LHX-MIB DEFINITIONS ::= BEGIN
IMPORTS
MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE,
enterprises, Integer32, Unsigned32 FROM SNMPv2-SMI
MODULE-COMPLIANCE, OBJECT-GROUP, NOTIFICATION-GROUP FROM SNMPv2-CONF
TEXTUAL-CONVENTION, DisplayString, TruthValue FROM SNMPv2-TC
InetAddressType, InetAddress, InetPortNumber FROM INET-ADDRESS-MIB
sysContact, sysName, sysLocation FROM RFC1213-MIB;
raritan MODULE-IDENTITY
LAST-UPDATED "201701270000Z" -- January 27, 2017
ORGANIZATION "Raritan"
CONTACT-INFO "
Author: Raritan Americas, Inc.
postal: Raritan Americas, Inc.
400 Cottontail Lane
Somerset, NJ 08873
email: tech@raritan.com
phone: +1 732 764 8886
"
DESCRIPTION "This MIB describes the SNMP functions of the
Schroff Varistar LHX heat exchanger
supported by Raritan devices."
REVISION "201701270000Z" -- January 27, 2017
DESCRIPTION "1) Added deviceSerialNumber under trapInformation
2) Added deviceSerialNumber to the OBJECTS clause of all traps
"
REVISION "201501050000Z" -- January 5, 2015
DESCRIPTION "1) Added agentInetPortNumber under trapInformation
2) Added agentInetPortNumber as a varbind to all traps
"
REVISION "201307240000Z" -- July 24, 2013
DESCRIPTION "SHX 30 support:
- add lhxVoltageLow, lhxBaseElectronicsFailure and
lhxCondenserPumpFailure traps
- add model and fwVersion to lhxConfigurationTable
- add sensorName to sensorConfigurationTable
- support valvePosition sensor type
- add sysContact, sysName, sysLocation to all traps"
REVISION "201208130000Z" -- August 13, 2012
DESCRIPTION "Extend LHX MIB:
- add maximumCoolingState
- add alertState
- add defaultFanSpeed
- make defaultFanSpeed read-writable"
REVISION "201105030000Z" -- May 3, 2011
DESCRIPTION "The first version of the MIB."
::= { enterprises 13742 }
lhxgw OBJECT IDENTIFIER ::= { raritan 9 }
traps OBJECT IDENTIFIER ::= { lhxgw 0 }
configuration OBJECT IDENTIFIER ::= { lhxgw 1 }
measurements OBJECT IDENTIFIER ::= { lhxgw 2 }
conformance OBJECT IDENTIFIER ::= { lhxgw 3 }
lhx OBJECT IDENTIFIER ::= { configuration 3 }
gwSensors OBJECT IDENTIFIER ::= { configuration 4 }
trapInformation OBJECT IDENTIFIER ::= { traps 0 }
compliances OBJECT IDENTIFIER ::= { conformance 1 }
groups OBJECT IDENTIFIER ::= { conformance 2 }
-- Textual Conventions
OperationalStateEnumeration
::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"The operational states of an lhx controller."
SYNTAX INTEGER {
disconnected(0),
offline(1),
online(2)
}
GwSensorTypeEnumeration
::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"The types an lhx sensor can be."
SYNTAX INTEGER {
airTemperature(0),
waterTemperature(1),
fanSpeed(2),
doorContact(3),
valvePosition(4)
}
SensorUnitsEnumeration
::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"The units an lhx sensor can be."
SYNTAX INTEGER {
none(-1),
other(0),
volt(1),
amp(2),
watt(3),
voltamp(4),
wattHour(5),
voltampHour(6),
degreeC(7),
hertz(8),
percent(9),
meterpersec(10),
pascal(11),
psi(12),
g(13),
degreeF(14),
feet(15),
inches(16),
cm(17),
meters(18),
rpm(19)
}
SensorStateEnumeration
::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"The states a sensor can be in."
SYNTAX INTEGER {
unavailable(-1),
open(0),
closed(1),
belowLowerCritical(2),
belowLowerWarning(3),
normal(4),
aboveUpperWarning(5),
aboveUpperCritical(6),
on(7),
off(8),
detected(9),
notDetected(10),
alarmed(11)
}
-- the traps
lhxSensorFailure
NOTIFICATION-TYPE
OBJECTS {
deviceName,
sysContact,
sysName,
sysLocation,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
lhxErrorCode,
portId,
probeId,
deviceSerialNumber
}
STATUS current
DESCRIPTION
"A sensor failure (broken or short circuit) occurred."
::= { traps 1 }
lhxFanFailure
NOTIFICATION-TYPE
OBJECTS {
deviceName,
sysContact,
sysName,
sysLocation,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
lhxErrorCode,
portId,
fanId,
deviceSerialNumber
}
STATUS current
DESCRIPTION
"A fan motor failure occurred."
::= { traps 2 }
lhxPowerSupplyFailure
NOTIFICATION-TYPE
OBJECTS {
deviceName,
sysContact,
sysName,
sysLocation,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
lhxErrorCode,
portId,
powerSupplyId,
deviceSerialNumber
}
STATUS current
DESCRIPTION
"A power supply failure occurred."
::= { traps 3 }
lhxThresholdAirOutlet
NOTIFICATION-TYPE
OBJECTS {
deviceName,
sysContact,
sysName,
sysLocation,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
lhxErrorCode,
portId,
deviceSerialNumber
}
STATUS current
DESCRIPTION
"The air outlet temperature threshold was crossed."
::= { traps 4 }
lhxThresholdAirInlet
NOTIFICATION-TYPE
OBJECTS {
deviceName,
sysContact,
sysName,
sysLocation,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
lhxErrorCode,
portId,
deviceSerialNumber
}
STATUS current
DESCRIPTION
"The air inlet temperature threshold was crossed."
::= { traps 5 }
lhxThresholdWaterInlet
NOTIFICATION-TYPE
OBJECTS {
deviceName,
sysContact,
sysName,
sysLocation,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
lhxErrorCode,
portId,
deviceSerialNumber
}
STATUS current
DESCRIPTION
"The water inlet temperature threshold was crossed."
::= { traps 6 }
lhxDoorOpened
NOTIFICATION-TYPE
OBJECTS {
deviceName,
sysContact,
sysName,
sysLocation,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
lhxErrorCode,
portId,
deviceSerialNumber
}
STATUS current
DESCRIPTION
"The door was opened."
::= { traps 7 }
lhxMaximumCoolingRequest
NOTIFICATION-TYPE
OBJECTS {
deviceName,
sysContact,
sysName,
sysLocation,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
lhxErrorCode,
portId,
deviceSerialNumber
}
STATUS current
DESCRIPTION
"Maximum cooling was requested."
::= { traps 8 }
lhxEmergencyCooling
NOTIFICATION-TYPE
OBJECTS {
deviceName,
sysContact,
sysName,
sysLocation,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
lhxErrorCode,
portId,
deviceSerialNumber
}
STATUS current
DESCRIPTION
"Emergency cooling was activated."
::= { traps 9 }
lhxWaterLeak
NOTIFICATION-TYPE
OBJECTS {
deviceName,
sysContact,
sysName,
sysLocation,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
lhxErrorCode,
portId,
deviceSerialNumber
}
STATUS current
DESCRIPTION
"Water leakage was detected."
::= { traps 10 }
lhxThresholdHumidity
NOTIFICATION-TYPE
OBJECTS {
deviceName,
sysContact,
sysName,
sysLocation,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
lhxErrorCode,
portId,
deviceSerialNumber
}
STATUS current
DESCRIPTION
"The humidity threshold was crossed."
::= { traps 11 }
lhxExternalWaterCoolingFailure
NOTIFICATION-TYPE
OBJECTS {
deviceName,
sysContact,
sysName,
sysLocation,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
lhxErrorCode,
portId,
deviceSerialNumber
}
STATUS current
DESCRIPTION
"An external water cooling failure occurred."
::= { traps 12 }
lhxThresholdWaterOutlet
NOTIFICATION-TYPE
OBJECTS {
deviceName,
sysContact,
sysName,
sysLocation,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
lhxErrorCode,
portId,
deviceSerialNumber
}
STATUS current
DESCRIPTION
"The water outlet temperature threshold was crossed."
::= { traps 13 }
lhxParameterDataLoss
NOTIFICATION-TYPE
OBJECTS {
deviceName,
sysContact,
sysName,
sysLocation,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
lhxErrorCode,
portId,
deviceSerialNumber
}
STATUS current
DESCRIPTION
"Data loss in parameter memory was detected."
::= { traps 14 }
lhxStBusError
NOTIFICATION-TYPE
OBJECTS {
deviceName,
sysContact,
sysName,
sysLocation,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
lhxErrorCode,
portId,
deviceSerialNumber
}
STATUS current
DESCRIPTION
"An ST-Bus communication error was detected."
::= { traps 15 }
lhxCollectiveFault
NOTIFICATION-TYPE
OBJECTS {
deviceName,
sysContact,
sysName,
sysLocation,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
lhxErrorCode,
portId,
deviceSerialNumber
}
STATUS current
DESCRIPTION
"An error was detected."
::= { traps 16 }
gwSensorStateChange
NOTIFICATION-TYPE
OBJECTS {
deviceName,
sysContact,
sysName,
sysLocation,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
portId,
sensorTypeId,
sensorId,
probeId,
measurementsSensorTimeStamp,
measurementsSensorValue,
measurementsSensorState,
oldSensorState,
deviceSerialNumber
}
STATUS current
DESCRIPTION
"Sensor State Change."
::= { traps 17 }
gwLhxOperationalStateChange
NOTIFICATION-TYPE
OBJECTS {
deviceName,
sysContact,
sysName,
sysLocation,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
portId,
operationalState,
oldOperationalState,
deviceSerialNumber
}
STATUS current
DESCRIPTION
"Operational State Change."
::= { traps 18 }
lhxVoltageLow
NOTIFICATION-TYPE
OBJECTS {
deviceName,
sysContact,
sysName,
sysLocation,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
lhxErrorCode,
portId,
deviceSerialNumber
}
STATUS current
DESCRIPTION
"The supply voltage of an LHX became low."
::= { traps 19 }
lhxBaseElectronicsFailure
NOTIFICATION-TYPE
OBJECTS {
deviceName,
sysContact,
sysName,
sysLocation,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
lhxErrorCode,
portId,
deviceSerialNumber
}
STATUS current
DESCRIPTION
"The base electronics of an LHX controller failed."
::= { traps 20 }
lhxCondenserPumpFailure
NOTIFICATION-TYPE
OBJECTS {
deviceName,
sysContact,
sysName,
sysLocation,
deviceInetAddressType,
deviceInetIPAddress,
lhxErrorCode,
agentInetPortNumber,
portId,
deviceSerialNumber
}
STATUS current
DESCRIPTION
"An LHX condenser pump failed."
::= { traps 21 }
-- the TrapInformation
deviceName
OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The user-defined name for the Device."
::= { trapInformation 1 }
deviceInetAddressType
OBJECT-TYPE
SYNTAX InetAddressType
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The type of address format"
::= { trapInformation 2 }
deviceInetIPAddress
OBJECT-TYPE
SYNTAX InetAddress
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The current IP address. A value of 0.0.0.0 indicates an
error or an unset option."
::= { trapInformation 3 }
lhxErrorCode
OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The LHX error code (F1 - F25, EP)."
::= { trapInformation 4 }
portId OBJECT-TYPE
SYNTAX Integer32(1..256)
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"A unique value for the physical port, the LHX controlller
is connected to.
Its value ranges between 1 and the value of portCount."
::= { trapInformation 5 }
probeId
OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The physical Sensor ID (F1 - F7)."
::= { trapInformation 6 }
fanId OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The Fan ID (M1 - M6)."
::= { trapInformation 7 }
powerSupplyId
OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The Power Supply ID (1, 2)."
::= { trapInformation 8 }
oldSensorState
OBJECT-TYPE
SYNTAX SensorStateEnumeration
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The old sensor state used in Sensor State Transition traps."
::= { trapInformation 9 }
sensorTypeId
OBJECT-TYPE
SYNTAX GwSensorTypeEnumeration
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"A unique value for the type of sensor."
::= { trapInformation 10 }
sensorId
OBJECT-TYPE
SYNTAX Integer32(1..256)
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"A unique value for each sensor. Its value
ranges between 1 and the value of sensorCount."
::= { trapInformation 11 }
oldOperationalState
OBJECT-TYPE
SYNTAX OperationalStateEnumeration
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The old operational state used in Operational State Transition traps."
DEFVAL {0}
::= { trapInformation 12 }
agentInetPortNumber OBJECT-TYPE
SYNTAX InetPortNumber
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The UDP port number used for accessing
the SNMP agent on the device.
Examples:
If the associated device MIB (PX2-MIB, EMD-MIB) has deviceCascadeType set to portForwarding, then
master: 50500
slave 1:50501
slave 2: 50502
......
If cascading mode is not portForwarding and default (Standard) ports are being used, then
port: 161
"
::= { trapInformation 13 }
deviceSerialNumber
OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The serial number of the Device."
::= { trapInformation 14 }
-- the LHX configuration
portCount
OBJECT-TYPE
SYNTAX Integer32(1..255)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of lhx units supported."
::= { configuration 1 }
sensorCountTable
OBJECT-TYPE
SYNTAX SEQUENCE OF SensorCountEntryStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of lhx sensor count extries."
::= { configuration 2 }
sensorCountEntry
OBJECT-TYPE
SYNTAX SensorCountEntryStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing the number of lhx sensors of a certain type."
INDEX { portIdx, sensorTypeIdx }
::= { sensorCountTable 1 }
SensorCountEntryStruct
::= SEQUENCE {
sensorCount Integer32
}
sensorCount
OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of sensors."
::= { sensorCountEntry 1 }
-- lhx centric configuration
lhxConfigurationTable
OBJECT-TYPE
SYNTAX SEQUENCE OF LhxConfigurationEntryStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of lhx controller configuration extries.
The number of entries is given by the value of portCount."
::= { lhx 1 }
lhxConfigurationEntry
OBJECT-TYPE
SYNTAX LhxConfigurationEntryStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing parameters for an lhx."
INDEX { portIdx }
::= { lhxConfigurationTable 1 }
LhxConfigurationEntryStruct
::= SEQUENCE {
operationalState OperationalStateEnumeration,
setpointVentilators Integer32,
setpointWaterValve Integer32,
defaultFanSpeed Integer32,
maximumCoolingState TruthValue,
alertState TruthValue,
model DisplayString,
fwVersion DisplayString
}
operationalState
OBJECT-TYPE
SYNTAX OperationalStateEnumeration
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The operational state of the lhx controller.
To switch LHX power state while controller is connected,
set operationalState to 1 (off) or 2 (on).
Switching power state while LHX is disconnected or to
0 (disconnected) is undefined."
DEFVAL {0}
::= { lhxConfigurationEntry 1 }
setpointVentilators
OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The setpoint of the ventilators."
DEFVAL {0}
::= { lhxConfigurationEntry 2 }
setpointWaterValve
OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The setpoint of the water valve."
DEFVAL {0}
::= { lhxConfigurationEntry 3 }
defaultFanSpeed
OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The 'default' fan speed during normal operation in per mill.
Default is 80% (= 800)."
DEFVAL {0}
::= { lhxConfigurationEntry 4 }
maximumCoolingState
OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Indicates whether maximum cooling was requested or not.
To request maximum cooling, set maximumCoolingState to 1 (true).
Setting maximumCoolingState to 2 (false) is undefined,
set alertState to 2 (false) instead."
DEFVAL {2}
::= { lhxConfigurationEntry 5 }
alertState
OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Indicates whether LHX controler is in alert state or not.
To acknowledge alert status, set alertState to 2 (false).
Setting alertState to 1 (true) is undefined."
DEFVAL {2}
::= { lhxConfigurationEntry 6 }
model
OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The model indentifier of an LHX controller."
::= { lhxConfigurationEntry 7 }
fwVersion
OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The firmware version of an LHX controller."
::= { lhxConfigurationEntry 8 }
-- sensor centric configuration
sensorConfigurationTable
OBJECT-TYPE
SYNTAX SEQUENCE OF SensorConfigurationEntryStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of lhx sensor configuration extries.
The number of entries is given by the value of portCount."
::= { gwSensors 1 }
sensorConfigurationEntry
OBJECT-TYPE
SYNTAX SensorConfigurationEntryStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing parameters for an lhx."
INDEX { portIdx, sensorTypeIdx, sensorIdx }
::= { sensorConfigurationTable 1 }
SensorConfigurationEntryStruct
::= SEQUENCE {
portIdx Integer32,
sensorTypeIdx Integer32,
sensorIdx Integer32,
sensorLabel DisplayString,
sensorUnit SensorUnitsEnumeration,
sensorDecimalDigits Unsigned32,
sensorMaximum Integer32,
sensorMinimum Integer32,
sensorHysteresis Unsigned32,
sensorLowerCriticalThreshold Integer32,
sensorLowerWarningThreshold Integer32,
sensorUpperCriticalThreshold Integer32,
sensorUpperWarningThreshold Integer32,
sensorEnabledThresholds BITS,
sensorThresholdMaximum Integer32,
sensorThresholdMinimum Integer32,
sensorName DisplayString
}
portIdx
OBJECT-TYPE
SYNTAX Integer32(1..256)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A unique value for each port. Its value
ranges between 1 and the value of portCount."
::= { sensorConfigurationEntry 1 }
sensorTypeIdx
OBJECT-TYPE
SYNTAX Integer32(0..255)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A unique value for the type of sensor."
::= { sensorConfigurationEntry 2 }
sensorIdx
OBJECT-TYPE
SYNTAX Integer32(1..256)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A unique value for each sensor. Its value
ranges between 1 and the value of sensorCount."
::= { sensorConfigurationEntry 3 }
sensorLabel
OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The short ID of the sensor (e.g. F1, M2)."
::= { sensorConfigurationEntry 4 }
sensorUnit
OBJECT-TYPE
SYNTAX SensorUnitsEnumeration
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The base units.
This parameter does not apply to state sensors."
::= { sensorConfigurationEntry 5 }
sensorDecimalDigits
OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of digits displayed to the right of the decimal point.
This parameter does not apply to state sensors."
::= { sensorConfigurationEntry 6 }
sensorMaximum
OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The largest possible value.
The value of this OID variable should be scaled by
sensorDecimalDigits. For example, if the value is 1 and
sensorDecimalDigits is 2, then actual value is 0.01.
This parameter does not apply to state sensors."
::= { sensorConfigurationEntry 7 }
sensorMinimum
OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The smallest possible value.
The value of this OID variable should be scaled by
sensorDecimalDigits. For example, if the value is 1 and
sensorDecimalDigits is 2, then actual value is 0.01.
This parameter does not apply to state sensors."
::= { sensorConfigurationEntry 8 }
sensorHysteresis
OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The hysteresis used for deassertions.
The value of this OID variable should be scaled by
sensorDecimalDigits. For example, if the value is 1 and
sensorDecimalDigits is 2, then actual value is 0.01.
This parameter does not apply to state sensors."
::= { sensorConfigurationEntry 9 }
sensorLowerCriticalThreshold
OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The lower critical threshold.
The value of this OID variable should be scaled by
sensorDecimalDigits. For example, if the value is 1 and
sensorDecimalDigits is 2, then actual value is 0.01.
This parameter does not apply to state sensors."
::= { sensorConfigurationEntry 10 }
sensorLowerWarningThreshold
OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The lower non-critical (warning) threshold.
The value of this OID variable should be scaled by
sensorDecimalDigits. For example, if the value is 1 and
sensorDecimalDigits is 2, then actual value is 0.01.
This parameter does not apply to state sensors."
::= { sensorConfigurationEntry 11 }
sensorUpperCriticalThreshold
OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The upper critical threshold.
The value of this OID variable should be scaled by
sensorDecimalDigits. For example, if the value is 1 and
sensorDecimalDigits is 2, then actual value is 0.01.
This parameter does not apply to state sensors."
::= { sensorConfigurationEntry 12 }
sensorUpperWarningThreshold
OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The upper non-critical (warning) threshold.
The value of this OID variable should be scaled by
sensorDecimalDigits. For example, if the value is 1 and
sensorDecimalDigits is 2, then actual value is 0.01.
This parameter does not apply to state sensors."
::= { sensorConfigurationEntry 13 }
sensorEnabledThresholds
OBJECT-TYPE
SYNTAX BITS {
lowerCritical(0),
lowerWarning(1),
upperWarning(2),
upperCritical(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A bit string which indicates which thresholds are enabled.
This parameter does not apply to state sensors."
::= { sensorConfigurationEntry 14 }
sensorThresholdMaximum
OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The largest possible threshold value.
The value of this OID variable should be scaled by
sensorDecimalDigits. For example, if the value is 1 and
sensorDecimalDigits is 2, then actual value is 0.01.
This parameter does not apply to state sensors."
::= { sensorConfigurationEntry 15 }
sensorThresholdMinimum
OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The smallest possible threshold value.
The value of this OID variable should be scaled by
sensorDecimalDigits. For example, if the value is 1 and
sensorDecimalDigits is 2, then actual value is 0.01.
This parameter does not apply to state sensors."
::= { sensorConfigurationEntry 16 }
sensorName
OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The descriptive ID of the sensor (e.g. Fan Speed 1)."
::= { sensorConfigurationEntry 17 }
-- the Sensor Measurements table
sensorMeasurementsTable
OBJECT-TYPE
SYNTAX SEQUENCE OF SensorMeasurementsEntryStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of external sensor entries. The number of
entries is given by the value of sensorCount
for the LHX."
::= { measurements 1 }
sensorMeasurementsEntry
OBJECT-TYPE
SYNTAX SensorMeasurementsEntryStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing measurement objects for an external sensor."
INDEX { portIdx, sensorTypeIdx, sensorIdx }
::= { sensorMeasurementsTable 1 }
SensorMeasurementsEntryStruct
::= SEQUENCE {
measurementsSensorIsAvailable TruthValue,
measurementsSensorState SensorStateEnumeration,
measurementsSensorValue Integer32,
measurementsSensorTimeStamp Unsigned32
}
measurementsSensorIsAvailable
OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Is the sensor available?"
::= { sensorMeasurementsEntry 1 }
measurementsSensorState
OBJECT-TYPE
SYNTAX SensorStateEnumeration
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The sensor state."
::= { sensorMeasurementsEntry 2 }
measurementsSensorValue
OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The sensor reading.
This parameter does not apply to state sensors."
::= { sensorMeasurementsEntry 3 }
measurementsSensorTimeStamp
OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The sensor reading timestamp."
::= { sensorMeasurementsEntry 4 }
-- Conformance Information
-- compliance statements
complianceRev1
MODULE-COMPLIANCE
STATUS current
DESCRIPTION
"The requirements for conformance to the LHX-MIB."
MODULE -- this module
GROUP configurationGroup
DESCRIPTION
"The configuration group."
GROUP measurementsGroup
DESCRIPTION
"The measurements group."
GROUP trapInformationGroup
DESCRIPTION
"The information group."
GROUP trapsGroup
DESCRIPTION
"The traps group."
::= { compliances 1 }
-- units of conformance
configurationGroup
OBJECT-GROUP
OBJECTS {
portCount,
portId,
operationalState,
sensorCount,
sensorLabel,
sensorUnit,
sensorDecimalDigits,
sensorMaximum,
sensorMinimum,
sensorHysteresis,
sensorLowerCriticalThreshold,
sensorLowerWarningThreshold,
sensorUpperCriticalThreshold,
sensorUpperWarningThreshold,
sensorEnabledThresholds,
setpointVentilators,
setpointWaterValve,
defaultFanSpeed,
maximumCoolingState,
alertState,
sensorThresholdMaximum,
sensorThresholdMinimum,
model,
fwVersion,
sensorName
}
STATUS current
DESCRIPTION
"A collection of objects representing configuration data."
::= { groups 1 }
measurementsGroup
OBJECT-GROUP
OBJECTS {
measurementsSensorIsAvailable,
measurementsSensorState,
measurementsSensorValue,
measurementsSensorTimeStamp
}
STATUS current
DESCRIPTION
"A collection of objects providing the measurement
capability of LHX."
::= { groups 2 }
trapInformationGroup
OBJECT-GROUP
OBJECTS {
deviceName,
deviceInetAddressType,
deviceInetIPAddress,
lhxErrorCode,
portId,
probeId,
fanId,
powerSupplyId,
oldSensorState,
sensorTypeId,
sensorId,
oldOperationalState,
agentInetPortNumber,
deviceSerialNumber
}
STATUS current
DESCRIPTION
"A collection of objects providing
information in the traps."
::= { groups 3 }
trapsGroup
NOTIFICATION-GROUP
NOTIFICATIONS {
lhxSensorFailure,
lhxFanFailure,
lhxPowerSupplyFailure,
lhxThresholdAirOutlet,
lhxThresholdAirInlet,
lhxThresholdWaterInlet,
lhxDoorOpened,
lhxMaximumCoolingRequest,
lhxEmergencyCooling,
lhxWaterLeak,
lhxThresholdHumidity,
lhxExternalWaterCoolingFailure,
lhxThresholdWaterOutlet,
lhxParameterDataLoss,
lhxStBusError,
lhxCondenserPumpFailure,
gwSensorStateChange,
gwLhxOperationalStateChange,
lhxCollectiveFault,
lhxVoltageLow,
lhxBaseElectronicsFailure
}
STATUS current
DESCRIPTION
"A collection of traps."
::= { groups 4 }
END