Observium_CE/mibs/apnl/APNL-MODULAR-PDU-MIB

1049 lines
25 KiB
Plaintext

-- Last edit: Thu Jan 24 13:00:00 2013
-- Jeroen Verheul
--
-- File: apnl-modular-pdu-v2.0.mib
--
-- Contact
-- Vincent Veltens <v.veltens@apnederland.nl>
-- Release version V2.0
APNL-MODULAR-PDU-MIB DEFINITIONS ::= BEGIN
IMPORTS
NOTIFICATION-TYPE, OBJECT-TYPE, MODULE-IDENTITY,
enterprises, IpAddress, Unsigned32, Integer32
FROM SNMPv2-SMI
DateAndTime, DisplayString
FROM SNMPv2-TC;
apNederland MODULE-IDENTITY
LAST-UPDATED "201301241000Z"
ORGANIZATION
"AP Nederland"
CONTACT-INFO
"Vincent Veltens <v.veltens@apnederland.nl>"
DESCRIPTION
"This MIB module defines the modular PDU version of AP Nederland."
REVISION "201301241305Z"
DESCRIPTION
"Initial Version"
::= { enterprises 29640 }
-- Tue Mar 20 2012.
--
apnlDirectory OBJECT IDENTIFIER ::= { apNederland 1 }
apnlMib OBJECT IDENTIFIER ::= { apNederland 2 }
apnlTmp OBJECT IDENTIFIER ::= { apNederland 3 }
apnlModules OBJECT IDENTIFIER ::= { apNederland 4 }
-- Blackbox CM Communication module (mib definition is in apnl-mib.mib).
cm OBJECT IDENTIFIER ::= { apnlModules 1 }
cmTraps OBJECT IDENTIFIER ::= { apnlModules 2 }
-- Modular PDU Communication module
pdu OBJECT IDENTIFIER ::= { apnlModules 3 }
pduTraps OBJECT IDENTIFIER ::= { apnlModules 4 }
apnlTest OBJECT IDENTIFIER ::= { apNederland 5 }
apnlDemo OBJECT IDENTIFIER ::= { apNederland 6 }
apnlMIBConformance OBJECT IDENTIFIER ::= { apNederland 7 }
pduType OBJECT-TYPE
SYNTAX INTEGER {
pduModular (0),
pduGateway1 (1),
pduGateway2 (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Type of the Pdu.
PduModular (0) Modulaire OEC2 PDU communication through SNMPV3, MOD-BUS or AP-BUS in emulation mode.
PduGateway1 (1) Gateway to connect OEC1 products with external AP-BUS protocol to OEC2 Manager (SNMPV3).
PduGateway2 (2) Gateway to connect OEC2 products with external MOD-BUS to OEC Manager (SNMPV3).
"
::= { pdu 1 }
-- Product serial number
pduProductIdentifier OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Unique serial number to identify a pdu, the number is between 1 and 65535. "
::= { pdu 2 }
pduSerialNumber OBJECT-TYPE
SYNTAX DisplayString (SIZE(1..16))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU onboard Serial Number."
::= { pdu 3 }
pduStatus OBJECT-TYPE
SYNTAX INTEGER {
pduBusy (0),
pduReady1 (1),
pduAlarm (2),
pduError (3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status of the Pdu.
pduBusy (0) Indicates that an admin command is in progress.
pduReady (1) The execution of an admin command was successfull.
pduAlarm (2) This state is not in use.
pduError (3) The execution of an admin command failed."
::= { pdu 4 }
pduPower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "kiloWattHours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total measured pdu power in Kilo Watt's*Hour."
::= { pdu 5 }
pduPowerL1 OBJECT-TYPE
SYNTAX Unsigned32
UNITS "kiloWattHours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total measured pdu power in Kilo Watt's*Hour for phase 1."
::= { pdu 6 }
pduPowerL2 OBJECT-TYPE
SYNTAX Unsigned32
UNITS "kiloWattHours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total measured pdu power in Kilo Watt's*Hour for phase 2."
::= { pdu 7 }
pduPowerL3 OBJECT-TYPE
SYNTAX Unsigned32
UNITS "kiloWattHours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total measured pdu power in Kilo Watt's*Hour for phase 3."
::= { pdu 8 }
pduKvar OBJECT-TYPE
SYNTAX Unsigned32
UNITS "KiloWattHours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total Reactive Power of the pdu. It is the power that magnetic equipment
(transformer, motor and relay) needs to produce the magnetizing flux."
REFERENCE
"http://standby.iea-4e.org/files/otherfiles/0000/0059/PowerFactorBasics.pdf"
::= { pdu 9 }
pduKvarL1 OBJECT-TYPE
SYNTAX Unsigned32
UNITS "KiloWattHours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total Reactive Power of the pdu for phase 1. It is the power that magnetic equipment
(transformer, motor and relay) needs to produce the magnetizing flux."
REFERENCE
"http://standby.iea-4e.org/files/otherfiles/0000/0059/PowerFactorBasics.pdf"
::= { pdu 10 }
pduKvarL2 OBJECT-TYPE
SYNTAX Unsigned32
UNITS "KiloWattHours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total Reactive Power of the pdu for phase 2. It is the power that magnetic equipment
(transformer, motor and relay) needs to produce the magnetizing flux."
REFERENCE
"http://standby.iea-4e.org/files/otherfiles/0000/0059/PowerFactorBasics.pdf"
::= { pdu 11 }
pduKvarL3 OBJECT-TYPE
SYNTAX Unsigned32
UNITS "KiloWattHours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total Reactive Power of the pdu for phase 3. It is the power that magnetic equipment
(transformer, motor and relay) needs to produce the magnetizing flux."
REFERENCE
"http://standby.iea-4e.org/files/otherfiles/0000/0059/PowerFactorBasics.pdf"
::= { pdu 12 }
pdulAcurrent OBJECT-TYPE
SYNTAX Unsigned32
UNITS "DeciAmpers"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total measured ac current for the pdu (in 1/10th Amperes) ."
::= { pdu 13 }
pduAcurrentL1 OBJECT-TYPE
SYNTAX Unsigned32
UNITS "DeciAmpers"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total measured ac current for phase 1 (in 1/10th Amperes)."
::= { pdu 14 }
pduAcurrentL2 OBJECT-TYPE
SYNTAX Unsigned32
UNITS "DeciAmpers"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total measured ac current for phase 2 (in 1/10th Amperes)."
::= { pdu 15 }
pduAcurrentL3 OBJECT-TYPE
SYNTAX Unsigned32
UNITS "DeciAmpers"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total measured ac current for phase 3 (in 1/10th Amperes)."
::= { pdu 16 }
pduCurIpAddress OBJECT-TYPE
SYNTAX IpAddress
UNITS "IPv4 Addr"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current PDU IPv4 Address by which TCP/IP access is available.
"
::= { pdu 17 }
pduCurSubNetMask OBJECT-TYPE
SYNTAX IpAddress
UNITS "IPv4 Addr"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current PDU IPv4 Subnet Mask used by the Ipstack (e.g: 255.255.255.0)."
::= { pdu 18 }
pduCurDefGwAddress OBJECT-TYPE
SYNTAX IpAddress
UNITS "IPv4 Addr"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current PDU IPv4 default gateway address used by the Ipstack (e.g: 192.168.1.1)."
::= { pdu 19 }
-- Number of items in the node table.
pduNumberOfNodes OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of items in the node table."
::= { pdu 20 }
-- Number of items in the sensor table.
--
pduNumberOfSensors OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of items in the sensor table."
::= { pdu 21 }
-- apnl upper level scalars
--
pduSoftwareVersion OBJECT-TYPE
SYNTAX DisplayString (SIZE(1..10))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU software version number."
::= { pdu 22 }
pduFirmwareVersion OBJECT-TYPE
SYNTAX DisplayString (SIZE(1..10))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU firmware version number."
::= { pdu 23 }
pduBusProtocol OBJECT-TYPE
SYNTAX INTEGER {
apbus (0),
modbus (1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Selected protocol used on the external bus of the pdu.
AP-BUS (0) Protocol used by OEC1 products or by OEC2 products in emulation mode.
MOD-BUS (1) Protocol used by OEC2 products."
::= { pdu 24 }
pduAdminCommand OBJECT-TYPE
SYNTAX INTEGER {
noOp (0),
rebootPdu (1),
rediscover (2),
updateSofware (3),
resetConfig (4),
resetSNMPv3Config (5),
resetNetworkSetting (6),
readDataFromBusPdu (7),
writeDataToBusPdu (8)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"PDU admin management Commands:
noOp (0) No operation.
rebootPdu (1) Reboot the PDU (to execute new settings).
rediscover (2) Not supported.
updateSofware (3) Not supported.
resetConfig (4) Node and group tables will be cleared .
resetSNMPv3Config (5) Not supported.
resetNetworkSetting (6) Reset network params: ip address, defualt gatewy, subnet mask.
readDataFromBusPdu (7) Read data from a PDU connected to the external bus (address is set in pduBusAddress).
writeDataToBusPdu (8) With this command modified data is writen back to the bus PDU (address is set in pduBusAddress).
"
::= { pdu 25 }
pduStartupIpAddress OBJECT-TYPE
SYNTAX IpAddress
UNITS "IPv4 Addr"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Not supported.
"
::= { pdu 26 }
pduStartupSubNetMask OBJECT-TYPE
SYNTAX IpAddress
UNITS "IPv4 Addr"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Not supported."
::= { pdu 27 }
pduStartupDefGwAddress OBJECT-TYPE
SYNTAX IpAddress
UNITS "IPv4 Addr"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Not supported."
::= { pdu 28 }
pduRealTimeClock OBJECT-TYPE
SYNTAX DateAndTime
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"PDU Real-Time Clock. Maybe set by the manager."
::= { pdu 29 }
pduEnableFeatures OBJECT-TYPE
SYNTAX BITS {
globalWebEnabled (0),
globalUsbEnabled (1),
globalSwitchEnabled (2),
displaySwitchEnabled (3),
webSwitchEnabled (4)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Array of bits each one an specific feature within the pdu:
globalWebEnabled (0) This bit enables the PDU webpages.
globalUsbEnabled (1) This bit enables the USB menu.
globalSwitchEnabled (2) This bit enables switching in general.
displaySwitchEnabled (3) This bit enables switching through the presentation module.
webSwitchEnabled (4) This bit enables switching throuhg the web inteface.
"
::= { pdu 30 }
pduBusAddress OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Address used to access this PDU via the external bus.
When MOD-BUS protocol is used the address is valid between 1-247.
When AP-BUS protocol is used the address is valid between 1-65535.
"
::= { pdu 31 }
pduName OBJECT-TYPE
SYNTAX DisplayString (SIZE(1..32))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Name of the PDU."
::= { pdu 32 }
-- The port table.
nodeTable OBJECT-TYPE
SYNTAX SEQUENCE OF NodeEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table of the modules on the PDU.
Each entry represents an module unit.
"
::= { pdu 33 }
nodeEntry OBJECT-TYPE
SYNTAX NodeEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An port entry in the port table."
INDEX { nodeIndex }
::= { nodeTable 1 }
NodeEntry ::= SEQUENCE {
nodeIndex
Unsigned32,
nodeType
INTEGER,
nodeOutlet
Unsigned32,
nodeAlarmStatus
BITS,
nodePower
Unsigned32,
nodeAcurrent
Unsigned32,
nodePeakCurrent
Unsigned32,
nodeVoltage
Unsigned32,
nodeMinVoltage
Unsigned32,
nodeKvar
Unsigned32,
nodeFrequency
Unsigned32,
nodePowerFactor
Unsigned32,
nodeSwitchOperStatus
INTEGER,
nodeSwitchAdminStatus
INTEGER,
nodeCurrHiThresh
Unsigned32,
nodeCurrLoThresh
Unsigned32,
nodeVoltHiThresh
Unsigned32,
nodeVoltLoThresh
Unsigned32,
nodeAlarmSelector
BITS,
nodeName
DisplayString,
nodePhase
INTEGER
}
nodeIndex OBJECT-TYPE
SYNTAX Unsigned32 (1..30)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The node table Index."
::= { nodeEntry 1 }
nodeType OBJECT-TYPE
SYNTAX INTEGER {
typeUnknown (0),
typePresModChar (1),
typePresModMono (2),
typePresModGraph (3),
typePowerMeter (4),
typePowerMeterSwitch (5),
typeSwitch (6)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Type of the node.
TypeUnknown (0) Unknown node.
TypePresModChar (1) PM LCD Character Module.
TypePresModMono (2) PM Mono Graphics Module.
TypePresModGraph (3) PM Color Graphics Module.
TypePowerMeter (4) Power meter.
TypePowerMeterSwitch (5) Switchable power meter.
TypeSwitch (6) Switch only.
"
::= { nodeEntry 2 }
nodeOutlet OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number associated with the physical outlet of the node.
The special value of 0 indicates that this entry is not associated with a physical port."
::= { nodeEntry 3 }
nodeAlarmStatus OBJECT-TYPE
SYNTAX BITS {
trapCurrHi (0),
trapCurrLo (1),
trapVoltHi (2),
trapVoltLo (3),
switchOn (4),
switchOff (5)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Array of bits each one indicates an alarm activated in the alarm selector value.
TrapCurrHi (0) The current is to high against the high current threshold.
TrapCurrLo (1) The current is to low against the low current threshold.
TrapVoltHi (2) The voltage is to high against the high voltage threshold.
TrapVoltLo (3) The volage is to low against the low voltage threshold.
SwitchOn (4) The switch is on against the switch on bitfield.
SwitchOff (5) The switch is off against the switch off bitfield.
"
::= { nodeEntry 4 }
nodePower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "kiloWattHours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The measured node power in Kilo Watt's*Hour."
::= { nodeEntry 5 }
nodeAcurrent OBJECT-TYPE
SYNTAX Unsigned32
UNITS "DeciAmpers"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The measured ac current at the node (in 1/10th Amperes)."
::= { nodeEntry 6 }
nodePeakCurrent OBJECT-TYPE
SYNTAX Unsigned32
UNITS "DeciAmpers"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The measured max current since last reset of the node (in 1/10th Amperes)."
::= { nodeEntry 7 }
nodeVoltage OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The measured voltage on the node."
::= { nodeEntry 8 }
nodeMinVoltage OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The measured minimum voltage at the node since last reset."
::= { nodeEntry 9 }
nodeKvar OBJECT-TYPE
SYNTAX Unsigned32
UNITS "KiloWattHours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The Reactive Power. It is the power that magnetic equipment
(transformer, motor and relay) needs to produce the magnetizing flux."
REFERENCE
"http://standby.iea-4e.org/files/otherfiles/0000/0059/PowerFactorBasics.pdf"
::= { nodeEntry 10 }
nodeFrequency OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Hertz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The frequency of alternating current in Hertz. e.g 50 in Europe or 60 in USA."
REFERENCE
"http://en.wikipedia.org/wiki/Hertz"
::= { nodeEntry 11 }
nodePowerFactor OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The effective power facton (Cosinus Phi) in percents of the node."
REFERENCE
"http://en.wikipedia.org/wiki/Power_factor"
::= { nodeEntry 12 }
nodeSwitchOperStatus OBJECT-TYPE
SYNTAX INTEGER {
unknown (0),
off (1),
on (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The actual operational Status of the node.
Unknown (0) not known status.
Off (1) switch is off.
On (2) switch is on."
::= { nodeEntry 13 }
nodeSwitchAdminStatus OBJECT-TYPE
SYNTAX INTEGER {
unknown (0),
off (1),
on (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The desired admin Status of the switch.
Unknown (0) not known.
Off (1) switch is off.
On (2) switch is on."
::= { nodeEntry 14 }
nodeCurrHiThresh OBJECT-TYPE
SYNTAX Unsigned32
UNITS "DeciAmpers"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The current high threshold (in 1/10th Amperes)."
::= { nodeEntry 15 }
nodeCurrLoThresh OBJECT-TYPE
SYNTAX Unsigned32
UNITS "DeciAmpers"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The current low threshold (in 1/10th Amperes)."
::= { nodeEntry 16 }
nodeVoltHiThresh OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The voltage high threshold."
::= { nodeEntry 17 }
nodeVoltLoThresh OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The voltage low threshold."
::= { nodeEntry 18 }
nodeAlarmSelector OBJECT-TYPE
SYNTAX BITS {
trapCurrHi (0),
trapCurrLo (1),
trapVoltHi (2),
trapVoltLo (3),
switchOn (4),
switchOff (5)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Array of bits each one controls one alarm.
TrapCurrHi (0) Enable/disable the high current alarm.
TrapCurrLo (1) Enable/disable the low current alarm.
TrapVoltHi (2) Enable/disable the high voltage alarm.
TrapVoltLo (3) Enable/disable the low voltage alarm.
SwitchOn (4) Enable/disable the specific switch on alarm.
SwitchOff (5) Enable/disable the specific switch off alarm."
::= { nodeEntry 19 }
nodeName OBJECT-TYPE
SYNTAX DisplayString (SIZE(1..14))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The node name. My be set by manager."
::= { nodeEntry 20 }
nodePhase OBJECT-TYPE
SYNTAX INTEGER {
phaseUnknown (0),
phaseL1 (1),
phaseL2 (2),
phaseL3 (3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The measured phase of the node.
Maybe assigned when not configured in production.
PhaseUnknown (0).
PhaseL1 (1).
PhaseL2 (2).
PhaseL3 (3).
"
::= { nodeEntry 21 }
--
-- The Sensors Table
--
sensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF SensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table of the Sensors on the PDU.
Each entry represents an an Sensor unit.
"
::= { pdu 34 }
sensorEntry OBJECT-TYPE
SYNTAX SensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An Sensor Entry in the Sensor table"
INDEX { sensorIndex }
::= { sensorTable 1 }
SensorEntry ::= SEQUENCE {
sensorIndex
Unsigned32,
sensorType
INTEGER,
sensorAlarmStatus
BITS,
sensorValue
Integer32,
sensorSwitchOperStatus
INTEGER,
sensorSwitchAdminStatus
INTEGER,
sensorHiThresh
Integer32,
sensorLoThresh
Integer32,
sensorAlarmSelector
BITS,
sensorName
DisplayString
}
sensorIndex OBJECT-TYPE
SYNTAX Unsigned32 (1..4)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The Sensor table Index."
::= { sensorEntry 1 }
sensorType OBJECT-TYPE
SYNTAX INTEGER {
other (0),
temperature (1),
humidity (2),
smoke (3),
co1 (4),
vibration (5),
doorStatus (6)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Sensor Typ:
Measured values are used according to sensor type.
Other (0) unknown sensor type.
Temperature (1) .
Humidity (2).
Smoke (3).
CO1 (4).
Vibration (5).
Doorstatus (6)."
::= { sensorEntry 2 }
sensorAlarmStatus OBJECT-TYPE
SYNTAX BITS {
trapHi (0),
trapLo (1),
switchOn (2),
switchOff (3),
beeperHi (4),
beeperLo (5)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Array of bits each one indicates an alarm activated in the alarm selector value."
::= { sensorEntry 3 }
sensorValue OBJECT-TYPE
SYNTAX Integer32
UNITS "by type"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The measured value of the sensor, units are depending on sensor type."
::= { sensorEntry 4 }
sensorSwitchOperStatus OBJECT-TYPE
SYNTAX INTEGER {
unknown (0),
off (1),
on (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The actual operational Status of the switch."
::= { sensorEntry 5 }
sensorSwitchAdminStatus OBJECT-TYPE
SYNTAX INTEGER {
unknown (0),
off (1),
on (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The desired admin Status of the switch."
::= { sensorEntry 6 }
-- thresholds
sensorHiThresh OBJECT-TYPE
SYNTAX Integer32
UNITS "by type"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"High threshold."
::= { sensorEntry 7 }
sensorLoThresh OBJECT-TYPE
SYNTAX Integer32
UNITS "by type"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Low threshold."
::= { sensorEntry 8 }
sensorAlarmSelector OBJECT-TYPE
SYNTAX BITS {
trapHi (0),
trapLo (1),
switchOn (2),
switchOff (3),
beeperHi (4),
beeperLo (5)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Array of bits each one controls one alarm.
E.g trap, beeper etc."
::= { sensorEntry 9 }
sensorName OBJECT-TYPE
SYNTAX DisplayString (SIZE(1..12))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The sensor name. May be set by the manager."
::= { sensorEntry 10 }
--
-- PDU traps
--
-- Trap to inform the manager about:
-- 1. voltage
-- 2. current
-- 4. sensor (temperature, humidity)
-- 5. switch
-- 6. startup
-- 7. power
-- Trap Type enumration to indicate the kind of alarm that sent
trapType OBJECT-TYPE
SYNTAX INTEGER {
voltageHiAlarm (0),
voltageLoAlarm (1),
currentHiAlarm (2),
currentLoAlarm (3),
tempHiAlarm (4),
tempLoAlarm (5),
humidityHiAlarm (6),
humidityLoAlarm (7),
switchOnAlarm (8),
switchOffAlarm (9),
powerHiAlarm (10),
blackBoxColdTrap (11)
}
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"An enumation value to indicate an Alarm trap: pduPduAlarm."
::= { pduTraps 1 }
pduTableType OBJECT-TYPE
SYNTAX INTEGER {
pduNodeTable (0),
pduSensorTable (1)
}
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The table type."
::= { pduTraps 2 }
--
-- The Index of the table entry for which the trap is made.
-- It has the same value of the table index (which is not-accessible
--
trapTableIndex OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The index of the table entry for which the trap is issued."
::= { pduTraps 3 }
-- The thershold type which the trap is made.
--
trapThreshHoldType OBJECT-TYPE
SYNTAX INTEGER {
trapThresholdOther (0),
trapThresholdHi (1),
trapThresholdLo (2)
}
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The threshold type for which the trap is made."
::= { pduTraps 4 }
-- The reference threshold value
--
trapThreshHold OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The threshold reference value."
::= { pduTraps 5 }
--
-- traps definitions
--
pduVoltageAlarm NOTIFICATION-TYPE
OBJECTS { trapType,
trapTableIndex,
trapThreshHoldType,
trapThreshHold }
STATUS current
DESCRIPTION
"Voltage alarm."
::= { pduTraps 6 }
pduCurrentAlarm NOTIFICATION-TYPE
OBJECTS { trapType,
trapTableIndex,
trapThreshHoldType,
trapThreshHold }
STATUS current
DESCRIPTION
"Current alaram."
::= { pduTraps 7 }
pduPowerAlarm NOTIFICATION-TYPE
OBJECTS { trapType,
trapTableIndex,
trapThreshHoldType,
trapThreshHold }
STATUS current
DESCRIPTION
"Power alarm."
::= { pduTraps 8 }
sensorAlarm NOTIFICATION-TYPE
OBJECTS { trapType,
trapTableIndex,
trapThreshHoldType,
trapThreshHold }
STATUS current
DESCRIPTION
"Sensor Alarm:
Temperature, Humidity or another type.
The sensorType indicates the type of alarm.
The sensorValue indicate the measured value."
::= { pduTraps 9 }
pduSwitchAlarm NOTIFICATION-TYPE
OBJECTS { trapType,
trapTableIndex }
STATUS current
DESCRIPTION
"Not supported."
::= { pduTraps 10 }
END