-- s412 MIB version 3.10 8 Apr 05
|
|
-- for use with 3.10 and up
|
|
-- added ES definitions, subtree 40.9 for status and 40.10 for config
|
|
-- deprecated SNMP Manager 1, 40.1.4
|
|
-- added contact 6 snmp objects and traps
|
|
-- added traps for eventsensor points
|
|
-- added analog1 and analog2 names
|
|
-- modified analog1 and analog2 traps to send analog names
|
|
-- input78mode changed to read-only, deprecated
|
|
-- added humidityName
|
|
-- added temperatureName
|
|
-- modified sensor name comments to indicate 30 character wide names
|
|
|
|
|
|
s412-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
private, internet, mgmt, NetworkAddress, IpAddress,
|
|
Counter, Gauge, TimeTicks, enterprises
|
|
FROM RFC1155-SMI
|
|
OBJECT-TYPE
|
|
FROM RFC-1212
|
|
DisplayString
|
|
FROM SNMPv2-TC
|
|
TRAP-TYPE
|
|
FROM RFC-1215 ;
|
|
|
|
|
|
|
|
asentria OBJECT IDENTIFIER ::= { enterprises 3052 }
|
|
--1.3.6.1.4.1.3052
|
|
|
|
s412 OBJECT IDENTIFIER ::= { asentria 41 }
|
|
--1.3.6.1.4.1.3052.41
|
|
|
|
device OBJECT IDENTIFIER ::= { s412 1 }
|
|
--1.3.6.1.4.1.3052.41.1
|
|
|
|
contacts OBJECT IDENTIFIER ::= { s412 2 }
|
|
--1.3.6.1.4.1.3052.41.2
|
|
|
|
relays OBJECT IDENTIFIER ::= { s412 3 }
|
|
--1.3.6.1.4.1.3052.41.3
|
|
|
|
tempsensor OBJECT IDENTIFIER ::= { s412 4 }
|
|
--1.3.6.1.4.1.3052.41.4
|
|
|
|
humiditysensor OBJECT IDENTIFIER ::= { s412 5 }
|
|
--1.3.6.1.4.1.3052.41.5
|
|
|
|
passthrough OBJECT IDENTIFIER ::= { s412 6 }
|
|
--1.3.6.1.4.1.3052.41.6
|
|
|
|
ftp OBJECT IDENTIFIER ::= { s412 7 }
|
|
--1.3.6.1.4.1.3052.41.7
|
|
|
|
analog OBJECT IDENTIFIER ::= { s412 8 }
|
|
--1.3.6.1.4.1.3052.41.8
|
|
|
|
eventSensorStatus OBJECT IDENTIFIER ::= { s412 10 }
|
|
--1.3.6.1.4.1.3052.41.10
|
|
|
|
eventSensorConfig OBJECT IDENTIFIER ::= { s412 11 }
|
|
--1.3.6.1.4.1.3052.41.11
|
|
|
|
techsupport OBJECT IDENTIFIER ::= { s412 99 }
|
|
--1.3.6.1.4.1.3052.41.99
|
|
|
|
mibend OBJECT IDENTIFIER ::= { s412 100 }
|
|
--1.3.6.1.4.1.3052.41.100
|
|
|
|
contact1 OBJECT IDENTIFIER ::= { contacts 1 }
|
|
--1.3.6.1.4.1.3052.41.2.1
|
|
|
|
contact2 OBJECT IDENTIFIER ::= { contacts 2 }
|
|
--1.3.6.1.4.1.3052.41.2.2
|
|
|
|
contact3 OBJECT IDENTIFIER ::= { contacts 3 }
|
|
--1.3.6.1.4.1.3052.41.2.3
|
|
|
|
contact4 OBJECT IDENTIFIER ::= { contacts 4 }
|
|
--1.3.6.1.4.1.3052.41.2.4
|
|
|
|
contact5 OBJECT IDENTIFIER ::= { contacts 5 }
|
|
--1.3.6.1.4.1.3052.41.2.5
|
|
|
|
contact6 OBJECT IDENTIFIER ::= { contacts 6 }
|
|
--1.3.6.1.4.1.3052.41.2.6
|
|
|
|
relay1 OBJECT IDENTIFIER ::= { relays 1 }
|
|
--1.3.6.1.4.1.3052.41.3.1
|
|
|
|
relay2 OBJECT IDENTIFIER ::= { relays 2 }
|
|
--1.3.6.1.4.1.3052.41.3.2
|
|
|
|
analog1 OBJECT IDENTIFIER ::= { analog 1 }
|
|
--1.3.6.1.4.1.3052.41.8.1
|
|
|
|
analog2 OBJECT IDENTIFIER ::= { analog 2 }
|
|
--1.3.6.1.4.1.3052.41.8.2
|
|
|
|
-- device section
|
|
|
|
serialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"8-character serial number"
|
|
::= { device 1 }
|
|
--1.3.6.1.4.1.3052.41.1.1
|
|
|
|
firmwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Firmware version text string"
|
|
::= { device 2 }
|
|
--1.3.6.1.4.1.3052.41.1.2
|
|
|
|
siteID OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Site Identifier, up to 12 characters."
|
|
::= { device 3 }
|
|
--1.3.6.1.4.1.3052.41.1.3
|
|
|
|
snmpManager OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"This is snmp manager #1 "
|
|
::= { device 4 }
|
|
--1.3.6.1.4.1.3052.41.1.4
|
|
|
|
forceTraps OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Any write non-zero forces set of traps to be send to the SNMP Manager"
|
|
::= { device 6 }
|
|
--1.3.6.1.4.1.3052.41.1.6
|
|
|
|
thisTrapText OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A text string included in all traps"
|
|
::= { device 7 }
|
|
--1.3.6.1.4.1.3052.41.1.7
|
|
|
|
alarmStatus OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A text status of all alarms"
|
|
::= { device 8 }
|
|
--1.3.6.1.4.1.3052.41.1.8
|
|
|
|
snmpManager1 OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"SNMP manager #1 "
|
|
::= { device 9 }
|
|
--1.3.6.1.4.1.3052.41.1.9
|
|
|
|
snmpManager2 OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"SNMP manager #2 "
|
|
::= { device 10 }
|
|
--1.3.6.1.4.1.3052.41.1.10
|
|
|
|
snmpManager3 OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"SNMP manager #3 "
|
|
::= { device 11 }
|
|
--1.3.6.1.4.1.3052.41.1.11
|
|
|
|
snmpManager4 OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"SNMP manager #4 "
|
|
::= { device 12 }
|
|
--1.3.6.1.4.1.3052.41.1.12
|
|
|
|
statusRepeatHours OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0=none, 1-24 Number of Hours between Status Traps being Sent"
|
|
::= { device 13 }
|
|
--1.3.6.1.4.1.3052.41.1.13
|
|
|
|
serialTimeout OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"5-30, Minutes of non-activity timeout on serial setup"
|
|
::= { device 14 }
|
|
--1.3.6.1.4.1.3052.41.1.14
|
|
|
|
powerupTrapsend OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-no, 1-yes, send traps for all sensors on powerup"
|
|
::= { device 15 }
|
|
--1.3.6.1.4.1.3052.41.1.15
|
|
|
|
netlossTrapsend OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-no, 1-yes, send traps for detected netloss and back up"
|
|
::= { device 16 }
|
|
--1.3.6.1.4.1.3052.41.1.16
|
|
|
|
buildID OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"5-chars max text for build identifier"
|
|
::= { device 17 }
|
|
--1.3.6.1.4.1.3052.41.1.17
|
|
|
|
-- contacts section
|
|
|
|
contact1Name OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Name for contact, up to 30 characters"
|
|
::= { contact1 1 }
|
|
--1.3.6.1.4.1.3052.41.2.1.1
|
|
|
|
contact1State OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Current State of Contact, 0-open 1-closed"
|
|
::= { contact1 2 }
|
|
--1.3.6.1.4.1.3052.41.2.1.2
|
|
|
|
contact1AlarmEnable OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-alarms disabled 1-alarms enabled"
|
|
::= { contact1 3 }
|
|
--1.3.6.1.4.1.3052.41.2.1.3
|
|
|
|
contact1ActiveDirection OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-alarm on open 1-alarm on closed"
|
|
::= { contact1 4 }
|
|
--1.3.6.1.4.1.3052.41.2.1.4
|
|
|
|
contact1Threshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of seconds that the contact must remain in a state before generating a trap, range 0-255"
|
|
::= { contact1 5 }
|
|
--1.3.6.1.4.1.3052.41.2.1.5
|
|
|
|
contact1ReturnNormalTrap OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-return to normal traps not sent, 1-sent"
|
|
::= { contact1 6 }
|
|
--1.3.6.1.4.1.3052.41.2.1.6
|
|
|
|
contact1TrapRepeat OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-no repeats. 1-255 number of minutes between repeats of alarm traps."
|
|
::= { contact1 7 }
|
|
--1.3.6.1.4.1.3052.41.2.1.7
|
|
|
|
contact1Severity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"1-minor 2-major 3-critical 4-severe 5-warning"
|
|
::= { contact1 8 }
|
|
--1.3.6.1.4.1.3052.41.2.1.8
|
|
|
|
contact2Name OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Name for contact, up to 30 characters"
|
|
::= { contact2 1 }
|
|
--1.3.6.1.4.1.3052.41.2.2.1
|
|
|
|
contact2State OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Current State of Contact, 0-open 1-closed"
|
|
::= { contact2 2 }
|
|
--1.3.6.1.4.1.3052.41.2.2.2
|
|
|
|
contact2AlarmEnable OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-no alarms 1-alarms enabled"
|
|
::= { contact2 3 }
|
|
--1.3.6.1.4.1.3052.41.2.2.3
|
|
|
|
contact2ActiveDirection OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-alarm on open 1-alarm on closed"
|
|
::= { contact2 4 }
|
|
--1.3.6.1.4.1.3052.41.2.2.4
|
|
|
|
contact2Threshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of seconds must be in a state to be 'open' or 'closed'"
|
|
::= { contact2 5 }
|
|
--1.3.6.1.4.1.3052.41.2.2.5
|
|
|
|
contact2ReturnNormalTrap OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-not sent, 1-sent"
|
|
::= { contact2 6 }
|
|
--1.3.6.1.4.1.3052.41.2.2.6
|
|
|
|
contact2TrapRepeat OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-no repeats. 1-255 number of minutes between repeats of alarm traps"
|
|
::= { contact2 7 }
|
|
--1.3.6.1.4.1.3052.41.2.2.7
|
|
|
|
contact2Severity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"1-minor 2-major 3-critical 4-severe 5-warning"
|
|
::= { contact2 8 }
|
|
--1.3.6.1.4.1.3052.41.2.2.8
|
|
|
|
contact3Name OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Name for contact, up to 30 characters"
|
|
::= { contact3 1 }
|
|
--1.3.6.1.4.1.3052.41.2.3.1
|
|
|
|
contact3State OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Current State of Contact, 0-open 1-closed"
|
|
::= { contact3 2 }
|
|
--1.3.6.1.4.1.3052.41.2.3.2
|
|
|
|
contact3AlarmEnable OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-no alarms 1-alarms enabled"
|
|
::= { contact3 3 }
|
|
--1.3.6.1.4.1.3052.41.2.3.3
|
|
|
|
contact3ActiveDirection OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-alarm on open 1-alarm on closed"
|
|
::= { contact3 4 }
|
|
--1.3.6.1.4.1.3052.41.2.3.4
|
|
|
|
contact3Threshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of seconds must be in a state to be 'open' or 'closed'"
|
|
::= { contact3 5 }
|
|
--1.3.6.1.4.1.3052.41.2.3.5
|
|
|
|
contact3ReturnNormalTrap OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-not sent, 1-sent"
|
|
::= { contact3 6 }
|
|
--1.3.6.1.4.1.3052.41.2.3.6
|
|
|
|
contact3TrapRepeat OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-no repeats. 1-255 number of minutes between repeats of alarm traps"
|
|
::= { contact3 7 }
|
|
--1.3.6.1.4.1.3052.41.2.3.7
|
|
|
|
contact3Severity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"1-minor 2-major 3-critical 4-severe 5-warning"
|
|
::= { contact3 8 }
|
|
--1.3.6.1.4.1.3052.41.2.3.8
|
|
|
|
contact4Name OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Name for contact, up to 30 characters"
|
|
::= { contact4 1 }
|
|
--1.3.6.1.4.1.3052.41.2.4.1
|
|
|
|
contact4State OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Current State of Contact, 0-open 1-closed"
|
|
::= { contact4 2 }
|
|
--1.3.6.1.4.1.3052.41.2.4.2
|
|
|
|
contact4AlarmEnable OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-no alarms 1-alarms enabled"
|
|
::= { contact4 3 }
|
|
--1.3.6.1.4.1.3052.41.2.4.3
|
|
|
|
contact4ActiveDirection OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-alarm on open 1-alarm on closed"
|
|
::= { contact4 4 }
|
|
--1.3.6.1.4.1.3052.41.2.4.4
|
|
|
|
contact4Threshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of seconds must be in a state to be 'open' or 'closed'"
|
|
::= { contact4 5 }
|
|
--1.3.6.1.4.1.3052.41.2.4.5
|
|
|
|
contact4ReturnNormalTrap OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-not sent, 1-sent"
|
|
::= { contact4 6 }
|
|
--1.3.6.1.4.1.3052.41.2.4.6
|
|
|
|
contact4TrapRepeat OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-no repeats. 1-255 number of minutes between repeats of alarm traps"
|
|
::= { contact4 7 }
|
|
--1.3.6.1.4.1.3052.41.2.4.7
|
|
|
|
contact4Severity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"1-minor 2-major 3-critical 4-severe 5-warning"
|
|
::= { contact4 8 }
|
|
--1.3.6.1.4.1.3052.41.2.4.8
|
|
|
|
contact5Name OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Name for contact, up to 30 characters"
|
|
::= { contact5 1 }
|
|
--1.3.6.1.4.1.3052.41.2.5.1
|
|
|
|
contact5State OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Current State of Contact, 0-open 1-closed"
|
|
::= { contact5 2 }
|
|
--1.3.6.1.4.1.3052.41.2.5.2
|
|
|
|
contact5AlarmEnable OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-no alarms 1-alarms enabled"
|
|
::= { contact5 3 }
|
|
--1.3.6.1.4.1.3052.41.2.5.3
|
|
|
|
contact5ActiveDirection OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-alarm on open 1-alarm on closed"
|
|
::= { contact5 4 }
|
|
--1.3.6.1.4.1.3052.41.2.5.4
|
|
|
|
contact5Threshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of seconds must be in a state to be 'open' or 'closed'"
|
|
::= { contact5 5 }
|
|
--1.3.6.1.4.1.3052.41.2.5.5
|
|
|
|
contact5ReturnNormalTrap OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-not sent, 1-sent"
|
|
::= { contact5 6 }
|
|
--1.3.6.1.4.1.3052.41.2.5.6
|
|
|
|
contact5TrapRepeat OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-no repeats. 1-255 number of minutes between repeats of alarm traps"
|
|
::= { contact5 7 }
|
|
--1.3.6.1.4.1.3052.41.2.5.7
|
|
|
|
contact5Severity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"1-minor 2-major 3-critical 4-severe 5-warning"
|
|
::= { contact5 8 }
|
|
--1.3.6.1.4.1.3052.41.2.5.8
|
|
|
|
contact6Name OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Name for contact, up to 30 characters"
|
|
::= { contact6 1 }
|
|
--1.3.6.1.4.1.3052.41.2.6.1
|
|
|
|
contact6State OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Current State of Contact, 0-open 1-closed"
|
|
::= { contact6 2 }
|
|
--1.3.6.1.4.1.3052.41.2.6.2
|
|
|
|
contact6AlarmEnable OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-no alarms 1-alarms enabled"
|
|
::= { contact6 3 }
|
|
--1.3.6.1.4.1.3052.41.2.6.3
|
|
|
|
contact6ActiveDirection OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-alarm on open 1-alarm on closed"
|
|
::= { contact6 4 }
|
|
--1.3.6.1.4.1.3052.41.2.6.4
|
|
|
|
contact6Threshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of seconds must be in a state to be 'open' or 'closed'"
|
|
::= { contact6 5 }
|
|
--1.3.6.1.4.1.3052.41.2.6.5
|
|
|
|
contact6ReturnNormalTrap OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-not sent, 1-sent"
|
|
::= { contact6 6 }
|
|
--1.3.6.1.4.1.3052.41.2.6.6
|
|
|
|
contact6TrapRepeat OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-no repeats. 1-255 number of minutes between repeats of alarm traps."
|
|
::= { contact6 7 }
|
|
--1.3.6.1.4.1.3052.41.2.6.7
|
|
|
|
contact6Severity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"1-minor 2-major 3-critical 4-severe 5-warning"
|
|
::= { contact6 8 }
|
|
--1.3.6.1.4.1.3052.41.2.6.8
|
|
|
|
-- relays section
|
|
|
|
relay1Name OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Name for relay, up to 30 characters"
|
|
::= { relay1 1 }
|
|
--1.3.6.1.4.1.3052.41.3.1.1
|
|
|
|
relay1CurrentState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-opened, 1-closed"
|
|
::= { relay1 2 }
|
|
--1.3.6.1.4.1.3052.41.3.1.2
|
|
|
|
relay1PowerupState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-opened, 1-closed"
|
|
::= { relay1 3 }
|
|
--1.3.6.1.4.1.3052.41.3.1.3
|
|
|
|
relay2Name OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Name for relay, up to 30 characters"
|
|
::= { relay2 1 }
|
|
--1.3.6.1.4.1.3052.41.3.2.1
|
|
|
|
relay2CurrentState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-opened, 1-closed"
|
|
::= { relay2 2 }
|
|
--1.3.6.1.4.1.3052.41.3.2.2
|
|
|
|
relay2PowerupState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-opened, 1-closed"
|
|
::= { relay2 3 }
|
|
--1.3.6.1.4.1.3052.41.3.2.3
|
|
|
|
|
|
-- temp sensor section
|
|
|
|
tempValue OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Current Temperature Value, in C or F based on 1.3.6.1.4.1.3052.41.4.10"
|
|
::= { tempsensor 1 }
|
|
--1.3.6.1.4.1.3052.41.4.1
|
|
|
|
tempAlarmEnable OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0=alarms disabled, 1=alarms enabled"
|
|
::= { tempsensor 2 }
|
|
--1.3.6.1.4.1.3052.41.4.2
|
|
|
|
tempHighLevel OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Level at which the High alarm goes active"
|
|
::= { tempsensor 3 }
|
|
--1.3.6.1.4.1.3052.41.4.3
|
|
|
|
tempVeryHighLevel OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Level at which the Very High alarm goes active"
|
|
::= { tempsensor 4 }
|
|
--1.3.6.1.4.1.3052.41.4.4
|
|
|
|
tempLowLevel OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Level at which the Low alarm goes active"
|
|
::= { tempsensor 5 }
|
|
--1.3.6.1.4.1.3052.41.4.5
|
|
|
|
tempVeryLowLevel OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Level at which the Very Low alarm goes active"
|
|
::= { tempsensor 6 }
|
|
--1.3.6.1.4.1.3052.41.4.6
|
|
|
|
tempAlarmThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Seconds must be in a range to be an alarm"
|
|
::= { tempsensor 7 }
|
|
--1.3.6.1.4.1.3052.41.4.7
|
|
|
|
tempReturnNormalTrap OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-not sent, 1-send trap on return to normal range"
|
|
::= { tempsensor 8 }
|
|
--1.3.6.1.4.1.3052.41.4.8
|
|
|
|
tempTrapRepeat OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-no repeats. 1-255 number of minutes between repeats of alarm traps."
|
|
::= { tempsensor 9 }
|
|
--1.3.6.1.4.1.3052.41.4.9
|
|
|
|
tempMode OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0=all temp readings and levels in degrees F, 1=in degrees C"
|
|
::= { tempsensor 10 }
|
|
--1.3.6.1.4.1.3052.41.4.10
|
|
|
|
tempHighSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"High Level Severity 1-minor 2-major 3-critical 4-severe 5-warning"
|
|
::= { tempsensor 11 }
|
|
--1.3.6.1.4.1.3052.41.4.11
|
|
|
|
tempVeryHighSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Very High Level Severity 1-minor 2-major 3-critical 4-severe 5-warning"
|
|
::= { tempsensor 12 }
|
|
--1.3.6.1.4.1.3052.41.4.12
|
|
|
|
tempLowSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Low Level Severity 1-minor 2-major 3-critical 4-severe 5-warning"
|
|
::= { tempsensor 13 }
|
|
--1.3.6.1.4.1.3052.41.4.13
|
|
|
|
tempVeryLowSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Very Low Level Severity 1-minor 2-major 3-critical 4-severe 5-warning"
|
|
::= { tempsensor 14 }
|
|
--1.3.6.1.4.1.3052.41.4.14
|
|
|
|
tempName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Name for temperature sensor, up to 30 characters"
|
|
::= { tempsensor 15 }
|
|
--1.3.6.1.4.1.3052.41.4.15
|
|
|
|
|
|
-- humidity sensor section
|
|
|
|
humidityValue OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Current Relative Humidity Value (0-100%)"
|
|
::= { humiditysensor 1 }
|
|
--1.3.6.1.4.1.3052.41.5.1
|
|
|
|
humidityAlarmEnable OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0=alarms disabled, 1=alarms enabled"
|
|
::= { humiditysensor 2 }
|
|
--1.3.6.1.4.1.3052.41.5.2
|
|
|
|
humidityHighLevel OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Level at which the High alarm goes active"
|
|
::= { humiditysensor 3 }
|
|
--1.3.6.1.4.1.3052.41.5.3
|
|
|
|
humidityVeryHighLevel OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Level at which the Very High alarm goes active"
|
|
::= { humiditysensor 4 }
|
|
--1.3.6.1.4.1.3052.41.5.4
|
|
|
|
humidityLowLevel OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Level at which the Low alarm goes active"
|
|
::= { humiditysensor 5 }
|
|
--1.3.6.1.4.1.3052.41.5.5
|
|
|
|
humidityVeryLowLevel OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Level at which the Very Low alarm goes active"
|
|
::= { humiditysensor 6 }
|
|
--1.3.6.1.4.1.3052.41.5.6
|
|
|
|
humidityAlarmThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Seconds must be in a range to be an alarm"
|
|
::= { humiditysensor 7 }
|
|
--1.3.6.1.4.1.3052.41.5.7
|
|
|
|
humidityReturnNormalTrap OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-not sent, 1-send trap on return to normal range"
|
|
::= { humiditysensor 8 }
|
|
--1.3.6.1.4.1.3052.41.5.8
|
|
|
|
humidityTrapRepeat OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-no repeats. 1-255 number of minutes between repeats of alarm traps."
|
|
::= { humiditysensor 9 }
|
|
--1.3.6.1.4.1.3052.41.5.9
|
|
|
|
humidityHighSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"High Level Severity 1-minor 2-major 3-critical 4-severe 5-warning"
|
|
::= { humiditysensor 10 }
|
|
--1.3.6.1.4.1.3052.41.5.10
|
|
|
|
humidityVeryHighSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Very High Level Severity 1-minor 2-major 3-critical 4-severe 5-warning"
|
|
::= { humiditysensor 11 }
|
|
--1.3.6.1.4.1.3052.41.5.11
|
|
|
|
humidityLowSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Low Level Severity 1-minor 2-major 3-critical 4-severe 5-warning"
|
|
::= { humiditysensor 12 }
|
|
--1.3.6.1.4.1.3052.41.5.12
|
|
|
|
humidityVeryLowSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Very Low Level Severity 1-minor 2-major 3-critical 4-severe 5-warning"
|
|
::= { humiditysensor 13 }
|
|
--1.3.6.1.4.1.3052.41.5.13
|
|
|
|
humidityName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Name for humidity sensor, up to 30 characters"
|
|
::= { humiditysensor 14 }
|
|
--1.3.6.1.4.1.3052.41.5.14
|
|
|
|
|
|
-- passthrough section
|
|
|
|
ptNeedPassword OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-no 1-yes, is password required for passthrough connection."
|
|
::= { passthrough 1 }
|
|
--1.3.6.1.4.1.3052.41.6.1
|
|
|
|
ptSayLoginText OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-no 1-yes, is passthrough login text displayed on connection."
|
|
::= { passthrough 2 }
|
|
--1.3.6.1.4.1.3052.41.6.2
|
|
|
|
ptLoginText OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-24 char string which may be displayed on socket connection.
|
|
Requires that ptSayLoginText be enabled to display this string."
|
|
::= { passthrough 3 }
|
|
--1.3.6.1.4.1.3052.41.6.3
|
|
|
|
ptSaySiteID OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-no 1-yes, is SiteID displayed on pass through connection."
|
|
::= { passthrough 4 }
|
|
--1.3.6.1.4.1.3052.41.6.4
|
|
|
|
ptUsername OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-16 char string for Username used in serial passthrough connections"
|
|
::= { passthrough 5 }
|
|
--1.3.6.1.4.1.3052.41.6.5
|
|
|
|
ptPassword OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-16 char string for Password used in serial passthrough connections"
|
|
::= { passthrough 6 }
|
|
--1.3.6.1.4.1.3052.41.6.6
|
|
|
|
ptTimeout OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"number of minutes (1-255) of idle activity (both directions) which causes disconnect. 0-never"
|
|
::= { passthrough 7 }
|
|
--1.3.6.1.4.1.3052.41.6.7
|
|
|
|
ptEscChar OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"ASCII character code (e.g, Escape=27) which if entered on the tcp port three times
|
|
in a row causes disconnect. 0-none"
|
|
::= { passthrough 8 }
|
|
--1.3.6.1.4.1.3052.41.6.8
|
|
|
|
ptLfstripToPort OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-no 1-yes linefeed characters received on TCP connection are removed from stream to serial port"
|
|
::= { passthrough 9 }
|
|
--1.3.6.1.4.1.3052.41.6.9
|
|
|
|
ptLfstripFromPort OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-no 1-yes linefeed characters received on serial port are removed from stream to TCP connection"
|
|
::= { passthrough 10 }
|
|
--1.3.6.1.4.1.3052.41.6.10
|
|
|
|
ptSerialBaudrate OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"300 600 1200 2400 4800 9600 19200 baud are allowed values"
|
|
::= { passthrough 11 }
|
|
--1.3.6.1.4.1.3052.41.6.11
|
|
|
|
ptSerialWordlength OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"7 or 8 bit word selection"
|
|
::= { passthrough 12 }
|
|
--1.3.6.1.4.1.3052.41.6.12
|
|
|
|
ptSerialParity OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"N E O are allowed values for parity (none, even, odd) [a single-character string]"
|
|
::= { passthrough 13 }
|
|
--1.3.6.1.4.1.3052.41.6.13
|
|
|
|
ptTCPPortnumber OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"IP port number for passthrough connection (range 1024-65534)"
|
|
::= { passthrough 14 }
|
|
--1.3.6.1.4.1.3052.41.6.14
|
|
|
|
-- ftp branch
|
|
|
|
ftpUsername OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-16 char string for Username used in ftp server for updates"
|
|
::= { ftp 1 }
|
|
--1.3.6.1.4.1.3052.41.7.1
|
|
|
|
ftpPassword OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-16 char string for Password used in ftp server for updates"
|
|
::= { ftp 2 }
|
|
--1.3.6.1.4.1.3052.41.7.2
|
|
|
|
-- analog sensor section
|
|
|
|
analog1Value OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Value of current analog reading, in 1/100 volt, +- 9999 range"
|
|
::= { analog1 1 }
|
|
--1.3.6.1.4.1.3052.41.8.1.1
|
|
|
|
analog1AlarmEnable OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0=no alarms, 1=send alarms"
|
|
::= { analog1 2 }
|
|
--1.3.6.1.4.1.3052.41.8.1.2
|
|
|
|
analog1HighLevel OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Level at which the High alarm goes active"
|
|
::= { analog1 3 }
|
|
--1.3.6.1.4.1.3052.41.8.1.3
|
|
|
|
analog1VeryHighLevel OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Level at which the Very High alarm goes active"
|
|
::= { analog1 4 }
|
|
--1.3.6.1.4.1.3052.41.8.1.4
|
|
|
|
analog1LowLevel OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Level at which the Low alarm goes active"
|
|
::= { analog1 5 }
|
|
--1.3.6.1.4.1.3052.41.8.1.5
|
|
|
|
analog1VeryLowLevel OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Level at which the Very Low alarm goes active"
|
|
::= { analog1 6 }
|
|
--1.3.6.1.4.1.3052.41.8.1.6
|
|
|
|
analog1AlarmThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Seconds must be in a range to be an alarm"
|
|
::= { analog1 7 }
|
|
--1.3.6.1.4.1.3052.41.8.1.7
|
|
|
|
analog1ReturnNormalTrap OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-not sent, 1-send trap on return to normal range"
|
|
::= { analog1 8 }
|
|
--1.3.6.1.4.1.3052.41.8.1.8
|
|
|
|
analog1TrapRepeat OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-no repeats else number of minutes between repeats of trap"
|
|
::= { analog1 9 }
|
|
--1.3.6.1.4.1.3052.41.8.1.9
|
|
|
|
analog1HighSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"High Level Severity 1-minor 2-major 3-critical 4-severe 5-warning"
|
|
::= { analog1 10 }
|
|
--1.3.6.1.4.1.3052.41.8.1.10
|
|
|
|
analog1VeryHighSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Very High Level Severity 1-minor 2-major 3-critical 4-severe 5-warning"
|
|
::= { analog1 11 }
|
|
--1.3.6.1.4.1.3052.41.8.1.11
|
|
|
|
analog1LowSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Low Level Severity 1-minor 2-major 3-critical 4-severe 5-warning"
|
|
::= { analog1 12 }
|
|
--1.3.6.1.4.1.3052.41.8.1.12
|
|
|
|
analog1VeryLowSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Very Low Level Severity 1-minor 2-major 3-critical 4-severe 5-warning"
|
|
::= { analog1 13 }
|
|
--1.3.6.1.4.1.3052.41.8.1.13
|
|
|
|
analog1Name OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Name for analog sensor 1, up to 30 characters"
|
|
::= { analog1 14 }
|
|
--1.3.6.1.4.1.3052.41.8.1.14
|
|
|
|
analog2Value OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Value of current analog reading, in 1/100 volt, +- 9999 range"
|
|
::= { analog2 1 }
|
|
--1.3.6.1.4.1.3052.41.8.2.1
|
|
|
|
analog2AlarmEnable OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0=no alarms, 1=send alarms"
|
|
::= { analog2 2 }
|
|
--1.3.6.1.4.1.3052.41.8.2.2
|
|
|
|
analog2HighLevel OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Level at which the High alarm goes active"
|
|
::= { analog2 3 }
|
|
--1.3.6.1.4.1.3052.41.8.2.3
|
|
|
|
analog2VeryHighLevel OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Level at which the Very High alarm goes active"
|
|
::= { analog2 4 }
|
|
--1.3.6.1.4.1.3052.41.8.2.4
|
|
|
|
analog2LowLevel OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Level at which the Low alarm goes active"
|
|
::= { analog2 5 }
|
|
--1.3.6.1.4.1.3052.41.8.2.5
|
|
|
|
analog2VeryLowLevel OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Level at which the Very Low alarm goes active"
|
|
::= { analog2 6 }
|
|
--1.3.6.1.4.1.3052.41.8.2.6
|
|
|
|
analog2AlarmThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Seconds must be in a range to be an alarm"
|
|
::= { analog2 7 }
|
|
--1.3.6.1.4.1.3052.41.8.2.7
|
|
|
|
analog2ReturnNormalTrap OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-not sent, 1-send trap on return to normal range"
|
|
::= { analog2 8 }
|
|
--1.3.6.1.4.1.3052.41.8.2.8
|
|
|
|
analog2TrapRepeat OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0-no repeats else number of minutes between repeats of trap"
|
|
::= { analog2 9 }
|
|
--1.3.6.1.4.1.3052.41.8.2.9
|
|
|
|
analog2HighSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"High Level Severity 1-minor 2-major 3-critical 4-severe 5-warning"
|
|
::= { analog2 10 }
|
|
--1.3.6.1.4.1.3052.41.8.2.10
|
|
|
|
analog2VeryHighSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Very High Level Severity 1-minor 2-major 3-critical 4-severe 5-warning"
|
|
::= { analog2 11 }
|
|
--1.3.6.1.4.1.3052.41.8.2.11
|
|
|
|
analog2LowSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Low Level Severity 1-minor 2-major 3-critical 4-severe 5-warning"
|
|
::= { analog2 12 }
|
|
--1.3.6.1.4.1.3052.41.8.2.12
|
|
|
|
analog2VeryLowSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Very Low Level Severity 1-minor 2-major 3-critical 4-severe 5-warning"
|
|
::= { analog2 13 }
|
|
--1.3.6.1.4.1.3052.41.8.2.13
|
|
|
|
analog2Name OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Name for analog sensor 2, up to 30 characters"
|
|
::= { analog2 14 }
|
|
--1.3.6.1.4.1.3052.41.8.2.14
|
|
|
|
-- voltage section
|
|
|
|
|
|
-- ES status section
|
|
|
|
esPointTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF ESPoint
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"
|
|
This table organizes 4 basic attributes of points. A point
|
|
is a particular sensor on an EventSensor (e.g., temperature,
|
|
humidity, contact closure 2, relay 5, etc.). The 4 point
|
|
attributes are its name, whether it's in its event state,
|
|
the point's value as a number and its value as a string.
|
|
|
|
Points are referenced by a point index. The point index
|
|
is a string of 3 numbers separated by periods.
|
|
It contains all the information necessary for getting a piece
|
|
of data off an event sensor; namely, which EventSensor,
|
|
point class, and which-sensor-of-that-class (a.k.a. point).
|
|
"
|
|
::= { eventSensorStatus 1 }
|
|
--1.3.6.1.4.1.3052.41.10.1
|
|
|
|
esPointEntry OBJECT-TYPE
|
|
SYNTAX ESPoint
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Entry for EventSensor point table"
|
|
INDEX { esIndexES, esIndexPC, esIndexPoint }
|
|
::= { esPointTable 1 }
|
|
--1.3.6.1.4.1.3052.41.10.1.1
|
|
|
|
esIndexES OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The part of the point index that refers to an
|
|
EventSensor.
|
|
|
|
The point index is a string of 3 numbers separated
|
|
by periods. It contains all the information
|
|
necessary for getting a piece of data off an event
|
|
sensor; namely, which EventSensor, point class,
|
|
and which-sensor-of-that-class (a.k.a. point).
|
|
|
|
This object's allowable values are 1 through 4,
|
|
which refer to attached EventSensors.
|
|
|
|
The number corresponding to an EventSensor is
|
|
determined by the user at the initial configuration
|
|
time. If there is an internal sensor in the unit,
|
|
it will always be the first item in the Sensor
|
|
Events setup menu.
|
|
|
|
For example, if a new EventSensor is configured as
|
|
the 2nd entry AFTER the internal EventSensor (if
|
|
one exists) in the Sensor Events Setup Menu, then
|
|
that EventSensor will be known from then on as
|
|
EventSensor 2. All point indeces with esIndexES=2
|
|
will now refer to that particular EventSensor.
|
|
"
|
|
::= { esPointEntry 1 }
|
|
--1.3.6.1.4.1.3052.41.10.1.1.1
|
|
|
|
esIndexPC OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The part of the point index that refers to point class.
|
|
|
|
The point index is a string of 3 numbers separated by periods.
|
|
It contains all the information necessary for getting a piece
|
|
of data off an event sensor; namely, which EventSensor,
|
|
point class, and which-sensor-of-that-class (a.k.a. point).
|
|
|
|
The values for this object are:
|
|
1=temperature sensor
|
|
2=contact closure
|
|
3=humidity sensor
|
|
4=noise sensor
|
|
5=analog input
|
|
6=relay
|
|
"
|
|
::= { esPointEntry 2 }
|
|
--1.3.6.1.4.1.3052.41.10.1.1.2
|
|
|
|
esIndexPoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The part of the point index that delineates which
|
|
sensor on the EventSensor.
|
|
|
|
So this combined with esIndexPC (Point Class or type)
|
|
and esIndexES (which EventSensor) uniquely defines each
|
|
point (sensor or relay) attached to a unit. For
|
|
example, if esIndexES is 3, esIndexPC is 1 and
|
|
esIndexPoint is 4 then this is the Fourth Temperature
|
|
Sensor on EventSensor number 3."
|
|
::= { esPointEntry 3 }
|
|
--1.3.6.1.4.1.3052.41.10.1.1.3
|
|
|
|
esPointName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name of the point on an EventSensor. For example,
|
|
'AC temp' (in the case of the temperature sensor on an
|
|
EventSensor).
|
|
|
|
There can be multiple points of the same point class on an
|
|
EventSensor (e.g., 8 contact closures) and multiple sensor
|
|
classes on an EventSensor (e.g., temperature, contact closure,
|
|
humidity).
|
|
|
|
If the point referenced by a given point index is solitary
|
|
(e.g., temperature sensor, because there can be only one on
|
|
an EventSensor), then this object reads as '<EventSensor
|
|
name>'. Setting this object for solitary point indices sets
|
|
the EventSensor name only.
|
|
|
|
On the other hand, if a given point is among other points of
|
|
the same point class on an EventSensor, then this object reads
|
|
as '<Sensor name>'. Setting this object for these NON-
|
|
solitary point indices sets the sensor name only - not the
|
|
EventSensor name."
|
|
::= { esPointEntry 4 }
|
|
--1.3.6.1.4.1.3052.41.10.1.1.4
|
|
|
|
esPointInEventState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A number referring to the event state of a point
|
|
on an EventSensor. This number can have different
|
|
meanings depending on the point class.
|
|
|
|
If the point class is temperature, humidity, or
|
|
analog input, then the values of this object are:
|
|
1=very low
|
|
2=low
|
|
3=normal
|
|
4=high
|
|
5=very high
|
|
|
|
For contact closures and relays the values of this
|
|
object are:
|
|
1=point in event state
|
|
2=point in normal state
|
|
|
|
For any point class and any point, if the event
|
|
state is undefined, then the value of this object
|
|
is 0.
|
|
|
|
For any point class except relay, this object is
|
|
read-only. For relays, setting this object to 1
|
|
puts the relay into its open state.
|
|
Setting it to 2 puts the relay into its closed
|
|
state.
|
|
"
|
|
::= { esPointEntry 5 }
|
|
--1.3.6.1.4.1.3052.41.10.1.1.5
|
|
|
|
esPointValueInt OBJECT-TYPE
|
|
SYNTAX INTEGER (-32768..32767)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A number referring to the value of a point on an
|
|
EventSensor.
|
|
|
|
If the point class is temperature, then this object
|
|
is the temperature in its configured scale (default
|
|
is Fahrenheit).
|
|
|
|
If the point class is contact closure or relay, then
|
|
this object is either 0 (open) or 1 (closed).
|
|
|
|
If the point class is humidity, then this object
|
|
is the percent relative humidity.
|
|
|
|
If the point class is analog input, then this
|
|
object is the signed input value in tenths of the
|
|
configured units.
|
|
|
|
For any point class except relay, this object is
|
|
read-only. For relays, setting this object to 1
|
|
closes the relay, while setting it to 0 opens it.
|
|
This works regardless of the control mode of the
|
|
relay.
|
|
"
|
|
::= { esPointEntry 6 }
|
|
--1.3.6.1.4.1.3052.41.10.1.1.6
|
|
|
|
esPointValueStr OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A string referring to the value of a point on an
|
|
EventSensor.
|
|
|
|
For contact closures and relays this object is
|
|
either 'Open' or 'Closed'.
|
|
|
|
For temperature and humidity point classes, this
|
|
object is the string representation of the
|
|
esPointValueInt object. For temperature, 'C' or
|
|
'F' is including in the string to indicate scale.
|
|
|
|
For analog inputs, this object is the string
|
|
representation of the plus/minus input in volts.
|
|
"
|
|
::= { esPointEntry 7 }
|
|
--1.3.6.1.4.1.3052.41.10.1.1.7
|
|
|
|
-- ES config section
|
|
|
|
esNumberEventSensors OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of EventSensors recognized by the s412
|
|
Range: 0-4"
|
|
::= { eventSensorConfig 1 }
|
|
--1.3.6.1.4.1.3052.41.11.1
|
|
|
|
esTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF ESExist
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The table of what EventSensors are attached to the unit"
|
|
::= { eventSensorConfig 2 }
|
|
--1.3.6.1.4.1.3052.41.11.2
|
|
|
|
esEntry OBJECT-TYPE
|
|
SYNTAX ESExist
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Table entry for EventSensor table"
|
|
INDEX { esIndex }
|
|
::= { esTable 1 }
|
|
--1.3.6.1.4.1.3052.41.11.2.1
|
|
|
|
esIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This number refers to an EventSensor; it has the
|
|
same meaning as the esIndexES object (see above),
|
|
except that this object is used only within the
|
|
esTable branch.
|
|
|
|
This object's allowable values are 1 through 4,
|
|
which refer to additional attached EventSensors.
|
|
|
|
The number corresponding to an EventSensor is
|
|
determined by the user at the initial configuration
|
|
time.
|
|
"
|
|
::= { esEntry 1 }
|
|
--1.3.6.1.4.1.3052.41.11.2.1.1
|
|
|
|
esID OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The factory-assigned ID of the EventSensor"
|
|
::= { esEntry 2 }
|
|
--1.3.6.1.4.1.3052.41.11.2.1.2
|
|
|
|
|
|
esNumberTempSensors OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of temperature sensors on the EventSensor"
|
|
::= { esEntry 3 }
|
|
--1.3.6.1.4.1.3052.41.11.2.1.3
|
|
|
|
esTempReportingMode OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Description of how temperature values should
|
|
be interpreted."
|
|
::= { esEntry 4 }
|
|
--1.3.6.1.4.1.3052.41.11.2.1.4
|
|
|
|
esNumberCCs OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of contact closures on the EventSensor."
|
|
::= { esEntry 5 }
|
|
--1.3.6.1.4.1.3052.41.11.2.1.5
|
|
|
|
esCCReportingMode OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Description of how CC values should be interpreted."
|
|
::= { esEntry 6 }
|
|
--1.3.6.1.4.1.3052.41.11.2.1.6
|
|
|
|
esNumberHumidSensors OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of humidity sensors on the EventSensor."
|
|
::= { esEntry 7 }
|
|
--1.3.6.1.4.1.3052.41.11.2.1.7
|
|
|
|
esHumidReportingMode OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Description of how humidity sensor values should be
|
|
interpreted."
|
|
::= { esEntry 8 }
|
|
--1.3.6.1.4.1.3052.41.11.2.1.8
|
|
|
|
|
|
|
|
esNumberAnalog OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of analog inputs on the EventSensor."
|
|
::= { esEntry 13 }
|
|
--1.3.6.1.4.1.3052.41.11.2.1.13
|
|
|
|
esAnalogReportingMode OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Description of how analog input values should be
|
|
interpreted."
|
|
::= { esEntry 14 }
|
|
--1.3.6.1.4.1.3052.41.11.2.1.14
|
|
|
|
esNumberRelayOutputs OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of relay outputs on the EventSensor"
|
|
::= { esEntry 15 }
|
|
--1.3.6.1.4.1.3052.41.11.2.1.15
|
|
|
|
esRelayReportingMode OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Description of how relay output values
|
|
should be interpreted."
|
|
::= { esEntry 16 }
|
|
--1.3.6.1.4.1.3052.41.11.2.1.16
|
|
|
|
|
|
-- tech support (and windows setup application) section
|
|
-- requires special community name for writes
|
|
|
|
techsupportIPAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"May read or Set IP Address, takes effect on restart"
|
|
::= { techsupport 1 }
|
|
--1.3.6.1.4.1.3052.41.99.1
|
|
|
|
techsupportNetMask OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"May read or Set NetMask, takes effect on restart"
|
|
::= { techsupport 2 }
|
|
--1.3.6.1.4.1.3052.41.99.2
|
|
|
|
techsupportRouter OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"May read or Set Router IP Address, takes effect on restart"
|
|
::= { techsupport 3 }
|
|
--1.3.6.1.4.1.3052.41.99.3
|
|
|
|
techsupportRestart OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Reads as 0, any Write resets unit so new IP, Netmask, Router may be used"
|
|
::= { techsupport 4 }
|
|
--1.3.6.1.4.1.3052.41.99.4
|
|
|
|
techsupportVersionNumber OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Version Number of Firmware"
|
|
::= { techsupport 5 }
|
|
--1.3.6.1.4.1.3052.41.99.5
|
|
|
|
|
|
mibendObject OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An object after all active mib items, to help some managers compile"
|
|
::= { mibend 1 }
|
|
--1.3.6.1.4.1.3052.41.100.1
|
|
|
|
-- object definitions
|
|
|
|
ESPoint ::=
|
|
SEQUENCE {
|
|
esIndexES
|
|
INTEGER,
|
|
esIndexPC
|
|
INTEGER,
|
|
esIndexPoint
|
|
INTEGER,
|
|
esPointName
|
|
DisplayString,
|
|
esPointInEventState
|
|
INTEGER,
|
|
esPointValueInt
|
|
INTEGER,
|
|
esPointValueStr
|
|
DisplayString
|
|
}
|
|
|
|
ESExist ::=
|
|
SEQUENCE {
|
|
esIndex
|
|
INTEGER,
|
|
esID
|
|
DisplayString,
|
|
esNumberTempSensors
|
|
INTEGER,
|
|
esTempReportingMode
|
|
DisplayString,
|
|
esNumberCCs
|
|
INTEGER,
|
|
esCCReportingMode
|
|
DisplayString,
|
|
esNumberHumidSensors
|
|
INTEGER,
|
|
esHumidReportingMode
|
|
DisplayString,
|
|
esNumberAnalog
|
|
INTEGER,
|
|
esAnalogReportingMode
|
|
DisplayString,
|
|
esNumberRelayOutputs
|
|
INTEGER,
|
|
esRelayReportingMode
|
|
DisplayString
|
|
}
|
|
|
|
|
|
-- end of MIB objects
|
|
|
|
|
|
-- TRAP DEFINITIONS
|
|
|
|
|
|
contact1ActiveTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, contact1Name, contact1State }
|
|
DESCRIPTION
|
|
"Sent to show Contact 1 is in the alarm state"
|
|
::= 20001
|
|
|
|
contact2ActiveTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, contact2Name, contact2State }
|
|
DESCRIPTION
|
|
"Sent to show Contact 2 is in the alarm state"
|
|
::= 20002
|
|
|
|
contact3ActiveTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, contact3Name, contact3State }
|
|
DESCRIPTION
|
|
"Sent to show Contact 3 is in the alarm state"
|
|
::= 20003
|
|
|
|
contact4ActiveTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, contact4Name, contact4State }
|
|
DESCRIPTION
|
|
"Sent to show Contact 4 is in the alarm state"
|
|
::= 20004
|
|
|
|
contact5ActiveTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, contact5Name, contact5State }
|
|
DESCRIPTION
|
|
"Sent to show Contact 5 is in the alarm state"
|
|
::= 20005
|
|
|
|
contact6ActiveTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, contact6Name, contact6State }
|
|
DESCRIPTION
|
|
"Sent to show Contact 6 is in the alarm state"
|
|
::= 20006
|
|
|
|
tempHighTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, tempValue }
|
|
DESCRIPTION
|
|
"Sent to show Temp exceeded High Temp Threshold"
|
|
::= 20010
|
|
|
|
tempVeryHighTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, tempValue }
|
|
DESCRIPTION
|
|
"Sent to show Temp exceeded Very High Temp Threshold"
|
|
::= 20011
|
|
|
|
tempLowTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, tempValue }
|
|
DESCRIPTION
|
|
"Sent to show Temp went below Low Temp Threshold"
|
|
::= 20012
|
|
|
|
tempVeryLowTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, tempValue }
|
|
DESCRIPTION
|
|
"Sent to show Temp went below Very Low Temp Threshold"
|
|
::= 20013
|
|
|
|
humidityHighTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, humidityValue }
|
|
DESCRIPTION
|
|
"Sent to show humidity exceeded High humidity Threshold"
|
|
::= 20020
|
|
|
|
humidityVeryHighTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, humidityValue }
|
|
DESCRIPTION
|
|
"Sent to show humidity exceeded Very High humidity Threshold"
|
|
::= 20021
|
|
|
|
humidityLowTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, humidityValue }
|
|
DESCRIPTION
|
|
"Sent to show humidity went below Low humidity Threshold"
|
|
::= 20022
|
|
|
|
humidityVeryLowTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, humidityValue }
|
|
DESCRIPTION
|
|
"Sent to show humidity went below Very Low humidity Threshold"
|
|
::= 20023
|
|
|
|
analog1HighTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, analog1Name, analog1Value }
|
|
DESCRIPTION
|
|
"Sent to show analog1 exceeded High analog1 Threshold"
|
|
::= 20030
|
|
|
|
analog1VeryHighTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, analog1Name, analog1Value }
|
|
DESCRIPTION
|
|
"Sent to show analog1 exceeded Very High analog1 Threshold"
|
|
::= 20031
|
|
|
|
analog1LowTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, analog1Name, analog1Value }
|
|
DESCRIPTION
|
|
"Sent to show analog1 went below Low analog1 Threshold"
|
|
::= 20032
|
|
|
|
analog1VeryLowTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, analog1Name, analog1Value }
|
|
DESCRIPTION
|
|
"Sent to show analog1 went below Very Low analog1 Threshold"
|
|
::= 20033
|
|
|
|
analog2HighTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, analog2Name, analog2Value }
|
|
DESCRIPTION
|
|
"Sent to show analog2 exceeded High analog2 Threshold"
|
|
::= 20040
|
|
|
|
analog2VeryHighTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, analog2Name, analog2Value }
|
|
DESCRIPTION
|
|
"Sent to show analog2 exceeded Very High analog2 Threshold"
|
|
::= 20041
|
|
|
|
analog2LowTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, analog2Name, analog2Value }
|
|
DESCRIPTION
|
|
"Sent to show analog2 went below Low analog2 Threshold"
|
|
::= 20042
|
|
|
|
analog2VeryLowTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, analog2Name, analog2Value }
|
|
DESCRIPTION
|
|
"Sent to show analog2 went below Very Low analog2 Threshold"
|
|
::= 20043
|
|
|
|
contactESActiveTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, esPointName, esPointValueInt, esIndexES, esIndexPoint }
|
|
DESCRIPTION
|
|
"Sent to show EventSensor contact is in the alarm state"
|
|
::= 20101
|
|
|
|
tempESHighTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, esPointName, esPointValueInt, esIndexES, esIndexPoint }
|
|
DESCRIPTION
|
|
"Sent to show Temp exceeded High Threshold on an EventSensor"
|
|
::= 20110
|
|
|
|
tempESVeryHighTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, esPointName, esPointValueInt, esIndexES, esIndexPoint }
|
|
DESCRIPTION
|
|
"Sent to show Temp exceeded Very High Threshold on an EventSensor"
|
|
::= 20111
|
|
|
|
tempESLowTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, esPointName, esPointValueInt, esIndexES, esIndexPoint }
|
|
DESCRIPTION
|
|
"Sent to show Temp went below Low Threshold on an EventSensor"
|
|
::= 20112
|
|
|
|
tempESVeryLowTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, esPointName, esPointValueInt, esIndexES, esIndexPoint }
|
|
DESCRIPTION
|
|
"Sent to show Temp went below Very Low Threshold on an EventSensor"
|
|
::= 20113
|
|
|
|
humidityESHighTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, esPointName, esPointValueInt, esIndexES, esIndexPoint }
|
|
DESCRIPTION
|
|
"Sent to show humidity exceeded High Threshold on an EventSensor"
|
|
::= 20120
|
|
|
|
humidityESVeryHighTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, esPointName, esPointValueInt, esIndexES, esIndexPoint }
|
|
DESCRIPTION
|
|
"Sent to show humidity exceeded Very High Threshold on an EventSensor"
|
|
::= 20121
|
|
|
|
humidityESLowTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, esPointName, esPointValueInt, esIndexES, esIndexPoint }
|
|
DESCRIPTION
|
|
"Sent to show humidity went below Low Threshold on an EventSensor"
|
|
::= 20122
|
|
|
|
humidityESVeryLowTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, esPointName, esPointValueInt, esIndexES, esIndexPoint }
|
|
DESCRIPTION
|
|
"Sent to show humidity went below Very Low Threshold on an EventSensor"
|
|
::= 20123
|
|
|
|
voltageESHighTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, esPointName, esPointValueInt, esIndexES, esIndexPoint }
|
|
DESCRIPTION
|
|
"Sent to show voltage exceeded High Threshold on an EventSensor"
|
|
::= 20130
|
|
|
|
voltageESVeryHighTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, esPointName, esPointValueInt, esIndexES, esIndexPoint }
|
|
DESCRIPTION
|
|
"Sent to show voltage exceeded Very High Threshold on an EventSensor"
|
|
::= 20131
|
|
|
|
voltageESLowTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, esPointName, esPointValueInt, esIndexES, esIndexPoint }
|
|
DESCRIPTION
|
|
"Sent to show voltage went below Low Threshold on an EventSensor"
|
|
::= 20132
|
|
|
|
voltageESVeryLowTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, esPointName, esPointValueInt, esIndexES, esIndexPoint }
|
|
DESCRIPTION
|
|
"Sent to show voltage went below Very Low Threshold on an EventSensor"
|
|
::= 20133
|
|
|
|
contact1NormalTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, contact1Name, contact1State }
|
|
DESCRIPTION
|
|
"Sent to show Contact 1 is in the normal state"
|
|
::= 21001
|
|
|
|
contact2NormalTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, contact2Name, contact2State }
|
|
DESCRIPTION
|
|
"Sent to show Contact 2 is in the normal state"
|
|
::= 21002
|
|
|
|
contact3NormalTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, contact3Name, contact3State }
|
|
DESCRIPTION
|
|
"Sent to show Contact 3 is in the normal state"
|
|
::= 21003
|
|
|
|
contact4NormalTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, contact4Name, contact4State }
|
|
DESCRIPTION
|
|
"Sent to show Contact 4 is in the normal state"
|
|
::= 21004
|
|
|
|
contact5NormalTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, contact5Name, contact5State }
|
|
DESCRIPTION
|
|
"Sent to show Contact 5 is in the normal state"
|
|
::= 21005
|
|
|
|
contact6NormalTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, contact6Name, contact6State }
|
|
DESCRIPTION
|
|
"Sent to show Contact 6 is in the normal state"
|
|
::= 21006
|
|
|
|
tempNormalTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, tempValue }
|
|
DESCRIPTION
|
|
"Sent to show Temp went back to Normal range"
|
|
::= 21010
|
|
|
|
humidityNormalTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, humidityValue }
|
|
DESCRIPTION
|
|
"Sent to show Humidity went back to Normal range"
|
|
::= 21020
|
|
|
|
analog1NormalTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, analog1Name, analog1Value }
|
|
DESCRIPTION
|
|
"Sent to show analog1 went back to Normal range"
|
|
::= 21030
|
|
|
|
analog2NormalTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, analog2Name, analog2Value }
|
|
DESCRIPTION
|
|
"Sent to show analog2 went back to Normal range"
|
|
::= 21040
|
|
|
|
contactESNormalTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, esPointName, esPointValueInt, esIndexES, esIndexPoint }
|
|
DESCRIPTION
|
|
"Send to show EventSensor contact has returned to normal state"
|
|
::= 21101
|
|
|
|
tempESNormalTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, esPointName, esPointValueInt, esIndexES, esIndexPoint }
|
|
DESCRIPTION
|
|
"Sent to show EventSensor Temp went back to Normal range"
|
|
::= 21110
|
|
|
|
humidityESNormalTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, esPointName, esPointValueInt, esIndexES, esIndexPoint }
|
|
DESCRIPTION
|
|
"Sent to show EventSensor Humidity went back to Normal range"
|
|
::= 21120
|
|
|
|
voltageESNormalTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID, esPointName, esPointValueInt, esIndexES, esIndexPoint }
|
|
DESCRIPTION
|
|
"Sent to show EventSensor voltage went back to Normal range"
|
|
::= 21130
|
|
|
|
testTrap TRAP-TYPE
|
|
ENTERPRISE s412
|
|
VARIABLES { thisTrapText, siteID }
|
|
DESCRIPTION
|
|
"Sent for testing the SNMP interface"
|
|
::= 22000
|
|
|
|
|
|
|
|
END
|
|
|
|
|