-- IPT PDU SNMP configuration MIB
--
-- (c) 2013-2015 IPT Limited
--
-- Written by Designer Systems Ltd
-- V1.03.00
-- PEN 38218 supplied under license by Designer Systems Ltd
PDUSNMP DEFINITIONS ::= BEGIN
IMPORTS
enterprises, IpAddress, Gauge, TimeTicks FROM RFC1155-SMI
DisplayString FROM RFC1213-MIB
OBJECT-TYPE FROM RFC-1212
TRAP-TYPE FROM RFC-1215
NOTIFICATION-TYPE FROM SNMPv2-SMI
MODULE-IDENTITY FROM SNMPv2-SMI
Integer32, Unsigned32 FROM SNMPv2-SMI
OBJECT-GROUP FROM SNMPv2-CONF
NOTIFICATION-GROUP FROM SNMPv2-CONF
MODULE-COMPLIANCE FROM SNMPv2-CONF
DateAndTime FROM SNMPv2-TC
TEXTUAL-CONVENTION FROM SNMPv2-TC;
pdu-SNMP MODULE-IDENTITY
LAST-UPDATED "201511271712Z"
ORGANIZATION "IPT Limited"
CONTACT-INFO "sales@iptltd.com"
DESCRIPTION "IPT SNMP PDU MIB definition"
-- V1.03.00
REVISION "201511271712Z"
DESCRIPTION "Forth release (MIB validation changes to
support Open MNS)"
-- V1.02.00
REVISION "201511201712Z"
DESCRIPTION "Third release (Added socket All ON and
all OFF support)"
-- V1.01.00
REVISION "201509021712Z"
DESCRIPTION "Second release (Added trap clears and renamed
existing traps to set type)"
-- V1.00.00
REVISION "201309201712Z"
DESCRIPTION "First release"
::= { ipt-pdu-SNMP 1 }
ipt-pdu-SNMP OBJECT IDENTIFIER ::= { enterprises 38218 }
slave-SiteTotals OBJECT IDENTIFIER ::= { pdu-SNMP 1 }
slave-Server OBJECT IDENTIFIER ::= { pdu-SNMP 2 }
pdu-Configuration OBJECT IDENTIFIER ::= { pdu-SNMP 3 }
trap-Destinations OBJECT IDENTIFIER ::= { pdu-SNMP 4 }
pdu-Information OBJECT IDENTIFIER ::= { pdu-SNMP 5 }
pdu-Meters OBJECT IDENTIFIER ::= { pdu-SNMP 6 }
pdu-sockets OBJECT IDENTIFIER ::= { pdu-SNMP 7 }
pdu-Environmental OBJECT IDENTIFIER ::= { pdu-SNMP 8 }
pdu-Security OBJECT IDENTIFIER ::= { pdu-SNMP 9 }
pdu-Logs OBJECT IDENTIFIER ::= { pdu-SNMP 10 }
pdu-Traps OBJECT IDENTIFIER ::= { pdu-SNMP 11 }
pdu-TrapThresholds OBJECT IDENTIFIER ::= { pdu-Traps 1 }
slave-pdus OBJECT IDENTIFIER ::= { ipt-pdu-SNMP 2 }
slave-Information OBJECT IDENTIFIER ::= { slave-pdus 2 }
slave-Status OBJECT IDENTIFIER ::= { slave-pdus 3 }
slave-sockets OBJECT IDENTIFIER ::= { slave-pdus 4 }
slave-Environmental OBJECT IDENTIFIER ::= { slave-pdus 5 }
slave-Security OBJECT IDENTIFIER ::= { slave-pdus 6 }
slave-Traps OBJECT IDENTIFIER ::= { slave-pdus 7 }
slave-TrapSetNotifications OBJECT IDENTIFIER ::= { slave-Traps 1 }
slave-TrapClearNotifications OBJECT IDENTIFIER ::= { slave-Traps 2 }
slave-Global OBJECT IDENTIFIER ::= { ipt-pdu-SNMP 3 }
-- pdu-SNMP.slave-SiteTotals
slave-SiteTotalkWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Total Energy used by all slaves on site in kWh x10."
::= { slave-SiteTotals 1 }
slave-SiteTotalBtu OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Total Energy used by all slaves on site in Btu x10."
::= { slave-SiteTotals 2 }
slave-SiteTotalKgCO2 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Total Energy used by all slaves on site in KgCO2 x10."
::= { slave-SiteTotals 3 }
-- pdu-SNMP.slave-Server
slave-Nopdus OBJECT-TYPE
SYNTAX INTEGER (0..32)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Number of pdu's connected in SLAVE mode"
::= { slave-Server 1 }
slaves-Online OBJECT-TYPE
SYNTAX INTEGER (0..32)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Number of pdu's ONLINE in SLAVE mode."
::= { slave-Server 2 }
slave-ServerStatus OBJECT-TYPE
SYNTAX INTEGER {stopped(0),running(1),searching(2),getinfo(3),listening(4)}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Server status"
::= { slave-Server 3 }
-- pdu-SNMP.pdu-Configuration
pdu-ClientName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compatible - pdu Client name."
::= { pdu-Configuration 1 }
pdu-LocationName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compatible - pdu Location Name."
::= { pdu-Configuration 2 }
pdu-FirmwareVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - pdu firmware version."
::= { pdu-Configuration 3 }
pdu-KgCO2Conversion OBJECT-TYPE
SYNTAX INTEGER (1..1000)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compatible - KgCO2 conversion factor x1000 [544 = 0.544]"
::= { pdu-Configuration 4 }
pdu-MODBUSTimeout OBJECT-TYPE
SYNTAX INTEGER (500..5000)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compatible - MODBUS Timeout in mS."
::= { pdu-Configuration 5 }
pdu-MODBUSRetry OBJECT-TYPE
SYNTAX INTEGER (1..10)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compatible - MODBUS Retry value."
::= { pdu-Configuration 6 }
pdu-NotUsed1 OBJECT-TYPE
SYNTAX INTEGER (0)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Not used."
::= { pdu-Configuration 7 }
pdu-AlarmPeriod OBJECT-TYPE
SYNTAX INTEGER (1..240)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compatible - Alarm period check in minutes."
::= { pdu-Configuration 8 }
pdu-DHCPStatus OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compatible - DHCP Enable.Set to 1 to ENABLE or 0 to DISABLE DHCP support."
::= { pdu-Configuration 9 }
pdu-IPAddress OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compatible - pdu IP Address."
::= { pdu-Configuration 10 }
pdu-SubNetMask OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compatible - pdu Sub-net mask."
::= { pdu-Configuration 11 }
pdu-CabinetID OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION "pdu Cabinet ID."
::= { pdu-Configuration 12 }
pdu-socketPeriod OBJECT-TYPE
SYNTAX INTEGER (0..5000)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "pdu socket ON sequence period (mS) 0=OFF."
::= { pdu-Configuration 13 }
pdu-LockPeriod OBJECT-TYPE
SYNTAX INTEGER (1..240)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "pdu Lock activation period (S)."
::= { pdu-Configuration 14 }
pdu-RTC-Hour OBJECT-TYPE
SYNTAX INTEGER (0..23)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "pdu RTC Hour [24 hour clock]."
::= { pdu-Configuration 15 }
pdu-RTC-Minute OBJECT-TYPE
SYNTAX INTEGER (1..59)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "pdu RTC Minute."
::= { pdu-Configuration 16 }
pdu-RTC-Date OBJECT-TYPE
SYNTAX INTEGER (1..31)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "pdu RTC Date."
::= { pdu-Configuration 17 }
pdu-RTC-Month OBJECT-TYPE
SYNTAX INTEGER (1..12)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "pdu RTC Month."
::= { pdu-Configuration 18 }
pdu-RTC-Year OBJECT-TYPE
SYNTAX INTEGER (0..99)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "pdu RTC Year [tens only]."
::= { pdu-Configuration 19 }
-- pdu-SNMP.trap-Destinations
trapDestinationsTable OBJECT-TYPE
SYNTAX SEQUENCE OF TrapDestinationsEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION ""
::= { trap-Destinations 1 }
trapDestinationsEntry OBJECT-TYPE
SYNTAX TrapDestinationsEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Table of Trap notification destinations."
INDEX { trapDestinationsIndex }
::= { trapDestinationsTable 1 }
TrapDestinationsEntry ::= SEQUENCE {
trapDestinationsIndex
INTEGER,
trapDestinationsStatus
INTEGER,
trapDestinationsIP
IpAddress,
trapDestinationsCommunity
DisplayString
}
trapDestinationsIndex OBJECT-TYPE
SYNTAX INTEGER (0..1)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Trap destination index [0..1]."
::= { trapDestinationsEntry 1 }
trapDestinationsStatus OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Trap destination status. Set to 1 to ENABLE or 0 to DISABLE trap destination."
::= { trapDestinationsEntry 2 }
trapDestinationsIP OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Trap destination IP address. Set to the IP address of the destination SNMP manager."
::= { trapDestinationsEntry 3 }
trapDestinationsCommunity OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Trap destination SNMP community. Set to the community name to be used with the destination SNMP manager."
::= { trapDestinationsEntry 4 }
-- pdu-SNMP.pdu-Information
pdu-Firmware OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "pdu Firmware version."
::= { pdu-Information 1 }
pdu-Nosockets OBJECT-TYPE
SYNTAX INTEGER (0..32)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "pdu Number of sockets."
::= { pdu-Information 2 }
pdu-ProductName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "pdu Product name."
::= { pdu-Information 3 }
pdu-SerialNumber OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "pdu Serial number."
::= { pdu-Information 4 }
-- pdu-SNMP.pdu-Meters
pdu-meter1-VRMS OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "pdu Meter 1 RMS Voltage (VAC) x10."
::= { pdu-Meters 1 }
pdu-meter1-IRMS OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "pdu Meter 1 RMS Current (A) x100."
::= { pdu-Meters 2 }
pdu-meter1-KWH OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "pdu Meter 1 total energy consumption (kW/h) x10."
::= { pdu-Meters 3 }
pdu-meter1-KW OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "pdu Meter 1 Kilowatts (kW) x1000."
::= { pdu-Meters 4 }
pdu-meter1-TPMU OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "pdu Meter 1 Internal Temperature (C) x10."
::= { pdu-Meters 5 }
pdu-meter1-IPK OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "pdu Meter 1 Peak Current (A) x10."
::= { pdu-Meters 6 }
pdu-meter1-VPK OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "pdu Meter 1 Peak Voltage (V) x10."
::= { pdu-Meters 7 }
pdu-meter1-PF OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "pdu Meter 1 Power Factor x1000"
::= { pdu-Meters 8 }
pdu-meter1-Freq OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "pdu Meter 1 Frequency x10"
::= { pdu-Meters 9 }
pdu-meter2-VRMS OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "pdu Meter 2 RMS Voltage (VAC) x10."
::= { pdu-Meters 10 }
pdu-meter2-IRMS OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "pdu Meter 2 RMS Current (A) x100."
::= { pdu-Meters 11 }
pdu-meter2-KWH OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "pdu Meter 2 total energy consumption (kW/h) x10."
::= { pdu-Meters 12 }
pdu-meter2-KW OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "pdu Meter 2 Kilowatts (kW) x1000."
::= { pdu-Meters 13 }
pdu-meter2-TPMU OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "pdu Meter 2 Internal Temperature (C) x10."
::= { pdu-Meters 14 }
pdu-meter2-IPK OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "pdu Meter 2 Peak Current (A) x10."
::= { pdu-Meters 15 }
pdu-meter2-VPK OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "pdu Meter 2 Peak Voltage (V) x10."
::= { pdu-Meters 16 }
pdu-meter2-PF OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "pdu Meter 2 Power Factor x1000"
::= { pdu-Meters 17 }
pdu-meter2-Freq OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "pdu Meter 2 Frequency x10"
::= { pdu-Meters 18 }
pdu-meter3-VRMS OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "pdu Meter 3 RMS Voltage (VAC) x100."
::= { pdu-Meters 19 }
pdu-meter3-IRMS OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "pdu Meter 3 RMS Current (A) x10."
::= { pdu-Meters 20 }
pdu-meter3-KWH OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "pdu Meter 3 total energy consumption (kW/h) x10."
::= { pdu-Meters 21 }
pdu-meter3-KW OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "pdu Meter 3 Kilowatts (kW) x1000."
::= { pdu-Meters 22 }
pdu-meter3-TPMU OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "pdu Meter 3 Internal Temperature (C) x10."
::= { pdu-Meters 23 }
pdu-meter3-IPK OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "pdu Meter 3 Peak Current (A) x10."
::= { pdu-Meters 24 }
pdu-meter3-VPK OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "pdu Meter 3 Peak Voltage (V) x10."
::= { pdu-Meters 25 }
pdu-meter3-PF OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "pdu Meter 3 Power Factor x1000"
::= { pdu-Meters 26 }
pdu-meter3-Freq OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "pdu Meter 3 Frequency x10"
::= { pdu-Meters 27 }
-- pdu-SNMP.pdu-sockets
pdu-socketsTable OBJECT-TYPE
SYNTAX SEQUENCE OF Pdu-socketsEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION ""
::= { pdu-sockets 1 }
pdu-socketsEntry OBJECT-TYPE
SYNTAX Pdu-socketsEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Table of socket status parameters."
INDEX { socket-Index }
::= { pdu-socketsTable 1 }
Pdu-socketsEntry ::= SEQUENCE {
socket-Index
INTEGER,
socket-Number
INTEGER,
socket-Equipment
DisplayString,
socket-ONOFF
INTEGER,
socket-AMPS
INTEGER,
socket-KWH
Integer32,
socket-INFO
INTEGER
}
socket-Index OBJECT-TYPE
SYNTAX INTEGER (0..47)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "socket index"
::= { pdu-socketsEntry 1 }
socket-Number OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket number [Range 1 to 48]"
::= { pdu-socketsEntry 2 }
socket-Equipment OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION "socket equipment name."
::= { pdu-socketsEntry 3 }
socket-ONOFF OBJECT-TYPE
SYNTAX INTEGER {off(0),on(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "socket ON/OFF status [Set to 1 to switch ON, 0 to switch OFF]"
::= { pdu-socketsEntry 4 }
socket-AMPS OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket current (Amps) x10."
::= { pdu-socketsEntry 5 }
socket-KWH OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "socket Energy (kWh) x10."
::= { pdu-socketsEntry 6 }
socket-INFO OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket information (status, phase and picture)."
::= { pdu-socketsEntry 7 }
-- pdu-SNMP.pdu-Environmental
pdu-environmental-Temp1 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Environmental Temperature probe 1 (C) x100."
::= { pdu-Environmental 1 }
pdu-environmental-Temp1-Location OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental Temperature probe 1 location name."
::= { pdu-Environmental 2 }
pdu-environmental-Temp2 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Environmental Temperature probe 2 (C) x100."
::= { pdu-Environmental 3 }
pdu-environmental-Temp2-Location OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental Temperature probe 2 location name."
::= { pdu-Environmental 4 }
pdu-environmental-Temp3 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Environmental Temperature probe 3 (C) x100."
::= { pdu-Environmental 5 }
pdu-environmental-Temp3-Location OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental Temperature probe 3 location name."
::= { pdu-Environmental 6 }
pdu-environmental-Temp4 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Environmental Temperature probe 4 (C) x100."
::= { pdu-Environmental 7 }
pdu-environmental-Temp4-Location OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental Temperature probe 4 location name."
::= { pdu-Environmental 8 }
pdu-environmental-Temp5 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Environmental Temperature probe 5 (C) x100."
::= { pdu-Environmental 9 }
pdu-environmental-Temp5-Location OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental Temperature probe 5 location name."
::= { pdu-Environmental 10 }
pdu-environmental-Temp6 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Environmental Temperature probe 6 (C) x100."
::= { pdu-Environmental 11 }
pdu-environmental-Temp6-Location OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental Temperature probe 6 location name."
::= { pdu-Environmental 12 }
pdu-environmental-Temp7 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Environmental Temperature probe 7 (C) x100."
::= { pdu-Environmental 13 }
pdu-environmental-Temp7-Location OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental Temperature probe 7 location name."
::= { pdu-Environmental 14 }
pdu-environmental-Temp8 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Environmental Temperature probe 8 (C) x100."
::= { pdu-Environmental 15 }
pdu-environmental-Temp8-Location OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental Temperature probe 8 location name."
::= { pdu-Environmental 16 }
pdu-environmental-HumidityTemp OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Environmental Humidity probe Temperature (C) x100."
::= { pdu-Environmental 17 }
pdu-environmental-Humidity OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Environmental humidity probe (%) x100."
::= { pdu-Environmental 18 }
pdu-environmental-Contact1 OBJECT-TYPE
SYNTAX INTEGER {open(0),closed(1)}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Environmental contact input 1 status."
::= { pdu-Environmental 19 }
pdu-environmental-Contact1-Location OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental contact input 1 location name."
::= { pdu-Environmental 20 }
pdu-environmental-Contact2 OBJECT-TYPE
SYNTAX INTEGER {open(0),closed(1)}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Environmental contact input 2 status."
::= { pdu-Environmental 21 }
pdu-environmental-Contact2-Location OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental contact input 2 location name."
::= { pdu-Environmental 22 }
pdu-environmental-Contact3 OBJECT-TYPE
SYNTAX INTEGER {open(0),closed(1)}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Environmental contact input 3 status."
::= { pdu-Environmental 23 }
pdu-environmental-Contact3-Location OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental contact input 3 location name."
::= { pdu-Environmental 24 }
-- pdu-SNMP.pdu-Security
pdu-Security-Door OBJECT-TYPE
SYNTAX INTEGER {open(0),closed(1)}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Security door contact status."
::= { pdu-Security 1 }
pdu-Security-Lock OBJECT-TYPE
SYNTAX INTEGER {locked(0),unlocked(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Security lock status [Set to 1 to unlock]"
::= { pdu-Security 2 }
pdu-Security-Wild OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Security Card/PIN Wildcard status.
Set with 1 to enable or 0 to disable Wildcard feature."
::= { pdu-Security 3 }
pdu-Security-UnlockTimeDate OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Time and data of last unlock."
::= { pdu-Security 4 }
pdu-SecurityTable OBJECT-TYPE
SYNTAX SEQUENCE OF Pdu-SecurityEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION ""
::= { pdu-Security 5 }
pdu-SecurityEntry OBJECT-TYPE
SYNTAX Pdu-SecurityEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Table of pdu- Card/PIN codes."
INDEX { pdu-Security-Index }
::= { pdu-SecurityTable 1 }
Pdu-SecurityEntry ::= SEQUENCE {
pdu-Security-Index
INTEGER,
pdu-Security-Code
Integer32
}
pdu-Security-Index OBJECT-TYPE
SYNTAX INTEGER (1..32)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Security Card/PIN code index."
::= { pdu-SecurityEntry 1 }
pdu-Security-Code OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Security Card/PIN number."
::= { pdu-SecurityEntry 2 }
-- pdu-SNMP.pdu-Logs
pdu-Logs-Number OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Log file number of log lines stored."
::= { pdu-Logs 1 }
pdu-Logs-Index OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Log file line index pointer.
Set to line to be read."
::= { pdu-Logs 2 }
pdu-Logs-Data OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Log file log line data."
::= { pdu-Logs 3 }
pdu-Logs-Clear OBJECT-TYPE
SYNTAX INTEGER {reset(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Log file clear.
Set with 1 to clear log file."
::= { pdu-Logs 4 }
-- pdu-SNMP.pdu-Traps.pdu-TrapThresholds
meter1-VRMSLowAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 1 Voltage LOW alarm disabled/enabled."
::= { pdu-TrapThresholds 1 }
meter1-VRMSLow OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "eter 1 Voltage LOW trap threshold x10."
::= { pdu-TrapThresholds 2 }
meter1-VRMSHighAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 1 Voltage HIGH alarm disabled/enabled."
::= { pdu-TrapThresholds 3 }
meter1-VRMSHigh OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 1 Voltage HIGH trap threshold x10."
::= { pdu-TrapThresholds 4 }
meter1-IRMSLowAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 1 Current LOW alarm disabled/enabled."
::= { pdu-TrapThresholds 5 }
meter1-IRMSLow OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 1 Current LOW trap threshold x10."
::= { pdu-TrapThresholds 6 }
meter1-IRMSHighAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 1 Current HIGH alarm disabled/enabled."
::= { pdu-TrapThresholds 7 }
meter1-IRMSHigh OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 1 Current HIGH trap threshold x10."
::= { pdu-TrapThresholds 8 }
meter1-KWSLowAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 1 Kilowatts LOW alarm disabled/enabled."
::= { pdu-TrapThresholds 9 }
meter1-KWSLow OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 1 Kilowatts LOW trap threshold x10."
::= { pdu-TrapThresholds 10 }
meter1-KWSHighAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 1 Kilowatts HIGH alarm disabled/enabled."
::= { pdu-TrapThresholds 11 }
meter1-KWSHigh OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 1 Kilowatts HIGH trap threshold x10."
::= { pdu-TrapThresholds 12 }
meter1-TempLowAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 1 Internal temperature LOW alarm disabled/enabled."
::= { pdu-TrapThresholds 13 }
meter1-TempLow OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 1 Internal temperature LOW trap threshold x10."
::= { pdu-TrapThresholds 14 }
meter1-TempHighAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 1 Internal temperature HIGH alarm disabled/enabled."
::= { pdu-TrapThresholds 15 }
meter1-TempHigh OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 1 Internal temperature HIGH trap threshold x10."
::= { pdu-TrapThresholds 16 }
meter1-PFLowAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 1 Power factor LOW alarm disabled/enabled."
::= { pdu-TrapThresholds 17 }
meter1-PFLow OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 1 Power factor LOW trap threshold x10."
::= { pdu-TrapThresholds 18 }
meter1-PFHighAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 1 Power factor HIGH alarm disabled/enabled."
::= { pdu-TrapThresholds 19 }
meter1-PFHigh OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 1 Power factor HIGH trap threshold x10."
::= { pdu-TrapThresholds 20 }
meter1-FreqLowAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 1 Frequency LOW alarm disabled/enabled."
::= { pdu-TrapThresholds 21 }
meter1-FreqLow OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 1 Frequency LOW trap threshold x10."
::= { pdu-TrapThresholds 22 }
meter1-FreqHighAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 1 Frequency HIGH alarm disabled/enabled."
::= { pdu-TrapThresholds 23 }
meter1-FreqHigh OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 1 Frequency HIGH trap threshold x10."
::= { pdu-TrapThresholds 24 }
meter2-VRMSLowAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 2 Voltage LOW alarm disabled/enabled."
::= { pdu-TrapThresholds 25 }
meter2-VRMSLow OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "eter 1 Voltage LOW trap threshold x10."
::= { pdu-TrapThresholds 26 }
meter2-VRMSHighAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 2 Voltage HIGH alarm disabled/enabled."
::= { pdu-TrapThresholds 27 }
meter2-VRMSHigh OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 2 Voltage HIGH trap threshold x10."
::= { pdu-TrapThresholds 28 }
meter2-IRMSLowAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 2 Current LOW alarm disabled/enabled."
::= { pdu-TrapThresholds 29 }
meter2-IRMSLow OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 2 Current LOW trap threshold x10."
::= { pdu-TrapThresholds 30 }
meter2-IRMSHighAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 2 Current HIGH alarm disabled/enabled."
::= { pdu-TrapThresholds 31 }
meter2-IRMSHigh OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 2 Current HIGH trap threshold x10."
::= { pdu-TrapThresholds 32 }
meter2-KWSLowAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 2 Kilowatts LOW alarm disabled/enabled."
::= { pdu-TrapThresholds 33 }
meter2-KWSLow OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 2 Kilowatts LOW trap threshold x10."
::= { pdu-TrapThresholds 34 }
meter2-KWSHighAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 2 Kilowatts HIGH alarm disabled/enabled."
::= { pdu-TrapThresholds 35 }
meter2-KWSHigh OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 2 Kilowatts HIGH trap threshold x10."
::= { pdu-TrapThresholds 36 }
meter2-TempLowAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 2 Internal temperature LOW alarm disabled/enabled."
::= { pdu-TrapThresholds 37 }
meter2-TempLow OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 2 Internal temperature LOW trap threshold x10."
::= { pdu-TrapThresholds 38 }
meter2-TempHighAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 2 Internal temperature HIGH alarm disabled/enabled."
::= { pdu-TrapThresholds 39 }
meter2-TempHigh OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 2 Internal temperature HIGH trap threshold x10."
::= { pdu-TrapThresholds 40 }
meter2-PFLowAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 2 Power factor LOW alarm disabled/enabled."
::= { pdu-TrapThresholds 41 }
meter2-PFLow OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 2 Power factor LOW trap threshold x10."
::= { pdu-TrapThresholds 42 }
meter2-PFHighAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 2 Power factor HIGH alarm disabled/enabled."
::= { pdu-TrapThresholds 43 }
meter2-PFHigh OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 2 Power factor HIGH trap threshold x10."
::= { pdu-TrapThresholds 44 }
meter2-FreqLowAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 2 Frequency LOW alarm disabled/enabled."
::= { pdu-TrapThresholds 45 }
meter2-FreqLow OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 2 Frequency LOW trap threshold x10."
::= { pdu-TrapThresholds 46 }
meter2-FreqHighAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 2 Frequency HIGH alarm disabled/enabled."
::= { pdu-TrapThresholds 47 }
meter2-FreqHigh OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 2 Frequency HIGH trap threshold x10."
::= { pdu-TrapThresholds 48 }
meter3-VRMSLowAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 3 Voltage LOW alarm disabled/enabled."
::= { pdu-TrapThresholds 49 }
meter3-VRMSLow OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "eter 1 Voltage LOW trap threshold x10."
::= { pdu-TrapThresholds 50 }
meter3-VRMSHighAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 3 Voltage HIGH alarm disabled/enabled."
::= { pdu-TrapThresholds 51 }
meter3-VRMSHigh OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 3 Voltage HIGH trap threshold x10."
::= { pdu-TrapThresholds 52 }
meter3-IRMSLowAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 3 Current LOW alarm disabled/enabled."
::= { pdu-TrapThresholds 53 }
meter3-IRMSLow OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 3 Current LOW trap threshold x10."
::= { pdu-TrapThresholds 54 }
meter3-IRMSHighAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 3 Current HIGH alarm disabled/enabled."
::= { pdu-TrapThresholds 55 }
meter3-IRMSHigh OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 3 Current HIGH trap threshold x10."
::= { pdu-TrapThresholds 56 }
meter3-KWSLowAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 3 Kilowatts LOW alarm disabled/enabled."
::= { pdu-TrapThresholds 57 }
meter3-KWSLow OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 3 Kilowatts LOW trap threshold x10."
::= { pdu-TrapThresholds 58 }
meter3-KWSHighAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 3 Kilowatts HIGH alarm disabled/enabled."
::= { pdu-TrapThresholds 59 }
meter3-KWSHigh OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 3 Kilowatts HIGH trap threshold x10."
::= { pdu-TrapThresholds 60 }
meter3-TempLowAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 3 Internal temperature LOW alarm disabled/enabled."
::= { pdu-TrapThresholds 61 }
meter3-TempLow OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 3 Internal temperature LOW trap threshold x10."
::= { pdu-TrapThresholds 62 }
meter3-TempHighAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 3 Internal temperature HIGH alarm disabled/enabled."
::= { pdu-TrapThresholds 63 }
meter3-TempHigh OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 3 Internal temperature HIGH trap threshold x10."
::= { pdu-TrapThresholds 64 }
meter3-PFLowAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 3 Power factor LOW alarm disabled/enabled."
::= { pdu-TrapThresholds 65 }
meter3-PFLow OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 3 Power factor LOW trap threshold x10."
::= { pdu-TrapThresholds 66 }
meter3-PFHighAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 3 Power factor HIGH alarm disabled/enabled."
::= { pdu-TrapThresholds 67 }
meter3-PFHigh OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 3 Power factor HIGH trap threshold x10."
::= { pdu-TrapThresholds 68 }
meter3-FreqLowAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 3 Frequency LOW alarm disabled/enabled."
::= { pdu-TrapThresholds 69 }
meter3-FreqLow OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 3 Frequency LOW trap threshold x10."
::= { pdu-TrapThresholds 70 }
meter3-FreqHighAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 3 Frequency HIGH alarm disabled/enabled."
::= { pdu-TrapThresholds 71 }
meter3-FreqHigh OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Meter 3 Frequency HIGH trap threshold x10."
::= { pdu-TrapThresholds 72 }
socket-ThresholdsTable OBJECT-TYPE
SYNTAX SEQUENCE OF Socket-ThresholdsEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION ""
::= { pdu-TrapThresholds 73 }
socket-ThresholdsEntry OBJECT-TYPE
SYNTAX Socket-ThresholdsEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Table of socket trap notification thresholds."
INDEX { socket-ThresholdsNumber }
::= { socket-ThresholdsTable 1 }
Socket-ThresholdsEntry ::= SEQUENCE {
socket-ThresholdsNumber
INTEGER,
socket-AMPSLowAlarm
INTEGER,
socket-AMPSLow
INTEGER,
socket-AMPSHighAlarm
INTEGER,
socket-AMPSHigh
INTEGER
}
socket-ThresholdsNumber OBJECT-TYPE
SYNTAX INTEGER (1..48)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Trap threshold socket- number [1..48]."
::= { socket-ThresholdsEntry 1 }
socket-AMPSLowAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "socket Current LOW alarm disabled/enabled."
::= { socket-ThresholdsEntry 2 }
socket-AMPSLow OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "socket Current LOW trap threshold x10."
::= { socket-ThresholdsEntry 3 }
socket-AMPSHighAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "socket Current HIGH alarm disabled/enabled."
::= { socket-ThresholdsEntry 4 }
socket-AMPSHigh OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "socket Current HIGH trap threshold x10."
::= { socket-ThresholdsEntry 5 }
environmental-Temp1LowAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental temperature probe 1 LOW alarm disabled/enabled."
::= { pdu-TrapThresholds 74 }
environmental-Temp1Low OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental temperature probe 1 LOW trap threshold x10."
::= { pdu-TrapThresholds 75 }
environmental-Temp1HighAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental temperature probe 1 HIGH alarm disabled/enabled."
::= { pdu-TrapThresholds 76 }
environmental-Temp1High OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental temperature probe 1 HIGH trap threshold x10."
::= { pdu-TrapThresholds 77 }
environmental-Temp2LowAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental temperature probe 2 LOW alarm disabled/enabled."
::= { pdu-TrapThresholds 78 }
environmental-Temp2Low OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental temperature probe 2 LOW trap threshold x10."
::= { pdu-TrapThresholds 79 }
environmental-Temp2HighAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental temperature probe 2 HIGH alarm disabled/enabled."
::= { pdu-TrapThresholds 80 }
environmental-Temp2High OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental temperature probe 2 HIGH trap threshold x10."
::= { pdu-TrapThresholds 81 }
environmental-Temp3LowAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental temperature probe 3 LOW alarm disabled/enabled."
::= { pdu-TrapThresholds 82 }
environmental-Temp3Low OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental temperature probe 3 LOW trap threshold x10."
::= { pdu-TrapThresholds 83 }
environmental-Temp3HighAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental temperature probe 3 HIGH alarm disabled/enabled."
::= { pdu-TrapThresholds 84 }
environmental-Temp3High OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental temperature probe 3 HIGH trap threshold x10."
::= { pdu-TrapThresholds 85 }
environmental-Temp4LowAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental temperature probe 4 LOW alarm disabled/enabled."
::= { pdu-TrapThresholds 86 }
environmental-Temp4Low OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental temperature probe 4 LOW trap threshold x10."
::= { pdu-TrapThresholds 87 }
environmental-Temp4HighAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental temperature probe 4 HIGH alarm disabled/enabled."
::= { pdu-TrapThresholds 88 }
environmental-Temp4High OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental temperature probe 4 HIGH trap threshold x10."
::= { pdu-TrapThresholds 89 }
environmental-Temp5LowAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental temperature probe 5 LOW alarm disabled/enabled."
::= { pdu-TrapThresholds 90 }
environmental-Temp5Low OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental temperature probe 5 LOW trap threshold x10."
::= { pdu-TrapThresholds 91 }
environmental-Temp5HighAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental temperature probe 5 HIGH alarm disabled/enabled."
::= { pdu-TrapThresholds 92 }
environmental-Temp5High OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental temperature probe 5 HIGH trap threshold x10."
::= { pdu-TrapThresholds 93 }
environmental-Temp6LowAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental temperature probe 6 LOW alarm disabled/enabled."
::= { pdu-TrapThresholds 94 }
environmental-Temp6Low OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental temperature probe 6 LOW trap threshold x10."
::= { pdu-TrapThresholds 95 }
environmental-Temp6HighAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental temperature probe 6 HIGH alarm disabled/enabled."
::= { pdu-TrapThresholds 96 }
environmental-Temp6High OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental temperature probe 6 HIGH trap threshold x10."
::= { pdu-TrapThresholds 97 }
environmental-Temp7LowAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental temperature probe 7 LOW alarm disabled/enabled."
::= { pdu-TrapThresholds 98 }
environmental-Temp7Low OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental temperature probe 7 LOW trap threshold x10."
::= { pdu-TrapThresholds 99 }
environmental-Temp7HighAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental temperature probe 7 HIGH alarm disabled/enabled."
::= { pdu-TrapThresholds 100 }
environmental-Temp7High OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental temperature probe 7 HIGH trap threshold x10."
::= { pdu-TrapThresholds 101 }
environmental-Temp8LowAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental temperature probe 8 LOW alarm disabled/enabled."
::= { pdu-TrapThresholds 102 }
environmental-Temp8Low OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental temperature probe 8 LOW trap threshold x10."
::= { pdu-TrapThresholds 103 }
environmental-Temp8HighAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental temperature probe 8 HIGH alarm disabled/enabled."
::= { pdu-TrapThresholds 104 }
environmental-Temp8High OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental temperature probe 8 HIGH trap threshold x10."
::= { pdu-TrapThresholds 105 }
environmental-HumidityTempLowAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental humidity probe temperature LOW alarm disabled/enabled."
::= { pdu-TrapThresholds 106 }
environmental-HumidityTempLow OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental humidity probe temperature LOW trap threshold x10."
::= { pdu-TrapThresholds 107 }
environmental-HumidityTempHighAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental humidity probe temperature HIGH alarm disabled/enabled."
::= { pdu-TrapThresholds 108 }
environmental-HumidityTempHigh OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental humidity probe temperature HIGH trap threshold x10."
::= { pdu-TrapThresholds 109 }
environmental-HumidityLowAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental humidity probe LOW alarm disabled/enabled."
::= { pdu-TrapThresholds 110 }
environmental-HumidityLow OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental humidity probe LOW trap threshold x10."
::= { pdu-TrapThresholds 111 }
environmental-HumidityHighAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental humidity probe HIGH alarm disabled/enabled."
::= { pdu-TrapThresholds 112 }
environmental-HumidityHigh OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental humidity probe HIGH trap threshold x10."
::= { pdu-TrapThresholds 113 }
environmental-Contact1OpenedAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental Contact 1 OPENED alarm disabled/enabled."
::= { pdu-TrapThresholds 114 }
environmental-Contact1ClosedAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental Contact 1 CLOSED alarm disabled/enabled."
::= { pdu-TrapThresholds 115 }
environmental-Contact2OpenedAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental Contact 2 OPENED alarm disabled/enabled."
::= { pdu-TrapThresholds 116 }
environmental-Contact2ClosedAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental Contact 2 CLOSED alarm disabled/enabled."
::= { pdu-TrapThresholds 117 }
environmental-Contact3OpenedAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental Contact 3 OPENED alarm disabled/enabled."
::= { pdu-TrapThresholds 118 }
environmental-Contact3ClosedAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Environmental Contact 3 CLOSED alarm disabled/enabled."
::= { pdu-TrapThresholds 119 }
security-DoorOpenedAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Security Door OPENED alarm disabled/enabled."
::= { pdu-TrapThresholds 120 }
security-DoorClosedAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Security Door CLOSED alarm disabled/enabled."
::= { pdu-TrapThresholds 121 }
security-LockUnlockedAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Security Lock UNLOCKED alarm disabled/enabled."
::= { pdu-TrapThresholds 122 }
security-LockLockedAlarm OBJECT-TYPE
SYNTAX INTEGER {disabled(0),enabled(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Security Lock LOCKED alarm disabled/enabled."
::= { pdu-TrapThresholds 123 }
-- slave-pdu
slave-slaveSelected OBJECT-TYPE
SYNTAX INTEGER (1..32)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compatible - Currently selected slave pdu.
Set to number between 1 and slave-Nopdus"
::= { slave-pdus 1 }
-- pdu.pduInfo
slave-pduName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - slave pdu Name."
::= { slave-Information 1 }
slave-pduStatus OBJECT-TYPE
SYNTAX INTEGER {offline(0),online(1),disabled(2)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compatible - slave pdu ONLINE / OFFLINE or DISABLED status."
::= { slave-Information 2 }
slave-pduAddress OBJECT-TYPE
SYNTAX INTEGER (1..32)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - slave pdu MODBUS Address."
::= { slave-Information 3 }
slave-pduFirmware OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - slave pdu Firmware version."
::= { slave-Information 4 }
slave-Info-NotUsed2 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Not used."
::= { slave-Information 5 }
slave-pduNosockets OBJECT-TYPE
SYNTAX INTEGER (0..48)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - slave pdu Number of sockets."
::= { slave-Information 6 }
slave-Info-NotUsed3 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Not used."
::= { slave-Information 7 }
slave-Info-NotUsed4 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Not used."
::= { slave-Information 8 }
slave-Info-pduReset OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compatible - slave pdu Reset."
::= { slave-Information 9 }
slave-Info-pdukWhReset OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compatible - slave pdu Reset energy."
::= { slave-Information 10 }
-- pdu.slave-Status
slave-meter1-VRMS OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compatible - slave Meter 1 RMS Voltage (VAC) x10."
::= { slave-Status 1 }
slave-meter1-IRMS OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - slave Meter 1 RMS Current (A) x10."
::= { slave-Status 2 }
slave-meter1-KWH OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - slave Meter 1 total energy consumption (kW/h) x10."
::= { slave-Status 3 }
slave-meter1-KW OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - slave Meter 1 Kilowatts (kW) x1000."
::= { slave-Status 4 }
slave-meter1-TPMU OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - slave Meter 1 Internal Temperature (C) x10."
::= { slave-Status 5 }
slave-Status-NotUsed1 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Not used."
::= { slave-Status 6 }
slave-Status-NotUsed2 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Not used."
::= { slave-Status 7 }
slave-meter1-IPK OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - slave Meter 1 Peak Current (A) x10."
::= { slave-Status 8 }
slave-meter1-VPK OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - slave Meter 1 Peak Voltage (V) x10."
::= { slave-Status 9 }
slave-meter1-PF OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - slave Meter 1 Power Factor x1000"
::= { slave-Status 10 }
slave-Status-NotUsed3 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Not used."
::= { slave-Status 11 }
slave-Status-NotUsed4 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Not used."
::= { slave-Status 12 }
slave-Status-NotUsed5 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Not used."
::= { slave-Status 13 }
slave-meter1-Freq OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - slave Meter 1 Frequency x10"
::= { slave-Status 14 }
slave-meter2-VRMS OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - slave Meter 2 RMS Voltage (VAC) x10."
::= { slave-Status 15 }
slave-meter2-IRMS OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - slave Meter 2 RMS Current (A) x10."
::= { slave-Status 16 }
slave-meter2-KWH OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - slave Meter 2 total energy consumption (kW/h) x10."
::= { slave-Status 17 }
slave-meter2-KW OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - slave Meter 2 Kilowatts (kW) x1000."
::= { slave-Status 18 }
slave-meter2-TPMU OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - slave Meter 2 Internal Temperature (C) x10."
::= { slave-Status 19 }
slave-meter2-IPK OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - slave Meter 2 Peak Current (A) x10."
::= { slave-Status 20 }
slave-meter2-VPK OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - slave Meter 2 Peak Voltage (V) x10."
::= { slave-Status 21 }
slave-meter2-PF OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - slave Meter 2 Power Factor x1000"
::= { slave-Status 22 }
slave-meter2-Freq OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - slave Meter 2 Frequency x10"
::= { slave-Status 23 }
slave-meter3-VRMS OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - slave Meter 3 RMS Voltage (VAC) x10."
::= { slave-Status 24 }
slave-meter3-IRMS OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - slave Meter 3 RMS Current (A) x10."
::= { slave-Status 25 }
slave-meter3-KWH OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - slave Meter 3 total energy consumption (kW/h) x10."
::= { slave-Status 26 }
slave-meter3-KW OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - slave Meter 3 Kilowatts (kW) x1000."
::= { slave-Status 27 }
slave-meter3-TPMU OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - slave Meter 3 Internal Temperature (C) x10."
::= { slave-Status 28 }
slave-meter3-IPK OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - slave Meter 3 Peak Current (A) x10."
::= { slave-Status 29 }
slave-meter3-VPK OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - slave Meter 3 Peak Voltage (V) x10."
::= { slave-Status 30 }
slave-meter3-PF OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - slave Meter 3 Power Factor x1000"
::= { slave-Status 31 }
slave-meter3-Freq OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - slave Meter 3 Frequency x10"
::= { slave-Status 32 }
-- pdu.slave-sockets
slave-socketsTable OBJECT-TYPE
SYNTAX SEQUENCE OF Slave-socketsEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION ""
::= { slave-sockets 1 }
slave-socketsEntry OBJECT-TYPE
SYNTAX Slave-socketsEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Table of socket status parameters."
INDEX { slave-socket-Index }
::= { slave-socketsTable 1 }
Slave-socketsEntry ::= SEQUENCE {
slave-socket-Index
INTEGER,
slave-socket-Number
INTEGER,
slave-socket-NotUsed1
DisplayString,
slave-socket-ONOFF
INTEGER,
slave-socket-AMPS
INTEGER,
slave-socket-KWH
Integer32
}
slave-socket-Index OBJECT-TYPE
SYNTAX INTEGER (1..48)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "socket index"
::= { slave-socketsEntry 1 }
slave-socket-Number OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "socket number [Range 1 to 48]"
::= { slave-socketsEntry 2 }
slave-socket-NotUsed1 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Not used."
::= { slave-socketsEntry 3 }
slave-socket-ONOFF OBJECT-TYPE
SYNTAX INTEGER {off(0),on(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "socket ON/OFF status [Compatible - Write ignored]"
::= { slave-socketsEntry 4 }
slave-socket-AMPS OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket current (Amps) x10."
::= { slave-socketsEntry 5 }
slave-socket-KWH OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "socket Energy (kWh) x10."
::= { slave-socketsEntry 6 }
socket-Selected OBJECT-TYPE
SYNTAX INTEGER (1..48)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compatible - Currently selected socket.
Set to number between 1 and slave-pduNosockets"
::= { slave-sockets 2 }
socket-AllON OBJECT-TYPE
SYNTAX INTEGER (1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Set all sockets in system to ON."
::= { slave-sockets 3 }
socket-AllOFF OBJECT-TYPE
SYNTAX INTEGER (1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Set all sockets in system to OFF."
::= { slave-sockets 4 }
-- pdu.slave-Environmental
slave-environmental-Temp1 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Environmental Temperature probe 1 (C) x100."
::= { slave-Environmental 1 }
slave-environmental-Temp2 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Environmental Temperature probe 2 (C) x100."
::= { slave-Environmental 2 }
slave-environmental-Temp3 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Environmental Temperature probe 3 (C) x100."
::= { slave-Environmental 3 }
slave-environmental-Temp4 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Environmental Temperature probe 4 (C) x100."
::= { slave-Environmental 4 }
slave-environmental-Temp5 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Environmental Temperature probe 5 (C) x100."
::= { slave-Environmental 5 }
slave-environmental-Temp6 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Environmental Temperature probe 6 (C) x100."
::= { slave-Environmental 6 }
slave-environmental-Temp7 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Environmental Temperature probe 7 (C) x100."
::= { slave-Environmental 7 }
slave-environmental-Temp8 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Environmental Temperature probe 8 (C) x100."
::= { slave-Environmental 8 }
slave-environmental-HumidityTemp OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Environmental Humidity probe Temperature (C) x100."
::= { slave-Environmental 9 }
slave-environmental-Humidity OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Environmental humidity probe (%) x100."
::= { slave-Environmental 10 }
slave-environmental-Contact1 OBJECT-TYPE
SYNTAX INTEGER {open(0),closed(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compatible - Environmental contact input 1 status."
::= { slave-Environmental 11 }
slave-environmental-Contact2 OBJECT-TYPE
SYNTAX INTEGER {open(0),closed(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compatible - Environmental contact input 2 status."
::= { slave-Environmental 12 }
slave-environmental-Contact3 OBJECT-TYPE
SYNTAX INTEGER {open(0),closed(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compatible - Environmental contact input 3 status."
::= { slave-Environmental 13 }
-- pdu.slave-Security
slave-Security-Door OBJECT-TYPE
SYNTAX INTEGER {open(0),closed(1)}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Security door contact status."
::= { slave-Security 1 }
slave-Security-Lock OBJECT-TYPE
SYNTAX INTEGER {locked(0),unlocked(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compatible - Security lock status.
Set with any data to force unlock."
::= { slave-Security 2 }
-- slave-Traps.slave-TrapSetNotifications
slave-Set-meter1-VRMSLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-VRMS }
STATUS current
DESCRIPTION "Meter 1 Voltage LOW trap SET notification"
::= { slave-TrapSetNotifications 1 }
slave-Set-meter1-VRMSHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-VRMS }
STATUS current
DESCRIPTION "Meter 1 Voltage HIGH trap SET notification"
::= { slave-TrapSetNotifications 2 }
slave-Set-meter1-IRMSLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-IRMS }
STATUS current
DESCRIPTION "Meter 1 Amps LOW trap SET notification"
::= { slave-TrapSetNotifications 3 }
slave-Set-meter1-IRMSHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-IRMS }
STATUS current
DESCRIPTION "Meter 1 Amps HIGH trap SET notification"
::= { slave-TrapSetNotifications 4 }
slave-Set-meter1-KWSLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-KW }
STATUS current
DESCRIPTION "Meter 1 Kilowatts LOW trap SET notification"
::= { slave-TrapSetNotifications 5 }
slave-Set-meter1-KWSHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-KW }
STATUS current
DESCRIPTION "Meter 1 Kilowatts HIGH trap SET notification"
::= { slave-TrapSetNotifications 6 }
slave-Set-meter1-TempLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-TPMU }
STATUS current
DESCRIPTION "Meter 1 Temperature LOW trap SET notification"
::= { slave-TrapSetNotifications 7 }
slave-Set-meter1-TempHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-TPMU }
STATUS current
DESCRIPTION "Meter 1 Temperature HIGH trap SET notification"
::= { slave-TrapSetNotifications 8 }
slave-Set-socket-AMPSLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, socket-Number }
STATUS current
DESCRIPTION "socket Amps LOW trap SET notification"
::= { slave-TrapSetNotifications 9 }
slave-Set-socket-AMPSHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, socket-Number }
STATUS current
DESCRIPTION "socket Amps HIGH trap SET notification"
::= { slave-TrapSetNotifications 10 }
slave-Set-environmental-Temp1Low NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp1 }
STATUS current
DESCRIPTION "Environmental Temperature probe 1 LOW trap SET notification"
::= { slave-TrapSetNotifications 11 }
slave-Set-environmental-Temp1High NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp1 }
STATUS current
DESCRIPTION "Environmental Temperature probe 1 HIGH trap SET notification"
::= { slave-TrapSetNotifications 12 }
slave-Set-environmental-Temp2Low NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp2 }
STATUS current
DESCRIPTION "Environmental Temperature probe 2 LOW trap SET notification"
::= { slave-TrapSetNotifications 13 }
slave-Set-environmental-Temp2High NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp2 }
STATUS current
DESCRIPTION "Environmental Temperature probe 2 HIGH trap SET notification"
::= { slave-TrapSetNotifications 14 }
slave-Set-environmental-Temp3Low NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp3 }
STATUS current
DESCRIPTION "Environmental Temperature probe 3 LOW trap SET notification"
::= { slave-TrapSetNotifications 15 }
slave-Set-environmental-Temp3High NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp3 }
STATUS current
DESCRIPTION "Environmental Temperature probe 3 HIGH trap SET notification"
::= { slave-TrapSetNotifications 16 }
slave-Set-environmental-Temp4Low NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp4 }
STATUS current
DESCRIPTION "Environmental Temperature probe 4 LOW trap SET notification"
::= { slave-TrapSetNotifications 17 }
slave-Set-environmental-Temp4High NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp4 }
STATUS current
DESCRIPTION "Environmental Temperature probe 4 HIGH trap SET notification"
::= { slave-TrapSetNotifications 18 }
slave-Set-environmental-Temp5Low NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp5 }
STATUS current
DESCRIPTION "Environmental Temperature probe 5 LOW trap SET notification"
::= { slave-TrapSetNotifications 19 }
slave-Set-environmental-Temp5High NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp5 }
STATUS current
DESCRIPTION "Environmental Temperature probe 5 HIGH trap SET notification"
::= { slave-TrapSetNotifications 20 }
slave-Set-environmental-Temp6Low NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp6 }
STATUS current
DESCRIPTION "Environmental Temperature probe 6 LOW trap SET notification"
::= { slave-TrapSetNotifications 21 }
slave-Set-environmental-Temp6High NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp6 }
STATUS current
DESCRIPTION "Environmental Temperature probe 6 HIGH trap SET notification"
::= { slave-TrapSetNotifications 22 }
slave-Set-environmental-Temp7Low NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp7 }
STATUS current
DESCRIPTION "Environmental Temperature probe 7 LOW trap SET notification"
::= { slave-TrapSetNotifications 23 }
slave-Set-environmental-Temp7High NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp7 }
STATUS current
DESCRIPTION "Environmental Temperature probe 7 HIGH trap SET notification"
::= { slave-TrapSetNotifications 24 }
slave-Set-environmental-Temp8Low NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp8 }
STATUS current
DESCRIPTION "Environmental Temperature probe 8 LOW trap SET notification"
::= { slave-TrapSetNotifications 25 }
slave-Set-environmental-Temp8High NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp8 }
STATUS current
DESCRIPTION "Environmental Temperature probe 8 HIGH trap SET notification"
::= { slave-TrapSetNotifications 26 }
slave-Set-environmental-HumidityTempLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-HumidityTemp }
STATUS current
DESCRIPTION "Environmental Humidity probe Temperature LOW trap SET notification"
::= { slave-TrapSetNotifications 27 }
slave-Set-environmental-HumidityTempHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-HumidityTemp }
STATUS current
DESCRIPTION "Environmental Humidity probe Temperature HIGH trap SET notification"
::= { slave-TrapSetNotifications 28 }
slave-Set-environmental-HumidityLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Humidity }
STATUS current
DESCRIPTION "Environmental Humidity probe LOW trap SET notification"
::= { slave-TrapSetNotifications 29 }
slave-Set-environmental-HumidityHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Humidity }
STATUS current
DESCRIPTION "Environmental Humidity probe HIGH trap SET notification"
::= { slave-TrapSetNotifications 30 }
slave-Set-environmental-Contact1Open NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Contact1 }
STATUS current
DESCRIPTION "Environmental Contact 1 OPEN trap SET notification"
::= { slave-TrapSetNotifications 31 }
slave-Set-environmental-Contact1Closed NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Contact1 }
STATUS current
DESCRIPTION "Environmental Contact 1 CLOSED trap SET notification"
::= { slave-TrapSetNotifications 32 }
slave-Set-environmental-Contact2Open NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Contact2 }
STATUS current
DESCRIPTION "Environmental Contact 2 OPEN trap SET notification"
::= { slave-TrapSetNotifications 33 }
slave-Set-environmental-Contact2Closed NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Contact2 }
STATUS current
DESCRIPTION "Environmental Contact 2 CLOSED trap SET notification"
::= { slave-TrapSetNotifications 34 }
slave-Set-environmental-Contact3Open NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Contact3 }
STATUS current
DESCRIPTION "Environmental Contact 3 OPEN trap SET notification"
::= { slave-TrapSetNotifications 35 }
slave-Set-environmental-Contact3Closed NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Contact3 }
STATUS current
DESCRIPTION "Environmental Contact 3 CLOSED trap SET notification"
::= { slave-TrapSetNotifications 36 }
slave-Set-Security-DoorOpen NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-Security-Door }
STATUS current
DESCRIPTION "Environmental Door OPEN trap SET notification"
::= { slave-TrapSetNotifications 37 }
slave-Set-Security-DoorClosed NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-Security-Door }
STATUS current
DESCRIPTION "Environmental Door CLOSED trap SET notification"
::= { slave-TrapSetNotifications 38 }
slave-Set-Security-LockUnlocked NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-Security-Lock }
STATUS current
DESCRIPTION "Environmental Lock UNLOCKED trap SET notification"
::= { slave-TrapSetNotifications 39 }
slave-Set-Security-LockLocked NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-Security-Lock }
STATUS current
DESCRIPTION "Environmental Lock LOCKED trap SET notification"
::= { slave-TrapSetNotifications 40 }
slave-Set-pduOffline NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-pduStatus }
STATUS current
DESCRIPTION "pdu OFFLINE trap SET notification"
::= { slave-TrapSetNotifications 41 }
slave-Set-meter1-PFLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-PF }
STATUS current
DESCRIPTION "Meter 1 Power Factor LOW trap SET notification"
::= { slave-TrapSetNotifications 42 }
slave-Set-meter1-PFHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-PF }
STATUS current
DESCRIPTION "Meter 1 Power Factor HIGH trap SET notification"
::= { slave-TrapSetNotifications 43 }
slave-Set-meter1-FreqLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-Freq }
STATUS current
DESCRIPTION "Meter 1 Frequency LOW trap SET notification"
::= { slave-TrapSetNotifications 44 }
slave-Set-meter1-FreqHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-Freq }
STATUS current
DESCRIPTION "Meter 1 Frequency HIGH trap SET notification"
::= { slave-TrapSetNotifications 45 }
slave-Set-meter2-VRMSLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-VRMS }
STATUS current
DESCRIPTION "Meter 2 Voltage LOW trap SET notification"
::= { slave-TrapSetNotifications 46 }
slave-Set-meter2-VRMSHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-VRMS }
STATUS current
DESCRIPTION "Meter 2 Voltage HIGH trap SET notification"
::= { slave-TrapSetNotifications 47 }
slave-Set-meter2-IRMSLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-IRMS }
STATUS current
DESCRIPTION "Meter 2 Amps LOW trap SET notification"
::= { slave-TrapSetNotifications 48 }
slave-Set-meter2-IRMSHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-IRMS }
STATUS current
DESCRIPTION "Meter 2 Amps HIGH trap SET notification"
::= { slave-TrapSetNotifications 49 }
slave-Set-meter2-KWSLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-KW }
STATUS current
DESCRIPTION "Meter 2 Kilowatts LOW trap SET notification"
::= { slave-TrapSetNotifications 50 }
slave-Set-meter2-KWSHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-KW }
STATUS current
DESCRIPTION "Meter 2 Kilowatts HIGH trap SET notification"
::= { slave-TrapSetNotifications 51 }
slave-Set-meter2-TempLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-TPMU }
STATUS current
DESCRIPTION "Meter 2 Temperature LOW trap SET notification"
::= { slave-TrapSetNotifications 52 }
slave-Set-meter2-TempHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-TPMU }
STATUS current
DESCRIPTION "Meter 2 Temperature HIGH trap SET notification"
::= { slave-TrapSetNotifications 53 }
slave-Set-meter2-PFLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-PF }
STATUS current
DESCRIPTION "Meter 2 Power Factor LOW trap SET notification"
::= { slave-TrapSetNotifications 54 }
slave-Set-meter2-PFHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-PF }
STATUS current
DESCRIPTION "Meter 2 Power Factor HIGH trap SET notification"
::= { slave-TrapSetNotifications 55 }
slave-Set-meter2-FreqLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-Freq }
STATUS current
DESCRIPTION "Meter 2 Frequency LOW trap SET notification"
::= { slave-TrapSetNotifications 56 }
slave-Set-meter2-FreqHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-Freq }
STATUS current
DESCRIPTION "Meter 2 Frequency HIGH trap SET notification"
::= { slave-TrapSetNotifications 57 }
slave-Set-meter3-VRMSLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-VRMS }
STATUS current
DESCRIPTION "Meter 3 Voltage LOW trap SET notification"
::= { slave-TrapSetNotifications 58 }
slave-Set-meter3-VRMSHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-VRMS }
STATUS current
DESCRIPTION "Meter 3 Voltage HIGH trap SET notification"
::= { slave-TrapSetNotifications 59 }
slave-Set-meter3-IRMSLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-IRMS }
STATUS current
DESCRIPTION "Meter 3 Amps LOW trap SET notification"
::= { slave-TrapSetNotifications 60 }
slave-Set-meter3-IRMSHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-IRMS }
STATUS current
DESCRIPTION "Meter 3 Amps HIGH trap SET notification"
::= { slave-TrapSetNotifications 61 }
slave-Set-meter3-KWSLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-KW }
STATUS current
DESCRIPTION "Meter 3 Kilowatts LOW trap SET notification"
::= { slave-TrapSetNotifications 62 }
slave-Set-meter3-KWSHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-KW }
STATUS current
DESCRIPTION "Meter 3 Kilowatts HIGH trap SET notification"
::= { slave-TrapSetNotifications 63 }
slave-Set-meter3-TempLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-TPMU }
STATUS current
DESCRIPTION "Meter 3 Temperature LOW trap SET notification"
::= { slave-TrapSetNotifications 64 }
slave-Set-meter3-TempHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-TPMU }
STATUS current
DESCRIPTION "Meter 3 Temperature HIGH trap SET notification"
::= { slave-TrapSetNotifications 65 }
slave-Set-meter3-PFLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-PF }
STATUS current
DESCRIPTION "Meter 3 Power Factor LOW trap SET notification"
::= { slave-TrapSetNotifications 66 }
slave-Set-meter3-PFHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-PF }
STATUS current
DESCRIPTION "Meter 3 Power Factor HIGH trap SET notification"
::= { slave-TrapSetNotifications 67 }
slave-Set-meter3-FreqLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-Freq }
STATUS current
DESCRIPTION "Meter 3 Frequency LOW trap SET notification"
::= { slave-TrapSetNotifications 68 }
slave-Set-meter3-FreqHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-Freq }
STATUS current
DESCRIPTION "Meter 3 Frequency HIGH trap SET notification"
::= { slave-TrapSetNotifications 69 }
-- slave-Traps.slave-TrapClearNotifications
slave-Clear-meter1-VRMSLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-VRMS }
STATUS current
DESCRIPTION "Meter 1 Voltage LOW trap CLEAR notification"
::= { slave-TrapClearNotifications 1 }
slave-Clear-meter1-VRMSHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-VRMS }
STATUS current
DESCRIPTION "Meter 1 Voltage HIGH trap CLEAR notification"
::= { slave-TrapClearNotifications 2 }
slave-Clear-meter1-IRMSLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-IRMS }
STATUS current
DESCRIPTION "Meter 1 Amps LOW trap CLEAR notification"
::= { slave-TrapClearNotifications 3 }
slave-Clear-meter1-IRMSHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-IRMS }
STATUS current
DESCRIPTION "Meter 1 Amps HIGH trap CLEAR notification"
::= { slave-TrapClearNotifications 4 }
slave-Clear-meter1-KWSLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-KW }
STATUS current
DESCRIPTION "Meter 1 Kilowatts LOW trap CLEAR notification"
::= { slave-TrapClearNotifications 5 }
slave-Clear-meter1-KWSHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-KW }
STATUS current
DESCRIPTION "Meter 1 Kilowatts HIGH trap CLEAR notification"
::= { slave-TrapClearNotifications 6 }
slave-Clear-meter1-TempLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-TPMU }
STATUS current
DESCRIPTION "Meter 1 Temperature LOW trap CLEAR notification"
::= { slave-TrapClearNotifications 7 }
slave-Clear-meter1-TempHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-TPMU }
STATUS current
DESCRIPTION "Meter 1 Temperature HIGH trap CLEAR notification"
::= { slave-TrapClearNotifications 8 }
slave-Clear-socket-AMPSLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, socket-Number }
STATUS current
DESCRIPTION "socket Amps LOW trap CLEAR notification"
::= { slave-TrapClearNotifications 9 }
slave-Clear-socket-AMPSHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, socket-Number }
STATUS current
DESCRIPTION "socket Amps HIGH trap CLEAR notification"
::= { slave-TrapClearNotifications 10 }
slave-Clear-environmental-Temp1Low NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp1 }
STATUS current
DESCRIPTION "Environmental Temperature probe 1 LOW trap CLEAR notification"
::= { slave-TrapClearNotifications 11 }
slave-Clear-environmental-Temp1High NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp1 }
STATUS current
DESCRIPTION "Environmental Temperature probe 1 HIGH trap CLEAR notification"
::= { slave-TrapClearNotifications 12 }
slave-Clear-environmental-Temp2Low NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp2 }
STATUS current
DESCRIPTION "Environmental Temperature probe 2 LOW trap CLEAR notification"
::= { slave-TrapClearNotifications 13 }
slave-Clear-environmental-Temp2High NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp2 }
STATUS current
DESCRIPTION "Environmental Temperature probe 2 HIGH trap CLEAR notification"
::= { slave-TrapClearNotifications 14 }
slave-Clear-environmental-Temp3Low NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp3 }
STATUS current
DESCRIPTION "Environmental Temperature probe 3 LOW trap CLEAR notification"
::= { slave-TrapClearNotifications 15 }
slave-Clear-environmental-Temp3High NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp3 }
STATUS current
DESCRIPTION "Environmental Temperature probe 3 HIGH trap CLEAR notification"
::= { slave-TrapClearNotifications 16 }
slave-Clear-environmental-Temp4Low NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp4 }
STATUS current
DESCRIPTION "Environmental Temperature probe 4 LOW trap CLEAR notification"
::= { slave-TrapClearNotifications 17 }
slave-Clear-environmental-Temp4High NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp4 }
STATUS current
DESCRIPTION "Environmental Temperature probe 4 HIGH trap CLEAR notification"
::= { slave-TrapClearNotifications 18 }
slave-Clear-environmental-Temp5Low NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp5 }
STATUS current
DESCRIPTION "Environmental Temperature probe 5 LOW trap CLEAR notification"
::= { slave-TrapClearNotifications 19 }
slave-Clear-environmental-Temp5High NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp5 }
STATUS current
DESCRIPTION "Environmental Temperature probe 5 HIGH trap CLEAR notification"
::= { slave-TrapClearNotifications 20 }
slave-Clear-environmental-Temp6Low NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp6 }
STATUS current
DESCRIPTION "Environmental Temperature probe 6 LOW trap CLEAR notification"
::= { slave-TrapClearNotifications 21 }
slave-Clear-environmental-Temp6High NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp6 }
STATUS current
DESCRIPTION "Environmental Temperature probe 6 HIGH trap CLEAR notification"
::= { slave-TrapClearNotifications 22 }
slave-Clear-environmental-Temp7Low NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp7 }
STATUS current
DESCRIPTION "Environmental Temperature probe 7 LOW trap CLEAR notification"
::= { slave-TrapClearNotifications 23 }
slave-Clear-environmental-Temp7High NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp7 }
STATUS current
DESCRIPTION "Environmental Temperature probe 7 HIGH trap CLEAR notification"
::= { slave-TrapClearNotifications 24 }
slave-Clear-environmental-Temp8Low NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp8 }
STATUS current
DESCRIPTION "Environmental Temperature probe 8 LOW trap CLEAR notification"
::= { slave-TrapClearNotifications 25 }
slave-Clear-environmental-Temp8High NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp8 }
STATUS current
DESCRIPTION "Environmental Temperature probe 8 HIGH trap CLEAR notification"
::= { slave-TrapClearNotifications 26 }
slave-Clear-environmental-HumidityTempLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-HumidityTemp }
STATUS current
DESCRIPTION "Environmental Humidity probe Temperature LOW trap CLEAR notification"
::= { slave-TrapClearNotifications 27 }
slave-Clear-environmental-HumidityTempHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-HumidityTemp }
STATUS current
DESCRIPTION "Environmental Humidity probe Temperature HIGH trap CLEAR notification"
::= { slave-TrapClearNotifications 28 }
slave-Clear-environmental-HumidityLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Humidity }
STATUS current
DESCRIPTION "Environmental Humidity probe LOW trap CLEAR notification"
::= { slave-TrapClearNotifications 29 }
slave-Clear-environmental-HumidityHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Humidity }
STATUS current
DESCRIPTION "Environmental Humidity probe HIGH trap CLEAR notification"
::= { slave-TrapClearNotifications 30 }
slave-Clear-environmental-Contact1Open NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Contact1 }
STATUS current
DESCRIPTION "Environmental Contact 1 OPEN trap CLEAR notification"
::= { slave-TrapClearNotifications 31 }
slave-Clear-environmental-Contact1Closed NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Contact1 }
STATUS current
DESCRIPTION "Environmental Contact 1 CLOSED trap CLEAR notification"
::= { slave-TrapClearNotifications 32 }
slave-Clear-environmental-Contact2Open NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Contact2 }
STATUS current
DESCRIPTION "Environmental Contact 2 OPEN trap CLEAR notification"
::= { slave-TrapClearNotifications 33 }
slave-Clear-environmental-Contact2Closed NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Contact2 }
STATUS current
DESCRIPTION "Environmental Contact 2 CLOSED trap CLEAR notification"
::= { slave-TrapClearNotifications 34 }
slave-Clear-environmental-Contact3Open NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Contact3 }
STATUS current
DESCRIPTION "Environmental Contact 3 OPEN trap CLEAR notification"
::= { slave-TrapClearNotifications 35 }
slave-Clear-environmental-Contact3Closed NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Contact3 }
STATUS current
DESCRIPTION "Environmental Contact 3 CLOSED trap CLEAR notification"
::= { slave-TrapClearNotifications 36 }
slave-Clear-Security-DoorOpen NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-Security-Door }
STATUS current
DESCRIPTION "Environmental Door OPEN trap CLEAR notification"
::= { slave-TrapClearNotifications 37 }
slave-Clear-Security-DoorClosed NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-Security-Door }
STATUS current
DESCRIPTION "Environmental Door CLOSED trap CLEAR notification"
::= { slave-TrapClearNotifications 38 }
slave-Clear-Security-LockUnlocked NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-Security-Lock }
STATUS current
DESCRIPTION "Environmental Lock UNLOCKED trap CLEAR notification"
::= { slave-TrapClearNotifications 39 }
slave-Clear-Security-LockLocked NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-Security-Lock }
STATUS current
DESCRIPTION "Environmental Lock LOCKED trap CLEAR notification"
::= { slave-TrapClearNotifications 40 }
slave-Clear-pduOffline NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-pduStatus }
STATUS current
DESCRIPTION "pdu OFFLINE trap CLEAR notification"
::= { slave-TrapClearNotifications 41 }
slave-Clear-meter1-PFLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-PF }
STATUS current
DESCRIPTION "Meter 1 Power Factor LOW trap CLEAR notification"
::= { slave-TrapClearNotifications 42 }
slave-Clear-meter1-PFHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-PF }
STATUS current
DESCRIPTION "Meter 1 Power Factor HIGH trap CLEAR notification"
::= { slave-TrapClearNotifications 43 }
slave-Clear-meter1-FreqLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-Freq }
STATUS current
DESCRIPTION "Meter 1 Frequency LOW trap CLEAR notification"
::= { slave-TrapClearNotifications 44 }
slave-Clear-meter1-FreqHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-Freq }
STATUS current
DESCRIPTION "Meter 1 Frequency HIGH trap CLEAR notification"
::= { slave-TrapClearNotifications 45 }
slave-Clear-meter2-VRMSLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-VRMS }
STATUS current
DESCRIPTION "Meter 2 Voltage LOW trap CLEAR notification"
::= { slave-TrapClearNotifications 46 }
slave-Clear-meter2-VRMSHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-VRMS }
STATUS current
DESCRIPTION "Meter 2 Voltage HIGH trap CLEAR notification"
::= { slave-TrapClearNotifications 47 }
slave-Clear-meter2-IRMSLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-IRMS }
STATUS current
DESCRIPTION "Meter 2 Amps LOW trap CLEAR notification"
::= { slave-TrapClearNotifications 48 }
slave-Clear-meter2-IRMSHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-IRMS }
STATUS current
DESCRIPTION "Meter 2 Amps HIGH trap CLEAR notification"
::= { slave-TrapClearNotifications 49 }
slave-Clear-meter2-KWSLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-KW }
STATUS current
DESCRIPTION "Meter 2 Kilowatts LOW trap CLEAR notification"
::= { slave-TrapClearNotifications 50 }
slave-Clear-meter2-KWSHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-KW }
STATUS current
DESCRIPTION "Meter 2 Kilowatts HIGH trap CLEAR notification"
::= { slave-TrapClearNotifications 51 }
slave-Clear-meter2-TempLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-TPMU }
STATUS current
DESCRIPTION "Meter 2 Temperature LOW trap CLEAR notification"
::= { slave-TrapClearNotifications 52 }
slave-Clear-meter2-TempHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-TPMU }
STATUS current
DESCRIPTION "Meter 2 Temperature HIGH trap CLEAR notification"
::= { slave-TrapClearNotifications 53 }
slave-Clear-meter2-PFLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-PF }
STATUS current
DESCRIPTION "Meter 2 Power Factor LOW trap CLEAR notification"
::= { slave-TrapClearNotifications 54 }
slave-Clear-meter2-PFHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-PF }
STATUS current
DESCRIPTION "Meter 2 Power Factor HIGH trap CLEAR notification"
::= { slave-TrapClearNotifications 55 }
slave-Clear-meter2-FreqLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-Freq }
STATUS current
DESCRIPTION "Meter 2 Frequency LOW trap CLEAR notification"
::= { slave-TrapClearNotifications 56 }
slave-Clear-meter2-FreqHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-Freq }
STATUS current
DESCRIPTION "Meter 2 Frequency HIGH trap CLEAR notification"
::= { slave-TrapClearNotifications 57 }
slave-Clear-meter3-VRMSLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-VRMS }
STATUS current
DESCRIPTION "Meter 3 Voltage LOW trap CLEAR notification"
::= { slave-TrapClearNotifications 58 }
slave-Clear-meter3-VRMSHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-VRMS }
STATUS current
DESCRIPTION "Meter 3 Voltage HIGH trap CLEAR notification"
::= { slave-TrapClearNotifications 59 }
slave-Clear-meter3-IRMSLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-IRMS }
STATUS current
DESCRIPTION "Meter 3 Amps LOW trap CLEAR notification"
::= { slave-TrapClearNotifications 60 }
slave-Clear-meter3-IRMSHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-IRMS }
STATUS current
DESCRIPTION "Meter 3 Amps HIGH trap CLEAR notification"
::= { slave-TrapClearNotifications 61 }
slave-Clear-meter3-KWSLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-KW }
STATUS current
DESCRIPTION "Meter 3 Kilowatts LOW trap CLEAR notification"
::= { slave-TrapClearNotifications 62 }
slave-Clear-meter3-KWSHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-KW }
STATUS current
DESCRIPTION "Meter 3 Kilowatts HIGH trap CLEAR notification"
::= { slave-TrapClearNotifications 63 }
slave-Clear-meter3-TempLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-TPMU }
STATUS current
DESCRIPTION "Meter 3 Temperature LOW trap CLEAR notification"
::= { slave-TrapClearNotifications 64 }
slave-Clear-meter3-TempHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-TPMU }
STATUS current
DESCRIPTION "Meter 3 Temperature HIGH trap CLEAR notification"
::= { slave-TrapClearNotifications 65 }
slave-Clear-meter3-PFLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-PF }
STATUS current
DESCRIPTION "Meter 3 Power Factor LOW trap CLEAR notification"
::= { slave-TrapClearNotifications 66 }
slave-Clear-meter3-PFHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-PF }
STATUS current
DESCRIPTION "Meter 3 Power Factor HIGH trap CLEAR notification"
::= { slave-TrapClearNotifications 67 }
slave-Clear-meter3-FreqLow NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-Freq }
STATUS current
DESCRIPTION "Meter 3 Frequency LOW trap CLEAR notification"
::= { slave-TrapClearNotifications 68 }
slave-Clear-meter3-FreqHigh NOTIFICATION-TYPE
OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-Freq }
STATUS current
DESCRIPTION "Meter 3 Frequency HIGH trap CLEAR notification"
::= { slave-TrapClearNotifications 69 }
-- slave-Global
slave-Global-Table OBJECT-TYPE
SYNTAX SEQUENCE OF Slave-Global-Entry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION ""
::= { slave-Global 1 }
slave-Global-Entry OBJECT-TYPE
SYNTAX Slave-Global-Entry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Table of Trap notification destinations."
INDEX { slave-Global-Index }
::= { slave-Global-Table 1 }
Slave-Global-Entry ::= SEQUENCE {
slave-Global-Index
INTEGER,
slave-Global-Status
INTEGER,
slave-Global-Address
INTEGER,
slave-Global-Nosockets
INTEGER,
slave-Global-meter1-VRMS
INTEGER,
slave-Global-meter1-IRMS
INTEGER,
slave-Global-meter1-VRMS
INTEGER,
slave-Global-meter1-KWH
Integer32,
slave-Global-meter1-KW
INTEGER,
slave-Global-meter1-TPMU
INTEGER,
slave-Global-meter1-PF
INTEGER,
slave-Global-environmental-Temp1
INTEGER,
slave-Global-environmental-Temp2
INTEGER,
slave-Global-environmental-Temp3
INTEGER,
slave-Global-environmental-Temp4
INTEGER,
slave-Global-environmental-Temp5
INTEGER,
slave-Global-environmental-Temp6
INTEGER,
slave-Global-environmental-Temp7
INTEGER,
slave-Global-environmental-Temp8
INTEGER,
slave-Global-environmental-HumidityTemp
INTEGER,
slave-Global-environmental-Humidity
INTEGER,
slave-Global-environmental-Contact1
INTEGER,
slave-Global-environmental-Contact2
INTEGER,
slave-Global-environmental-Contact3
INTEGER,
slave-Global-Security-Door
INTEGER,
slave-Global-Security-Lock
INTEGER,
slave-Global-sockets
Integer32,
slave-Global-socket1Amps
INTEGER,
slave-Global-socket2Amps
INTEGER,
slave-Global-socket3Amps
INTEGER,
slave-Global-socket4Amps
INTEGER,
slave-Global-socket5Amps
INTEGER,
slave-Global-socket6Amps
INTEGER,
slave-Global-socket7Amps
INTEGER,
slave-Global-socket8Amps
INTEGER,
slave-Global-socket9Amps
INTEGER,
slave-Global-socket10Amps
INTEGER,
slave-Global-socket11Amps
INTEGER,
slave-Global-socket12Amps
INTEGER,
slave-Global-socket13Amps
INTEGER,
slave-Global-socket14Amps
INTEGER,
slave-Global-socket15Amps
INTEGER,
slave-Global-socket16Amps
INTEGER,
slave-Global-socket17Amps
INTEGER,
slave-Global-socket18Amps
INTEGER,
slave-Global-socket19Amps
INTEGER,
slave-Global-socket20Amps
INTEGER,
slave-Global-socket21Amps
INTEGER,
slave-Global-socket22Amps
INTEGER,
slave-Global-socket23Amps
INTEGER,
slave-Global-socket24Amps
INTEGER,
slave-Global-socket25Amps
INTEGER,
slave-Global-socket26Amps
INTEGER,
slave-Global-socket27Amps
INTEGER,
slave-Global-socket28Amps
INTEGER,
slave-Global-socket29Amps
INTEGER,
slave-Global-socket30Amps
INTEGER,
slave-Global-socket31Amps
INTEGER,
slave-Global-socket32Amps
INTEGER,
slave-Global-socket1kWh
Integer32,
slave-Global-socket2kWh
Integer32,
slave-Global-socket3kWh
Integer32,
slave-Global-socket4kWh
Integer32,
slave-Global-socket5kWh
Integer32,
slave-Global-socket6kWh
Integer32,
slave-Global-socket7kWh
Integer32,
slave-Global-socket8kWh
Integer32,
slave-Global-socket9kWh
Integer32,
slave-Global-socket10kWh
Integer32,
slave-Global-socket11kWh
Integer32,
slave-Global-socket12kWh
Integer32,
slave-Global-socket13kWh
Integer32,
slave-Global-socket14kWh
Integer32,
slave-Global-socket15kWh
Integer32,
slave-Global-socket16kWh
Integer32,
slave-Global-socket17kWh
Integer32,
slave-Global-socket18kWh
Integer32,
slave-Global-socket19kWh
Integer32,
slave-Global-socket20kWh
Integer32,
slave-Global-socket21kWh
Integer32,
slave-Global-socket22kWh
Integer32,
slave-Global-socket23kWh
Integer32,
slave-Global-socket24kWh
Integer32,
slave-Global-socket25kWh
Integer32,
slave-Global-socket26kWh
Integer32,
slave-Global-socket27kWh
Integer32,
slave-Global-socket28kWh
Integer32,
slave-Global-socket29kWh
Integer32,
slave-Global-socket30kWh
Integer32,
slave-Global-socket31kWh
Integer32,
slave-Global-socket32kWh
Integer32,
slave-Global-socket33Amps
INTEGER,
slave-Global-socket34Amps
INTEGER,
slave-Global-socket35Amps
INTEGER,
slave-Global-socket36Amps
INTEGER,
slave-Global-socket37Amps
INTEGER,
slave-Global-socket38Amps
INTEGER,
slave-Global-socket39Amps
INTEGER,
slave-Global-socket40Amps
INTEGER,
slave-Global-socket41Amps
INTEGER,
slave-Global-socket42Amps
INTEGER,
slave-Global-socket43Amps
INTEGER,
slave-Global-socket44Amps
INTEGER,
slave-Global-socket45Amps
INTEGER,
slave-Global-socket46Amps
INTEGER,
slave-Global-socket47Amps
INTEGER,
slave-Global-socket48Amps
INTEGER,
slave-Global-socket33kWh
Integer32,
slave-Global-socket34kWh
Integer32,
slave-Global-socket35kWh
Integer32,
slave-Global-socket36kWh
Integer32,
slave-Global-socket37kWh
Integer32,
slave-Global-socket38kWh
Integer32,
slave-Global-socket39kWh
Integer32,
slave-Global-socket40kWh
Integer32,
slave-Global-socket41kWh
Integer32,
slave-Global-socket42kWh
Integer32,
slave-Global-socket43kWh
Integer32,
slave-Global-socket44kWh
Integer32,
slave-Global-socket45kWh
Integer32,
slave-Global-socket46kWh
Integer32,
slave-Global-socket47kWh
Integer32,
slave-Global-socket48kWh
Integer32,
slave-Global-sockets2
Integer32,
slave-Global-meter1-Freq
INTEGER,
slave-Global-meter2-VRMS
INTEGER,
slave-Global-meter2-IRMS
INTEGER,
slave-Global-meter2-VRMS
INTEGER,
slave-Global-meter2-KWH
Integer32,
slave-Global-meter2-KW
INTEGER,
slave-Global-meter2-TPMU
INTEGER,
slave-Global-meter2-PF
INTEGER,
slave-Global-meter2-Freq
INTEGER,
slave-Global-meter3-VRMS
INTEGER,
slave-Global-meter3-IRMS
INTEGER,
slave-Global-meter3-VRMS
INTEGER,
slave-Global-meter3-KWH
Integer32,
slave-Global-meter3-KW
INTEGER,
slave-Global-meter3-TPMU
INTEGER,
slave-Global-meter3-PF
INTEGER,
slave-Global-meter3-Freq
INTEGER
}
slave-Global-Index OBJECT-TYPE
SYNTAX INTEGER (0..31)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "pdu index [0..Nopdus]."
::= { slave-Global-Entry 1 }
slave-Global-Status OBJECT-TYPE
SYNTAX INTEGER {offline(0),online(1),disabled(2)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compatible - pdu ONLINE / OFFLINE or DISABLED status."
::= { slave-Global-Entry 2 }
slave-Global-Address OBJECT-TYPE
SYNTAX INTEGER (1..32)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - pdu MODBUS Address."
::= { slave-Global-Entry 3 }
slave-Global-Nosockets OBJECT-TYPE
SYNTAX INTEGER (0..48)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - pdu Number of sockets."
::= { slave-Global-Entry 4 }
slave-Global-meter1-VRMS OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Meter 1 RMS Voltage (VAC) x10."
::= { slave-Global-Entry 5 }
slave-Global-meter1-IRMS OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Meter 1 RMS Current (A) x10."
::= { slave-Global-Entry 6 }
slave-Global-meter1-KWH OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Meter 1 Total energy consumption (kW/h) x10."
::= { slave-Global-Entry 7 }
slave-Global-meter1-KW OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Meter 1 Kilowatts (kW) x1000."
::= { slave-Global-Entry 8 }
slave-Global-meter1-TPMU OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Meter 1 Internal Temperature (C) x10."
::= { slave-Global-Entry 9 }
slave-Global-meter1-PF OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Meter 1 Power Factor x1000"
::= { slave-Global-Entry 10 }
slave-Global-environmental-Temp1 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Environmental Temperature probe 1 (C) x100."
::= { slave-Global-Entry 11 }
slave-Global-environmental-Temp2 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Environmental Temperature probe 2 (C) x100."
::= { slave-Global-Entry 12 }
slave-Global-environmental-Temp3 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Environmental Temperature probe 3 (C) x100."
::= { slave-Global-Entry 13 }
slave-Global-environmental-Temp4 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Environmental Temperature probe 4 (C) x100."
::= { slave-Global-Entry 14 }
slave-Global-environmental-Temp5 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Environmental Temperature probe 5 (C) x100."
::= { slave-Global-Entry 15 }
slave-Global-environmental-Temp6 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Environmental Temperature probe 6 (C) x100."
::= { slave-Global-Entry 16 }
slave-Global-environmental-Temp7 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Environmental Temperature probe 7 (C) x100."
::= { slave-Global-Entry 17 }
slave-Global-environmental-Temp8 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Environmental Temperature probe 8 (C) x100."
::= { slave-Global-Entry 18 }
slave-Global-environmental-HumidityTemp OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Environmental Humidity probe Temperature (C) x100."
::= { slave-Global-Entry 19 }
slave-Global-environmental-Humidity OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Environmental humidity probe (%) x100."
::= { slave-Global-Entry 20 }
slave-Global-environmental-Contact1 OBJECT-TYPE
SYNTAX INTEGER {open(0),closed(1),none(3)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compatible - Environmental contact input 1 status.
Set with any data to clear status."
::= { slave-Global-Entry 21 }
slave-Global-environmental-Contact2 OBJECT-TYPE
SYNTAX INTEGER {open(0),closed(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compatible - Environmental contact input 2 status.
Set with any data to clear status."
::= { slave-Global-Entry 22 }
slave-Global-environmental-Contact3 OBJECT-TYPE
SYNTAX INTEGER {open(0),closed(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compatible - Environmental contact input 3 status.
Set with any data to clear status."
::= { slave-Global-Entry 23 }
slave-Global-Security-Door OBJECT-TYPE
SYNTAX INTEGER {open(0),closed(1)}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - Environmental door contact status."
::= { slave-Global-Entry 24 }
slave-Global-Security-Lock OBJECT-TYPE
SYNTAX INTEGER {locked(0),unlocked(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compatible - Environmental lock status.
Set with any data to force unlock."
::= { slave-Global-Entry 25 }
slave-Global-sockets OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compatible - socket status bits 1 to 32
Set or clear bit to control socket, Bit 0 = socket 1, Bit 31 = socket 32"
::= { slave-Global-Entry 26 }
slave-Global-socket1Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket Amps value x10."
::= { slave-Global-Entry 27 }
slave-Global-socket2Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket Amps value x10."
::= { slave-Global-Entry 28 }
slave-Global-socket3Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket Amps value x10."
::= { slave-Global-Entry 29 }
slave-Global-socket4Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket Amps value x10."
::= { slave-Global-Entry 30 }
slave-Global-socket5Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket Amps value x10."
::= { slave-Global-Entry 31 }
slave-Global-socket6Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket Amps value x10."
::= { slave-Global-Entry 32 }
slave-Global-socket7Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket Amps value x10."
::= { slave-Global-Entry 33 }
slave-Global-socket8Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket Amps value x10."
::= { slave-Global-Entry 34 }
slave-Global-socket9Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket Amps value x10."
::= { slave-Global-Entry 35 }
slave-Global-socket10Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket Amps value x10."
::= { slave-Global-Entry 36 }
slave-Global-socket11Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket Amps value x10."
::= { slave-Global-Entry 37 }
slave-Global-socket12Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket Amps value x10."
::= { slave-Global-Entry 38 }
slave-Global-socket13Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket Amps value x10."
::= { slave-Global-Entry 39 }
slave-Global-socket14Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket Amps value x10."
::= { slave-Global-Entry 40 }
slave-Global-socket15Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket Amps value x10."
::= { slave-Global-Entry 41 }
slave-Global-socket16Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket Amps value x10."
::= { slave-Global-Entry 42 }
slave-Global-socket17Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket Amps value x10."
::= { slave-Global-Entry 43 }
slave-Global-socket18Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket Amps value x10."
::= { slave-Global-Entry 44 }
slave-Global-socket19Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket Amps value x10."
::= { slave-Global-Entry 45 }
slave-Global-socket20Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket Amps value x10."
::= { slave-Global-Entry 46 }
slave-Global-socket21Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket Amps value x10."
::= { slave-Global-Entry 47 }
slave-Global-socket22Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket Amps value x10."
::= { slave-Global-Entry 48 }
slave-Global-socket23Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket Amps value x10."
::= { slave-Global-Entry 49 }
slave-Global-socket24Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket Amps value x10."
::= { slave-Global-Entry 50 }
slave-Global-socket25Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket Amps value x10."
::= { slave-Global-Entry 51 }
slave-Global-socket26Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket Amps value x10."
::= { slave-Global-Entry 52 }
slave-Global-socket27Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket Amps value x10."
::= { slave-Global-Entry 53 }
slave-Global-socket28Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket Amps value x10."
::= { slave-Global-Entry 54 }
slave-Global-socket29Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket Amps value x10."
::= { slave-Global-Entry 55 }
slave-Global-socket30Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket Amps value x10."
::= { slave-Global-Entry 56 }
slave-Global-socket31Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket Amps value x10."
::= { slave-Global-Entry 57 }
slave-Global-socket32Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket Amps value x10."
::= { slave-Global-Entry 58 }
slave-Global-socket1kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket kWh value x10."
::= { slave-Global-Entry 59 }
slave-Global-socket2kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket kWh value x10."
::= { slave-Global-Entry 60 }
slave-Global-socket3kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket kWh value x10."
::= { slave-Global-Entry 61 }
slave-Global-socket4kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket kWh value x10."
::= { slave-Global-Entry 62 }
slave-Global-socket5kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket kWh value x10."
::= { slave-Global-Entry 63 }
slave-Global-socket6kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket kWh value x10."
::= { slave-Global-Entry 64 }
slave-Global-socket7kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket kWh value x10."
::= { slave-Global-Entry 65 }
slave-Global-socket8kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket kWh value x10."
::= { slave-Global-Entry 66 }
slave-Global-socket9kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket kWh value x10."
::= { slave-Global-Entry 67 }
slave-Global-socket10kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket kWh value x10."
::= { slave-Global-Entry 68 }
slave-Global-socket11kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket kWh value x10."
::= { slave-Global-Entry 69 }
slave-Global-socket12kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket kWh value x10."
::= { slave-Global-Entry 70 }
slave-Global-socket13kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket kWh value x10."
::= { slave-Global-Entry 71 }
slave-Global-socket14kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket kWh value x10."
::= { slave-Global-Entry 72 }
slave-Global-socket15kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket kWh value x10."
::= { slave-Global-Entry 73 }
slave-Global-socket16kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket kWh value x10."
::= { slave-Global-Entry 74 }
slave-Global-socket17kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket kWh value x10."
::= { slave-Global-Entry 75 }
slave-Global-socket18kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket kWh value x10."
::= { slave-Global-Entry 76 }
slave-Global-socket19kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket kWh value x10."
::= { slave-Global-Entry 77 }
slave-Global-socket20kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket kWh value x10."
::= { slave-Global-Entry 78 }
slave-Global-socket21kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket kWh value x10."
::= { slave-Global-Entry 79 }
slave-Global-socket22kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket kWh value x10."
::= { slave-Global-Entry 80 }
slave-Global-socket23kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket kWh value x10."
::= { slave-Global-Entry 81 }
slave-Global-socket24kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket kWh value x10."
::= { slave-Global-Entry 82 }
slave-Global-socket25kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket kWh value x10."
::= { slave-Global-Entry 83 }
slave-Global-socket26kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket kWh value x10."
::= { slave-Global-Entry 84 }
slave-Global-socket27kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket kWh value x10."
::= { slave-Global-Entry 85 }
slave-Global-socket28kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket kWh value x10."
::= { slave-Global-Entry 86 }
slave-Global-socket29kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket kWh value x10."
::= { slave-Global-Entry 87 }
slave-Global-socket30kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket kWh value x10."
::= { slave-Global-Entry 88 }
slave-Global-socket31kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket kWh value x10."
::= { slave-Global-Entry 89 }
slave-Global-socket32kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compatible - socket kWh value x10."
::= { slave-Global-Entry 90 }
slave-Global-socket33Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket Amps value x10."
::= { slave-Global-Entry 91 }
slave-Global-socket34Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket Amps value x10."
::= { slave-Global-Entry 92 }
slave-Global-socket35Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket Amps value x10."
::= { slave-Global-Entry 93 }
slave-Global-socket36Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket Amps value x10."
::= { slave-Global-Entry 94 }
slave-Global-socket37Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket Amps value x10."
::= { slave-Global-Entry 95 }
slave-Global-socket38Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket Amps value x10."
::= { slave-Global-Entry 96 }
slave-Global-socket39Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket Amps value x10."
::= { slave-Global-Entry 97 }
slave-Global-socket40Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket Amps value x10."
::= { slave-Global-Entry 98 }
slave-Global-socket41Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket Amps value x10."
::= { slave-Global-Entry 99 }
slave-Global-socket42Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket Amps value x10."
::= { slave-Global-Entry 100 }
slave-Global-socket43Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket Amps value x10."
::= { slave-Global-Entry 101 }
slave-Global-socket44Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket Amps value x10."
::= { slave-Global-Entry 102 }
slave-Global-socket45Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket Amps value x10."
::= { slave-Global-Entry 103 }
slave-Global-socket46Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket Amps value x10."
::= { slave-Global-Entry 104 }
slave-Global-socket47Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket Amps value x10."
::= { slave-Global-Entry 105 }
slave-Global-socket48Amps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket Amps value x10."
::= { slave-Global-Entry 106 }
slave-Global-socket33kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket kWh value x10."
::= { slave-Global-Entry 107 }
slave-Global-socket34kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket kWh value x10."
::= { slave-Global-Entry 108 }
slave-Global-socket35kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket kWh value x10."
::= { slave-Global-Entry 109 }
slave-Global-socket36kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket kWh value x10."
::= { slave-Global-Entry 110 }
slave-Global-socket37kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket kWh value x10."
::= { slave-Global-Entry 111 }
slave-Global-socket38kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket kWh value x10."
::= { slave-Global-Entry 112 }
slave-Global-socket39kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket kWh value x10."
::= { slave-Global-Entry 113 }
slave-Global-socket40kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket kWh value x10."
::= { slave-Global-Entry 114 }
slave-Global-socket41kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket kWh value x10."
::= { slave-Global-Entry 115 }
slave-Global-socket42kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket kWh value x10."
::= { slave-Global-Entry 116 }
slave-Global-socket43kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket kWh value x10."
::= { slave-Global-Entry 117 }
slave-Global-socket44kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket kWh value x10."
::= { slave-Global-Entry 118 }
slave-Global-socket45kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket kWh value x10."
::= { slave-Global-Entry 119 }
slave-Global-socket46kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket kWh value x10."
::= { slave-Global-Entry 120 }
slave-Global-socket47kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket kWh value x10."
::= { slave-Global-Entry 121 }
slave-Global-socket48kWh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "socket kWh value x10."
::= { slave-Global-Entry 122 }
slave-Global-sockets2 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "socket status bits 33-48
Set or clear bit to control socket,
Bit 0 = socket 33, Bit 15 = socket 48"
::= { slave-Global-Entry 123 }
slave-Global-meter1-Freq OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Meter 1 Frequency x10"
::= { slave-Global-Entry 124 }
slave-Global-meter2-VRMS OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Meter 2 RMS Voltage (VAC) x10."
::= { slave-Global-Entry 125 }
slave-Global-meter2-IRMS OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Meter 2 RMS Current (A) x10."
::= { slave-Global-Entry 126 }
slave-Global-meter2-KWH OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Meter 2 Total energy consumption (kW/h) x10."
::= { slave-Global-Entry 127 }
slave-Global-meter2-KW OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Meter 2 Kilowatts (kW) x1000."
::= { slave-Global-Entry 128 }
slave-Global-meter2-TPMU OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Meter 2 Internal Temperature (C) x10."
::= { slave-Global-Entry 129 }
slave-Global-meter2-PF OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Meter 2 Power Factor x1000"
::= { slave-Global-Entry 130 }
slave-Global-meter2-Freq OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Meter 2 Frequency x10"
::= { slave-Global-Entry 131 }
slave-Global-meter3-VRMS OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Meter 3 RMS Voltage (VAC) x10."
::= { slave-Global-Entry 132 }
slave-Global-meter3-IRMS OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Meter 3 RMS Current (A) x10."
::= { slave-Global-Entry 133 }
slave-Global-meter3-KWH OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Meter 3 Total energy consumption (kW/h) x10."
::= { slave-Global-Entry 134 }
slave-Global-meter3-KW OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Meter 3 Kilowatts (kW) x1000."
::= { slave-Global-Entry 135 }
slave-Global-meter3-TPMU OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Meter 3 Internal Temperature (C) x10."
::= { slave-Global-Entry 136 }
slave-Global-meter3-PF OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Meter 3 Power Factor x1000"
::= { slave-Global-Entry 137 }
slave-Global-meter3-Freq OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Meter 3 Frequency x10"
::= { slave-Global-Entry 138 }
END