-- MIB table for H6520
|
|
--
|
|
-- v1.0 for firmware 9-5-0-0, 2017-04-19
|
|
-----------------------------------------------------------------------
|
|
H6520-MIB DEFINITIONS ::= BEGIN
|
|
|
|
|
|
IMPORTS
|
|
enterprises
|
|
FROM RFC1155-SMI
|
|
OBJECT-TYPE
|
|
FROM RFC-1212
|
|
TRAP-TYPE
|
|
FROM RFC-1215;
|
|
|
|
DisplayString ::= OCTET STRING
|
|
|
|
|
|
comet OBJECT IDENTIFIER ::= { enterprises 22626 }
|
|
products OBJECT IDENTIFIER ::= { comet 1 }
|
|
h6520 OBJECT IDENTIFIER ::= { products 2 }
|
|
values OBJECT IDENTIFIER ::= { h6520 1 }
|
|
global OBJECT IDENTIFIER ::= { h6520 2 }
|
|
valuesInt OBJECT IDENTIFIER ::= { h6520 3 }
|
|
settings OBJECT IDENTIFIER ::= { h6520 4 }
|
|
traps OBJECT IDENTIFIER ::= { h6520 5 }
|
|
tables OBJECT IDENTIFIER ::= { h6520 6 }
|
|
|
|
|
|
-----------------------------------------------------------------------
|
|
-- Measured values - String
|
|
-----------------------------------------------------------------------
|
|
temp OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Temperature"
|
|
::= { values 1 }
|
|
|
|
hum OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Relative humidity"
|
|
::= { values 2 }
|
|
|
|
compVal OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Computed value"
|
|
::= { values 3 }
|
|
|
|
co2 OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "CO2 level"
|
|
::= { values 4 }
|
|
|
|
re1 OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Relay 1 state; open, closed"
|
|
::= { values 8 }
|
|
|
|
re2 OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Relay 2 state; open, closed"
|
|
::= { values 9 }
|
|
|
|
tempAlarm1 OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm1 on Temperature; none, active"
|
|
::= { values 10 }
|
|
|
|
humAlarm1 OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm1 on Relative humidity; none, active"
|
|
::= { values 11 }
|
|
|
|
compValAlarm1 OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm1 on Computed value; none, active"
|
|
::= { values 12 }
|
|
|
|
co2Alarm1 OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm1 on CO2 level; none, active"
|
|
::= { values 13 }
|
|
|
|
tempAlarm2 OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm2 on Temperature; none, active"
|
|
::= { values 14 }
|
|
|
|
humAlarm2 OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm2 on Relative humidity; none, active"
|
|
::= { values 15 }
|
|
|
|
compValAlarm2 OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm2 on Computed value; none, active"
|
|
::= { values 16 }
|
|
|
|
co2Alarm2 OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm2 on CO2 level; none, active"
|
|
::= { values 17 }
|
|
|
|
tempUnit OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Temperature Unit"
|
|
::= { values 21 }
|
|
|
|
humUnit OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Relative humidity Unit"
|
|
::= { values 22 }
|
|
|
|
compValUnit OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Computed value Unit"
|
|
::= { values 23 }
|
|
|
|
co2Unit OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "CO2 level Unit"
|
|
::= { values 24 }
|
|
|
|
|
|
-----------------------------------------------------------------------
|
|
-- Device informations
|
|
-----------------------------------------------------------------------
|
|
sensorName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..68))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Device name"
|
|
::= { global 1 }
|
|
|
|
serialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..16))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Serial number"
|
|
::= { global 2 }
|
|
|
|
deviceType OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65534)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Device type"
|
|
::= { global 3 }
|
|
|
|
|
|
-----------------------------------------------------------------------
|
|
-- Measured values - Integer
|
|
-----------------------------------------------------------------------
|
|
tempInt OBJECT-TYPE
|
|
SYNTAX INTEGER (-5000..20000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Temperature (value*10)"
|
|
::= { valuesInt 1 }
|
|
|
|
humInt OBJECT-TYPE
|
|
SYNTAX INTEGER (-5000..20000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Relative humidity (value*10)"
|
|
::= { valuesInt 2 }
|
|
|
|
compValInt OBJECT-TYPE
|
|
SYNTAX INTEGER (-5000..20000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Computed value (value*10)"
|
|
::= { valuesInt 3 }
|
|
|
|
co2Int OBJECT-TYPE
|
|
SYNTAX INTEGER (-5000..20000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "CO2 level (value*X)"
|
|
::= { valuesInt 4 }
|
|
|
|
re1Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Relay 1 state"
|
|
::= { valuesInt 8 }
|
|
|
|
re2Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Relay 2 state"
|
|
::= { valuesInt 9 }
|
|
|
|
tempAlarm1Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm1 on Temperature"
|
|
::= { valuesInt 10 }
|
|
|
|
humAlarm1Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm1 on Relative humidity"
|
|
::= { valuesInt 11 }
|
|
|
|
compValAlarm1Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm1 on Computed value"
|
|
::= { valuesInt 12 }
|
|
|
|
co2Alarm1Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm1 on CO2 level"
|
|
::= { valuesInt 13 }
|
|
|
|
tempAlarm2Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm2 on Temperature"
|
|
::= { valuesInt 14 }
|
|
|
|
humAlarm2Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm2 on Relative humidity"
|
|
::= { valuesInt 15 }
|
|
|
|
compValAlarm2Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm2 on Computed value"
|
|
::= { valuesInt 16 }
|
|
|
|
co2Alarm2Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm2 on CO2 level"
|
|
::= { valuesInt 17 }
|
|
|
|
|
|
-----------------------------------------------------------------------
|
|
-- Alarm settings
|
|
-----------------------------------------------------------------------
|
|
tempLim1Int OBJECT-TYPE
|
|
SYNTAX INTEGER (-5000..20000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Temperature Alarm1 Limit (value*10)"
|
|
::= { settings 1 }
|
|
|
|
humLim1Int OBJECT-TYPE
|
|
SYNTAX INTEGER (-5000..20000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Humidity Alarm1 Limit (value*10)"
|
|
::= { settings 2 }
|
|
|
|
compValLim1Int OBJECT-TYPE
|
|
SYNTAX INTEGER (-5000..20000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Computed Alarm1 Limit (value*10)"
|
|
::= { settings 3 }
|
|
|
|
co2Lim1Int OBJECT-TYPE
|
|
SYNTAX INTEGER (-5000..20000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "CO2 level Alarm1 Limit (value*X)"
|
|
::= { settings 4 }
|
|
|
|
tempLim2Int OBJECT-TYPE
|
|
SYNTAX INTEGER (-5000..20000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Temperature Alarm2 Limit (value*10)"
|
|
::= { settings 5 }
|
|
|
|
humLim2Int OBJECT-TYPE
|
|
SYNTAX INTEGER (-5000..20000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Humidity Alarm2 Limit (value*10)"
|
|
::= { settings 6 }
|
|
|
|
compValLim2Int OBJECT-TYPE
|
|
SYNTAX INTEGER (-5000..20000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Computed value Alarm2 Limit (value*10)"
|
|
::= { settings 7 }
|
|
|
|
co2Lim2Int OBJECT-TYPE
|
|
SYNTAX INTEGER (-5000..20000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "CO2 level Alarm2 Limit (value*X)"
|
|
::= { settings 8 }
|
|
|
|
tempHyst1Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..10000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Temperature Alarm1 Hysteresis (value*10)"
|
|
::= { settings 9 }
|
|
|
|
humHyst1Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..10000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Humidity Alarm1 Hysteresis (value*10)"
|
|
::= { settings 10 }
|
|
|
|
compValHyst1Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..10000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Computed value Alarm1 Hysteresis (value*10)"
|
|
::= { settings 11 }
|
|
|
|
co2Hyst1Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..10000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "CO2 level Alarm1 Hysteresis (value*X)"
|
|
::= { settings 12 }
|
|
|
|
tempHyst2Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..10000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Temperature Alarm2 Hysteresis (value*10)"
|
|
::= { settings 13 }
|
|
|
|
humHyst2Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..10000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Humidity Alarm2 Hysteresis (value*10)"
|
|
::= { settings 14 }
|
|
|
|
compValHyst2Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..10000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Computed value Alarm2 Hysteresis (value*10)"
|
|
::= { settings 15 }
|
|
|
|
co2Hyst2Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..10000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "CO2 level Alarm2 Hysteresis (value*X)"
|
|
::= { settings 16 }
|
|
|
|
tempDelay1Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..30000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Temperature Alarm1 Delay [sec]"
|
|
::= { settings 17 }
|
|
|
|
humDelay1Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..30000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Humidity Alarm1 Delay [sec]"
|
|
::= { settings 18 }
|
|
|
|
compValDelay1Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..30000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Computed value Alarm1 Delay [sec]"
|
|
::= { settings 19 }
|
|
|
|
co2Delay1Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..30000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "CO2 level Alarm1 Delay [sec]"
|
|
::= { settings 20 }
|
|
|
|
tempDelay2Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..30000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Temperature Alarm2 Delay [sec]"
|
|
::= { settings 21 }
|
|
|
|
humDelay2Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..30000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Humidity Alarm2 Delay [sec]"
|
|
::= { settings 22 }
|
|
|
|
compValDelay2Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..30000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Computed value Alarm2 Delay [sec]"
|
|
::= { settings 23 }
|
|
|
|
co2Delay2Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..30000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "CO2 level Alarm2 Delay [sec]"
|
|
::= { settings 24 }
|
|
|
|
tempType1Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..2)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Temperature Alarm1 Type; 0-disbaled, 1-low, 2-high"
|
|
::= { settings 25 }
|
|
|
|
humType1Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..2)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Humidity Alarm1 Type; 0-disbaled, 1-low, 2-high"
|
|
::= { settings 26 }
|
|
|
|
compValType1Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..2)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Computed value Alarm1 Type; 0-disbaled, 1-low, 2-high"
|
|
::= { settings 27 }
|
|
|
|
co2Type1Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..2)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "CO2 level Alarm1 Type; 0-disbaled, 1-low, 2-high"
|
|
::= { settings 28 }
|
|
|
|
tempType2Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..2)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Temperature Alarm2 Type; 0-disbaled, 1-low, 2-high"
|
|
::= { settings 29 }
|
|
|
|
humType2Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..2)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Humidity Alarm2 Type; 0-disbaled, 1-low, 2-high"
|
|
::= { settings 30 }
|
|
|
|
compValType2Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..2)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Computed value Alarm2 Type; 0-disbaled, 1-low, 2-high"
|
|
::= { settings 31 }
|
|
|
|
co2Type2Int OBJECT-TYPE
|
|
SYNTAX INTEGER (0..2)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "CO2 level Alarm2 Type; 0-disbaled, 1-low, 2-high"
|
|
::= { settings 32 }
|
|
|
|
|
|
-----------------------------------------------------------------------
|
|
-- Trap message
|
|
-----------------------------------------------------------------------
|
|
messageString OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..32))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Message giving more detailed information on trap"
|
|
::= { traps 1 }
|
|
|
|
|
|
-----------------------------------------------------------------------
|
|
-- Tables
|
|
-----------------------------------------------------------------------
|
|
historyTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF HistoryEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Table of the history values"
|
|
::= { tables 1 }
|
|
|
|
historyEntry OBJECT-TYPE
|
|
SYNTAX HistoryEntry
|
|
ACCESS not-accessible
|
|
STATUS optional
|
|
DESCRIPTION "History values entries"
|
|
INDEX { histTemp }
|
|
::= { historyTable 1 }
|
|
|
|
HistoryEntry ::=
|
|
SEQUENCE {
|
|
histTemp
|
|
INTEGER,
|
|
histHum
|
|
INTEGER,
|
|
histCompVal
|
|
INTEGER,
|
|
histCO2
|
|
INTEGER
|
|
}
|
|
|
|
histTemp OBJECT-TYPE
|
|
SYNTAX INTEGER(-5000..20000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Temperature reading"
|
|
::= { historyEntry 1 }
|
|
|
|
histHum OBJECT-TYPE
|
|
SYNTAX INTEGER(-5000..20000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Humidity reading"
|
|
::= { historyEntry 2 }
|
|
|
|
histCompVal OBJECT-TYPE
|
|
SYNTAX INTEGER (-5000..20000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Computed value reading"
|
|
::= { historyEntry 3 }
|
|
|
|
histCO2 OBJECT-TYPE
|
|
SYNTAX INTEGER(-5000..20000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "CO2 level reading"
|
|
::= { historyEntry 4 }
|
|
|
|
|
|
-----------------------------------------------------------------------
|
|
-- Traps definition
|
|
-----------------------------------------------------------------------
|
|
|
|
trapTest TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString }
|
|
DESCRIPTION "Testing trap, testing trap by TSensor software"
|
|
::= 0
|
|
|
|
trapNTPError TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString }
|
|
DESCRIPTION "Error on time synchronisation via NTP"
|
|
::= 1
|
|
|
|
trapEmailErrLogin TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString }
|
|
DESCRIPTION "SMTP error - unknown server"
|
|
::= 2
|
|
|
|
trapEmailErrAuth TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString }
|
|
DESCRIPTION "SMTP error - authentication error"
|
|
::= 3
|
|
|
|
trapEmailErrSome TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString }
|
|
DESCRIPTION "SMTP error - error during communication with server, unexpected return code"
|
|
::= 4
|
|
|
|
trapEmailErrSocket TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString }
|
|
DESCRIPTION "SMTP error - socket error, server is not available"
|
|
::= 5
|
|
|
|
trapEmailErrDNS TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString }
|
|
DESCRIPTION "SMTP error - DNS error"
|
|
::= 6
|
|
|
|
trapSOAPErrFile TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString }
|
|
DESCRIPTION "SOAP error - file SOAP not found"
|
|
::= 7
|
|
|
|
trapSOAPErrDNS TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString }
|
|
DESCRIPTION "SOAP error - DNS error"
|
|
::= 8
|
|
|
|
trapSOAPErrSocket TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString }
|
|
DESCRIPTION "SOAP error - socket error, server is not available"
|
|
::= 9
|
|
|
|
trapSOAPErrDelivery TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString }
|
|
DESCRIPTION "SOAP error - delivery error, wrong return code from server"
|
|
::= 10
|
|
|
|
trapTempAlarm1 TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString, temp, tempAlarm1Int }
|
|
DESCRIPTION "Trap for alarm1 on Temperature"
|
|
::= 11
|
|
|
|
trapHumAlarm1 TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString, hum, humAlarm1Int }
|
|
DESCRIPTION "Trap for alarm1 on Relative humidity"
|
|
::= 12
|
|
|
|
trapCompValAlarm1 TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString, compVal, compValAlarm1Int }
|
|
DESCRIPTION "Trap for alarm1 on Computed value"
|
|
::= 13
|
|
|
|
trapCO2Alarm1 TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString, co2, co2Alarm1Int }
|
|
DESCRIPTION "Trap for alarm1 on CO2 level"
|
|
::= 14
|
|
|
|
trapTempAlarm2 TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString, temp, tempAlarm2Int }
|
|
DESCRIPTION "Trap for alarm2 on Temperature"
|
|
::= 21
|
|
|
|
trapHumAlarm2 TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString, hum, humAlarm2Int }
|
|
DESCRIPTION "Trap for alarm2 on Relative humidity"
|
|
::= 22
|
|
|
|
trapCompValAlarm2 TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString, compVal, compValAlarm2Int }
|
|
DESCRIPTION "Trap for alarm2 on Computed value"
|
|
::= 23
|
|
|
|
trapCO2Alarm2 TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString, co2, co2Alarm2Int }
|
|
DESCRIPTION "Trap for alarm2 on CO2 level"
|
|
::= 24
|
|
|
|
trapTempClrAlarm1 TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString, temp, tempAlarm1Int }
|
|
DESCRIPTION "Trap for clearing alarm 1 on Temperature"
|
|
::= 31
|
|
|
|
trapHumClrAlarm1 TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString, hum, humAlarm1Int }
|
|
DESCRIPTION "Trap for clearing alarm 1 on Relative humidity"
|
|
::= 32
|
|
|
|
trapCompValClrAlarm1 TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString, compVal, compValAlarm1Int }
|
|
DESCRIPTION "Trap for clearing alarm 1 on Computed value"
|
|
::= 33
|
|
|
|
trapCO2ClrAlarm1 TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString, co2, co2Alarm1Int }
|
|
DESCRIPTION "Trap for clearing alarm 1 on CO2 level"
|
|
::= 34
|
|
|
|
trapTempClrAlarm2 TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString, temp, tempAlarm2Int }
|
|
DESCRIPTION "Trap for clearing alarm 2 on Temperature"
|
|
::= 41
|
|
|
|
trapHumClrAlarm2 TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString, hum, humAlarm2Int }
|
|
DESCRIPTION "Trap for clearing alarm 2 on Relative humidity"
|
|
::= 42
|
|
|
|
trapCompValClrAlarm2 TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString, compVal, compValAlarm2Int }
|
|
DESCRIPTION "Trap for clearing alarm 2 on Computed value"
|
|
::= 43
|
|
|
|
trapCO2ClrAlarm2 TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString, co2, co2Alarm2Int }
|
|
DESCRIPTION "Trap for clearing alarm 2 on CO2 level"
|
|
::= 44
|
|
|
|
trapRelay1Closed TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString, re1Int }
|
|
DESCRIPTION "Trap for closed Relay 1"
|
|
::= 70
|
|
|
|
trapRelay2Closed TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString, re2Int }
|
|
DESCRIPTION "Trap for closed Relay 2"
|
|
::= 71
|
|
|
|
trapRelay1Open TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString, re1Int }
|
|
DESCRIPTION "Trap for open Relay 1"
|
|
::= 72
|
|
|
|
trapRelay2Open TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString, re2Int }
|
|
DESCRIPTION "Trap for open Relay 2"
|
|
::= 73
|
|
|
|
trapAcousticActivated TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString }
|
|
DESCRIPTION "Trap for activated acoustic"
|
|
::= 74
|
|
|
|
trapAcousticDeactivated TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString }
|
|
DESCRIPTION "Trap for deactivated acoustic"
|
|
::= 75
|
|
|
|
|
|
END
|