ENVIROMUXMINI-MIB DEFINITIONS ::= BEGIN
IMPORTS
OBJECT-GROUP, NOTIFICATION-GROUP FROM SNMPv2-CONF
MODULE-IDENTITY, OBJECT-TYPE, OBJECT-IDENTITY,
enterprises, NOTIFICATION-TYPE FROM SNMPv2-SMI
DisplayString, TEXTUAL-CONVENTION FROM SNMPv2-TC;
enviromuxMini MODULE-IDENTITY
LAST-UPDATED "200909241400Z"
ORGANIZATION "Network Technologies Inc."
CONTACT-INFO
"Adrian Bica - Engineering
Postal: 1275 Danner Dr,
Aurora, OH 442022
US
Tel: 330-562-7070
Fax: 330-562-1999
WEB: www.nti1.com"
DESCRIPTION "ENVIROMUX-MINI MIB module"
REVISION "200909241400Z"
DESCRIPTION "Rev. 1.2. Individual traps for return from alert"
REVISION "200704131400Z"
DESCRIPTION "Rev. 1.1"
REVISION "200503301400Z"
DESCRIPTION "Rev. 1.0"
::= { hardware 3 }
-- the root of the subtree for Network Technologies Inc
nti OBJECT IDENTIFIER ::= {enterprises 3699}
-- subtree for products
products OBJECT IDENTIFIER ::= {nti 1}
hardware OBJECT IDENTIFIER ::= {products 1}
software OBJECT IDENTIFIER ::= {products 2}
otherProduct OBJECT IDENTIFIER ::= {hardware 200}
monitoring OBJECT IDENTIFIER ::= {enviromuxMini 1}
administration OBJECT IDENTIFIER ::= {enviromuxMini 2}
envTraps OBJECT IDENTIFIER ::= {enviromuxMini 100}
envGroups OBJECT IDENTIFIER ::= {enviromuxMini 200}
temperatureSensor1 OBJECT IDENTIFIER ::= {monitoring 1}
temperatureSensor2 OBJECT IDENTIFIER ::= {monitoring 2}
humiditySensor1 OBJECT IDENTIFIER ::= {monitoring 3}
humiditySensor2 OBJECT IDENTIFIER ::= {monitoring 4}
dryContact1 OBJECT IDENTIFIER ::= {monitoring 5}
dryContact2 OBJECT IDENTIFIER ::= {monitoring 6}
dryContact3 OBJECT IDENTIFIER ::= {monitoring 7}
dryContact4 OBJECT IDENTIFIER ::= {monitoring 8}
waterSensor OBJECT IDENTIFIER ::= {monitoring 9}
hostSystem OBJECT IDENTIFIER ::= {administration 1}
temperatureSensor1Adm OBJECT IDENTIFIER ::= {administration 2}
temperatureSensor2Adm OBJECT IDENTIFIER ::= {administration 3}
humiditySensor1Adm OBJECT IDENTIFIER ::= {administration 4}
humiditySensor2Adm OBJECT IDENTIFIER ::= {administration 5}
dryContact1Adm OBJECT IDENTIFIER ::= {administration 6}
dryContact2Adm OBJECT IDENTIFIER ::= {administration 7}
dryContact3Adm OBJECT IDENTIFIER ::= {administration 8}
dryContact4Adm OBJECT IDENTIFIER ::= {administration 9}
waterSensorAdm OBJECT IDENTIFIER ::= {administration 10}
-- textual conventions
DecimalPointValue ::= TEXTUAL-CONVENTION
DISPLAY-HINT "d-1"
STATUS current
DESCRIPTION
"Display integer values using a decimal point before last digit"
SYNTAX INTEGER (-1000..1000)
-- groups
unitGroup OBJECT-GROUP
OBJECTS {version,
temperatureSensor1CurrentValue, temperatureSensor1Alert, temperatureSensor1Name, temperatureSensor1Unit,
temperatureSensor1LowThreshold, temperatureSensor1HighThreshold,
temperatureSensor2CurrentValue, temperatureSensor2Alert, temperatureSensor2Name, temperatureSensor2Unit,
temperatureSensor2LowThreshold, temperatureSensor2HighThreshold,
humiditySensor1CurrentValue, humiditySensor1Alert, humiditySensor1Name, humiditySensor1LowThreshold, humiditySensor1HighThreshold,
humiditySensor2CurrentValue, humiditySensor2Alert, humiditySensor2Name, humiditySensor2LowThreshold, humiditySensor2HighThreshold,
dryContact1Status, dryContact1Alert, dryContact1Name, dryContact1AlertStatus,
dryContact2Status, dryContact2Alert, dryContact2Name, dryContact2AlertStatus,
dryContact3Status, dryContact3Alert, dryContact3Name, dryContact3AlertStatus,
dryContact4Status, dryContact4Alert, dryContact4Name, dryContact4AlertStatus,
waterStatus, waterAlert, waterName, waterAlertStatus,
sysName, sysLocation, sysIP, sysMask, sysGateway, sysDNS }
STATUS current
DESCRIPTION "System parameters group"
::= {envGroups 1}
envTrapsGroup NOTIFICATION-GROUP
NOTIFICATIONS { temperatureSensor1Trap, temperatureSensor2Trap, humiditySensor1Trap, humiditySensor2Trap,
dryContactSensor1Trap, dryContactSensor2Trap, dryContactSensor3Trap, dryContactSensor4Trap,
waterSensor1Trap, logTrap, overflowTrap }
STATUS current
DESCRIPTION "Traps group"
::= {envGroups 2}
-- code version
version OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Code version"
::= {enviromuxMini 3}
-- temperature 1
temperatureSensor1CurrentValue OBJECT-TYPE
SYNTAX DecimalPointValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current value of the temperature sensor connected to port 1 in tenths of degrees .
This port is the right RJ-45 sensor port. The value is expressed in the units
indicated in temperatureSensor1Unit.
This object is only applicable if a temperature sensor is connected to port 1."
::= {temperatureSensor1 1}
temperatureSensor1Alert OBJECT-TYPE
SYNTAX INTEGER {off(0), on(1)}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current alert status of the temperature sensor connected to port 1.
This port is the right RJ-45 sensor port. A value of 0 indicates
that the sensor has not crossed either of its specified thresholds,
while a value of 1 indicates that it has.
This object is only applicable if a temperature sensor is connected to port 1."
::= {temperatureSensor1 2}
temperatureSensor1Name OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Current name assigned to the temperature sensor connected to port 1.
This port is the right RJ-45 sensor port. This value corresponds directly
with the name entered in the configuration page for this sensor.
This object is only applicable if a temperature sensor is connected to port 1."
::= {temperatureSensor1Adm 1}
temperatureSensor1Unit OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Temperature units for the value of the temperature sensor connected to port 1.
This port is the right RJ-45 sensor port. The unit may either be Fahrenheit or Celsius,
and corresponds directly with the unit chosen on the configuration page for this sensor.
This object is only applicable if a temperature sensor is connected to port 1 or 2."
::= {temperatureSensor1Adm 2}
temperatureSensor1LowThreshold OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Low threshold assigned to the temperature sensor connected to port 1.
This port is the right RJ-45 sensor port. This value corresponds directly
with the low threshold value entered in the configuration page for this sensor.
This object is only applicable if a temperature sensor is connected to port 1."
::= {temperatureSensor1Adm 3}
temperatureSensor1HighThreshold OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"High threshold assigned to the temperature sensor connected to port 1.
This port is the right RJ-45 sensor port. This value corresponds directly
with the high threshold value entered in the configuration page for this sensor.
This object is only applicable if a temperature sensor is connected to port 1."
::= {temperatureSensor1Adm 4}
-- temperature 2
temperatureSensor2CurrentValue OBJECT-TYPE
SYNTAX DecimalPointValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current value of the temperature sensor connected to port 2 in tenths of degrees .
This port is the left RJ-45 sensor port. The value is expressed in the units
indicated in temperatureSensor2Unit.
This object is only applicable if a temperature sensor is connected to port 2."
::= {temperatureSensor2 1}
temperatureSensor2Alert OBJECT-TYPE
SYNTAX INTEGER {off(0), on(1)}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current alert status of the temperature sensor connected to port 2.
This port is the left RJ-45 sensor port. A value of 0 indicates
that the sensor has not crossed either of its specified thresholds,
while a value of 1 indicates that it has.
This object is only applicable if a temperature sensor is connected to port 2."
::= {temperatureSensor2 2}
temperatureSensor2Name OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Current name assigned to the temperature sensor connected to port 2.
This port is the left RJ-45 sensor port. This value corresponds directly
with the name entered in the configuration page for this sensor.
This object is only applicable if a temperature sensor is connected to port 2."
::= {temperatureSensor2Adm 1}
temperatureSensor2Unit OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Temperature units for the value of the temperature sensor connected to port 2.
This port is the left RJ-45 sensor port. The unit may either be Fahrenheit or Celsius,
and corresponds directly with the unit chosen on the configuration page for this sensor.
This object is only applicable if a temperature sensor is connected to port 1 or 2."
::= {temperatureSensor2Adm 2}
temperatureSensor2LowThreshold OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Low threshold assigned to the temperature sensor connected to port 2.
This port is the left RJ-45 sensor port. This value corresponds directly
with the low threshold value entered in the configuration page for this sensor.
This object is only applicable if a temperature sensor is connected to port 2."
::= {temperatureSensor2Adm 3}
temperatureSensor2HighThreshold OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"High threshold assigned to the temperature sensor connected to port 2.
This port is the left RJ-45 sensor port. This value corresponds directly
with the high threshold value entered in the configuration page for this sensor.
This object is only applicable if a temperature sensor is connected to port 2."
::= {temperatureSensor2Adm 4}
-- humidity 1
humiditySensor1CurrentValue OBJECT-TYPE
SYNTAX DecimalPointValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current integer value in tenths of percents of the humidity sensor connected to port 1.
This port is the right RJ-45 sensor port. The value corresponds directly with
the value displayed on the summary page and the status page for this sensor.
This object is only applicable if a humidity sensor is connected to port 1."
::= {humiditySensor1 1}
humiditySensor1Alert OBJECT-TYPE
SYNTAX INTEGER {off(0), on(1)}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current alert status of the humidity sensor connected to port 1.
This port is the right RJ-45 sensor port. A value of 0 indicates
that the sensor has not crossed either of its specified thresholds,
while a value of 1 indicates that it has.
This object is only applicable if a humidity sensor is connected to port 1."
::= {humiditySensor1 2}
humiditySensor1Name OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Current name assigned to the humidity sensor connected to port 1.
This port is the right RJ-45 sensor port. This value corresponds directly
with the name entered in the configuration page for this sensor.
This object is only applicable if a humidity sensor is connected to port 1."
::= {humiditySensor1Adm 1}
humiditySensor1LowThreshold OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Low threshold assigned to the humidity sensor connected to port 1.
This port is the right RJ-45 sensor port. This value corresponds directly
with the low threshold value entered in the configuration page for this sensor.
This object is only applicable if a humidity sensor is connected to port 1."
::= {humiditySensor1Adm 2}
humiditySensor1HighThreshold OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"High threshold assigned to the humidity sensor connected to port 1.
This port is the right RJ-45 sensor port. This value corresponds directly
with the high threshold value entered in the configuration page for this sensor.
This object is only applicable if a humidity sensor is connected to port 1."
::= {humiditySensor1Adm 3}
-- humidity 2
humiditySensor2CurrentValue OBJECT-TYPE
SYNTAX DecimalPointValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current integer value in tenths of percents of the humidity sensor connected to port 2.
This port is the left RJ-45 sensor port. The value corresponds directly
with the value displayed on the summary page and the status page for this sensor.
This object is only applicable if a humidity sensor is connected to port 2."
::= {humiditySensor2 1}
humiditySensor2Alert OBJECT-TYPE
SYNTAX INTEGER {off(0), on(1)}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current alert status of the humidity sensor connected to port 2.
This port is the left RJ-45 sensor port. A value of 0 indicates
that the sensor has not crossed either of its specified thresholds,
while a value of 1 indicates that it has.
his object is only applicable if a humidity sensor is connected to port 2."
::= {humiditySensor2 2}
humiditySensor2Name OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Current name assigned to the humidity sensor connected to port 2.
This port is the left RJ-45 sensor port. This value corresponds directly
with the name entered in the configuration page for this sensor.
This object is only applicable if a humidity sensor is connected to port 2."
::= {humiditySensor2Adm 1}
humiditySensor2LowThreshold OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Low threshold assigned to the humidity sensor connected to port 2.
This port is the left RJ-45 sensor port. This value corresponds directly
with the low threshold value entered in the configuration page for this sensor.
This object is only applicable if a humidity sensor is connected to port 2."
::= {humiditySensor2Adm 2}
humiditySensor2HighThreshold OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"High threshold assigned to the humidity sensor connected to port 1.
This port is the right RJ-45 sensor port. This value corresponds directly
with the high threshold value entered in the configuration page for this sensor.
This object is only applicable if a humidity sensor is connected to port 1."
::= {humiditySensor2Adm 3}
-- dry contact 1
dryContact1Status OBJECT-TYPE
SYNTAX INTEGER {open(0), closed(1)}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current integer value of the dry contact sensor connected to port 1.
A value of 0 represents OPEN, and a value of 1 represents CLOSED.
The value corresponds directly with the value displayed on the
summary page and the status page for this sensor.
This object is only applicable if a dry contact sensor is connected to port 1."
::= {dryContact1 1}
dryContact1Alert OBJECT-TYPE
SYNTAX INTEGER {off(0), on(1)}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current alert status of the dry contact sensor connected to port 1.
A value of 0 indicates that the sensor has not been set to its alert condition,
while a value of 1 indicates that it has.
This object is only applicable if a dry contact sensor is connected to port 1."
::= {dryContact1 2}
dryContact1Name OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Current name assigned to the dry contact sensor connected to port 1.
This value corresponds directly with the name entered in the configuration page for this sensor.
This object is only applicable if a dry contact sensor is connected to port 1."
::= {dryContact1Adm 1}
dryContact1AlertStatus OBJECT-TYPE
SYNTAX INTEGER {alertWhenOpen(0), alertWhenClosed(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Status which generates an alert condition for the dry contact sensor connected to port 1.
A value of 0 represents OPEN, and a value of 1 represents CLOSED.
This value corresponds directly with the Alert When value entered in the configuration page for this sensor.
This object is only applicable if a dry contact sensor is connected to port 1."
::= {dryContact1Adm 2}
-- dry contact 2
dryContact2Status OBJECT-TYPE
SYNTAX INTEGER {open(0), closed(1)}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current integer value of the dry contact sensor connected to port 2.
A value of 0 represents OPEN, and a value of 1 represents CLOSED.
The value corresponds directly with the value displayed on the summary page and the status page for this sensor.
This object is only applicable if a dry contact sensor is connected to port 2."
::= {dryContact2 1}
dryContact2Alert OBJECT-TYPE
SYNTAX INTEGER {off(0), on(1)}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current alert status of the dry contact sensor connected to port 2.
value of 0 indicates that the sensor has not been set to its alert condition,
while a value of 1 indicates that it has.
This object is only applicable if a dry contact sensor is connected to port 2."
::= {dryContact2 2}
dryContact2Name OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Current name assigned to the dry contact sensor connected to port 2.
This value corresponds directly with the name entered in the configuration page for this sensor.
This object is only applicable if a dry contact sensor is connected to port 2."
::= {dryContact2Adm 1}
dryContact2AlertStatus OBJECT-TYPE
SYNTAX INTEGER {alertWhenOpen(0), alertWhenClosed(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Status which generates an alert condition for the dry contact sensor connected to port 2.
A value of 0 represents OPEN, and a value of 1 represents CLOSED.
This value corresponds directly with the Alert When value entered in the configuration page for this sensor.
This object is only applicable if a dry contact sensor is connected to port 2."
::= {dryContact2Adm 2}
-- dry contact 3
dryContact3Status OBJECT-TYPE
SYNTAX INTEGER {open(0), closed(1)}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current integer value of the dry contact sensor connected to port 3.
A value of 0 represents OPEN, and a value of 1 represents CLOSED.
The value corresponds directly with the value displayed on the summary page and the status page for this sensor.
This object is only applicable if a dry contact sensor is connected to port 3."
::= {dryContact3 1}
dryContact3Alert OBJECT-TYPE
SYNTAX INTEGER {off(0), on(1)}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current alert status of the dry contact sensor connected to port 3.
A value of 0 indicates that the sensor has not been set to its alert condition,
while a value of 1 indicates that it has.
This object is only applicable if a dry contact sensor is connected to port 3."
::= {dryContact3 2}
dryContact3Name OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Current name assigned to the dry contact sensor connected to port 3.
This value corresponds directly with the name entered in the configuration page for this sensor.
This object is only applicable if a dry contact sensor is connected to port 3."
::= {dryContact3Adm 1}
dryContact3AlertStatus OBJECT-TYPE
SYNTAX INTEGER {alertWhenOpen(0), alertWhenClosed(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Status which generates an alert condition for the dry contact sensor connected to port 3.
A value of 0 represents OPEN, and a value of 1 represents CLOSED.
This value corresponds directly with the Alert When value entered in the configuration page for this sensor.
This object is only applicable if a dry contact sensor is connected to port 3."
::= {dryContact3Adm 2}
-- dry contact 4
dryContact4Status OBJECT-TYPE
SYNTAX INTEGER {open(0), closed(1)}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current integer value of the dry contact sensor connected to port 4.
A value of 0 represents OPEN, and a value of 1 represents CLOSED.
The value corresponds directly with the value displayed on the summary page and the status page for this sensor.
This object is only applicable if a dry contact sensor is connected to port 4."
::= {dryContact4 1}
dryContact4Alert OBJECT-TYPE
SYNTAX INTEGER {off(0), on(1)}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current alert status of the dry contact sensor connected to port 4.
A value of 0 indicates that the sensor has not been set to its alert condition,
while a value of 1 indicates that it has.
This object is only applicable if a dry contact sensor is connected to port 4."
::= {dryContact4 2}
dryContact4Name OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Current name assigned to the dry contact sensor connected to port 4.
This value corresponds directly with the name entered in the configuration page for this sensor.
This object is only applicable if a dry contact sensor is connected to port 4."
::= {dryContact4Adm 1}
dryContact4AlertStatus OBJECT-TYPE
SYNTAX INTEGER {alertWhenOpen(0), alertWhenClosed(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Status which generates an alert condition for the dry contact sensor connected to port 4.
A value of 0 represents OPEN, and a value of 1 represents CLOSED.
This value corresponds directly with the Alert When value entered in the configuration page for this sensor.
This object is only applicable if a dry contact sensor is connected to port 4."
::= {dryContact4Adm 2}
-- water 1
waterStatus OBJECT-TYPE
SYNTAX INTEGER {open(0), closed(1)}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current integer value of the water sensor.
A value of 0 represents OPEN, and a value of 1 represents CLOSED.
The value corresponds directly with the value displayed on the summary page and the status page for this sensor.
This object is only applicable if a water sensor is connected."
::= {waterSensor 1}
waterAlert OBJECT-TYPE
SYNTAX INTEGER {off(0), on(1)}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current alert status of the water sensor.
A value of 0 indicates that the sensor has not been set to its alert condition,
while a value of 1 indicates that it has.
This object is only applicable if a water sensor is connected."
::= {waterSensor 2}
waterName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Current name assigned to the water sensor.
This value corresponds directly with the name entered in the configuration page for this sensor.
This object is only applicable if a water sensor is connected."
::= {waterSensorAdm 1}
waterAlertStatus OBJECT-TYPE
SYNTAX INTEGER {alertWhenOpen(0), alertWhenClosed(1)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Status which generates an alert condition for the water sensor.
A value of 0 represents OPEN, and a value of 1 represents CLOSED.
This value corresponds directly with the Alert When value entered in the configuration page for this sensor.
This object is only applicable if a water sensor is connected."
::= {waterSensorAdm 2}
-- host system
sysName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System node name.
This value corresponds directly with the Node Name field on the General configuration page under the ADMINISTRATION menu."
::= {hostSystem 1}
sysLocation OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System node location.
his value corresponds directly with the Node Location field on the General configuration page under the ADMINISTRATION menu."
::= {hostSystem 2}
sysIP OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System IP address.
This value corresponds directly with the IP address assigned to the ENVIROMUX-MINI on the Network configuration page under the ADMINISTRATION menu."
::= {hostSystem 3}
sysMask OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System Subnet Mask.
This value corresponds directly with the Subnet Mask assigned to the ENVIROMUX-MINI on the Network configuration page under the ADMINISTRATION menu."
::= {hostSystem 4}
sysGateway OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System Default Gateway.
This value corresponds directly with the Default Gateway assigned to the ENVIROMUX-MINI on the Network configuration page under the ADMINISTRATION menu."
::= {hostSystem 5}
sysDNS OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System DNS server.
This value corresponds directly with the DNS server assigned to the ENVIROMUX-MINI on the Network configuration page under the ADMINISTRATION menu."
::= {hostSystem 6}
-- traps
temperatureSensor1Trap NOTIFICATION-TYPE
STATUS current
DESCRIPTION "Trap for alert from temperature sensor connected to port 1. Received if this sensor is configured to send SNMP traps using the Configuration page, and SNMP is enabled on the Network configuration page under the ADMINISTRATION menu."
::= { envTraps 1 }
temperatureSensor2Trap NOTIFICATION-TYPE
STATUS current
DESCRIPTION "Trap for alert from temperature sensor connected to port 2. Received if this sensor is configured to send SNMP traps using the Configuration page, and SNMP is enabled on the Network configuration page under the ADMINISTRATION menu."
::= { envTraps 2 }
humiditySensor1Trap NOTIFICATION-TYPE
STATUS current
DESCRIPTION "Trap for alert from humidity sensor connected to port 1. Received if this sensor is configured to send SNMP traps using the Configuration page, and SNMP is enabled on the Network configuration page under the ADMINISTRATION menu."
::= { envTraps 3 }
humiditySensor2Trap NOTIFICATION-TYPE
STATUS current
DESCRIPTION "Trap for alert from humidity sensor connected to port 2. Received if this sensor is configured to send SNMP traps using the Configuration page, and SNMP is enabled on the Network configuration page under the ADMINISTRATION menu."
::= { envTraps 4 }
dryContactSensor1Trap NOTIFICATION-TYPE
STATUS current
DESCRIPTION "Trap for alert from dry contact sensor connected to port 1. Received if this sensor is configured to send SNMP traps using the Configuration page, and SNMP is enabled on the Network configuration page under the ADMINISTRATION menu."
::= { envTraps 5 }
dryContactSensor2Trap NOTIFICATION-TYPE
STATUS current
DESCRIPTION "Trap for alert from dry contact sensor connected to port 2. Received if this sensor is configured to send SNMP traps using the Configuration page, and SNMP is enabled on the Network configuration page under the ADMINISTRATION menu."
::= { envTraps 6 }
dryContactSensor3Trap NOTIFICATION-TYPE
STATUS current
DESCRIPTION "Trap for alert from dry contact sensor connected to port 3. Received if this sensor is configured to send SNMP traps using the Configuration page, and SNMP is enabled on the Network configuration page under the ADMINISTRATION menu."
::= { envTraps 7 }
dryContactSensor4Trap NOTIFICATION-TYPE
STATUS current
DESCRIPTION "Trap for alert from dry contact sensor connected to port 4. Received if this sensor is configured to send SNMP traps using the Configuration page, and SNMP is enabled on the Network configuration page under the ADMINISTRATION menu."
::= { envTraps 8 }
waterSensor1Trap NOTIFICATION-TYPE
STATUS current
DESCRIPTION "Trap for alert from water sensor. Received if this sensor is configured to send SNMP traps using the Configuration page, and SNMP is enabled on the Network configuration page under the ADMINISTRATION menu."
::= { envTraps 9 }
temperatureSensor1RetTrap NOTIFICATION-TYPE
STATUS current
DESCRIPTION "Trap for return from alert from temperature sensor connected to port 1. Received if this sensor is configured to send SNMP traps using the Configuration page, and SNMP is enabled on the Network configuration page under the ADMINISTRATION menu."
::= { envTraps 11 }
temperatureSensor2RetTrap NOTIFICATION-TYPE
STATUS current
DESCRIPTION "Trap for return from alert from temperature sensor connected to port 2. Received if this sensor is configured to send SNMP traps using the Configuration page, and SNMP is enabled on the Network configuration page under the ADMINISTRATION menu."
::= { envTraps 12 }
humiditySensor1RetTrap NOTIFICATION-TYPE
STATUS current
DESCRIPTION "Trap for return from alert from humidity sensor connected to port 1. Received if this sensor is configured to send SNMP traps using the Configuration page, and SNMP is enabled on the Network configuration page under the ADMINISTRATION menu."
::= { envTraps 13 }
humiditySensor2RetTrap NOTIFICATION-TYPE
STATUS current
DESCRIPTION "Trap for return from alert from humidity sensor connected to port 2. Received if this sensor is configured to send SNMP traps using the Configuration page, and SNMP is enabled on the Network configuration page under the ADMINISTRATION menu."
::= { envTraps 14 }
dryContactSensor1RetTrap NOTIFICATION-TYPE
STATUS current
DESCRIPTION "Trap for return from alert from dry contact sensor connected to port 1. Received if this sensor is configured to send SNMP traps using the Configuration page, and SNMP is enabled on the Network configuration page under the ADMINISTRATION menu."
::= { envTraps 15 }
dryContactSensor2RetTrap NOTIFICATION-TYPE
STATUS current
DESCRIPTION "Trap for return from alert from dry contact sensor connected to port 2. Received if this sensor is configured to send SNMP traps using the Configuration page, and SNMP is enabled on the Network configuration page under the ADMINISTRATION menu."
::= { envTraps 16 }
dryContactSensor3RetTrap NOTIFICATION-TYPE
STATUS current
DESCRIPTION "Trap for return from alert from dry contact sensor connected to port 3. Received if this sensor is configured to send SNMP traps using the Configuration page, and SNMP is enabled on the Network configuration page under the ADMINISTRATION menu."
::= { envTraps 17 }
dryContactSensor4RetTrap NOTIFICATION-TYPE
STATUS current
DESCRIPTION "Trap for return from alert from dry contact sensor connected to port 4. Received if this sensor is configured to send SNMP traps using the Configuration page, and SNMP is enabled on the Network configuration page under the ADMINISTRATION menu."
::= { envTraps 18 }
waterSensor1RetTrap NOTIFICATION-TYPE
STATUS current
DESCRIPTION "Trap for return from alert from water sensor. Received if this sensor is configured to send SNMP traps using the Configuration page, and SNMP is enabled on the Network configuration page under the ADMINISTRATION menu."
::= { envTraps 19 }
logTrap NOTIFICATION-TYPE
STATUS current
DESCRIPTION "Trap generated when a log entry is created. Received if log entries are configured to be sent as SNMP traps using the Log Methods page, and SNMP is enabled on the Network configuration page under the ADMINISTRATION menu."
::= { envTraps 100 }
overflowTrap NOTIFICATION-TYPE
STATUS current
DESCRIPTION "Trap generated when has reached 90% capacity. Received if log overflow alerts are enabled and are configured to be sent as SNMP traps using the Log Overflow page, and SNMP is enabled on the Network configuration page under the ADMINISTRATION menu."
::= { envTraps 101 }
END