Observium_CE/mibs/ibm/IBM-PDU-MIB

1149 lines
48 KiB
Plaintext

IBM-PDU-MIB DEFINITIONS ::= BEGIN
IMPORTS
MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE FROM SNMPv2-SMI
enterprises, Integer32, Unsigned32 FROM SNMPv2-SMI
MODULE-COMPLIANCE, OBJECT-GROUP, NOTIFICATION-GROUP FROM SNMPv2-CONF
TEXTUAL-CONVENTION, DisplayString FROM SNMPv2-TC;
ibmPowerDistributionUnitMIB MODULE-IDENTITY
LAST-UPDATED "201205310000Z"
ORGANIZATION "International Business Machines"
CONTACT-INFO "International Business Machines
1 New Orchard Road
Armonk, New York 10504-1722
United States
E-mail: ews@us.ibm.com"
DESCRIPTION "The MIB module representing a power disribution
unit supported by a single SNMP agent"
REVISION "201205310000Z"
DESCRIPTION "1. Additions of fields ibmPduReboot, ibmPduOutletGlobalDelayTimer,
and ibmPduOutletIndividualDelayTimer for IBM/Netezza.
Licensed Materials - Property of IBM
Copyright IBM Corp. 2012"
REVISION "201201180000Z"
DESCRIPTION "The IBM Power Distribution Unit MIB definitions for
enabling power monitoring and management of an IBM
Power Unit.
Licensed Materials - Property of IBM
Copyright IBM Corp. 2009"
::= { ibmProd 223 }
ibm OBJECT IDENTIFIER ::= { enterprises 2 }
ibmProd OBJECT IDENTIFIER ::= { ibm 6 }
ibmPduMetadata OBJECT IDENTIFIER ::= { ibmPowerDistributionUnitMIB 7 }
ibmPduDevice OBJECT IDENTIFIER ::= { ibmPowerDistributionUnitMIB 8 }
ibmPduOutlets OBJECT IDENTIFIER ::= { ibmPduDevice 2 }
ibmPduPower OBJECT IDENTIFIER ::= { ibmPduDevice 3 }
ibmPduEnvironment OBJECT IDENTIFIER ::= { ibmPduDevice 4 }
ibmPduExternalMonitors OBJECT IDENTIFIER ::= { ibmPowerDistributionUnitMIB 9 }
ibmPduTraps OBJECT IDENTIFIER ::= { ibmPowerDistributionUnitMIB 0 }
ibmPduTrapData OBJECT IDENTIFIER ::= { ibmPduTraps 1 }
ibmPduTrapDataObjects OBJECT IDENTIFIER ::= { ibmPduTrapData 1 }
ibmPduConformance OBJECT IDENTIFIER ::= { ibmPowerDistributionUnitMIB 2 }
ibmPduCompliances OBJECT IDENTIFIER ::= { ibmPduConformance 1 }
ibmPduGroups OBJECT IDENTIFIER ::= { ibmPduConformance 2 }
ibmPduLocation OBJECT IDENTIFIER ::= { ibmPduMetadata 1 }
ibmPduImage OBJECT IDENTIFIER ::= { ibmPduMetadata 2 }
-- ////////////////////////////////////////////////////////
-- //////////////// TEXTUAL-CONVENTIONs ///////////////////
-- ////////////////////////////////////////////////////////
IbmPduPowerBuf ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION "Buffer that contains the power records. This buffer
contains ibmPduBufferEntries (default 120) average
power samples, in Watts, at 4 bytes each sample, in
little-endian format."
SYNTAX OCTET STRING(SIZE(480))
IbmPduEnvBuf ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION "Buffer that contains temperature or humidity records.
This buffer contains ibmPduBufferEntries (default 120)
average point-in-time samples at 2 bytes each in
little-endian format."
SYNTAX OCTET STRING(SIZE(240))
IbmPduMilliAmps ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION "Used for floating point amperage values since SNMP
does not support floating point numbers."
SYNTAX Unsigned32
IbmPduMilliVolt ::= TEXTUAL-CONVENTION
STATUS voltage
DESCRIPTION "Used for floating point voltage values since SNMP
does not support floating point numbers."
SYNTAX Unsigned32
-- ////////////////////////////////////////////////////////
-- ///////////////////// ibmDevice ATTRs /////////////////////
-- ////////////////////////////////////////////////////////
ibmPduBufferTagValue OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Used for the update interval of power and environmental
registers. The buffer tag is incremented every sample
of data that is captured in the buffer."
::= { ibmPowerDistributionUnitMIB 3 }
ibmPduSampleRate OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Sample rate in seconds for each entry in the sampled buffer.
The default is 30."
::= { ibmPowerDistributionUnitMIB 4 }
ibmPduBufferVersion OBJECT-TYPE
SYNTAX DisplayString(SIZE(0..7))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Version of the snapshot buffer."
::= { ibmPowerDistributionUnitMIB 5 }
ibmPduBufferEntries OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of entries contained in each data buffer.
The default is 120."
::= { ibmPowerDistributionUnitMIB 6 }
ibmPduSoftwareVersion OBJECT-TYPE
SYNTAX DisplayString(SIZE (0..63))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Version of the software loaded on the PDU."
::= { ibmPduMetadata 3 }
ibmPduMachineType OBJECT-TYPE
SYNTAX DisplayString(SIZE (0..4))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Machine type of the PDU."
::= { ibmPduMetadata 4 }
ibmPduModelNumber OBJECT-TYPE
SYNTAX DisplayString(SIZE (0..15))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Model number of the PDU."
::= { ibmPduMetadata 5 }
ibmPduPartNumber OBJECT-TYPE
SYNTAX DisplayString(SIZE (0..10))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Part number of the PDU."
::= { ibmPduMetadata 6 }
ibmPduName OBJECT-TYPE
SYNTAX DisplayString(SIZE (0..63))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Name of the device."
::= { ibmPduMetadata 7 }
ibmPduManufacturer OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The name of manufacturer."
::= { ibmPduMetadata 8 }
ibmPduSerialNumber OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..6))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Serial number of the device."
::= { ibmPduMetadata 9 }
ibmPduDescription OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Description of the device."
::= { ibmPduMetadata 10 }
ibmPduUrl OBJECT-TYPE
SYNTAX DisplayString(SIZE(0..127))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "URL of the web interface to the ibmDevice if available."
::= { ibmPduMetadata 11 }
ibmPduReboot OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Set 1 to reboot PDU."
::= { ibmPduMetadata 12 }
ibmPduDateTime OBJECT-TYPE
SYNTAX DateAndTime
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Set or get PDU Date and Time."
::= { ibmPduMetadata 13 }
-- ////////////////////////////////////////////////////////
-- ////////////////////// ibmLocation ////////////////////////
-- ////////////////////////////////////////////////////////
ibmPduTelephoneNumber OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..31))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Telephone number of building and site
where the device is located."
::= { ibmPduLocation 1 }
ibmPduCountryRegion OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..31))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Country or region where the device
is located."
::= { ibmPduLocation 2 }
ibmPduStreetAddress OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..31))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Street address of building where the
device is located."
::= { ibmPduLocation 3 }
ibmPduCity OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..31))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "City where the device is located."
::= { ibmPduLocation 4 }
ibmPduStateProvince OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "State or province where the device
is located."
::= { ibmPduLocation 5 }
ibmPduPostalCode OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Postal code where the device is
located."
::= { ibmPduLocation 6 }
ibmPduBuilding OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Building name where the device is
located."
::= { ibmPduLocation 7 }
ibmPduFloor OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..7))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Floor number or designation where
the device is located."
::= { ibmPduLocation 8 }
ibmPduRoomNumber OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..7))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Room number where the device is
located."
::= { ibmPduLocation 9 }
ibmPduRow OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..7))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Row number where the device is
located."
::= { ibmPduLocation 10 }
ibmPduAisle OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..7))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Aisle number where the device is
located."
::= { ibmPduLocation 11 }
ibmPduDisplaceHeight OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Displaced height in Centimeters."
::= { ibmPduLocation 12 }
ibmPduAltitude OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Altitude in Meters."
::= { ibmPduLocation 13 }
ibmPduOtherInfo OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Additional ibmLocation information."
::= { ibmPduLocation 14 }
-- ////////////////////////////////////////////////////////
-- ///////////////////// IMAGE ATTRS //////////////////////
-- ////////////////////////////////////////////////////////
ibmPduLogo OBJECT-TYPE
SYNTAX OCTET STRING(SIZE(65535))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Device logo or image."
::= { ibmPduImage 1 }
ibmPduDeviceFront OBJECT-TYPE
SYNTAX OCTET STRING(SIZE(65535))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Image of the front of the device."
::= { ibmPduImage 2 }
ibmPduDeviceRear OBJECT-TYPE
SYNTAX OCTET STRING(SIZE(65535))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Image of the back of the device."
::= { ibmPduImage 3 }
-- ////////////////////////////////////////////////////////
-- ///////////////////// ibmDevice POWER /////////////////////
-- ////////////////////////////////////////////////////////
ibmPduPhaseCount OBJECT-TYPE
SYNTAX INTEGER {
single(1),
three(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The number of input power phases for the PDU."
::= { ibmPduPower 1 }
ibmPduPhaseTable OBJECT-TYPE
SYNTAX SEQUENCE OF IbmPduPowerPhaseStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A list of power phase entries. The number of
entries is given by phaseNumber."
::= { ibmPduPower 2 }
ibmPduPhaseTableEntry OBJECT-TYPE
SYNTAX IbmPduPowerPhaseStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A value contained within the PowerPhaseStruct."
INDEX { ibmPduPhaseNumber }
::= { ibmPduPhaseTable 1 }
IbmPduPowerPhaseStruct ::= SEQUENCE { ibmPduPhaseNumber Unsigned32,
ibmPduPhaseAvgPower IbmPduPowerBuf,
ibmPduPhaseMaxPower IbmPduPowerBuf,
ibmPduPhaseLastPowerReading Unsigned32 }
ibmPduPhaseNumber OBJECT-TYPE
SYNTAX Unsigned32(1..3)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "The power phase number."
::= { ibmPduPhaseTableEntry 1 }
ibmPduPhaseAvgPower OBJECT-TYPE
SYNTAX IbmPduPowerBuf
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Buffer containing average power values. Refer to
description of IbmPduPowerBuf for information about
buffer format."
::= { ibmPduPhaseTableEntry 2 }
ibmPduPhaseMaxPower OBJECT-TYPE
SYNTAX IbmPduPowerBuf
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Buffer containing max power values. Refer to
description of IbmPduPowerBuf for information about
buffer format."
::= { ibmPduPhaseTableEntry 3 }
ibmPduPhaseLastPowerReading OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The value of the most recent power reading for this
phase, in Watts."
::= { ibmPduPhaseTableEntry 4 }
-- ////////////////////////////////////////////////////////
-- ///////////////////// ENVIRONMENT //////////////////////
-- ////////////////////////////////////////////////////////
ibmPduThermalBuffer OBJECT-TYPE
SYNTAX IbmPduEnvBuf
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Buffer that contains the thermal records. Refer to
description of IbmPduEnvBuf for information about
buffer format."
::= { ibmPduEnvironment 1 }
ibmPduHumidityBuffer OBJECT-TYPE
SYNTAX IbmPduEnvBuf
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Buffer that contains the humdity records. Refer to
description of IbmPduEnvBuf for information about
buffer format."
::= { ibmPduEnvironment 2 }
ibmPduThermalThresholdWarning OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "The value of the warning threshold for
the given temperature returned in Celsius."
::= { ibmPduEnvironment 3 }
ibmPduThermalThresholdCritical OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "The value of the critical threshold for
the given temperature returned in Celsius."
::= { ibmPduEnvironment 4 }
ibmPduHumidityThresholdWarning OBJECT-TYPE
SYNTAX Unsigned32(0..100)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "The value of the warning threshold for
the given humidity returned as a percent."
::= { ibmPduEnvironment 5 }
ibmPduHumidityThresholdCritical OBJECT-TYPE
SYNTAX Unsigned32(0..100)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "The value of the critical threshold for
the given humidity returned as a percent."
::= { ibmPduEnvironment 6 }
ibmPduThermalLastReading OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The value of the most recent temperature reading for
the internal temperature sensor, in degrees Celsius."
::= { ibmPduEnvironment 7 }
ibmPduHumidityLastReading OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The value of the most recent humidity reading for
the internal humidity sensor, as a percentage."
::= { ibmPduEnvironment 8 }
-- ////////////////////////////////////////////////////////
-- //////////////////////// OUTLETS ///////////////////////
-- ////////////////////////////////////////////////////////
ibmPduOutletCount OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The number of outlets (regardless of their current state) present on this PDU."
::= { ibmPduOutlets 1 }
ibmPduOutletTable OBJECT-TYPE
SYNTAX SEQUENCE OF IbmPduOutletStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A list of outlet entries. The number of entries is given by the value of
outletCount."
::= { ibmPduOutlets 2 }
ibmPduOutletGlobalDelayTimer OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Global delay timer for all outlets. Range: 0 sec ~ 3600 sec. Default value:0 sec. To combine with Individual Delay timer to control outlet state/behavior as rack power on/restore"
::= { ibmPduOutlets 3 }
ibmPduOutletEntry OBJECT-TYPE
SYNTAX IbmPduOutletStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A value contained within the OutletStruct."
INDEX { ibmPduOutletNumber }
::= { ibmPduOutletTable 1 }
IbmPduOutletStruct ::= SEQUENCE { ibmPduOutletNumber Integer32,
ibmPduOutletName DisplayString,
ibmPduOutletType INTEGER,
ibmPduOutletDescription DisplayString,
ibmPduOutletAvgPower IbmPduPowerBuf,
ibmPduOutletMaxPower IbmPduPowerBuf,
ibmPduOutletPowerFactor Unsigned32,
ibmPduOutletVoltage IbmPduMilliVolt,
ibmPduOutletCurrent IbmPduMilliAmps,
ibmPduOutletMaxCapacity IbmPduMilliAmps,
ibmPduOutletCurrentThresholdWarning IbmPduMilliAmps,
ibmPduOutletCurrentThresholdCritical IbmPduMilliAmps,
ibmPduOutletState INTEGER,
ibmPduOutletGroupIndex Unsigned32,
ibmPduOutletLastPowerReading Unsigned32,
ibmPduOutletIndividualDelayTimer Unsigned32}
ibmPduOutletNumber OBJECT-TYPE
SYNTAX Integer32(0..255)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "The unique index of the given outlet."
::= { ibmPduOutletEntry 1 }
ibmPduOutletName OBJECT-TYPE
SYNTAX DisplayString(SIZE (0..64))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Text describing the name or designation of the given outlet."
::= { ibmPduOutletEntry 2 }
ibmPduOutletType OBJECT-TYPE
SYNTAX INTEGER { c13(0),
c19(1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of the outlet."
::= { ibmPduOutletEntry 3 }
ibmPduOutletDescription OBJECT-TYPE
SYNTAX DisplayString(SIZE (0..63))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Description of the outlet."
::= { ibmPduOutletEntry 4 }
ibmPduOutletAvgPower OBJECT-TYPE
SYNTAX IbmPduPowerBuf
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Buffer containing average power values. Refer to
description of IbmPduPowerBuf for information about
buffer format."
::= { ibmPduOutletEntry 5 }
ibmPduOutletMaxPower OBJECT-TYPE
SYNTAX IbmPduPowerBuf
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Buffer containing max power values. Refer to
description of IbmPduPowerBuf for information about
buffer format."
::= { ibmPduOutletEntry 6 }
ibmPduOutletPowerFactor OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The value of the Power Factor of the given outlet."
::= { ibmPduOutletEntry 7 }
ibmPduOutletVoltage OBJECT-TYPE
SYNTAX IbmPduMilliVolt
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The value of the Voltage of the given outlet
returned in MilliVolt."
::= { ibmPduOutletEntry 8 }
ibmPduOutletCurrent OBJECT-TYPE
SYNTAX IbmPduMilliAmps
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The value of the Current of the given outlet
returned in Milliamps."
::= { ibmPduOutletEntry 9 }
ibmPduOutletMaxCapacity OBJECT-TYPE
SYNTAX IbmPduMilliAmps
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The maximum capacity of the current
outlet in Milliamps."
::= { ibmPduOutletEntry 10 }
ibmPduOutletCurrentThresholdWarning OBJECT-TYPE
SYNTAX IbmPduMilliAmps
MAX-ACCESS read-write
STATUS current
DESCRIPTION "The value of the warning threshold
for the given outlet returned in Milliamps."
::= { ibmPduOutletEntry 11 }
ibmPduOutletCurrentThresholdCritical OBJECT-TYPE
SYNTAX IbmPduMilliAmps
MAX-ACCESS read-write
STATUS current
DESCRIPTION "The value of the critical threshold
for the given outlet returned in Milliamps."
::= { ibmPduOutletEntry 12 }
ibmPduOutletState OBJECT-TYPE
SYNTAX INTEGER { error(-1),
off(0),
on(1),
cycling(2),
delaySwitch10(3),
delaySwitch30(4),
delaySwitch60(5)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "The value of the operational state for the given outlet.
This can also be used to set (change) the outlet state."
::= { ibmPduOutletEntry 13 }
ibmPduOutletGroupIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The index of the outlet group in which the outlet resides.
If there are no outlet groups present, the default is 0."
::= { ibmPduOutletEntry 14 }
ibmPduOutletLastPowerReading OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The value of the most recent power reading for this
outlet, in Watts."
::= { ibmPduOutletEntry 15 }
ibmPduOutletIndividualDelayTimer OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "The delay timer for each outlet as AC power restored. Range: 0 sec ~ 3600 sec. Default Value: 0 sec. To combine with Global Delay timer to control outlet state/behavior as rack power or or restore"
::= { ibmPduOutletEntry 16 }
-- ////////////////////////////////////////////////////////
-- ////////////////// EXTERNAL MONITORS ///////////////////
-- ////////////////////////////////////////////////////////
ibmPduExtMonitorCount OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The number of external monitors (regardless of
their current state) present on this PDU."
::= { ibmPduExternalMonitors 1 }
ibmPduExtMonitorTable OBJECT-TYPE
SYNTAX SEQUENCE OF IbmPduExternalMonitorStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A list of external monitors. The number of
entries is given by the value of externalMonitorCount."
::= { ibmPduExternalMonitors 2 }
ibmPduExtMonitorEntry OBJECT-TYPE
SYNTAX IbmPduExternalMonitorStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A value contained within the ExternalMonitorStruct."
INDEX { ibmPduExtMonitorNumber }
::= { ibmPduExtMonitorTable 1 }
IbmPduExternalMonitorStruct ::= SEQUENCE { ibmPduExtMonitorNumber Integer32,
ibmPduExtThermalBuffer IbmPduEnvBuf,
ibmPduExtHumidityBuffer IbmPduEnvBuf,
ibmPduExtThermalThresholdWarning Unsigned32,
ibmPduExtThermalThresholdCritical Unsigned32,
ibmPduExtHumidityThresholdWarning Unsigned32,
ibmPduExtHumidityThresholdCritical Unsigned32,
ibmPduExtThermalLastReading Unsigned32,
ibmPduExtHumidityLastReading Unsigned32
}
ibmPduExtMonitorNumber OBJECT-TYPE
SYNTAX Integer32(0..255)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "The unique index of the given external monitor."
::= { ibmPduExtMonitorEntry 1 }
ibmPduExtThermalBuffer OBJECT-TYPE
SYNTAX IbmPduEnvBuf
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Buffer that contains the thermal records. Refer to
description of IbmPduEnvBuf for information about
buffer format."
::= { ibmPduExtMonitorEntry 2 }
ibmPduExtHumidityBuffer OBJECT-TYPE
SYNTAX IbmPduEnvBuf
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Buffer that contains the humdity records. Refer to
description of IbmPduEnvBuf for information about
buffer format."
::= { ibmPduExtMonitorEntry 3 }
ibmPduExtThermalThresholdWarning OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "The value of the warning threshold for
the given temperature returned in Celsius."
::= { ibmPduExtMonitorEntry 4 }
ibmPduExtThermalThresholdCritical OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "The value of the critical threshold for
the given temperature returned in Celsius."
::= { ibmPduExtMonitorEntry 5 }
ibmPduExtHumidityThresholdWarning OBJECT-TYPE
SYNTAX Unsigned32(0..100)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "The value of the warning threshold for
the given humidity returned as a percent."
::= { ibmPduExtMonitorEntry 6 }
ibmPduExtHumidityThresholdCritical OBJECT-TYPE
SYNTAX Unsigned32(0..100)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "The value of the critical threshold for
the given humidity returned as a percent."
::= { ibmPduExtMonitorEntry 7 }
ibmPduExtThermalLastReading OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The value of the most recent temperature reading for
the external temperature sensor, in degrees Celsius.
If no external temperature sensor is connected, a
value of -1 should be returned."
::= { ibmPduExtMonitorEntry 8 }
ibmPduExtHumidityLastReading OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The value of the most recent humidity reading for
the external humidity sensor, as a percentage. If no
external humidity sensor is connected, a value of -1
should be returned."
::= { ibmPduExtMonitorEntry 9 }
-- ////////////////////////////////////////////////////////
-- ////////////////////// Traps ///////////////////////////
-- ////////////////////////////////////////////////////////
ibmPduObjectIndex OBJECT-TYPE
SYNTAX Unsigned32(0..255)
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION "Index in the table of an outlet or external meter"
::= { ibmPduTrapDataObjects 1 }
ibmPduObjectType OBJECT-TYPE
SYNTAX INTEGER { pdu(0),
outlet(1),
extMeter(2)
}
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION "The type of object represented in the trap."
::= { ibmPduTrapDataObjects 2 }
ibmPduObjectID OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION "Unique ID or name of the object represented in the trap."
::= { ibmPduTrapDataObjects 3 }
ibmPduSeverity OBJECT-TYPE
SYNTAX INTEGER { informational(0),
warning(1),
critical(2)
}
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION "Severity of the trap."
::= { ibmPduTrapDataObjects 4 }
ibmPduTrapDescription OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION "Textual description of the trap."
::= { ibmPduTrapDataObjects 5 }
ibmPduState OBJECT-TYPE
SYNTAX INTEGER { powerOff(0),
powerOn(1),
reboot(2),
delayedOn(3),
delayedOff(4)
}
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION "State change for management of an outlet."
::= { ibmPduTrapDataObjects 6 }
ibmPduVoltageWarning OBJECT-TYPE
SYNTAX INTEGER { voltageNormal(0),
voltageOutOfRange(1)
}
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION "Voltage Warning."
::= { ibmPduTrapDataObjects 7 }
ibmPduCurrentThreshold NOTIFICATION-TYPE
OBJECTS { ibmPduObjectIndex,
ibmPduObjectType,
ibmPduObjectID,
ibmPduSeverity,
ibmPduTrapDescription
}
STATUS current
DESCRIPTION "Threshold for Current events set by the user."
::= { ibmPduTraps 1 }
ibmPduThermalThreshold NOTIFICATION-TYPE
OBJECTS { ibmPduObjectIndex,
ibmPduObjectType,
ibmPduObjectID,
ibmPduSeverity,
ibmPduTrapDescription
}
STATUS current
DESCRIPTION "Threshold for thermal events set by the user."
::= { ibmPduTraps 2 }
ibmPduHumidityThreshold NOTIFICATION-TYPE
OBJECTS { ibmPduObjectIndex,
ibmPduObjectType,
ibmPduObjectID,
ibmPduSeverity,
ibmPduTrapDescription
}
STATUS current
DESCRIPTION "Threshold for humidity events set by the user."
::= { ibmPduTraps 3 }
ibmPduOutletStateChange NOTIFICATION-TYPE
OBJECTS { ibmPduObjectIndex,
ibmPduObjectID,
ibmPduState,
ibmPduTrapDescription
}
STATUS current
DESCRIPTION "Outlet state has changed."
::= { ibmPduTraps 4 }
ibmPduFirmwareChanged NOTIFICATION-TYPE
OBJECTS { ibmPduObjectID,
ibmPduTrapDescription
}
STATUS current
DESCRIPTION "PDU firmware has been updated."
::= { ibmPduTraps 5 }
ibmPduDeviceStateChange NOTIFICATION-TYPE
OBJECTS { ibmPduObjectID,
ibmPduState,
ibmPduTrapDescription
}
STATUS current
DESCRIPTION "Device state has changed."
::= { ibmPduTraps 6 }
ibmPduACVoltageWarning NOTIFICATION-TYPE
OBJECTS { ibmPduObjectID,
ibmPduVoltageWarning
}
STATUS current
DESCRIPTION "AC Voltage +/- 15% Normal."
::= { ibmPduTraps 7 }
-- ////////////////////////////////////////////////////////
-- /////////////////// Compliances ////////////////////////
-- ////////////////////////////////////////////////////////
ibmPduDeviceGroup OBJECT-GROUP
OBJECTS { ibmPduBufferTagValue,
ibmPduSampleRate,
ibmPduBufferVersion,
ibmPduBufferEntries,
ibmPduSoftwareVersion,
ibmPduMachineType,
ibmPduModelNumber,
ibmPduPartNumber,
ibmPduName,
ibmPduManufacturer,
ibmPduSerialNumber,
ibmPduDescription,
ibmPduUrl,
ibmPduReboot,
ibmPduPhaseCount,
ibmPduPhaseAvgPower,
ibmPduPhaseMaxPower,
ibmPduPhaseLastPowerReading,
ibmPduThermalBuffer,
ibmPduHumidityBuffer,
ibmPduThermalThresholdWarning,
ibmPduThermalThresholdCritical,
ibmPduHumidityThresholdWarning,
ibmPduHumidityThresholdCritical,
ibmPduThermalLastReading,
ibmPduHumidityLastReading
}
STATUS current
DESCRIPTION "A group of objects containing base information about
the overall PDU."
::= { ibmPduGroups 1 }
ibmPduImageGroup OBJECT-GROUP
OBJECTS { ibmPduLogo,
ibmPduDeviceFront,
ibmPduDeviceRear
}
STATUS current
DESCRIPTION "A group of objects containing image information
of the PDU."
::= { ibmPduGroups 2 }
ibmPduLocationGroup OBJECT-GROUP
OBJECTS { ibmPduTelephoneNumber,
ibmPduCountryRegion,
ibmPduStreetAddress,
ibmPduCity,
ibmPduStateProvince,
ibmPduPostalCode,
ibmPduBuilding,
ibmPduFloor,
ibmPduRoomNumber,
ibmPduRow,
ibmPduAisle,
ibmPduDisplaceHeight,
ibmPduAltitude,
ibmPduOtherInfo
}
STATUS current
DESCRIPTION "A group of objects containing ibmLocation information
of the PDU."
::= { ibmPduGroups 3 }
ibmPduOutletGroup OBJECT-GROUP
OBJECTS { ibmPduOutletCount,
ibmPduOutletName,
ibmPduOutletType,
ibmPduOutletDescription,
ibmPduOutletAvgPower,
ibmPduOutletMaxPower,
ibmPduOutletCurrent,
ibmPduOutletMaxCapacity,
ibmPduOutletCurrentThresholdWarning,
ibmPduOutletCurrentThresholdCritical,
ibmPduOutletState,
ibmPduOutletGroupIndex,
ibmPduOutletLastPowerReading,
ibmPduOutletIndividualDelayTimer,
ibmPduOutletGlobalDelayTimer
}
STATUS current
DESCRIPTION "A group of objects containing information about
the outlets in a PDU."
::= { ibmPduGroups 4 }
ibmPduExtMonitorGroup OBJECT-GROUP
OBJECTS { ibmPduExtMonitorCount,
ibmPduExtThermalBuffer,
ibmPduExtHumidityBuffer,
ibmPduExtThermalThresholdWarning,
ibmPduExtThermalThresholdCritical,
ibmPduExtHumidityThresholdWarning,
ibmPduOutletCurrentThresholdCritical,
ibmPduExtHumidityThresholdCritical,
ibmPduExtThermalLastReading,
ibmPduExtHumidityLastReading
}
STATUS current
DESCRIPTION "A group of objects containing information about
external thermal and humidity monitors connected
to the PDU."
::= { ibmPduGroups 5 }
ibmPduTrapDataGroup OBJECT-GROUP
OBJECTS { ibmPduObjectIndex,
ibmPduObjectType,
ibmPduObjectID,
ibmPduSeverity,
ibmPduState,
ibmPduTrapDescription,
ibmPduVoltageWarning
}
STATUS current
DESCRIPTION "A group of object containing data for traps."
::= { ibmPduGroups 6 }
ibmPduTrapGroup NOTIFICATION-GROUP
NOTIFICATIONS { ibmPduCurrentThreshold,
ibmPduThermalThreshold,
ibmPduHumidityThreshold,
ibmPduOutletStateChange,
ibmPduFirmwareChanged,
ibmPduDeviceStateChange,
ibmPduACVoltageWarning
}
STATUS current
DESCRIPTION "A group of objects containing information about
traps of the PDU, its outlets, and external meters."
::= { ibmPduGroups 7 }
ibmPduCompliance MODULE-COMPLIANCE
STATUS current
DESCRIPTION "The requirements for conformance to the PDU-MIB."
MODULE -- this module
MANDATORY-GROUPS {
ibmPduDeviceGroup,
ibmPduLocationGroup,
ibmPduImageGroup,
ibmPduOutletGroup,
ibmPduExtMonitorGroup,
ibmPduTrapDataGroup,
ibmPduTrapGroup
}
::= { ibmPduCompliances 8 }
END