457 lines
10 KiB
Plaintext
457 lines
10 KiB
Plaintext
KMX-LAN DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
enterprises
|
|
FROM RFC1155-SMI
|
|
OBJECT-TYPE
|
|
FROM RFC-1212
|
|
TRAP-TYPE
|
|
FROM RFC-1215
|
|
DisplayString
|
|
FROM RFC1213-MIB;
|
|
|
|
kentix OBJECT IDENTIFIER ::= { enterprises 37954 }
|
|
|
|
multisensorLan OBJECT IDENTIFIER ::= { kentix 2 }
|
|
|
|
-- Kentix KMS-LAN MODULE-IDENTITY
|
|
-- LAST-UPDATED "20140626"
|
|
-- ORGANIZATION
|
|
-- "Kentix GmbH"
|
|
-- CONTACT-INFO
|
|
-- "info@kentix.de"
|
|
-- DESCRIPTION
|
|
-- "KMS-LAN MIB module"
|
|
--
|
|
-- REVISION "20140626REV01"
|
|
-- DESCRIPTION
|
|
-- "MIB Release version 4.1"
|
|
-- ::= { multisensorLan }
|
|
|
|
datapoints OBJECT IDENTIFIER ::= { multisensorLan 1 }
|
|
|
|
-- Temperature
|
|
|
|
temperatureEntry OBJECT IDENTIFIER ::= { datapoints 1 }
|
|
|
|
|
|
temperatureValue OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Temperature on the Kentix KMS-LAN for that datatpoint (Factor 0.1)"
|
|
::= { temperatureEntry 1 }
|
|
|
|
temperatureMin OBJECT-TYPE
|
|
SYNTAX INTEGER (0..99)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Temperature Min on the Kentix KMS-LAN for that datatpoint"
|
|
::= { temperatureEntry 2 }
|
|
|
|
temperatureMax OBJECT-TYPE
|
|
SYNTAX INTEGER (0..99)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Temperature Max on the Kentix KMS-LAN for that datatpoint"
|
|
::= { temperatureEntry 3 }
|
|
|
|
temperatureAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Alarm on the Kentix KMS-LAN for that datatpoint"
|
|
::= { temperatureEntry 4 }
|
|
|
|
temperatureAlarmtext OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Alarmmessage on the Kentix KMS-LAN for that datatpoint"
|
|
::= { temperatureEntry 5 }
|
|
|
|
temperatureAlarmArm OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Arm/Disarm TemperatureAlarm on the Kentix KMS-LAN"
|
|
::= { temperatureEntry 6 }
|
|
|
|
|
|
-- Humidity
|
|
|
|
humidityEntry OBJECT IDENTIFIER ::= { datapoints 2 }
|
|
|
|
humidityValue OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Humidity on the Kentix KMS-LAN for that datatpoint (Factor 0.1)"
|
|
::= { humidityEntry 1 }
|
|
|
|
humidityMin OBJECT-TYPE
|
|
SYNTAX INTEGER (0..99)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Humidity Min on the Kentix KMS-LAN for that datatpoint"
|
|
::= { humidityEntry 2 }
|
|
|
|
humidityMax OBJECT-TYPE
|
|
SYNTAX INTEGER (0..99)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Humidity Max on the Kentix KMS-LAN for that datatpoint"
|
|
::= { humidityEntry 3 }
|
|
|
|
humidityAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Alarm on the Kentix KMS-LAN for that datatpoint"
|
|
::= { humidityEntry 4 }
|
|
|
|
humidityAlarmtext OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Alarmmessage on the Kentix KMS-LAN for that datatpoint"
|
|
::= { humidityEntry 5 }
|
|
|
|
|
|
humidityAlarmArm OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Arm/Disarm HumidityAlarm on the Kentix KMS-LAN"
|
|
::= { humidityEntry 6 }
|
|
|
|
|
|
-- Dewpoint
|
|
|
|
dewpointEntry OBJECT IDENTIFIER ::= { datapoints 3 }
|
|
|
|
|
|
dewpointValue OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Dewpoint on the Kentix KMS-LAN for that datatpoint (Factor 0.1)"
|
|
::= { dewpointEntry 1 }
|
|
|
|
dewpointMin OBJECT-TYPE
|
|
SYNTAX INTEGER (0..99)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Dewpoint Min on the Kentix KMS-LAN for that datatpoint"
|
|
::= { dewpointEntry 2 }
|
|
|
|
dewpointAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Alarm on the Kentix KMS-LAN for that datatpoint"
|
|
::= { dewpointEntry 3 }
|
|
|
|
dewpointAlarmtext OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Alarmmessage on the Kentix KMS-LAN for that datatpoint"
|
|
::= { dewpointEntry 4 }
|
|
|
|
|
|
dewpointAlarmArm OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Arm/Disarm DewpointAlarm on the Kentix KMS-LAN"
|
|
::= { dewpointEntry 6 }
|
|
-- Carbon Monoxide
|
|
|
|
coEntry OBJECT IDENTIFIER ::= { datapoints 4 }
|
|
|
|
|
|
coValue OBJECT-TYPE
|
|
SYNTAX INTEGER (-100..100)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Carbon Monoxide on the Kentix KMS-LAN for that datatpoint"
|
|
::= { coEntry 1 }
|
|
|
|
coMax OBJECT-TYPE
|
|
SYNTAX INTEGER (0..99)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Carbon Monoxide Min on the Kentix KMS-LAN for that datatpoint"
|
|
::= { coEntry 2 }
|
|
|
|
coAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Alarm on the Kentix KMS-LAN for that datatpoint"
|
|
::= { coEntry 3 }
|
|
|
|
coAlarmtext OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Alarmmessage on the Kentix KMS-LAN for that datatpoint"
|
|
::= { coEntry 4 }
|
|
|
|
|
|
|
|
coAlarmArm OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Arm/Disarm COAlarm on the Kentix KMS-LAN"
|
|
::= { coEntry 6 }
|
|
|
|
-- Motion
|
|
|
|
motionEntry OBJECT IDENTIFIER ::= { datapoints 5 }
|
|
|
|
|
|
motionValue OBJECT-TYPE
|
|
SYNTAX INTEGER (0..100)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Motion on the Kentix KMS-LAN for that datatpoint"
|
|
::= { motionEntry 1 }
|
|
|
|
motionMax OBJECT-TYPE
|
|
SYNTAX INTEGER (0..99)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Motion Min on the Kentix KMS-LAN for that datatpoint"
|
|
::= { motionEntry 2 }
|
|
|
|
motionAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Alarm on the Kentix KMS-LAN for that datatpoint"
|
|
::= { motionEntry 3 }
|
|
|
|
motionAlarmtext OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Alarmmessage on the Kentix KMS-LAN for that datatpoint"
|
|
::= { motionEntry 4 }
|
|
|
|
|
|
motionAlarmArm OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Arm/Disarm MotionAlarm on the Kentix KMS-LAN"
|
|
::= { motionEntry 6 }
|
|
|
|
-- Digital IN 1
|
|
|
|
digitalIn1 OBJECT IDENTIFIER ::= { datapoints 6 }
|
|
|
|
|
|
digitalIn1Value OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Digital IN 1 on the Kentix KMS-LAN for that datatpoint"
|
|
::= { digitalIn1 1 }
|
|
|
|
|
|
digitalIn1Name OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Digital IN 1 on the Kentix KMS-LAN for that datatpoint"
|
|
::= { digitalIn1 2 }
|
|
|
|
|
|
|
|
-- Digital IN 2
|
|
|
|
digitalIn2 OBJECT IDENTIFIER ::= { datapoints 7 }
|
|
|
|
|
|
digitalIn2Value OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Digital IN 2 on the Kentix KMS-LAN for that datatpoint"
|
|
::= { digitalIn2 1 }
|
|
|
|
|
|
digitalIn2Name OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Digital IN 2 on the Kentix KMS-LAN for that datatpoint"
|
|
::= { digitalIn2 2 }
|
|
|
|
|
|
|
|
|
|
-- Digital OUT 2
|
|
|
|
digitalOut2 OBJECT IDENTIFIER ::= { datapoints 8 }
|
|
|
|
|
|
digitalOut2Value OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Digital OUT 2 on the Kentix KMS-LAN for that datatpoint"
|
|
::= { digitalOut2 1 }
|
|
|
|
|
|
|
|
|
|
buzzerTime OBJECT IDENTIFIER ::= { datapoints 9 }
|
|
|
|
|
|
buzzerTimeValue OBJECT-TYPE
|
|
SYNTAX INTEGER (0..999)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Buzzer on the Kentix KMS-LAN for that datatpoint"
|
|
::= { buzzerTime 1 }
|
|
|
|
-- RelayTime
|
|
|
|
relayTime OBJECT IDENTIFIER ::= { datapoints 10 }
|
|
|
|
|
|
relayTimeValue OBJECT-TYPE
|
|
SYNTAX INTEGER (0..999)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Buzzer Time on the Kentix KMS-LAN for that datatpoint"
|
|
::= { relayTime 1 }
|
|
|
|
-- Arm-Disarm Motion
|
|
|
|
rearmMotion OBJECT IDENTIFIER ::= { datapoints 11 }
|
|
|
|
rearmMotionValue OBJECT-TYPE
|
|
SYNTAX INTEGER (0..999)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Arm-Disarm Motion on the Kentix KMS-LAN for that datatpoint"
|
|
::= { rearmMotion 1 }
|
|
|
|
-- Vibration
|
|
|
|
vibrationEntry OBJECT IDENTIFIER ::= { datapoints 12 }
|
|
|
|
|
|
vibrationValue OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Vibration on the Kentix KMS-LAN for that datatpoint"
|
|
::= { vibrationEntry 1 }
|
|
|
|
vibrationMax OBJECT-TYPE
|
|
SYNTAX INTEGER (0..2)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Vibration Profile (0 = Low/1 = Medium/2 = High) on the Kentix KMS-LAN for that datatpoint"
|
|
::= { vibrationEntry 2 }
|
|
|
|
vibrationAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Alarm on the Kentix KMS-LAN for that datatpoint"
|
|
::= { vibrationEntry 3 }
|
|
|
|
vibrationAlarmtext OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Alarmmessage on the Kentix KMS-LAN for that datatpoint"
|
|
::= { vibrationEntry 4 }
|
|
|
|
|
|
vibrationAlarmArm OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Arm/Disarm VibrationAlarm on the Kentix KMS-LAN"
|
|
::= { vibrationEntry 6 }
|
|
|
|
alarmText OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Alarm Text send to the Manager"
|
|
::= { multisensorLan 2 }
|
|
|
|
|
|
wrongLogin TRAP-TYPE
|
|
ENTERPRISE kentix
|
|
DESCRIPTION
|
|
"wrong login of a user"
|
|
::= 1
|
|
|
|
login TRAP-TYPE
|
|
ENTERPRISE kentix
|
|
DESCRIPTION
|
|
"login of user"
|
|
::= 2
|
|
|
|
alarm TRAP-TYPE
|
|
ENTERPRISE kentix
|
|
VARIABLES { alarmText }
|
|
DESCRIPTION
|
|
"SNMP Trap for each multisensor alarm"
|
|
::= 3
|
|
|
|
|
|
END
|
|
|