Observium_CE/mibs/teracom/TERACOM-TCW241-MIB

1642 lines
43 KiB
Plaintext

TERACOM-TCW241-MIB DEFINITIONS ::= BEGIN
IMPORTS
MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE, enterprises, IpAddress, Integer32, snmpModules
FROM SNMPv2-SMI
DateAndTime, MacAddress, DisplayString FROM SNMPv2-TC
TEXTUAL-CONVENTION FROM SNMPv2-TC
MODULE-COMPLIANCE, OBJECT-GROUP , NOTIFICATION-GROUP
FROM SNMPv2-CONF;
snmpMIB MODULE-IDENTITY
LAST-UPDATED "201801300000Z"
ORGANIZATION "TERACOM"
CONTACT-INFO
"EMail: info@teracomsystems.com"
DESCRIPTION
"The MIB module for TCW241 SNMP entities."
REVISION "201801300000Z"
DESCRIPTION
"TCW241v1.2"
::= { snmpModules 1 }
teracom OBJECT IDENTIFIER ::= { enterprises 38783 }
tcw241 OBJECT IDENTIFIER ::= { teracom 3 }
trapNotifications OBJECT IDENTIFIER ::= { tcw241 0 }
product OBJECT IDENTIFIER ::= { tcw241 1 }
setup OBJECT IDENTIFIER ::= { tcw241 2 }
monitorNcontrol OBJECT IDENTIFIER ::= { tcw241 3 }
tcw241MIBConformance OBJECT IDENTIFIER ::= { tcw241 4 }
tcw241MIBCompliances OBJECT IDENTIFIER ::= { tcw241MIBConformance 1 }
tcw241MIBGroups OBJECT IDENTIFIER ::= { tcw241MIBConformance 2 }
CONTROLLED ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Relay control logic"
SYNTAX INTEGER
{ manual(0),sensor11(1),sensor12(2),sensor21(3),sensor22(4),
sensor31(5),sensor32(6),sensor41(7),sensor42(8),sensor51(9),
sensor52(10),sensor61(11),sensor62(12),sensor71(13),sensor72(14),
sensor81(15),sensor82(16),analog1(17),analog2(18),analog3(19),analog4(20),
digital1(21),digital2(22),digital3(23),digital4(24),
anyAlarm(25),anySensor(26),anyAnalog(27),anyDigital(28),
func1(29),func2(30),func3(31),func4(32),
shedule1(33),shedule2(34),shedule3(35),shedule4(36),
virtual1(37),virtual2(38),virtual3(39),virtual4(40)
}
RELAYACTION ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Relay action"
SYNTAX INTEGER
{turnon(0),pulse(2)}
VIRTUALPARENT ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Virtual input parent"
SYNTAX INTEGER
{ none(0),sensor11(1),sensor12(2),sensor21(3),sensor22(4),
sensor31(5),sensor32(6),sensor41(7),sensor42(8),sensor51(9),
sensor52(10),sensor61(11),sensor62(12),sensor71(13),sensor72(14),
sensor81(15),sensor82(16),analog1(17),analog2(18),analog3(19),analog4(20)
}
SensorId ::= TEXTUAL-CONVENTION
DISPLAY-HINT "16a"
STATUS current
DESCRIPTION
"Sensor ROM code in ASCII HEX format"
SYNTAX OCTET STRING (SIZE (16))
AnalogValue ::= TEXTUAL-CONVENTION
DISPLAY-HINT "d-3"
STATUS current
DESCRIPTION
"Analog value x1000 in Integer format"
SYNTAX Integer32
SensorValue ::= TEXTUAL-CONVENTION
DISPLAY-HINT "d-3"
STATUS current
DESCRIPTION
"Sensor value x1000 in Integer format"
SYNTAX Integer32
VirtualValue ::= TEXTUAL-CONVENTION
DISPLAY-HINT "d-3"
STATUS current
DESCRIPTION
"Virtual input value x1000 in Integer format"
SYNTAX Integer32
name OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Name of product"
::= { product 1 }
version OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Version string"
::= { product 2 }
dateTime OBJECT-TYPE
SYNTAX DateAndTime
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Date and time"
::= { product 3 }
network OBJECT IDENTIFIER ::= { setup 1 }
deviceID OBJECT-TYPE
SYNTAX MacAddress
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Device ID is Default MAC Address"
::= { network 1 }
hostName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..38))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Host Name"
::= { network 2 }
deviceIP OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Device IP Address"
::= { network 3 }
io OBJECT IDENTIFIER ::= { setup 2 }
sensorsSetup OBJECT IDENTIFIER ::= { io 1 }
sensor1setup OBJECT IDENTIFIER ::= { sensorsSetup 1 }
sensor2setup OBJECT IDENTIFIER ::= { sensorsSetup 2 }
sensor3setup OBJECT IDENTIFIER ::= { sensorsSetup 3 }
sensor4setup OBJECT IDENTIFIER ::= { sensorsSetup 4 }
sensor5setup OBJECT IDENTIFIER ::= { sensorsSetup 5 }
sensor6setup OBJECT IDENTIFIER ::= { sensorsSetup 6 }
sensor7setup OBJECT IDENTIFIER ::= { sensorsSetup 7 }
sensor8setup OBJECT IDENTIFIER ::= { sensorsSetup 8 }
s1description OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..12))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sensor1 description"
::= { sensor1setup 1 }
sensor11setup OBJECT IDENTIFIER ::= { sensor1setup 2 }
sensor12setup OBJECT IDENTIFIER ::= { sensor1setup 3 }
s11MAXInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"S11 maximum value x1000 in Integer format"
::= { sensor11setup 1 }
s11MINInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"S11 minimum value x1000 in Integer format"
::= { sensor11setup 2 }
s11HYSTInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"S11 hysteresis value x1000 in Integer format"
::= { sensor11setup 3 }
s12MAXInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"S12 maximum value x1000 in Integer format"
::= { sensor12setup 1 }
s12MINInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"S12 minimum value x1000 in Integer format"
::= { sensor12setup 2 }
s12HYSTInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"S12 hysteresis value x1000 in Integer format"
::= { sensor12setup 3 }
s2description OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..12))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"sensor2 description"
::= { sensor2setup 1 }
sensor21setup OBJECT IDENTIFIER ::= { sensor2setup 2 }
sensor22setup OBJECT IDENTIFIER ::= { sensor2setup 3 }
s21MAXInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s21 maximum value x1000 in Integer format"
::= { sensor21setup 1 }
s21MINInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s21 minimum value x1000 in Integer format"
::= { sensor21setup 2 }
s21HYSTInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s21 hysteresis value x1000 in Integer format"
::= { sensor21setup 3 }
s22MAXInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s22 maximum value x1000 in Integer format"
::= { sensor22setup 1 }
s22MINInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s22 minimum value x1000 in Integer format"
::= { sensor22setup 2 }
s22HYSTInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s22 hysteresis value x1000 in Integer format"
::= { sensor22setup 3 }
s3description OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..12))
MAX-ACCESS read-write
STATUS current DESCRIPTION
"sensor3 description"
::= { sensor3setup 1 }
sensor31setup OBJECT IDENTIFIER ::= { sensor3setup 2 }
sensor32setup OBJECT IDENTIFIER ::= { sensor3setup 3 }
s31MAXInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s31 maximum value x1000 in Integer format"
::= { sensor31setup 1 }
s31MINInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s31 minimum value x1000 in Integer format"
::= { sensor31setup 2 }
s31HYSTInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s31 hysteresis value x1000 in Integer format"
::= { sensor31setup 3 }
s32MAXInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s32 maximum value x1000 in Integer format"
::= { sensor32setup 1 }
s32MINInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s32 minimum value x1000 in Integer format"
::= { sensor32setup 2 }
s32HYSTInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s32 hysteresis value x1000 in Integer format"
::= { sensor32setup 3 }
s4description OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..12))
MAX-ACCESS read-write
STATUS current DESCRIPTION
"sensor4 description"
::= { sensor4setup 1 }
sensor41setup OBJECT IDENTIFIER ::= { sensor4setup 2 }
sensor42setup OBJECT IDENTIFIER ::= { sensor4setup 3 }
s41MAXInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s41 maximum value x1000 in Integer format"
::= { sensor41setup 1 }
s41MINInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s41 minimum value x1000 in Integer format"
::= { sensor41setup 2 }
s41HYSTInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s41 hysteresis value x1000 in Integer format"
::= { sensor41setup 3 }
s42MAXInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s42 maximum value x1000 in Integer format"
::= { sensor42setup 1 }
s42MINInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s42 minimum value x1000 in Integer format"
::= { sensor42setup 2 }
s42HYSTInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s42 hysteresis value x1000 in Integer format"
::= { sensor42setup 3 }
s5description OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..12))
MAX-ACCESS read-write
STATUS current DESCRIPTION
"sensor5 description"
::= { sensor5setup 1 }
sensor51setup OBJECT IDENTIFIER ::= { sensor5setup 2 }
sensor52setup OBJECT IDENTIFIER ::= { sensor5setup 3 }
s51MAXInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s51 maximum value x1000 in Integer format"
::= { sensor51setup 1 }
s51MINInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s51 minimum value x1000 in Integer format"
::= { sensor51setup 2 }
s51HYSTInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s51 hysteresis value x1000 in Integer format"
::= { sensor51setup 3 }
s52MAXInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s52 maximum value x1000 in Integer format"
::= { sensor52setup 1 }
s52MINInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s52 minimum value x1000 in Integer format"
::= { sensor52setup 2 }
s52HYSTInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s52 hysteresis value x1000 in Integer format"
::= { sensor52setup 3 }
s6description OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..12))
MAX-ACCESS read-write
STATUS current DESCRIPTION
"sensor6 description"
::= { sensor6setup 1 }
sensor61setup OBJECT IDENTIFIER ::= { sensor6setup 2 }
sensor62setup OBJECT IDENTIFIER ::= { sensor6setup 3 }
s61MAXInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s61 maximum value x1000 in Integer format"
::= { sensor61setup 1 }
s61MINInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s61 minimum value x1000 in Integer format"
::= { sensor61setup 2 }
s61HYSTInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s61 hysteresis value x1000 in Integer format"
::= { sensor61setup 3 }
s62MAXInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s62 maximum value x1000 in Integer format"
::= { sensor62setup 1 }
s62MINInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s62 minimum value x1000 in Integer format"
::= { sensor62setup 2 }
s62HYSTInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s62 hysteresis value x1000 in Integer format"
::= { sensor62setup 3 }
s7description OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..12))
MAX-ACCESS read-write
STATUS current DESCRIPTION
"sensor7 description"
::= { sensor7setup 1 }
sensor71setup OBJECT IDENTIFIER ::= { sensor7setup 2 }
sensor72setup OBJECT IDENTIFIER ::= { sensor7setup 3 }
s71MAXInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s71 maximum value x1000 in Integer format"
::= { sensor71setup 1 }
s71MINInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s71 minimum value x1000 in Integer format"
::= { sensor71setup 2 }
s71HYSTInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s71 hysteresis value x1000 in Integer format"
::= { sensor71setup 3 }
s72MAXInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s72 maximum value x1000 in Integer format"
::= { sensor72setup 1 }
s72MINInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s72 minimum value x1000 in Integer format"
::= { sensor72setup 2 }
s72HYSTInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s72 hysteresis value x1000 in Integer format"
::= { sensor72setup 3 }
s8description OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..12))
MAX-ACCESS read-write
STATUS current DESCRIPTION
"sensor8 description"
::= { sensor8setup 1 }
sensor81setup OBJECT IDENTIFIER ::= { sensor8setup 2 }
sensor82setup OBJECT IDENTIFIER ::= { sensor8setup 3 }
s81MAXInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s81 maximum value x1000 in Integer format"
::= { sensor81setup 1 }
s81MINInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s81 minimum value x1000 in Integer format"
::= { sensor81setup 2 }
s81HYSTInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s81 hysteresis value x1000 in Integer format"
::= { sensor81setup 3 }
s82MAXInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s82 maximum value x1000 in Integer format"
::= { sensor82setup 1 }
s82MINInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s82 minimum value x1000 in Integer format"
::= { sensor82setup 2 }
s82HYSTInt OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"s82 hysteresis value x1000 in Integer format"
::= { sensor82setup 3 }
analogSetup OBJECT IDENTIFIER ::= { io 2 }
analog1setup OBJECT IDENTIFIER ::= { analogSetup 1 }
analog2setup OBJECT IDENTIFIER ::= { analogSetup 2 }
analog3setup OBJECT IDENTIFIER ::= { analogSetup 3 }
analog4setup OBJECT IDENTIFIER ::= { analogSetup 4 }
voltage1description OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..12))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Voltage 1 description"
::= { analog1setup 1 }
voltage1max OBJECT-TYPE
SYNTAX AnalogValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Voltage 1 maximum x1000 in Integer format"
::= { analog1setup 2 }
voltage1min OBJECT-TYPE
SYNTAX AnalogValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Voltage 1 minimum x1000 in Integer format"
::= { analog1setup 3 }
voltage1hyst OBJECT-TYPE
SYNTAX AnalogValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Voltage 1 hysteresis x1000 in Integer format"
::= { analog1setup 4 }
voltage2description OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..12))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Voltage 2 description"
::= { analog2setup 1 }
voltage2max OBJECT-TYPE
SYNTAX AnalogValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Voltage 2 maximum x1000 in Integer format"
::= { analog2setup 2 }
voltage2min OBJECT-TYPE
SYNTAX AnalogValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Voltage 2 minimum x1000 in Integer format"
::= { analog2setup 3 }
voltage2hyst OBJECT-TYPE
SYNTAX AnalogValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Voltage 2 hysteresis x1000 in Integer format"
::= { analog2setup 4 }
voltage3description OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..12))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Voltage 3 description"
::= { analog3setup 1 }
voltage3max OBJECT-TYPE
SYNTAX AnalogValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Voltage 3 maximum x1000 in Integer format"
::= { analog3setup 2 }
voltage3min OBJECT-TYPE
SYNTAX AnalogValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Voltage 3 minimum x1000 in Integer format"
::= { analog3setup 3 }
voltage3hyst OBJECT-TYPE
SYNTAX AnalogValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Voltage 3 hysteresis x1000 in Integer format"
::= { analog3setup 4 }
voltage4description OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..12))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Voltage 4 description"
::= { analog4setup 1 }
voltage4max OBJECT-TYPE
SYNTAX AnalogValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Voltage 4 maximum x1000 in Integer format"
::= { analog4setup 2 }
voltage4min OBJECT-TYPE
SYNTAX AnalogValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Voltage 4 minimum x1000 in Integer format"
::= { analog4setup 3 }
voltage4hyst OBJECT-TYPE
SYNTAX AnalogValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Voltage 4 hysteresis x1000 in Integer format"
::= { analog4setup 4 }
digitalSetup OBJECT IDENTIFIER ::= { io 3 }
digitalInput1description OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..12))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Digital Input 1 description"
::= { digitalSetup 1 }
digitalInput2description OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..12))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Digital Input 2 description"
::= { digitalSetup 2 }
digitalInput3description OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..12))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Digital Input 3 description"
::= { digitalSetup 3 }
digitalInput4description OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..12))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Digital Input 4 description"
::= { digitalSetup 4 }
relaysSetup OBJECT IDENTIFIER ::= { io 4 }
relay1setup OBJECT IDENTIFIER ::= { relaysSetup 1 }
relay2setup OBJECT IDENTIFIER ::= { relaysSetup 2 }
relay3setup OBJECT IDENTIFIER ::= { relaysSetup 3 }
relay4setup OBJECT IDENTIFIER ::= { relaysSetup 4 }
relay1description OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..12))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Relay 1 description"
::= { relay1setup 1 }
relay1pulseWidth OBJECT-TYPE
SYNTAX Integer32 (1..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Relay1 Pulse x100ms"
::= { relay1setup 2 }
relay1controlledBy OBJECT-TYPE
SYNTAX CONTROLLED
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Relay1 control logic"
::= { relay1setup 3 }
relay1action OBJECT-TYPE
SYNTAX RELAYACTION
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Relay1 action"
::= { relay1setup 4 }
relay2description OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..12))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Relay 2 description"
::= { relay2setup 1 }
relay2pulseWidth OBJECT-TYPE
SYNTAX Integer32 (1..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Relay2 Pulse x100ms"
::= { relay2setup 2 }
relay2controlledBy OBJECT-TYPE
SYNTAX CONTROLLED
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Relay2 control logic"
::= { relay2setup 3 }
relay2action OBJECT-TYPE
SYNTAX RELAYACTION
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Relay2 action"
::= { relay2setup 4 }
relay3description OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..12))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Relay 3 description"
::= { relay3setup 1 }
relay3pulseWidth OBJECT-TYPE
SYNTAX Integer32 (1..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Relay3 Pulse x100ms"
::= { relay3setup 2 }
relay3controlledBy OBJECT-TYPE
SYNTAX CONTROLLED
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Relay3 control logic"
::= { relay3setup 3 }
relay3action OBJECT-TYPE
SYNTAX RELAYACTION
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Relay3 action"
::= { relay3setup 4 }
relay4description OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..12))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Relay 4 description"
::= { relay4setup 1 }
relay4pulseWidth OBJECT-TYPE
SYNTAX Integer32 (1..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Relay4 Pulse x100ms"
::= { relay4setup 2 }
relay4controlledBy OBJECT-TYPE
SYNTAX CONTROLLED
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Relay4 control logic"
::= { relay4setup 3 }
relay4action OBJECT-TYPE
SYNTAX RELAYACTION
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Relay4 action"
::= { relay4setup 4 }
virtualSetup OBJECT IDENTIFIER ::= { io 5 }
virtual1setup OBJECT IDENTIFIER ::= { virtualSetup 1 }
virtual2setup OBJECT IDENTIFIER ::= { virtualSetup 2 }
virtual3setup OBJECT IDENTIFIER ::= { virtualSetup 3 }
virtual4setup OBJECT IDENTIFIER ::= { virtualSetup 4 }
virtualInput1description OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..12))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Virtual input 1 description"
::= { virtual1setup 1 }
virtualInput1max OBJECT-TYPE
SYNTAX VirtualValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Virtual input 1 maximum"
::= { virtual1setup 2 }
virtualInput1min OBJECT-TYPE
SYNTAX VirtualValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Virtual input 1 minimum"
::= { virtual1setup 3 }
virtualInput1hyst OBJECT-TYPE
SYNTAX VirtualValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Virtual input 1 hysteresis"
::= { virtual1setup 4 }
virtualInput1Parent OBJECT-TYPE
SYNTAX VIRTUALPARENT
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Virtual input 1 parent"
::= { virtual1setup 5 }
virtualInput2description OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..12))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Virtual input 2 description"
::= { virtual2setup 1 }
virtualInput2max OBJECT-TYPE
SYNTAX VirtualValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Virtual input 2 maximum"
::= { virtual2setup 2 }
virtualInput2min OBJECT-TYPE
SYNTAX VirtualValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Virtual input 2 minimum"
::= { virtual2setup 3 }
virtualInput2hyst OBJECT-TYPE
SYNTAX VirtualValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Virtual input 2 hysteresis"
::= { virtual2setup 4 }
virtualInput2Parent OBJECT-TYPE
SYNTAX VIRTUALPARENT
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Virtual input 2 parent"
::= { virtual2setup 5 }
virtualInput3description OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..12))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Virtual input 3 description"
::= { virtual3setup 1 }
virtualInput3max OBJECT-TYPE
SYNTAX VirtualValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Virtual input 3 maximum"
::= { virtual3setup 2 }
virtualInput3min OBJECT-TYPE
SYNTAX VirtualValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Virtual input 3 minimum"
::= { virtual3setup 3 }
virtualInput3hyst OBJECT-TYPE
SYNTAX VirtualValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Virtual input 3 hysteresis"
::= { virtual3setup 4 }
virtualInput3Parent OBJECT-TYPE
SYNTAX VIRTUALPARENT
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Virtual input 3 parent"
::= { virtual3setup 5 }
virtualInput4description OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..12))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Virtual input 4 description"
::= { virtual4setup 1 }
virtualInput4max OBJECT-TYPE
SYNTAX VirtualValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Virtual input 4 maximum"
::= { virtual4setup 2 }
virtualInput4min OBJECT-TYPE
SYNTAX VirtualValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Virtual input 4 minimum"
::= { virtual4setup 3 }
virtualInput4hyst OBJECT-TYPE
SYNTAX VirtualValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Virtual input 4 hysteresis"
::= { virtual4setup 4 }
virtualInput4Parent OBJECT-TYPE
SYNTAX VIRTUALPARENT
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Virtual input 4 parent"
::= { virtual4setup 5 }
sensors OBJECT IDENTIFIER ::= { monitorNcontrol 1 }
sensor1 OBJECT IDENTIFIER ::= { sensors 1 }
s11Int OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"S11 value x1000 in Integer format"
::= { sensor1 1 }
s12Int OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"S12 value x1000 in Integer format"
::= { sensor1 2 }
s1ID OBJECT-TYPE
SYNTAX SensorId
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"S1 ID value"
::= { sensor1 3 }
sensor2 OBJECT IDENTIFIER ::= { sensors 2 }
s21Int OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"S21 value x1000 in Integer format"
::= { sensor2 1 }
s22Int OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"S22 value x1000 in Integer format"
::= { sensor2 2 }
s2ID OBJECT-TYPE
SYNTAX SensorId
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"S2 ID value"
::= { sensor2 3 }
sensor3 OBJECT IDENTIFIER ::= { sensors 3 }
s31Int OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"S31 value x1000 in Integer format"
::= { sensor3 1 }
s32Int OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"S32 value x1000 in Integer format"
::= { sensor3 2 }
s3ID OBJECT-TYPE
SYNTAX SensorId
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"S3 ID value"
::= { sensor3 3 }
sensor4 OBJECT IDENTIFIER ::= { sensors 4 }
s41Int OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"S41 value x1000 in Integer format"
::= { sensor4 1 }
s42Int OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"S42 value x1000 in Integer format"
::= { sensor4 2 }
s4ID OBJECT-TYPE
SYNTAX SensorId
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"S4 ID value"
::= { sensor4 3 }
sensor5 OBJECT IDENTIFIER ::= { sensors 5 }
s51Int OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"S51 value x1000 in Integer format"
::= { sensor5 1 }
s52Int OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"S52 value x1000 in Integer format"
::= { sensor5 2 }
s5ID OBJECT-TYPE
SYNTAX SensorId
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"S5 ID value"
::= { sensor5 3 }
sensor6 OBJECT IDENTIFIER ::= { sensors 6 }
s61Int OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"S61 value x1000 in Integer format"
::= { sensor6 1 }
s62Int OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"S62 value x1000 in Integer format"
::= { sensor6 2 }
s6ID OBJECT-TYPE
SYNTAX SensorId
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"S6 ID value"
::= { sensor6 3 }
sensor7 OBJECT IDENTIFIER ::= { sensors 7 }
s71Int OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"S71 value x1000 in Integer format"
::= { sensor7 1 }
s72Int OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"S72 value x1000 in Integer format"
::= { sensor7 2 }
s7ID OBJECT-TYPE
SYNTAX SensorId
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"S7 ID value"
::= { sensor7 3 }
sensor8 OBJECT IDENTIFIER ::= { sensors 8 }
s81Int OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"S81 value x1000 in Integer format"
::= { sensor8 1 }
s82Int OBJECT-TYPE
SYNTAX SensorValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"S82 value x1000 in Integer format"
::= { sensor8 2 }
s8ID OBJECT-TYPE
SYNTAX SensorId
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"S8 ID value"
::= { sensor8 3 }
analog OBJECT IDENTIFIER ::= { monitorNcontrol 2 }
voltage1Int OBJECT-TYPE
SYNTAX AnalogValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Voltage1 x1000 in Integer format"
::= { analog 1 }
voltage2Int OBJECT-TYPE
SYNTAX AnalogValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Voltage2 x1000 in Integer format"
::= { analog 2 }
voltage3Int OBJECT-TYPE
SYNTAX AnalogValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Voltage3 x1000 in Integer format"
::= { analog 3 }
voltage4Int OBJECT-TYPE
SYNTAX AnalogValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Voltage4 x1000 in Integer format"
::= { analog 4 }
digital OBJECT IDENTIFIER ::= { monitorNcontrol 3 }
digitalInput1State OBJECT-TYPE
SYNTAX INTEGER { closed(0), open(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Digital1 Input State"
::= { digital 1 }
digitalInput2State OBJECT-TYPE
SYNTAX INTEGER { closed(0), open(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Digital2 Input State"
::= { digital 2 }
digitalInput3State OBJECT-TYPE
SYNTAX INTEGER { closed(0), open(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Digital3 Input State"
::= { digital 3 }
digitalInput4State OBJECT-TYPE
SYNTAX INTEGER { closed(0), open(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Digital4 Input State"
::= { digital 4 }
relays OBJECT IDENTIFIER ::= { monitorNcontrol 4 }
relay1 OBJECT IDENTIFIER ::= { relays 1 }
relay1State OBJECT-TYPE
SYNTAX INTEGER { off(0), on(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Relay1 State"
::= { relay1 1 }
relay1Pulse OBJECT-TYPE
SYNTAX INTEGER { off(0), on(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Relay1 Pulse"
::= { relay1 2 }
relay2 OBJECT IDENTIFIER ::= { relays 2 }
relay2State OBJECT-TYPE
SYNTAX INTEGER { off(0), on(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Relay2 State"
::= { relay2 1 }
relay2Pulse OBJECT-TYPE
SYNTAX INTEGER { off(0), on(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Relay2 Pulse"
::= { relay2 2 }
relay3 OBJECT IDENTIFIER ::= { relays 3 }
relay3State OBJECT-TYPE
SYNTAX INTEGER { off(0), on(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Relay3 State"
::= { relay3 1 }
relay3Pulse OBJECT-TYPE
SYNTAX INTEGER { off(0), on(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Relay3 Pulse"
::= { relay3 2 }
relay4 OBJECT IDENTIFIER ::= { relays 4 }
relay4State OBJECT-TYPE
SYNTAX INTEGER { off(0), on(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Relay4 State"
::= { relay4 1 }
relay4Pulse OBJECT-TYPE
SYNTAX INTEGER { off(0), on(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Relay4 Pulse"
::= { relay4 2 }
--- configurationSaved
configurationSaved OBJECT-TYPE
SYNTAX INTEGER { unsaved(0), saved(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Configuration save status SAVED/UNSAVED"
::= { monitorNcontrol 5 }
restartDevice OBJECT-TYPE
SYNTAX INTEGER { cancel(0), restart(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Restart Device"
::= { monitorNcontrol 6}
temperatureUnit OBJECT-TYPE
SYNTAX INTEGER { celcius(0), fahrenheit(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Unit of the all temperature values"
::= { monitorNcontrol 7}
hardwareErr OBJECT-TYPE
SYNTAX INTEGER { noErr(0), owErr(1), hwErr(2) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Hardware Error"
::= { monitorNcontrol 8}
pressureUnit OBJECT-TYPE
SYNTAX INTEGER { hPa(0), mbar(1), mmhg(2) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Unit of the pressure value"
::= { monitorNcontrol 9}
functions OBJECT IDENTIFIER ::= { monitorNcontrol 10 }
func1State OBJECT-TYPE
SYNTAX INTEGER { false(0), true(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Funtion 1 State"
::= { functions 1 }
func2State OBJECT-TYPE
SYNTAX INTEGER { false(0), true(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Funtion 2 State"
::= { functions 2 }
func3State OBJECT-TYPE
SYNTAX INTEGER { false(0), true(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Funtion 3 State"
::= { functions 3 }
func4State OBJECT-TYPE
SYNTAX INTEGER { false(0), true(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Funtion 4 State"
::= { functions 4 }
virtual OBJECT IDENTIFIER ::= { monitorNcontrol 11 }
virtualInput1Int OBJECT-TYPE
SYNTAX VirtualValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Virtual input 1 x1000 in Integer format"
::= { virtual 1 }
virtualInput2Int OBJECT-TYPE
SYNTAX VirtualValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Virtual input 2 x1000 in Integer format"
::= { virtual 2 }
virtualInput3Int OBJECT-TYPE
SYNTAX VirtualValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Virtual input 3 x1000 in Integer format"
::= { virtual 3 }
virtualInput4Int OBJECT-TYPE
SYNTAX VirtualValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Virtual input 4 x1000 in Integer format"
::= { virtual 4 }
snmp-trap-notification NOTIFICATION-TYPE
OBJECTS { digitalInput1State,digitalInput2State,
digitalInput3State,digitalInput4State,
voltage1Int,voltage2Int,voltage3Int,voltage4Int,
s11Int,s12Int,
s21Int,s22Int,
s31Int,s32Int,
s41Int,s42Int,
s51Int,s52Int,
s61Int,s62Int,
s71Int,s72Int,
s81Int,s82Int,
restartDevice,deviceIP,
func1State, func2State, func3State, func4State,
virtualInput1Int, virtualInput2Int, virtualInput3Int, virtualInput4Int
}
STATUS current
DESCRIPTION
"SMIV2 Trap notification information for the SNMP Manager."
::= {trapNotifications 1}
tcw241MIBCompliances1 MODULE-COMPLIANCE
STATUS current
DESCRIPTION
"This group is for SNMP applications."
MODULE -- this module
MANDATORY-GROUPS { tcw241ProductGroup, tcw241SetupGroup, tcw241MonitorGroup, tcw241TrapGroup}
::= { tcw241MIBCompliances 1 }
tcw241ProductGroup OBJECT-GROUP
OBJECTS {name, version, dateTime}
STATUS current
DESCRIPTION
"A collection of objects providing basic product info."
::= { tcw241MIBGroups 1 }
tcw241SetupGroup OBJECT-GROUP
OBJECTS { deviceID, hostName, deviceIP,
s1description, s11MAXInt, s11MINInt, s11HYSTInt, s12MAXInt, s12MINInt, s12HYSTInt,
s2description, s21MAXInt, s21MINInt, s21HYSTInt, s22MAXInt, s22MINInt, s22HYSTInt,
s3description, s31MAXInt, s31MINInt, s31HYSTInt, s32MAXInt, s32MINInt, s32HYSTInt,
s4description, s41MAXInt, s41MINInt, s41HYSTInt, s42MAXInt, s42MINInt, s42HYSTInt,
s5description, s51MAXInt, s51MINInt, s51HYSTInt, s52MAXInt, s52MINInt, s52HYSTInt,
s6description, s61MAXInt, s61MINInt, s61HYSTInt, s62MAXInt, s62MINInt, s62HYSTInt,
s7description, s71MAXInt, s71MINInt, s71HYSTInt, s72MAXInt, s72MINInt, s72HYSTInt,
s8description, s81MAXInt, s81MINInt, s81HYSTInt, s82MAXInt, s82MINInt, s82HYSTInt,
voltage1description, voltage1max, voltage1min, voltage1hyst,
voltage2description, voltage2max, voltage2min, voltage2hyst,
voltage3description, voltage3max, voltage3min, voltage3hyst,
voltage4description, voltage4max, voltage4min, voltage4hyst,
digitalInput1description, digitalInput2description, digitalInput3description, digitalInput4description,
relay1description, relay1pulseWidth, relay1controlledBy, relay1action,
relay2description, relay2pulseWidth, relay2controlledBy, relay2action,
relay3description, relay3pulseWidth, relay3controlledBy, relay3action,
relay4description, relay4pulseWidth, relay4controlledBy, relay4action,
virtualInput1description, virtualInput1max, virtualInput1min, virtualInput1hyst, virtualInput1Parent,
virtualInput2description, virtualInput2max, virtualInput2min, virtualInput2hyst, virtualInput2Parent,
virtualInput3description, virtualInput3max, virtualInput3min, virtualInput3hyst, virtualInput3Parent,
virtualInput4description, virtualInput4max, virtualInput4min, virtualInput4hyst, virtualInput4Parent
}
STATUS current
DESCRIPTION
"A collection of objects providing basic setup."
::= { tcw241MIBGroups 2 }
tcw241MonitorGroup OBJECT-GROUP
OBJECTS { s11Int, s12Int, s1ID, s21Int, s22Int, s2ID, s31Int, s32Int, s3ID,
s41Int, s42Int, s4ID, s51Int, s52Int, s5ID, s61Int, s62Int, s6ID,
s71Int, s72Int, s7ID, s81Int, s82Int, s8ID,
voltage1Int, voltage2Int, voltage3Int, voltage4Int,
digitalInput1State, digitalInput2State, digitalInput3State, digitalInput4State,
relay1State, relay1Pulse, relay2State, relay2Pulse, relay3State, relay3Pulse, relay4State, relay4Pulse,
configurationSaved, restartDevice, temperatureUnit, hardwareErr, pressureUnit,
func1State, func2State, func3State, func4State,
virtualInput1Int, virtualInput2Int, virtualInput3Int, virtualInput4Int
}
STATUS current
DESCRIPTION
"A collection of objects providing basic monitoring
and control of a product."
::= { tcw241MIBGroups 3 }
tcw241TrapGroup NOTIFICATION-GROUP
NOTIFICATIONS {snmp-trap-notification}
STATUS current
DESCRIPTION
"SNMP Trap Notification object."
::= { tcw241MIBGroups 4 }
END