CYCLADES-ACS5K-PM-MIB DEFINITIONS ::= BEGIN
|
|
|
|
-- Avocent Vendor MIB OID Tree
|
|
-- Release 3.3.0-9 05/24/2011
|
|
-- The cyACS5KPM has the ACS 5000' power mgmt MIB :
|
|
|
|
IMPORTS
|
|
cyACS5KMgmt
|
|
FROM CYCLADES-ACS5K-MIB
|
|
OBJECT-TYPE, MODULE-IDENTITY, Integer32
|
|
FROM SNMPv2-SMI
|
|
InterfaceIndex, InterfaceIndexOrZero
|
|
FROM IF-MIB
|
|
DisplayString
|
|
FROM SNMPv2-TC;
|
|
|
|
cyACS5KPM MODULE-IDENTITY
|
|
LAST-UPDATED "201007260000Z"
|
|
ORGANIZATION "Avocent Corporation"
|
|
CONTACT-INFO "postal : Avocent Corporation
|
|
47281 Bayside Parkway
|
|
Fremont, CA 94538, USA
|
|
e-mail : Technical Support
|
|
techsupport@avocent.com"
|
|
DESCRIPTION "This module defines objects of the Proxy for PM "
|
|
REVISION "201007260000Z"
|
|
DESCRIPTION "First Draft"
|
|
::= { cyACS5KMgmt 5 }
|
|
|
|
cyNumberOfPM OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The total number of PM's connected on the unit"
|
|
::= { cyACS5KPM 1 }
|
|
|
|
cyPMTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF CyPMEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Allows to read information about each connected PM"
|
|
::= { cyACS5KPM 2 }
|
|
|
|
cyPMEntry OBJECT-TYPE
|
|
SYNTAX CyPMEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Information about the connected PM"
|
|
INDEX { cyPMSerialPortNumber }
|
|
::= { cyPMTable 1 }
|
|
|
|
CyPMEntry ::= SEQUENCE {
|
|
cyPMSerialPortNumber InterfaceIndex,
|
|
cyPMNumberOutlets Integer32,
|
|
cyPMNumberUnits Integer32,
|
|
cyPMCurrent DisplayString,
|
|
cyPMVersion DisplayString,
|
|
cyPMCommand DisplayString
|
|
}
|
|
|
|
cyPMSerialPortNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The number of the serial port when the PM is connected."
|
|
::= { cyPMEntry 1 }
|
|
|
|
cyPMNumberOutlets OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of outlets."
|
|
::= { cyPMEntry 2 }
|
|
|
|
cyPMNumberUnits OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Total number of PM unists that are accessed by this
|
|
serial port."
|
|
::= { cyPMEntry 3 }
|
|
|
|
cyPMCurrent OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Current reading for the PM."
|
|
::= { cyPMEntry 4 }
|
|
|
|
cyPMVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The software version of the PM."
|
|
::= { cyPMEntry 5 }
|
|
|
|
cyPMCommand OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (1..100))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "A character string for the user to send commands to
|
|
PM. He can use it to does the save command.
|
|
Or to list the outlets that need to be turned off,
|
|
or turned on , or cycled or locked or unlocked as a
|
|
group. The command is the first word and is followed
|
|
by a space and the outlet list (otulets commands).
|
|
Valid commands are 'on', 'off', 'cycle', 'lock',
|
|
'unlock', 'save'."
|
|
::= { cyPMEntry 7 }
|
|
|
|
cyPMUnitTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF CyPMUnitEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Allow operations on specific PM unit connected"
|
|
::= { cyACS5KPM 3 }
|
|
|
|
cyPMUnitEntry OBJECT-TYPE
|
|
SYNTAX CyPMUnitEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Allow operations on outlet"
|
|
INDEX { cyPMSerialPortNumber, cyPMUnitNumber }
|
|
::= { cyPMUnitTable 1 }
|
|
|
|
CyPMUnitEntry ::= SEQUENCE {
|
|
cyPMUnitNumber InterfaceIndex,
|
|
cyPMUnitVersion DisplayString,
|
|
cyPMUnitOutlets Integer32,
|
|
cyPMUnitFirstOutlet Integer32,
|
|
cyPMUnitCurrent Integer32,
|
|
cyPMUnitMaxCurrent Integer32,
|
|
cyPMUnitSequenceInterval Integer32,
|
|
cyPMUnitCycleInterval Integer32,
|
|
cyPMUnitID DisplayString,
|
|
cyPMUnitPhases INTEGER,
|
|
cyPMUnitBanks Integer32,
|
|
cyPMUnitNominalVoltage Integer32,
|
|
cyPMUnitPower Integer32
|
|
}
|
|
|
|
cyPMUnitNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "The number of the PM unit in the daisy-chained mode."
|
|
::= { cyPMUnitEntry 1 }
|
|
|
|
cyPMUnitVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The software version of this PM unit."
|
|
::= { cyPMUnitEntry 2 }
|
|
|
|
cyPMUnitOutlets OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of outlets of this PM unit."
|
|
::= { cyPMUnitEntry 3 }
|
|
|
|
cyPMUnitFirstOutlet OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of the first outlet of this PM unit."
|
|
::= { cyPMUnitEntry 4 }
|
|
|
|
cyPMUnitCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Current of this PM unit in AMP.
|
|
The value of this object is the actual current in
|
|
AMP * 10. You need to translate the readed value
|
|
(Ex. : value is 5, the current is 0.5 AMP.)"
|
|
::= { cyPMUnitEntry 5 }
|
|
|
|
cyPMUnitMaxCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Maximum current of this PM unit in AMP.
|
|
The value of this object is the maximum current in
|
|
AMP * 10. You need to translate the readed value
|
|
(Ex. : value is 5, the maximum current is 0.5 AMP.)"
|
|
::= { cyPMUnitEntry 6 }
|
|
|
|
cyPMUnitSequenceInterval OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Sequence interval delay.
|
|
Valid values are 2 to 15 (seconds)."
|
|
::= { cyPMUnitEntry 9 }
|
|
|
|
cyPMUnitCycleInterval OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of seconds that a socket stays off
|
|
before turning it back on."
|
|
::= { cyPMUnitEntry 10 }
|
|
|
|
cyPMUnitID OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "PDU identification."
|
|
::= { cyPMUnitEntry 11 }
|
|
|
|
cyPMUnitPhases OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
single-phase(0),
|
|
three-phase(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of phases of this PDU unit."
|
|
::= { cyPMUnitEntry 12 }
|
|
|
|
cyPMUnitBanks OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of banks of this PDU unit."
|
|
::= { cyPMUnitEntry 13 }
|
|
|
|
cyPMUnitNominalVoltage OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Nominal Voltage configured for this PDU unit, when it does not have voltage sensor"
|
|
::= { cyPMUnitEntry 14 }
|
|
|
|
cyPMUnitPower OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Power Consumption of this PDU unit (it is estimated when PDU does not have voltage sensor)."
|
|
::= { cyPMUnitEntry 15 }
|
|
|
|
cyOutletTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF CyOutletEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Allow operations on outlet"
|
|
::= { cyACS5KPM 4 }
|
|
|
|
cyOutletEntry OBJECT-TYPE
|
|
SYNTAX CyOutletEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Allow operations on outlet"
|
|
INDEX { cyPMSerialPortNumber, cyOutletNumber }
|
|
::= { cyOutletTable 1 }
|
|
|
|
CyOutletEntry ::= SEQUENCE {
|
|
cyOutletNumber InterfaceIndexOrZero,
|
|
cyOutletName DisplayString,
|
|
cyOutletServer DisplayString,
|
|
cyOutletPower INTEGER,
|
|
cyOutletLock INTEGER,
|
|
cyOutletPUInterval Integer32,
|
|
cyOutletMinimumOnInterval Integer32,
|
|
cyOutletMinimumOffInterval Integer32,
|
|
cyOutletWakeupState Integer32,
|
|
cyOutletPduID DisplayString,
|
|
cyOutletPduNumber Integer32
|
|
}
|
|
|
|
cyOutletNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndexOrZero
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "The outlet number on the PM. Zero is ALL outlets."
|
|
::= { cyOutletEntry 1 }
|
|
|
|
cyOutletName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(1 .. 8))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The name given to a particular outlet Maximum size is 8 characters."
|
|
::= { cyOutletEntry 2 }
|
|
|
|
cyOutletServer OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Alias of the Server connected to this outlet ."
|
|
::= { cyOutletEntry 3 }
|
|
|
|
cyOutletPower OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off (0),
|
|
on (1),
|
|
cycle (2),
|
|
unknow (3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Getting this object will return the power state of
|
|
the outlet. Valid return states are UNKNOW, OFF and
|
|
ON. Setting this object will change the power state
|
|
of the outlet."
|
|
::= { cyOutletEntry 4 }
|
|
|
|
cyOutletLock OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unlock (0),
|
|
lock (1),
|
|
unknow (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Getting this object will return the lock state of
|
|
the outlet. Setting this object will change the
|
|
lock state of the outlet."
|
|
::= { cyOutletEntry 5 }
|
|
|
|
cyOutletPUInterval OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The power unit interval of this outlet in seconds.
|
|
The value of this object is the actual interval in
|
|
seconds * 10. You need to translate the readed value
|
|
(Ex. : value is 5, the interval is 0.5 seconds.)"
|
|
::= { cyOutletEntry 6 }
|
|
|
|
cyOutletMinimumOnInterval OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Minimum time in seconds an outlet will stay on before
|
|
turning it off."
|
|
::= { cyOutletEntry 7 }
|
|
|
|
cyOutletMinimumOffInterval OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Minimum time in seconds an outlet will stay off before
|
|
turning it on."
|
|
::= { cyOutletEntry 8 }
|
|
|
|
cyOutletWakeupState OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Outlet state after a cold boot. It can be set to on
|
|
or off."
|
|
::= { cyOutletEntry 9 }
|
|
|
|
cyOutletPduID OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "PDU identification."
|
|
::= { cyOutletEntry 10}
|
|
|
|
cyOutletPduNumber OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "The number of the PDU unit in the daisy-chained mode."
|
|
::= { cyOutletEntry 11 }
|
|
|
|
cyPMElecPduTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF CyPMElecPduTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Allow operations on elecmon element of the PDUs"
|
|
::= { cyACS5KPM 5 }
|
|
|
|
cyPMElecPduTableEntry OBJECT-TYPE
|
|
SYNTAX CyPMElecPduTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "each entry has the information about the elecmon element of the PDUs."
|
|
INDEX { cyPMElecPduTablePortNumber, cyPMElecPduTablePduNumber }
|
|
::= { cyPMElecPduTable 1 }
|
|
|
|
CyPMElecPduTableEntry ::= SEQUENCE {
|
|
cyPMElecPduTablePortNumber InterfaceIndex, -- serial port #
|
|
cyPMElecPduTablePduNumber InterfaceIndex, -- pdu number in the chain
|
|
cyPMElecPduTableCurrentValue Integer32, -- actual value for current
|
|
cyPMElecPduTableCurrentMax Integer32, -- max value for current
|
|
cyPMElecPduTablePowerValue Integer32, -- actual value for power
|
|
cyPMElecPduTablePowerMax Integer32, -- max value for power
|
|
cyPMElecPduTableVoltageValue Integer32, -- actual value for voltage
|
|
cyPMElecPduTableVoltageMax Integer32, -- max value for voltage
|
|
cyPMElecPduTablePowerFactorValue Integer32, -- actual value for powerfactor
|
|
cyPMElecPduTablePowerFactorMax Integer32, -- max value for powerfactor
|
|
cyPMElecPduTablePowerType INTEGER, -- type of power
|
|
cyPMElecPduTableVoltageType INTEGER, -- type of voltage
|
|
cyPMElecPduTablePowerFactorType INTEGER -- type of powerfactor
|
|
}
|
|
|
|
cyPMElecPduTablePortNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Serial Port number where the PDU is connected."
|
|
::= { cyPMElecPduTableEntry 1 }
|
|
|
|
cyPMElecPduTablePduNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The number of the PDU unit in the daisy-chained mode"
|
|
::= { cyPMElecPduTableEntry 2 }
|
|
|
|
cyPMElecPduTableCurrentValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Actual value of current in the element (A x 10)."
|
|
::= { cyPMElecPduTableEntry 3 }
|
|
|
|
cyPMElecPduTableCurrentMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Maximum detected value of current in the element (A x 10).
|
|
Write operation accepts only 0 for reset action."
|
|
::= { cyPMElecPduTableEntry 4 }
|
|
|
|
cyPMElecPduTablePowerValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Actual value of power in the element (W x 10)."
|
|
::= { cyPMElecPduTableEntry 5 }
|
|
|
|
cyPMElecPduTablePowerMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Maximum value of power in the element (W x 10).
|
|
Write operation accepts only 0 for reset action."
|
|
::= { cyPMElecPduTableEntry 6 }
|
|
|
|
cyPMElecPduTableVoltageValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Actual value of voltage in the element (V).When element
|
|
does not have voltage sensor, it returns 0."
|
|
::= { cyPMElecPduTableEntry 7 }
|
|
|
|
cyPMElecPduTableVoltageMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Maximum value of voltage in the element (V). When element
|
|
does not have voltage sensor, it returns 0. Write operation
|
|
accepts only 0 for reset action."
|
|
::= { cyPMElecPduTableEntry 8 }
|
|
|
|
cyPMElecPduTablePowerFactorValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Actual value of power factor in the element (Pf x 10).
|
|
When element does not have power factor sensor, returns 0."
|
|
::= { cyPMElecPduTableEntry 9 }
|
|
|
|
cyPMElecPduTablePowerFactorMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Maximum value of power factor in the element (Pf x 10).
|
|
When element does not have power factor sensor, returns 0.
|
|
Write operation accepts only 0 for reset action."
|
|
::= { cyPMElecPduTableEntry 10 }
|
|
|
|
cyPMElecPduTablePowerType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
estimated(1),
|
|
measured(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "This PDU unit's Power sensor type."
|
|
::= { cyPMElecPduTableEntry 11 }
|
|
|
|
cyPMElecPduTableVoltageType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
estimated(1),
|
|
measured(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "This PDU unit's has voltage sensor type."
|
|
::= { cyPMElecPduTableEntry 12 }
|
|
|
|
cyPMElecPduTablePowerFactorType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
estimated(1),
|
|
measured(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "This PDU unit's Power Factor sensor type."
|
|
::= { cyPMElecPduTableEntry 13 }
|
|
|
|
cyPMElecPhaseTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF CyPMElecPhaseTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Allow operations on elecmon element for phases"
|
|
::= { cyACS5KPM 6 }
|
|
|
|
cyPMElecPhaseTableEntry OBJECT-TYPE
|
|
SYNTAX CyPMElecPhaseTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "each entry has the information about the elecmon for phase."
|
|
INDEX {
|
|
cyPMElecPhaseTablePortNumber,
|
|
cyPMElecPhaseTablePduNumber,
|
|
cyPMElecPhaseTableIndex
|
|
}
|
|
::= { cyPMElecPhaseTable 1 }
|
|
|
|
CyPMElecPhaseTableEntry ::= SEQUENCE {
|
|
cyPMElecPhaseTablePortNumber InterfaceIndex, -- serial port #
|
|
cyPMElecPhaseTablePduNumber InterfaceIndex, -- pdu number in the chain
|
|
cyPMElecPhaseTableIndex InterfaceIndex, -- index of the element
|
|
cyPMElecPhaseTableName DisplayString, -- phase sysname
|
|
cyPMElecPhaseTableCurrentValue Integer32, -- actual value for current
|
|
cyPMElecPhaseTableCurrentMax Integer32, -- max value for current
|
|
cyPMElecPhaseTablePowerValue Integer32, -- actual value for power
|
|
cyPMElecPhaseTablePowerMax Integer32, -- max value for power
|
|
cyPMElecPhaseTableVoltageValue Integer32, -- actual value for voltage
|
|
cyPMElecPhaseTableVoltageMax Integer32, -- max value for voltage
|
|
cyPMElecPhaseTablePowerFactorValue Integer32, -- actual value for powerfactor
|
|
cyPMElecPhaseTablePowerFactorMax Integer32, -- max value for powerfactor
|
|
cyPMElecPhaseTablePowerType INTEGER, -- type of power
|
|
cyPMElecPhaseTableVoltageType INTEGER, -- type of voltage
|
|
cyPMElecPhaseTablePowerFactorType INTEGER -- type of powerfactor
|
|
}
|
|
|
|
cyPMElecPhaseTablePortNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Serial Port number where the PDU is connected."
|
|
::= { cyPMElecPhaseTableEntry 1 }
|
|
|
|
cyPMElecPhaseTablePduNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The number of the PDU unit in the daisy-chained mode"
|
|
::= { cyPMElecPhaseTableEntry 2 }
|
|
|
|
cyPMElecPhaseTableIndex OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "index of the phase in the PDU. Index can be 1,2 or 3."
|
|
::= { cyPMElecPhaseTableEntry 3 }
|
|
|
|
cyPMElecPhaseTableName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Sys-name of the phase."
|
|
::= { cyPMElecPhaseTableEntry 4 }
|
|
|
|
cyPMElecPhaseTableCurrentValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Actual value of current in the phase (A x 10)."
|
|
::= { cyPMElecPhaseTableEntry 5 }
|
|
|
|
cyPMElecPhaseTableCurrentMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Maximum detected value of current in the phase (A x 10).
|
|
Write operation accepts only 0 for reset action."
|
|
::= { cyPMElecPhaseTableEntry 6 }
|
|
|
|
cyPMElecPhaseTablePowerValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Actual value of power in the phase (W x 10)."
|
|
::= { cyPMElecPhaseTableEntry 7 }
|
|
|
|
cyPMElecPhaseTablePowerMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Maximum value of power in the phase (W x 10).Write operation
|
|
accepts only 0 for reset action."
|
|
::= { cyPMElecPhaseTableEntry 8 }
|
|
|
|
cyPMElecPhaseTableVoltageValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Actual value of voltage in the phase (V).When phase does
|
|
not have voltage sensor, it returns 0."
|
|
::= { cyPMElecPhaseTableEntry 9 }
|
|
|
|
cyPMElecPhaseTableVoltageMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Maximum value of voltage in the phase (V). When phase does
|
|
not have voltage sensor, it returns 0. Write operation accepts
|
|
only 0 for reset action."
|
|
::= { cyPMElecPhaseTableEntry 10 }
|
|
|
|
cyPMElecPhaseTablePowerFactorValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Actual value of power factor in the phase (Pf x 10). When
|
|
phase does not have power factor sensor, returns 0."
|
|
::= { cyPMElecPhaseTableEntry 11 }
|
|
|
|
cyPMElecPhaseTablePowerFactorMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Maximum value of power factor in the phase (Pf x 10). When
|
|
phase does not have power factor sensor, returns 0.Write
|
|
operation accepts only 0 for reset action."
|
|
::= { cyPMElecPhaseTableEntry 12 }
|
|
|
|
cyPMElecPhaseTablePowerType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
estimated(1),
|
|
measured(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The type of Power sensor for this elecmon"
|
|
::= { cyPMElecPhaseTableEntry 13 }
|
|
|
|
cyPMElecPhaseTableVoltageType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
estimated(1),
|
|
measured(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The type of Voltage sensor for this elecmon"
|
|
::= { cyPMElecPhaseTableEntry 14 }
|
|
|
|
cyPMElecPhaseTablePowerFactorType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
estimated(1),
|
|
measured(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The type of Power Factor sensor for this elecmon"
|
|
::= { cyPMElecPhaseTableEntry 15 }
|
|
|
|
cyPMElecBankTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF CyPMElecBankTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Allow operations on elecmon element for banks"
|
|
::= { cyACS5KPM 7 }
|
|
|
|
cyPMElecBankTableEntry OBJECT-TYPE
|
|
SYNTAX CyPMElecBankTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "each entry has the information about the elecmon for Bank."
|
|
INDEX {
|
|
cyPMElecBankTablePortNumber,
|
|
cyPMElecBankTablePduNumber,
|
|
cyPMElecBankTableIndex
|
|
}
|
|
::= { cyPMElecBankTable 1 }
|
|
|
|
CyPMElecBankTableEntry ::= SEQUENCE {
|
|
cyPMElecBankTablePortNumber InterfaceIndex, -- serial port #
|
|
cyPMElecBankTablePduNumber InterfaceIndex, -- pdu number in the chain
|
|
cyPMElecBankTableIndex InterfaceIndex, -- index of the element
|
|
cyPMElecBankTableName DisplayString, -- Bank sysname
|
|
cyPMElecBankTableCurrentValue Integer32, -- actual value for current
|
|
cyPMElecBankTableCurrentMax Integer32, -- max value for current
|
|
cyPMElecBankTablePowerValue Integer32, -- actual value for power
|
|
cyPMElecBankTablePowerMax Integer32, -- max value for power
|
|
cyPMElecBankTableVoltageValue Integer32, -- actual value for voltage
|
|
cyPMElecBankTableVoltageMax Integer32, -- max value for voltage
|
|
cyPMElecBankTablePowerFactorValue Integer32, -- actual value for powerfactor
|
|
cyPMElecBankTablePowerFactorMax Integer32, -- max value for powerfactor
|
|
cyPMElecBankTablePowerType INTEGER, -- type of power
|
|
cyPMElecBankTableVoltageType INTEGER, -- type of voltage
|
|
cyPMElecBankTablePowerFactorType INTEGER -- type of powerfactor
|
|
}
|
|
|
|
cyPMElecBankTablePortNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Serial Port number where the PDU is connected."
|
|
::= { cyPMElecBankTableEntry 1 }
|
|
|
|
cyPMElecBankTablePduNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The number of the PDU unit in the daisy-chained mode"
|
|
::= { cyPMElecBankTableEntry 2 }
|
|
|
|
cyPMElecBankTableIndex OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "index of the Bank in the PDU. Index can be 1,2, ... number of banks of the PDU."
|
|
::= { cyPMElecBankTableEntry 3 }
|
|
|
|
cyPMElecBankTableName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Sys-name of the Bank."
|
|
::= { cyPMElecBankTableEntry 4 }
|
|
|
|
cyPMElecBankTableCurrentValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Actual value of current in the Bank (A x 10)."
|
|
::= { cyPMElecBankTableEntry 5 }
|
|
|
|
cyPMElecBankTableCurrentMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Maximum detected value of current in the Bank (A x 10).
|
|
Write operation accepts only 0 for reset action."
|
|
::= { cyPMElecBankTableEntry 6 }
|
|
|
|
cyPMElecBankTablePowerValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Actual value of power in the Bank (W x 10)."
|
|
::= { cyPMElecBankTableEntry 7 }
|
|
|
|
cyPMElecBankTablePowerMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Maximum value of power in the Bank (W x 10).Write operation
|
|
accepts only 0 for reset action."
|
|
::= { cyPMElecBankTableEntry 8 }
|
|
|
|
cyPMElecBankTableVoltageValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Actual value of voltage in the Bank (V).When Bank does
|
|
not have voltage sensor, it returns 0."
|
|
::= { cyPMElecBankTableEntry 9 }
|
|
|
|
cyPMElecBankTableVoltageMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Maximum value of voltage in the Bank (V). When Bank does
|
|
not have voltage sensor, it returns 0. Write operation accepts
|
|
only 0 for reset action."
|
|
::= { cyPMElecBankTableEntry 10 }
|
|
|
|
cyPMElecBankTablePowerFactorValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Actual value of power factor in the Bank (Pf x 10). When
|
|
Bank does not have power factor sensor, returns 0."
|
|
::= { cyPMElecBankTableEntry 11 }
|
|
|
|
cyPMElecBankTablePowerFactorMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Maximum value of power factor in the Bank (Pf x 10). When
|
|
Bank does not have power factor sensor, returns 0.Write
|
|
operation accepts only 0 for reset action."
|
|
::= { cyPMElecBankTableEntry 12 }
|
|
|
|
cyPMElecBankTablePowerType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
estimated(1),
|
|
measured(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The type of Power sensor for this elecmon"
|
|
::= { cyPMElecBankTableEntry 13 }
|
|
|
|
cyPMElecBankTableVoltageType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
estimated(1),
|
|
measured(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The type of Voltage sensor for this elecmon"
|
|
::= { cyPMElecBankTableEntry 14 }
|
|
|
|
cyPMElecBankTablePowerFactorType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
estimated(1),
|
|
measured(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The type of Power Factor sensor for this elecmon"
|
|
::= { cyPMElecBankTableEntry 15 }
|
|
|
|
cyPMElecOutletTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF CyPMElecOutletTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Allow operations on elecmon element for outlets"
|
|
::= { cyACS5KPM 8 }
|
|
|
|
cyPMElecOutletTableEntry OBJECT-TYPE
|
|
SYNTAX CyPMElecOutletTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "each entry has the information about the elecmon for Outlet."
|
|
INDEX {
|
|
cyPMElecOutletTablePortNumber,
|
|
cyPMElecOutletTablePduNumber,
|
|
cyPMElecOutletTableNumber
|
|
}
|
|
::= { cyPMElecOutletTable 1 }
|
|
|
|
CyPMElecOutletTableEntry ::= SEQUENCE {
|
|
cyPMElecOutletTablePortNumber InterfaceIndex, -- serial port #
|
|
cyPMElecOutletTablePduNumber InterfaceIndex, -- pdu number in the chain
|
|
cyPMElecOutletTableNumber InterfaceIndex, -- outlet number in the PDU
|
|
cyPMElecOutletTableName DisplayString, -- Outlet name
|
|
cyPMElecOutletTableCurrentValue Integer32, -- actual value for current
|
|
cyPMElecOutletTableCurrentMax Integer32, -- max value for current
|
|
cyPMElecOutletTablePowerValue Integer32, -- actual value for power
|
|
cyPMElecOutletTablePowerMax Integer32, -- max value for power
|
|
cyPMElecOutletTableVoltageValue Integer32, -- actual value for voltage
|
|
cyPMElecOutletTableVoltageMax Integer32, -- max value for voltage
|
|
cyPMElecOutletTablePowerFactorValue Integer32, -- actual value for powerfactor
|
|
cyPMElecOutletTablePowerFactorMax Integer32, -- max value for powerfactor
|
|
cyPMElecOutletTablePowerType INTEGER, -- type of power
|
|
cyPMElecOutletTableVoltageType INTEGER, -- type of voltage
|
|
cyPMElecOutletTablePowerFactorType INTEGER -- type of powerfactor
|
|
}
|
|
|
|
cyPMElecOutletTablePortNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Serial Port number where the PDU is connected."
|
|
::= { cyPMElecOutletTableEntry 1 }
|
|
|
|
cyPMElecOutletTablePduNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The number of the PDU unit in the daisy-chained mode"
|
|
::= { cyPMElecOutletTableEntry 2 }
|
|
|
|
cyPMElecOutletTableNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "outlet number in the PDU"
|
|
::= { cyPMElecOutletTableEntry 3 }
|
|
|
|
cyPMElecOutletTableName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "name of the Outlet."
|
|
::= { cyPMElecOutletTableEntry 4 }
|
|
|
|
cyPMElecOutletTableCurrentValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Actual value of current in the Outlet (A x 10)."
|
|
::= { cyPMElecOutletTableEntry 5 }
|
|
|
|
cyPMElecOutletTableCurrentMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Maximum detected value of current in the Outlet (A x 10).
|
|
Write operation accepts only 0 for reset action."
|
|
::= { cyPMElecOutletTableEntry 6 }
|
|
|
|
cyPMElecOutletTablePowerValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Actual value of power in the Outlet (W x 10)."
|
|
::= { cyPMElecOutletTableEntry 7 }
|
|
|
|
cyPMElecOutletTablePowerMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Maximum value of power in the Outlet (W x 10).Write operation
|
|
accepts only 0 for reset action."
|
|
::= { cyPMElecOutletTableEntry 8 }
|
|
|
|
cyPMElecOutletTableVoltageValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Actual value of voltage in the Outlet (V).When Outlet does
|
|
not have voltage sensor, it returns 0."
|
|
::= { cyPMElecOutletTableEntry 9 }
|
|
|
|
cyPMElecOutletTableVoltageMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Maximum value of voltage in the Outlet (V). When Outlet does
|
|
not have voltage sensor, it returns 0. Write operation accepts
|
|
only 0 for reset action."
|
|
::= { cyPMElecOutletTableEntry 10 }
|
|
|
|
cyPMElecOutletTablePowerFactorValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Actual value of power factor in the Outlet (Pf x 10). When
|
|
Outlet does not have power factor sensor, returns 0."
|
|
::= { cyPMElecOutletTableEntry 11 }
|
|
|
|
cyPMElecOutletTablePowerFactorMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Maximum value of power factor in the Outlet (Pf x 10). When
|
|
Outlet does not have power factor sensor, returns 0.Write
|
|
operation accepts only 0 for reset action."
|
|
::= { cyPMElecOutletTableEntry 12 }
|
|
|
|
cyPMElecOutletTablePowerType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
estimated(1),
|
|
measured(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The type of Power sensor for this elecmon"
|
|
::= { cyPMElecOutletTableEntry 13 }
|
|
|
|
cyPMElecOutletTableVoltageType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
estimated(1),
|
|
measured(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The type of Voltage sensor for this elecmon"
|
|
::= { cyPMElecOutletTableEntry 14 }
|
|
|
|
cyPMElecOutletTablePowerFactorType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
estimated(1),
|
|
measured(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The type of Power Factor sensor for this elecmon"
|
|
::= { cyPMElecOutletTableEntry 15 }
|
|
|
|
cyPMEnvMonTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF CyPMEnvMonTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Allow operations on environmental monitors"
|
|
::= { cyACS5KPM 9 }
|
|
|
|
cyPMEnvMonTableEntry OBJECT-TYPE
|
|
SYNTAX CyPMEnvMonTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "each entry has the information about the environmental monitors."
|
|
INDEX {
|
|
cyPMEnvMonTablePortNumber,
|
|
cyPMEnvMonTablePduNumber,
|
|
cyPMEnvMonTableIndex
|
|
}
|
|
::= { cyPMEnvMonTable 1 }
|
|
|
|
CyPMEnvMonTableEntry ::= SEQUENCE {
|
|
cyPMEnvMonTablePortNumber InterfaceIndex, -- serial port #
|
|
cyPMEnvMonTablePduNumber InterfaceIndex, -- pdu number in the chain
|
|
cyPMEnvMonTableIndex InterfaceIndex, -- index of the monitor
|
|
cyPMEnvMonTableName DisplayString, -- monitor sysname
|
|
cyPMEnvMonTableType INTEGER, -- type of the monitor
|
|
cyPMEnvMonTableStatus INTEGER, -- status of monitors
|
|
cyPMEnvMonTableValue Integer32, -- current value of monitor
|
|
cyPMEnvMonTableMaxValue Integer32
|
|
}
|
|
|
|
cyPMEnvMonTablePortNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Serial Port number where the PDU is connected."
|
|
::= { cyPMEnvMonTableEntry 1 }
|
|
|
|
cyPMEnvMonTablePduNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The number of the PDU unit in the daisy-chained mode"
|
|
::= { cyPMEnvMonTableEntry 2 }
|
|
|
|
cyPMEnvMonTableIndex OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "index of the environmental monitor in the PDU."
|
|
::= { cyPMEnvMonTableEntry 3 }
|
|
|
|
cyPMEnvMonTableName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Name of the environmental monitor."
|
|
::= { cyPMEnvMonTableEntry 4 }
|
|
|
|
cyPMEnvMonTableType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
temp-internal (1),
|
|
temperature (2),
|
|
humidity (3),
|
|
air-flow (4),
|
|
smoke (5),
|
|
dry-concact (6),
|
|
water-level (7),
|
|
motion (8),
|
|
unplugged (9),
|
|
unknown (10)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The type of environmental monitor."
|
|
::= { cyPMEnvMonTableEntry 5 }
|
|
|
|
cyPMEnvMonTableStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
triggered(2),
|
|
not-applicable(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The status of Dry-Contact/Water-level/Smoke/Motion monitors.
|
|
Dry-Contact sensor: Opened(1), closed(2).
|
|
Water level: Normal (1), Triggered(2).
|
|
Smoke sensor: not-detected(1), detected(2).
|
|
Motion sensor: not-detected(1), detected(2)."
|
|
::= { cyPMEnvMonTableEntry 6 }
|
|
|
|
cyPMEnvMonTableValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Actual value of Temperature/Humidity/Air-flow monitors (x 10)."
|
|
::= { cyPMEnvMonTableEntry 7 }
|
|
|
|
cyPMEnvMonTableMaxValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Maximum detected value of Temperature/Humidity/Air-flow monitor (x 10).
|
|
Write operation accepts only 0 for reset action."
|
|
::= { cyPMEnvMonTableEntry 8 }
|
|
|
|
END
|
|
|