606 lines
12 KiB
Plaintext

ND020-MIB DEFINITIONS ::= BEGIN
IMPORTS
MODULE-IDENTITY, OBJECT-TYPE,
Integer32, enterprises, Unsigned32
FROM SNMPv2-SMI;
ndMeter MODULE-IDENTITY
LAST-UPDATED "201104200000Z"
ORGANIZATION "Northern Design (Electronics) Ltd."
CONTACT-INFO
" Northern Design (Electronics) Ltd.
Postal: 228 Bolton Road.
Bradford
BD3 0QW
UK
Tel: +44 1274 729533
E-mail: support@ndmeter.co.uk"
DESCRIPTION
"The Structure of Management Information for
Northern Design Energy Meters"
REVISION "201104200000Z"
DESCRIPTION
"Initial version of this MIB module."
::= { enterprises 37778 } -- assigned by IANA
meterkWhH OBJECT-TYPE
SYNTAX Unsigned32
UNITS "kWh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"kWh High."
::= { ndMeter 7680 }
meterkWhL OBJECT-TYPE
SYNTAX Unsigned32
UNITS "kWh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"kWh Low."
::= { ndMeter 7681 }
meterkVAhH OBJECT-TYPE
SYNTAX Unsigned32
UNITS "kVAh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"kVAh High."
::= { ndMeter 7682 }
meterkVAhL OBJECT-TYPE
SYNTAX Unsigned32
UNITS "kVAh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"kVAh Low."
::= { ndMeter 7683 }
meterkvarhH OBJECT-TYPE
SYNTAX Unsigned32
UNITS "kvarh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"kvarh High."
::= { ndMeter 7684 }
meterkvarhL OBJECT-TYPE
SYNTAX Unsigned32
UNITS "kvarh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"kvarh Low."
::= { ndMeter 7685 }
meterEkWhH OBJECT-TYPE
SYNTAX Unsigned32
UNITS "kvarh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Export kWh High."
::= { ndMeter 7686 }
meterEkWhL OBJECT-TYPE
SYNTAX Unsigned32
UNITS "kvarh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Export kWh Low."
::= { ndMeter 7687 }
meterP1Amps OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase 1 current scaled by Ki."
::= { ndMeter 7688 }
meterP2Amps OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase 2 current scaled by Ki."
::= { ndMeter 7689 }
meterP3Amps OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase 3 current scaled by Ki."
::= { ndMeter 7690 }
meterP1Volts OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Voltsx10"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase 1 voltage scaled by Kvp."
::= { ndMeter 7691 }
meterP2Volts OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Voltsx10"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase 2 voltage scaled by Kvp."
::= { ndMeter 7692 }
meterP3Volts OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Voltsx10"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase 3 voltage scaled by Kvp."
::= { ndMeter 7693 }
meterP1P2Volts OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Voltsx10"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase1 Phase2 voltage scaled by Kvl."
::= { ndMeter 7694 }
meterP2P3Volts OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Voltsx10"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase2 Phase3 voltage scaled by Kvl."
::= { ndMeter 7695 }
meterP3P1Volts OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Voltsx10"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase3 Phase1 voltage scaled by Kvl."
::= { ndMeter 7696 }
meterFreq OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Hz x 10"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Frequency x 10."
::= { ndMeter 7697 }
meterPh1PF OBJECT-TYPE
SYNTAX Integer32
UNITS "PF x 100"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase1 PF x 100."
::= { ndMeter 7698 }
meterPh2PF OBJECT-TYPE
SYNTAX Integer32
UNITS "PF x 100"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase2 PF x 100."
::= { ndMeter 7699 }
meterPh3PF OBJECT-TYPE
SYNTAX Integer32
UNITS "PF x 100"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase3 PF x 100."
::= { ndMeter 7700 }
meterSysPh1PF OBJECT-TYPE
SYNTAX Integer32
UNITS "PF x 100"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System PF x 100."
::= { ndMeter 7701 }
meterP1kW OBJECT-TYPE
SYNTAX Integer32
UNITS "kW"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase 1 kW scaled by Kp."
::= { ndMeter 7702 }
meterP2kW OBJECT-TYPE
SYNTAX Integer32
UNITS "kW"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase 2 kW scaled by Kp."
::= { ndMeter 7703 }
meterP3kW OBJECT-TYPE
SYNTAX Integer32
UNITS "kW"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase 3 kW scaled by Kp."
::= { ndMeter 7704 }
meterSyskW OBJECT-TYPE
SYNTAX Integer32
UNITS "kW"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System kW scaled by Kp."
::= { ndMeter 7705 }
meterP1kVA OBJECT-TYPE
SYNTAX Unsigned32
UNITS "kVA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase 1 kVA scaled by Kp."
::= { ndMeter 7706 }
meterP2kVA OBJECT-TYPE
SYNTAX Unsigned32
UNITS "kVA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase 2 kVA scaled by Kp."
::= { ndMeter 7707 }
meterP3kVA OBJECT-TYPE
SYNTAX Unsigned32
UNITS "kVA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase 3 kVA scaled by Kp."
::= { ndMeter 7708 }
meterSyskVA OBJECT-TYPE
SYNTAX Unsigned32
UNITS "kVA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System kVA scaled by Kp."
::= { ndMeter 7709 }
meterP1kvar OBJECT-TYPE
SYNTAX Integer32
UNITS "kvar"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase 1 kvar scaled by Kp."
::= { ndMeter 7710 }
meterP2kvar OBJECT-TYPE
SYNTAX Integer32
UNITS "kvar"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase 2 kvar scaled by Kp."
::= { ndMeter 7711 }
meterP3kvar OBJECT-TYPE
SYNTAX Integer32
UNITS "kvar"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase 3 kvar scaled by Kp."
::= { ndMeter 7712 }
meterSyskvar OBJECT-TYPE
SYNTAX Integer32
UNITS "kvar"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System kvar scaled by Kp."
::= { ndMeter 7713 }
meterP1AmpsDem OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase 1 current demand scaled by Ki."
::= { ndMeter 7714 }
meterP2AmpsDem OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase 2 current demand scaled by Ki."
::= { ndMeter 7715 }
meterP3AmpsDem OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase 3 current demand scaled by Ki."
::= { ndMeter 7716 }
meterP1VoltsDem OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Voltsx10"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase 1 voltage demand scaled by Kvp."
::= { ndMeter 7717 }
meterP2VoltsDem OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Voltsx10"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase 2 voltage demand scaled by Kvp."
::= { ndMeter 7718 }
meterP3VoltsDem OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Voltsx10"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase 3 voltage demand scaled by Kvp."
::= { ndMeter 7719 }
meterPkP1Amps OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Peak Phase 1 current scaled by Ki."
::= { ndMeter 7720 }
meterPkP2Amps OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Peak Phase 2 current scaled by Ki."
::= { ndMeter 7721 }
meterPkP3Amps OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Peak Phase 3 current scaled by Ki."
::= { ndMeter 7722 }
meterPkP1Volts OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Voltsx10"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Peak Phase 1 voltage scaled by Kvp."
::= { ndMeter 7723 }
meterPkP2Volts OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Voltsx10"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Peak Phase 2 voltage scaled by Kvp."
::= { ndMeter 7724 }
meterPkP3Volts OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Voltsx10"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Peak Phase 3 voltage scaled by Kvp."
::= { ndMeter 7725 }
meterkWDem OBJECT-TYPE
SYNTAX Integer32
UNITS "kW"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"kW Demand scaled with Kp."
::= { ndMeter 7726 }
meterkVADem OBJECT-TYPE
SYNTAX Unsigned32
UNITS "kVA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"kVA Demand scaled with Kp."
::= { ndMeter 7727 }
meterkvarDem OBJECT-TYPE
SYNTAX Integer32
UNITS "kvar"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"kvar Demand scaled with Kp."
::= { ndMeter 7728 }
meterPkkWDem OBJECT-TYPE
SYNTAX Integer32
UNITS "kW"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Peak kW Demand scaled with Kp."
::= { ndMeter 7729 }
meterPkkVADem OBJECT-TYPE
SYNTAX Unsigned32
UNITS "kVA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Peak kVA Demand scaled with Kp."
::= { ndMeter 7730 }
meterPkkvarDem OBJECT-TYPE
SYNTAX Integer32
UNITS "kvar"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Peak kvar Demand scaled with Kp."
::= { ndMeter 7731 }
meterNeuAmps OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Neutral current x 10."
::= { ndMeter 7732 }
meterAmpsScal OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Ki"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Amps scale."
::= { ndMeter 7733 }
meterPhVoltScal OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Kvp"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase Volts scale."
::= { ndMeter 7734 }
meterLLVoltScal OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Kvl"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Line Volts scale."
::= { ndMeter 7735 }
meterPowerScal OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Kp"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Power scale."
::= { ndMeter 7736 }
meterEnergyScal OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Ke"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Energy scale."
::= { ndMeter 7737 }
END