPort,
blueNet2NtpTimeZone,
blueNet2MaxNtpServers,
blueNet2NtpServerRowStatus,
blueNet2NtpServerAddress,
blueNet2NtpServerFriendlyName,
blueNet2NtpServerDescription
}
STATUS current
DESCRIPTION "Conformance group for BlueNet2 PDU NTP configuration."
::= { blueNet2Groups 8 }
blueNet2SmtpGroup OBJECT-GROUP
OBJECTS {
blueNet2SmtpService,
blueNet2SmtpPort,
blueNet2SmtpServer,
blueNet2SmtpAuth,
blueNet2SmtpUsername,
blueNet2SmtpPassword,
blueNet2SmtpFrom,
blueNet2SmtpReply,
blueNet2MaxSmtpReceivers,
blueNet2SmtpReceiverRowStatus,
blueNet2SmtpReceiverAddress,
blueNet2SmtpReceiverFriendlyName,
blueNet2SmtpReceiverDescription
}
STATUS current
DESCRIPTION "Conformance group for BlueNet2 PDU SMTP configuration."
::= { blueNet2Groups 9 }
blueNet2SyslogGroup OBJECT-GROUP
OBJECTS {
blueNet2SyslogService,
blueNet2SyslogFacility,
blueNet2MaxSyslogServers,
blueNet2SyslogServerRowStatus,
blueNet2SyslogServerAddress,
blueNet2SyslogServerPort,
blueNet2SyslogServerFriendlyName,
blueNet2SyslogServerDescription,
blueNet2SyslogServerProtocol
}
STATUS current
DESCRIPTION "Conformance group for BlueNet2 PDU syslog operations."
::= { blueNet2Groups 10 }
blueNet2DeviceGroup OBJECT-GROUP
OBJECTS {
blueNet2OverallDeviceStatus,
blueNet2NumberOfDevices,
blueNet2LastChangeOverallDeviceStatus,
blueNet2LastChangeNumberOfDevices,
blueNet2LastChangeDeviceSettings,
blueNet2LastChangeDevices,
blueNet2DevicesAccumulatedStatus,
blueNet2DeviceGuid,
blueNet2DeviceName,
blueNet2DeviceFriendlyName,
blueNet2DeviceDescription,
blueNet2DeviceType,
blueNet2DeviceStatus,
blueNet2DeviceAlarm,
blueNet2DeviceLastChange,
blueNet2DeviceEntPhysicalIndex,
blueNet2DevicePartNr,
blueNet2DeviceSNr,
blueNet2DeviceFwV,
blueNet2DeviceHwV,
blueNet2DeviceSwV,
blueNet2DeviceOsV,
blueNet2DeviceMAC,
blueNet2DeviceNumberOfSensors,
blueNet2DeviceNumberOfCircuits,
blueNet2DeviceNumberOfPhases,
blueNet2DeviceNumberOfFuses,
blueNet2DeviceNumberOfSockets,
blueNet2DeviceNumberOfRCMs,
blueNet2DeviceNumberOfVars,
blueNet2DeviceLocation,
blueNet2DeviceProductDate,
blueNet2DeviceModbusAddr
}
STATUS current
DESCRIPTION "Conformance group for BlueNet2 PDU device information."
::= { blueNet2Groups 11 }
blueNet2SensorGroup OBJECT-GROUP
OBJECTS {
blueNet2OverallSensorStatus,
blueNet2NumberOfSensors,
blueNet2LastChangeOverallSensorStatus,
blueNet2LastChangeNumberOfSensors,
blueNet2LastChangeSensorSettings,
blueNet2LastChangeSensors,
blueNet2SensorsAccumulatedStatus,
blueNet2SensorGuid,
blueNet2SensorName,
blueNet2SensorFriendlyName,
blueNet2SensorDescription,
blueNet2SensorType,
blueNet2SensorStatus,
blueNet2SensorAlarm,
blueNet2SensorLastChange,
blueNet2SensorEntPhysicalIndex,
blueNet2SensorNumberOfVars,
blueNet2SensorHwV,
blueNet2SensorFwV,
blueNet2SensorSNr,
blueNet2SensorVariableGuid,
blueNet2SensorVariableName,
blueNet2SensorVariableFriendlyName,
blueNet2SensorVariableDescription,
blueNet2SensorVariableGPIOMode,
blueNet2SensorVariableGPIOSwitch,
blueNet2SensorVariableGPIOState
}
STATUS current
DESCRIPTION "Conformance group for BlueNet2 PDU sensor information."
::= { blueNet2Groups 12 }
blueNet2CircuitGroup OBJECT-GROUP
OBJECTS {
blueNet2OverallCircuitStatus,
blueNet2NumberOfCircuits,
blueNet2LastChangeOverallCircuitStatus,
blueNet2LastChangeNumberOfCircuits,
blueNet2LastChangeCircuitSettings,
blueNet2LastChangeCircuits,
blueNet2CircuitGuid,
blueNet2CircuitName,
blueNet2CircuitFriendlyName,
blueNet2CircuitDescription,
blueNet2CircuitType,
blueNet2CircuitStatus,
blueNet2CircuitNumberOfPhases
}
STATUS current
DESCRIPTION "Conformance group for BlueNet2 PDU circuit information."
::= { blueNet2Groups 13 }
blueNet2PhaseGroup OBJECT-GROUP
OBJECTS {
blueNet2PhaseGuid,
blueNet2PhaseName,
blueNet2PhaseFriendlyName,
blueNet2PhaseDescription,
blueNet2PhaseStatus,
blueNet2PhaseNumberOfFuses
}
STATUS current
DESCRIPTION "Conformance group for BlueNet2 PDU phase information."
::= { blueNet2Groups 14 }
blueNet2FuseGroup OBJECT-GROUP
OBJECTS {
blueNet2FuseGuid,
blueNet2FuseName,
blueNet2FuseFriendlyName,
blueNet2FuseDescription,
blueNet2FuseType,
blueNet2FuseStatus,
blueNet2FuseNumberOfSockets
}
STATUS current
DESCRIPTION "Conformance group for BlueNet2 PDU fuse information."
::= { blueNet2Groups 15 }
blueNet2SocketGroup OBJECT-GROUP
OBJECTS {
blueNet2SocketGuid,
blueNet2SocketName,
blueNet2SocketFriendlyName,
blueNet2SocketDescription,
blueNet2SocketType,
blueNet2SocketStatus,
blueNet2SocketMode,
blueNet2SocketIdentify,
blueNet2SocketMemberIndex
}
STATUS current
DESCRIPTION "Conformance group for BlueNet2 PDU socket information."
::= { blueNet2Groups 16 }
blueNet2RcmGroup OBJECT-GROUP
OBJECTS {
blueNet2RcmGuid,
blueNet2RcmName,
blueNet2RcmFriendlyName,
blueNet2RcmDescription,
blueNet2RcmType,
blueNet2RcmStatus
}
STATUS current
DESCRIPTION "Conformance group for BlueNet2 PDU RCM information."
::= { blueNet2Groups 17 }
blueNet2SocketGroupGroup OBJECT-GROUP
OBJECTS {
blueNet2OverallSocketGroupStatus,
blueNet2NumberOfSocketGroups,
blueNet2LastChangeOverallSocketGroupStatus,
blueNet2LastChangeNumberOfSocketGroups,
blueNet2LastChangeSocketGroupSettings,
blueNet2LastChangeSocketGroups,
blueNet2SocketGroupsAccumulatedStatus,
blueNet2SocketGroupsInUse,
blueNet2MaxSocketGroups,
blueNet2SocketGroupRowStatus,
blueNet2SocketGroupGuid,
blueNet2SocketGroupName,
blueNet2SocketGroupFriendlyName,
blueNet2SocketGroupDescription,
blueNet2SocketGroupStatus,
blueNet2SocketGroupMode,
blueNet2SocketGroupIdentify,
blueNet2SocketGroupEntPhysicalIndex,
blueNet2SocketGroupAccumulatedStatus,
blueNet2SocketGroupMembers
}
STATUS current
DESCRIPTION "Conformance group for BlueNet2 PDU socket groups."
::= { blueNet2Groups 18 }
blueNet2VariableGroup OBJECT-GROUP
OBJECTS {
blueNet2OverallVariableStatus,
blueNet2NumberOfVariables,
blueNet2LastChangeOverallVariableStatus,
blueNet2LastChangeNumberOfVariables,
blueNet2LastChangeVariableSettings,
blueNet2LastChangeVariableStatus,
blueNet2VariablesAccumulatedStatus,
blueNet2NumberOfChangesVariableScaling,
blueNet2LastChangeVariableScaling,
blueNet2LastChangeVariableReset,
blueNet2VariableGuid,
blueNet2VariableName,
blueNet2VariableFriendlyName,
blueNet2VariableDescription,
blueNet2VariableType,
blueNet2VariableStatus,
blueNet2VariableAlarm,
blueNet2VariableScaling,
blueNet2VariableUnit,
blueNet2VariableSetPoint,
blueNet2VariableMode,
blueNet2VariableEntPhysicalIndex,
blueNet2VariableSetPointType,
blueNet2VariableSetPointMinValue,
blueNet2VariableSetPointMaxValue,
blueNet2VariableSetPointLowerAlarm,
blueNet2VariableSetPointLowerWarning,
blueNet2VariableSetPointUpperWarning,
blueNet2VariableSetPointUpperAlarm,
blueNet2VariableSetPointHysteresis,
blueNet2VariableSetPointRcmACUpperAlarmThreshold,
blueNet2VariableSetPointRcmACUpperAlarmGradient,
blueNet2VariableSetPointRcmACUpperWarningThreshold,
blueNet2VariableSetPointRcmACUpperWarningGradient,
blueNet2VariableDataType,
blueNet2VariableDataStatus,
blueNet2VariableDataValue,
blueNet2VariableDataDateTime,
blueNet2VariableDataByTypeType,
blueNet2VariableDataByTypeStatus,
blueNet2VariableDataByTypeValue,
blueNet2VariableDataByTypeDateTime,
blueNet2VariableDataByStateType,
blueNet2VariableDataByStateStatus,
blueNet2VariableDataByStateValue,
blueNet2VariableDataByStateDateTime,
blueNet2VariableDataBySourceType,
blueNet2VariableDataBySourceStatus,
blueNet2VariableDataBySourceValue,
blueNet2VariableDataBySourceDateTime
}
STATUS current
DESCRIPTION "Conformance group for BlueNet2 PDU variable information."
::= { blueNet2Groups 19 }
blueNet2MPGroup OBJECT-GROUP
OBJECTS {
blueNet2MPGuid,
blueNet2MPName,
blueNet2MPFriendlyName,
blueNet2MPState,
blueNet2MPTimeStamp
}
STATUS current
DESCRIPTION "Conformance group for BlueNet2 Measurement Point information."
::= { blueNet2Groups 20 }
blueNet2SpdGroup OBJECT-GROUP
OBJECTS {
blueNet2SpdGuid,
blueNet2SpdName,
blueNet2SpdFriendlyName,
blueNet2SpdDescription,
blueNet2SpdType,
blueNet2SpdStatus
}
STATUS current
DESCRIPTION "Conformance group for BlueNet2 PDU SPD information."
::= { blueNet2Groups 21 }
-- *****************************************************************************
-- Capabilities --
-- please refer to BACHMANN-BLUENET2-CAPABILITY-MIB definitions --
-- *****************************************************************************
END