-- * APC cPDU SNMP MIB DEFINITIONS
-- * $Date: 25 NOVEMBER 2021 10:00:00 $
-- * $Revision: 1.3 $
-- Revised
-- Confidential - Need To Know
-- ****************************************************************************
--
-- APC cPDU SNMP
-- Management Information Base for SNMP Network Management for PDU
--
-- Copyright (c) 2021 APC
--
-- The APC Enterprise number is 318.
-- The ASN.1 prefix to, and including the APC is:
-- 1.3.6.1.4.1.318
--
-- MIB Version 1.3
--
-- *********************************************************************
-- Release History
-- Updated the CASCADING OID DESCRIPTION
-- Updated the OID Description for OLED Orientation
--
-- *********************************************************************
-- ===================================================================================
-- sysDescr (1.3.6.1.2.1.1.1) which is defined in RFC1213.MIB.
-- sysObjectID (1.3.6.1.2.1.1.2) which is defined in RFC1213.MIB.
-- sysContact (1.3.6.1.2.1.1.4) which is defined in RFC1213.MIB.
-- sysName (1.3.6.1.2.1.1.5) is which is defined in RFC1213.MIB.
-- sysLocation (1.3.6.1.2.1.1.6) which is defined in RFC1213.MIB.
--
-- sysDescr OBJECT-TYPE
-- SYNTAX DisplayString (SIZE (0..255))
-- ACCESS read-only
-- STATUS mandatory
-- DESCRIPTION
-- "A textual description of the entity. This value
-- should include the full name, hardware version and
-- firmware version of management module's.
-- It is mandatory that this only contain
-- printable ASCII characters."
-- ::= { system 1 }
--
-- sysObjectID OBJECT-TYPE
-- SYNTAX DisplayString (SIZE (0..255))
-- ACCESS read-write
-- STATUS mandatory
-- DESCRIPTION
-- "Return the OID of the management module for PDU defined in the APC.MIB
-- i.e. .1.3.6.1.4.1.318.1.1.32 is for OIDs."
-- ::= { system 2 }
--
-- sysContact OBJECT-TYPE
-- SYNTAX DisplayString (SIZE (0..255))
-- ACCESS read-write
-- STATUS mandatory
-- DESCRIPTION
-- "The textual identification of the contact person
-- for this managed node, together with information
-- on how to contact this person."
-- ::= { system 4 }
--
-- sysName OBJECT-TYPE
-- SYNTAX DisplayString (SIZE (0..255))
-- ACCESS read-write
-- STATUS mandatory
-- DESCRIPTION
-- "An administratively-assigned name for this
-- managed node. By convention, this is the node's
-- fully-qualified domain name."
-- ::= { system 5 }
--
-- sysLocation OBJECT-TYPE
-- SYNTAX DisplayString (SIZE (0..255))
-- ACCESS read-write
-- STATUS mandatory
-- DESCRIPTION
-- "The physical location of this node (e.g.,
-- `telephone closet, 3rd floor')."
-- ::= { system 6 }
--
-- ====================================================================================
--
-- ====================================================================================
CPDU-MIB DEFINITIONS ::= BEGIN
IMPORTS
enterprises, IpAddress, Gauge, TimeTicks FROM RFC1155-SMI
DisplayString FROM RFC1213-MIB
SnmpAdminString FROM SNMP-FRAMEWORK-MIB
OBJECT-TYPE FROM RFC-1212
TRAP-TYPE FROM RFC-1215
InetAddressType FROM INET-ADDRESS-MIB
InetAddress FROM INET-ADDRESS-MIB
MacAddress FROM SNMPv2-TC;
-- IMPORTS End
apc OBJECT IDENTIFIER ::= { enterprises 318 }
products OBJECT IDENTIFIER ::= { apc 1 }
hardware OBJECT IDENTIFIER ::= { products 1 }
cPDU OBJECT IDENTIFIER ::= { hardware 32 }
-- ++++ Start of cPDU ++++
pduNamePlate OBJECT IDENTIFIER ::= { cPDU 1 }
pduUnit OBJECT IDENTIFIER ::= { cPDU 2 }
pduInputPhase OBJECT IDENTIFIER ::= { cPDU 3 }
pduCircuitBreaker OBJECT IDENTIFIER ::= { cPDU 4 }
pduOutlet OBJECT IDENTIFIER ::= { cPDU 5 }
pduExternalSensor OBJECT IDENTIFIER ::= { cPDU 6 }
pduSmartCabinet OBJECT IDENTIFIER ::= { cPDU 7 }
pduTraps OBJECT IDENTIFIER ::= { cPDU 8 }
pduEhandle OBJECT IDENTIFIER ::= { cPDU 9 }
-- Start pduNamePlate
pduNamePlateTableSize OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total number of PDUs"
::= { pduNamePlate 1 }
-- pduNamePlateTable
pduNamePlateTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduNamePlateEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table of PDU nameplate data"
::= { pduNamePlate 2 }
pduNamePlateEntry OBJECT-TYPE
SYNTAX PduNamePlateEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Nameplate data from the PDU being queried. The numbers of entries equals the value of pduNamePlateTableSize."
INDEX { pduNamePlateIndex }
::= { pduNamePlateTable 1 }
PduNamePlateEntry ::= SEQUENCE {
pduNamePlateIndex
Integer32,
pduNamePlateName
DisplayString,
pduNamePlateLocation
DisplayString,
pduNamePlateInetAddressType
INTEGER,
pduNamePlateIPAddress
InetAddress,
pduNamePlateInetNetMask
InetAddress,
pduNamePlateInetGateway
InetAddress,
pduNamePlateMACAddress
MacAddress,
pduNamePlateUTCTimeOffset
DisplayString,
pduNamePlateModelNumber
DisplayString,
pduNamePlatePartNumber
DisplayString,
pduNamePlateSerialNumber
DisplayString,
pduNamePlateDateofManufacture
DisplayString,
pduNamePlateFirmwareVersion
DisplayString,
pduNamePlateFirmwareVersionTimeStamp
DisplayString,
pduNamePlateType
INTEGER
}
pduNamePlateIndex OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The index of the PDU nameplate table entry"
::= { pduNamePlateEntry 1 }
pduNamePlateName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A user-defined string identifying the PDU"
::= { pduNamePlateEntry 2 }
pduNamePlateLocation OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A user-defined string identifying the location of PDU"
::= { pduNamePlateEntry 3 }
pduNamePlateInetAddressType OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The type of address format"
::= { pduNamePlateEntry 4 }
pduNamePlateIPAddress OBJECT-TYPE
SYNTAX InetAddress
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current IP address. A value of 0.0.0.0 indicates an error or an unset option"
::= { pduNamePlateEntry 5 }
pduNamePlateInetNetMask OBJECT-TYPE
SYNTAX InetAddress
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current netmask. A value of 0.0.0.0 indiates an error or an unset option"
::= { pduNamePlateEntry 6 }
pduNamePlateInetGateway OBJECT-TYPE
SYNTAX InetAddress
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current gateway. A value of 0.0.0.0 indicates an error or an unset option"
::= { pduNamePlateEntry 7 }
pduNamePlateMACAddress OBJECT-TYPE
SYNTAX MacAddress
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The assigned MAC address for the PDU"
::= { pduNamePlateEntry 8 }
pduNamePlateUTCTimeOffset OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The difference in hours and minutes from Coordinated Universal
Time(UTC) for the time used in a particular time zone"
::= { pduNamePlateEntry 9 }
pduNamePlateModelNumber OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU model number"
::= { pduNamePlateEntry 10 }
pduNamePlatePartNumber OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU part number"
::= { pduNamePlateEntry 11 }
pduNamePlateSerialNumber OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU serial number"
::= { pduNamePlateEntry 12 }
pduNamePlateDateofManufacture OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The date the PDU was manufactured in mm/dd/yyyy format"
::= { pduNamePlateEntry 13 }
pduNamePlateFirmwareVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU firmware version"
::= { pduNamePlateEntry 14 }
pduNamePlateFirmwareVersionTimeStamp OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Timestamp of when the PDU firmware was last updated"
::= { pduNamePlateEntry 15 }
pduNamePlateType OBJECT-TYPE
SYNTAX INTEGER {singlePhase (1),delta (2),wye (3)}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The type of input"
::= { pduNamePlateEntry 16 }
-- Start pduUnit
pduUnitTableSize OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of units."
::= { pduUnit 1 }
pduUnitConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduUnitConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table of PDU configuration data"
::= { pduUnit 2 }
pduUnitConfigEntry OBJECT-TYPE
SYNTAX PduUnitConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Configuration data from the PDU being queried. The number of entries equals the value of pduUnitTableSize"
INDEX { pduUnitConfigIndex }
::= { pduUnitConfigTable 1 }
PduUnitConfigEntry ::= SEQUENCE {
pduUnitConfigIndex
Integer32,
pduUnitConfigName
DisplayString,
pduUnitConfigLocation
DisplayString,
pduUnitConfigDisplayOrientation
INTEGER,
pduUnitConfigOledDisplayControl
INTEGER,
pduUnitConfigColdstartDelay
Unsigned32,
pduUnitConfigGlobalOutletStateOnStartup
INTEGER,
pduUnitConfigLowerCriticalThreshold
Unsigned32,
pduUnitConfigLowerWarningThreshold
Unsigned32,
pduUnitConfigUpperCriticalThreshold
Unsigned32,
pduUnitConfigUpperWarningThreshold
Unsigned32,
pduUnitConfigAlarmResetThreshold
Unsigned32,
pduUnitConfigAlarmStateChangeDelay
Unsigned32,
pduUnitConfigEnabledThresholds
BITS,
pduUnitConfigPeakPowerReset
INTEGER,
pduUnitConfigEnergyReset
INTEGER,
pduUnitConfigOutletPeakPowerReset
INTEGER,
pduUnitConfigOutletEnergyReset
INTEGER,
pduUnitConfigSsh
INTEGER,
pduUnitConfigResetNetworkManagementCard
INTEGER,
}
pduUnitConfigIndex OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The index of the PDU Unit Config Entry"
::= { pduUnitConfigEntry 1 }
pduUnitConfigName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A user-defined string identifying the PDU"
::= { pduUnitConfigEntry 2 }
pduUnitConfigLocation OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A user-defined string identifying the location of the PDU"
::= { pduUnitConfigEntry 3 }
pduUnitConfigDisplayOrientation OBJECT-TYPE
SYNTAX INTEGER {
displayNormal (1),
displayReverse (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Indicates the intended physical orientation of the oLED display
displayNormal (1) indicates normal orientation.
displayReverse (2) indicates upside down orientation
NOTE:
This OID is compatible only with the two display NMC module. It does not work with the single display NMC module."
::= { pduUnitConfigEntry 4 }
pduUnitConfigOledDisplayControl OBJECT-TYPE
SYNTAX INTEGER {
displayOff (1),
displayOn (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Used to turn oled display On or Off
displayOff (1) to turn dispaly OFF.
displayOn (2) to turn dispaly ON"
::= { pduUnitConfigEntry 5 }
pduUnitConfigColdstartDelay OBJECT-TYPE
SYNTAX Unsigned32 (0..3600)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The amount of time, specified in seconds, between when power
is provided to the PDU and when the PDU start providing basic master
power to the outlets"
::= { pduUnitConfigEntry 6 }
pduUnitConfigGlobalOutletStateOnStartup OBJECT-TYPE
SYNTAX INTEGER {
off (0),
on (1),
lastKnownState (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The outlet state on device startup; applies to all outlets
unless overridden at the outlet level"
::= { pduUnitConfigEntry 7 }
pduUnitConfigLowerCriticalThreshold OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User-defined lower critical unit active power alarm threshold measured in Watts"
::= { pduUnitConfigEntry 8 }
pduUnitConfigLowerWarningThreshold OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User-defined lower non-critical (warning) unit active power alarm threshold measured in Watts"
::= { pduUnitConfigEntry 9 }
pduUnitConfigUpperCriticalThreshold OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User-defined upper critical unit active power alarm threshold measured in Watts"
::= { pduUnitConfigEntry 10 }
pduUnitConfigUpperWarningThreshold OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User-defined upper non-critical (warning) unit active power alarm threshold measured in Watts"
::= { pduUnitConfigEntry 11 }
pduUnitConfigAlarmResetThreshold OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The hysteresis used for deassertions in Watts"
::= { pduUnitConfigEntry 12 }
pduUnitConfigAlarmStateChangeDelay OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported."
::= { pduUnitConfigEntry 13 }
pduUnitConfigEnabledThresholds OBJECT-TYPE
SYNTAX BITS {
lowerCritical (0),
lowerWarning (1),
upperWarning (2),
upperCritical (3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A bit string indicating which alarm thresholds are enabled"
::= { pduUnitConfigEntry 14 }
pduUnitConfigPeakPowerReset OBJECT-TYPE
SYNTAX INTEGER {
noOperation (1),
reset (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Setting this OID to reset (2) will cause the existing peak power value
to be replaced by the current load power value. Getting this OID will
do nothing and return the noOperation(1) value. "
::= { pduUnitConfigEntry 15 }
pduUnitConfigEnergyReset OBJECT-TYPE
SYNTAX INTEGER {
noOperation (1),
reset (2),
notSupported (3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Setting this OID to reset (2) will cause the device energy meter value
to be reset to zero. Getting this OID in models that support this
feature will do nothing and return the noOperation(1) value. Models
that do not support this feature will respond to this OID with a
value of notSupported (3). Attempts to set this OID in these models will fail. "
::= { pduUnitConfigEntry 16 }
pduUnitConfigOutletPeakPowerReset OBJECT-TYPE
SYNTAX INTEGER {
noOperation (1),
reset (2),
notSupported (3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Setting this OID to reset (2) will cause the outlet peak power meter value
to be reset to zero. Getting this OID in models that support this
feature will do nothing and return the noOperation(1) value. Models
that do not support this feature will respond to this OID with a
value of notSupported (3). Attempts to set this OID in these models will fail. "
::= { pduUnitConfigEntry 17 }
pduUnitConfigOutletEnergyReset OBJECT-TYPE
SYNTAX INTEGER {
noOperation (1),
reset (2),
notSupported (3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Setting this OID to reset (2) will cause the outlet energy meter value
to be reset to zero. Getting this OID in models that support this
feature will do nothing and return the noOperation(1) value. Models
that do not support this feature will respond to this OID with a
value of notSupported (3). Attempts to set this OID in these models will fail. "
::= { pduUnitConfigEntry 18 }
pduUnitConfigSsh OBJECT-TYPE
SYNTAX INTEGER {
off (0),
on (1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Setting this OID to off(0) will disable the SSH connection. Setting this OID to on(1) will enable the SSH connection."
::= { pduUnitConfigEntry 19 }
pduUnitConfigResetNetworkManagementCard OBJECT-TYPE
SYNTAX INTEGER {
noOperation (0),
reset (1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Getting this OID will return noOperation(0). Setting this OID to reset(1) will reset NMC."
::= { pduUnitConfigEntry 20 }
pduUnitPropertiesTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduUnitPropertiesEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table of PDU properties"
::= { pduUnit 3 }
pduUnitPropertiesEntry OBJECT-TYPE
SYNTAX PduUnitPropertiesEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A unit properties entry containing objects for a particular unit."
INDEX { pduUnitPropertiesIndex }
::= { pduUnitPropertiesTable 1 }
PduUnitPropertiesEntry ::= SEQUENCE {
pduUnitPropertiesIndex
Integer32,
pduUnitPropertiesName
DisplayString,
pduUnitPropertiesOutletCount
Integer32,
pduUnitPropertiesSwitchedOutletCount
Integer32,
pduUnitPropertiesMeteredOutletCount
Integer32,
pduUnitPropertiesInputPhaseCount
Integer32,
pduUnitPropertiesCircuitBreakerCount
Integer32,
pduUnitPropertiesMaxExternalSensorCount
Integer32,
pduUnitPropertiesConnExternalSensorCount
Integer32,
pduUnitPropertiesRatedVoltage
DisplayString,
pduUnitPropertiesRatedMaxCurrent
DisplayString,
pduUnitPropertiesRatedFrequency
DisplayString,
pduUnitPropertiesRatedPower
DisplayString,
pduUnitPropertiesOrientation
INTEGER,
pduUnitPropertiesOutletLayout
INTEGER,
pduUnitPropertiesCascadeMemberType
INTEGER,
}
pduUnitPropertiesIndex OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The index of the PDU properties table entry"
::= { pduUnitPropertiesEntry 1 }
pduUnitPropertiesName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A user-defined string identifying the PDU"
::= { pduUnitPropertiesEntry 2 }
pduUnitPropertiesOutletCount OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total number of outlets on the PDU"
::= { pduUnitPropertiesEntry 3 }
pduUnitPropertiesSwitchedOutletCount OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total number of switched outlets on the PDU"
::= { pduUnitPropertiesEntry 4 }
pduUnitPropertiesMeteredOutletCount OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total number of metered outlets on the PDU"
::= { pduUnitPropertiesEntry 5 }
pduUnitPropertiesInputPhaseCount OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total number of phases on the PDU"
::= { pduUnitPropertiesEntry 6 }
pduUnitPropertiesCircuitBreakerCount OBJECT-TYPE
SYNTAX Integer32 (0..255)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total number of circuit breaker on the PDU"
::= { pduUnitPropertiesEntry 7 }
pduUnitPropertiesMaxExternalSensorCount OBJECT-TYPE
SYNTAX Integer32 (0..255)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The maximum number of external sensors that can be connected to the PDU"
::= { pduUnitPropertiesEntry 8 }
pduUnitPropertiesConnExternalSensorCount OBJECT-TYPE
SYNTAX Integer32 (0..255)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current number of external sensors connected to the PDU"
::= { pduUnitPropertiesEntry 9 }
pduUnitPropertiesRatedVoltage OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU voltage rating in Volts"
::= { pduUnitPropertiesEntry 10 }
pduUnitPropertiesRatedMaxCurrent OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU current rating in Amps"
::= { pduUnitPropertiesEntry 11 }
pduUnitPropertiesRatedFrequency OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU frequency rating in Hz"
::= { pduUnitPropertiesEntry 12 }
pduUnitPropertiesRatedPower OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU VA (VoltAmps) rating."
::= { pduUnitPropertiesEntry 13 }
pduUnitPropertiesOrientation OBJECT-TYPE
SYNTAX INTEGER {
horizontal (1),
vertical (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU orientation "
::= { pduUnitPropertiesEntry 14 }
pduUnitPropertiesOutletLayout OBJECT-TYPE
SYNTAX INTEGER {
seqPhaseToNuetral (1),
seqPhaseToPhase (2),
seqPhToNeu21PhToPh (3),
seqPhToPhGrouped (4),
seqPhToNGrouped (5),
seqPToN1516PToPGrouped (6),
seqPhToPh2xGrouped (7),
seqPhToN2xGrouped (8),
seqNotApplicable (9)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The outlet layout for the PDU. Getting this OID will return outlet layout for the device.
seqPhaseToNeutral(1) indicates outlet layout as follows:
1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,...
seqPhaseToPhase(2) indicates outlet layout as follows:
1:1-2,2:2-3,3:3-1,4:1-2,5:2-3,...
seqPhToNeu21PhToPh(3) indicates outlet layout as follows:
1:1-N,2:2-N...21:3-N,22:1-2,23:2-3,24:3-1,...
seqPhToPhGrouped(4) indicates outlet layout as follows:
This unit has 3 outlet groups. Group 1:1-2, Group 2:2-3, Group 3:3-1.
seqPhToNGrouped(5) indicates outlet layout as follows:
This unit has 3 outlet groups. Group 1:1-N, Group 2:2-N, Group 3:3-N.
seqPToN1516PToPGrouped(6) indicates outlet layout as follows:
This unit has 4 outlet groups. Group 1 (Outlets 1-14):1-2,
Group 2 (Outlets 15-16):1-N, Group 3:2-3, Group 4:3-1.
seqPhToPh2xGrouped(7) indicates outlet layout as follows:
This unit has 6 outlet groups. Group 1:1-2, Group 2:1-2, Group 3:2-3,
Group 4:2-3, Group 5:3-1, Group 6:3-1.
seqPhToN2xGrouped(8) indicates outlet layout as follows:
This unit has 6 outlet groups. Group 1:1-N, Group 2:1-N, Group 3:2-N,
Group 4:2-N, Group 5:3-N, Group 6:3-N.
seqNotApplicable(9):"
::= { pduUnitPropertiesEntry 15 }
pduUnitPropertiesCascadeMemberType OBJECT-TYPE
SYNTAX INTEGER {
standalone (1),
parent (2),
child (3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The cascading member type"
::= { pduUnitPropertiesEntry 16 }
pduUnitStatusTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduUnitStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table of PDU status information"
::= { pduUnit 4 }
pduUnitStatusEntry OBJECT-TYPE
SYNTAX PduUnitStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Status information from the PDU being queried"
INDEX { pduUnitStatusIndex }
::= { pduUnitStatusTable 1 }
PduUnitStatusEntry ::= SEQUENCE {
pduUnitStatusIndex
Integer32,
pduUnitStatusName
DisplayString,
pduUnitStatusLoadState
INTEGER,
pduUnitStatusActivePower
Integer32,
pduUnitStatusApparentPower
Integer32,
pduUnitStatusPeakPower
Integer32,
pduUnitStatusPeakPowerTimestamp
DisplayString,
pduUnitStatusPeakPowerStartTime
DisplayString,
pduUnitStatusEnergy
Integer32,
pduUnitStatusResettableEnergy
Integer32,
pduUnitStatusEnergyStartTime
DisplayString,
pduUnitStatusOutletsEnergyStartTime
DisplayString
}
pduUnitStatusIndex OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The index of the PDU status table entry"
::= { pduUnitStatusEntry 1 }
pduUnitStatusName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A user-defined string identifying the PDU"
::= { pduUnitStatusEntry 2 }
pduUnitStatusLoadState OBJECT-TYPE
SYNTAX INTEGER {
upperCritical (1),
upperWarning (2),
lowerWarning (3),
lowerCritical (4),
normal (5)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Returns the present load status of the PDU based on Active Power."
::= { pduUnitStatusEntry 3 }
pduUnitStatusActivePower OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Returns power consumption, in Watts(W),
of the PDU being queried."
::= { pduUnitStatusEntry 4 }
pduUnitStatusApparentPower OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Returns power consumption, in Volt-Amps(VA)
of the PDU load being queried."
::= { pduUnitStatusEntry 5 }
pduUnitStatusPeakPower OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Returns peak power consumption, in Watts(W),
of the PDU being queried."
::= { pduUnitStatusEntry 6 }
pduUnitStatusPeakPowerTimestamp OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates the date and time that peak power consumption occurred"
::= { pduUnitStatusEntry 7 }
pduUnitStatusPeakPowerStartTime OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates the date and time of the last device peak power reset"
::= { pduUnitStatusEntry 8 }
pduUnitStatusEnergy OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Returns total energy consumed, in tenths of Kilowatt-Hours(kWh), of the PDU over its lifetime."
::= { pduUnitStatusEntry 9 }
pduUnitStatusResettableEnergy OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A user resettable energy meter measuring PDU energy consumption
in tenths of kilowatt-hours(kWh)."
::= { pduUnitStatusEntry 10 }
pduUnitStatusEnergyStartTime OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates the date and time of the last device energy meter reset"
::= { pduUnitStatusEntry 11 }
pduUnitStatusOutletsEnergyStartTime OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates the date and time of the last outlets energy meter reset"
::= { pduUnitStatusEntry 12 }
-- Power share table
pduUnitPsTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduUnitPsEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Aggregate Object with number of entries equal to number of PDUs and Power share "
::= { pduUnit 5}
pduUnitPsEntry OBJECT-TYPE
SYNTAX PduUnitPsEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The Power share entry containing the avaliable, input, output etc."
INDEX { pduUnitPsIndex }
::= { pduUnitPsTable 1 }
PduUnitPsEntry ::= SEQUENCE {
pduUnitPsIndex
INTEGER,
pduUnitPsSupportUpstreamStatus
INTEGER,
pduUnitPsSupportDownstreamStatus
INTEGER,
pduUnitPsOptMode
INTEGER
}
pduUnitPsIndex OBJECT-TYPE
SYNTAX INTEGER (1..4)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The index of the PDU Power share table entry"
::= { pduUnitPsEntry 1 }
pduUnitPsSupportUpstreamStatus OBJECT-TYPE
SYNTAX INTEGER
{
notAvailable(0),
available(1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Power share support status on upstream PDU "
::= { pduUnitPsEntry 2}
pduUnitPsSupportDownstreamStatus OBJECT-TYPE
SYNTAX INTEGER
{
notAvailable(0),
available(1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Power share support status on downstream PDU "
::= { pduUnitPsEntry 3 }
pduUnitPsOptMode OBJECT-TYPE
SYNTAX INTEGER
{
backupPower(0),
mainPower(1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Operating power status. "
::= { pduUnitPsEntry 4 }
-- Start pduInputPhase
pduInputPhaseTableSize OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of PDU Input Phases "
::= { pduInputPhase 1 }
pduInputPhaseConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduInputPhaseConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table of PDU Input Phase configuration data"
::= { pduInputPhase 2 }
pduInputPhaseConfigEntry OBJECT-TYPE
SYNTAX PduInputPhaseConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An input phase entry containing objects for a particular input phase."
INDEX { pduUnitConfigIndex, pduInputPhaseConfigIndex }
::= { pduInputPhaseConfigTable 1 }
PduInputPhaseConfigEntry ::= SEQUENCE {
pduInputPhaseConfigIndex
Integer32,
pduInputPhaseConfigCount
Integer32,
pduInputPhaseConfigOverloadRestriction
INTEGER,
pduInputPhaseConfigCurrentLowerCriticalThreshold
Unsigned32,
pduInputPhaseConfigCurrentLowerWarningThreshold
Unsigned32,
pduInputPhaseConfigCurrentUpperCriticalThreshold
Unsigned32,
pduInputPhaseConfigCurrentUpperWarningThreshold
Unsigned32,
pduInputPhaseConfigVoltageLowerCriticalThreshold
Unsigned32,
pduInputPhaseConfigVoltageLowerWarningThreshold
Unsigned32,
pduInputPhaseConfigVoltageUpperCriticalThreshold
Unsigned32,
pduInputPhaseConfigVoltageUpperWarningThreshold
Unsigned32,
pduInputPhaseConfigCurrentAlarmResetThreshold
Unsigned32,
pduInputPhaseConfigCurrentAlarmStateChangeDelay
Integer32,
pduInputPhaseConfigCurrentEnabledThresholds
BITS,
pduInputPhaseConfigVoltageAlarmResetThreshold
Unsigned32,
pduInputPhaseConfigVoltageAlarmStateChangeDelay
Integer32,
pduInputPhaseConfigVoltageEnabledThresholds
BITS
}
pduInputPhaseConfigIndex OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The index of the PDU Input Phase configuration table entry"
::= { pduInputPhaseConfigEntry 1 }
pduInputPhaseConfigCount OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total number of Input Phases"
::= { pduInputPhaseConfigEntry 2 }
pduInputPhaseConfigOverloadRestriction OBJECT-TYPE
SYNTAX INTEGER {
alwaysAllowTurnOn (1),
restrictOnUpperWarning (2),
restrictOnUpperCritical (3),
notSupported (4)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This OID controls the behavior of a Switched PDU Input Phase when an
overload condition is possible and additional outlets are requested
to be turned on. Setting this OID to alwaysAllowTurnON (1) will always
allow the outlets on the corresponding Input Phase to turn on. Setting
this OID to restrictOnUpperWarning (2) will not allow outlets on the
corresponding Input Phase to turn on if the
pduInputPhaseConfigUpperWarningThreshold OID is exceeded. Setting
this OID to restrictOnUpperCritical (3) will not allow outlets on
the corresponding Input Phase to turn on if the
pduInputPhaseConfigUpperCriticalThreshold OID is exceeded. Models
that do not support this feature will respond to this OID with a
value of notSupported (4). Attempts to set this OID in these
models will fail. "
::= { pduInputPhaseConfigEntry 3 }
pduInputPhaseConfigCurrentLowerCriticalThreshold OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User-defined lower critical input phase current alarm threshold in hundredths of Amps(A)."
::= { pduInputPhaseConfigEntry 4 }
pduInputPhaseConfigCurrentLowerWarningThreshold OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User-defined lower non-critical (warning) input phase current alarm threshold in hundredths of Amps(A)."
::= { pduInputPhaseConfigEntry 5 }
pduInputPhaseConfigCurrentUpperCriticalThreshold OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User-defined upper critical input phase current alarm threshold in hundredths of Amps(A)."
::= { pduInputPhaseConfigEntry 6 }
pduInputPhaseConfigCurrentUpperWarningThreshold OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User-defined upper non-critical (warning) input phase current alarm threshold in hundredths of Amps(A)."
::= { pduInputPhaseConfigEntry 7 }
pduInputPhaseConfigVoltageLowerCriticalThreshold OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User-defined lower critical input phase voltage alarm threshold in Volts(V)."
::= { pduInputPhaseConfigEntry 8 }
pduInputPhaseConfigVoltageLowerWarningThreshold OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User-defined lower non-critical (warning) input phase voltage alarm threshold in Volts(V)."
::= { pduInputPhaseConfigEntry 9 }
pduInputPhaseConfigVoltageUpperCriticalThreshold OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User-defined upper critical input phase voltage alarm threshold in Volts(V)."
::= { pduInputPhaseConfigEntry 10 }
pduInputPhaseConfigVoltageUpperWarningThreshold OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User-defined upper non-critical (warning) input phase voltage alarm threshold in Volts(V)."
::= { pduInputPhaseConfigEntry 11 }
pduInputPhaseConfigCurrentAlarmResetThreshold OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The hysteresis used for current alarm deassertions in hundredths of Amps(A)."
::= { pduInputPhaseConfigEntry 12 }
pduInputPhaseConfigCurrentAlarmStateChangeDelay OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The delay measured in samples before a current state is asserted. If the
value is zero, then the state is asserted as soon as it is
detected; if it is non-zero, say n, then the assertion condition
must exist for n+1 consecutive samples before the corresponding
assertion event is reported. "
::= { pduInputPhaseConfigEntry 13 }
pduInputPhaseConfigCurrentEnabledThresholds OBJECT-TYPE
SYNTAX BITS {
lowerCritical (0),
lowerWarning (1),
upperWarning (2),
upperCritical (3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A bit string indicating which current alarm thresholds are enabled."
::= { pduInputPhaseConfigEntry 14 }
pduInputPhaseConfigVoltageAlarmResetThreshold OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The hysteresis used for voltage alarm deassertions in Volts(V)."
::= { pduInputPhaseConfigEntry 15 }
pduInputPhaseConfigVoltageAlarmStateChangeDelay OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The delay measured in samples before a voltage state is asserted. If the
value is zero, then the state is asserted as soon as it is
detected; if it is non-zero, say n, then the assertion condition
must exist for n+1 consecutive samples before the corresponding
assertion event is reported. "
::= { pduInputPhaseConfigEntry 16 }
pduInputPhaseConfigVoltageEnabledThresholds OBJECT-TYPE
SYNTAX BITS {
lowerCritical (0),
lowerWarning (1),
upperWarning (2),
upperCritical (3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A bit string indicating which voltage alarm thresholds are enabled."
::= { pduInputPhaseConfigEntry 17 }
pduInputPhasePropertiesTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduInputPhasePropertiesEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table of PDU Input Phase properties"
::= { pduInputPhase 3 }
pduInputPhasePropertiesEntry OBJECT-TYPE
SYNTAX PduInputPhasePropertiesEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An input phase properties entry containing objects for a particular input phase."
INDEX { pduUnitPropertiesIndex, pduInputPhasePropertiesIndex }
::= { pduInputPhasePropertiesTable 1 }
PduInputPhasePropertiesEntry ::= SEQUENCE {
pduInputPhasePropertiesIndex
Integer32,
pduInputPhasePropertiesCount
Integer32
}
pduInputPhasePropertiesIndex OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The index of the PDU Input Phase status entry"
::= { pduInputPhasePropertiesEntry 1 }
pduInputPhasePropertiesCount OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The numeric Input Phase ID"
::= { pduInputPhasePropertiesEntry 2 }
pduInputPhaseStatusTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduInputPhaseStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table of PDU Input Phase status data"
::= { pduInputPhase 4 }
pduInputPhaseStatusEntry OBJECT-TYPE
SYNTAX PduInputPhaseStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An input phase status entry containing objects for a particular input phase."
INDEX { pduUnitStatusIndex, pduInputPhaseStatusIndex }
::= { pduInputPhaseStatusTable 1 }
PduInputPhaseStatusEntry ::= SEQUENCE {
pduInputPhaseStatusIndex
Integer32,
pduInputPhaseStatusCount
Integer32,
pduInputPhaseStatusCurrentState
INTEGER,
pduInputPhaseStatusVoltageState
INTEGER,
pduInputPhaseStatusCurrent
Integer32,
pduInputPhaseStatusVoltage
Integer32,
pduInputPhaseStatusActivePower
Integer32,
pduInputPhaseStatusApparentPower
Integer32,
pduInputPhaseStatusPowerFactor
Integer32
}
pduInputPhaseStatusIndex OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The index of the PDU Input Phase status entry"
::= { pduInputPhaseStatusEntry 1 }
pduInputPhaseStatusCount OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The numeric Input Phase ID"
::= { pduInputPhaseStatusEntry 2 }
pduInputPhaseStatusCurrentState OBJECT-TYPE
SYNTAX INTEGER {
upperCritical (1),
upperWarning (2),
lowerWarning (3),
lowerCritical (4),
normal (5)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates the present current status of the PDU Phase in case of Y connection or PDU Line in case of Delta conneciton."
::= { pduInputPhaseStatusEntry 3 }
pduInputPhaseStatusVoltageState OBJECT-TYPE
SYNTAX INTEGER {
upperCritical (1),
upperWarning (2),
lowerWarning (3),
lowerCritical (4),
normal (5)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates the present voltage status of the PDU Input Phase being queried"
::= { pduInputPhaseStatusEntry 4 }
pduInputPhaseStatusCurrent OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Returns the current draw, in hundredths of Amps(A)"
::= { pduInputPhaseStatusEntry 5 }
pduInputPhaseStatusVoltage OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Returns the voltage, in Volts(V)"
::= { pduInputPhaseStatusEntry 6 }
pduInputPhaseStatusActivePower OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Returns power consumption, in Watts(W)"
::= { pduInputPhaseStatusEntry 7 }
pduInputPhaseStatusApparentPower OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Returns power consumption, in Volt-Amps(VA)"
::= { pduInputPhaseStatusEntry 8 }
pduInputPhaseStatusPowerFactor OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Returns the ratio of active to apparent power of the PDU."
::= { pduInputPhaseStatusEntry 9 }
-- Start pduCircuitBreaker
pduCircuitBreakerTableSize OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of PDU Circuit Breakers"
::= { pduCircuitBreaker 1 }
pduCircuitBreakerConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduCircuitBreakerConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table of PDU Circuit Breaker configuration data"
::= { pduCircuitBreaker 2 }
pduCircuitBreakerConfigEntry OBJECT-TYPE
SYNTAX PduCircuitBreakerConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A circuit breaker configuration entry containing objects for a particular circuit breaker."
INDEX { pduUnitConfigIndex, pduCircuitBreakerConfigIndex }
::= { pduCircuitBreakerConfigTable 1 }
PduCircuitBreakerConfigEntry ::= SEQUENCE {
pduCircuitBreakerConfigIndex
Integer32,
pduCircuitBreakerConfigCount
Integer32,
pduCircuitBreakerName
DisplayString,
pduCircuitBreakerConfigOverloadRestriction
INTEGER,
pduCircuitBreakerConfigLowerCriticalThreshold
Unsigned32,
pduCircuitBreakerConfigLowerWarningThreshold
Unsigned32,
pduCircuitBreakerConfigUpperCriticalThreshold
Unsigned32,
pduCircuitBreakerConfigUpperWarningThreshold
Unsigned32,
pduCircuitBreakerConfigAlarmResetThreshold
Unsigned32,
pduCircuitBreakerConfigAlarmStateChangeDelay
Unsigned32,
pduCircuitBreakerConfigEnabledThresholds
BITS
}
pduCircuitBreakerConfigIndex OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The index of the PDU Circuit Breaker configuration table entry"
::= { pduCircuitBreakerConfigEntry 1 }
pduCircuitBreakerConfigCount OBJECT-TYPE
SYNTAX Integer32 (0..255)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of circuit breakers on the PDU"
::= { pduCircuitBreakerConfigEntry 2 }
pduCircuitBreakerName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The label of the circuit breaker"
::= { pduCircuitBreakerConfigEntry 3 }
pduCircuitBreakerConfigOverloadRestriction OBJECT-TYPE
SYNTAX INTEGER {
alwaysAllowTurnOn (1),
restrictOnUpperWarning (2),
restrictOnUpperCritical (3),
notSupported (4)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This OID controls the behavior of a Switched PDU Circuit
Breaker when an overload condition is possible and additional
outlets are requested to be turned on. Setting this OID to
alwaysAllowTurnON (1) will always allow the outlets on the
corresponding Circuit Breaker to turn on. Setting this OID
to restrictOnUpperWarning (2) will not allow outlets on the
corresponding Circuit Breaker to turn on if the
pduCircuitBreakerConfigUpperWarningThreshold OID is exceeded.
Setting this OID to restrictOnUpperCritical (3) will not
allow outlets on the corresponding Circuit Breaker to turn
on if the pduCircuitBreakerConfigUpperCriticalThreshold OID
is exceeded. Models that do not support this feature will
respond to this OID with a value of notSupported (4).
Attempts to set this OID in these models will fail. "
::= { pduCircuitBreakerConfigEntry 4 }
pduCircuitBreakerConfigLowerCriticalThreshold OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User-defined lower critical circuit breaker current alarm threshold in hundredths of Amps(A)."
::= { pduCircuitBreakerConfigEntry 5 }
pduCircuitBreakerConfigLowerWarningThreshold OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User-defined lower non-critical (warning) circuit breaker current alarm threshold in hundredths of Amps(A)."
::= { pduCircuitBreakerConfigEntry 6 }
pduCircuitBreakerConfigUpperCriticalThreshold OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User-defined upper critical circuit breaker current alarm threshold in hundredths of Amps(A)."
::= { pduCircuitBreakerConfigEntry 7 }
pduCircuitBreakerConfigUpperWarningThreshold OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User-defined upper non-critical (warning) circuit breaker current alarm threshold in hundredths of Amps(A)."
::= { pduCircuitBreakerConfigEntry 8 }
pduCircuitBreakerConfigAlarmResetThreshold OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The hysteresis used for deassertions in hundredths of Amps(A)."
::= { pduCircuitBreakerConfigEntry 9 }
pduCircuitBreakerConfigAlarmStateChangeDelay OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The delay measured in samples before a state is asserted.
If the value is zero, then the state is asserted as soon
as it is detected; if it is non-zero, say n, then the
assertion condition must exist for n+1 consecutive samples
before the corresponding assertion event is reported."
::= { pduCircuitBreakerConfigEntry 10 }
pduCircuitBreakerConfigEnabledThresholds OBJECT-TYPE
SYNTAX BITS {
lowerCritical (0),
lowerWarning (1),
upperWarning (2),
upperCritical (3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A bit string indicating which alarm thresholds are enabled."
::= { pduCircuitBreakerConfigEntry 11 }
pduCircuitBreakerPropertiesTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduCircuitBreakerPropertiesEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table of PDU circuit breaker properties"
::= { pduCircuitBreaker 3 }
pduCircuitBreakerPropertiesEntry OBJECT-TYPE
SYNTAX PduCircuitBreakerPropertiesEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A circuit breaker properties entry containing objects for a particular circuit breaker."
INDEX { pduUnitPropertiesIndex, pduCircuitBreakerPropertiesIndex }
::= { pduCircuitBreakerPropertiesTable 1 }
PduCircuitBreakerPropertiesEntry ::= SEQUENCE {
pduCircuitBreakerPropertiesIndex
Integer32,
pduCircuitBreakerPropertiesCount
Integer32,
pduCircuitBreakerPropertiesInputLayout
INTEGER,
pduCircuitBreakerPropertiesCurrentRating
Integer32
}
pduCircuitBreakerPropertiesIndex OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The index of the PDU Circuit Breaker properties table entry"
::= { pduCircuitBreakerPropertiesEntry 1 }
pduCircuitBreakerPropertiesCount OBJECT-TYPE
SYNTAX Integer32 (0..255)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of Circuit Breakers"
::= { pduCircuitBreakerPropertiesEntry 2 }
pduCircuitBreakerPropertiesInputLayout OBJECT-TYPE
SYNTAX INTEGER {
seqPhase1ToNeutral (1),
seqPhase2ToNeutral (2),
seqPhase3ToNeutral (3),
seqPhase1ToPhase2 (4),
seqPhase2ToPhase3 (5),
seqPhase3ToPhase1 (6)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This OID describes the outlet phase connections on
the referenced bank as follows:
seqPhase1ToNeutral(1) indicates that outlets attached
to circuit breaker are connected from Phase 1 to Neutral.
seqPhase2ToNeutral(2) indicates that outlets attached
to circuit breaker are connected from Phase 2 to Neutral.
seqPhase3ToNeutral(3) indicates that outlets attached
to circuit breaker are connected from Phase 3 to Neutral.
seqPhase1ToPhase2(4) indicates that outlets attached
to circuit breaker are connected from Phase 1 to Phase2.
seqPhase2ToPhase3(5) indicates that outlets attached
to circuit breaker are connected from Phase 2 to Phase3.
seqPhase3ToPhase1(6) indicates that outlets attached
to circuit breaker are connected from Phase 3 to Phase1. "
::= { pduCircuitBreakerPropertiesEntry 3 }
pduCircuitBreakerPropertiesCurrentRating OBJECT-TYPE
SYNTAX Integer32 (0..255)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of Circuit Breakers"
::= { pduCircuitBreakerPropertiesEntry 4 }
pduCircuitBreakerStatusTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduCircuitBreakerStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table of PDU circuit breaker status data"
::= { pduCircuitBreaker 4 }
pduCircuitBreakerStatusEntry OBJECT-TYPE
SYNTAX PduCircuitBreakerStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A circuit breaker status entry containing objects for a particular circuit breaker."
INDEX { pduUnitStatusIndex, pduCircuitBreakerStatusIndex }
::= { pduCircuitBreakerStatusTable 1 }
PduCircuitBreakerStatusEntry ::= SEQUENCE {
pduCircuitBreakerStatusIndex
Integer32,
pduCircuitBreakerStatusCount
Integer32,
pduCircuitBreakerLabel
DisplayString,
pduCircuitBreakerStatusLoadState
INTEGER,
pduCircuitBreakerStatusCurrent
Integer32
}
pduCircuitBreakerStatusIndex OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The index of the PDU Circuit Breaker status table entry"
::= { pduCircuitBreakerStatusEntry 1 }
pduCircuitBreakerStatusCount OBJECT-TYPE
SYNTAX Integer32 (0..255)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of Circuit Breakers"
::= { pduCircuitBreakerStatusEntry 2 }
pduCircuitBreakerLabel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The label on the PDU identifying the circuit breaker"
::= { pduCircuitBreakerStatusEntry 3 }
pduCircuitBreakerStatusLoadState OBJECT-TYPE
SYNTAX INTEGER {
upperCritical (1),
upperWarning (2),
lowerWarning (3),
lowerCritical (4),
normal (5),
off (6)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates the present load status of the PDU Circuit
Breaker being queried"
::= { pduCircuitBreakerStatusEntry 4 }
pduCircuitBreakerStatusCurrent OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Returns the current draw, in hundredths of Amps(A), of the load on
the PDU Circuit Breaker being queried."
::= { pduCircuitBreakerStatusEntry 5 }
-- Start pduOutlet
pduOutletSwitchedTableSize OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of PDU Outlets"
::= { pduOutlet 1 }
pduOutletSwitchedConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduOutletSwitchedConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table of PDU Switched Outlet configuration data"
::= { pduOutlet 2 }
pduOutletSwitchedConfigEntry OBJECT-TYPE
SYNTAX PduOutletSwitchedConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An outlet configuration entry containing objects for a particular outlet."
INDEX { pduUnitConfigIndex, pduOutletSwitchedConfigIndex }
::= { pduOutletSwitchedConfigTable 1 }
PduOutletSwitchedConfigEntry ::= SEQUENCE {
pduOutletSwitchedConfigIndex
Integer32,
pduOutletSwitchedName
DisplayString,
pduOutletSwitchedStateOnStartup
INTEGER,
pduOutletSwitchedConfigPowerOnTime
Integer32,
pduOutletSwitchedConfigPowerOffTime
Integer32,
pduOutletSwitchedConfigRebootDuration
Integer32
}
pduOutletSwitchedConfigIndex OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The index of the PDU Switched Outlet configuration table entry"
::= { pduOutletSwitchedConfigEntry 1 }
pduOutletSwitchedName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The user-defined name for the Switched Outlet"
::= { pduOutletSwitchedConfigEntry 2 }
pduOutletSwitchedStateOnStartup OBJECT-TYPE
SYNTAX INTEGER {
off (0),
on (1),
lastKnownState (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The outlet state on device startup; overrides
the global value pduUnitConfigGlobalOutletStateOnStartup."
::= { pduOutletSwitchedConfigEntry 3 }
pduOutletSwitchedConfigPowerOnTime OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The amount of delay, in seconds, between when power is
provided to outlets the outlet and when this outlet
starts providing power"
::= { pduOutletSwitchedConfigEntry 4 }
pduOutletSwitchedConfigPowerOffTime OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The amount of time, in seconds, this outlet will delay
powering off"
::= { pduOutletSwitchedConfigEntry 5 }
pduOutletSwitchedConfigRebootDuration OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The amount of time, in seconds, this outlet will remain
in powered off state before returning to power on state
during a reboot action."
::= { pduOutletSwitchedConfigEntry 6 }
pduOutletSwitchedPropertiesTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduOutletSwitchedPropertiesEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table of PDU Switched Outlet properties"
::= { pduOutlet 3 }
pduOutletSwitchedPropertiesEntry OBJECT-TYPE
SYNTAX PduOutletSwitchedPropertiesEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An outlet properties entry containing objects for a particular outlet."
INDEX { pduUnitPropertiesIndex, pduOutletSwitchedPropertiesIndex }
::= { pduOutletSwitchedPropertiesTable 1 }
PduOutletSwitchedPropertiesEntry ::= SEQUENCE {
pduOutletSwitchedPropertiesIndex
Integer32,
pduOutletSwitchedPropertiesNumber
Integer32,
pduOutletSwitchedPropertiesName
DisplayString,
pduOutletSwitchedPropertiesInputPhaseLayout
INTEGER,
pduOutletSwitchedPropertiesCircuitBreaker
Integer32,
pduOutletSwitchedPropertiesCurrentRating
Integer32
}
pduOutletSwitchedPropertiesIndex OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The index of the PDU Switched Outlet properties table entry"
::= { pduOutletSwitchedPropertiesEntry 1 }
pduOutletSwitchedPropertiesNumber OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The numeric Switched Outlet ID"
::= { pduOutletSwitchedPropertiesEntry 2 }
pduOutletSwitchedPropertiesName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The user-defined switched outlet ID string"
::= { pduOutletSwitchedPropertiesEntry 3 }
pduOutletSwitchedPropertiesInputPhaseLayout OBJECT-TYPE
SYNTAX INTEGER {
seqPhase1ToNeutral (1),
seqPhase2ToNeutral (2),
seqPhase3ToNeutral (3),
seqPhase1ToPhase2 (4),
seqPhase2ToPhase3 (5),
seqPhase3ToPhase1 (6)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This OID describes the outlet phase connections
on the referenced bank as follows:
seqPhase1ToNeutral(1) indicates that outlets
attached to Switched Outlet are connected from Phase 1 to Neutral.
seqPhase2ToNeutral(2) indicates that outlets
attached to Switched Outlet are connected from Phase 2 to Neutral.
seqPhase3ToNeutral(3) indicates that outlets
attached to Switched Outlet are connected from Phase 3 to Neutral.
seqPhase1ToPhase2(4) indicates that outlets
attached to Switched Outlet are connected from Phase 1 to Phase2.
seqPhase2ToPhase3(5) indicates that outlets
attached to Switched Outlet are connected from Phase 2 to Phase3.
seqPhase3ToPhase1(6) indicates that outlets
attached to Switched Outlet are connected from Phase 3 to Phase1. "
::= { pduOutletSwitchedPropertiesEntry 4 }
pduOutletSwitchedPropertiesCircuitBreaker OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The numeric Circuit Breaker ID"
::= { pduOutletSwitchedPropertiesEntry 5 }
pduOutletSwitchedPropertiesCurrentRating OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current rating of outlet in hundreths of ampere"
::= { pduOutletSwitchedPropertiesEntry 6 }
pduOutletSwitchedStatusTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduOutletSwitchedStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table of PDU Switched Outlet status data"
::= { pduOutlet 4 }
pduOutletSwitchedStatusEntry OBJECT-TYPE
SYNTAX PduOutletSwitchedStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Status data from the PDU Switched Outlet being queried"
INDEX { pduUnitStatusIndex, pduOutletSwitchedStatusIndex }
::= { pduOutletSwitchedStatusTable 1 }
PduOutletSwitchedStatusEntry ::= SEQUENCE {
pduOutletSwitchedStatusIndex
Integer32,
pduOutletSwitchedStatusNumber
Integer32,
pduOutletSwitchedStatusName
DisplayString,
pduOutletSwitchedStatusState
INTEGER
}
pduOutletSwitchedStatusIndex OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The index of the PDU Switched Outlet status table entry"
::= { pduOutletSwitchedStatusEntry 1 }
pduOutletSwitchedStatusNumber OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The numeric Switched Outlet ID"
::= { pduOutletSwitchedStatusEntry 2 }
pduOutletSwitchedStatusName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The user-defined switched outlet ID string"
::= { pduOutletSwitchedStatusEntry 3 }
pduOutletSwitchedStatusState OBJECT-TYPE
SYNTAX INTEGER {
off (0),
on (1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates the present switch state of the
PDU switched outlet being queried"
::= { pduOutletSwitchedStatusEntry 4 }
pduOutletSwitchedControlTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduOutletSwitchedControlEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table of PDU Switched Outlet status data"
::= { pduOutlet 5 }
pduOutletSwitchedControlEntry OBJECT-TYPE
SYNTAX PduOutletSwitchedControlEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Status data from the PDU Switched Outlet
being queried"
INDEX { pduUnitConfigIndex, pduOutletSwitchedControlIndex }
::= { pduOutletSwitchedControlTable 1 }
PduOutletSwitchedControlEntry ::= SEQUENCE {
pduOutletSwitchedControlIndex
Integer32,
pduOutletSwitchedControlNumber
Integer32,
pduOutletSwitchedControlName
DisplayString,
pduOutletSwitchedControlCommand
INTEGER
}
pduOutletSwitchedControlIndex OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The index to the PDU switched outlet
control data table entry"
::= { pduOutletSwitchedControlEntry 1 }
pduOutletSwitchedControlNumber OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The numeric Switched Outlet ID"
::= { pduOutletSwitchedControlEntry 2 }
pduOutletSwitchedControlName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The user-defined switched outlet ID string"
::= { pduOutletSwitchedControlEntry 3 }
pduOutletSwitchedControlCommand OBJECT-TYPE
SYNTAX INTEGER {
immediateOff (1),
immediateOn (2),
delayedOff (3),
delayedOn (4),
immediateReboot (5),
delayedReboot (6),
outletUnknown (7)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Getting this variable will return the outlet state.
If the outlet is on, the immediateOn (2)
value will be returned. If the outlet is off,
the immediateOff (1) value will be returned.
If the state of the outlet cannot be determined, the
outletUnknown (7) value will be returned. If the
outletUnknown condition should occur, all devices
powered by the PDU should be shut down. The PDU's
power should then be cycled to clear this condition.
Setting this variable to immediateOn (2) will immediately
turn the outlet on. Setting this variable to
immediateOff (1) will immediately turn the outlet off.
Setting this variable to immediateReboot (5)
will cause the Switched PDU to perform an immediateOff
command, wait the pduOutletSwitchedConfigRebootDuration
OID time, and then perform an immediateOn command.
Setting this variable to delayedOn (4) will turn the
outlet on after the pduOutletSwitchedConfigPowerOnTime
OID time has elapsed. Setting this variable to
delayedOff (3) will turn the outlet off after the
pduOutletSwitchedConfigPowerOffTime OID time has elapsed.
Setting this variable to delayedReboot (6) will cause
the Switched PDU to perform a delayedOff command, wait
the pduOutletSwitchedConfigRebootDuration OID time, and
then perform a delayedOn command."
::= { pduOutletSwitchedControlEntry 4 }
pduOutletMeteredTableSize OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of PDU Outlets"
::= { pduOutlet 6 }
pduOutletMeteredConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduOutletMeteredConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table of PDU Metered Outlet configuration data"
::= { pduOutlet 7 }
pduOutletMeteredConfigEntry OBJECT-TYPE
SYNTAX PduOutletMeteredConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An outlet configuration entry containing objects for a particular outlet."
INDEX { pduUnitConfigIndex, pduOutletMeteredConfigIndex }
::= { pduOutletMeteredConfigTable 1 }
PduOutletMeteredConfigEntry ::= SEQUENCE {
pduOutletMeteredConfigIndex
Integer32,
pduOutletMeteredName
DisplayString,
pduOutletMeteredConfigLowerCriticalThreshold
Unsigned32,
pduOutletMeteredConfigLowerWarningThreshold
Unsigned32,
pduOutletMeteredConfigUpperCriticalThreshold
Unsigned32,
pduOutletMeteredConfigUpperWarningThreshold
Unsigned32,
pduOutletMeteredConfigAlarmResetThreshold
Unsigned32,
pduOutletMeteredConfigAlarmStateChangeDelay
Unsigned32,
pduOutletMeteredConfigEnabledThresholds
BITS
}
pduOutletMeteredConfigIndex OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The index of the PDU Metered Outlet
configuration table entry"
::= { pduOutletMeteredConfigEntry 1 }
pduOutletMeteredName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The user-defined name for the Metered Outlet"
::= { pduOutletMeteredConfigEntry 2 }
pduOutletMeteredConfigLowerCriticalThreshold OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User-defined lower critical outlet active power alarm threshold in Watts(W)."
::= { pduOutletMeteredConfigEntry 3 }
pduOutletMeteredConfigLowerWarningThreshold OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User-defined lower non-critical (warning) outlet active power alarm threshold in Watts(W)."
::= { pduOutletMeteredConfigEntry 4 }
pduOutletMeteredConfigUpperCriticalThreshold OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User-defined upper critical outlet active power alarm threshold in Watts(W)."
::= { pduOutletMeteredConfigEntry 5 }
pduOutletMeteredConfigUpperWarningThreshold OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User-defined upper non-critical (warning) outlet active power alarm threshold in Watts(W)."
::= { pduOutletMeteredConfigEntry 6 }
pduOutletMeteredConfigAlarmResetThreshold OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The hysteresis used for deassertions in Watts(W)."
::= { pduOutletMeteredConfigEntry 7 }
pduOutletMeteredConfigAlarmStateChangeDelay OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The delay measured in samples before a state
is asserted. If the value is zero, then the state
is asserted as soon as it is detected; if it is
non-zero, say n, then the assertion condition must
exist for n+1 consecutive samples before the
corresponding assertion event is reported."
::= { pduOutletMeteredConfigEntry 8 }
pduOutletMeteredConfigEnabledThresholds OBJECT-TYPE
SYNTAX BITS {
lowerCritical (0),
lowerWarning (1),
upperWarning (2),
upperCritical (3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A bit string indicating which alarm
thresholds are enabled."
::= { pduOutletMeteredConfigEntry 9 }
pduOutletMeteredPropertiesTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduOutletMeteredPropertiesEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table of PDU Metered Outlet properties"
::= { pduOutlet 8 }
pduOutletMeteredPropertiesEntry OBJECT-TYPE
SYNTAX PduOutletMeteredPropertiesEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Configuration data from the PDU Metered
Outlet being queried"
INDEX { pduUnitPropertiesIndex, pduOutletMeteredPropertiesIndex }
::= { pduOutletMeteredPropertiesTable 1 }
PduOutletMeteredPropertiesEntry ::= SEQUENCE {
pduOutletMeteredPropertiesIndex
Integer32,
pduOutletMeteredPropertiesNumber
Integer32,
pduOutletMeteredPropertiesName
DisplayString,
pduOutletMeteredPropertiesInputPhaseLayout
INTEGER,
pduOutletMeteredPropertiesCircuitBreaker
Integer32,
pduOutletMeteredPropertiesPowerRating
Integer32,
pduOutletMeteredPropertiesCurrentRating
Integer32
}
pduOutletMeteredPropertiesIndex OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The index of the PDU Metered Outlet
properties table entry"
::= { pduOutletMeteredPropertiesEntry 1 }
pduOutletMeteredPropertiesNumber OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The numeric Metered Outlet ID"
::= { pduOutletMeteredPropertiesEntry 2 }
pduOutletMeteredPropertiesName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The user-defined Metered outlet ID string"
::= { pduOutletMeteredPropertiesEntry 3 }
pduOutletMeteredPropertiesInputPhaseLayout OBJECT-TYPE
SYNTAX INTEGER {
seqPhase1ToNeutral (1),
seqPhase2ToNeutral (2),
seqPhase3ToNeutral (3),
seqPhase1ToPhase2 (4),
seqPhase2ToPhase3 (5),
seqPhase3ToPhase1 (6)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This OID describes the outlet phase connections
on the referenced bank as follows:
seqPhase1ToNeutral(1) indicates that outlets attached
to Metered Outlet are connected from Phase 1 to Neutral.
seqPhase2ToNeutral(2) indicates that outlets attached
to Metered Outlet are connected from Phase 2 to Neutral.
seqPhase3ToNeutral(3) indicates that outlets attached
to Metered Outlet are connected from Phase 3 to Neutral.
seqPhase1ToPhase2(4) indicates that outlets attached
to Metered Outlet are connected from Phase 1 to Phase2.
seqPhase2ToPhase3(5) indicates that outlets attached
to Metered Outlet are connected from Phase 2 to Phase3.
seqPhase3ToPhase1(6) indicates that outlets attached
to Metered Outlet are connected from Phase 3 to Phase1. "
::= { pduOutletMeteredPropertiesEntry 4 }
pduOutletMeteredPropertiesCircuitBreaker OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The numeric Circuit Breaker ID"
::= { pduOutletMeteredPropertiesEntry 5 }
pduOutletMeteredPropertiesPowerRating OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Maximum power rating of the PDU metered outlet"
::= { pduOutletMeteredPropertiesEntry 6 }
pduOutletMeteredPropertiesCurrentRating OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Metered outlet current rating in hundreths of ampere"
::= { pduOutletMeteredPropertiesEntry 7 }
pduOutletMeteredStatusTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduOutletMeteredStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table of PDU Metered Outlet status data"
::= { pduOutlet 9 }
pduOutletMeteredStatusEntry OBJECT-TYPE
SYNTAX PduOutletMeteredStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Status data from the PDU Metered Outlet being queried"
INDEX { pduUnitStatusIndex, pduOutletMeteredStatusIndex }
::= { pduOutletMeteredStatusTable 1 }
PduOutletMeteredStatusEntry ::= SEQUENCE {
pduOutletMeteredStatusIndex
Integer32,
pduOutletMeteredStatusNumber
Integer32,
pduOutletMeteredStatusName
DisplayString,
pduOutletMeteredStatusLoadState
INTEGER,
pduOutletMeteredStatusCurrent
Integer32,
pduOutletMeteredStatusActivePower
Integer32,
pduOutletMeteredStatusPowerFactor
Integer32,
pduOutletMeteredStatusPeakPower
Integer32,
pduOutletMeteredStatusPeakPowerTimeStamp
DisplayString,
pduOutletMeteredStatusPeakPowerStartTime
DisplayString,
pduOutletMeteredStatusResettableEnergy
Integer32
}
pduOutletMeteredStatusIndex OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The index of the PDU Metered Outlet status table entry"
::= { pduOutletMeteredStatusEntry 1 }
pduOutletMeteredStatusNumber OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The numeric Metered Outlet ID"
::= { pduOutletMeteredStatusEntry 2 }
pduOutletMeteredStatusName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The user-defined Metered outlet ID string"
::= { pduOutletMeteredStatusEntry 3 }
pduOutletMeteredStatusLoadState OBJECT-TYPE
SYNTAX INTEGER {
upperCritical (1),
upperWarning (2),
lowerWarning (3),
lowerCritical (4),
normal (5)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Returns the present load status of the PDU metered outlet being queried."
::= { pduOutletMeteredStatusEntry 4 }
pduOutletMeteredStatusCurrent OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Returns the current draw, in hundredths of Amps(A), of the load on the PDU
outlet being queried."
::= { pduOutletMeteredStatusEntry 5 }
pduOutletMeteredStatusActivePower OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Returns the power draw, in Watts(W), of the load
on the PDU outlet being queried."
::= { pduOutletMeteredStatusEntry 6 }
pduOutletMeteredStatusPowerFactor OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Returns the ratio of active to apparent power
of the PDU Outlet being queried"
::= { pduOutletMeteredStatusEntry 7 }
pduOutletMeteredStatusPeakPower OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Returns peak power consumption, in Watts(W),
of the Rack PDU outlet being queried."
::= { pduOutletMeteredStatusEntry 8 }
pduOutletMeteredStatusPeakPowerTimeStamp OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates the date and time that this metered
outlet's peak power consumption occurred"
::= { pduOutletMeteredStatusEntry 9 }
pduOutletMeteredStatusPeakPowerStartTime OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates the start date and time that this metered
outlet began recording peak power observations"
::= { pduOutletMeteredStatusEntry 10 }
pduOutletMeteredStatusResettableEnergy OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A user resettable energy meter measuring outlet load energy
consumption in tenths of Kilowatt-Hours(kWh)."
::= { pduOutletMeteredStatusEntry 11 }
-- Start pduExternalSensor
pduExternalSensorTableSize OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total number of External Sensors"
::= { pduExternalSensor 1 }
pduExternalSensorNamePlateTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduExternalSensorNamePlateEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table of PDU ExternalSensorNamePlate data"
::= { pduExternalSensor 2 }
pduExternalSensorNamePlateEntry OBJECT-TYPE
SYNTAX PduExternalSensorNamePlateEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"External Sensor Name Plate data from the external
sensor being queried. The number of entries equals
the value of pduExternalSensorNamePlateTableSize."
INDEX { pduNamePlateIndex, pduExternalSensorNamePlateIndex }
::= { pduExternalSensorNamePlateTable 1 }
PduExternalSensorNamePlateEntry ::= SEQUENCE {
pduExternalSensorNamePlateIndex
Integer32,
pduExternalSensorNamePlateName
DisplayString,
pduExternalSensorNamePlateDescription
DisplayString,
pduExternalSensorNamePlateLocation
DisplayString,
pduExternalSensorNamePlateSerialNumber
DisplayString,
pduExternalSensorNamePlateType
INTEGER,
pduExternalSensorNamePlateUnits
INTEGER,
pduExternalSensorNamePlateIdentifier
Integer32
}
pduExternalSensorNamePlateIndex OBJECT-TYPE
SYNTAX Integer32 (0..255)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The index of the PDU External Sensor status table entry"
::= { pduExternalSensorNamePlateEntry 1 }
pduExternalSensorNamePlateName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A user-defined string identifying the external sensor"
::= { pduExternalSensorNamePlateEntry 2 }
pduExternalSensorNamePlateDescription OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A user-defined description of the external sensor"
::= { pduExternalSensorNamePlateEntry 3 }
pduExternalSensorNamePlateLocation OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A user-defined string identifying the location of the PDU"
::= { pduExternalSensorNamePlateEntry 4 }
pduExternalSensorNamePlateSerialNumber OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The serial number of the external sensor being queried"
::= { pduExternalSensorNamePlateEntry 5 }
pduExternalSensorNamePlateType OBJECT-TYPE
SYNTAX INTEGER {
temperature (1),
humidity (2),
doorSwitch (3),
dryContact (4),
spotFluid (5),
ropeFluid (6),
smoke (7),
beacon (8),
airVelocity (9),
modbusAdapter (17),
hidAdapter (18)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The type of external sensor."
::= { pduExternalSensorNamePlateEntry 6 }
pduExternalSensorNamePlateUnits OBJECT-TYPE
SYNTAX INTEGER {
logic (0),
degreeC (1),
degreeF (2),
percent (3),
mps (4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The base units the external sensor is measured in.
This parameter does not apply to onOff, trip, vibration,
waterDetection, smokeDetection sensors. "
::= { pduExternalSensorNamePlateEntry 7 }
pduExternalSensorNamePlateIdentifier OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Unique identifier of the external sensor."
::= { pduExternalSensorNamePlateEntry 8 }
pduExternalSensorConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduExternalSensorConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table of PDU External Sensor configuration data"
::= { pduExternalSensor 3 }
pduExternalSensorConfigEntry OBJECT-TYPE
SYNTAX PduExternalSensorConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Configuration data from the PDU External
Sensor being queried"
INDEX { pduUnitConfigIndex, pduExternalSensorConfigIndex }
::= { pduExternalSensorConfigTable 1 }
PduExternalSensorConfigEntry ::= SEQUENCE {
pduExternalSensorConfigIndex
Integer32,
pduExternalSensorConfigLowerCriticalThreshold
Unsigned32,
pduExternalSensorConfigLowerWarningThreshold
Unsigned32,
pduExternalSensorConfigUpperCriticalThreshold
Unsigned32,
pduExternalSensorConfigUpperWarningThreshold
Unsigned32,
pduExternalSensorConfigEnabledThresholds
BITS,
pduExternalSensorConfigAlarmState
INTEGER
}
pduExternalSensorConfigIndex OBJECT-TYPE
SYNTAX Integer32 (0..255)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The index of the PDU External Sensor
configuration table entry"
::= { pduExternalSensorConfigEntry 1 }
pduExternalSensorConfigLowerCriticalThreshold OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User-defined lower critical alarm threshold in pduExternalSensorNamePlateUnits."
::= { pduExternalSensorConfigEntry 2 }
pduExternalSensorConfigLowerWarningThreshold OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User-defined lower non-critical (warning) alarm threshold in pduExternalSensorNamePlateUnits."
::= { pduExternalSensorConfigEntry 3 }
pduExternalSensorConfigUpperCriticalThreshold OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User-defined upper critical alarm threshold in pduExternalSensorNamePlateUnits."
::= { pduExternalSensorConfigEntry 4 }
pduExternalSensorConfigUpperWarningThreshold OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User-defined upper non-critical (warning) alarm threshold in pduExternalSensorNamePlateUnits."
::= { pduExternalSensorConfigEntry 5 }
pduExternalSensorConfigEnabledThresholds OBJECT-TYPE
SYNTAX BITS {
lowerCritical (0),
lowerWarning (1),
upperWarning (2),
upperCritical (3),
binarySensorAlarm (4)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A bit string indicating which alarm
thresholds are enabled."
::= { pduExternalSensorConfigEntry 6 }
pduExternalSensorConfigAlarmState OBJECT-TYPE
SYNTAX INTEGER {
on (1),
off (0)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User defined alarm state of external sensor"
::= { pduExternalSensorConfigEntry 7 }
pduExternalSensorStatusTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduExternalSensorStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table of PDU External Sensor status data"
::= { pduExternalSensor 4 }
pduExternalSensorStatusEntry OBJECT-TYPE
SYNTAX PduExternalSensorStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Status data from the PDU External Sensor
being queried"
INDEX { pduUnitStatusIndex, pduExternalSensorStatusIndex }
::= { pduExternalSensorStatusTable 1 }
PduExternalSensorStatusEntry ::= SEQUENCE {
pduExternalSensorStatusIndex
Integer32,
pduExternalSensorStatusName
DisplayString,
pduExternalSensorStatusCommStatus
INTEGER,
pduExternalSensorStatusState
INTEGER,
pduExternalSensorStatusValue
Integer32,
pduExternalSensorStatusTimeStamp
DisplayString,
pduExternalSensorStatusHighPrecisionValue
Integer32
}
pduExternalSensorStatusIndex OBJECT-TYPE
SYNTAX Integer32 (0..255)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The index of the PDU External Sensor status table entry"
::= { pduExternalSensorStatusEntry 1 }
pduExternalSensorStatusName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The user-defined name for the External Sensor"
::= { pduExternalSensorStatusEntry 2 }
pduExternalSensorStatusCommStatus OBJECT-TYPE
SYNTAX INTEGER {
notInstalled (1),
commsOk (2),
commsLost (3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The communications status of the sensor"
::= { pduExternalSensorStatusEntry 3 }
pduExternalSensorStatusState OBJECT-TYPE
SYNTAX INTEGER {
notPresent (0), alarmed (1), normal (2), belowLowerCritical (3), belowLowerWarning (4), aboveUpperWarning (5), aboveUpperCritical (6)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This OID reports the current state of the sensor.
A notPresent (0) response indicates that no sensor is attached.
An alarmed (1) response indicates that the sensor is present
and its measured reading indicates alarmed.
A normal (2) response indicates that the sensor is present
and its measured reading lies within all thresholds.
A belowLowerCritical (3) response indicates that the sensor
is present and its measured reading lies below the lower critical threshold.
A belowLowerWarning (4) response indicates that the sensor
is present and its measured reading lies below the lower warning threshold.
An aboveUpperWarning (5) response indicates that the sensor
is present and its measured reading lies above the upper warning threshold.
An aboveUpperCritical (6) response indicates that the sensor
is present and its measured reading lies above the upper critical threshold."
::= { pduExternalSensorStatusEntry 4 }
pduExternalSensorStatusValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Sensor reading in pduExternalSensorConfigUnits value."
::= { pduExternalSensorStatusEntry 5 }
pduExternalSensorStatusTimeStamp OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The sensor reading timestamp."
::= { pduExternalSensorStatusEntry 6 }
pduExternalSensorStatusHighPrecisionValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Temperature sensor reading in tenths of pduExternalSensorConfigUnits value.
This OID is applied to temperature sensor only"
::= { pduExternalSensorStatusEntry 7 }
-- Smart Cabinet
pduUnitSmartCabinetTableSize OBJECT-TYPE
SYNTAX Integer32 (0..255)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total number of Smart Cabinet Configuration "
::= { pduSmartCabinet 1 }
pduUnitSmartCabinetTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduUnitSmartCabinetEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table of Smart Cabinet information"
::= { pduSmartCabinet 2 }
pduUnitSmartCabinetEntry OBJECT-TYPE
SYNTAX PduUnitSmartCabinetEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Information of Smart Cabinet"
INDEX { pduUnitSmartCabinetIndex }
::= { pduUnitSmartCabinetTable 1 }
PduUnitSmartCabinetEntry ::= SEQUENCE {
pduUnitSmartCabinetIndex
Integer32,
pduUnitSmartCabinetCardUserName
DisplayString,
pduUnitSmartCabinetCardID
Integer32,
pduUnitSmartCabinetTimestamp
DisplayString,
pduUnitSmartCabinetDoor
INTEGER
}
pduUnitSmartCabinetIndex OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The index of the PDU Smart Cabinet table entry"
::= { pduUnitSmartCabinetEntry 1 }
pduUnitSmartCabinetCardUserName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"User name of ID card"
::= { pduUnitSmartCabinetEntry 2 }
pduUnitSmartCabinetCardID OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Card ID."
::= { pduUnitSmartCabinetEntry 3 }
pduUnitSmartCabinetTimestamp OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates the date and time of information update"
::= { pduUnitSmartCabinetEntry 4 }
pduUnitSmartCabinetDoor OBJECT-TYPE
SYNTAX INTEGER {
hotAisle (1),
coldAisle (2) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Aisle of Smart Cabinet. "
::= { pduUnitSmartCabinetEntry 5 }
pduUnitSmartCabinetControl OBJECT IDENTIFIER ::= { pduSmartCabinet 3 }
pduUnitSmartCabinetControlUserName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User name of ID card"
::= { pduUnitSmartCabinetControl 1 }
pduUnitSmartCabinetControlCardID OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Card ID."
::= { pduUnitSmartCabinetControl 2 }
pduUnitSmartCabinetControlTimestamp OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Indicates the date and time of information update"
::= { pduUnitSmartCabinetControl 3 }
pduUnitSmartCabinetControlDoor OBJECT-TYPE
SYNTAX INTEGER {
hotAisle (1),
coldAisle (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Aisle of Smart Cabinet. "
::= { pduUnitSmartCabinetControl 4 }
pduUnitSmartCabinetCardIDEdit OBJECT-TYPE
SYNTAX INTEGER {
grant (0), remove (1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Smart Cabinet edit CardID "
::= { pduUnitSmartCabinetControl 5 }
pduUnitSmartCabinetColdAisleLockStatus OBJECT-TYPE
SYNTAX INTEGER {
unlock (0), lock (1), notPresent (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Smart Cabinet ColdAisle lock state "
::= { pduUnitSmartCabinetControl 6 }
pduUnitSmartCabinetHotAisleLockStatus OBJECT-TYPE
SYNTAX INTEGER {
unlock (0), lock (1), notPresent (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Smart Cabinet HotAisle lock state "
::= { pduUnitSmartCabinetControl 7 }
pduUnitSmartCabinetLockStateTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduUnitSmartCabinetLockStateEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table of Smart Cabinet aisle state control"
::= { pduSmartCabinet 4 }
pduUnitSmartCabinetLockStateEntry OBJECT-TYPE
SYNTAX PduUnitSmartCabinetLockStateEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Information of Smart Cabinet Lock State"
INDEX { pduUnitSmartCabinetLockStateIndex }
::= { pduUnitSmartCabinetLockStateTable 1 }
PduUnitSmartCabinetLockStateEntry ::= SEQUENCE {
pduUnitSmartCabinetLockStateIndex
Integer32,
pduUnitSmartCabinetColdAisleLockState
INTEGER,
pduUnitSmartCabinetHotAisleLockState
INTEGER,
pduUnitSmartCabinetColdAisleLockLabel
DisplayString,
pduUnitSmartCabinetHotAisleLockLabel
DisplayString
}
pduUnitSmartCabinetLockStateIndex OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The index of the PDU Smart Cabinet table entry"
::= { pduUnitSmartCabinetLockStateEntry 1 }
pduUnitSmartCabinetColdAisleLockState OBJECT-TYPE
SYNTAX INTEGER {
unlock (0), lock (1), notPresent (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Smart Cabinet ColdAisle lock state "
::= { pduUnitSmartCabinetLockStateEntry 2 }
pduUnitSmartCabinetHotAisleLockState OBJECT-TYPE
SYNTAX INTEGER {
unlock (0), lock (1), notPresent (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Smart Cabinet HotAisle lock state "
::= { pduUnitSmartCabinetLockStateEntry 3 }
pduUnitSmartCabinetColdAisleLockLabel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Label of cold aisle smartcabinet"
::= { pduUnitSmartCabinetLockStateEntry 4 }
pduUnitSmartCabinetHotAisleLockLabel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Label of hot aisle smartcabinet"
::= { pduUnitSmartCabinetLockStateEntry 5 }
-- Traps Information
trapsInfo OBJECT IDENTIFIER ::= { pduTraps 1 }
trapsInfoTable OBJECT-TYPE
SYNTAX SEQUENCE OF TrapsInfoEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of Trap Information entries. The number of
entries are given by the value of pduUnitTableSize."
::= { trapsInfo 1 }
trapsInfoEntry OBJECT-TYPE
SYNTAX TrapsInfoEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing objects used in traps"
INDEX { trapsInfoIndex }
::= { trapsInfoTable 1 }
TrapsInfoEntry ::= SEQUENCE {
trapsInfoIndex
Integer32,
userName
DisplayString,
userUpdated
DisplayString,
firmwareVersion
DisplayString,
roleUpdated
DisplayString,
smtpRecipients
DisplayString,
smtpServer
DisplayString
}
trapsInfoIndex OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The index of the traps table entry"
::= { trapsInfoEntry 1 }
userName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The user currently logged in."
::= { trapsInfoEntry 2 }
userUpdated OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The user added, deleted, or modified."
::= { trapsInfoEntry 3 }
firmwareVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The version of Firmware."
::= { trapsInfoEntry 4 }
roleUpdated OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The role added, deleted, or modified."
::= { trapsInfoEntry 5 }
smtpRecipients OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Comma separated list of SMTP recipients"
::= { trapsInfoEntry 6 }
smtpServer OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The IP address/host name of the SMTP server"
::= { trapsInfoEntry 7 }
pduIndex OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"A unique value for PDU. Its value ranges between 1
and the value of PDU count"
::= { trapsInfo 2 }
externalSensorIndex OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"A unique value for each sensor. Its value ranges between 1
and the value of external sensor count."
::= { trapsInfo 3 }
serverPing OBJECT-TYPE
SYNTAX INTEGER {
pingEnable (1),
pingDisable (2),
serverReachable (3),
serverNotReachable (4)
}
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Whether server ping has been enabled or disabled and
whether the server is reachable or not reachable"
::= { trapsInfo 4 }
usbDevice OBJECT-TYPE
SYNTAX INTEGER {
connected (1),
disconnected (2)
}
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Whether a USB device has been connected or disconnected"
::= { trapsInfo 5 }
errorDescription OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Description of the Error"
::= { trapsInfo 6 }
cascading OBJECT-TYPE
SYNTAX INTEGER {
connected (1),
disconnected (2)
}
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Whether a cascading member has been connected or disconnected"
::= { trapsInfo 7 }
systemCommunication OBJECT-TYPE
SYNTAX INTEGER {
ok (1),
lost (2)
}
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Whether the Network management card has lost contact with cascading member."
::= { trapsInfo 8 }
trapCode OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"A number identifying the event for the trap that was sent.
Mapped unique trap code per unique event to be used by ISEE's
decoder ring."
::= { trapsInfo 9 }
trapDescription OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"A string identifying the event for that last trap that was sent."
::= { trapsInfo 10 }
trapCritical NOTIFICATION-TYPE
OBJECTS {
trapCode,
trapDescription,
sysDescr,
pduNamePlateIPAddress}
STATUS current
DESCRIPTION
"A critical alarm has occurred."
::= {pduTraps 1}
trapWarning NOTIFICATION-TYPE
OBJECTS {
trapCode,
trapDescription,
sysDescr,
pduNamePlateIPAddress}
STATUS current
DESCRIPTION
"A warning alarm has occurred."
::= {pduTraps 2}
trapInformation NOTIFICATION-TYPE
OBJECTS {
trapCode,
trapDescription,
sysDescr,
pdug5IPv4Address }
STATUS current
DESCRIPTION
"An informational alarm has occurred."
::= {pduTraps 3}
trapCleared NOTIFICATION-TYPE
OBJECTS {
trapCode,
trapDescription,
sysDescr,
pduNamePlateIPAddress}
STATUS current
DESCRIPTION
"An alarm has cleared."
::= {pduTraps 4}
trapTest NOTIFICATION-TYPE
OBJECTS {
trapCode,
trapDescription,
sysDescr,
pduNamePlateIPAddress}
STATUS current
DESCRIPTION
"Test trap sent to a trap receiver to check proper reception of traps"
::= {pduTraps 5}
-- ======Ehandle Sensor Status==========
pduEhandleTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduEhandleEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of contact sensors. The number of entries are
given by number of pdu and pduEhandleCount."
::= { pduEhandle 1 }
pduEhandleEntry OBJECT-TYPE
SYNTAX PduEhandleEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"An entry for a contact sensor"
INDEX { pduEhandleIndex }
::= { pduEhandleTable 1 }
PduEhandleEntry ::= SEQUENCE
{
pduEhandleIndex INTEGER,
pduEhandleAisle INTEGER,
pduEhandleHandleOperation INTEGER,
pduEhandleFwVer DisplayString,
pduEhandleMechanicalLock INTEGER,
pduEhandleSerial DisplayString,
pduEhandleHwVer DisplayString,
pduEhandleAutoLockTime INTEGER,
pduEhandleDoorOpenTime INTEGER,
pduEhandleMaxDoorOpenTime INTEGER,
pduEhandleUserPinLength INTEGER,
pduEhandleUserPinMode INTEGER,
pduEhandleAisleControl INTEGER
}
pduEhandleIndex OBJECT-TYPE
SYNTAX INTEGER (1..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index of the PDU HID table entry"
::= { pduEhandleEntry 1 }
pduEhandleAisle OBJECT-TYPE
SYNTAX INTEGER
{
hot(1),
cold(2)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Aisle of HID handle. "
::= { pduEhandleEntry 2 }
pduEhandleHandleOperation OBJECT-TYPE
SYNTAX INTEGER
{
unlock(1),
lock(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"HID handle control opterations "
::= { pduEhandleEntry 3 }
pduEhandleFwVer OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The firmware revision level of the HID"
::= { pduEhandleEntry 4 }
pduEhandleMechanicalLock OBJECT-TYPE
SYNTAX INTEGER
{
unlock(1),
lock(2)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"HID Mechanical opterations "
::= { pduEhandleEntry 5 }
pduEhandleSerial OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Serial Number of the HID"
::= { pduEhandleEntry 6 }
pduEhandleHwVer OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The hardware revision level of the HID"
::= { pduEhandleEntry 7 }
pduEhandleAutoLockTime OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"HID Electronic Latch Autolock Time in seconds, Value ranges (0-999) "
::= { pduEhandleEntry 8 }
pduEhandleDoorOpenTime OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"HID Door Open Time in seconds, Value ranges (0-999)"
::= { pduEhandleEntry 9 }
pduEhandleMaxDoorOpenTime OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"HID Max Door Open Time in seconds, Value ranges (0-32400),
critical alarm will be raised if door is left open past this time"
::= { pduEhandleEntry 10 }
pduEhandleUserPinLength OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Rack Access User minimum PIN Length, value ranges(1-15)"
::= { pduEhandleEntry 11 }
pduEhandleUserPinMode OBJECT-TYPE
SYNTAX INTEGER
{
visible(1),
hidden (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Rack Access User PIN mode setting"
::= { pduEhandleEntry 12 }
pduEhandleAisleControl OBJECT-TYPE
SYNTAX INTEGER
{
combined (1),
standalone(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Rack Access Aisle Control setting,
when set to standalone each aisle will controlled seprately,
when set to combined opposite aisle can be controlled with authenticated control action on either aisle"
::= { pduEhandleEntry 13 }
-- ======EHANDLE control table==========
pduEhandleControlTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduEhandleControlEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of smartcard. The number of entries are
given by number of pdu and pduEhandleCount."
::= { pduEhandle 2 }
pduEhandleControlEntry OBJECT-TYPE
SYNTAX PduEhandleControlEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The smart card table entry containing the usrname, cardid, cardaisle etc."
INDEX { pduEhandleControlIndex }
::= { pduEhandleControlTable 1 }
PduEhandleControlEntry ::= SEQUENCE
{
pduEhandleControlIndex INTEGER,
pduEhandleControlUserName DisplayString,
pduEhandleControlCardIdStr DisplayString,
pduEhandleControlTimestamp DisplayString,
pduEhandleControlCardAisle INTEGER,
pduEhandleControlStartTime DisplayString,
pduEhandleControlExpireTime DisplayString,
pduEhandleControlTempUser INTEGER,
pduEhandleControlPin DisplayString,
}
pduEhandleControlIndex OBJECT-TYPE
SYNTAX INTEGER (1..200)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index of the PDU smartcard table entry"
::= { pduEhandleControlEntry 1 }
pduEhandleControlUserName OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-write
STATUS mandatory
DESCRIPTION
"User name of smartcard"
::= { pduEhandleControlEntry 2 }
pduEhandleControlCardIdStr OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-write
STATUS mandatory
DESCRIPTION
"smartcard ID."
::= { pduEhandleControlEntry 3 }
pduEhandleControlTimestamp OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicates the date and time of accessing"
::= { pduEhandleControlEntry 4 }
pduEhandleControlCardAisle OBJECT-TYPE
SYNTAX INTEGER
{
hot(1),
cold(2),
both (3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Aisle of authorized card"
::= { pduEhandleControlEntry 5 }
pduEhandleControlStartTime OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicates the start date and time Rack access user is given access"
::= { pduEhandleControlEntry 6 }
pduEhandleControlExpireTime OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicates the date and time when the access of user card will expire, To set expire time first set user as temporary user"
::= { pduEhandleControlEntry 7 }
pduEhandleControlTempUser OBJECT-TYPE
SYNTAX INTEGER
{
no(1),
yes(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicates if the card user has temporary access"
::= { pduEhandleControlEntry 8 }
pduEhandleControlPin OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Rack acess control entry keypad PIN"
::= { pduEhandleControlEntry 9 }
-- ++++ End of cPDU ++++
END