-- MIB table for P8552
|
||
--
|
||
-- v4.0 for firmware 4-5-8.x, 2015-09-08
|
||
-----------------------------------------------------------------------
|
||
P8552-MIB DEFINITIONS ::= BEGIN
|
||
|
||
|
||
IMPORTS
|
||
enterprises
|
||
FROM RFC1155-SMI
|
||
OBJECT-TYPE
|
||
FROM RFC-1212
|
||
TRAP-TYPE
|
||
FROM RFC-1215;
|
||
|
||
DisplayString ::= OCTET STRING
|
||
|
||
|
||
comet OBJECT IDENTIFIER ::= { enterprises 22626 }
|
||
products OBJECT IDENTIFIER ::= { comet 1 }
|
||
p8552 OBJECT IDENTIFIER ::= { products 5 }
|
||
global OBJECT IDENTIFIER ::= { p8552 1 }
|
||
channels OBJECT IDENTIFIER ::= { p8552 2 }
|
||
channel1 OBJECT IDENTIFIER ::= { channels 1 }
|
||
channel2 OBJECT IDENTIFIER ::= { channels 2 }
|
||
channel3 OBJECT IDENTIFIER ::= { channels 3 }
|
||
channel4 OBJECT IDENTIFIER ::= { channels 4 }
|
||
bin1 OBJECT IDENTIFIER ::= { channels 6 }
|
||
bin2 OBJECT IDENTIFIER ::= { channels 7 }
|
||
bin3 OBJECT IDENTIFIER ::= { channels 8 }
|
||
traps OBJECT IDENTIFIER ::= { p8552 3 }
|
||
tables OBJECT IDENTIFIER ::= { p8552 4 }
|
||
|
||
|
||
-----------------------------------------------------------------------
|
||
-- global
|
||
-----------------------------------------------------------------------
|
||
sensorName OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..68))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Device name"
|
||
::= { global 1 }
|
||
|
||
serialNumber OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..16))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Serial number"
|
||
::= { global 2 }
|
||
|
||
deviceType OBJECT-TYPE
|
||
SYNTAX INTEGER (0..65534)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Device type"
|
||
::= { global 3 }
|
||
|
||
|
||
-----------------------------------------------------------------------
|
||
-- channels
|
||
-----------------------------------------------------------------------
|
||
|
||
-----------------------------------------------------------------------
|
||
-- channel1
|
||
-----------------------------------------------------------------------
|
||
ch1Name OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..16))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 1 name"
|
||
::= { channel1 1 }
|
||
|
||
ch1Val OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..8))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 1 value"
|
||
::= { channel1 2 }
|
||
|
||
ch1IntVal OBJECT-TYPE
|
||
SYNTAX INTEGER (-550..1250)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 1 value * 10 (12.5 dgr C = 125)"
|
||
::= { channel1 3 }
|
||
|
||
ch1Alarm OBJECT-TYPE
|
||
SYNTAX INTEGER (0..2)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Alarm on channel 1; 0 - No alarm, 1 - Alarm High, 2 - Alarm Low"
|
||
::= { channel1 4 }
|
||
|
||
ch1LimHi OBJECT-TYPE
|
||
SYNTAX INTEGER (-550..1250)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 1 upper alarm limit (value * 10)"
|
||
::= { channel1 5 }
|
||
|
||
ch1LimLo OBJECT-TYPE
|
||
SYNTAX INTEGER (-550..1250)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 1 low alarm limit (value * 10)"
|
||
::= { channel1 6 }
|
||
|
||
ch1LimHyst OBJECT-TYPE
|
||
SYNTAX INTEGER (-550..1250)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 1 hysteressis (value * 10)"
|
||
::= { channel1 7 }
|
||
|
||
ch1LimDelay OBJECT-TYPE
|
||
SYNTAX INTEGER (0..65534)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 1 delay [sec]"
|
||
::= { channel1 8 }
|
||
|
||
ch1Unit OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..8))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Unit on channel 1; <20>C, <20>F, %RH"
|
||
::= { channel1 9 }
|
||
|
||
ch1AlarmStr OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..8))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Alarm on channel 1; none, high, low"
|
||
::= { channel1 10 }
|
||
|
||
ch1Min OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..8))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 1 minimal value"
|
||
::= { channel1 11 }
|
||
|
||
ch1Max OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..8))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 1 maximal value"
|
||
::= { channel1 12 }
|
||
|
||
|
||
-----------------------------------------------------------------------
|
||
-- channel2
|
||
-----------------------------------------------------------------------
|
||
ch2Name OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..16))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 2 name"
|
||
::= { channel2 1 }
|
||
|
||
ch2Val OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..8))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 2 value"
|
||
::= { channel2 2 }
|
||
|
||
ch2IntVal OBJECT-TYPE
|
||
SYNTAX INTEGER (-550..1250)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 2 value * 10 (12.5 dgr C = 125)"
|
||
::= { channel2 3 }
|
||
|
||
ch2Alarm OBJECT-TYPE
|
||
SYNTAX INTEGER (0..2)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Alarm on channel 2; 0 - No alarm, 1 - Alarm High, 2 - Alarm Low"
|
||
::= { channel2 4 }
|
||
|
||
ch2LimHi OBJECT-TYPE
|
||
SYNTAX INTEGER (-550..1250)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 2 upper alarm limit (value * 10)"
|
||
::= { channel2 5 }
|
||
|
||
ch2LimLo OBJECT-TYPE
|
||
SYNTAX INTEGER (-550..1250)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 2 low alarm limit (value * 10)"
|
||
::= { channel2 6 }
|
||
|
||
ch2LimHyst OBJECT-TYPE
|
||
SYNTAX INTEGER (-550..1250)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 2 hysteressis (value * 10)"
|
||
::= { channel2 7 }
|
||
|
||
ch2LimDelay OBJECT-TYPE
|
||
SYNTAX INTEGER (0..65534)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 2 delay [sec]"
|
||
::= { channel2 8 }
|
||
|
||
ch2Unit OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..8))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Unit on channel 2; <20>C, <20>F, %RH"
|
||
::= { channel2 9 }
|
||
|
||
ch2AlarmStr OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..8))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Alarm on channel 2; none, high, low"
|
||
::= { channel2 10 }
|
||
|
||
ch2Min OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..8))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 2 minimal value"
|
||
::= { channel2 11 }
|
||
|
||
ch2Max OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..8))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 2 maximal value"
|
||
::= { channel2 12 }
|
||
|
||
|
||
-----------------------------------------------------------------------
|
||
-- channel3
|
||
-----------------------------------------------------------------------
|
||
ch3Name OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..16))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 3 name"
|
||
::= { channel3 1 }
|
||
|
||
ch3Val OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..8))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 3 value"
|
||
::= { channel3 2 }
|
||
|
||
ch3IntVal OBJECT-TYPE
|
||
SYNTAX INTEGER (-550..1250)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 3 value * 10 (12.5 dgr C = 125)"
|
||
::= { channel3 3 }
|
||
|
||
ch3Alarm OBJECT-TYPE
|
||
SYNTAX INTEGER (0..2)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Alarm on channel 3; 0 - No alarm, 1 - Alarm High, 2 - Alarm Low"
|
||
::= { channel3 4 }
|
||
|
||
ch3LimHi OBJECT-TYPE
|
||
SYNTAX INTEGER (-550..1250)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 3 upper alarm limit (value * 10)"
|
||
::= { channel3 5 }
|
||
|
||
ch3LimLo OBJECT-TYPE
|
||
SYNTAX INTEGER (-550..1250)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 3 low alarm limit (value * 10)"
|
||
::= { channel3 6 }
|
||
|
||
ch3LimHyst OBJECT-TYPE
|
||
SYNTAX INTEGER (-550..1250)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 3 hysteressis (value * 10)"
|
||
::= { channel3 7 }
|
||
|
||
ch3LimDelay OBJECT-TYPE
|
||
SYNTAX INTEGER (0..65534)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 3 delay [sec]"
|
||
::= { channel3 8 }
|
||
|
||
ch3Unit OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..8))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Unit on channel 3; <20>C, <20>F, %RH"
|
||
::= { channel3 9 }
|
||
|
||
ch3AlarmStr OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..8))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Alarm on channel 3; none, high, low"
|
||
::= { channel3 10 }
|
||
|
||
ch3Min OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..8))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 3 minimal value"
|
||
::= { channel3 11 }
|
||
|
||
ch3Max OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..8))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 3 maximal value"
|
||
::= { channel3 12 }
|
||
|
||
|
||
-----------------------------------------------------------------------
|
||
-- channel4
|
||
-----------------------------------------------------------------------
|
||
ch4Name OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..16))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 4 name"
|
||
::= { channel4 1 }
|
||
|
||
ch4Val OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..8))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 4 value"
|
||
::= { channel4 2 }
|
||
|
||
ch4IntVal OBJECT-TYPE
|
||
SYNTAX INTEGER (-550..1250)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 4 value * 10 (12.5 dgr C = 125)"
|
||
::= { channel4 3 }
|
||
|
||
ch4Alarm OBJECT-TYPE
|
||
SYNTAX INTEGER (0..2)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Alarm on channel 4; 0 - No alarm, 1 - Alarm High, 2 - Alarm Low"
|
||
::= { channel4 4 }
|
||
|
||
ch4LimHi OBJECT-TYPE
|
||
SYNTAX INTEGER (-550..1250)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 4 upper alarm limit (value * 10)"
|
||
::= { channel4 5 }
|
||
|
||
ch4LimLo OBJECT-TYPE
|
||
SYNTAX INTEGER (-550..1250)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 4 low alarm limit (value * 10)"
|
||
::= { channel4 6 }
|
||
|
||
ch4LimHyst OBJECT-TYPE
|
||
SYNTAX INTEGER (-550..1250)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 4 hysteressis (value * 10)"
|
||
::= { channel4 7 }
|
||
|
||
ch4LimDelay OBJECT-TYPE
|
||
SYNTAX INTEGER (0..65534)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 4 delay [sec]"
|
||
::= { channel4 8 }
|
||
|
||
ch4Unit OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..8))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Unit on channel 4; <20>C, <20>F, %RH"
|
||
::= { channel4 9 }
|
||
|
||
ch4AlarmStr OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..8))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Alarm on channel 4; none, high, low"
|
||
::= { channel4 10 }
|
||
|
||
ch4Min OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..8))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 4 minimal value"
|
||
::= { channel4 11 }
|
||
|
||
ch4Max OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..8))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 4 maximal value"
|
||
::= { channel4 12 }
|
||
|
||
|
||
-----------------------------------------------------------------------
|
||
-- bin1
|
||
-----------------------------------------------------------------------
|
||
bin1Name OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..16))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "BIN Input 1 name"
|
||
::= { bin1 1 }
|
||
|
||
bin1Val OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..8))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "BIN Input 1 value"
|
||
::= { bin1 2 }
|
||
|
||
bin1IntVal OBJECT-TYPE
|
||
SYNTAX INTEGER (-550..1250)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "BIN Input 1 value - Integer"
|
||
::= { bin1 3 }
|
||
|
||
bin1AlarmStr OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..8))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Alarm on BIN Input 1; none, active"
|
||
::= { bin1 4 }
|
||
|
||
bin1Alarm OBJECT-TYPE
|
||
SYNTAX INTEGER (0..1)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Alarm on BIN Input 1; 0 - No alarm, 1 - Alarm active"
|
||
::= { bin1 5 }
|
||
|
||
|
||
-----------------------------------------------------------------------
|
||
-- bin2
|
||
-----------------------------------------------------------------------
|
||
bin2Name OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..16))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "BIN Input 2 name"
|
||
::= { bin2 1 }
|
||
|
||
bin2Val OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..8))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "BIN Input 2 value"
|
||
::= { bin2 2 }
|
||
|
||
bin2IntVal OBJECT-TYPE
|
||
SYNTAX INTEGER (-550..1250)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "BIN Input 2 value - Integer"
|
||
::= { bin2 3 }
|
||
|
||
bin2AlarmStr OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..8))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Alarm on BIN Input 2; none, active"
|
||
::= { bin2 4 }
|
||
|
||
bin2Alarm OBJECT-TYPE
|
||
SYNTAX INTEGER (0..1)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Alarm on BIN Input 2; 0 - No alarm, 1 - Alarm active"
|
||
::= { bin2 5 }
|
||
|
||
|
||
-----------------------------------------------------------------------
|
||
-- bin3
|
||
-----------------------------------------------------------------------
|
||
bin3Name OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..16))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "BIN Input 3 name"
|
||
::= { bin3 1 }
|
||
|
||
bin3Val OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..8))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "BIN Input 3 value"
|
||
::= { bin3 2 }
|
||
|
||
bin3IntVal OBJECT-TYPE
|
||
SYNTAX INTEGER (-550..1250)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "BIN Input 3 value - Integer"
|
||
::= { bin3 3 }
|
||
|
||
bin3AlarmStr OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..8))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Alarm on BIN Input 3; none, active"
|
||
::= { bin3 4 }
|
||
|
||
bin3Alarm OBJECT-TYPE
|
||
SYNTAX INTEGER (0..1)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Alarm on BIN Input 3; 0 - No alarm, 1 - Alarm active"
|
||
::= { bin3 5 }
|
||
|
||
|
||
-----------------------------------------------------------------------
|
||
-- traps string
|
||
-----------------------------------------------------------------------
|
||
messageString OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..32))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Message giving more detailed information on alarms"
|
||
::= { traps 1 }
|
||
|
||
|
||
-----------------------------------------------------------------------
|
||
-- tables
|
||
-----------------------------------------------------------------------
|
||
historyTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HistoryEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "Table of the history values"
|
||
::= { tables 1 }
|
||
|
||
historyEntry OBJECT-TYPE
|
||
SYNTAX HistoryEntry
|
||
ACCESS not-accessible
|
||
STATUS optional
|
||
DESCRIPTION "History values entries"
|
||
INDEX { ch1value }
|
||
::= { historyTable 1 }
|
||
|
||
HistoryEntry ::=
|
||
SEQUENCE {
|
||
ch1value
|
||
INTEGER,
|
||
ch2value
|
||
INTEGER,
|
||
ch3value
|
||
INTEGER,
|
||
ch4value
|
||
INTEGER
|
||
}
|
||
|
||
ch1value OBJECT-TYPE
|
||
SYNTAX INTEGER (-550..1250)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 1 history reading"
|
||
::= { historyEntry 1 }
|
||
|
||
ch2value OBJECT-TYPE
|
||
SYNTAX INTEGER (-550..1250)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 2 history reading"
|
||
::= { historyEntry 2 }
|
||
|
||
ch3value OBJECT-TYPE
|
||
SYNTAX INTEGER (-550..1250)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 3 history reading"
|
||
::= { historyEntry 3 }
|
||
|
||
ch4value OBJECT-TYPE
|
||
SYNTAX INTEGER (-550..1250)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Channel 4 history reading"
|
||
::= { historyEntry 4 }
|
||
|
||
|
||
-----------------------------------------------------------------------
|
||
-- traps definition
|
||
-----------------------------------------------------------------------
|
||
trapTest TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { sensorName, messageString }
|
||
DESCRIPTION
|
||
"Testing trap, testing trap by TSensor software"
|
||
::= 0
|
||
|
||
trapNTPError TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { sensorName, messageString }
|
||
DESCRIPTION
|
||
"Error on time synchronisation via NTP"
|
||
::= 1
|
||
|
||
trapEmailErrLogin TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { sensorName, messageString }
|
||
DESCRIPTION
|
||
"SMTP error - unknown server"
|
||
::= 2
|
||
|
||
trapEmailErrAuth TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { sensorName, messageString }
|
||
DESCRIPTION
|
||
"SMTP error - authentication error"
|
||
::= 3
|
||
|
||
trapEmailErrSome TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { sensorName, messageString }
|
||
DESCRIPTION
|
||
"SMTP error - error during communication with server, unexpected return code"
|
||
::= 4
|
||
|
||
trapEmailErrSocket TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { sensorName, messageString }
|
||
DESCRIPTION
|
||
"SMTP error - socket error, server is not available"
|
||
::= 5
|
||
|
||
trapEmailErrDNS TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { sensorName, messageString }
|
||
DESCRIPTION
|
||
"SMTP error - DNS error"
|
||
::= 6
|
||
|
||
trapSOAPErrFile TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { sensorName, messageString }
|
||
DESCRIPTION
|
||
"SOAP error - file SOAP not found"
|
||
::= 7
|
||
|
||
trapSOAPErrDNS TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { sensorName, messageString }
|
||
DESCRIPTION
|
||
"SOAP error - DNS error"
|
||
::= 8
|
||
|
||
trapSOAPErrSocket TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { sensorName, messageString }
|
||
DESCRIPTION
|
||
"SOAP error - socket error, server is not available"
|
||
::= 9
|
||
|
||
trapSOAPErrDelivery TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { sensorName, messageString }
|
||
DESCRIPTION
|
||
"SOAP error - delivery error, wrong return code from server"
|
||
::= 10
|
||
|
||
trapCh1HighAlarm TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { ch1Name, ch1Val, ch1Alarm, sensorName, messageString }
|
||
DESCRIPTION
|
||
"Trap for high alarm on Channel 1"
|
||
::= 11
|
||
|
||
trapCh2HighAlarm TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { ch2Name, ch2Val, ch2Alarm, sensorName, messageString }
|
||
DESCRIPTION
|
||
"Trap for high alarm on Channel 2"
|
||
::= 12
|
||
|
||
trapCh3HighAlarm TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { ch3Name, ch3Val, ch3Alarm, sensorName, messageString }
|
||
DESCRIPTION
|
||
"Trap for high alarm on Channel 3"
|
||
::= 13
|
||
|
||
trapCh4HighAlarm TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { ch4Name, ch4Val, ch4Alarm, sensorName, messageString }
|
||
DESCRIPTION
|
||
"Trap for high alarm on Channel 4"
|
||
::= 14
|
||
|
||
trapCh1LowAlarm TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { ch1Name, ch1Val, ch1Alarm, sensorName, messageString }
|
||
DESCRIPTION
|
||
"Trap for low alarm on Channel 1"
|
||
::= 21
|
||
|
||
trapCh2LowAlarm TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { ch2Name, ch2Val, ch2Alarm, sensorName, messageString }
|
||
DESCRIPTION
|
||
"Trap for low alarm on Channel 2"
|
||
::= 22
|
||
|
||
trapCh3LowAlarm TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { ch3Name, ch3Val, ch3Alarm, sensorName, messageString }
|
||
DESCRIPTION
|
||
"Trap for low alarm on Channel 3"
|
||
::= 23
|
||
|
||
trapCh4LowAlarm TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { ch4Name, ch4Val, ch4Alarm, sensorName, messageString }
|
||
DESCRIPTION
|
||
"Trap for low alarm on Channel 4"
|
||
::= 24
|
||
|
||
trapCh1ClrAlarm TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { ch1Name, ch1Val, ch1Alarm, sensorName, messageString }
|
||
DESCRIPTION
|
||
"Trap for clearing alarm on Channel 1"
|
||
::= 31
|
||
|
||
trapCh2ClrAlarm TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { ch2Name, ch2Val, ch2Alarm, sensorName, messageString }
|
||
DESCRIPTION
|
||
"Trap for clearing alarm on Channel 2"
|
||
::= 32
|
||
|
||
trapCh3ClrAlarm TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { ch3Name, ch3Val, ch3Alarm, sensorName, messageString }
|
||
DESCRIPTION
|
||
"Trap for clearing alarm on Channel 3"
|
||
::= 33
|
||
|
||
trapCh4ClrAlarm TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { ch4Name, ch4Val, ch4Alarm, sensorName, messageString }
|
||
DESCRIPTION
|
||
"Trap for clearing alarm on Channel 4"
|
||
::= 34
|
||
|
||
trapCh1Error TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { ch1Name, ch1Val, ch1Alarm, sensorName, messageString }
|
||
DESCRIPTION
|
||
"Trap for error on Channel 1"
|
||
::= 41
|
||
|
||
trapCh2Error TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { ch2Name, ch2Val, ch2Alarm, sensorName, messageString }
|
||
DESCRIPTION
|
||
"Trap for error on Channel 2"
|
||
::= 42
|
||
|
||
trapCh3Error TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { ch3Name, ch3Val, ch3Alarm, sensorName, messageString }
|
||
DESCRIPTION
|
||
"Trap for error on Channel 3"
|
||
::= 43
|
||
|
||
trapCh4Error TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { ch4Name, ch4Val, ch4Alarm, sensorName, messageString }
|
||
DESCRIPTION
|
||
"Trap for error on Channel 4"
|
||
::= 44
|
||
|
||
trapBin1Alarm TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { bin1Name, bin1Val, bin1Alarm, sensorName, messageString }
|
||
DESCRIPTION
|
||
"Trap for alarm on Bin 1"
|
||
::= 51
|
||
|
||
trapBin2Alarm TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { bin2Name, bin2Val, bin2Alarm, sensorName, messageString }
|
||
DESCRIPTION
|
||
"Trap for alarm on Bin 2"
|
||
::= 52
|
||
|
||
trapBin3Alarm TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { bin3Name, bin3Val, bin3Alarm, sensorName, messageString }
|
||
DESCRIPTION
|
||
"Trap for alarm on Bin 3"
|
||
::= 53
|
||
|
||
trapBin1ClrAlarm TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { bin1Name, bin1Val, bin1Alarm, sensorName, messageString }
|
||
DESCRIPTION
|
||
"Trap for clearing alarm on Bin 1"
|
||
::= 61
|
||
|
||
trapBin2ClrAlarm TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { bin2Name, bin2Val, bin2Alarm, sensorName, messageString }
|
||
DESCRIPTION
|
||
"Trap for clearing alarm on Bin 2"
|
||
::= 62
|
||
|
||
trapBin3ClrAlarm TRAP-TYPE
|
||
ENTERPRISE comet
|
||
VARIABLES { bin3Name, bin3Val, bin3Alarm, sensorName, messageString }
|
||
DESCRIPTION
|
||
"Trap for clearing alarm on Bin 3"
|
||
::= 63
|
||
|
||
|
||
END
|
||
|