EMD-MIB DEFINITIONS ::= BEGIN
IMPORTS
MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE,
enterprises, Integer32, Unsigned32 FROM SNMPv2-SMI
MODULE-COMPLIANCE, OBJECT-GROUP, NOTIFICATION-GROUP FROM SNMPv2-CONF
TEXTUAL-CONVENTION, DisplayString, MacAddress, TruthValue FROM SNMPv2-TC
InetAddressType, InetAddress, InetPortNumber FROM INET-ADDRESS-MIB
sysContact, sysName, sysLocation FROM RFC1213-MIB;
raritan MODULE-IDENTITY
LAST-UPDATED "201510260000Z" -- October 26, 2015
ORGANIZATION "Raritan"
CONTACT-INFO "
Author: Raritan Americas, Inc.
postal: Raritan Americas, Inc.
400 Cottontail Lane
Somerset, NJ 08873
email: tech@raritan.com
phone: +1 732 764 8886
"
DESCRIPTION "This MIB describes the SNMP functions of the
EMX Environmental Monitoring Device by Raritan Computer."
REVISION "201510260000Z" -- October 26, 2015
DESCRIPTION "EMX release 3.2.10:
1) SensorUnitsEnumeration: Added
degrees(20)
voltampReactive(23)
2) Added to trapInformation:
phoneNumber
Added the following traps:
smsMessageTransmissionFailure trap
"
REVISION "201409290000Z" -- September 29, 2014
DESCRIPTION "EMX release 3.1.0:
- Allow configuration of default thresholds
for peripheral devices
1) Added externalSensorTypeDefaultThresholdsTable
2) Added:
externalSensorUseDefaultThresholds
3) Added agentInetPortNumber under trapInformation
4) Added agentInetPortNumber as a varbind to all traps
5) SensorTypeEnumeration: Added
absoluteHumidity(28)
"
REVISION "201402210000Z" -- February 21, 2014
DESCRIPTION "EMX release 2.6.0:
- Send trap on peripheral device firmware update
- Allow peripheral device auto management to be disabled
- Support DX-PIR occupancy sensor
1) Added traps: radiusError, serverReachabilityError
2) Added unknownPeripheralDeviceAttached trap
3) Added:
PeripheralDeviceFirmwareUpdateStateEnumeration
peripheralDeviceFirmwareUpdateState
peripheralDeviceFirmwareUpdate trap
4) Added:
peripheralDevicesAutoManagement
5) Added userName to the following traps:
bulkConfigurationSaved
bulkConfigurationCopied
deviceSettingsSaved
deviceSettingsRestored
lhxSupportChanged
6) Added:
externalSensorAlarmedToNormalDelay
7) SensorUnitsEnumeration: Added
grampercubicmeter(22)
"
REVISION "201312170000Z" -- December 17, 2013
DESCRIPTION "EMX release 2.5.0:
- Support for G2 peripheral devices
- Support Webcams
1) Added externalSensorIsActuator to the externalSensorConfigurationTable
2) Added actuatorControlTable
3) Added required sensor types and units
4) Added traps: webcamInserted and webcamRemoved
5) Added trapInformation parameters: webcamModel, webcamConnectionPort
6) Added serverConnectivityUnrecoverable trap
7) Added peripheralDevicePackageTable containing information on peripheral
device packages
"
REVISION "201210010000Z" -- October 1, 2012
DESCRIPTION "Added the following traps:
deviceSettingsSaved, deviceSettingsRestored
"
REVISION "201207110000Z" -- July 11, 2012
DESCRIPTION "Added a comment before the section listing the traps.
The comment notes that the deviceInetAddressType and
deviceInetIPAddress fields are not used for IPv6 traps
"
REVISION "201205250000Z" -- May 25, 2012
DESCRIPTION "added userAccepted/DeclinedRestrictedServiceAgreement traps"
REVISION "201201250000Z" -- January 25, 2012
DESCRIPTION "added lhxSupportChanged trap."
REVISION "201112140000Z" -- December 14, 2011
DESCRIPTION "
1. Added usbSlaveConnected, usbSlaveDisconnected traps
"
REVISION "201112120000Z" -- December 12, 2011
DESCRIPTION "
1. Added cascadedDeviceConnected to unitConfiguration
"
REVISION "201111040000Z" -- November 4, 2011
DESCRIPTION "
1. Added DeviceIdentificationParameterEnumeration
2. Added deviceIdentificationChanged Trap
3. Added sysContact, sysName, sysLocation to all traps
"
REVISION "201108260000Z" -- August 26, 2011
DESCRIPTION "Added model name."
REVISION "201108050000Z" -- August 8, 2011
DESCRIPTION "Added external sensor port number."
REVISION "201106300000Z" -- June 30, 2011
DESCRIPTION "Added sensor log."
REVISION "201103300000Z" -- March 30, 2011
DESCRIPTION "Changed MAX-ACCESS for externalOnOffSensorSubtype to read-write."
REVISION "201103100000Z" -- March 10, 2011
DESCRIPTION "Remove unused deviceNumber from ExternalSensorStateChangeTrap."
REVISION "201102140000Z" -- February 14, 2011
DESCRIPTION "The first version of the MIB."
::= { enterprises 13742 }
emd OBJECT IDENTIFIER ::= { raritan 8 }
traps OBJECT IDENTIFIER ::= { emd 0 }
trapInformation OBJECT IDENTIFIER ::= { traps 0 }
configuration OBJECT IDENTIFIER ::= { emd 1 }
measurements OBJECT IDENTIFIER ::= { emd 2 }
conformance OBJECT IDENTIFIER ::= { emd 3 }
log OBJECT IDENTIFIER ::= { emd 4 }
control OBJECT IDENTIFIER ::= { emd 5 }
unit OBJECT IDENTIFIER ::= { configuration 1 }
externalSensors OBJECT IDENTIFIER ::= { configuration 2 }
serverReachability OBJECT IDENTIFIER ::= { configuration 3 }
measurementsExternalSensor OBJECT IDENTIFIER ::= { measurements 1 }
compliances OBJECT IDENTIFIER ::= { conformance 1 }
groups OBJECT IDENTIFIER ::= { conformance 2 }
logUnit OBJECT IDENTIFIER ::= { log 1 }
logExternalSensor OBJECT IDENTIFIER ::= { log 2 }
actuatorControl OBJECT IDENTIFIER ::= { control 1 }
-- Conformance Information
-- compliance statements
complianceRev1 MODULE-COMPLIANCE
STATUS current
DESCRIPTION
"The requirements for conformance to the EMD-MIB."
MODULE -- this module
GROUP configGroup
DESCRIPTION
"The configuration group."
GROUP measurementsGroup
DESCRIPTION
"The measurements group."
GROUP trapInformationGroup
DESCRIPTION
"The information group."
GROUP trapsGroup
DESCRIPTION
"The information group."
GROUP logGroup
DESCRIPTION
"The log group."
GROUP controlGroup
DESCRIPTION
"The control group."
::= { compliances 1 }
-- units of conformance
configGroup OBJECT-GROUP
OBJECTS {
externalSensorCount,
deviceInetAddressType,
deviceInetIPAddress,
deviceInetNetmask,
deviceInetGateway,
deviceMACAddress,
utcOffset,
model,
deviceName,
hardwareVersion,
firmwareVersion,
externalSensorType,
externalSensorSerialNumber,
externalSensorName,
externalSensorDescription,
externalSensorXCoordinate,
externalSensorYCoordinate,
externalSensorZCoordinate,
externalSensorChannelNumber,
externalOnOffSensorSubtype,
externalSensorUnits,
externalSensorDecimalDigits,
externalSensorAccuracy,
externalSensorResolution,
externalSensorTolerance,
externalSensorMaximum,
externalSensorMinimum,
externalSensorHysteresis,
externalSensorStateChangeDelay,
externalSensorLowerCriticalThreshold,
externalSensorLowerWarningThreshold,
externalSensorUpperCriticalThreshold,
externalSensorUpperWarningThreshold,
externalSensorEnabledThresholds,
externalSensorPort,
externalSensorsZCoordinateUnits,
externalSensorIsActuator,
externalSensorUseDefaultThresholds,
externalSensorTypeDefaultHysteresis,
externalSensorTypeDefaultStateChangeDelay,
externalSensorTypeDefaultLowerCriticalThreshold,
externalSensorTypeDefaultLowerWarningThreshold,
externalSensorTypeDefaultUpperCriticalThreshold,
externalSensorTypeDefaultUpperWarningThreshold,
externalSensorTypeDefaultEnabledThresholds,
managedExternalSensorCount,
serverCount,
serverIPAddress,
serverPingEnabled,
measurementPeriod,
measurementsPerLogEntry,
logSize,
cascadedDeviceConnected,
peripheralDevicePackageSerialNumber,
peripheralDevicePackageModel,
peripheralDevicePackageFirmwareVersion,
peripheralDevicePackageMinFirmwareVersion,
peripheralDevicePackageFirmwareTimeStamp,
peripheralDevicePackagePosition,
peripheralDevicePackageState,
peripheralDevicesAutoManagement,
externalSensorAlarmedToNormalDelay,
synchronizeWithNTPServer,
useDHCPProvidedNTPServer,
firstNTPServerAddressType,
firstNTPServerAddress,
secondNTPServerAddressType,
secondNTPServerAddress
}
STATUS current
DESCRIPTION
"A collection of objects representing configuration data."
::= { groups 1 }
measurementsGroup OBJECT-GROUP
OBJECTS {
measurementsExternalSensorIsAvailable,
measurementsExternalSensorState,
measurementsExternalSensorValue,
measurementsExternalSensorTimeStamp
}
STATUS current
DESCRIPTION
"A collection of objects providing the measurement
capability of EMD."
::= { groups 2 }
trapInformationGroup OBJECT-GROUP
OBJECTS {
userName,
targetUser,
imageVersion,
roleName,
oldSensorState,
externalSensorNumber,
typeOfSensor,
smtpMessageRecipients,
smtpServer,
errorDescription,
deviceChangedParameter,
changedParameterNewValue,
lhxSupportEnabled,
webcamModel,
webcamConnectionPort,
peripheralDeviceRomcode,
peripheralDeviceFirmwareUpdateState,
agentInetPortNumber,
phoneNumber
}
STATUS current
DESCRIPTION
"A collection of objects providing
information in the traps."
::= { groups 3 }
trapsGroup NOTIFICATION-GROUP
NOTIFICATIONS {
systemStarted,
systemReset,
userLogin,
userLogout,
userAuthenticationFailure,
userSessionTimeout,
userAdded,
userModified,
userDeleted,
roleAdded,
roleModified,
roleDeleted,
deviceUpdateStarted,
deviceUpdateCompleted,
userBlocked,
userPasswordChanged,
passwordSettingsChanged,
firmwareValidationFailed,
logFileCleared,
bulkConfigurationSaved,
bulkConfigurationCopied,
externalSensorStateChange,
smtpMessageTransmissionFailure,
ldapError,
deviceUpdateFailed,
pingServerEnabled,
pingServerDisabled,
serverNotReachable,
serverReachable,
deviceIdentificationChanged,
usbSlaveConnected,
usbSlaveDisconnected,
lhxSupportChanged,
userAcceptedRestrictedServiceAgreement,
userDeclinedRestrictedServiceAgreement,
deviceSettingsSaved,
deviceSettingsRestored,
webcamInserted,
webcamRemoved,
serverConnectivityUnrecoverable,
radiusError,
serverReachabilityError,
unknownPeripheralDeviceAttached,
peripheralDeviceFirmwareUpdate,
smsMessageTransmissionFailure
}
STATUS current
DESCRIPTION
"A collection of traps."
::= { groups 4 }
logGroup OBJECT-GROUP
OBJECTS {
dataLogging,
oldestLogID,
newestLogID,
logTimeStamp,
dataLoggingEnableForAllSensors,
logExternalSensorDataAvailable,
logExternalSensorState,
logExternalSensorAvgValue,
logExternalSensorMaxValue,
logExternalSensorMinValue
}
STATUS current
DESCRIPTION
"A collection of objects providing the logging capabilities
about the EMD."
::= { groups 5 }
controlGroup OBJECT-GROUP
OBJECTS {
actuatorState
}
STATUS current
DESCRIPTION
"A collection of objects providing the ability to control
actuators of the EMD."
::= { groups 6 }
-- Textual Conventions
SensorTypeEnumeration ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"The types a sensor can be."
SYNTAX INTEGER {
rmsCurrent(1),
peakCurrent(2),
unbalancedCurrent(3),
rmsVoltage(4),
activePower(5),
apparentPower(6),
powerFactor(7),
activeEnergy(8),
apparentEnergy(9),
temperature(10),
humidity(11),
airFlow(12),
airPressure(13),
onOff(14),
trip(15),
vibration(16),
waterDetection(17),
smokeDetection(18),
binary(19),
contact(20),
fanSpeed(21),
absoluteHumidity(28),
other(30),
none(31),
illuminance(42),
doorContact(43),
tamperDetection(44),
motionDetection(45)
}
SensorStateEnumeration ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"The states a sensor can be in."
SYNTAX INTEGER {
unavailable(-1),
open(0),
closed(1),
belowLowerCritical(2),
belowLowerWarning(3),
normal(4),
aboveUpperWarning(5),
aboveUpperCritical(6),
on(7),
off(8),
detected(9),
notDetected(10),
alarmed(11)
}
SensorUnitsEnumeration ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"The types a sensor can be."
SYNTAX INTEGER {
none(-1),
other(0),
volt(1),
amp(2),
watt(3),
voltamp(4),
wattHour(5),
voltampHour(6),
degreeC(7),
hertz(8),
percent(9),
meterpersec(10),
pascal(11),
psi(12),
g(13),
degreeF(14),
feet(15),
inches(16),
cm(17),
meters(18),
rpm(19),
degrees(20),
lux(21),
grampercubicmeter(22),
voltampReactive(23)
}
ExternalSensorsZCoordinateUnitsEnumeration ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"The units of the external Sensor Z Coordinate.
rackUnits implies that the Z Coordinate for all
external sensors is in rack Units (U)
text implies that the Z Coordinate for all
external sensors is a text string (label)"
SYNTAX INTEGER {
rackUnits(0),
text(1)
}
HundredthsOfAPercentage ::= TEXTUAL-CONVENTION
DISPLAY-HINT "d"
STATUS current
DESCRIPTION
"Data type for reporting values in hundredths of
percentage, i.e. 0.01 %."
SYNTAX Unsigned32 (0..10000)
DeviceIdentificationParameterEnumeration ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"The configurable parameters."
SYNTAX INTEGER { deviceName(0),
sysContact(1),
sysName(2),
sysLocation(3)
}
PeripheralDeviceFirmwareUpdateStateEnumeration ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"The state of an peripheral device firmware update."
SYNTAX INTEGER { started(1),
successful(2),
failed(3)
}
-- the Unit group
-- The UnitConfiguration contains information on the EMD's configuration.
unitConfiguration OBJECT IDENTIFIER ::= { unit 1 }
deviceName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The user-defined name for the EMD."
::= { unitConfiguration 1 }
hardwareVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The main boards hardware version."
::= { unitConfiguration 2 }
firmwareVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The firmware version."
::= { unitConfiguration 3 }
utcOffset OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current UTC offset."
::= { unitConfiguration 4 }
externalSensorCount OBJECT-TYPE
SYNTAX Integer32(0..255)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of external sensors."
::= { unitConfiguration 5 }
managedExternalSensorCount OBJECT-TYPE
SYNTAX Integer32(0..255)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of managed external sensors "
::= { unitConfiguration 6 }
externalSensorsZCoordinateUnits OBJECT-TYPE
SYNTAX ExternalSensorsZCoordinateUnitsEnumeration
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"External Sensor Z Coordinate units:
Freeform Text or Rack Units (U).
Default is U."
::= { unitConfiguration 7 }
deviceMACAddress OBJECT-TYPE
SYNTAX MacAddress
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current MAC address."
::= { unitConfiguration 8 }
deviceInetAddressType OBJECT-TYPE
SYNTAX InetAddressType
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The type of address format"
::= { unitConfiguration 9 }
deviceInetIPAddress OBJECT-TYPE
SYNTAX InetAddress
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current IP address. A value of 0.0.0.0
indicates an error or an unset option."
::= { unitConfiguration 10 }
deviceInetNetmask OBJECT-TYPE
SYNTAX InetAddress
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current netmask. A value of 0.0.0.0 indicates
an error or an unset option."
::= { unitConfiguration 11 }
deviceInetGateway OBJECT-TYPE
SYNTAX InetAddress
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current gateway. A value of 0.0.0.0 indicates
an error or an unset option."
::= { unitConfiguration 12 }
serverCount OBJECT-TYPE
SYNTAX Integer32(0..255)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of entries in serverReachabilityTable"
::= { unitConfiguration 13 }
model OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The EMD device model."
::= { unitConfiguration 14 }
cascadedDeviceConnected OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether a device is connected using an USB cable to
the USB-A port of this EMX in a cascaded configuration.
true: Connected
false: Not Connected"
::= { unitConfiguration 15 }
peripheralDevicesAutoManagement OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set enabled state of auto management for new peripheral devices."
::= { unitConfiguration 16}
synchronizeWithNTPServer OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set enabled state of the device's NTP client."
::= { unitConfiguration 17 }
useDHCPProvidedNTPServer OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enable usage of the DHCP/BOOTP provided NTP server addresses;
the value is used only if synchronizeWithNTPServer is enabled."
::= { unitConfiguration 18 }
firstNTPServerAddressType OBJECT-TYPE
SYNTAX InetAddressType
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Represents the type of firstNTPServerAddress."
DEFVAL { ipv4 }
::= { unitConfiguration 19 }
firstNTPServerAddress OBJECT-TYPE
SYNTAX InetAddress
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The address of the primary NTP server."
::= { unitConfiguration 20 }
secondNTPServerAddressType OBJECT-TYPE
SYNTAX InetAddressType
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Represents the type of secondNTPServerAddress."
DEFVAL { ipv4 }
::= { unitConfiguration 21 }
secondNTPServerAddress OBJECT-TYPE
SYNTAX InetAddress
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The address of the secondary NTP server."
::= { unitConfiguration 22 }
-- The LogConfiguration table contains information on the logs in the EMD.
logConfiguration OBJECT IDENTIFIER ::= { unit 2 }
dataLogging OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Data Retrieval: enabled/disabled."
::= { logConfiguration 1 }
measurementPeriod OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Data Collection periodicity. This is the periodicity of the data collected by the PX.
This value is fixed at 1 second."
::= { logConfiguration 2 }
measurementsPerLogEntry OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The number of measurements used for each entry in the log."
::= { logConfiguration 3 }
logSize OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of entries in the log."
::= { logConfiguration 4 }
dataLoggingEnableForAllSensors OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Operation to control data logging for all sensors.
If this OID is set to true, then all xxxSensorLogAvailable are set to true
If this OID is set to false, then all xxxSensorLogAvailable are set to false
"
::= { logConfiguration 5 }
-- the externalSensorConfiguration table
-- The externalSensorConfiguration table contains information
-- on the EMD's external Sensors.
externalSensorConfigurationTable OBJECT-TYPE
SYNTAX SEQUENCE OF ExternalSensorConfigurationEntryStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of externalSensor configuration entries. The number of
entries is given by the value of externalSensorCount for the EMD."
::= { externalSensors 1 }
externalSensorConfigurationEntry OBJECT-TYPE
SYNTAX ExternalSensorConfigurationEntryStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing parameters for an external sensor."
INDEX { sensorID }
::= { externalSensorConfigurationTable 1 }
ExternalSensorConfigurationEntryStruct ::= SEQUENCE {
sensorID Integer32,
externalSensorType SensorTypeEnumeration,
externalSensorSerialNumber DisplayString,
externalSensorName DisplayString,
externalSensorDescription DisplayString,
externalSensorXCoordinate DisplayString,
externalSensorYCoordinate DisplayString,
externalSensorZCoordinate DisplayString,
externalSensorChannelNumber Integer32,
externalOnOffSensorSubtype SensorTypeEnumeration,
externalSensorUnits SensorUnitsEnumeration,
externalSensorDecimalDigits Unsigned32,
externalSensorAccuracy HundredthsOfAPercentage,
externalSensorResolution Unsigned32,
externalSensorTolerance Unsigned32,
externalSensorMaximum Integer32,
externalSensorMinimum Integer32,
externalSensorHysteresis Unsigned32,
externalSensorStateChangeDelay Unsigned32,
externalSensorLowerCriticalThreshold Integer32,
externalSensorLowerWarningThreshold Integer32,
externalSensorUpperCriticalThreshold Integer32,
externalSensorUpperWarningThreshold Integer32,
externalSensorEnabledThresholds BITS,
externalSensorPort DisplayString,
externalSensorIsActuator TruthValue,
externalSensorAlarmedToNormalDelay Integer32,
externalSensorUseDefaultThresholds TruthValue
}
sensorID OBJECT-TYPE
SYNTAX Integer32(1..256)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A unique value for each sensor. Its value
ranges between 1 and the value of externalSensorCount."
::= { externalSensorConfigurationEntry 1 }
externalSensorType OBJECT-TYPE
SYNTAX SensorTypeEnumeration
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The type of sensor."
::= { externalSensorConfigurationEntry 2 }
externalSensorSerialNumber OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The sensor serial number."
::= { externalSensorConfigurationEntry 3 }
externalSensorName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The user-defined name."
::= { externalSensorConfigurationEntry 4 }
externalSensorDescription OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The user-defined description."
::= { externalSensorConfigurationEntry 5 }
externalSensorXCoordinate OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The X coordinate."
::= { externalSensorConfigurationEntry 6 }
externalSensorYCoordinate OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The Y coordinate."
::= { externalSensorConfigurationEntry 7 }
externalSensorZCoordinate OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The Z coordinate."
::= { externalSensorConfigurationEntry 8 }
externalSensorChannelNumber OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The channel number, applies only to contact sensors;
-1 for other sensors"
::= { externalSensorConfigurationEntry 9 }
externalOnOffSensorSubtype OBJECT-TYPE
SYNTAX SensorTypeEnumeration
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Type of measurement in case sensor type is discrete OnOff"
::= { externalSensorConfigurationEntry 10 }
externalSensorUnits OBJECT-TYPE
SYNTAX SensorUnitsEnumeration
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The base units.
This parameter does not apply to onOff, trip, vibration,
waterDetection, smokeDetection sensors.
"
::= { externalSensorConfigurationEntry 11 }
externalSensorDecimalDigits OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of digits displayed to the right of the decimal point
This parameter does not apply
to onOff, trip, vibration, waterDetection,
smokeDetection sensors."
::= { externalSensorConfigurationEntry 12 }
externalSensorAccuracy OBJECT-TYPE
SYNTAX HundredthsOfAPercentage
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The accuracy: how close (in percent) the measurement
is to the actual value.
This parameter does not apply
to onOff, trip, vibration, waterDetection,
smokeDetection sensors."
::= { externalSensorConfigurationEntry 13 }
externalSensorResolution OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The resolution: the minimum difference between any two measured
values. The value of this OID variable should be scaled by
externalSensorDecimalDigits. For example, if the value is 1 and
externalSensorDecimalDigits is 2, then actual value is 0.01.
This parameter does not apply
to onOff, trip, vibration, waterDetection,
smokeDetection sensors."
::= { externalSensorConfigurationEntry 14 }
externalSensorTolerance OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The resolution: the difference between a sensor value and the
actual value. The value of this OID variable should be scaled by
(externalSensorDecimalDigits + 1).
For example, if the value is 50 and
externalSensorDecimalDigits is 2, then actual value is 0.05.
This parameter does not apply
to onOff, trip, vibration, waterDetection,
smokeDetection sensors."
::= { externalSensorConfigurationEntry 15 }
externalSensorMaximum OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The largest possible value
The value of this OID variable should be scaled by
externalSensorDecimalDigits. For example, if the value is 1 and
externalSensorDecimalDigits is 2, then actual value is 0.01.
This parameter does not apply
to onOff, trip, vibration, waterDetection,
smokeDetection sensors."
::= { externalSensorConfigurationEntry 16 }
externalSensorMinimum OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The smallest possible value
The value of this OID variable should be scaled by
externalSensorDecimalDigits. For example, if the value is 1 and
externalSensorDecimalDigits is 2, then actual value is 0.01.
This parameter does not apply
to onOff, trip, vibration, waterDetection,
smokeDetection sensors."
::= { externalSensorConfigurationEntry 17 }
externalSensorHysteresis OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The hysteresis used for deassertions
The value of this OID variable should be scaled by
externalSensorDecimalDigits. For example, if the value is 1 and
externalSensorDecimalDigits is 2, then actual value is 0.01.
This parameter does not apply
to onOff, trip, vibration, waterDetection,
smokeDetection sensors."
::= { externalSensorConfigurationEntry 18 }
externalSensorStateChangeDelay OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The delay measured in samples before a state is asserted.
If the value is zero, then the state is asserted as soon as
it is detected; if it is non-zero, say n, then the assertion
condition must exist for n+1 consecutive samples before the
corresponding assertion event is reported.
At present, this value cannot be written (set)"
::= { externalSensorConfigurationEntry 19 }
externalSensorLowerCriticalThreshold OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The lower critical threshold
The value of this OID variable should be scaled by
externalSensorDecimalDigits. For example, if the value is 1 and
externalSensorDecimalDigits is 2, then actual value is 0.01.
This parameter does not apply
to onOff, trip, vibration, waterDetection,
smokeDetection sensors."
::= { externalSensorConfigurationEntry 20 }
externalSensorLowerWarningThreshold OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The lower non-critical (warning) threshold
The value of this OID variable should be scaled by
externalSensorDecimalDigits. For example, if the value is 1 and
externalSensorDecimalDigits is 2, then actual value is 0.01.
This parameter does not apply
to onOff, trip, vibration, waterDetection,
smokeDetection sensors."
::= { externalSensorConfigurationEntry 21 }
externalSensorUpperCriticalThreshold OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The upper critical threshold
The value of this OID variable should be scaled by
externalSensorDecimalDigits. For example, if the value is 1 and
externalSensorDecimalDigits is 2, then actual value is 0.01.
This parameter does not apply
to onOff, trip, vibration, waterDetection,
smokeDetection sensors."
::= { externalSensorConfigurationEntry 22 }
externalSensorUpperWarningThreshold OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The upper non-critical (warning) threshold
The value of this OID variable should be scaled by
externalSensorDecimalDigits. For example, if the value is 1 and
externalSensorDecimalDigits is 2, then actual value is 0.01.
This parameter does not apply
to onOff, trip, vibration, waterDetection,
smokeDetection sensors."
::= { externalSensorConfigurationEntry 23 }
externalSensorEnabledThresholds OBJECT-TYPE
SYNTAX BITS {
lowerCritical(0),
lowerWarning(1),
upperWarning(2),
upperCritical(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A bit string which indicates which thresholds are enabled.
This parameter does not apply
to onOff, trip, vibration, waterDetection,
smokeDetection sensors"
::= { externalSensorConfigurationEntry 24 }
externalSensorPort OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The position of the sensor.
The format is a semicolon separated list of Keyword:value pairs -
Keyword1:Value1;Keyword2:value2;...
Keyword can be one of the following:
ONBOARD, DEVICE-1WIREPORT, HUBPORT, CHAIN-POSITION
Examples
1) Onboard Sensor
ONBOARD:CC1
2) Old sensor connected to device 1-wire port
DEVICE-1WIREPORT:2
3) New style sensor connected to device 1-wire port
DEVICE-1WIREPORT:2;CHAIN-POSITION:3
4) New style sensor connected to hub port 3
DEVICE-1WIREPORT:2;CHAIN-POSITION:1;HUBPORT:3;CHAIN-POSITION:1
5) Old style sensor connected to end of new style sensor chain
DEVICE-1WIREPORT:2;
"
::= { externalSensorConfigurationEntry 25 }
externalSensorIsActuator OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Is this an actuator?
True: It is an actuator
False: It is not an actuator"
::= { externalSensorConfigurationEntry 26 }
externalSensorAlarmedToNormalDelay OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The delay in seconds for transitions from the alarmed state to the normal state.
If the sensor type is motionDetection,
then it can set to a value greater >= 0
For all other sensor types,
the value is 0 and cannot be set to any other value.
"
::= { externalSensorConfigurationEntry 27 }
externalSensorUseDefaultThresholds OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Use default thresholds for this sensor?
True: Use default thresholds for this sensor
False: Do not use default thresholds for this sensor"
::= { externalSensorConfigurationEntry 28 }
-- The ExternalSensorTypeDefaultThresholdsTable contains information about default thresholds for G1 sensor types.
-- It is used for bulk configuration of G1 external sensors.
externalSensorTypeDefaultThresholdsTable OBJECT-TYPE
SYNTAX SEQUENCE OF ExternalSensorTypeDefaultThresholdsEntryStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of entries listing the default thresholds for each sensor type."
::= { externalSensors 4 }
externalSensorTypeDefaultThresholdsEntry OBJECT-TYPE
SYNTAX ExternalSensorTypeDefaultThresholdsEntryStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing default thresholds for a sensor type."
INDEX { externalSensorType }
::= { externalSensorTypeDefaultThresholdsTable 1 }
ExternalSensorTypeDefaultThresholdsEntryStruct ::= SEQUENCE {
externalSensorTypeDefaultHysteresis Unsigned32,
externalSensorTypeDefaultStateChangeDelay Unsigned32,
externalSensorTypeDefaultLowerCriticalThreshold Integer32,
externalSensorTypeDefaultLowerWarningThreshold Integer32,
externalSensorTypeDefaultUpperCriticalThreshold Integer32,
externalSensorTypeDefaultUpperWarningThreshold Integer32,
externalSensorTypeDefaultEnabledThresholds BITS
}
externalSensorTypeDefaultHysteresis OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The hysteresis used for deassertions
The value of this OID variable should be scaled by
externalSensorDecimalDigits. For example, if the value is 1 and
externalSensorDecimalDigits is 2, then actual value is 0.01.
This parameter does not apply to onOff, trip, vibration,
waterDetection, smokeDetection sensors."
::= { externalSensorTypeDefaultThresholdsEntry 3 }
externalSensorTypeDefaultStateChangeDelay OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The delay measured in samples before a state is asserted.
If the value is zero, then the state is asserted as soon as
it is detected; if it is non-zero, say n, then the assertion
condition must exist for n+1 consecutive samples before the
corresponding assertion event is reported.
At present, this value cannot be written (set)"
::= { externalSensorTypeDefaultThresholdsEntry 4 }
externalSensorTypeDefaultLowerCriticalThreshold OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The lower critical threshold
The value of this OID variable should be scaled by
externalSensorDecimalDigits. For example, if the value is 1 and
externalSensorDecimalDigits is 2, then actual value is 0.01.
This parameter does not apply to onOff, trip, vibration,
waterDetection, smokeDetection sensors."
::= { externalSensorTypeDefaultThresholdsEntry 5 }
externalSensorTypeDefaultLowerWarningThreshold OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The lower non-critical (warning) threshold
The value of this OID variable should be scaled by
externalSensorDecimalDigits. For example, if the value is 1 and
externalSensorDecimalDigits is 2, then actual value is 0.01.
This parameter does not apply to onOff, trip, vibration,
waterDetection, smokeDetection sensors."
::= { externalSensorTypeDefaultThresholdsEntry 6 }
externalSensorTypeDefaultUpperCriticalThreshold OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The upper critical threshold
The value of this OID variable should be scaled by
externalSensorDecimalDigits. For example, if the value is 1 and
externalSensorDecimalDigits is 2, then actual value is 0.01.
This parameter does not apply to onOff, trip, vibration,
waterDetection, smokeDetection sensors."
::= { externalSensorTypeDefaultThresholdsEntry 7 }
externalSensorTypeDefaultUpperWarningThreshold OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The upper non-critical (warning) threshold
The value of this OID variable should be scaled by
externalSensorDecimalDigits. For example, if the value is 1 and
externalSensorDecimalDigits is 2, then actual value is 0.01.
This parameter does not apply to onOff, trip, vibration,
waterDetection, smokeDetection sensors."
::= { externalSensorTypeDefaultThresholdsEntry 8 }
externalSensorTypeDefaultEnabledThresholds OBJECT-TYPE
SYNTAX BITS {
lowerCritical(0),
lowerWarning(1),
upperWarning(2),
upperCritical(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A bit string which indicates which thresholds are enabled.
This parameter does not apply to onOff, trip, vibration,
waterDetection, smokeDetection sensors
"
::= { externalSensorTypeDefaultThresholdsEntry 9}
-- The PeripheralDevicePackageTable table contains information on the peripheral Device Packages connected to the PDU
peripheralDevicePackageTable OBJECT-TYPE
SYNTAX SEQUENCE OF PeripheralDevicePackageEntryStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of entries for the peripheral Device Packages connected to
an EMX. The number of entries is given by the value of
peripheralDevicePackagesCount."
::= { externalSensors 5}
peripheralDevicePackageEntry OBJECT-TYPE
SYNTAX PeripheralDevicePackageEntryStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing objects for a controller."
INDEX { peripheralDevicePackageId }
::= { peripheralDevicePackageTable 1 }
PeripheralDevicePackageEntryStruct ::= SEQUENCE {
peripheralDevicePackageId Integer32,
peripheralDevicePackageSerialNumber DisplayString,
peripheralDevicePackageModel DisplayString,
peripheralDevicePackageFirmwareVersion DisplayString,
peripheralDevicePackageMinFirmwareVersion DisplayString,
peripheralDevicePackageFirmwareTimeStamp Unsigned32,
peripheralDevicePackagePosition DisplayString,
peripheralDevicePackageState DisplayString
}
peripheralDevicePackageId OBJECT-TYPE
SYNTAX Integer32(1..256)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A unique value for each peripheral device package."
::= { peripheralDevicePackageEntry 1 }
peripheralDevicePackageSerialNumber OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The peripheral device package serial number."
::= { peripheralDevicePackageEntry 3 }
peripheralDevicePackageModel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The peripheral device package model.
Examples are DX-D2C6, DPX2-T1, DPX2-T1H1, DPX2-T2H1, DPX2-T3H1"
::= { peripheralDevicePackageEntry 4 }
peripheralDevicePackageFirmwareVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The peripheral device package firmware version."
::= { peripheralDevicePackageEntry 5 }
peripheralDevicePackageMinFirmwareVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The peripheral device package minimum firmware version.
This field may be empty. If it is not empty, then it shall not be
possible to downgrade the peripheral device firmware to a
version < minimum firmware version number."
::= { peripheralDevicePackageEntry 6 }
peripheralDevicePackageFirmwareTimeStamp OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The time when the peripheralDevicePackage firmware was updated in
UNIX(epoch)time.
It is measured in seconds relative to January 1, 1970 (midnight UTC/GMT),
i.e a value of 0 indicates January 1, 1970 (midnight UTC/GMT)."
::= { peripheralDevicePackageEntry 7 }
peripheralDevicePackagePosition OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The position of the package.
The format is a semicolon separated list of Keyword:value pairs -
Keyword1:Value1;Keyword2:value2;...
Keyword can be one of the following:
ONBOARD, DEVICE-1WIREPORT, HUBPORT, CHAIN-POSITION
Examples
1) Onboard Sensor
ONBOARD:CC1
2) Old sensor connected to device 1-wire port
DEVICE-1WIREPORT:2
3) New style sensor connected to device 1-wire port
DEVICE-1WIREPORT:2;CHAIN-POSITION:3
4) New style sensor connected to hub port 3
DEVICE-1WIREPORT:2;CHAIN-POSITION:1;HUBPORT:3;CHAIN-POSITION:1
5) Old style sensor connected to end of new style sensor chain
DEVICE-1WIREPORT:2;
"
::= { peripheralDevicePackageEntry 8 }
peripheralDevicePackageState OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The state of the package."
::= { peripheralDevicePackageEntry 9 }
-- the server reachability table
-- The server Reachability table contains information on the ping feature.
serverReachabilityTable OBJECT-TYPE
SYNTAX SEQUENCE OF ServerReachabilityEntryStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of server entries. The number of
entries is given by the value of serverCount for the EMD."
::= { serverReachability 1 }
serverReachabilityEntry OBJECT-TYPE
SYNTAX ServerReachabilityEntryStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing parameters for a server."
INDEX { serverID }
::= { serverReachabilityTable 1 }
ServerReachabilityEntryStruct ::= SEQUENCE {
serverID Integer32,
serverIPAddress DisplayString,
serverPingEnabled TruthValue
}
serverID OBJECT-TYPE
SYNTAX Integer32(1..256)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A unique value for each server. Its value
ranges between 1 and the value of serverCount for that EMD"
::= { serverReachabilityEntry 1 }
serverIPAddress OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The IP Address/host name of the server"
::= { serverReachabilityEntry 2 }
serverPingEnabled OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Is ping enabled for this server?"
::= { serverReachabilityEntry 3 }
-- the log table
-- The logIndexTable
oldestLogID OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The index of the oldest data in the buffer for this EMD."
::= { logUnit 1 }
newestLogID OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The index of the newest data in the buffer for this EMD."
::= { logUnit 2 }
-- The logTimeStampTable
logTimeStampTable OBJECT-TYPE
SYNTAX SEQUENCE OF LogTimeStampEntryStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of entries containing the timestamps of the entries in the log."
::= { logUnit 3 }
logTimeStampEntry OBJECT-TYPE
SYNTAX LogTimeStampEntryStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing the timestamp for log entries."
INDEX { logIndex }
::= { logTimeStampTable 1 }
LogTimeStampEntryStruct ::= SEQUENCE {logIndex Integer32,
logTimeStamp Unsigned32
}
logIndex OBJECT-TYPE
SYNTAX Integer32(1..256)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A unique value for each entry in the log. Its value
ranges between 1 and the value of logSize."
::= { logTimeStampEntry 1 }
logTimeStamp OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The time when the data was collected. It is measured in seconds relative to
January 1, 1970 (midnight UTC/GMT), i.e a value of 0 indicates
January 1, 1970 (midnight UTC/GMT)."
::= { logTimeStampEntry 2 }
-- The externalSensorLogTable
externalSensorLogTable OBJECT-TYPE
SYNTAX SEQUENCE OF ExternalSensorLogEntryStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of external sensor entries. The number of
entries is given by the value of externalSensorCount for the EMD."
::= { logExternalSensor 1 }
externalSensorLogEntry OBJECT-TYPE
SYNTAX ExternalSensorLogEntryStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing log objects for an external sensor."
INDEX { sensorID, logIndex }
::= { externalSensorLogTable 1 }
ExternalSensorLogEntryStruct ::= SEQUENCE {
logExternalSensorDataAvailable TruthValue,
logExternalSensorState SensorStateEnumeration,
logExternalSensorAvgValue Integer32,
logExternalSensorMaxValue Integer32,
logExternalSensorMinValue Integer32
}
logExternalSensorDataAvailable OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Is data available for this sensor during this measurement period?"
::= { externalSensorLogEntry 2 }
logExternalSensorState OBJECT-TYPE
SYNTAX SensorStateEnumeration
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The sensor state."
::= { externalSensorLogEntry 3 }
logExternalSensorAvgValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The sensor reading average value."
::= { externalSensorLogEntry 4 }
logExternalSensorMaxValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The sensor reading maximum value."
::= { externalSensorLogEntry 5 }
logExternalSensorMinValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The sensor reading minimum value."
::= { externalSensorLogEntry 6 }
-- the Measurements tables
-- The externalSensorMeasurementsTable
externalSensorMeasurementsTable OBJECT-TYPE
SYNTAX SEQUENCE OF ExternalSensorMeasurementsEntryStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of external sensor entries. The number of
entries is given by the value of externalSensorCount
for the EMD."
::= { measurementsExternalSensor 1 }
externalSensorMeasurementsEntry OBJECT-TYPE
SYNTAX ExternalSensorMeasurementsEntryStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing measurement objects for an external sensor."
INDEX { sensorID }
::= { externalSensorMeasurementsTable 1 }
ExternalSensorMeasurementsEntryStruct ::= SEQUENCE {
measurementsExternalSensorIsAvailable TruthValue,
measurementsExternalSensorState SensorStateEnumeration,
measurementsExternalSensorValue Integer32,
measurementsExternalSensorTimeStamp Unsigned32
}
measurementsExternalSensorIsAvailable OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Is the sensor available?"
::= { externalSensorMeasurementsEntry 1 }
measurementsExternalSensorState OBJECT-TYPE
SYNTAX SensorStateEnumeration
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The sensor state."
::= { externalSensorMeasurementsEntry 2 }
measurementsExternalSensorValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The sensor reading.
This parameter does not apply
to onOff, trip, vibration, waterDetection,
smokeDetection sensors."
::= { externalSensorMeasurementsEntry 3 }
measurementsExternalSensorTimeStamp OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The sensor reading timestamp."
::= { externalSensorMeasurementsEntry 4 }
-- the actuatorControlTable
-- The actuatorControl table implements user-initiated state changes for an actuator.
actuatorControlTable OBJECT-TYPE
SYNTAX SEQUENCE OF ActuatorControlEntryStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of actuators for an EMX. "
::= { actuatorControl 1 }
actuatorControlEntry OBJECT-TYPE
SYNTAX ActuatorControlEntryStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry for implementing user-initiated state changes for an actuator."
INDEX { sensorID }
::= { actuatorControlTable 1 }
ActuatorControlEntryStruct ::= SEQUENCE {
actuatorState SensorStateEnumeration
}
actuatorState OBJECT-TYPE
SYNTAX SensorStateEnumeration
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The actuator state.
A Get operation retrieves the state of the actuator.
A Set operation changes the stae of the sensor.
The valid states for set operations are on and Off.
Attempting to set the state to any other value will generate an error. "
::= { actuatorControlEntry 1 }
-- the TrapInformation
-- The TrapInformation table defines information sent in the traps.
userName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The user currently logged in."
::= { trapInformation 1 }
targetUser OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The user added, deleted, or modified."
::= { trapInformation 2 }
imageVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The version of the upgrade image."
::= { trapInformation 3 }
roleName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The role added, deleted, or modified."
::= { trapInformation 4 }
smtpMessageRecipients OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Comma separated list of SMTP Message recipients"
::= { trapInformation 5 }
smtpServer OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The IP address/host name of the SMTP server"
::= { trapInformation 6 }
-- Additional Information needed for traps.
oldSensorState OBJECT-TYPE
SYNTAX SensorStateEnumeration
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The old sensor state used in
Sensor State Transition traps."
::= { trapInformation 7}
externalSensorNumber OBJECT-TYPE
SYNTAX Integer32(1..256)
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"A unique value for each sensor. Its value
ranges between 1 and the value of
externalSensorCount."
::= { trapInformation 8 }
typeOfSensor OBJECT-TYPE
SYNTAX SensorTypeEnumeration
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The type of sensor."
::= { trapInformation 9 }
errorDescription OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Description of the Error"
::= { trapInformation 10 }
deviceChangedParameter OBJECT-TYPE
SYNTAX DeviceIdentificationParameterEnumeration
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Description of the parameter(s) that changed."
::= { trapInformation 11 }
changedParameterNewValue OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The new value of the changed parameter"
::= { trapInformation 12 }
lhxSupportEnabled OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The new enabled state for Schroff LHX Support."
::= { trapInformation 13 }
webcamModel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The model of the Webcam "
::= { trapInformation 14 }
webcamConnectionPort OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The port to which the Webcam is connected "
::= { trapInformation 15 }
peripheralDeviceRomcode OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The Romcode of an peripheral device"
::= { trapInformation 16 }
peripheralDeviceFirmwareUpdateState OBJECT-TYPE
SYNTAX PeripheralDeviceFirmwareUpdateStateEnumeration
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The firmware update state of an peripheral device"
::= { trapInformation 17 }
agentInetPortNumber OBJECT-TYPE
SYNTAX InetPortNumber
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The UDP port number used for accessing
the SNMP agent on the device.
Examples:
If deviceCascadeType is portForwarding, then
master: 50500
slave 1:50501
slave 2: 50502
......
If cascading mode is not portForwarding and default
(Standard) ports are being used, then port: 161"
::= { trapInformation 18 }
phoneNumber OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The phone number of e.g. an SMS receiver."
::= { trapInformation 19 }
-- Start the traps
-- All traps contain the deviceInetAddressType and deviceInetIPAddress fields.
-- For IPv4, these parameters contain the IP Address Type and IP address
-- For IPv6, these parameters are not used
systemStarted NOTIFICATION-TYPE
OBJECTS { deviceName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
sysContact,
sysName,
sysLocation }
STATUS current
DESCRIPTION
"The system has started."
::= { traps 1 }
systemReset NOTIFICATION-TYPE
OBJECTS { deviceName,
userName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
sysContact,
sysName,
sysLocation }
STATUS current
DESCRIPTION
"The system was reset. The conditions under which
this trap is sent include, but are not limited
to, the following.
using the GUI - Maintenance->Reset Unit
using the CLI - reset emd unit"
::= { traps 2 }
userLogin NOTIFICATION-TYPE
OBJECTS { deviceName,
userName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
sysContact,
sysName,
sysLocation }
STATUS current
DESCRIPTION
"A user logged in."
::= { traps 3 }
userLogout NOTIFICATION-TYPE
OBJECTS { deviceName,
userName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
sysContact,
sysName,
sysLocation }
STATUS current
DESCRIPTION
"A user logged out."
::= { traps 4 }
userAuthenticationFailure NOTIFICATION-TYPE
OBJECTS { deviceName,
userName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
sysContact,
sysName,
sysLocation }
STATUS current
DESCRIPTION
"A user authentication attempt failed."
::= { traps 5 }
userSessionTimeout NOTIFICATION-TYPE
OBJECTS { deviceName,
userName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
sysContact,
sysName,
sysLocation }
STATUS current
DESCRIPTION
"A user timed out from the device."
::= { traps 6 }
userAdded NOTIFICATION-TYPE
OBJECTS { deviceName,
userName,
targetUser,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
sysContact,
sysName,
sysLocation }
STATUS current
DESCRIPTION
"A user was added to the system."
::= { traps 7 }
userModified NOTIFICATION-TYPE
OBJECTS { deviceName,
userName,
targetUser,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
sysContact,
sysName,
sysLocation }
STATUS current
DESCRIPTION
"A user account was modified."
::= { traps 8 }
userDeleted NOTIFICATION-TYPE
OBJECTS { deviceName,
userName,
targetUser,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
sysContact,
sysName,
sysLocation }
STATUS current
DESCRIPTION
"A user was deleted from the system."
::= { traps 9 }
roleAdded NOTIFICATION-TYPE
OBJECTS { deviceName,
userName,
roleName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
sysContact,
sysName,
sysLocation }
STATUS current
DESCRIPTION
"A role was added to the system."
::= { traps 10 }
roleModified NOTIFICATION-TYPE
OBJECTS { deviceName,
userName,
roleName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
sysContact,
sysName,
sysLocation }
STATUS current
DESCRIPTION
"A role was modified."
::= { traps 11 }
roleDeleted NOTIFICATION-TYPE
OBJECTS { deviceName,
userName,
roleName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
sysContact,
sysName,
sysLocation }
STATUS current
DESCRIPTION
"A role was deleted from the system."
::= { traps 12 }
deviceUpdateStarted NOTIFICATION-TYPE
OBJECTS { deviceName,
userName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
imageVersion,
sysContact,
sysName,
sysLocation }
STATUS current
DESCRIPTION
"The device update has started."
::= { traps 13 }
deviceUpdateCompleted NOTIFICATION-TYPE
OBJECTS { deviceName,
userName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
imageVersion,
sysContact,
sysName,
sysLocation }
STATUS current
DESCRIPTION
"The device update has completed."
::= { traps 14 }
userBlocked NOTIFICATION-TYPE
OBJECTS { deviceName,
userName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
sysContact,
sysName,
sysLocation }
STATUS current
DESCRIPTION
"A blocked user tried to log in."
::= { traps 15 }
userPasswordChanged NOTIFICATION-TYPE
OBJECTS { deviceName,
userName,
targetUser,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
sysContact,
sysName,
sysLocation }
STATUS current
DESCRIPTION
"User password was changed."
::= { traps 16 }
passwordSettingsChanged NOTIFICATION-TYPE
OBJECTS { deviceName,
userName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
sysContact,
sysName,
sysLocation }
STATUS current
DESCRIPTION
"Strong password settings changed."
::= { traps 17 }
firmwareValidationFailed NOTIFICATION-TYPE
OBJECTS { deviceName,
userName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
sysContact,
sysName,
sysLocation }
STATUS current
DESCRIPTION
"Firmware validation failed."
::= { traps 18 }
logFileCleared NOTIFICATION-TYPE
OBJECTS { deviceName,
userName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
sysContact,
sysName,
sysLocation }
STATUS current
DESCRIPTION
"The log file has been cleared."
::= { traps 19 }
bulkConfigurationSaved NOTIFICATION-TYPE
OBJECTS { deviceName,
userName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
sysContact,
sysName,
sysLocation }
STATUS current
DESCRIPTION
"Bulk Configuration saved."
::= { traps 20 }
bulkConfigurationCopied NOTIFICATION-TYPE
OBJECTS { deviceName,
userName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
sysContact,
sysName,
sysLocation }
STATUS current
DESCRIPTION
"Bulk Configuration saved."
::= { traps 21 }
externalSensorStateChange NOTIFICATION-TYPE
OBJECTS { deviceName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
externalSensorNumber,
typeOfSensor,
measurementsExternalSensorTimeStamp,
measurementsExternalSensorValue,
measurementsExternalSensorState,
oldSensorState,
externalSensorSerialNumber,
externalOnOffSensorSubtype,
externalSensorChannelNumber,
sysContact,
sysName,
sysLocation }
STATUS current
DESCRIPTION
"External Sensor State Change."
::= { traps 22 }
smtpMessageTransmissionFailure NOTIFICATION-TYPE
OBJECTS { deviceName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
smtpMessageRecipients,
smtpServer,
sysContact,
sysName,
sysLocation }
STATUS current
DESCRIPTION
"SMTP message transmission failure"
::= { traps 23 }
ldapError NOTIFICATION-TYPE
OBJECTS { deviceName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
errorDescription,
sysContact,
sysName,
sysLocation }
STATUS current
DESCRIPTION
"LDAP Error occurred; errorDescription describes
the error"
::= { traps 24 }
deviceUpdateFailed NOTIFICATION-TYPE
OBJECTS { deviceName,
userName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
imageVersion,
sysContact,
sysName,
sysLocation }
STATUS current
DESCRIPTION
"The device update has failed."
::= { traps 25 }
pingServerEnabled NOTIFICATION-TYPE
OBJECTS { deviceName,
userName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
serverIPAddress,
sysContact,
sysName,
sysLocation }
STATUS current
DESCRIPTION
"The ping feature has been enabled"
::= { traps 26 }
pingServerDisabled NOTIFICATION-TYPE
OBJECTS { deviceName,
userName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
serverIPAddress,
sysContact,
sysName,
sysLocation }
STATUS current
DESCRIPTION
"The ping feature has been disabled"
::= { traps 27 }
serverNotReachable NOTIFICATION-TYPE
OBJECTS { deviceName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
serverIPAddress,
sysContact,
sysName,
sysLocation }
STATUS current
DESCRIPTION
"The server is not reachable"
::= { traps 28 }
serverReachable NOTIFICATION-TYPE
OBJECTS { deviceName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
serverIPAddress,
sysContact,
sysName,
sysLocation }
STATUS current
DESCRIPTION
"The server is reachable"
::= { traps 29 }
deviceIdentificationChanged NOTIFICATION-TYPE
OBJECTS { deviceName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
userName,
deviceChangedParameter,
changedParameterNewValue,
sysContact,
sysName,
sysLocation }
STATUS current
DESCRIPTION
"Device identification has changed"
::= { traps 30 }
usbSlaveConnected NOTIFICATION-TYPE
OBJECTS { deviceName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
sysContact,
sysName,
sysLocation
}
STATUS current
DESCRIPTION
"USB Connectivity to slave has been established"
::= { traps 31 }
usbSlaveDisconnected NOTIFICATION-TYPE
OBJECTS { deviceName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
sysContact,
sysName,
sysLocation
}
STATUS current
DESCRIPTION
"USB Connectivity to slave has been lost"
::= { traps 32 }
lhxSupportChanged NOTIFICATION-TYPE
OBJECTS { deviceName,
userName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
sysContact,
sysName,
sysLocation,
lhxSupportEnabled
}
STATUS current
DESCRIPTION
"The Schroff LHX Support changed to state 'lhxSupportEnabled'."
::= { traps 33 }
userAcceptedRestrictedServiceAgreement NOTIFICATION-TYPE
OBJECTS { deviceName,
userName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
sysContact,
sysName,
sysLocation
}
STATUS current
DESCRIPTION
"The user accepted the Restricted Service Agreement."
::= { traps 34 }
userDeclinedRestrictedServiceAgreement NOTIFICATION-TYPE
OBJECTS { deviceName,
userName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
sysContact,
sysName,
sysLocation
}
STATUS current
DESCRIPTION
"The user declined the Restricted Service Agreement."
::= { traps 35 }
deviceSettingsSaved NOTIFICATION-TYPE
OBJECTS { deviceName,
userName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
sysContact,
sysName,
sysLocation
}
STATUS current
DESCRIPTION
"Device Settings have been saved."
::= { traps 36 }
deviceSettingsRestored NOTIFICATION-TYPE
OBJECTS { deviceName,
userName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
sysContact,
sysName,
sysLocation
}
STATUS current
DESCRIPTION
"Device Settings have been restored."
::= { traps 37 }
webcamInserted NOTIFICATION-TYPE
OBJECTS { deviceName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
webcamModel,
webcamConnectionPort,
sysContact,
sysName,
sysLocation
}
STATUS current
DESCRIPTION
"A webcam has been inserted"
::= { traps 38 }
webcamRemoved NOTIFICATION-TYPE
OBJECTS { deviceName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
webcamModel,
webcamConnectionPort,
sysContact,
sysName,
sysLocation
}
STATUS current
DESCRIPTION
"A webcam has been removed"
::= { traps 39 }
serverConnectivityUnrecoverable NOTIFICATION-TYPE
OBJECTS { deviceName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
serverIPAddress,
sysContact,
sysName,
sysLocation
}
STATUS current
DESCRIPTION
"The connection to the server could not be recovered"
::= { traps 40 }
radiusError NOTIFICATION-TYPE
OBJECTS { deviceName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
errorDescription,
sysContact,
sysName,
sysLocation
}
STATUS current
DESCRIPTION
"LDAP Error occurred; errorDescription describes the error"
::= { traps 41 }
serverReachabilityError NOTIFICATION-TYPE
OBJECTS { deviceName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
serverIPAddress,
errorDescription,
sysContact,
sysName,
sysLocation }
STATUS current
DESCRIPTION
"Server Reachability Error occurred; errorDescription describes the error.
This trap is sent when the Error state is entered.
Reasons for transitioning to the Error state include the following:
Unable to resolve the server hostname."
::= { traps 42 }
unknownPeripheralDeviceAttached NOTIFICATION-TYPE
OBJECTS { deviceName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
peripheralDeviceRomcode,
peripheralDevicePackagePosition,
sysContact,
sysName,
sysLocation
}
STATUS current
DESCRIPTION
"An unknown peripheral device was attached."
::= { traps 43 }
peripheralDeviceFirmwareUpdate NOTIFICATION-TYPE
OBJECTS { deviceName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
peripheralDevicePackageSerialNumber,
peripheralDeviceFirmwareUpdateState,
peripheralDevicePackageFirmwareVersion,
sysContact,
sysName,
sysLocation
}
STATUS current
DESCRIPTION
"The firmware update state of a peripheral device changed while
performing update to peripheralDevicePackageFirmwareVersion."
::= { traps 44 }
smsMessageTransmissionFailure NOTIFICATION-TYPE
OBJECTS { deviceName,
deviceInetAddressType,
deviceInetIPAddress,
agentInetPortNumber,
phoneNumber,
sysContact,
sysName,
sysLocation
}
STATUS current
DESCRIPTION
"Sending an SMS message failed."
::= { traps 45 }
END