2786 lines
83 KiB
Plaintext
2786 lines
83 KiB
Plaintext
WebGraph-2xThermometer-US-MIB DEFINITIONS ::= BEGIN
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.35
|
||
----------------------------------------------------------------
|
||
-- 28.06.2018 New:
|
||
-- systax errors corrected
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.34
|
||
----------------------------------------------------------------
|
||
-- 12.12.2017 New:
|
||
-- wtWebioAn2GraphMQTTLastWillEnable
|
||
-- wtWebioAn2GraphMQTTLastWillTopic
|
||
-- wtWebioAn2GraphMQTTLastWillMsg
|
||
-- wtWebioAn2GraphMQTTLastWillQoS
|
||
-- wtWebioAn2GraphMQTTLastWillRetain
|
||
-- wtWebioAn2GraphMQTTLastWillConnectEnable
|
||
-- wtWebioAn2GraphMQTTLastWillConnectMsg
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.33
|
||
----------------------------------------------------------------
|
||
-- 07.09.2017 New: wtWebioAnxGraphAlarmManagerPort
|
||
-- wtWebioAnxGraphAlarmMQTT_QoS
|
||
-- wtWebioAnxGraphAlarmMQTT_Retain
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.32
|
||
----------------------------------------------------------------
|
||
-- 09.11.2016 New: wtWebioAn2GraphMQTT group
|
||
-- HTTP Request, MQTT Alarm, REST
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.31
|
||
----------------------------------------------------------------
|
||
-- 15.07.2015 Changes for new Navigation (__JB__)
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.30
|
||
----------------------------------------------------------------
|
||
-- 22.06.2010 Output with decimal point
|
||
--
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.29
|
||
----------------------------------------------------------------
|
||
-- 12.01.2009 Webio
|
||
-- Trap numbering
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.28
|
||
----------------------------------------------------------------
|
||
-- 19.01.2007 Webio
|
||
-- New Graphics java script base parameter
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.27
|
||
----------------------------------------------------------------
|
||
-- 09.11.2006 Webio
|
||
-- DHCP enable
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.25
|
||
----------------------------------------------------------------
|
||
-- 28.06.2006 New: Community String Trap
|
||
--
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.24
|
||
----------------------------------------------------------------
|
||
-- 23.12.2005 #57607, WebGraph 2x Thermometer
|
||
--
|
||
|
||
|
||
IMPORTS
|
||
|
||
OBJECT-TYPE FROM RFC-1212
|
||
TRAP-TYPE FROM RFC-1215
|
||
DisplayString, PhysAddress FROM RFC1213-MIB
|
||
enterprises, TimeTicks, IpAddress, NetworkAddress FROM RFC1155-SMI;
|
||
|
||
|
||
-- IpAddress ::=
|
||
-- [APPLICATION 0]
|
||
-- IMPLICIT OCTET STRING (SIZE (4))
|
||
-- Counter ::=
|
||
-- [APPLICATION 1]
|
||
-- IMPLICIT INTEGER (0..4294967295)
|
||
-- Gauge ::=
|
||
-- [APPLICATION 2]
|
||
-- IMPLICIT INTEGER (0..4294967295)
|
||
-- TimeTicks ::=
|
||
-- [APPLICATION 3]
|
||
-- IMPLICIT INTEGER (0..4294967295)
|
||
|
||
|
||
-- DisplayString ::= OCTET STRING
|
||
-- PhysAddress ::= OCTET STRING
|
||
|
||
-- internet OBJECT IDENTIFIER ::= { iso org(3) dod(6) 1 }
|
||
-- privat OBJECT IDENTIFIER ::= { internet 4 }
|
||
-- enterprises OBJECT IDENTIFIER ::= { privat 1 }
|
||
|
||
|
||
|
||
-- Wiesemann & Theis Com-Server MIB
|
||
|
||
wut OBJECT IDENTIFIER ::= { enterprises 5040 }
|
||
wtComServer OBJECT IDENTIFIER ::= { wut 1 }
|
||
wtWebio OBJECT IDENTIFIER ::= { wtComServer 2 }
|
||
|
||
-- wtWebio Tree
|
||
|
||
wtWebioAn2Graph OBJECT IDENTIFIER ::= { wtWebio 43 }
|
||
|
||
-- wtWebioAn2Graph Tree
|
||
|
||
wtWebioAn2GraphTemp OBJECT IDENTIFIER ::= { wtWebioAn2Graph 1 }
|
||
wtWebioAn2GraphSessCntrl OBJECT IDENTIFIER ::= { wtWebioAn2Graph 2 }
|
||
wtWebioAn2GraphConfig OBJECT IDENTIFIER ::= { wtWebioAn2Graph 3 }
|
||
wtWebioAn2GraphDiag OBJECT IDENTIFIER ::= { wtWebioAn2Graph 4 }
|
||
|
||
-- wtWebioAn2GraphConfig Tree
|
||
|
||
wtWebioAn2GraphDevice OBJECT IDENTIFIER ::= { wtWebioAn2GraphConfig 1 }
|
||
wtWebioAn2GraphPorts OBJECT IDENTIFIER ::= { wtWebioAn2GraphConfig 2 }
|
||
wtWebioAn2GraphManufact OBJECT IDENTIFIER ::= { wtWebioAn2GraphConfig 3 }
|
||
|
||
-- wtWebioAn2GraphDevice Tree
|
||
|
||
wtWebioAn2GraphText OBJECT IDENTIFIER ::= { wtWebioAn2GraphDevice 1 }
|
||
wtWebioAn2GraphTimeDate OBJECT IDENTIFIER ::= { wtWebioAn2GraphDevice 2 }
|
||
wtWebioAn2GraphBasic OBJECT IDENTIFIER ::= { wtWebioAn2GraphDevice 3 }
|
||
wtWebioAn2GraphDatalogger OBJECT IDENTIFIER ::= { wtWebioAn2GraphDevice 4 }
|
||
wtWebioAn2GraphAlarm OBJECT IDENTIFIER ::= { wtWebioAn2GraphDevice 5 }
|
||
wtWebioAn2GraphGraphics OBJECT IDENTIFIER ::= { wtWebioAn2GraphDevice 6 }
|
||
|
||
-- wtWebioAn2GraphTimeDate Tree
|
||
|
||
wtWebioAn2GraphTimeZone OBJECT IDENTIFIER ::= { wtWebioAn2GraphTimeDate 1 }
|
||
wtWebioAn2GraphTimeServer OBJECT IDENTIFIER ::= { wtWebioAn2GraphTimeDate 2 }
|
||
wtWebioAn2GraphDeviceClock OBJECT IDENTIFIER ::= { wtWebioAn2GraphTimeDate 3 }
|
||
|
||
-- wtWebioAn2GraphBasic Tree
|
||
|
||
wtWebioAn2GraphNetwork OBJECT IDENTIFIER ::= { wtWebioAn2GraphBasic 1 }
|
||
wtWebioAn2GraphHTTP OBJECT IDENTIFIER ::= { wtWebioAn2GraphBasic 2 }
|
||
wtWebioAn2GraphMail OBJECT IDENTIFIER ::= { wtWebioAn2GraphBasic 3 }
|
||
wtWebioAn2GraphSNMP OBJECT IDENTIFIER ::= { wtWebioAn2GraphBasic 4 }
|
||
wtWebioAn2GraphUDP OBJECT IDENTIFIER ::= { wtWebioAn2GraphBasic 5 }
|
||
wtWebioAn2GraphSyslog OBJECT IDENTIFIER ::= { wtWebioAn2GraphBasic 6 }
|
||
wtWebioAn2GraphFTP OBJECT IDENTIFIER ::= { wtWebioAn2GraphBasic 7 }
|
||
wtWebioAn2GraphLanguage OBJECT IDENTIFIER ::= { wtWebioAn2GraphBasic 9 }
|
||
wtWebioAn2GraphMQTT OBJECT IDENTIFIER ::= { wtWebioAn2GraphBasic 12 }
|
||
wtWebioAn2GraphREST OBJECT IDENTIFIER ::= { wtWebioAn2GraphBasic 13 }
|
||
|
||
|
||
-- wtWebioAn2GraphGraphics Tree
|
||
|
||
wtWebioAn2GraphGraphicsBase OBJECT IDENTIFIER ::= { wtWebioAn2GraphGraphics 1 }
|
||
wtWebioAn2GraphGraphicsSelect OBJECT IDENTIFIER ::= { wtWebioAn2GraphGraphics 2 }
|
||
wtWebioAn2GraphGraphicsScale OBJECT IDENTIFIER ::= { wtWebioAn2GraphGraphics 3 }
|
||
|
||
-- wtWebioAn2GraphTemp Group
|
||
------------------------
|
||
|
||
wtWebioAn2GraphSensors OBJECT-TYPE
|
||
SYNTAX INTEGER (1..2)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Number of temperature sensors"
|
||
::= { wtWebioAn2GraphTemp 1 }
|
||
|
||
-- Interface Table
|
||
|
||
wtWebioAn2GraphSensorTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF WtWebioAn2GraphSensorEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"List of sensors."
|
||
::= { wtWebioAn2GraphTemp 2 }
|
||
|
||
wtWebioAn2GraphSensorEntry OBJECT-TYPE
|
||
SYNTAX WtWebioAn2GraphSensorEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Temperature sensor numbers."
|
||
INDEX { wtWebioAn2GraphSensorNo }
|
||
::= { wtWebioAn2GraphSensorTable 1 }
|
||
|
||
WtWebioAn2GraphSensorEntry ::= SEQUENCE {
|
||
wtWebioAn2GraphSensorNo INTEGER
|
||
}
|
||
|
||
wtWebioAn2GraphSensorNo OBJECT-TYPE
|
||
SYNTAX INTEGER (1..2)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Temperature sensor number."
|
||
::= { wtWebioAn2GraphSensorEntry 1 }
|
||
|
||
|
||
-- wtWebioAn2GraphTempValue Table
|
||
|
||
wtWebioAn2GraphTempValueTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF WtWebioAn2GraphTempValueEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"List of temperature values corresponding to the channel numbers."
|
||
::= { wtWebioAn2GraphTemp 3 }
|
||
|
||
wtWebioAn2GraphTempValueEntry OBJECT-TYPE
|
||
SYNTAX WtWebioAn2GraphTempValueEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Temperatures of the sensors."
|
||
INDEX { wtWebioAn2GraphSensorNo }
|
||
::= { wtWebioAn2GraphTempValueTable 1 }
|
||
|
||
WtWebioAn2GraphTempValueEntry ::= SEQUENCE{
|
||
wtWebioAn2GraphTempValue OCTET STRING
|
||
}
|
||
|
||
wtWebioAn2GraphTempValue OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (5))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Temperature value of the sensor, ASCII, 5 characters in length."
|
||
::= { wtWebioAn2GraphTempValueEntry 1 }
|
||
|
||
-- wtWebioAn2GraphBinaryTempValue Table
|
||
|
||
wtWebioAn2GraphBinaryTempValueTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF WtWebioAn2GraphBinaryTempValueEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"List of binary temperature values corresponding to the channel numbers."
|
||
::= { wtWebioAn2GraphTemp 4 }
|
||
|
||
wtWebioAn2GraphBinaryTempValueEntry OBJECT-TYPE
|
||
SYNTAX WtWebioAn2GraphBinaryTempValueEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Binary temperature values of the sensors."
|
||
INDEX { wtWebioAn2GraphSensorNo }
|
||
::= { wtWebioAn2GraphBinaryTempValueTable 1 }
|
||
|
||
WtWebioAn2GraphBinaryTempValueEntry ::= SEQUENCE{
|
||
wtWebioAn2GraphBinaryTempValue INTEGER
|
||
}
|
||
|
||
wtWebioAn2GraphBinaryTempValue OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Binary temperature value of the sensor in 1/10 degrees Celsius,
|
||
signed number, 0x4FFF6 indicates an
|
||
invalid measured value."
|
||
::= { wtWebioAn2GraphBinaryTempValueEntry 1 }
|
||
|
||
-- wtWebioAn2GraphTempValuePkt Table
|
||
|
||
wtWebioAn2GraphTempValuePktTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF WtWebioAn2GraphTempValuePktEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"List of temperature values corresponding to the channel numbers."
|
||
::= { wtWebioAn2GraphTemp 8 }
|
||
|
||
wtWebioAn2GraphTempValuePktEntry OBJECT-TYPE
|
||
SYNTAX WtWebioAn2GraphTempValuePktEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Temperatures of the sensors."
|
||
INDEX { wtWebioAn2GraphSensorNo }
|
||
::= { wtWebioAn2GraphTempValuePktTable 1 }
|
||
|
||
WtWebioAn2GraphTempValuePktEntry ::= SEQUENCE{
|
||
wtWebioAn2GraphTempValuePkt OCTET STRING
|
||
}
|
||
|
||
wtWebioAn2GraphTempValuePkt OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (5))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Temperature value of the sensor, ASCII, 5 characters in length, decimal point."
|
||
::= { wtWebioAn2GraphTempValuePktEntry 1 }
|
||
|
||
-- wtWebioAn2GraphSessCntrl Group
|
||
--------------------------------
|
||
|
||
wtWebioAn2GraphSessCntrlPassword OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Entering this password opens a session which is ended by writing a 1 to
|
||
wtWebioAn2GraphSessCntrlLogout. When read this variable provides a string of
|
||
length zero."
|
||
::= { wtWebioAn2GraphSessCntrl 1 }
|
||
|
||
wtWebioAn2GraphSessCntrlConfigMode OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
wtWebioAn2GraphSessCntrl-NoSession(0),
|
||
wtWebioAn2GraphSessCntrl-Session(1)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"When the device is in SNMP configuration mode, the value 1 is
|
||
returned, otherwise 0. If the read value is 0 even though the
|
||
password was written, the device is already in config mode and the
|
||
variables can only be read."
|
||
::= { wtWebioAn2GraphSessCntrl 2 }
|
||
|
||
wtWebioAn2GraphSessCntrlLogout OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"If the device is in configuration mode and the session was opened by
|
||
this SNMP Manager, writing a 1 to this variable will end the session
|
||
and all parameters are stored.
|
||
Writing a 2 discards all entries again.
|
||
When read this variable provides the value 0."
|
||
::= { wtWebioAn2GraphSessCntrl 3 }
|
||
|
||
wtWebioAn2GraphSessCntrlAdminPassword OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"This password protects access to the variables with administrator rights.
|
||
It can only be changed by the administrator. If no password was assigned,
|
||
the valid password is public."
|
||
::= { wtWebioAn2GraphSessCntrl 4 }
|
||
|
||
wtWebioAn2GraphSessCntrlConfigPassword OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"This password protects access to the variables with configurator rights. It can
|
||
be changed by the administrator and by the configurator. If no password was assigned,
|
||
the valid password is public. When read this variable provides a null-pointer."
|
||
::= { wtWebioAn2GraphSessCntrl 5 }
|
||
|
||
|
||
-- wtWebioAn2GraphText Group
|
||
------------------------
|
||
|
||
wtWebioAn2GraphDeviceName OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Name of the Webio, which is user definable."
|
||
::= { wtWebioAn2GraphText 1 }
|
||
|
||
wtWebioAn2GraphDeviceText OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Description of the Webio, which is user definable."
|
||
::= { wtWebioAn2GraphText 2 }
|
||
|
||
wtWebioAn2GraphDeviceLocation OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Description of the location of the Webio, which is user definable."
|
||
::= { wtWebioAn2GraphText 3 }
|
||
|
||
wtWebioAn2GraphDeviceContact OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Contact address of the system operator of the Webio, which is user definable."
|
||
::= { wtWebioAn2GraphText 4 }
|
||
|
||
-- wtWebioAn2GraphTimeZone Group
|
||
----------------------------
|
||
|
||
wtWebioAn2GraphTzOffsetHrs OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Offset hours for the time zone (winter time) with respect to UTC."
|
||
::= { wtWebioAn2GraphTimeZone 1 }
|
||
|
||
wtWebioAn2GraphTzOffsetMin OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Offset minutes for the time zone (winter time) with respect to UTC."
|
||
::= { wtWebioAn2GraphTimeZone 2 }
|
||
|
||
wtWebioAn2GraphTzEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(4))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Binary coded conditions:
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 1-7: unused
|
||
Bit 0 : Apply Timezone"
|
||
::= { wtWebioAn2GraphTimeZone 3 }
|
||
|
||
wtWebioAn2GraphStTzOffsetHrs OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Offset hours of the time zone (summer time) with respect to UTC."
|
||
::= { wtWebioAn2GraphTimeZone 4 }
|
||
|
||
wtWebioAn2GraphStTzOffsetMin OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Offset minutes of the time zone (summer time) with respect to UTC."
|
||
::= { wtWebioAn2GraphTimeZone 5 }
|
||
|
||
wtWebioAn2GraphStTzEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(4))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Binary coded conditions:
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 1-7: unused
|
||
Bit 0 : Apply Summertime"
|
||
::= { wtWebioAn2GraphTimeZone 6 }
|
||
|
||
wtWebioAn2GraphStTzStartMonth OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
wtWebioAn2GraphStartMonth-January(1),
|
||
wtWebioAn2GraphStartMonth-February(2),
|
||
wtWebioAn2GraphStartMonth-March(3),
|
||
wtWebioAn2GraphStartMonth-April(4),
|
||
wtWebioAn2GraphStartMonth-May(5),
|
||
wtWebioAn2GraphStartMonth-June(6),
|
||
wtWebioAn2GraphStartMonth-July(7),
|
||
wtWebioAn2GraphStartMonth-August(8),
|
||
wtWebioAn2GraphStartMonth-September(9),
|
||
wtWebioAn2GraphStartMonth-October(10),
|
||
wtWebioAn2GraphStartMonth-November(11),
|
||
wtWebioAn2GraphStartMonth-December(12)
|
||
}
|
||
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Month in which the change is made from winter time to summer time."
|
||
::= { wtWebioAn2GraphTimeZone 7 }
|
||
|
||
wtWebioAn2GraphStTzStartMode OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
wtWebioAn2GraphStartMode-first(1),
|
||
wtWebioAn2GraphStartMode-second(2),
|
||
wtWebioAn2GraphStartMode-third(3),
|
||
wtWebioAn2GraphStartMode-fourth(4),
|
||
wtWebioAn2GraphStartMode-last(5)
|
||
}
|
||
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Mode of the day of the week for which the change is made from winter time to summer time."
|
||
::= { wtWebioAn2GraphTimeZone 8 }
|
||
|
||
wtWebioAn2GraphStTzStartWday OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
wtWebioAn2GraphStartWday-Sunday(1),
|
||
wtWebioAn2GraphStartWday-Monday(2),
|
||
wtWebioAn2GraphStartWday-Tuesday(3),
|
||
wtWebioAn2GraphStartWday-Thursday(4),
|
||
wtWebioAn2GraphStartWday-Wednesday(5),
|
||
wtWebioAn2GraphStartWday-Friday(6),
|
||
wtWebioAn2GraphStartWday-Saturday(7)
|
||
}
|
||
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Day of the week on which the change is made from winter time to summer time"
|
||
::= { wtWebioAn2GraphTimeZone 9 }
|
||
|
||
wtWebioAn2GraphStTzStartHrs OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Hour in which the time zone is changed from winter to summer time with
|
||
respect to UTC."
|
||
::= { wtWebioAn2GraphTimeZone 10 }
|
||
|
||
wtWebioAn2GraphStTzStartMin OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Minute in which the time zone is changed from winter to summer time with
|
||
respect to UTC."
|
||
::= { wtWebioAn2GraphTimeZone 11 }
|
||
|
||
wtWebioAn2GraphStTzStopMonth OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
wtWebioAn2GraphStopMonth-January(1),
|
||
wtWebioAn2GraphStopMonth-February(2),
|
||
wtWebioAn2GraphStopMonth-March(3),
|
||
wtWebioAn2GraphStopMonth-April(4),
|
||
wtWebioAn2GraphStopMonth-May(5),
|
||
wtWebioAn2GraphStopMonth-June(6),
|
||
wtWebioAn2GraphStopMonth-July(7),
|
||
wtWebioAn2GraphStopMonth-August(8),
|
||
wtWebioAn2GraphStopMonth-September(9),
|
||
wtWebioAn2GraphStopMonth-October(10),
|
||
wtWebioAn2GraphStopMonth-November(11),
|
||
wtWebioAn2GraphStopMonth-December(12)
|
||
}
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Month in which the change is made from summer time to winter time."
|
||
::= { wtWebioAn2GraphTimeZone 12 }
|
||
|
||
wtWebioAn2GraphStTzStopMode OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
wtWebioAn2GraphStopMode-first(1),
|
||
wtWebioAn2GraphStopMode-second(2),
|
||
wtWebioAn2GraphStopMode-third(3),
|
||
wtWebioAn2GraphStopMode-fourth(4),
|
||
wtWebioAn2GraphStopMode-last(5)
|
||
}
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Mode of the week day on which the change is made from summer time to winter time."
|
||
::= { wtWebioAn2GraphTimeZone 13 }
|
||
|
||
wtWebioAn2GraphStTzStopWday OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
wtWebioAn2GraphStopWday-Sunday(1),
|
||
wtWebioAn2GraphStopWday-Monday(2),
|
||
wtWebioAn2GraphStopWday-Tuesday(3),
|
||
wtWebioAn2GraphStopWday-Thursday(4),
|
||
wtWebioAn2GraphStopWday-Wednesday(5),
|
||
wtWebioAn2GraphStopWday-Friday(6),
|
||
wtWebioAn2GraphStopWday-Saturday(7)
|
||
}
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Day of the week on which the change is made from summer time to winter time."
|
||
::= { wtWebioAn2GraphTimeZone 14 }
|
||
|
||
wtWebioAn2GraphStTzStopHrs OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Hour at which the time zone is changed from summer to winter time with
|
||
respect to UTC."
|
||
::= { wtWebioAn2GraphTimeZone 15 }
|
||
|
||
wtWebioAn2GraphStTzStopMin OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Minute at which the time zone is changed from summer to winter time with
|
||
respect to UTC."
|
||
::= { wtWebioAn2GraphTimeZone 16 }
|
||
|
||
-- wtWebioAn2GraphTimeServer Group
|
||
----------------------------
|
||
|
||
wtWebioAn2GraphTimeServer1 OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"IP address or name of the 1st time server in ASCII"
|
||
::= { wtWebioAn2GraphTimeServer 1 }
|
||
|
||
wtWebioAn2GraphTimeServer2 OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"IP address or name of the 2nd time server in ASCII"
|
||
::= { wtWebioAn2GraphTimeServer 2 }
|
||
|
||
wtWebioAn2GraphTsEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(4))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Binary coded conditions:
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 1-7: unused
|
||
Bit 0 : Apply Time Server"
|
||
::= { wtWebioAn2GraphTimeServer 3 }
|
||
|
||
wtWebioAn2GraphTsSyncTime OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Daily synchronisation time with the time server (hour: 0-23)."
|
||
::= { wtWebioAn2GraphTimeServer 4 }
|
||
|
||
-- wtWebioAn2GraphDeviceClock Group
|
||
----------------------------
|
||
|
||
wtWebioAn2GraphClockHrs OBJECT-TYPE
|
||
SYNTAX INTEGER (0..23)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Clock hours taking into account the time zone settings."
|
||
::= { wtWebioAn2GraphDeviceClock 1 }
|
||
|
||
wtWebioAn2GraphClockMin OBJECT-TYPE
|
||
SYNTAX INTEGER (0..59)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Clock minutes taking into account the time zone settings."
|
||
::= { wtWebioAn2GraphDeviceClock 2 }
|
||
|
||
wtWebioAn2GraphClockDay OBJECT-TYPE
|
||
SYNTAX INTEGER (1..31)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Date: Day of the month, taking into account the time zone settings."
|
||
::= { wtWebioAn2GraphDeviceClock 3 }
|
||
|
||
wtWebioAn2GraphClockMonth OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
wtWebioAn2GraphClockMonth-January(1),
|
||
wtWebioAn2GraphClockMonth-February(2),
|
||
wtWebioAn2GraphClockMonth-March(3),
|
||
wtWebioAn2GraphClockMonth-April(4),
|
||
wtWebioAn2GraphClockMonth-May(5),
|
||
wtWebioAn2GraphClockMonth-June(6),
|
||
wtWebioAn2GraphClockMonth-July(7),
|
||
wtWebioAn2GraphClockMonth-August(8),
|
||
wtWebioAn2GraphClockMonth-September(9),
|
||
wtWebioAn2GraphClockMonth-October(10),
|
||
wtWebioAn2GraphClockMonth-November(11),
|
||
wtWebioAn2GraphClockMonth-December(12)
|
||
}
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Date: Month, taking into account the time zone settings."
|
||
::= { wtWebioAn2GraphDeviceClock 4 }
|
||
|
||
wtWebioAn2GraphClockYear OBJECT-TYPE
|
||
SYNTAX INTEGER (0..65535)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Date: Year, taking into account the time zone settings."
|
||
::= { wtWebioAn2GraphDeviceClock 5 }
|
||
|
||
|
||
-- wtWebioAn2GraphNetwork Group
|
||
------------------------
|
||
|
||
wtWebioAn2GraphIpAddress OBJECT-TYPE
|
||
SYNTAX IpAddress
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"IP address of the Webio"
|
||
::= { wtWebioAn2GraphNetwork 1 }
|
||
|
||
wtWebioAn2GraphSubnetMask OBJECT-TYPE
|
||
SYNTAX IpAddress
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Subnet mask of the Webio"
|
||
::= { wtWebioAn2GraphNetwork 2 }
|
||
|
||
wtWebioAn2GraphGateway OBJECT-TYPE
|
||
SYNTAX IpAddress
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Gateway of the Webio"
|
||
::= { wtWebioAn2GraphNetwork 3 }
|
||
|
||
wtWebioAn2GraphDnsServer1 OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"IP address of the 1st DNS server in ASCII"
|
||
::= { wtWebioAn2GraphNetwork 4 }
|
||
|
||
wtWebioAn2GraphDnsServer2 OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"IP address of the 2nd DNS server in ASCII"
|
||
::= { wtWebioAn2GraphNetwork 5 }
|
||
|
||
wtWebioAn2GraphAddConfig OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Additional configuration (1=ON):
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 0: BOOTP disable
|
||
Bit 1: DHCP disable
|
||
"
|
||
::= { wtWebioAn2GraphNetwork 6 }
|
||
|
||
-- wtWebioAn2GraphHTTP Group
|
||
--------------------------------
|
||
|
||
wtWebioAn2GraphStartup OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Binary coded start page:
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 1: Index.htm
|
||
Bit 2: Home.htm
|
||
Bit 3: User.htm
|
||
Only one page may be selected at a time."
|
||
::= { wtWebioAn2GraphHTTP 1 }
|
||
|
||
wtWebioAn2GraphGetHeaderEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"If these bits are set, every answer of a short form GET question will be lead
|
||
by the IP-address and name of the device and/or a HTTP header:
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 1-6: unused
|
||
Bit 1 : GET HTTP enable
|
||
Bit 0 : GET Header enable"
|
||
::= { wtWebioAn2GraphHTTP 2 }
|
||
|
||
wtWebioAn2GraphHttpPort OBJECT-TYPE
|
||
SYNTAX INTEGER (1..65535)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Definition of the standard HTML port (Default: 80)."
|
||
::= { wtWebioAn2GraphHTTP 3 }
|
||
|
||
|
||
-- wtWebioAn2GraphMail Group
|
||
--------------------------------
|
||
|
||
wtWebioAn2GraphMailAdName OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Device name for mail administration."
|
||
::= { wtWebioAn2GraphMail 1 }
|
||
|
||
wtWebioAn2GraphMailReply OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Reply address for the mail server."
|
||
::= { wtWebioAn2GraphMail 2 }
|
||
|
||
wtWebioAn2GraphMailServer OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Name or IP address of the mail server."
|
||
::= { wtWebioAn2GraphMail 3 }
|
||
|
||
wtWebioAn1MailEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Set this bit to enable the sending of mails:
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 1-7: unused
|
||
Bit 0 : Mail enable"
|
||
::= { wtWebioAn2GraphMail 4 }
|
||
|
||
wtWebioAn2GraphMailAuthentication OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (4))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Selection of the authentication modi:
|
||
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output.
|
||
Bit 0 corresponds to the LSB.
|
||
OCTET 1: unused
|
||
OCTET 2: unused
|
||
OCTET 3: unused
|
||
OCTET 4: Bit 3-7: unused
|
||
Bit 2 : POP3 before SMTP
|
||
Bit 1 : ESMTP, authentication
|
||
Bit 0 : SMTP, no authentication"
|
||
::= { wtWebioAn2GraphMail 5 }
|
||
|
||
wtWebioAn2GraphMailAuthUser OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Name of the user to be authenticated."
|
||
::= { wtWebioAn2GraphMail 6 }
|
||
|
||
wtWebioAn2GraphMailAuthPassword OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Authentication password."
|
||
::= { wtWebioAn2GraphMail 7 }
|
||
|
||
wtWebioAn2GraphMailPop3Server OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Name or Ip-address of the POP3 Servers."
|
||
::= { wtWebioAn2GraphMail 8 }
|
||
|
||
|
||
-- wtWebioAn2GraphSNMP Group
|
||
--------------------------------
|
||
|
||
wtWebioAn2GraphSnmpCommunityStringRead OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Community string read only"
|
||
::= { wtWebioAn2GraphSNMP 1 }
|
||
|
||
wtWebioAn2GraphSnmpCommunityStringReadWrite OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Community string read / write"
|
||
::= { wtWebioAn2GraphSNMP 2 }
|
||
|
||
wtWebioAn2GraphSystemTrapManagerIP OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Name or IP address of the TCP server which accepts the system trap."
|
||
::= { wtWebioAn2GraphSNMP 3 }
|
||
|
||
wtWebioAn2GraphSystemTrapEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(4))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Binary coded trigger conditions:
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 0: ColdStart
|
||
Bit 1: WarmStart
|
||
Bit 2-7: unused"
|
||
::= { wtWebioAn2GraphSNMP 4 }
|
||
|
||
wtWebioAn2GraphSnmpEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Set bit 0 to enable SNMP.
|
||
If disabled, the device did not respond to any SNMP requests.
|
||
Bit 1 decided wether the community string of read operations
|
||
is compared with the system password or not:
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 1-7: unused
|
||
Bit 0 : SNMP enable"
|
||
::= { wtWebioAn2GraphSNMP 5 }
|
||
|
||
wtWebioAn2GraphSnmpCommunityStringTrap OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Community string send within traps."
|
||
::= { wtWebioAn2GraphSNMP 6 }
|
||
|
||
wtWebioAn2GraphSnmpSystemTrapManagerPort OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Port number of the TCP server which accepts the system trap."
|
||
::= { wtWebioAn2GraphSNMP 7 }
|
||
|
||
-- wtWebioAn2GraphUDP Group
|
||
--------------------------------
|
||
|
||
wtWebioAn2GraphUdpPort OBJECT-TYPE
|
||
SYNTAX INTEGER (1..65535)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Udp port to which the Udp queries ( short form GET requests) can be sent. This
|
||
port number must be unique within the device."
|
||
::= { wtWebioAn2GraphUDP 1 }
|
||
|
||
wtWebioAn2GraphUdpEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Set this bit to enable UDP support:
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 1-7: unused
|
||
Bit 0 : UDP enable"
|
||
::= { wtWebioAn2GraphUDP 2 }
|
||
|
||
|
||
-- wtWebioAn2GraphSyslog Group
|
||
--------------------------------
|
||
|
||
wtWebioAn2GraphSyslogServerIP OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Name or IP address of the Syslog server, which accepts the Syslog messgaes."
|
||
::= { wtWebioAn2GraphSyslog 1 }
|
||
|
||
wtWebioAn2GraphSyslogServerPort OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Portnumber of the Syslog servers, default 514."
|
||
::= { wtWebioAn2GraphSyslog 2 }
|
||
|
||
wtWebioAn2GraphSyslogSystemMessagesEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(4))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Binary coded trigger conditions:
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 0: ColdStart
|
||
Bit 1: WarmStart
|
||
Bit 2: Diag Messages
|
||
Bit 3-7: unused"
|
||
::= { wtWebioAn2GraphSyslog 3 }
|
||
|
||
wtWebioAn2GraphSyslogEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Set bit 0 to enable Syslog:
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 1-7: unused
|
||
Bit 0 : Syslog enable"
|
||
::= { wtWebioAn2GraphSyslog 4 }
|
||
|
||
-- wtWebioAn2GraphFTP Group
|
||
--------------------------------
|
||
|
||
wtWebioAn2GraphFTPServerIP OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Name or IP address of the FTP server, which accepts the FTP messages."
|
||
::= { wtWebioAn2GraphFTP 1 }
|
||
|
||
wtWebioAn2GraphFTPServerControlPort OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Portnumber of the control port of the FTP server, default 21."
|
||
::= { wtWebioAn2GraphFTP 2 }
|
||
|
||
wtWebioAn2GraphFTPUserName OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"FTP Loggin: user name."
|
||
::= { wtWebioAn2GraphFTP 3 }
|
||
|
||
wtWebioAn2GraphFTPPassword OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"FTP Loggin: user password."
|
||
::= { wtWebioAn2GraphFTP 4 }
|
||
|
||
wtWebioAn2GraphFTPAccount OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"FTP Loggin: name of account."
|
||
::= { wtWebioAn2GraphFTP 5 }
|
||
|
||
wtWebioAn2GraphFTPOption OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Bit 0 switches the FTP Server in Passiv-Mode,
|
||
the Client controls the data connection on its own:
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 1-7: unused
|
||
Bit 0 : PASV enable"
|
||
::= { wtWebioAn2GraphFTP 6 }
|
||
|
||
wtWebioAn2GraphFTPEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Set Bit 0 to enable FTP:
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 1-7: unused
|
||
Bit 0 : FTP enable"
|
||
::= { wtWebioAn2GraphFTP 7 }
|
||
|
||
-- wtWebioAn2GraphLanguage Group
|
||
--------------------------------
|
||
|
||
wtWebioAn2GraphLanguageSelect OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Language selection:
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 2-7: unused
|
||
Bit 1 : English
|
||
Bit 0 : German"
|
||
::= { wtWebioAn2GraphLanguage 1 }
|
||
|
||
-- wtWebioAn2GraphMQTT Group
|
||
--------------------------------
|
||
|
||
wtWebioAn2GraphMQTTEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Bit 7 schaltet MQTT frei:
|
||
Octet 1: ungenutzt
|
||
Octet 2: ungenutzt
|
||
Octet 3: ungenutzt
|
||
Octet 4:
|
||
Bit 0-6: ungenutzt
|
||
Bit 7 : MQTT enable"
|
||
::= { wtWebioAn2GraphMQTT 1 }
|
||
|
||
wtWebioAn2GraphMQTTBrockerIP OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Name or IP-address of the MQTT-Server."
|
||
::= { wtWebioAn2GraphMQTT 2 }
|
||
|
||
wtWebioAn2GraphMQTTUserName OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"MQTT login user name."
|
||
::= { wtWebioAn2GraphMQTT 3 }
|
||
|
||
wtWebioAn2GraphMQTTPassword OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"MQTT login password."
|
||
::= { wtWebioAn2GraphMQTT 4 }
|
||
|
||
wtWebioAn2GraphMQTTLocalPort OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Local port number."
|
||
::= { wtWebioAn2GraphMQTT 5 }
|
||
|
||
wtWebioAn2GraphMQTTBrokerServerPort OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"MQTT Server port number."
|
||
::= { wtWebioAn2GraphMQTT 6 }
|
||
|
||
wtWebioAn2GraphMQTTInterval OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Ping intervall, if no data has to be send: time in seconds."
|
||
::= { wtWebioAn2GraphMQTT 7 }
|
||
|
||
wtWebioAn2GraphMQTTLastWillEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Bit 0 activate MQTT LastWill message:
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 1-7: unused
|
||
Bit 0 : MQTT Last will enable"
|
||
::= { wtWebioAn2GraphMQTT 8 }
|
||
|
||
wtWebioAn2GraphMQTTLastWillTopic OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"MQTT Last Will Topic."
|
||
::= { wtWebioAn2GraphMQTT 9 }
|
||
|
||
wtWebioAn2GraphMQTTLastWillMsg OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"MQTT Last Will message."
|
||
::= { wtWebioAn2GraphMQTT 10 }
|
||
|
||
wtWebioAn2GraphMQTTLastWillQoS OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(4))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Binary coded MQTT Publish QoS:
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 0: QoS 0
|
||
Bit 1: QoS 1
|
||
Bit 2: QoS 2
|
||
Bit 3-7:unused"
|
||
::= { wtWebioAn2GraphMQTT 11 }
|
||
|
||
wtWebioAn2GraphMQTTLastWillRetain OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(4))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Binary coded MQTT Publish Retain properties:
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 0 : retain enable
|
||
Bit 1-7 : unused"
|
||
::= { wtWebioAn2GraphMQTT 12 }
|
||
|
||
wtWebioAn2GraphMQTTLastWillConnectEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Bit 0 activate MQTT LastWill Connect message:
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 1-7: unused
|
||
Bit 0 : MQTT Last will connect message enable"
|
||
::= { wtWebioAn2GraphMQTT 13 }
|
||
|
||
wtWebioAn2GraphMQTTLastWillConnectMsg OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"MQTT Last Will Connect message will be send with the QoS and Retain settings
|
||
of the LastWill message."
|
||
::= { wtWebioAn2GraphMQTT 14 }
|
||
|
||
|
||
-- wtWebioAn2GraphREST Group
|
||
--------------------------------
|
||
|
||
wtWebioAn2GraphRESTEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Bit 0 activates REST :
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 1-7: unused
|
||
Bit 0 : REST enable"
|
||
::= { wtWebioAn2GraphREST 1 }
|
||
|
||
wtWebioAn2GraphRESTDigestAuthEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Bit 0 activates Digest-Authentification:
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 1-7: unused
|
||
Bit 0 : Digest Auth enable"
|
||
::= { wtWebioAn2GraphREST 2 }
|
||
|
||
-- wtWebioAn2GraphDatalogger Group
|
||
--------------------------------
|
||
|
||
wtWebioAn2GraphLoggerTimebase OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
wtWebioAn2GraphDatalogger-1Min(1),
|
||
wtWebioAn2GraphDatalogger-5Min(2),
|
||
wtWebioAn2GraphDatalogger-15Min(3),
|
||
wtWebioAn2GraphDatalogger-60Min(4)
|
||
}
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Time base of the data logger"
|
||
::= { wtWebioAn2GraphDatalogger 1 }
|
||
|
||
wtWebioAn2GraphLoggerSensorSel OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(4))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Binary coded trigger conditions:
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 0: Sensor 1
|
||
Bit 1: Sensor 2
|
||
Bit 2: Sensor 3
|
||
Bit 3: Sensor 4
|
||
Bit 4: Sensor 5
|
||
Bit 5: Sensor 6
|
||
Bit 6: Sensor 7
|
||
Bit 7: Sensor 8"
|
||
::= { wtWebioAn2GraphDatalogger 2 }
|
||
|
||
wtWebioAn2GraphDisplaySensorSel OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(4))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Binary coded sensor selection:
|
||
only selected sensors will be shown in the graphical presentation:
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 0: Sensor 1
|
||
Bit 1: Sensor 2
|
||
Bit 2: Sensor 3
|
||
Bit 3: Sensor 4
|
||
Bit 4: Sensor 5
|
||
Bit 5: Sensor 6
|
||
Bit 6: Sensor 7
|
||
Bit 7: Sensor 8"
|
||
::= { wtWebioAn2GraphDatalogger 3 }
|
||
|
||
-- Graph Sensor Color Table
|
||
|
||
wtWebioAn2GraphSensorColorTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF WtWebioAn2GraphSensorColorEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"List of sensor colors for the praphical presentation."
|
||
::= { wtWebioAn2GraphDatalogger 4 }
|
||
|
||
wtWebioAn2GraphSensorColorEntry OBJECT-TYPE
|
||
SYNTAX WtWebioAn2GraphSensorColorEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Index numbers of the sensors."
|
||
INDEX { wtWebioAn2GraphSensorNo }
|
||
::= { wtWebioAn2GraphSensorColorTable 1 }
|
||
|
||
WtWebioAn2GraphSensorColorEntry ::= SEQUENCE {
|
||
wtWebioAn2GraphSensorColor OCTET STRING
|
||
}
|
||
|
||
wtWebioAn2GraphSensorColor OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(3))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Color of the sensors at the praphical presention."
|
||
::= { wtWebioAn2GraphSensorColorEntry 1 }
|
||
|
||
wtWebioAn2GraphAutoScaleEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"If bit 0 is set, vertical auto scale is enabled:
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 1-7: unused
|
||
Bit 0 : Auto Scale enable"
|
||
::= { wtWebioAn2GraphDatalogger 5 }
|
||
|
||
wtWebioAn2GraphVerticalUpperLimit OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"This value defines the maximum temperature shown in the graphical presentation,
|
||
if no auto scaling is selected.
|
||
Temperature in degrees with maximum 2 decimal places."
|
||
::= { wtWebioAn2GraphDatalogger 6 }
|
||
|
||
wtWebioAn2GraphVerticalLowerLimit OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"This value defines the minimum temperature shown in the graphical presentation,
|
||
if no auto scaling is selected.
|
||
Temperature in degrees with maximum 2 decimal places."
|
||
::= { wtWebioAn2GraphDatalogger 7 }
|
||
|
||
wtWebioAn2GraphHorizontalZoom OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
wtWebioAn2GraphZoom-25min(1),
|
||
wtWebioAn2GraphZoom-75min(2),
|
||
wtWebioAn2GraphZoom-5hrs(3),
|
||
wtWebioAn2GraphZoom-30hrs(4),
|
||
wtWebioAn2GraphZoom-5days(5),
|
||
wtWebioAn2GraphZoom-25days(6)
|
||
}
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Defines the default zoom stage, if no auto scaling is selected."
|
||
::= { wtWebioAn2GraphDatalogger 8 }
|
||
|
||
-- wtWebioAn2GraphAlarm Group
|
||
----------------------------
|
||
|
||
wtWebioAn2GraphAlarmCount OBJECT-TYPE
|
||
SYNTAX INTEGER (1..2)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Number of independent alarms."
|
||
::= { wtWebioAn2GraphAlarm 1 }
|
||
|
||
-- Alarm Interface Table
|
||
|
||
wtWebioAn2GraphAlarmIfTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF WtWebioAn2GraphAlarmIfEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"List of alarm indices."
|
||
::= { wtWebioAn2GraphAlarm 2 }
|
||
|
||
wtWebioAn2GraphAlarmIfEntry OBJECT-TYPE
|
||
SYNTAX WtWebioAn2GraphAlarmIfEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Numbers of the alarms."
|
||
INDEX { wtWebioAn2GraphAlarmNo }
|
||
::= { wtWebioAn2GraphAlarmIfTable 1 }
|
||
|
||
WtWebioAn2GraphAlarmIfEntry ::= SEQUENCE {
|
||
wtWebioAn2GraphAlarmNo INTEGER
|
||
}
|
||
|
||
wtWebioAn2GraphAlarmNo OBJECT-TYPE
|
||
SYNTAX INTEGER (1..2)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Alarm number."
|
||
::= { wtWebioAn2GraphAlarmIfEntry 1 }
|
||
|
||
-- Alarm Table
|
||
|
||
wtWebioAn2GraphAlarmTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF WtWebioAn2GraphAlarmEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"List of settings depending on the alarm number."
|
||
::= { wtWebioAn2GraphAlarm 3 }
|
||
|
||
wtWebioAn2GraphAlarmEntry OBJECT-TYPE
|
||
SYNTAX WtWebioAn2GraphAlarmEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Alarm parameters of the individual alarms."
|
||
INDEX { wtWebioAn2GraphAlarmNo }
|
||
::= { wtWebioAn2GraphAlarmTable 1 }
|
||
|
||
WtWebioAn2GraphAlarmEntry ::= SEQUENCE {
|
||
wtWebioAn2GraphAlarmTrigger OCTET STRING,
|
||
wtWebioAn2GraphAlarmMin OCTET STRING,
|
||
wtWebioAn2GraphAlarmMax OCTET STRING,
|
||
wtWebioAn2GraphAlarmHysteresis OCTET STRING,
|
||
wtWebioAn2GraphAlarmDelay OCTET STRING,
|
||
wtWebioAn2GraphAlarmInterval OCTET STRING,
|
||
wtWebioAn2GraphAlarmEnable OCTET STRING,
|
||
wtWebioAn2GraphAlarmEMailAddr OCTET STRING,
|
||
wtWebioAn2GraphAlarmMailSubject OCTET STRING,
|
||
wtWebioAn2GraphAlarmMailText OCTET STRING,
|
||
wtWebioAn2GraphAlarmManagerIP OCTET STRING,
|
||
wtWebioAn2GraphAlarmTrapText OCTET STRING,
|
||
wtWebioAn2GraphAlarmMailOptions OCTET STRING,
|
||
wtWebioAn2GraphAlarmTcpIpAddr OCTET STRING,
|
||
wtWebioAn2GraphAlarmTcpPort INTEGER,
|
||
wtWebioAn2GraphAlarmTcpText OCTET STRING,
|
||
wtWebioAn2GraphAlarmClearMailSubject OCTET STRING,
|
||
wtWebioAn2GraphAlarmClearMailText OCTET STRING,
|
||
wtWebioAn2GraphAlarmClearTrapText OCTET STRING,
|
||
wtWebioAn2GraphAlarmClearTcpText OCTET STRING,
|
||
wtWebioAn2GraphAlarmSyslogIpAddr OCTET STRING,
|
||
wtWebioAn2GraphAlarmSyslogPort INTEGER,
|
||
wtWebioAn2GraphAlarmSyslogText OCTET STRING,
|
||
wtWebioAn2GraphAlarmSyslogClearText OCTET STRING,
|
||
wtWebioAn2GraphAlarmFtpDataPort OCTET STRING,
|
||
wtWebioAn2GraphAlarmFtpFileName OCTET STRING,
|
||
wtWebioAn2GraphAlarmFtpText OCTET STRING,
|
||
wtWebioAn2GraphAlarmFtpClearText OCTET STRING,
|
||
wtWebioAn2GraphAlarmFtpOption OCTET STRING,
|
||
wtWebioAn2GraphAlarmTimerCron OCTET STRING,
|
||
wtWebioAn2GraphAlarmName OCTET STRING,
|
||
wtWebioAn2GraphAlarmActive OCTET STRING,
|
||
wtWebioAn2GraphAlarmHttpReqAuthEnable OCTET STRING,
|
||
wtWebioAn2GraphAlarmHttpReqAuthUser OCTET STRING,
|
||
wtWebioAn2GraphAlarmHttpReqAuthPassword OCTET STRING,
|
||
wtWebioAn2GraphAlarmHttpReqSetUrl OCTET STRING,
|
||
wtWebioAn2GraphAlarmHttpReqClearUrl OCTET STRING,
|
||
wtWebioAn2GraphAlarmHttpReqServerPort INTEGER,
|
||
wtWebioAn2GraphAlarmMqttTopicPath OCTET STRING,
|
||
wtWebioAn2GraphAlarmMqttTopicSetTopic OCTET STRING,
|
||
wtWebioAn2GraphAlarmMqttTopicClear OCTET STRING,
|
||
wtWebioAn2GraphAlarmSensorLostSelection OCTET STRING,
|
||
wtWebioAn2GraphAlarmLimitWindow OCTET STRING,
|
||
wtWebioAn2GraphAlarmSnmpManagerPort INTEGER,
|
||
wtWebioAn2GraphAlarmMqttQoS OCTET STRING,
|
||
wtWebioAn2GraphAlarmMqttRetain OCTET STRING
|
||
|
||
}
|
||
|
||
wtWebioAn2GraphAlarmTrigger OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(4))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Binary coded trigger conditions:
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3:
|
||
Bit 0: Timer
|
||
Bit 1: ColdStart
|
||
Bit 2: WarmStart
|
||
|
||
Octet 4:
|
||
Bit 0: Sensor 1
|
||
Bit 1: Sensor 2
|
||
Bit 2: Sensor 3
|
||
Bit 3: Sensor 4
|
||
Bit 4: Sensor 5
|
||
Bit 5: Sensor 6
|
||
Bit 6: Sensor 7
|
||
Bit 7: Sensor 8"
|
||
::= { wtWebioAn2GraphAlarmEntry 1 }
|
||
|
||
wtWebioAn2GraphAlarmMin OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Minimum temperature in degrees with maximum 2 decimal places."
|
||
::= { wtWebioAn2GraphAlarmEntry 2 }
|
||
|
||
wtWebioAn2GraphAlarmMax OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Maximum temperature in degrees with maximum 2 decimal places."
|
||
::= { wtWebioAn2GraphAlarmEntry 3 }
|
||
|
||
wtWebioAn2GraphAlarmHysteresis OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Temperature changes of this size clears the alarm state (MAX-hyst, MIN+hyst.)
|
||
, in degrees with maximum 2 decimal places."
|
||
::= { wtWebioAn2GraphAlarmEntry 4 }
|
||
|
||
wtWebioAn2GraphAlarmDelay OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Alarm will be delayed by setting this time while stable alarm
|
||
condition occur (time in minutes)."
|
||
::= { wtWebioAn2GraphAlarmEntry 5 }
|
||
|
||
|
||
wtWebioAn2GraphAlarmInterval OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Send interval for alarm messages."
|
||
::= { wtWebioAn2GraphAlarmEntry 6 }
|
||
|
||
wtWebioAn2GraphAlarmEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(4))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Binary coded alarm enable:
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 0: Mail Enable
|
||
Bit 1: SNMP Trap enable
|
||
Bit 2: TCP Client enable"
|
||
::= { wtWebioAn2GraphAlarmEntry 7 }
|
||
|
||
wtWebioAn2GraphAlarmEMailAddr OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"E-Mail address for sending the alarm mail to."
|
||
::= { wtWebioAn2GraphAlarmEntry 8 }
|
||
|
||
wtWebioAn2GraphAlarmMailSubject OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Subject line for alarm mail."
|
||
::= { wtWebioAn2GraphAlarmEntry 9 }
|
||
|
||
wtWebioAn2GraphAlarmMailText OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Alarm mail text: <Tn> provides the current temperature; n = 1..2.
|
||
<Z> provides the current time."
|
||
::= { wtWebioAn2GraphAlarmEntry 10 }
|
||
|
||
wtWebioAn2GraphAlarmManagerIP OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Name or IP address of the SNMP Manager which accepts the trap."
|
||
::= { wtWebioAn2GraphAlarmEntry 11 }
|
||
|
||
wtWebioAn2GraphAlarmTrapText OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"This text is sent in the trap body."
|
||
::= { wtWebioAn2GraphAlarmEntry 12 }
|
||
|
||
wtWebioAn2GraphAlarmMailOptions OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(4))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Binary coded options:
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 0 : Attach Thermo.csv Enable
|
||
Bit 1 : CSV-Data_since_last_report
|
||
Bit 2-7: unused"
|
||
::= { wtWebioAn2GraphAlarmEntry 13 }
|
||
|
||
wtWebioAn2GraphAlarmTcpIpAddr OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Name or IP address of the TCP server which accepts the trap."
|
||
::= { wtWebioAn2GraphAlarmEntry 14 }
|
||
|
||
wtWebioAn2GraphAlarmTcpPort OBJECT-TYPE
|
||
SYNTAX INTEGER (1..65535)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Port number of the TCP server which accepts the trap."
|
||
::= { wtWebioAn2GraphAlarmEntry 15 }
|
||
|
||
wtWebioAn2GraphAlarmTcpText OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"This text is sent in the TCP trap body."
|
||
::= { wtWebioAn2GraphAlarmEntry 16 }
|
||
|
||
wtWebioAn2GraphAlarmClearMailSubject OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Subject line for alarm clear mail."
|
||
::= { wtWebioAn2GraphAlarmEntry 17 }
|
||
|
||
wtWebioAn2GraphAlarmClearMailText OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Alarm clear mail text: <Tn> provides the current temperature; n = 1..2.
|
||
<Z> provides the current time."
|
||
::= { wtWebioAn2GraphAlarmEntry 18 }
|
||
|
||
wtWebioAn2GraphAlarmClearTrapText OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"This text is sent in the trap body."
|
||
::= { wtWebioAn2GraphAlarmEntry 19 }
|
||
|
||
wtWebioAn2GraphAlarmClearTcpText OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"This text is sent in the TCP trap body."
|
||
::= { wtWebioAn2GraphAlarmEntry 20 }
|
||
|
||
wtWebioAn2GraphAlarmSyslogIpAddr OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"IP address of the syslog server to which the Webio device should send syslog messages."
|
||
::= { wtWebioAn2GraphAlarmEntry 21 }
|
||
|
||
wtWebioAn2GraphAlarmSyslogPort OBJECT-TYPE
|
||
SYNTAX INTEGER (1..65535)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Port number of the syslog server to which the Webio device should send syslog messages."
|
||
::= { wtWebioAn2GraphAlarmEntry 22 }
|
||
|
||
wtWebioAn2GraphAlarmSyslogText OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
|
||
This text appears in the following syslog message body."
|
||
::= { wtWebioAn2GraphAlarmEntry 23 }
|
||
|
||
wtWebioAn2GraphAlarmSyslogClearText OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
|
||
This text appears in the following syslog message body."
|
||
::= { wtWebioAn2GraphAlarmEntry 24 }
|
||
|
||
wtWebioAn2GraphAlarmFtpDataPort OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Local data port: 1..65535 or AUTO: the next free port will be assigned."
|
||
::= { wtWebioAn2GraphAlarmEntry 25 }
|
||
|
||
wtWebioAn2GraphAlarmFtpFileName OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Name of the file including path informations."
|
||
::= { wtWebioAn2GraphAlarmEntry 26 }
|
||
|
||
wtWebioAn2GraphAlarmFtpText OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Message text to store on the FTP server."
|
||
::= { wtWebioAn2GraphAlarmEntry 27 }
|
||
|
||
wtWebioAn2GraphAlarmFtpClearText OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Alarm clear message to store on the FTP server."
|
||
::= { wtWebioAn2GraphAlarmEntry 28 }
|
||
|
||
wtWebioAn2GraphAlarmFtpOption OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(4))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Binary coded options, select only one option at the same time:
|
||
STORE = replace file
|
||
APPEND = append message at the end of the file
|
||
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 0 : STORE
|
||
Bit 1 : APPEND
|
||
Bit 2-7: unused"
|
||
::= { wtWebioAn2GraphAlarmEntry 29 }
|
||
|
||
wtWebioAn2GraphAlarmTimerCron OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"This entry contains 5 text fields space or tab seperated for time trigger definition.
|
||
Each field must match with the actual time to trigger a message, weekday and day of month
|
||
are interpreted separatley.
|
||
1: Minutes Range 0-59
|
||
2. Hours Range 0-23, 0 is midnight
|
||
3: Day of month Range 1-31
|
||
4: Month Range 1-12
|
||
5: Weekday Range 0-6, 0 is sunday
|
||
|
||
Syntax for every field:
|
||
- an asterix (*) enables every possible setting of a field
|
||
- single numbers seperated by commas
|
||
- a partition within the allowed range (1-5)
|
||
- step size within an partition of the allowed range (0-59/2: every second minute)."
|
||
::= { wtWebioAn2GraphAlarmEntry 30 }
|
||
|
||
-- __JB__
|
||
wtWebioAn2GraphAlarmName OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Alert name"
|
||
::= { wtWebioAn2GraphAlarmEntry 39 }
|
||
|
||
-- __JB__
|
||
wtWebioAn2GraphAlarmActive OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Alert active
|
||
1 = ON
|
||
0 = OFF"
|
||
::= { wtWebioAn2GraphAlarmEntry 40 }
|
||
|
||
wtWebioAn2GraphAlarmHttpReqAuthEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Binary coded options, select only one option at the same time:
|
||
OCTET 1: unused
|
||
OCTET 2: unused
|
||
OCTET 3: unused
|
||
OCTET 4, Bit 1-7: unused
|
||
Bit 0 : HHTP Request Authentication enable"
|
||
::= { wtWebioAn2GraphAlarmEntry 61 }
|
||
|
||
wtWebioAn2GraphAlarmHttpReqAuthUser OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"HTTP Request: User"
|
||
::= { wtWebioAn2GraphAlarmEntry 62 }
|
||
|
||
wtWebioAn2GraphAlarmHttpReqAuthPassword OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"HTTP Request: Password"
|
||
::= { wtWebioAn2GraphAlarmEntry 63 }
|
||
|
||
wtWebioAn2GraphAlarmHttpReqSetUrl OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"HTTP Request: Set URL"
|
||
::= { wtWebioAn2GraphAlarmEntry 64 }
|
||
|
||
wtWebioAn2GraphAlarmHttpReqClearUrl OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"HTTP Request: Clear URL"
|
||
::= { wtWebioAn2GraphAlarmEntry 65 }
|
||
|
||
wtWebioAn2GraphAlarmHttpReqServerPort OBJECT-TYPE
|
||
SYNTAX INTEGER (1..65535)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"HTTP Request: Server Port"
|
||
::= { wtWebioAn2GraphAlarmEntry 66 }
|
||
|
||
wtWebioAn2GraphAlarmMqttTopicPath OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"MQTT Publish: Topic path"
|
||
::= { wtWebioAn2GraphAlarmEntry 67 }
|
||
|
||
wtWebioAn2GraphAlarmMqttTopicSetTopic OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"MQTT Publish: Topic SET message"
|
||
::= { wtWebioAn2GraphAlarmEntry 68 }
|
||
|
||
wtWebioAn2GraphAlarmMqttTopicClear OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"MQTT Publish: Topic CLEAR message"
|
||
::= { wtWebioAn2GraphAlarmEntry 69 }
|
||
|
||
wtWebioAn2GraphAlarmSensorLostSelection OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Binary coded options:
|
||
OCTET 1: unused
|
||
OCTET 2: unused
|
||
OCTET 3: unused
|
||
OCTET 4:
|
||
Bit 2-7: unused
|
||
Bit 1 : Sensor 1
|
||
Bit 0 : Sensor 0 "
|
||
::= { wtWebioAn2GraphAlarmEntry 70 }
|
||
|
||
wtWebioAn2GraphAlarmLimitWindow OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"If window type is INSIDE the alarm is genereted when the temperature
|
||
is greater minumum value and lower than maximum value. If window type is OUTSIDE
|
||
the alarm is generated when the measured value is lower than the minimum value
|
||
or greater than the maximum value.
|
||
Binary coded options, select only one option at the same time:
|
||
OCTET 1: unused
|
||
OCTET 2: unused
|
||
OCTET 3: unused
|
||
OCTET 4, Bit 2-7: unused
|
||
Bit 1 : inside window
|
||
Bit 0 : outside window"
|
||
::= { wtWebioAn2GraphAlarmEntry 71 }
|
||
|
||
wtWebioAn2GraphAlarmSnmpManagerPort OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Port number of the SNMP Manager to which the Webio device should send SNMP traps."
|
||
::= { wtWebioAn2GraphAlarmEntry 76 }
|
||
|
||
wtWebioAn2GraphAlarmMqttQoS OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(4))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Binary coded value:
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 0: QoS 0
|
||
Bit 1: QoS 1
|
||
Bit 2: QoS 2
|
||
Bit 3-7:unused"
|
||
::= { wtWebioAn2GraphAlarmEntry 77 }
|
||
|
||
wtWebioAn2GraphAlarmMqttRetain OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(4))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Binary coded value:
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 0 : retain enable
|
||
Bit 1-7 : unused"
|
||
::= { wtWebioAn2GraphAlarmEntry 78 }
|
||
|
||
-- wtWebioAn2GraphGraphicsBase Group
|
||
----------------------------
|
||
|
||
wtWebioAn2GraphGraphicsBaseEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Defines the viewing options of the graphic:
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 0 : Auto scroll enable
|
||
Bit 1 : Show table
|
||
Bit 2 : Show graph
|
||
Bit 3 : Show control buttons
|
||
Bit 4 : Show config menu
|
||
Bit 5-7: unused"
|
||
::= { wtWebioAn2GraphGraphicsBase 1 }
|
||
|
||
wtWebioAn2GraphGraphicsBaseWidth OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Defines the width of the graphic in pixels."
|
||
::= { wtWebioAn2GraphGraphicsBase 2 }
|
||
|
||
wtWebioAn2GraphGraphicsBaseHeight OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Defines the height of the graphic in pixels."
|
||
::= { wtWebioAn2GraphGraphicsBase 3 }
|
||
|
||
wtWebioAn2GraphGraphicsBaseFrameColor OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(3))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Frame color definition in RGB."
|
||
::= { wtWebioAn2GraphGraphicsBase 4 }
|
||
|
||
wtWebioAn2GraphGraphicsBaseBackgroundColor OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(3))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Background color definition in RGB."
|
||
::= { wtWebioAn2GraphGraphicsBase 5 }
|
||
|
||
wtWebioAn2GraphGraphicsBasePollingrate OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Defines the pollingrate in seconds,
|
||
which defines the refreshing intervall of the graphic."
|
||
::= { wtWebioAn2GraphGraphicsBase 6 }
|
||
|
||
-- wtWebioAn2GraphGraphicsSelect Group
|
||
----------------------------
|
||
|
||
wtWebioAn2GraphGraphicsSelectDisplaySensorSel OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(4))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Binary coded sensor selection:
|
||
only selected sensors will be shown in the graphical presentation:
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 0: Sensor 1
|
||
Bit 1: Sensor 2
|
||
Bit 2: Sensor 3
|
||
Bit 3: Sensor 4
|
||
Bit 4: Sensor 5
|
||
Bit 5: Sensor 6
|
||
Bit 6: Sensor 7
|
||
Bit 7: Sensor 8"
|
||
::= { wtWebioAn2GraphGraphicsSelect 1 }
|
||
|
||
wtWebioAn2GraphGraphicsSelectDisplayShowExtrem OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(4))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Binary coded sensor selection:
|
||
only selected sensors will be shown with minima and maxima:
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 0: Sensor 1
|
||
Bit 1: Sensor 2
|
||
Bit 2: Sensor 3
|
||
Bit 3: Sensor 4
|
||
Bit 4: Sensor 5
|
||
Bit 5: Sensor 6
|
||
Bit 6: Sensor 7
|
||
Bit 7: Sensor 8"
|
||
::= { wtWebioAn2GraphGraphicsSelect 2 }
|
||
|
||
-- Graph Sensor Color Table
|
||
|
||
wtWebioAn2GraphSelectSensorColorTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF WtWebioAn2GraphSelectSensorColorEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"List of sensor colors for the praphical presentation."
|
||
::= { wtWebioAn2GraphGraphicsSelect 3 }
|
||
|
||
wtWebioAn2GraphSelectSensorColorEntry OBJECT-TYPE
|
||
SYNTAX WtWebioAn2GraphSelectSensorColorEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Numbers of the sensors."
|
||
INDEX { wtWebioAn2GraphSensorNo }
|
||
::= { wtWebioAn2GraphSelectSensorColorTable 1 }
|
||
|
||
WtWebioAn2GraphSelectSensorColorEntry ::= SEQUENCE {
|
||
wtWebioAn2GraphSelectGraphicsSensorColor OCTET STRING,
|
||
wtWebioAn2GraphSelectGraphicsSelectScale OCTET STRING
|
||
}
|
||
|
||
wtWebioAn2GraphSelectGraphicsSensorColor OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(3))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Color of the sensors at the praphical presention."
|
||
::= { wtWebioAn2GraphSelectSensorColorEntry 1 }
|
||
|
||
wtWebioAn2GraphSelectGraphicsSelectScale OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Assignes one of 4 scales to a sensor:
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 0 : Use Scale 1
|
||
Bit 1 : Use Scale 2
|
||
Bit 2 : Use Scale 3
|
||
Bit 3 : Use Scale 4
|
||
Bit 4-7: unused"
|
||
::= { wtWebioAn2GraphSelectSensorColorEntry 2 }
|
||
|
||
-- wtWebioAn2GraphGraphicsScale Group
|
||
----------------------------
|
||
|
||
wtWebioAn2GraphGraphicsScaleAutoScaleEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Select the Auto Scale Mode:
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 0 : Scale 1 Auto scale enable
|
||
Bit 1 : Scale 2 Auto scale enable
|
||
Bit 2 : Scale 3 Auto scale enable
|
||
Bit 3 : Scale 4 Auto scale enable
|
||
Bit 4-7: unused"
|
||
::= { wtWebioAn2GraphGraphicsScale 1 }
|
||
|
||
|
||
wtWebioAn2GraphGraphicsScaleAutoFitEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Select the Auto Fit Mode::
|
||
Octet 1: unused
|
||
Octet 2: unused
|
||
Octet 3: unused
|
||
Octet 4:
|
||
Bit 0 : Scale 1 Auto fit enable
|
||
Bit 1 : Scale 2 Auto fit enable
|
||
Bit 2 : Scale 3 Auto fit enable
|
||
Bit 3 : Scale 4 Auto fit enable
|
||
Bit 4-7: unused"
|
||
::= { wtWebioAn2GraphGraphicsScale 2 }
|
||
|
||
wtWebioAn2GraphGraphicsScale1Min OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Scale 1: Minimum."
|
||
::= { wtWebioAn2GraphGraphicsScale 3 }
|
||
|
||
wtWebioAn2GraphGraphicsScale2Min OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Scale 2: Minimum."
|
||
::= { wtWebioAn2GraphGraphicsScale 4 }
|
||
|
||
wtWebioAn2GraphGraphicsScale3Min OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Scale 3: Minimum."
|
||
::= { wtWebioAn2GraphGraphicsScale 5 }
|
||
|
||
wtWebioAn2GraphGraphicsScale4Min OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Scale 4: Minimum."
|
||
::= { wtWebioAn2GraphGraphicsScale 6 }
|
||
|
||
wtWebioAn2GraphGraphicsScale1Max OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Scale 1: Maximum."
|
||
::= { wtWebioAn2GraphGraphicsScale 7 }
|
||
|
||
wtWebioAn2GraphGraphicsScale2Max OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Scale 2: Maximum."
|
||
::= { wtWebioAn2GraphGraphicsScale 8 }
|
||
|
||
wtWebioAn2GraphGraphicsScale3Max OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Scale 3: Maximum."
|
||
::= { wtWebioAn2GraphGraphicsScale 9 }
|
||
|
||
wtWebioAn2GraphGraphicsScale4Max OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Scale 4: Maximum."
|
||
::= { wtWebioAn2GraphGraphicsScale 10 }
|
||
|
||
wtWebioAn2GraphGraphicsScale1Unit OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Scale 1: Unit."
|
||
::= { wtWebioAn2GraphGraphicsScale 11 }
|
||
|
||
wtWebioAn2GraphGraphicsScale2Unit OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Scale 2: Unit."
|
||
::= { wtWebioAn2GraphGraphicsScale 12 }
|
||
|
||
wtWebioAn2GraphGraphicsScale3Unit OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Scale 3: Unit."
|
||
::= { wtWebioAn2GraphGraphicsScale 13 }
|
||
|
||
wtWebioAn2GraphGraphicsScale4Unit OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Scale 4: Unit."
|
||
::= { wtWebioAn2GraphGraphicsScale 14 }
|
||
|
||
-- wtWebioAn2GraphPorts Group
|
||
----------------------------
|
||
|
||
-- Table
|
||
|
||
wtWebioAn2GraphPortTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF WtWebioAn2GraphPortEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"List of settings depending on the sensor number."
|
||
::= { wtWebioAn2GraphPorts 1 }
|
||
|
||
wtWebioAn2GraphPortEntry OBJECT-TYPE
|
||
SYNTAX WtWebioAn2GraphPortEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Sensor parameters for the individual sensors."
|
||
INDEX { wtWebioAn2GraphSensorNo }
|
||
::= { wtWebioAn2GraphPortTable 1 }
|
||
|
||
WtWebioAn2GraphPortEntry ::= SEQUENCE {
|
||
wtWebioAn2GraphPortName OCTET STRING,
|
||
wtWebioAn2GraphPortText OCTET STRING,
|
||
wtWebioAn2GraphPortOffset1 OCTET STRING,
|
||
wtWebioAn2GraphPortTemperature1 OCTET STRING,
|
||
wtWebioAn2GraphPortOffset2 OCTET STRING,
|
||
wtWebioAn2GraphPortTemperature2 OCTET STRING,
|
||
wtWebioAn2GraphPortComment OCTET STRING,
|
||
wtWebioAn2GraphPortSensorSelect OCTET STRING
|
||
|
||
|
||
}
|
||
|
||
wtWebioAn2GraphPortName OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Name of the sensor."
|
||
::= { wtWebioAn2GraphPortEntry 1 }
|
||
|
||
wtWebioAn2GraphPortText OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Description of the sensor."
|
||
::= { wtWebioAn2GraphPortEntry 2 }
|
||
|
||
wtWebioAn2GraphPortOffset1 OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 1."
|
||
::= { wtWebioAn2GraphPortEntry 3 }
|
||
|
||
wtWebioAn2GraphPortTemperature1 OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places."
|
||
::= { wtWebioAn2GraphPortEntry 4 }
|
||
|
||
wtWebioAn2GraphPortOffset2 OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 2."
|
||
::= { wtWebioAn2GraphPortEntry 5 }
|
||
|
||
wtWebioAn2GraphPortTemperature2 OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places."
|
||
::= { wtWebioAn2GraphPortEntry 6 }
|
||
|
||
wtWebioAn2GraphPortComment OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Offset calibration: informations of date, name of operator, reference devices."
|
||
::= { wtWebioAn2GraphPortEntry 7 }
|
||
|
||
wtWebioAn2GraphPortSensorSelect OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(4))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Bin<69>r kodierte Optionen f<>r Sensor:
|
||
Octet 1: ungenutzt
|
||
Octet 2: ungenutzt
|
||
Octet 3: ungenutzt
|
||
Octet 4:
|
||
Bit 0 : PT100
|
||
Bit 1 : PT1000 (default)
|
||
Bit 2-7: ungenutzt"
|
||
::= { wtWebioAn2GraphPortEntry 8 }
|
||
|
||
-- wtWebioAn2GraphManufact Group
|
||
----------------------------
|
||
|
||
wtWebioAn2GraphMfName OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Manufacturer company name"
|
||
::= { wtWebioAn2GraphManufact 1 }
|
||
|
||
wtWebioAn2GraphMfAddr OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Manufacturer address."
|
||
::= { wtWebioAn2GraphManufact 2 }
|
||
|
||
wtWebioAn2GraphMfHotline OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Manufacturer hotline."
|
||
::= { wtWebioAn2GraphManufact 3 }
|
||
|
||
wtWebioAn2GraphMfInternet OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Manufacturer Internet address."
|
||
::= { wtWebioAn2GraphManufact 4 }
|
||
|
||
wtWebioAn2GraphMfDeviceTyp OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Manufacturer device name (model number)."
|
||
::= { wtWebioAn2GraphManufact 5 }
|
||
|
||
wtWebioAn2GraphMfOrderNo OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Manufacturer part number."
|
||
::= { wtWebioAn2GraphManufact 6 }
|
||
|
||
-- wtWebioAn2GraphDiag Group
|
||
----------------------------
|
||
|
||
wtWebioAn2GraphDiagErrorCount OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Number of entries in the error memory."
|
||
::= { wtWebioAn2GraphDiag 1 }
|
||
|
||
wtWebioAn2GraphDiagBinaryError OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Error causes coded bit-by-bit."
|
||
::= { wtWebioAn2GraphDiag 2 }
|
||
|
||
wtWebioAn2GraphDiagErrorIndex OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The value of this variable is used as an index to read
|
||
an error massege from wtWebioAn2GraphDiagErrorMessage.
|
||
Errors are numbered from 1 to wtWebioAn2GraphDiagErrorCount.
|
||
Writing a valid value into this variable, making the appropriate
|
||
message readable from wtWebioAn2GraphDiagErrorMessage."
|
||
::= { wtWebioAn2GraphDiag 3 }
|
||
|
||
wtWebioAn2GraphDiagErrorMessage OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Using wtWebioAn2GraphDiagErrorIndex as an index, the appropriate message is available."
|
||
::= { wtWebioAn2GraphDiag 4 }
|
||
|
||
wtWebioAn2GraphDiagErrorClear OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS write-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Writing 1 into this variable clears all diagnosis messages."
|
||
::= { wtWebioAn2GraphDiag 5 }
|
||
|
||
-- TRAP DEFINITIONS
|
||
|
||
-- Diese SNMP-Traps werden gesendet, wenn die Alarmtriggerbedingungen zutreffen
|
||
|
||
wtWebioAn2GraphAlert1 TRAP-TYPE
|
||
ENTERPRISE wtWebioAn2Graph
|
||
VARIABLES { wtWebioAn2GraphAlarmTrapText }
|
||
DESCRIPTION
|
||
"This SNMP trap is generated when Alarm 1 was triggered,
|
||
SNMP trap enable is set and
|
||
SNMP is enabled."
|
||
-- NMS trap annotation
|
||
--#TYPE "Web-Thermograph Alarm 1"
|
||
--#SUMMARY "Alarm 1: %s"
|
||
--#ARGUMENTS {0}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 21
|
||
|
||
wtWebioAn2GraphAlert2 TRAP-TYPE
|
||
ENTERPRISE wtWebioAn2Graph
|
||
VARIABLES { wtWebioAn2GraphAlarmTrapText }
|
||
DESCRIPTION
|
||
"This SNMP trap is generated when Alarm 2 was triggered,
|
||
SNMP trap enable is set and
|
||
SNMP is enabled."
|
||
-- NMS trap annotation
|
||
--#TYPE "Web-Thermograph Alarm 2"
|
||
--#SUMMARY "Alarm 2: %s"
|
||
--#ARGUMENTS {0}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 22
|
||
|
||
wtWebioAn2GraphAlert3 TRAP-TYPE
|
||
ENTERPRISE wtWebioAn2Graph
|
||
VARIABLES { wtWebioAn2GraphAlarmTrapText }
|
||
DESCRIPTION
|
||
"This SNMP trap is generated when Alarm 3 was triggered,
|
||
SNMP trap enable is set and
|
||
SNMP is enabled."
|
||
-- NMS trap annotation
|
||
--#TYPE "Web-Thermograph Alarm 3"
|
||
--#SUMMARY "Alarm 3: %s"
|
||
--#ARGUMENTS {0}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 23
|
||
|
||
wtWebioAn2GraphAlert4 TRAP-TYPE
|
||
ENTERPRISE wtWebioAn2Graph
|
||
VARIABLES { wtWebioAn2GraphAlarmTrapText }
|
||
DESCRIPTION
|
||
"This SNMP trap is generated when Alarm 4 was triggered,
|
||
SNMP trap enable is set and
|
||
SNMP is enabled."
|
||
-- NMS trap annotation
|
||
--#TYPE "Web-Thermograph Alarm 4"
|
||
--#SUMMARY "Alarm 4: %s"
|
||
--#ARGUMENTS {0}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 24
|
||
|
||
wtWebioAn2GraphAlert5 TRAP-TYPE
|
||
ENTERPRISE wtWebioAn2Graph
|
||
VARIABLES { wtWebioAn2GraphAlarmTrapText }
|
||
DESCRIPTION
|
||
"This SNMP trap is generated when Alarm 5 was triggered,
|
||
SNMP trap enable is set and
|
||
SNMP is enabled."
|
||
-- NMS trap annotation
|
||
--#TYPE "Web-Thermograph Alarm 5"
|
||
--#SUMMARY "Alarm 5: %s"
|
||
--#ARGUMENTS {0}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 25
|
||
|
||
wtWebioAn2GraphAlert6 TRAP-TYPE
|
||
ENTERPRISE wtWebioAn2Graph
|
||
VARIABLES { wtWebioAn2GraphAlarmTrapText }
|
||
DESCRIPTION
|
||
"This SNMP trap is generated when Alarm 6 was triggered,
|
||
SNMP trap enable is set and
|
||
SNMP is enabled."
|
||
-- NMS trap annotation
|
||
--#TYPE "Web-Thermograph Alarm 6"
|
||
--#SUMMARY "Alarm 6: %s"
|
||
--#ARGUMENTS {0}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 26
|
||
|
||
wtWebioAn2GraphAlert7 TRAP-TYPE
|
||
ENTERPRISE wtWebioAn2Graph
|
||
VARIABLES { wtWebioAn2GraphAlarmTrapText }
|
||
DESCRIPTION
|
||
"This SNMP trap is generated when Alarm 7 was triggered,
|
||
SNMP trap enable is set and
|
||
SNMP is enabled."
|
||
-- NMS trap annotation
|
||
--#TYPE "Web-Thermograph Alarm 7"
|
||
--#SUMMARY "Alarm 7: %s"
|
||
--#ARGUMENTS {0}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 27
|
||
|
||
wtWebioAn2GraphAlert8 TRAP-TYPE
|
||
ENTERPRISE wtWebioAn2Graph
|
||
VARIABLES { wtWebioAn2GraphAlarmTrapText }
|
||
DESCRIPTION
|
||
"This SNMP trap is generated when Alarm 8 was triggered,
|
||
SNMP trap enable is set and
|
||
SNMP is enabled."
|
||
-- NMS trap annotation
|
||
--#TYPE "Web-Thermograph Alarm 8"
|
||
--#SUMMARY "Alarm 8: %s"
|
||
--#ARGUMENTS {0}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 28
|
||
|
||
|
||
wtWebioAn2GraphAlert9 TRAP-TYPE
|
||
ENTERPRISE wtWebioAn2Graph
|
||
VARIABLES { wtWebioAn2GraphAlarmClearTrapText }
|
||
DESCRIPTION
|
||
"This SNMP trap is generated when Alarm 1 was cleared,
|
||
SNMP trap enable is set and
|
||
SNMP is enabled."
|
||
-- NMS trap annotation
|
||
--#TYPE "Web-Thermograph Release Alarm 1"
|
||
--#SUMMARY "Release Alarm 1: %s"
|
||
--#ARGUMENTS {0}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 81
|
||
|
||
wtWebioAn2GraphAlert10 TRAP-TYPE
|
||
ENTERPRISE wtWebioAn2Graph
|
||
VARIABLES { wtWebioAn2GraphAlarmClearTrapText }
|
||
DESCRIPTION
|
||
"This SNMP trap is generated when Alarm 2 was cleared,
|
||
SNMP trap enable is set and
|
||
SNMP is enabled."
|
||
-- NMS trap annotation
|
||
--#TYPE "Web-Thermograph Release Alarm 2"
|
||
--#SUMMARY "Release Alarm 2: %s"
|
||
--#ARGUMENTS {0}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 82
|
||
|
||
wtWebioAn2GraphAlert11 TRAP-TYPE
|
||
ENTERPRISE wtWebioAn2Graph
|
||
VARIABLES { wtWebioAn2GraphAlarmClearTrapText }
|
||
DESCRIPTION
|
||
"This SNMP trap is generated when Alarm 3 was cleared,
|
||
SNMP trap enable is set and
|
||
SNMP is enabled."
|
||
-- NMS trap annotation
|
||
--#TYPE "Web-Thermograph Release Alarm 3"
|
||
--#SUMMARY "Release Alarm 3: %s"
|
||
--#ARGUMENTS {0}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 83
|
||
|
||
wtWebioAn2GraphAlert12 TRAP-TYPE
|
||
ENTERPRISE wtWebioAn2Graph
|
||
VARIABLES { wtWebioAn2GraphAlarmClearTrapText }
|
||
DESCRIPTION
|
||
"This SNMP trap is generated when Alarm 4 was cleared,
|
||
SNMP trap enable is set and
|
||
SNMP is enabled."
|
||
-- NMS trap annotation
|
||
--#TYPE "Web-Thermograph Release Alarm 4"
|
||
--#SUMMARY "Release Alarm 4: %s"
|
||
--#ARGUMENTS {0}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 84
|
||
|
||
wtWebioAn2GraphAlert13 TRAP-TYPE
|
||
ENTERPRISE wtWebioAn2Graph
|
||
VARIABLES { wtWebioAn2GraphAlarmClearTrapText }
|
||
DESCRIPTION
|
||
"This SNMP trap is generated when Alarm 5 was cleared,
|
||
SNMP trap enable is set and
|
||
SNMP is enabled."
|
||
-- NMS trap annotation
|
||
--#TYPE "Web-Thermograph Release Alarm 5"
|
||
--#SUMMARY "Release Alarm 5: %s"
|
||
--#ARGUMENTS {0}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 85
|
||
|
||
wtWebioAn2GraphAlert14 TRAP-TYPE
|
||
ENTERPRISE wtWebioAn2Graph
|
||
VARIABLES { wtWebioAn2GraphAlarmClearTrapText }
|
||
DESCRIPTION
|
||
"This SNMP trap is generated when Alarm 6 was cleared,
|
||
SNMP trap enable is set and
|
||
SNMP is enabled."
|
||
-- NMS trap annotation
|
||
--#TYPE "Web-Thermograph Release Alarm 6"
|
||
--#SUMMARY "Release Alarm 6: %s"
|
||
--#ARGUMENTS {0}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 86
|
||
|
||
wtWebioAn2GraphAlert15 TRAP-TYPE
|
||
ENTERPRISE wtWebioAn2Graph
|
||
VARIABLES { wtWebioAn2GraphAlarmClearTrapText }
|
||
DESCRIPTION
|
||
"This SNMP trap is generated when Alarm 7 was cleared,
|
||
SNMP trap enable is set and
|
||
SNMP is enabled."
|
||
-- NMS trap annotation
|
||
--#TYPE "Web-Thermograph Release Alarm 7"
|
||
--#SUMMARY "Release Alarm 7: %s"
|
||
--#ARGUMENTS {0}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 87
|
||
|
||
wtWebioAn2GraphAlert16 TRAP-TYPE
|
||
ENTERPRISE wtWebioAn2Graph
|
||
VARIABLES { wtWebioAn2GraphAlarmClearTrapText }
|
||
DESCRIPTION
|
||
"This SNMP trap is generated when Alarm 8 was cleared,
|
||
SNMP trap enable is set and
|
||
SNMP is enabled."
|
||
-- NMS trap annotation
|
||
--#TYPE "Web-Thermograph Release Alarm 8"
|
||
--#SUMMARY "Release Alarm 8: %s"
|
||
--#ARGUMENTS {0}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 88
|
||
|
||
wtWebioAn2GraphAlertDiag TRAP-TYPE
|
||
ENTERPRISE wtWebioAn2Graph
|
||
VARIABLES {
|
||
wtWebioAn2GraphDiagErrorIndex,
|
||
wtWebioAn2GraphDiagErrorMessage
|
||
}
|
||
DESCRIPTION
|
||
"This SNMP trap is generated when a diagnosis/error message was triggered,
|
||
SNMP trap enable is set and
|
||
SNMP is enabled."
|
||
-- NMS trap annotation
|
||
--#TYPE "Web-Thermograph Diagnose Error"
|
||
--#SUMMARY "Diagnose error index: %d, Message: %s."
|
||
--#ARGUMENTS {0,1}
|
||
--#SEVERITY MAJOR
|
||
--#TIMEINDEX 99
|
||
--#STATE DEGRADED
|
||
::= 110
|
||
|
||
END
|