Observium_CE/mibs/argus/Argus-MIB

1729 lines
59 KiB
Plaintext

Argus-MIB DEFINITIONS ::= BEGIN
--==========================================================================
-- ARGUS.MIB Rev B
--
-- NOTE: Refer to RFC2578 for the formal definition of the SNMPv2-SMI MIB.
--
-- Changes:
--
-- November 3, 2008
--
-- The following new definitions were added:
-- Resync
-- Alarm Trigger
-- Time stamp
--
-- Subtyping removed from sequence definitions.
--==========================================================================
IMPORTS
MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE, enterprises
FROM SNMPv2-SMI
DisplayString
FROM SNMPv2-TC;
argus MODULE-IDENTITY
LAST-UPDATED "200811030000Z"
ORGANIZATION "Argus Technologies"
CONTACT-INFO
" Randy Dahlgren
Postal: Argus Technologies
5700 Sidley Street
Vancouver, BC V5J 5E5
Canada
Tel: 1-604-436-5900
Fax: 1-604-436-1233
E-mail: rdahlgren@argus.ca"
DESCRIPTION
"This MIB defines the information block(s) available in system controllers
as defined by the following list:
- dcPwrSysDevice: the SM-series of controllers"
::= { enterprises 7309 }
dcpower OBJECT IDENTIFIER ::= { argus 4 }
dcPwrSysDevice OBJECT IDENTIFIER ::= { dcpower 1 }
dcPwrSysVariable OBJECT IDENTIFIER ::= { dcPwrSysDevice 1 }
dcPwrSysString OBJECT IDENTIFIER ::= { dcPwrSysDevice 2 }
dcPwrSysTraps OBJECT IDENTIFIER ::= { dcPwrSysDevice 3 }
dcPwrSysOutputsTbl OBJECT IDENTIFIER ::= { dcPwrSysDevice 4 }
dcPwrSysRelayTbl OBJECT IDENTIFIER ::= { dcPwrSysOutputsTbl 1 }
dcPwrSysAnalogOpTbl OBJECT IDENTIFIER ::= { dcPwrSysOutputsTbl 2 }
dcPwrSysAlrmsTbl OBJECT IDENTIFIER ::= { dcPwrSysDevice 5 }
dcPwrSysRectAlrmTbl OBJECT IDENTIFIER ::= { dcPwrSysAlrmsTbl 1 }
dcPwrSysDigAlrmTbl OBJECT IDENTIFIER ::= { dcPwrSysAlrmsTbl 2 }
dcPwrSysCurrAlrmTbl OBJECT IDENTIFIER ::= { dcPwrSysAlrmsTbl 3 }
dcPwrSysVoltAlrmTbl OBJECT IDENTIFIER ::= { dcPwrSysAlrmsTbl 4 }
dcPwrSysBattAlrmTbl OBJECT IDENTIFIER ::= { dcPwrSysAlrmsTbl 5 }
dcPwrSysTempAlrmTbl OBJECT IDENTIFIER ::= { dcPwrSysAlrmsTbl 6 }
dcPwrSysCustomAlrmTbl OBJECT IDENTIFIER ::= { dcPwrSysAlrmsTbl 7 }
dcPwrSysMiscAlrmTbl OBJECT IDENTIFIER ::= { dcPwrSysAlrmsTbl 8 }
dcPwrSysCtrlAlrmTbl OBJECT IDENTIFIER ::= { dcPwrSysAlrmsTbl 9 }
dcPwrSysAdioAlrmTbl OBJECT IDENTIFIER ::= { dcPwrSysAlrmsTbl 10 }
dcPwrSysConvAlrmTbl OBJECT IDENTIFIER ::= { dcPwrSysAlrmsTbl 11 }
dcPwrSysInputsTbl OBJECT IDENTIFIER ::= { dcPwrSysDevice 6 }
dcPwrSysDigIpTbl OBJECT IDENTIFIER ::= { dcPwrSysInputsTbl 1 }
dcPwrSysCntrlrIpTbl OBJECT IDENTIFIER ::= { dcPwrSysInputsTbl 2 }
dcPwrSysRectIpTbl OBJECT IDENTIFIER ::= { dcPwrSysInputsTbl 3 }
dcPwrSysCustomIpTbl OBJECT IDENTIFIER ::= { dcPwrSysInputsTbl 4 }
dcPwrSysConvIpTbl OBJECT IDENTIFIER ::= { dcPwrSysInputsTbl 5 }
dcPwrSysTimerIpTbl OBJECT IDENTIFIER ::= { dcPwrSysInputsTbl 6 }
dcPwrSysCounterIpTbl OBJECT IDENTIFIER ::= { dcPwrSysInputsTbl 7 }
dcPwrExternalControls OBJECT IDENTIFIER ::= { dcPwrSysDevice 8 }
dcPwrVarbindNameReference OBJECT IDENTIFIER ::= { dcPwrSysDevice 9 }
--==========================================================================
-- Start of variables
--==========================================================================
dcPwrSysChargeVolts OBJECT-TYPE
SYNTAX INTEGER (-1000000000..1000000000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Battery Charge Voltage. The integer value represent a two digit fix decimal (Value = real voltage * 100) in Volt"
::= { dcPwrSysVariable 1 }
dcPwrSysDischargeVolts OBJECT-TYPE
SYNTAX INTEGER (-1000000000..1000000000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Battery Discharge Voltage. The integer value represent a two digit fix decimal (Value = real voltage * 100) in Volt"
::= { dcPwrSysVariable 2 }
dcPwrSysChargeAmps OBJECT-TYPE
SYNTAX INTEGER (-1000000000..1000000000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Battery Charge Current. The integer value represent a two digit fix decimal (Value = real current * 100) in Amp"
::= { dcPwrSysVariable 3 }
dcPwrSysDischargeAmps OBJECT-TYPE
SYNTAX INTEGER (-1000000000..1000000000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Battery Discharge Current. The integer value represent a two digit fix decimal (Value = real current * 100) in Amp"
::= { dcPwrSysVariable 4 }
dcPwrSysMajorAlarm OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Major Alarm"
::= { dcPwrSysVariable 5 }
dcPwrSysMinorAlarm OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Minor Alarm"
::= { dcPwrSysVariable 6 }
--==========================================================================
-- Start of Strings
--==========================================================================
dcPwrSysSiteName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Site Name"
::= { dcPwrSysString 1 }
dcPwrSysSiteCity OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Site City"
::= { dcPwrSysString 2 }
dcPwrSysSiteRegion OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Site Region"
::= { dcPwrSysString 3 }
dcPwrSysSiteCountry OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Site Country"
::= { dcPwrSysString 4 }
dcPwrSysContactName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Contact Name"
::= { dcPwrSysString 5 }
dcPwrSysPhoneNumber OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Phone Number"
::= { dcPwrSysString 6 }
dcPwrSysSiteNumber OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Site Number"
::= { dcPwrSysString 7 }
dcPwrSysSystemType OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The type of system being monitored by the agent"
::= { dcPwrSysString 8 }
dcPwrSysSystemSerial OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The serial number of the monitored system"
::= { dcPwrSysString 9 }
dcPwrSysSystemNumber OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The number of the monitored system"
::= { dcPwrSysString 10 }
dcPwrSysSoftwareVersion OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The version of software running on the monitored system"
::= { dcPwrSysString 11 }
dcPwrSysSoftwareTimestamp OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The time stamp of the software running on the monitored system"
::= { dcPwrSysString 12 }
--==========================================================================
-- Start of Tables Information
--==========================================================================
--=================
-- Output table
--=================
--========================
-- Relay output sub table
--=========================
dcPwrSysRelayCount OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of relay variables in system controller relay table"
::= { dcPwrSysRelayTbl 1 }
dcPwrSysRelayTable OBJECT-TYPE
SYNTAX SEQUENCE OF DcPwrSysRelayEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A table of DC power system controller rectifier relay output variables"
::= { dcPwrSysRelayTbl 2 }
dcPwrSysRelayEntry OBJECT-TYPE
SYNTAX DcPwrSysRelayEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "An entry into the DC power system controller relay output group"
INDEX { dcPwrSysRelayIndex }
::= { dcPwrSysRelayTable 1 }
DcPwrSysRelayEntry
::= SEQUENCE {
dcPwrSysRelayIndex INTEGER,
dcPwrSysRelayName DisplayString,
dcPwrSysRelayIntegerValue INTEGER,
dcPwrSysRelayStringValue DisplayString,
dcPwrSysRelaySeverity INTEGER
}
dcPwrSysRelayIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The index of the relay variable in the power system controller relay output group"
::= { dcPwrSysRelayEntry 1 }
dcPwrSysRelayName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..30))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The description of the relay variable as reported by the DC power system controller relay output group"
::= { dcPwrSysRelayEntry 2 }
dcPwrSysRelayIntegerValue OBJECT-TYPE
SYNTAX INTEGER (-1000000000..1000000000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of the relay variable as reported by the DC power system controller relay output group"
::= { dcPwrSysRelayEntry 3 }
dcPwrSysRelayStringValue OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The string value of the relay variable as reported by the DC power system controller relay output group"
::= { dcPwrSysRelayEntry 4 }
dcPwrSysRelaySeverity OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of relay severity level of the extra variable as reported by the DC power system controller relay output group"
::= { dcPwrSysRelayEntry 5 }
--========================
-- Analog output sub table
--=========================
dcPwrSysAnalogOpCount OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of analog output variables in system controller analog output table"
::= { dcPwrSysAnalogOpTbl 1 }
dcPwrSysAnalogOpTable OBJECT-TYPE
SYNTAX SEQUENCE OF DcPwrSysAnalogOpEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A table of DC power system controller analog output variables"
::= { dcPwrSysAnalogOpTbl 2 }
dcPwrSysAnalogOpEntry OBJECT-TYPE
SYNTAX DcPwrSysAnalogOpEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "An entry into the DC power system controller analog output group"
INDEX { dcPwrSysAnalogOpIndex }
::= { dcPwrSysAnalogOpTable 1 }
DcPwrSysAnalogOpEntry
::= SEQUENCE {
dcPwrSysAnalogOpIndex INTEGER,
dcPwrSysAnalogOpName DisplayString,
dcPwrSysAnalogOpIntegerValue INTEGER,
dcPwrSysAnalogOpStringValue DisplayString,
dcPwrSysAnalogOpSeverity INTEGER
}
dcPwrSysAnalogOpIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The index of the analog variable in the power system controller analog output group"
::= { dcPwrSysAnalogOpEntry 1 }
dcPwrSysAnalogOpName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..30))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The description of the analog variable as reported by the DC power system controller analog output group"
::= { dcPwrSysAnalogOpEntry 2 }
dcPwrSysAnalogOpIntegerValue OBJECT-TYPE
SYNTAX INTEGER (-1000000000..1000000000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of the analog variable as reported by the DC power system controller analog output group"
::= { dcPwrSysAnalogOpEntry 3 }
dcPwrSysAnalogOpStringValue OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The string value of the analog variable as reported by the DC power system controller analog output group"
::= { dcPwrSysAnalogOpEntry 4 }
dcPwrSysAnalogOpSeverity OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of analog severity level of the extra variable as reported by the DC power system controller analog output group"
::= { dcPwrSysAnalogOpEntry 5 }
--=================
-- Alarm table
--=================
--============================
-- Rectifier alarm group
--============================
dcPwrSysRectAlrmCount OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of rectifier alarm variables in system controller alarm table"
::= { dcPwrSysRectAlrmTbl 1 }
dcPwrSysRectAlrmTable OBJECT-TYPE
SYNTAX SEQUENCE OF DcPwrSysRectAlrmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A table of DC power system controller rectifier alarm variables"
::= { dcPwrSysRectAlrmTbl 2 }
dcPwrSysRectAlrmEntry OBJECT-TYPE
SYNTAX DcPwrSysRectAlrmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "An entry into the DC power system controller rectifier alarm group"
INDEX { dcPwrSysRectAlrmIndex }
::= { dcPwrSysRectAlrmTable 1 }
DcPwrSysRectAlrmEntry
::= SEQUENCE {
dcPwrSysRectAlrmIndex INTEGER,
dcPwrSysRectAlrmName DisplayString,
dcPwrSysRectAlrmIntegerValue INTEGER,
dcPwrSysRectAlrmStringValue DisplayString,
dcPwrSysRectAlrmSeverity INTEGER
}
dcPwrSysRectAlrmIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The index of the alarm variable in the DC power system controller table rectifier alarm group"
::= { dcPwrSysRectAlrmEntry 1 }
dcPwrSysRectAlrmName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..30))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The description of the alarm variable as reported by the DC power system controller rectifier alarm group"
::= { dcPwrSysRectAlrmEntry 2 }
dcPwrSysRectAlrmIntegerValue OBJECT-TYPE
SYNTAX INTEGER (-1000000000..1000000000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of the alarm variable as reported by the DC power system controller rectifier alarm group"
::= { dcPwrSysRectAlrmEntry 3 }
dcPwrSysRectAlrmStringValue OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The string value of the alarm variable as reported by the DC power system controller rectifier alarm group"
::= { dcPwrSysRectAlrmEntry 4 }
dcPwrSysRectAlrmSeverity OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of alarm severity level of the extra variable as reported by the DC power system controller rectifier alarm group"
::= { dcPwrSysRectAlrmEntry 5 }
--============================
-- Digital alarm group
--============================
dcPwrSysDigAlrmCount OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of digital alarm variables in system controller alarm table"
::= { dcPwrSysDigAlrmTbl 1 }
dcPwrSysDigAlrmTable OBJECT-TYPE
SYNTAX SEQUENCE OF DcPwrSysDigAlrmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A table of DC power system controller digital alarm variables"
::= { dcPwrSysDigAlrmTbl 2 }
dcPwrSysDigAlrmEntry OBJECT-TYPE
SYNTAX DcPwrSysDigAlrmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "An entry into the DC power system controller digital alarm group"
INDEX { dcPwrSysDigAlrmIndex }
::= { dcPwrSysDigAlrmTable 1 }
DcPwrSysDigAlrmEntry
::= SEQUENCE {
dcPwrSysDigAlrmIndex INTEGER,
dcPwrSysDigAlrmName DisplayString,
dcPwrSysDigAlrmIntegerValue INTEGER,
dcPwrSysDigAlrmStringValue DisplayString,
dcPwrSysDigAlrmSeverity INTEGER
}
dcPwrSysDigAlrmIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The index of the alarm variable in the DC power system controller table digital alarm group"
::= { dcPwrSysDigAlrmEntry 1 }
dcPwrSysDigAlrmName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..30))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The description of the alarm variable as reported by the DC power system controller digital alarm group"
::= { dcPwrSysDigAlrmEntry 2 }
dcPwrSysDigAlrmIntegerValue OBJECT-TYPE
SYNTAX INTEGER (-1000000000..1000000000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of the alarm variable as reported by the DC power system controller digital alarm group"
::= { dcPwrSysDigAlrmEntry 3 }
dcPwrSysDigAlrmStringValue OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The string value of the alarm variable as reported by the DC power system controller digital alarm group"
::= { dcPwrSysDigAlrmEntry 4 }
dcPwrSysDigAlrmSeverity OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of alarm severity level of the extra variable as reported by the DC power system controller digital alarm group"
::= { dcPwrSysDigAlrmEntry 5 }
--============================
-- Current alarm group
--============================
dcPwrSysCurrAlrmCount OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of current alarm variables in system controller alarm table"
::= { dcPwrSysCurrAlrmTbl 1 }
dcPwrSysCurrAlrmTable OBJECT-TYPE
SYNTAX SEQUENCE OF DcPwrSysCurrAlrmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A table of DC power system controller current alarm variables"
::= { dcPwrSysCurrAlrmTbl 2 }
dcPwrSysCurrAlrmEntry OBJECT-TYPE
SYNTAX DcPwrSysCurrAlrmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "An entry into the DC power system controller current alarm group"
INDEX { dcPwrSysCurrAlrmIndex }
::= { dcPwrSysCurrAlrmTable 1 }
DcPwrSysCurrAlrmEntry
::= SEQUENCE {
dcPwrSysCurrAlrmIndex INTEGER,
dcPwrSysCurrAlrmName DisplayString,
dcPwrSysCurrAlrmIntegerValue INTEGER,
dcPwrSysCurrAlrmStringValue DisplayString,
dcPwrSysCurrAlrmSeverity INTEGER
}
dcPwrSysCurrAlrmIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The index of the alarm variable in the DC power system controller table current alarm group"
::= { dcPwrSysCurrAlrmEntry 1 }
dcPwrSysCurrAlrmName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..30))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The description of the alarm variable as reported by the DC power system controller current alarm group"
::= { dcPwrSysCurrAlrmEntry 2 }
dcPwrSysCurrAlrmIntegerValue OBJECT-TYPE
SYNTAX INTEGER (-1000000000..1000000000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of the alarm variable as reported by the DC power system controller current alarm group"
::= { dcPwrSysCurrAlrmEntry 3 }
dcPwrSysCurrAlrmStringValue OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The string value of the alarm variable as reported by the DC power system controller current alarm group"
::= { dcPwrSysCurrAlrmEntry 4 }
dcPwrSysCurrAlrmSeverity OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of alarm severity level of the extra variable as reported by the DC power system controller current alarm group"
::= { dcPwrSysCurrAlrmEntry 5 }
--============================
-- Voltage alarm group
--============================
dcPwrSysVoltAlrmCount OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of voltage alarm variables in system controller alarm table"
::= { dcPwrSysVoltAlrmTbl 1 }
dcPwrSysVoltAlrmTable OBJECT-TYPE
SYNTAX SEQUENCE OF DcPwrSysVoltAlrmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A table of DC power system controller voltage alarm variables"
::= { dcPwrSysVoltAlrmTbl 2 }
dcPwrSysVoltAlrmEntry OBJECT-TYPE
SYNTAX DcPwrSysVoltAlrmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "An entry into the DC power system controller voltage alarm group"
INDEX { dcPwrSysVoltAlrmIndex }
::= { dcPwrSysVoltAlrmTable 1 }
DcPwrSysVoltAlrmEntry
::= SEQUENCE {
dcPwrSysVoltAlrmIndex INTEGER,
dcPwrSysVoltAlrmName DisplayString,
dcPwrSysVoltAlrmIntegerValue INTEGER,
dcPwrSysVoltAlrmStringValue DisplayString,
dcPwrSysVoltAlrmSeverity INTEGER
}
dcPwrSysVoltAlrmIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The index of the alarm variable in the DC power system controller table voltage alarm group"
::= { dcPwrSysVoltAlrmEntry 1 }
dcPwrSysVoltAlrmName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..30))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The description of the alarm variable as reported by the DC power system controller voltage alarm group"
::= { dcPwrSysVoltAlrmEntry 2 }
dcPwrSysVoltAlrmIntegerValue OBJECT-TYPE
SYNTAX INTEGER (-1000000000..1000000000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of the alarm variable as reported by the DC power system controller voltage alarm group"
::= { dcPwrSysVoltAlrmEntry 3 }
dcPwrSysVoltAlrmStringValue OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The string value of the alarm variable as reported by the DC power system controller voltage alarm group"
::= { dcPwrSysVoltAlrmEntry 4 }
dcPwrSysVoltAlrmSeverity OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of alarm severity level of the extra variable as reported by the DC power system controller voltage alarm group"
::= { dcPwrSysVoltAlrmEntry 5 }
--============================
-- Battery alarm group
--============================
dcPwrSysBattAlrmCount OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of battery alarm variables in system controller alarm table"
::= { dcPwrSysBattAlrmTbl 1 }
dcPwrSysBattAlrmTable OBJECT-TYPE
SYNTAX SEQUENCE OF DcPwrSysBattAlrmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A table of DC power system controller battery alarm variables"
::= { dcPwrSysBattAlrmTbl 2 }
dcPwrSysBattAlrmEntry OBJECT-TYPE
SYNTAX DcPwrSysBattAlrmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "An entry into the DC power system controller battery alarm group"
INDEX { dcPwrSysBattAlrmIndex }
::= { dcPwrSysBattAlrmTable 1 }
DcPwrSysBattAlrmEntry
::= SEQUENCE {
dcPwrSysBattAlrmIndex INTEGER,
dcPwrSysBattAlrmName DisplayString,
dcPwrSysBattAlrmIntegerValue INTEGER,
dcPwrSysBattAlrmStringValue DisplayString,
dcPwrSysBattAlrmSeverity INTEGER
}
dcPwrSysBattAlrmIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The index of the alarm variable in the DC power system controller table battery alarm group"
::= { dcPwrSysBattAlrmEntry 1 }
dcPwrSysBattAlrmName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..30))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The description of the alarm variable as reported by the DC power system controller battery alarm group"
::= { dcPwrSysBattAlrmEntry 2 }
dcPwrSysBattAlrmIntegerValue OBJECT-TYPE
SYNTAX INTEGER (-1000000000..1000000000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of the alarm variable as reported by the DC power system controller battery alarm group"
::= { dcPwrSysBattAlrmEntry 3 }
dcPwrSysBattAlrmStringValue OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The string value of the alarm variable as reported by the DC power system controller battery alarm group"
::= { dcPwrSysBattAlrmEntry 4 }
dcPwrSysBattAlrmSeverity OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of alarm severity level of the extra variable as reported by the DC power system controller battery alarm group"
::= { dcPwrSysBattAlrmEntry 5 }
--============================
-- Temperature alarm group
--============================
dcPwrSysTempAlrmCount OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of temperature alarm variables in system controller alarm table"
::= { dcPwrSysTempAlrmTbl 1 }
dcPwrSysTempAlrmTable OBJECT-TYPE
SYNTAX SEQUENCE OF DcPwrSysTempAlrmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A table of DC power system controller temperature alarm variables"
::= { dcPwrSysTempAlrmTbl 2 }
dcPwrSysTempAlrmEntry OBJECT-TYPE
SYNTAX DcPwrSysTempAlrmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "An entry into the DC power system controller temperature alarm group"
INDEX { dcPwrSysTempAlrmIndex }
::= { dcPwrSysTempAlrmTable 1 }
DcPwrSysTempAlrmEntry
::= SEQUENCE {
dcPwrSysTempAlrmIndex INTEGER,
dcPwrSysTempAlrmName DisplayString,
dcPwrSysTempAlrmIntegerValue INTEGER,
dcPwrSysTempAlrmStringValue DisplayString,
dcPwrSysTempAlrmSeverity INTEGER
}
dcPwrSysTempAlrmIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The index of the alarm variable in the DC power system controller table temperature alarm group"
::= { dcPwrSysTempAlrmEntry 1 }
dcPwrSysTempAlrmName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..30))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The description of the alarm variable as reported by the DC power system controller temperature alarm group"
::= { dcPwrSysTempAlrmEntry 2 }
dcPwrSysTempAlrmIntegerValue OBJECT-TYPE
SYNTAX INTEGER (-1000000000..1000000000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of the alarm variable as reported by the DC power system controller temperature alarm group"
::= { dcPwrSysTempAlrmEntry 3 }
dcPwrSysTempAlrmStringValue OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The string value of the alarm variable as reported by the DC power system controller temperature alarm group"
::= { dcPwrSysTempAlrmEntry 4 }
dcPwrSysTempAlrmSeverity OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of alarm severity level of the extra variable as reported by the DC power system controller temperature alarm group"
::= { dcPwrSysTempAlrmEntry 5 }
--============================
-- Custom alarm group
--============================
dcPwrSysCustomAlrmCount OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of custom alarm variables in system controller alarm table"
::= { dcPwrSysCustomAlrmTbl 1 }
dcPwrSysCustomAlrmTable OBJECT-TYPE
SYNTAX SEQUENCE OF DcPwrSysCustomAlrmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A table of DC power system controller custom alarm variables"
::= { dcPwrSysCustomAlrmTbl 2 }
dcPwrSysCustomAlrmEntry OBJECT-TYPE
SYNTAX DcPwrSysCustomAlrmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "An entry into the DC power system controller custom alarm group"
INDEX { dcPwrSysCustomAlrmIndex }
::= { dcPwrSysCustomAlrmTable 1 }
DcPwrSysCustomAlrmEntry
::= SEQUENCE {
dcPwrSysCustomAlrmIndex INTEGER,
dcPwrSysCustomAlrmName DisplayString,
dcPwrSysCustomAlrmIntegerValue INTEGER,
dcPwrSysCustomAlrmStringValue DisplayString,
dcPwrSysCustomAlrmSeverity INTEGER
}
dcPwrSysCustomAlrmIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The index of the alarm variable in the DC power system controller table custom alarm group"
::= { dcPwrSysCustomAlrmEntry 1 }
dcPwrSysCustomAlrmName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..30))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The description of the alarm variable as reported by the DC power system controller custom alarm group"
::= { dcPwrSysCustomAlrmEntry 2 }
dcPwrSysCustomAlrmIntegerValue OBJECT-TYPE
SYNTAX INTEGER (-1000000000..1000000000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of the alarm variable as reported by the DC power system controller custom alarm group"
::= { dcPwrSysCustomAlrmEntry 3 }
dcPwrSysCustomAlrmStringValue OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The string value of the alarm variable as reported by the DC power system controller custom alarm group"
::= { dcPwrSysCustomAlrmEntry 4 }
dcPwrSysCustomAlrmSeverity OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of alarm severity level of the extra variable as reported by the DC power system controller custom alarm group"
::= { dcPwrSysCustomAlrmEntry 5 }
--============================
-- Misc alarm group
--============================
dcPwrSysMiscAlrmCount OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of misc alarm variables in system controller alarm table"
::= { dcPwrSysMiscAlrmTbl 1 }
dcPwrSysMiscAlrmTable OBJECT-TYPE
SYNTAX SEQUENCE OF DcPwrSysMiscAlrmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A table of DC power system controller misc alarm variables"
::= { dcPwrSysMiscAlrmTbl 2 }
dcPwrSysMiscAlrmEntry OBJECT-TYPE
SYNTAX DcPwrSysMiscAlrmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "An entry into the DC power system controller misc alarm group"
INDEX { dcPwrSysMiscAlrmIndex }
::= { dcPwrSysMiscAlrmTable 1 }
DcPwrSysMiscAlrmEntry
::= SEQUENCE {
dcPwrSysMiscAlrmIndex INTEGER,
dcPwrSysMiscAlrmName DisplayString,
dcPwrSysMiscAlrmIntegerValue INTEGER,
dcPwrSysMiscAlrmStringValue DisplayString,
dcPwrSysMiscAlrmSeverity INTEGER
}
dcPwrSysMiscAlrmIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The index of the alarm variable in the DC power system controller table misc alarm group"
::= { dcPwrSysMiscAlrmEntry 1 }
dcPwrSysMiscAlrmName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..30))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The description of the alarm variable as reported by the DC power system controller misc alarm group"
::= { dcPwrSysMiscAlrmEntry 2 }
dcPwrSysMiscAlrmIntegerValue OBJECT-TYPE
SYNTAX INTEGER (-1000000000..1000000000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of the alarm variable as reported by the DC power system controller misc alarm group"
::= { dcPwrSysMiscAlrmEntry 3 }
dcPwrSysMiscAlrmStringValue OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The string value of the alarm variable as reported by the DC power system controller misc alarm group"
::= { dcPwrSysMiscAlrmEntry 4 }
dcPwrSysMiscAlrmSeverity OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of alarm severity level of the extra variable as reported by the DC power system controller misc alarm group"
::= { dcPwrSysMiscAlrmEntry 5 }
--============================
-- Control alarm group
--============================
dcPwrSysCtrlAlrmCount OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of control alarm variables in system controller alarm table"
::= { dcPwrSysCtrlAlrmTbl 1 }
dcPwrSysCtrlAlrmTable OBJECT-TYPE
SYNTAX SEQUENCE OF DcPwrSysCtrlAlrmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A table of DC power system controller control alarm variables"
::= { dcPwrSysCtrlAlrmTbl 2 }
dcPwrSysCtrlAlrmEntry OBJECT-TYPE
SYNTAX DcPwrSysCtrlAlrmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "An entry into the DC power system controller control alarm group"
INDEX { dcPwrSysCtrlAlrmIndex }
::= { dcPwrSysCtrlAlrmTable 1 }
DcPwrSysCtrlAlrmEntry
::= SEQUENCE {
dcPwrSysCtrlAlrmIndex INTEGER,
dcPwrSysCtrlAlrmName DisplayString,
dcPwrSysCtrlAlrmIntegerValue INTEGER,
dcPwrSysCtrlAlrmStringValue DisplayString,
dcPwrSysCtrlAlrmSeverity INTEGER
}
dcPwrSysCtrlAlrmIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The index of the alarm variable in the DC power system controller table control alarm group"
::= { dcPwrSysCtrlAlrmEntry 1 }
dcPwrSysCtrlAlrmName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..30))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The description of the alarm variable as reported by the DC power system controller control alarm group"
::= { dcPwrSysCtrlAlrmEntry 2 }
dcPwrSysCtrlAlrmIntegerValue OBJECT-TYPE
SYNTAX INTEGER (-1000000000..1000000000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of the alarm variable as reported by the DC power system controller control alarm group"
::= { dcPwrSysCtrlAlrmEntry 3 }
dcPwrSysCtrlAlrmStringValue OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The string value of the alarm variable as reported by the DC power system controller control alarm group"
::= { dcPwrSysCtrlAlrmEntry 4 }
dcPwrSysCtrlAlrmSeverity OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of alarm severity level of the extra variable as reported by the DC power system controller control alarm group"
::= { dcPwrSysCtrlAlrmEntry 5 }
--============================
-- ADIO alarm group
--============================
dcPwrSysAdioAlrmCount OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of control alarm variables in Adio alarm table"
::= { dcPwrSysAdioAlrmTbl 1 }
dcPwrSysAdioAlrmTable OBJECT-TYPE
SYNTAX SEQUENCE OF DcPwrSysAdioAlrmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A table of DC power system controller Adio alarm variables"
::= { dcPwrSysAdioAlrmTbl 2 }
dcPwrSysAdioAlrmEntry OBJECT-TYPE
SYNTAX DcPwrSysAdioAlrmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "An entry into the DC power system controller Adio alarm group"
INDEX { dcPwrSysAdioAlrmIndex }
::= { dcPwrSysAdioAlrmTable 1 }
DcPwrSysAdioAlrmEntry
::= SEQUENCE {
dcPwrSysAdioAlrmIndex INTEGER,
dcPwrSysAdioAlrmName DisplayString,
dcPwrSysAdioAlrmIntegerValue INTEGER,
dcPwrSysAdioAlrmStringValue DisplayString,
dcPwrSysAdioAlrmSeverity INTEGER
}
dcPwrSysAdioAlrmIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The index of the alarm variable in the DC power system controller table Adio alarm group"
::= { dcPwrSysAdioAlrmEntry 1 }
dcPwrSysAdioAlrmName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..30))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The description of the alarm variable as reported by the DC power system controller Adio alarm group"
::= { dcPwrSysAdioAlrmEntry 2 }
dcPwrSysAdioAlrmIntegerValue OBJECT-TYPE
SYNTAX INTEGER (-1000000000..1000000000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of the alarm variable as reported by the DC power system controller Adio alarm group"
::= { dcPwrSysAdioAlrmEntry 3 }
dcPwrSysAdioAlrmStringValue OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The string value of the alarm variable as reported by the DC power system controller Adio alarm group"
::= { dcPwrSysAdioAlrmEntry 4 }
dcPwrSysAdioAlrmSeverity OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of alarm severity level of the extra variable as reported by the DC Adio system controller control alarm group"
::= { dcPwrSysAdioAlrmEntry 5 }
--============================
-- Converter alarm group
--============================
dcPwrSysConvAlrmCount OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of Converter alarm variables in system controller alarm table"
::= { dcPwrSysConvAlrmTbl 1 }
dcPwrSysConvAlrmTable OBJECT-TYPE
SYNTAX SEQUENCE OF DcPwrSysConvAlrmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A table of DC power system controller Converter alarm variables"
::= { dcPwrSysConvAlrmTbl 2 }
dcPwrSysConvAlrmEntry OBJECT-TYPE
SYNTAX DcPwrSysConvAlrmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "An entry into the DC power system controller Converter alarm group"
INDEX { dcPwrSysConvAlrmIndex }
::= { dcPwrSysConvAlrmTable 1 }
DcPwrSysConvAlrmEntry
::= SEQUENCE {
dcPwrSysConvAlrmIndex INTEGER,
dcPwrSysConvAlrmName DisplayString,
dcPwrSysConvAlrmIntegerValue INTEGER,
dcPwrSysConvAlrmStringValue DisplayString,
dcPwrSysConvAlrmSeverity INTEGER
}
dcPwrSysConvAlrmIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The index of the alarm variable in the DC power system controller table Converter alarm group"
::= { dcPwrSysConvAlrmEntry 1 }
dcPwrSysConvAlrmName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..30))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The description of the alarm variable as reported by the DC power system controller Converter alarm group"
::= { dcPwrSysConvAlrmEntry 2 }
dcPwrSysConvAlrmIntegerValue OBJECT-TYPE
SYNTAX INTEGER (-1000000000..1000000000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of the alarm variable as reported by the DC power system controller Converter alarm group"
::= { dcPwrSysConvAlrmEntry 3 }
dcPwrSysConvAlrmStringValue OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The string value of the alarm variable as reported by the DC power system controller Converter alarm group"
::= { dcPwrSysConvAlrmEntry 4 }
dcPwrSysConvAlrmSeverity OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of alarm severity level of the extra variable as reported by the DC power system controller Converter alarm group"
::= { dcPwrSysConvAlrmEntry 5 }
--============
-- Input table
--============
--=====================
-- Digital input group
--=====================
dcPwrSysDigIpCount OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of digital input variables in system controller digital input table"
::= { dcPwrSysDigIpTbl 1 }
dcPwrSysDigIpTable OBJECT-TYPE
SYNTAX SEQUENCE OF DcPwrSysDigIpEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A table of DC power system controller digital input variables"
::= { dcPwrSysDigIpTbl 2 }
dcPwrSysDigIpEntry OBJECT-TYPE
SYNTAX DcPwrSysDigIpEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "An entry into the DC power system controller digital input group"
INDEX { dcPwrSysDigIpIndex }
::= { dcPwrSysDigIpTable 1 }
DcPwrSysDigIpEntry
::= SEQUENCE {
dcPwrSysDigIpIndex INTEGER,
dcPwrSysDigIpName DisplayString,
dcPwrSysDigIpIntegerValue INTEGER,
dcPwrSysDigIpStringValue DisplayString
}
dcPwrSysDigIpIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The index of the digital input variable in the DC power system controller table digital input group"
::= { dcPwrSysDigIpEntry 1 }
dcPwrSysDigIpName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..30))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The description of the digital input variable as reported by the DC power system controller digital input group"
::= { dcPwrSysDigIpEntry 2 }
dcPwrSysDigIpIntegerValue OBJECT-TYPE
SYNTAX INTEGER (-1000000000..1000000000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of the digital input variable as reported by the DC power system controller digital input group"
::= { dcPwrSysDigIpEntry 3 }
dcPwrSysDigIpStringValue OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The string value of the digital input variable as reported by the DC power system controller digital input group"
::= { dcPwrSysDigIpEntry 4 }
--=========================
-- Controller input group
--=========================
dcPwrSysCntrlrIpCount OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of controller input variables in system controller controller input table"
::= { dcPwrSysCntrlrIpTbl 1 }
dcPwrSysCntrlrIpTable OBJECT-TYPE
SYNTAX SEQUENCE OF DcPwrSysCntrlrIpEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A table of DC power system controller controller input variables"
::= { dcPwrSysCntrlrIpTbl 2 }
dcPwrSysCntrlrIpEntry OBJECT-TYPE
SYNTAX DcPwrSysCntrlrIpEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "An entry into the DC power system controller controller input group"
INDEX { dcPwrSysCntrlrIpIndex }
::= { dcPwrSysCntrlrIpTable 1 }
DcPwrSysCntrlrIpEntry
::= SEQUENCE {
dcPwrSysCntrlrIpIndex INTEGER,
dcPwrSysCntrlrIpName DisplayString,
dcPwrSysCntrlrIpIntegerValue INTEGER,
dcPwrSysCntrlrIpStringValue DisplayString
}
dcPwrSysCntrlrIpIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The index of the controller input variable in the DC power system controller table controller input group"
::= { dcPwrSysCntrlrIpEntry 1 }
dcPwrSysCntrlrIpName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..30))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The description of the controller input variable as reported by the DC power system controller controller input group"
::= { dcPwrSysCntrlrIpEntry 2 }
dcPwrSysCntrlrIpIntegerValue OBJECT-TYPE
SYNTAX INTEGER (-1000000000..1000000000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of the controller input variable as reported by the DC power system controller controller input group"
::= { dcPwrSysCntrlrIpEntry 3 }
dcPwrSysCntrlrIpStringValue OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The string value of the controller input variable as reported by the DC power system controller controller input group"
::= { dcPwrSysCntrlrIpEntry 4 }
--========================
-- Rectifier input group
--========================
dcPwrSysRectIpCount OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of rectifier input variables in system controller rectifier input table"
::= { dcPwrSysRectIpTbl 1 }
dcPwrSysRectIpTable OBJECT-TYPE
SYNTAX SEQUENCE OF DcPwrSysRectIpEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A table of DC power system controller rectifier input variables"
::= { dcPwrSysRectIpTbl 2 }
dcPwrSysRectIpEntry OBJECT-TYPE
SYNTAX DcPwrSysRectIpEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "An entry into the DC power system controller rectifier input group"
INDEX { dcPwrSysRectIpIndex }
::= { dcPwrSysRectIpTable 1 }
DcPwrSysRectIpEntry
::= SEQUENCE {
dcPwrSysRectIpIndex INTEGER,
dcPwrSysRectIpName DisplayString,
dcPwrSysRectIpIntegerValue INTEGER,
dcPwrSysRectIpStringValue DisplayString
}
dcPwrSysRectIpIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The index of the rectifier input variable in the DC power system controller table rectifier input group"
::= { dcPwrSysRectIpEntry 1 }
dcPwrSysRectIpName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..30))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The description of the rectifier input variable as reported by the DC power system controller rectifier input group"
::= { dcPwrSysRectIpEntry 2 }
dcPwrSysRectIpIntegerValue OBJECT-TYPE
SYNTAX INTEGER (-1000000000..1000000000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of the rectifier input variable as reported by the DC power system controller rectifier input group"
::= { dcPwrSysRectIpEntry 3 }
dcPwrSysRectIpStringValue OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The string value of the rectifier input variable as reported by the DC power system controller rectifier input group"
::= { dcPwrSysRectIpEntry 4 }
--======================
-- Custom input group
--======================
dcPwrSysCustomIpCount OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of custom input variables in system controller custom input table"
::= { dcPwrSysCustomIpTbl 1 }
dcPwrSysCustomIpTable OBJECT-TYPE
SYNTAX SEQUENCE OF DcPwrSysCustomIpEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A table of DC power system controller digital custom variables"
::= { dcPwrSysCustomIpTbl 2 }
dcPwrSysCustomIpEntry OBJECT-TYPE
SYNTAX DcPwrSysCustomIpEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "An entry into the DC power system controller custom input group"
INDEX { dcPwrSysCustomIpIndex }
::= { dcPwrSysCustomIpTable 1 }
DcPwrSysCustomIpEntry
::= SEQUENCE {
dcPwrSysCustomIpIndex INTEGER,
dcPwrSysCustomIpName DisplayString,
dcPwrSysgCustomIpIntegerValue INTEGER,
dcPwrSysCustomIpStringValue DisplayString
}
dcPwrSysCustomIpIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The index of the custom input variable in the DC power system controller table custom input group"
::= { dcPwrSysCustomIpEntry 1 }
dcPwrSysCustomIpName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..30))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The description of the custom input variable as reported by the DC power system controller custom input group"
::= { dcPwrSysCustomIpEntry 2 }
dcPwrSysgCustomIpIntegerValue OBJECT-TYPE
SYNTAX INTEGER (-1000000000..1000000000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of the custom input variable as reported by the DC power system controller custom input group"
::= { dcPwrSysCustomIpEntry 3 }
dcPwrSysCustomIpStringValue OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The string value of the custom input variable as reported by the DC power system controller custom input group"
::= { dcPwrSysCustomIpEntry 4 }
--========================
-- Converter input group
--========================
dcPwrSysConvIpCount OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of Converter input variables in system controller Converter input table"
::= { dcPwrSysConvIpTbl 1 }
dcPwrSysConvIpTable OBJECT-TYPE
SYNTAX SEQUENCE OF DcPwrSysConvIpEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A table of DC power system controller Converter input variables"
::= { dcPwrSysConvIpTbl 2 }
dcPwrSysConvIpEntry OBJECT-TYPE
SYNTAX DcPwrSysConvIpEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "An entry into the DC power system controller Converter input group"
INDEX { dcPwrSysConvIpIndex }
::= { dcPwrSysConvIpTable 1 }
DcPwrSysConvIpEntry
::= SEQUENCE {
dcPwrSysConvIpIndex INTEGER,
dcPwrSysConvIpName DisplayString,
dcPwrSysConvIpIntegerValue INTEGER,
dcPwrSysConvIpStringValue DisplayString
}
dcPwrSysConvIpIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The index of the Converter input variable in the DC power system controller table Converter input group"
::= { dcPwrSysConvIpEntry 1 }
dcPwrSysConvIpName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..30))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The description of the Converter input variable as reported by the DC power system controller Converter input group"
::= { dcPwrSysConvIpEntry 2 }
dcPwrSysConvIpIntegerValue OBJECT-TYPE
SYNTAX INTEGER (-1000000000..1000000000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of the Converter input variable as reported by the DC power system controller Converter input group"
::= { dcPwrSysConvIpEntry 3 }
dcPwrSysConvIpStringValue OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The string value of the Converter input variable as reported by the DC power system controller Converter input group"
::= { dcPwrSysConvIpEntry 4 }
--========================
-- Timer input group
--========================
dcPwrSysTimerIpCount OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of Timererter input variables in system controller Timererter input table"
::= { dcPwrSysTimerIpTbl 1 }
dcPwrSysTimerIpTable OBJECT-TYPE
SYNTAX SEQUENCE OF DcPwrSysTimerIpEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A table of DC power system controller Timererter input variables"
::= { dcPwrSysTimerIpTbl 2 }
dcPwrSysTimerIpEntry OBJECT-TYPE
SYNTAX DcPwrSysTimerIpEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "An entry into the DC power system controller Timererter input group"
INDEX { dcPwrSysTimerIpIndex }
::= { dcPwrSysTimerIpTable 1 }
DcPwrSysTimerIpEntry
::= SEQUENCE {
dcPwrSysTimerIpIndex INTEGER,
dcPwrSysTimerIpName DisplayString,
dcPwrSysTimerIpIntegerValue INTEGER,
dcPwrSysTimerIpStringValue DisplayString
}
dcPwrSysTimerIpIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The index of the Timererter input variable in the DC power system controller table Timererter input group"
::= { dcPwrSysTimerIpEntry 1 }
dcPwrSysTimerIpName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..30))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The description of the Timererter input variable as reported by the DC power system controller Timererter input group"
::= { dcPwrSysTimerIpEntry 2 }
dcPwrSysTimerIpIntegerValue OBJECT-TYPE
SYNTAX INTEGER (-1000000000..1000000000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of the Timererter input variable as reported by the DC power system controller Timererter input group"
::= { dcPwrSysTimerIpEntry 3 }
dcPwrSysTimerIpStringValue OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The string value of the Timererter input variable as reported by the DC power system controller Timererter input group"
::= { dcPwrSysTimerIpEntry 4 }
--========================
-- Counter input group
--========================
dcPwrSysCounterIpCount OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of Countererter input variables in system controller Countererter input table"
::= { dcPwrSysCounterIpTbl 1 }
dcPwrSysCounterIpTable OBJECT-TYPE
SYNTAX SEQUENCE OF DcPwrSysCounterIpEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A table of DC power system controller Countererter input variables"
::= { dcPwrSysCounterIpTbl 2 }
dcPwrSysCounterIpEntry OBJECT-TYPE
SYNTAX DcPwrSysCounterIpEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "An entry into the DC power system controller Countererter input group"
INDEX { dcPwrSysCounterIpIndex }
::= { dcPwrSysCounterIpTable 1 }
DcPwrSysCounterIpEntry
::= SEQUENCE {
dcPwrSysCounterIpIndex INTEGER,
dcPwrSysCounterIpName DisplayString,
dcPwrSysCounterIpIntegerValue INTEGER,
dcPwrSysCounterIpStringValue DisplayString
}
dcPwrSysCounterIpIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The index of the Countererter input variable in the DC power system controller table Countererter input group"
::= { dcPwrSysCounterIpEntry 1 }
dcPwrSysCounterIpName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..30))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The description of the Countererter input variable as reported by the DC power system controller Countererter input group"
::= { dcPwrSysCounterIpEntry 2 }
dcPwrSysCounterIpIntegerValue OBJECT-TYPE
SYNTAX INTEGER (-1000000000..1000000000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of the Countererter input variable as reported by the DC power system controller Countererter input group"
::= { dcPwrSysCounterIpEntry 3 }
dcPwrSysCounterIpStringValue OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The string value of the Countererter input variable as reported by the DC power system controller Countererter input group"
::= { dcPwrSysCounterIpEntry 4 }
--==========================================================================
-- The OBJECT IDENTIFIERs for the traps must be defined in this manner to
-- satisfy the NetSight MIB compiler; in particular, nodes cannot be defined
-- concatenated in a single line, but must be defined explicitly node by node
-- (hence, the dcPwrSysDevice.dcPwrSysTraps.dcPwrSysTrap definition)
-- In addition, forward references to extra system variables are needed for
-- dcPwrSysTrap by CastleRock SNMPc for event filter and match features.
--==========================================================================
dcPwrSysTrap OBJECT IDENTIFIER ::= { dcPwrSysTraps 0 }
--==========================================================================
-- Start of Traps
--==========================================================================
dcPwrSysAlarmActiveTrap NOTIFICATION-TYPE
OBJECTS {
dcPwrSysRectAlrmStringValue,
dcPwrSysRectAlrmIndex,
dcPwrSysRectAlrmSeverity,
dcPwrSysSiteName,
dcPwrSysAlarmTriggerValue
}
STATUS current
DESCRIPTION "A trap issued when one of the alarms on the DC power system controller became active"
::= { dcPwrSysTrap 1 }
dcPwrSysAlarmClearedTrap NOTIFICATION-TYPE
OBJECTS {
dcPwrSysRectAlrmStringValue,
dcPwrSysRectAlrmIndex,
dcPwrSysRectAlrmSeverity,
dcPwrSysSiteName,
dcPwrSysAlarmTriggerValue
}
STATUS current
DESCRIPTION "A trap issued when one of the active alarms on the DC power system controller is cleared"
::= { dcPwrSysTrap 2 }
dcPwrSysRelayTrap NOTIFICATION-TYPE
OBJECTS {
dcPwrSysRelayIntegerValue,
dcPwrSysRelayStringValue,
dcPwrSysRelayIndex,
dcPwrSysRelaySeverity,
dcPwrSysSiteName
}
STATUS current
DESCRIPTION "A trap issued from a change in state in one of the relays on the DC power system controller"
::= { dcPwrSysTrap 3 }
dcPwrSysComOKTrap NOTIFICATION-TYPE
OBJECTS {
dcPwrSysSiteName
}
STATUS current
DESCRIPTION "A trap to indicate that communications with a DC power system controller has been established."
::= { dcPwrSysTrap 4 }
dcPwrSysComErrTrap NOTIFICATION-TYPE
OBJECTS {
dcPwrSysSiteName
}
STATUS current
DESCRIPTION "A trap to indicate that communications with a DC power system controller has been lost."
::= { dcPwrSysTrap 5 }
dcPwrSysAgentStartupTrap NOTIFICATION-TYPE
OBJECTS {
dcPwrSysSiteName
}
STATUS current
DESCRIPTION "A trap to indicate that the agent software has started up."
::= { dcPwrSysTrap 6 }
dcPwrSysAgentShutdownTrap NOTIFICATION-TYPE
OBJECTS {
dcPwrSysSiteName
}
STATUS current
DESCRIPTION "A trap to indicate that the agent software has shutdown."
::= { dcPwrSysTrap 7 }
dcPwrSysMajorAlarmActiveTrap NOTIFICATION-TYPE
OBJECTS {
dcPwrSysRectAlrmStringValue,
dcPwrSysRectAlrmIndex,
dcPwrSysRectAlrmSeverity,
dcPwrSysSiteName
}
STATUS current
DESCRIPTION "A trap issued as a summary of DC power system status. It is sent when the system goes into in Major Alarm"
::= { dcPwrSysTrap 8 }
dcPwrSysMajorAlarmClearedTrap NOTIFICATION-TYPE
OBJECTS {
dcPwrSysRectAlrmStringValue,
dcPwrSysRectAlrmIndex,
dcPwrSysRectAlrmSeverity,
dcPwrSysSiteName
}
STATUS current
DESCRIPTION "A trap issued as a summary of DC power system status. It is sent when the system comes out of Major Alarm"
::= { dcPwrSysTrap 9 }
dcPwrSysMinorAlarmActiveTrap NOTIFICATION-TYPE
OBJECTS {
dcPwrSysRectAlrmStringValue,
dcPwrSysRectAlrmIndex,
dcPwrSysRectAlrmSeverity,
dcPwrSysSiteName
}
STATUS current
DESCRIPTION "A trap issued as a summary of DC power system status. It is sent when the system goes into in Minor Alarm"
::= { dcPwrSysTrap 10 }
dcPwrSysMinorAlarmClearedTrap NOTIFICATION-TYPE
OBJECTS {
dcPwrSysRectAlrmStringValue,
dcPwrSysRectAlrmIndex,
dcPwrSysRectAlrmSeverity,
dcPwrSysSiteName
}
STATUS current
DESCRIPTION "A trap issued as a summary of DC power system status. It is sent when the system comes out of Minor Alarm"
::= { dcPwrSysTrap 11 }
--==========================================================================
-- Start of External Controls
--==========================================================================
dcPwrSysResyncAlarms OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Send/Resend all active alarms that were previously sent through SNMP notification."
::= { dcPwrExternalControls 1 }
--==========================================================================
-- Alarm Trigger
--==========================================================================
dcPwrSysAlarmTriggerValue OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION ""
::= { dcPwrVarbindNameReference 1 }
--==========================================================================
-- Time stamp
--==========================================================================
dcPwrSysTimeStamp OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION ""
::= { dcPwrVarbindNameReference 2 }
END