Observium_CE/mibs/scte/SCTE-HMS-HE-FAN-MIB

183 lines
5.2 KiB
Plaintext

-- Module Name: HMS117R6.MIB (SCTE 84-3)
SCTE-HMS-HE-FAN-MIB DEFINITIONS ::= BEGIN
IMPORTS
OBJECT-TYPE, MODULE-IDENTITY, Unsigned32
FROM SNMPv2-SMI
OBJECT-GROUP, MODULE-COMPLIANCE
FROM SNMPv2-CONF
entPhysicalIndex
FROM ENTITY-MIB
heFans, HeMilliAmp, HeFaultStatus
FROM SCTE-HMS-HEADENDIDENT-MIB;
heFanModuleMIB MODULE-IDENTITY
LAST-UPDATED "200403250410Z"
ORGANIZATION
"SCTE HMS Working Group"
CONTACT-INFO
"SCTE HMS Subcommittee, Chairman
mail to: standards@scte.org"
DESCRIPTION
"The MIB module is for representing Fans and Fan Groupings present
in the headend (or indoor) plant which are supported by a SNMP agent."
::= { heFans 1 }
heFanMIBObjects OBJECT IDENTIFIER ::= { heFanModuleMIB 1 }
-- Conformance information
heFanMIBConformance OBJECT IDENTIFIER ::= { heFanModuleMIB 2 }
heFanMIBCompliances OBJECT IDENTIFIER ::= { heFanMIBConformance 1 }
heFanMIBGroups OBJECT IDENTIFIER ::= { heFanMIBConformance 2 }
-- The Fan Unit Table
heFanUnitTable OBJECT-TYPE
SYNTAX SEQUENCE OF HeFanUnitEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table containing information about headend (or indoor)
fan groupings. Fans can be in a Fan Tray, Power Supplies,
attached to the Cabinet, or any fan entity managed by this
SNMP agent. Each fan grouping will have an associated entry
in the Entity mib."
::= { heFanMIBObjects 1 }
heFanUnitEntry OBJECT-TYPE
SYNTAX HeFanUnitEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Information about each Fan Grouping in the subsystem."
INDEX { entPhysicalIndex }
::= { heFanUnitTable 1 }
HeFanUnitEntry ::= SEQUENCE {
heFanUnitAlarm
HeFaultStatus
}
heFanUnitAlarm OBJECT-TYPE
SYNTAX HeFaultStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The fan grouping status. If every fan in the grouping is
operating in normal condition the value returned is
normal(1), otherwise the value returned will be fault(2).
This object must provide for the alarm management capabilities
with a corresponding entry in the discretePropertyTable of
SCTE-HMS-PROPERTY-MIB (ANSI/SCTE 38-1).
An Alarm Shall be recorded as an entry in the currentAlarmTable
of SCTE-HMS-PROPERTY-MIB (ANSI/SCTE 38-1).
A log record shall be added as an entry in the heCommonLogTable.
An heCommonAlarmEvent notification shall be sent."
::= { heFanUnitEntry 1 }
-- The Fan Status Table
heFanStatusTable OBJECT-TYPE
SYNTAX SEQUENCE OF HeFanStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of monitorable parameter entries for each fan or fan grouping."
::= { heFanMIBObjects 2 }
heFanStatusEntry OBJECT-TYPE
SYNTAX HeFanStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing management information applicable
to a particular fan or fan grouping for this particular fan entity unit."
INDEX { entPhysicalIndex,
heFanStatusIndex }
::= { heFanStatusTable 1 }
HeFanStatusEntry ::= SEQUENCE {
heFanStatusIndex
Unsigned32,
heFanStatusCurrent
HeMilliAmp,
heFanStatusAlarm
HeFaultStatus
}
heFanStatusIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An arbitrary value which uniquely identifies the fan or fan grouping
for this particular fan entity unit."
::= { heFanStatusEntry 1 }
heFanStatusCurrent OBJECT-TYPE
SYNTAX HeMilliAmp
UNITS "milliamperes"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current of this fan or fan grouping for this particular fan entity unit."
::= { heFanStatusEntry 2 }
heFanStatusAlarm OBJECT-TYPE
SYNTAX HeFaultStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This object contains the current alarm status for
this fan or fan grouping for this particular fan entity unit.
This object must provide for the alarm management capabilities
with a corresponding entry in the discretePropertyTable of
SCTE-HMS-PROPERTY-MIB (ANSI/SCTE 38-1).
An alarm shall be recorded as an entry in the currentAlarmTable
of SCTE-HMS-PROPERTY-MIB (ANSI/SCTE 38-1).
A log record shall be added as an entry in the heCommonLogTable.
An heCommonAlarmEvent notification shall be sent."
::= { heFanStatusEntry 3 }
-- Compliance statements
heFanCompliance MODULE-COMPLIANCE
STATUS current
DESCRIPTION
"The minimum compliance statement for indoor fans."
MODULE
MANDATORY-GROUPS { heFanUnitMandatoryGroup }
GROUP heFanStatusGroup
DESCRIPTION
"The heFanStatusGroup is unconditionally optional."
::= { heFanMIBCompliances 1 }
-- this module
heFanUnitMandatoryGroup OBJECT-GROUP
OBJECTS { heFanUnitAlarm }
STATUS current
DESCRIPTION
"The main group defines mandatory objects for all indoor fans."
::= { heFanMIBGroups 1 }
heFanStatusGroup OBJECT-GROUP
OBJECTS { heFanStatusAlarm,
heFanStatusCurrent }
STATUS current
DESCRIPTION
"A collection of objects that provide information applicable
to a particular fan's status parameters."
::= { heFanMIBGroups 2 }
END