HMIOMODULE-SNMP-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
MODULE-IDENTITY, OBJECT-IDENTITY,
|
|
OBJECT-TYPE, NOTIFICATION-TYPE,
|
|
Integer32, IpAddress FROM SNMPv2-SMI
|
|
TEXTUAL-CONVENTION,
|
|
DisplayString FROM SNMPv2-TC
|
|
hmChassis, hmChassisEvent FROM HMPRIV-MGMT-SNMP-MIB
|
|
InetPortNumber FROM INET-ADDRESS-MIB;
|
|
|
|
HmEnabledStatus ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION "Status of a feature"
|
|
SYNTAX INTEGER {
|
|
enable(1), -- feature is enabled
|
|
disable(2) -- feature is disabled
|
|
}
|
|
|
|
-- *************************************************************************
|
|
-- Group IO Module
|
|
-- *************************************************************************
|
|
hmIOModuleGroup MODULE-IDENTITY
|
|
LAST-UPDATED "201011081500Z" -- 08 Nov 2010 15:00:00 GMT
|
|
ORGANIZATION "Hirschmann Automation and Control GmbH"
|
|
CONTACT-INFO
|
|
"Customer Support
|
|
Postal:
|
|
Hirschmann Automation and Control GmbH
|
|
Stuttgarter Str. 45-51
|
|
72654 Neckartenzlingen
|
|
Germany
|
|
Tel: +49 7127 14 1981
|
|
Web: http://www.hicomcenter.com/
|
|
E-Mail: hicomcenter@hirschmann.com"
|
|
DESCRIPTION
|
|
"The Hirschmann Private IO Module definitions for Platform devices."
|
|
-- Revision history.
|
|
REVISION
|
|
"201011081500Z" -- 08 Nov 2010 15:00:00 GMT
|
|
DESCRIPTION
|
|
"first release"
|
|
::= { hmChassis 13 }
|
|
|
|
-- *************************************************************************
|
|
-- Group Config
|
|
-- *************************************************************************
|
|
hmIOModuleConfigGroup OBJECT IDENTIFIER
|
|
::= { hmIOModuleGroup 1 }
|
|
|
|
-- *************************************************************************
|
|
-- Goup Common Config
|
|
-- *************************************************************************
|
|
hmIOModConfigCommon OBJECT IDENTIFIER
|
|
::= { hmIOModuleConfigGroup 1 }
|
|
|
|
hmIOModConfigDigInputAdminState OBJECT-TYPE
|
|
SYNTAX HmEnabledStatus
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"enables sending SNMP traps or log events on input change.
|
|
(if disable(2) input task will do nothing)."
|
|
DEFVAL { disable }
|
|
::= { hmIOModConfigCommon 1 }
|
|
|
|
hmIOModConfigDigOutputAdminState OBJECT-TYPE
|
|
SYNTAX HmEnabledStatus
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"enables polling of output values (if disable(2) output task will do nothing)."
|
|
DEFVAL { disable }
|
|
::= { hmIOModConfigCommon 2 }
|
|
|
|
hmIOModConfigDigInputRefreshInterval OBJECT-TYPE
|
|
SYNTAX Integer32 (500..10000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The refresh interval (in ms) of the input values.
|
|
Minimum 500ms, Maximum 10000ms (10s)."
|
|
DEFVAL { 1000 }
|
|
::= { hmIOModConfigCommon 3 }
|
|
|
|
hmIOModConfigDigOutputRefreshInterval OBJECT-TYPE
|
|
SYNTAX Integer32 (500..10000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The refresh interval (in ms) of the output values.
|
|
Minimum 500ms, Maximum 10000ms (10s)."
|
|
DEFVAL { 1000 }
|
|
::= { hmIOModConfigCommon 4 }
|
|
|
|
hmIOModConfigDigOutputRetryCount OBJECT-TYPE
|
|
SYNTAX Integer32 (1..10)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The retry count for the output values.
|
|
when after the number of configured retries no SNMP get request
|
|
was answered, the output value (hmIOModOutputValue) will be
|
|
set to invalid (3). Minimum 1, Maximum 10."
|
|
DEFVAL { 3 }
|
|
::= { hmIOModConfigCommon 5 }
|
|
|
|
-- *************************************************************************
|
|
-- Table Digital Input Config
|
|
-- *************************************************************************
|
|
hmIOModConfigDigInputTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF HmIOModConfigDigInputEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"IO module config table for inputs"
|
|
::= { hmIOModuleConfigGroup 2 }
|
|
|
|
hmIOModConfigDigInputEntry OBJECT-TYPE
|
|
SYNTAX HmIOModConfigDigInputEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"IO module config entry for inputs"
|
|
INDEX {
|
|
hmIOModConfigDigInputModID,
|
|
hmIOModConfigDigInputID}
|
|
::= { hmIOModConfigDigInputTable 1 }
|
|
|
|
HmIOModConfigDigInputEntry ::= SEQUENCE {
|
|
hmIOModConfigDigInputModID Integer32,
|
|
hmIOModConfigDigInputID Integer32,
|
|
hmIOModConfigDigInputLogEvent HmEnabledStatus,
|
|
hmIOModConfigDigInputSnmpTrap HmEnabledStatus
|
|
}
|
|
|
|
hmIOModConfigDigInputModID OBJECT-TYPE
|
|
SYNTAX Integer32 (1..7)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The module ID of an input."
|
|
::= { hmIOModConfigDigInputEntry 1 }
|
|
|
|
hmIOModConfigDigInputID OBJECT-TYPE
|
|
SYNTAX Integer32 (1..4)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The ID of an input."
|
|
::= { hmIOModConfigDigInputEntry 2 }
|
|
|
|
hmIOModConfigDigInputLogEvent OBJECT-TYPE
|
|
SYNTAX HmEnabledStatus
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trigger an event log when input status changes.
|
|
If the value is disable (2), no event log entry will be written.
|
|
If the value is enable (1), an event log entry will be written when
|
|
the input state changes.
|
|
The input state will be checked acording to the refresh interval
|
|
entered in hmIOModConfigDigInputRefreshInterval."
|
|
DEFVAL { disable }
|
|
::= { hmIOModConfigDigInputEntry 3 }
|
|
|
|
hmIOModConfigDigInputSnmpTrap OBJECT-TYPE
|
|
SYNTAX HmEnabledStatus
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trigger an SNMP trap log when input status changes.
|
|
If the value is disable (2), no SNMP trap will be sent.
|
|
If the value is enable (1), a SNMP trap will be sent when
|
|
the input state changes.
|
|
The SNMP trap will be sent to all receivers configured
|
|
in hmAgentSnmpTrapReceiverConfigTable.
|
|
The input state will be checked acording to the refresh interval entered
|
|
in hmIOModConfigDigInputRefreshInterval."
|
|
DEFVAL { disable }
|
|
::= { hmIOModConfigDigInputEntry 4 }
|
|
|
|
-- *************************************************************************
|
|
-- Table Digital Output Config
|
|
-- *************************************************************************
|
|
hmIOModConfigDigOutputTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF HmIOModConfigDigOutputEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"IO module config table for outputs"
|
|
::= { hmIOModuleConfigGroup 3 }
|
|
|
|
hmIOModConfigDigOutputEntry OBJECT-TYPE
|
|
SYNTAX HmIOModConfigDigOutputEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"IO module config entry for outputs"
|
|
INDEX {
|
|
hmIOModConfigDigOutputModID,
|
|
hmIOModConfigDigOutputID }
|
|
::= { hmIOModConfigDigOutputTable 1 }
|
|
|
|
HmIOModConfigDigOutputEntry ::= SEQUENCE {
|
|
hmIOModConfigDigOutputModID Integer32,
|
|
hmIOModConfigDigOutputID Integer32,
|
|
hmIOModConfigDigOutputLogEvent HmEnabledStatus,
|
|
hmIOModConfigDigOutputSnmpTrap HmEnabledStatus,
|
|
hmIOModConfigDigOutputSourceIP IpAddress,
|
|
hmIOModConfigDigOutputSourceModID Integer32,
|
|
hmIOModConfigDigOutputSourceID Integer32,
|
|
hmIOModConfigDigOutputSourcePort InetPortNumber}
|
|
|
|
hmIOModConfigDigOutputModID OBJECT-TYPE
|
|
SYNTAX Integer32 (1..7)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The module ID of an output."
|
|
::= { hmIOModConfigDigOutputEntry 1 }
|
|
|
|
hmIOModConfigDigOutputID OBJECT-TYPE
|
|
SYNTAX Integer32 (1..4)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The ID of an output."
|
|
::= { hmIOModConfigDigOutputEntry 2 }
|
|
|
|
hmIOModConfigDigOutputLogEvent OBJECT-TYPE
|
|
SYNTAX HmEnabledStatus
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trigger an event log when output status changes.
|
|
If the value is disable (2), no event log entry will be written.
|
|
If the value is enable (1), an event log entry will be written when
|
|
the output state changes.
|
|
The output state will be checked acording to the refresh interval
|
|
entered in hmIOModConfigDigOutputRefreshInterval."
|
|
DEFVAL { disable }
|
|
::= { hmIOModConfigDigOutputEntry 3 }
|
|
|
|
hmIOModConfigDigOutputSnmpTrap OBJECT-TYPE
|
|
SYNTAX HmEnabledStatus
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trigger an SNMP trap log when output status changes.
|
|
If the value is disable (2), no SNMP trap will be sent.
|
|
If the value is enable (1), a SNMP trap will be sent when
|
|
the output state changes.
|
|
The SNMP trap will be sent to all receivers configured
|
|
in hmAgentSnmpTrapReceiverConfigTable.
|
|
The output state will be checked acording to the refresh interval
|
|
entered in hmIOModConfigDigOutputRefreshInterval."
|
|
DEFVAL { disable }
|
|
::= { hmIOModConfigDigOutputEntry 4 }
|
|
|
|
hmIOModConfigDigOutputSourceIP OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The IP address of an input mirrored to the output.
|
|
Use 0.0.0.0 if the output should not be set.
|
|
In this case hmIOModOutputValue is invalid (3).
|
|
Use 127.0.0.1 if an local input should be used."
|
|
DEFVAL { "0.0.0.0" }
|
|
::= { hmIOModConfigDigOutputEntry 5 }
|
|
|
|
hmIOModConfigDigOutputSourceModID OBJECT-TYPE
|
|
SYNTAX Integer32 (1..7)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The module ID of an input mirrored to the output.
|
|
Ignored when hmIOModConfigDigOutputSourceIP is 0.0.0.0."
|
|
DEFVAL { 1 }
|
|
::= { hmIOModConfigDigOutputEntry 6 }
|
|
|
|
hmIOModConfigDigOutputSourceID OBJECT-TYPE
|
|
SYNTAX Integer32 (1..4)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The ID of an input mirrored to the output.
|
|
Ignored when hmIOModConfigDigOutputSourceIP is 0.0.0.0."
|
|
DEFVAL { 1 }
|
|
::= { hmIOModConfigDigOutputEntry 7 }
|
|
|
|
hmIOModConfigDigOutputSourcePort OBJECT-TYPE
|
|
SYNTAX InetPortNumber
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The SNMP port number being used by the input mirrored to the output.
|
|
This port would be the destination for the SNMP requests for
|
|
polling the state of the input."
|
|
DEFVAL { 161 }
|
|
::= { hmIOModConfigDigOutputEntry 8 }
|
|
|
|
-- *************************************************************************
|
|
-- Group Value
|
|
-- *************************************************************************
|
|
hmIOModuleValueGroup OBJECT IDENTIFIER
|
|
::= { hmIOModuleGroup 2 }
|
|
|
|
-- *************************************************************************
|
|
-- Table Digital Input Value
|
|
-- *************************************************************************
|
|
hmIOModValueDigInputTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF HmIOModValueDigInputEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"IO module value table for inputs"
|
|
::= { hmIOModuleValueGroup 1 }
|
|
|
|
hmIOModValueDigInputEntry OBJECT-TYPE
|
|
SYNTAX HmIOModValueDigInputEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"IO module value entry for inputs"
|
|
INDEX {
|
|
hmIOModValueDigInputModID,
|
|
hmIOModValueDigInputID}
|
|
::= { hmIOModValueDigInputTable 1 }
|
|
|
|
HmIOModValueDigInputEntry ::= SEQUENCE {
|
|
hmIOModValueDigInputModID Integer32,
|
|
hmIOModValueDigInputID Integer32,
|
|
hmIOModValueDigInputValue INTEGER}
|
|
|
|
hmIOModValueDigInputModID OBJECT-TYPE
|
|
SYNTAX Integer32 (1..7)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The module ID of an input."
|
|
::= { hmIOModValueDigInputEntry 1 }
|
|
|
|
hmIOModValueDigInputID OBJECT-TYPE
|
|
SYNTAX Integer32 (1..4)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The ID of an input."
|
|
::= { hmIOModValueDigInputEntry 2 }
|
|
|
|
hmIOModValueDigInputValue OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
not-available (0),
|
|
high (1),
|
|
low (2)}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of the input.
|
|
If the value is not-available(0), then the IO module is not plugged in,
|
|
if the value is high(1), the input has high (+24V) value,
|
|
if the value is low(2), the input has low (0V) value."
|
|
::= { hmIOModValueDigInputEntry 3 }
|
|
|
|
|
|
-- *************************************************************************
|
|
-- Table Digital Output Value
|
|
-- *************************************************************************
|
|
hmIOModValueDigOutputTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF HmIOModValueDigOutputEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"IO module value table for outputs"
|
|
::= { hmIOModuleValueGroup 2 }
|
|
|
|
hmIOModValueDigOutputEntry OBJECT-TYPE
|
|
SYNTAX HmIOModValueDigOutputEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"IO module value entry for outputs"
|
|
INDEX {
|
|
hmIOModValueDigOutputModID,
|
|
hmIOModValueDigOutputID }
|
|
::= { hmIOModValueDigOutputTable 1 }
|
|
|
|
HmIOModValueDigOutputEntry ::= SEQUENCE {
|
|
hmIOModValueDigOutputModID Integer32,
|
|
hmIOModValueDigOutputID Integer32,
|
|
hmIOModValueDigOutputValue INTEGER}
|
|
|
|
hmIOModValueDigOutputModID OBJECT-TYPE
|
|
SYNTAX Integer32 (1..7)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The module ID of an Output."
|
|
::= { hmIOModValueDigOutputEntry 1 }
|
|
|
|
hmIOModValueDigOutputID OBJECT-TYPE
|
|
SYNTAX Integer32 (1..4)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The ID of an Output."
|
|
::= { hmIOModValueDigOutputEntry 2 }
|
|
|
|
hmIOModValueDigOutputValue OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
not-available (0),
|
|
high (1),
|
|
low (2),
|
|
invalid (3),
|
|
not-configured (4)}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Status of the output.
|
|
If the value is not-available(0), then the IO module is not plugged in,
|
|
if the value is high(1), the output has high (+24V) value,
|
|
if the value is low(2), the output has low (0V) value.
|
|
If the value is invalid (3), the output has low (0V) value and
|
|
the IO input source is configured but can not be read.
|
|
If the value is not-configured (4), the output has low (0V) value and
|
|
has no IO input source configured."
|
|
::= { hmIOModValueDigOutputEntry 3 }
|
|
|
|
-- *************************************************************************
|
|
-- TRAP's
|
|
-- *************************************************************************
|
|
hmIOModDigInputChangeTrap NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
hmIOModValueDigInputValue}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This trap is sent if the state of an input changes.
|
|
This trap is sent only when hmIOModConfigDigInputSnmpTrap is set
|
|
to enabled (1)."
|
|
::= { hmChassisEvent 16 }
|
|
|
|
hmIOModDigOutputChangeTrap NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
hmIOModValueDigOutputValue}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This trap is sent if the state of an input changes.
|
|
This trap is sent when hmIOModConfigDigOutputSnmpTrap is set
|
|
to enabled (1) or when the output value changes from or to invalid (3)"
|
|
::= { hmChassisEvent 17 }
|
|
|
|
END
|