-- MIB file for PoE Ethernet Sensors (PoE-X), created 4-May-2020 by KSL
|
|
-- REVISED
|
|
|
|
POEXMIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
enterprises
|
|
FROM RFC1155-SMI
|
|
OBJECT-TYPE
|
|
FROM RFC-1212
|
|
TRAP-TYPE
|
|
FROM RFC-1215
|
|
DisplayString
|
|
FROM RFC1213-MIB
|
|
TEXTUAL-CONVENTION
|
|
FROM SNMPv2-TC;
|
|
|
|
manufacturer OBJECT IDENTIFIER ::= { enterprises 41542 }
|
|
|
|
POEX OBJECT IDENTIFIER ::= { manufacturer 3 }
|
|
-- DESCRIPTION
|
|
-- "PoE-X Sensor platform supporting the delivery of data from a varity
|
|
-- of sensor type family on an Ethernet connection through the SNMP v1
|
|
-- protocol and others."
|
|
|
|
POEXGatewaySpecificInfo OBJECT IDENTIFIER ::= { POEX 1 }
|
|
-- DESCRIPTION
|
|
-- "The POEX reports certain information specific to the particular
|
|
-- gateway device, which are reported under this hierarchy."
|
|
|
|
--
|
|
-- Gateway-specific section
|
|
--
|
|
|
|
POEXGatewayID OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The serial number identifier of the gateway device assigned and
|
|
programmed by the manufacturer. This will ordinarily be printed
|
|
on a label on the housing of the device."
|
|
::= {POEXGatewaySpecificInfo 1}
|
|
|
|
POEXGatewayFirmwareVerNo OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The version number of the firmware of the gateway device. Note that
|
|
this can change upon a firmware update."
|
|
::= {POEXGatewaySpecificInfo 2}
|
|
|
|
POEXGatewaySensorDeviceCount OBJECT-TYPE
|
|
SYNTAX INTEGER(0..256)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of sensors registered to the gateway, i.e. on its netlist.
|
|
Note that this can change as sensors are added or removed."
|
|
::= {POEXGatewaySpecificInfo 3}
|
|
|
|
POEXGatewayTrapIPAddr OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The configured destination IP address for trap messages from this
|
|
gateway."
|
|
::= {POEXGatewaySpecificInfo 4}
|
|
|
|
POEXGatewaySensorTrapPort OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The configured IP port for trap messages from this gateway."
|
|
::= {POEXGatewaySpecificInfo 5}
|
|
|
|
--
|
|
-- Definitions of sensor-specific informational types
|
|
--
|
|
|
|
POEXSensorID ::= TEXTUAL-CONVENTION
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The serial number identifier of the sensor device assigned and
|
|
programmed by the manufacturer. This will ordinarily be printed
|
|
on a label on the housing of the device."
|
|
SYNTAX Unsigned32
|
|
|
|
POEXSensorRegistrationIndex ::= TEXTUAL-CONVENTION
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index number of a sensor device in a gateway's sensor
|
|
registration list. This is determined by the order in which a set
|
|
of sensors has been registered, but will not change so long as
|
|
the list remains fixed. This is included for legacy applications:
|
|
please consider using the more convenient
|
|
POEXSensorInfoTranslatedFormat and
|
|
POEXSensorInfoBySensorID hierarchies."
|
|
SYNTAX INTEGER(0..255)
|
|
|
|
POEXDatumNo ::= TEXTUAL-CONVENTION
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The datum number of a sequence of data readings from a sensor. The
|
|
range of this type depends upon the number of datums reported by
|
|
a sensor device. Thus, a 3-axis accelerometer sensor might report
|
|
three datums for the X, Y and Z axes, and the datums would range
|
|
from 1 to 3. For a simple temperature sensor reporting one
|
|
reading, this value would always be 1."
|
|
SYNTAX INTEGER(1..8)
|
|
|
|
POEXSensorDeviceType ::= TEXTUAL-CONVENTION
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The textual description of the type of the sensor device."
|
|
SYNTAX OCTET STRING
|
|
|
|
POEXDatumNumber ::= TEXTUAL-CONVENTION
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of a datum in a set of datums comprising a sensor reading.
|
|
For sensors reporting one datum, this will always be one. Otherwise
|
|
it will be a number between 1 and the number of datums reported by
|
|
the particular type of sensor."
|
|
SYNTAX INTEGER
|
|
|
|
POEXSensorDeviceReadingTranslatedValue ::= TEXTUAL-CONVENTION
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The value of a sensor reading, in textual format, translated
|
|
according to sensor and datum types. These formats can include
|
|
integers, fixed-point, and binary values. In several examples:
|
|
a pulse counter might report '12345', a current sensor might report
|
|
'1.43', and a door closed sensor might report 'Yes'."
|
|
SYNTAX OCTET STRING
|
|
|
|
POEXSensorDeviceReadingTranslatedUnits ::= TEXTUAL-CONVENTION
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The units or scale of value of a sensor reading, reported in textual
|
|
format. In several examples: a pulse counter might report 'Count',
|
|
a current sensor might report 'A', and a door sensor might report
|
|
'Closed'."
|
|
SYNTAX OCTET STRING
|
|
|
|
POEXSensorDeviceReadingValuesAll ::= TEXTUAL-CONVENTION
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"All of the datums for the most recent reading of the sensor device,
|
|
separated by commas, in textual format. For example, a report for a
|
|
temperature and humidity sensor might read '20.3, 35' indicating
|
|
20.3 degrees at 35 percent humidity. If only one datum is reported
|
|
by a sensor device, e.g. for a simple temperature sensor, it will be
|
|
reported singly with no commas."
|
|
SYNTAX OCTET STRING
|
|
|
|
POEXSensorDeviceReadingUnitsAll ::= TEXTUAL-CONVENTION
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"All of the units corresponding to the datums for the most recent
|
|
reading of the sensor device, separated by commas, in textual
|
|
format. For example, for a sensor reporting temperature and
|
|
humidity this might read 'degrees C, %RH'"
|
|
SYNTAX OCTET STRING
|
|
|
|
POEXSensorDeviceReadingUntranslated ::= TEXTUAL-CONVENTION
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The untranslated data block received from a sensor, in hexadecimal
|
|
format. This may be used where a translating function isn't yet
|
|
present, and for development purposes. Most users should use the
|
|
translated values delivered in the format of
|
|
POEXSensorDeviceReadingValuesAll."
|
|
SYNTAX OCTET STRING
|
|
|
|
POEXSensorDeviceReadingU32Value ::= TEXTUAL-CONVENTION
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Either a single sensor value of up to 32 bits, or half of a
|
|
64-bit value. Thus where a sensor value is reportable in a
|
|
single Unsigned32, one OID is sufficient to gather that value.
|
|
Where more than 32 bits are needed, the value is reported in two
|
|
successive values of type POEXSensorDeviceReadingU32Value.
|
|
Where a set of datums is reported, those datums are reported
|
|
beginning with the lowest-numbered OID proceeding sequentially
|
|
through the highest. Thus were a sensor to report a single-bit
|
|
value A followed by 32-bit and a 64 bit ones B and C, and where
|
|
OIDS x.10 through x.17 were used for reporting values, the value A
|
|
would be encoded in x.10, B in x.11 and C in x.12 (low-order bits)
|
|
and x.13 (high-order bits). These values are merely converted
|
|
from sensor-specific internal formats to integers, and not beyond
|
|
to human-readable formats.
|
|
Furthermore, where for a sensor datums extend only part-way through
|
|
the available U32Value OIDs, the ones unused may be filled with 0.
|
|
Where an SNMP walk is performed, the gateway may not traverse these
|
|
unused OIDs."
|
|
SYNTAX Unsigned32
|
|
|
|
POEXSensorDeviceReadingAge ::= TEXTUAL-CONVENTION
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The age of the sensor report received most recently from a sensor.
|
|
That time is reported as the number of seconds between the time of
|
|
the sensor report and the time this information is requested."
|
|
SYNTAX Unsigned32
|
|
|
|
POEXSensorDeviceReadingAlarming ::= TEXTUAL-CONVENTION
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Either 'Alarming' or 'Not alarming'. A device will report an alarm
|
|
if it is programmed with a threshold found to be exceeded. Examples:
|
|
a temperature sensor for a refrigeration unit can be programmed to
|
|
alarm if the measured temperature rises above a threshold, and
|
|
a door sensor might alarm if a security door is opened."
|
|
SYNTAX OCTET STRING
|
|
|
|
--
|
|
-- Sensor-specific section, translated format
|
|
--
|
|
|
|
POEXSensorInfoTranslatedFormatTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF POEXSensorInfoTranslatedFormatEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The (conceptual) table containing sensor-specific information in an
|
|
easy-to-use translated string format, indexed by sensor ID is reported
|
|
under this hierarchy. Sensor data is translated by the gateway from
|
|
sensor-internal format to human-readable and scriptable values. Use of
|
|
this format is preferred for most users. The gateway will report the
|
|
most current information received from sensors, according to their
|
|
programmed reporting period or heartbeat. When using this section
|
|
through getRequests or getNextRequests, successive polling is required
|
|
to keep sensor data current. This table can change as sensors are
|
|
added or removed. If queried, this OID will return the number of rows
|
|
in the table, which is the number of sensors registered to this gateway."
|
|
::= { POEX 2 }
|
|
|
|
-- Table portion consisting of non-datum-specific info
|
|
|
|
POEXSensorInfoTranslatedFormatEntry OBJECT-TYPE
|
|
SYNTAX POEXSensorInfoTranslatedFormatEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry (conceptual row) in the Translated Format Table containing
|
|
the latest sensor state for a single sensor."
|
|
INDEX { POEXSensorInfoTranslatedFormatSensorDeviceID }
|
|
::= { POEXSensorInfoTranslatedFormatTable 1 }
|
|
|
|
POEXSensorInfoTranslatedFormatEntry ::= SEQUENCE {
|
|
POEXSensorInfoTranslatedFormatSensorDeviceID POEXSensorID,
|
|
POEXSensorInfoTranslatedFormatSensorDeviceType POEXSensorDeviceType,
|
|
POEXSensorInfoTranslatedFormatSensorDeviceReadingValuesAll POEXSensorDeviceReadingValuesAll,
|
|
POEXSensorInfoTranslatedFormatSensorDeviceReadingUnitsAll POEXSensorDeviceReadingUnitsAll,
|
|
POEXSensorInfoTranslatedFormatSensorDeviceRptUT POEXSensorDeviceReadingUntranslated,
|
|
POEXSensorInfoTranslatedFormatSensorDeviceReadingTime DisplayString,
|
|
POEXSensorInfoTranslatedFormatSensorDeviceReadingAge POEXSensorDeviceReadingAge,
|
|
POEXSensorInfoTranslatedFormatSensorDeviceTypeNo DisplayString,
|
|
POEXSensorInfoTranslatedFormatSensorDeviceRFStrength DisplayString,
|
|
POEXSensorInfoTranslatedFormatSensorDeviceActive DisplayString,
|
|
POEXSensorInfoTranslatedFormatSensorDeviceAlarming POEXSensorDeviceReadingAlarming,
|
|
POEXSensorInfoTranslatedFormatSensorDeviceVoltage DisplayString,
|
|
POEXSensorInfoTranslatedFormatSensorDeviceWDIndexNo DisplayString
|
|
}
|
|
|
|
POEXSensorInfoTranslatedFormatSensorDeviceID OBJECT-TYPE
|
|
SYNTAX POEXSensorID
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The serial number identifier of the sensor device assigned and
|
|
programmed by the manufacturer. This will ordinarily be printed
|
|
on a label on the housing of the device."
|
|
::= { POEXSensorInfoTranslatedFormatEntry 1 }
|
|
|
|
POEXSensorInfoTranslatedFormatSensorDeviceType OBJECT-TYPE
|
|
SYNTAX POEXSensorDeviceType
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The textual description of the type of the sensor device."
|
|
::= {POEXSensorInfoTranslatedFormatEntry 2 }
|
|
|
|
POEXSensorInfoTranslatedFormatSensorDeviceReadingValuesAll OBJECT-TYPE
|
|
SYNTAX POEXSensorDeviceReadingValuesAll
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"All of the datums for the most recent reading of the sensor device,
|
|
separated by commas, in textual format. For example, a report for a
|
|
temperature and humidity sensor might read '20.3, 35' indicating
|
|
20.3 degrees at 35 percent humidity. If only one datum is reported
|
|
by a sensor device, e.g. for a simple temperature sensor, it will be
|
|
reported singly with no commas. The use of this OID is recommended
|
|
for most users, rather than the single value ones, because all values
|
|
can be retrieved atomically from a sensor in one SNMP request."
|
|
::= {POEXSensorInfoTranslatedFormatEntry 3 }
|
|
|
|
POEXSensorInfoTranslatedFormatSensorDeviceReadingUnitsAll OBJECT-TYPE
|
|
SYNTAX POEXSensorDeviceReadingUnitsAll
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"All of the units corresponding to the datums for the most recent
|
|
reading of the sensor device, separated by commas, in textual
|
|
format. For example, for a sensor reporting temperature and
|
|
humidity this might read 'degrees C, %RH'"
|
|
::= {POEXSensorInfoTranslatedFormatEntry 4 }
|
|
|
|
POEXSensorInfoTranslatedFormatSensorDeviceRptUT OBJECT-TYPE
|
|
SYNTAX POEXSensorDeviceReadingUntranslated
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The untranslated data block received from a sensor, in hexadecimal
|
|
format. This may be used where a translating function isn't yet
|
|
present, and for development purposes. Most users should use the
|
|
translated values delivered in the format of
|
|
POEXSensorDeviceReadingValuesAll."
|
|
::= {POEXSensorInfoTranslatedFormatEntry 5 }
|
|
|
|
POEXSensorInfoTranslatedFormatSensorDeviceReadingTime OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The time of the sensor report received most recently from a sensor.
|
|
That time is reported as the number of seconds elapsed since the epoch
|
|
of the gateway, which is presently Jan. 1, 2010."
|
|
::= {POEXSensorInfoTranslatedFormatEntry 6 }
|
|
|
|
POEXSensorInfoTranslatedFormatSensorDeviceReadingAge OBJECT-TYPE
|
|
SYNTAX POEXSensorDeviceReadingAge
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The age of the sensor report received most recently from a sensor.
|
|
That time is reported as the number of seconds between the time of
|
|
the sensor report and the time this information is requested."
|
|
::= {POEXSensorInfoTranslatedFormatEntry 7 }
|
|
|
|
POEXSensorInfoTranslatedFormatSensorDeviceTypeNo OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The manufacturer's type number that identifies the kind of sensor."
|
|
::= {POEXSensorInfoTranslatedFormatEntry 8 }
|
|
|
|
POEXSensorInfoTranslatedFormatSensorDeviceRFStrength OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The signal strength, in percent, of the radio link between the gateway
|
|
and the particular sensor, as measured at the time of the most recent
|
|
sensor report."
|
|
::= {POEXSensorInfoTranslatedFormatEntry 9 }
|
|
|
|
POEXSensorInfoTranslatedFormatSensorDeviceActive OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Either 'Active' or '' (an empty string). A sensor will be reported
|
|
active if it has recently communicated with the gateway since the last
|
|
reboot. If a sensor device does not show active, it is likely because
|
|
(1) the sensor lacks a power source, (2) the sensor is not in
|
|
proximity to the gateway, or (3) the gateway has recently been
|
|
powered on, and the sensor hasn't yet communicated."
|
|
::= {POEXSensorInfoTranslatedFormatEntry 10 }
|
|
|
|
POEXSensorInfoTranslatedFormatSensorDeviceAlarming OBJECT-TYPE
|
|
SYNTAX POEXSensorDeviceReadingAlarming
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Either 'Alarming' or 'Not alarming'. A device will report an alarm
|
|
if it is programmed with a threshold found to be exceeded. Examples:
|
|
a temperature sensor for a refrigeration unit can be programmed to
|
|
alarm if the measured temperature rises above a threshold, and
|
|
a door sensor might alarm if a security door is opened."
|
|
::= {POEXSensorInfoTranslatedFormatEntry 11 }
|
|
|
|
POEXSensorInfoTranslatedFormatSensorDeviceVoltage OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The value of the voltage of the supply powering a sensor device.
|
|
Ordinarily this will report the voltage at the battery terminals of
|
|
a sensor. It is provided mainly so batteries can be changed when
|
|
depleted."
|
|
::= {POEXSensorInfoTranslatedFormatEntry 12 }
|
|
|
|
POEXSensorInfoTranslatedFormatSensorDeviceWDIndexNo OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index number of the sensor in the gateway's sensor registration
|
|
table. This is the number used in referencing the sensor in the
|
|
POEXSensorInformationBySensorRegisOrder
|
|
hierarchy."
|
|
::= {POEXSensorInfoTranslatedFormatEntry 13 }
|
|
|
|
-- Table portion consisting of datum-specific info (single values and units addressed by device ID and datum)
|
|
|
|
POEXSensorInfoTranslatedFormatByDatumNumberEntry OBJECT-TYPE
|
|
SYNTAX POEXSensorInfoTranslatedFormatByDatumNumberEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry (conceptual row) in the Translated Format Table containing
|
|
the sensor datums, indexed by a sensor ID and datum number."
|
|
INDEX { POEXSensorInfoTranslatedFormatSensorDeviceID,
|
|
POEXSensorInfoTranslatedFormatByDatumNumberDatumNumber }
|
|
::= { POEXSensorInfoTranslatedFormatTable 2 }
|
|
|
|
POEXSensorInfoTranslatedFormatByDatumNumberEntry ::= SEQUENCE {
|
|
POEXSensorInfoTranslatedFormatByDatumNumberSensorDeviceID POEXSensorID,
|
|
POEXSensorInfoTranslatedFormatByDatumNumberDatumNumber POEXDatumNumber,
|
|
POEXSensorInfoTranslatedFormatByDatumNumberReadingValue POEXSensorDeviceReadingTranslatedValue,
|
|
POEXSensorInfoTranslatedFormatByDatumNumberReadingUnits POEXSensorDeviceReadingTranslatedUnits
|
|
}
|
|
|
|
POEXSensorInfoTranslatedFormatByDatumNumberSensorDeviceID OBJECT-TYPE
|
|
SYNTAX POEXSensorID
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The serial number identifier of the sensor device assigned and
|
|
programmed by the manufacturer. This will ordinarily be printed
|
|
on a label on the housing of the device."
|
|
::= { POEXSensorInfoTranslatedFormatByDatumNumberEntry 1 }
|
|
|
|
POEXSensorInfoTranslatedFormatByDatumNumberDatumNumber OBJECT-TYPE
|
|
SYNTAX POEXDatumNumber
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of a datum in a set of datums comprising a sensor reading.
|
|
For sensors reporting one datum, this will always be one. Otherwise
|
|
it will be a number between 1 and the number of datums reported by
|
|
the particular type of sensor."
|
|
::= { POEXSensorInfoTranslatedFormatByDatumNumberEntry 2 }
|
|
|
|
POEXSensorInfoTranslatedFormatByDatumNumberReadingValue OBJECT-TYPE
|
|
SYNTAX POEXSensorDeviceReadingTranslatedValue
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The value of a sensor reading, in textual format, translated
|
|
according to sensor and datum types. These formats can include
|
|
integers, fixed-point, and binary values. In several examples:
|
|
a pulse counter might report '12345', a current sensor might report
|
|
'1.43', and a door sensor might report 'closed'."
|
|
::= { POEXSensorInfoTranslatedFormatByDatumNumberEntry 3 }
|
|
|
|
POEXSensorInfoTranslatedFormatByDatumNumberReadingUnits OBJECT-TYPE
|
|
SYNTAX POEXSensorDeviceReadingTranslatedUnits
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The units or scale of value of a sensor reading, reported in textual
|
|
format. In several examples: a pulse counter might report 'Count',
|
|
a current sensor might report 'A', and a door sensor might report
|
|
'Closed'."
|
|
::= { POEXSensorInfoTranslatedFormatByDatumNumberEntry 4 }
|
|
|
|
--
|
|
-- Sensor-specific section, untranslated legacy format, by sensor ID
|
|
--
|
|
|
|
POEXSensorInfoBySensorIDTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF POEXSensorInfoBySensorIDSensorEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The (conceptual) table containing sensor information in a legacy
|
|
untranslated numeric format, addressed by sensor ID. This is provided
|
|
for users who need a precise match of the format of the older EGW1
|
|
platform. The gateway will report the most current information received
|
|
from sensors, according to their programmed reporting period or
|
|
heartbeat. A more convenient format to new users is available under
|
|
the POEXSensorInfoTranslatedFormat. If queried, this
|
|
OID will return the number of rows in the table, which is the number
|
|
of sensors registered to this gateway."
|
|
::= { POEX 3 }
|
|
|
|
POEXSensorInfoBySensorIDEntry OBJECT-TYPE
|
|
SYNTAX POEXSensorInfoBySensorIDEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry (conceptual row) in the untranslated by-sensor-ID-order
|
|
table containing the latest sensor state for a single sensor."
|
|
INDEX { POEXSensorInfoBySensorIDSensorDeviceID }
|
|
::= { POEXSensorInfoBySensorIDTable 1 }
|
|
|
|
POEXSensorInfoBySensorIDEntry ::= SEQUENCE {
|
|
POEXSensorInfoBySensorIDSensorDeviceID Unsigned32,
|
|
POEXSensorInfoBySensorIDSensorDeviceWDIndexNo INTEGER,
|
|
POEXSensorInfoBySensorIDSensorDeviceTypeNo INTEGER,
|
|
POEXSensorInfoBySensorIDSensorDeviceReadingAge Unsigned32,
|
|
POEXSensorInfoBySensorIDSensorDeviceActive INTEGER,
|
|
POEXSensorInfoBySensorIDSensorDeviceAlarming INTEGER,
|
|
POEXSensorInfoBySensorIDSensorDeviceVoltage INTEGER,
|
|
POEXSensorInfoBySensorIDSensorDeviceRFStrength INTEGER,
|
|
POEXSensorInfoBySensorIDSensorDeviceRptUT DisplayString,
|
|
POEXSensorInfoBySensorIDSensorDeviceReadingValue1 POEXSensorDeviceReadingU32Value,
|
|
POEXSensorInfoBySensorIDSensorDeviceReadingValue2 POEXSensorDeviceReadingU32Value,
|
|
POEXSensorInfoBySensorIDSensorDeviceReadingValue3 POEXSensorDeviceReadingU32Value,
|
|
POEXSensorInfoBySensorIDSensorDeviceReadingValue4 POEXSensorDeviceReadingU32Value,
|
|
POEXSensorInfoBySensorIDSensorDeviceReadingValue5 POEXSensorDeviceReadingU32Value,
|
|
POEXSensorInfoBySensorIDSensorDeviceReadingValue6 POEXSensorDeviceReadingU32Value,
|
|
POEXSensorInfoBySensorIDSensorDeviceReadingValue7 POEXSensorDeviceReadingU32Value,
|
|
POEXSensorInfoBySensorIDSensorDeviceReadingValue8 POEXSensorDeviceReadingU32Value
|
|
}
|
|
|
|
POEXSensorInfoBySensorIDSensorDeviceID OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The serial number identifier of the sensor device assigned and
|
|
programmed by the manufacturer. This will ordinarily be printed
|
|
on a label on the housing of the device."
|
|
INDEX { POEXSensorID }
|
|
::= {POEXSensorInfoBySensorIDEntry 1 }
|
|
|
|
POEXSensorInfoBySensorIDSensorDeviceWDIndexNo OBJECT-TYPE
|
|
SYNTAX INTEGER(0..255)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index number of the sensor in the gateway's sensor registration
|
|
table. This is the number used in referencing the sensor in the
|
|
POEXSensorInfoBySensorRegisOrder
|
|
hierarchy."
|
|
INDEX { POEXSensorID }
|
|
::= {POEXSensorInfoBySensorIDEntry 2 }
|
|
|
|
POEXSensorInfoBySensorIDSensorDeviceTypeNo OBJECT-TYPE
|
|
SYNTAX INTEGER(1..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The manufacturer's type number that identifies the kind of sensor."
|
|
INDEX { POEXSensorID }
|
|
::= {POEXSensorInfoBySensorIDEntry 3 }
|
|
|
|
POEXSensorInfoBySensorIDSensorDeviceReadingAge OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The age of the sensor report received most recently from a sensor.
|
|
That time is reported as the number of seconds between the time of
|
|
the sensor report and the time this information is requested."
|
|
INDEX { POEXSensorID }
|
|
::= {POEXSensorInfoBySensorIDEntry 4 }
|
|
|
|
POEXSensorInfoBySensorIDSensorDeviceActive OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Either 1 (active) or 0 (inactive). A sensor will be reported active
|
|
if it has recently communicated with the gateway since the last
|
|
reboot. If a sensor device does not show active, it is likely because
|
|
(1) the sensor lacks a power source, (2) the sensor is not in
|
|
proximity to the gateway, or (3) the gateway has recently been
|
|
powered on, and the sensor hasn't yet communicated."
|
|
INDEX { POEXSensorID }
|
|
::= {POEXSensorInfoBySensorIDEntry 5 }
|
|
|
|
POEXSensorInfoBySensorIDSensorDeviceAlarming OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Either 1 (alarming) or 0 (not alarming)'. A device will report an
|
|
alarm if it is programmed with a threshold found to be exceeded.
|
|
Examples: a temperature sensor for a refrigeration unit can be
|
|
programmed to alarm if the measured temperature rises above a
|
|
threshold, and a door sensor might alarm if a security door is opened."
|
|
INDEX { POEXSensorID }
|
|
::= {POEXSensorInfoBySensorIDEntry 6 }
|
|
|
|
POEXSensorInfoBySensorIDSensorDeviceVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER(0..255)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A value representing the voltage of the supply powering a sensor
|
|
device. Ordinarily this will report the voltage at the battery
|
|
terminals of a sensor. It is provided mainly so batteries can be
|
|
changed when depleted. The formula for calculating the voltage from
|
|
this number is: voltage=(150 + v) / 10.0."
|
|
INDEX { POEXSensorID }
|
|
::= {POEXSensorInfoBySensorIDEntry 7 }
|
|
|
|
POEXSensorInfoBySensorIDSensorDeviceRFStrength OBJECT-TYPE
|
|
SYNTAX INTEGER(-128..127)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The signal strength, in percent, of the radio link between the gateway
|
|
and the particular sensor, as measured at the time of the most recent
|
|
sensor report."
|
|
INDEX { POEXSensorID }
|
|
::= {POEXSensorInfoBySensorIDEntry 8 }
|
|
|
|
POEXSensorInfoBySensorIDSensorDeviceRptUT OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The untranslated data block received from a sensor, in hexadecimal
|
|
format. This may be used where a translating function isn't yet
|
|
present, and for development purposes. Most users should use the
|
|
translated values delivered in the format of
|
|
POEXSensorDeviceReadingValuesAll."
|
|
INDEX { POEXSensorID }
|
|
::= {POEXSensorInfoBySensorIDEntry 9 }
|
|
|
|
POEXSensorInfoBySensorIDSensorDeviceReadingValue1 OBJECT-TYPE
|
|
SYNTAX POEXSensorDeviceReadingU32Value
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The value of a single sensor reading, or one half of a 64-bit reading,
|
|
in integer format, not translated to human-readable form. See
|
|
POEXSensorDeviceReadingU32Value for further explanation."
|
|
INDEX { POEXSensorID }
|
|
::= {POEXSensorInfoBySensorIDEntry 10 }
|
|
|
|
POEXSensorInfoBySensorIDSensorDeviceReadingValue2 OBJECT-TYPE
|
|
SYNTAX POEXSensorDeviceReadingU32Value
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The value of a single sensor reading, or one half of a 64-bit reading,
|
|
in integer format, not translated to human-readable form. See
|
|
POEXSensorDeviceReadingU32Value for further explanation."
|
|
INDEX { POEXSensorID }
|
|
::= {POEXSensorInfoBySensorIDEntry 11 }
|
|
|
|
POEXSensorInfoBySensorIDSensorDeviceReadingValue3 OBJECT-TYPE
|
|
SYNTAX POEXSensorDeviceReadingU32Value
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The value of a single sensor reading, or one half of a 64-bit reading,
|
|
in integer format, not translated to human-readable form. See
|
|
POEXSensorDeviceReadingU32Value for further explanation."
|
|
INDEX { POEXSensorID }
|
|
::= {POEXSensorInfoBySensorIDEntry 12 }
|
|
|
|
POEXSensorInfoBySensorIDSensorDeviceReadingValue4 OBJECT-TYPE
|
|
SYNTAX POEXSensorDeviceReadingU32Value
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The value of a single sensor reading, or one half of a 64-bit reading,
|
|
in integer format, not translated to human-readable form. See
|
|
POEXSensorDeviceReadingU32Value for further explanation."
|
|
INDEX { POEXSensorID }
|
|
::= {POEXSensorInfoBySensorIDEntry 13 }
|
|
|
|
POEXSensorInfoBySensorIDSensorDeviceReadingValue5 OBJECT-TYPE
|
|
SYNTAX POEXSensorDeviceReadingU32Value
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The value of a single sensor reading, or one half of a 64-bit reading,
|
|
in integer format, not translated to human-readable form. See
|
|
POEXSensorDeviceReadingU32Value for further explanation."
|
|
INDEX { POEXSensorID }
|
|
::= {POEXSensorInfoBySensorIDEntry 14 }
|
|
|
|
POEXSensorInfoBySensorIDSensorDeviceReadingValue6 OBJECT-TYPE
|
|
SYNTAX POEXSensorDeviceReadingU32Value
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The value of a single sensor reading, or one half of a 64-bit reading,
|
|
in integer format, not translated to human-readable form. See
|
|
POEXSensorDeviceReadingU32Value for further explanation."
|
|
INDEX { POEXSensorID }
|
|
::= {POEXSensorInfoBySensorIDEntry 15 }
|
|
|
|
POEXSensorInfoBySensorIDSensorDeviceReadingValue7 OBJECT-TYPE
|
|
SYNTAX POEXSensorDeviceReadingU32Value
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The value of a single sensor reading, or one half of a 64-bit reading,
|
|
in integer format, not translated to human-readable form. See
|
|
POEXSensorDeviceReadingU32Value for further explanation."
|
|
INDEX { POEXSensorID }
|
|
::= {POEXSensorInfoBySensorIDEntry 16 }
|
|
|
|
POEXSensorInfoBySensorIDSensorDeviceReadingValue8 OBJECT-TYPE
|
|
SYNTAX POEXSensorDeviceReadingU32Value
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The value of a single sensor reading, or one half of a 64-bit reading,
|
|
in integer format, not translated to human-readable form. See
|
|
POEXSensorDeviceReadingU32Value for further explanation."
|
|
INDEX { POEXSensorID }
|
|
::= {POEXSensorInfoBySensorIDEntry 17 }
|
|
|
|
--
|
|
-- Sensor-specific section, untranslated legacy format, by registration order
|
|
--
|
|
|
|
POEXSensorInfoBySensorRegisOrderTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF POEXSensorInfoBySensorRegisOrderSensorEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The (conceptual) table containing an untranslated numeric format,
|
|
addressed by sensor registration order starting at 1 and ascending by
|
|
one, in a legacy integer format. This is provided for users who need a
|
|
precise match of the format and order of the older EGW1 platform.
|
|
The gateway will report the most current information received from
|
|
sensors, according to their programmed reporting period or heartbeat.
|
|
A more convenient format to new users is available under
|
|
the POEXSensorInfoTranslatedFormat. If queried, this
|
|
OID will return the number of rows in the table, which is the number
|
|
of sensors registered to this gateway."
|
|
::= { POEX 4 }
|
|
|
|
POEXSensorInfoBySensorRegisOrderEntry OBJECT-TYPE
|
|
SYNTAX POEXSensorInfoBySensorRegisOrderEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry (conceptual row) in the untranslated by-registration-order
|
|
table containing the latest sensor state for a single sensor."
|
|
INDEX { POEXSensorInfoBySensorRegisOrderSensDevID }
|
|
::= { POEXSensorInfoBySensorRegisOrderTable 1 }
|
|
|
|
POEXSensorInfoBySensorRegisOrderEntry ::= SEQUENCE {
|
|
POEXSensorInfoBySensorRegisOrderSensorDeviceID Unsigned32,
|
|
POEXSensorInfoBySensorRegisOrderSensorDeviceWDIndexNo INTEGER,
|
|
POEXSensorInfoBySensorRegisOrderSensorDeviceTypeNo INTEGER,
|
|
POEXSensorInfoBySensorRegisOrderSensorDeviceReadingAge Unsigned32,
|
|
POEXSensorInfoBySensorRegisOrderSensorDeviceActive INTEGER,
|
|
POEXSensorInfoBySensorRegisOrderSensorDeviceAlarming INTEGER,
|
|
POEXSensorInfoBySensorRegisOrderSensorDeviceVoltage INTEGER,
|
|
POEXSensorInfoBySensorRegisOrderSensorDeviceRFStrength INTEGER,
|
|
POEXSensorInfoBySensorRegisOrderSensorDeviceRptUT DisplayString,
|
|
POEXSensorInfoBySensorRegisOrderSensorDeviceReadingValue1 POEXSensorDeviceReadingU32Value,
|
|
POEXSensorInfoBySensorRegisOrderSensorDeviceReadingValue2 POEXSensorDeviceReadingU32Value,
|
|
POEXSensorInfoBySensorRegisOrderSensorDeviceReadingValue3 POEXSensorDeviceReadingU32Value,
|
|
POEXSensorInfoBySensorRegisOrderSensorDeviceReadingValue4 POEXSensorDeviceReadingU32Value,
|
|
POEXSensorInfoBySensorRegisOrderSensorDeviceReadingValue5 POEXSensorDeviceReadingU32Value,
|
|
POEXSensorInfoBySensorRegisOrderSensorDeviceReadingValue6 POEXSensorDeviceReadingU32Value,
|
|
POEXSensorInfoBySensorRegisOrderSensorDeviceReadingValue7 POEXSensorDeviceReadingU32Value,
|
|
POEXSensorInfoBySensorRegisOrderSensorDeviceReadingValue8 POEXSensorDeviceReadingU32Value
|
|
}
|
|
|
|
POEXSensorInfoBySensorRegisOrderSensDevID OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The serial number identifier of the sensor device assigned and
|
|
programmed by the manufacturer. This will ordinarily be printed
|
|
on a label on the housing of the device."
|
|
INDEX { POEXSensorRegistrationIndex }
|
|
::= {POEXSensorInfoBySensorRegisOrderEntry 1 }
|
|
|
|
POEXSensorInfoBySensorRegisOrderSensDevWDIndexNo OBJECT-TYPE
|
|
SYNTAX INTEGER(0..255)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index number of the sensor in the gateway's sensor registration
|
|
table. This is the number used in referencing the sensor in the
|
|
POEXSensorInfoBySensorRegisOrder hierarchy."
|
|
INDEX { POEXSensorRegistrationIndex }
|
|
::= {POEXSensorInfoBySensorRegisOrderEntry 2 }
|
|
|
|
POEXSensorInfoBySensorRegisOrderSensDevTypeNo OBJECT-TYPE
|
|
SYNTAX INTEGER(1..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The manufacturer's type number that identifies the kind of sensor."
|
|
INDEX { POEXSensorRegistrationIndex }
|
|
::= {POEXSensorInfoBySensorRegisOrderEntry 3 }
|
|
|
|
POEXSensorInfoBySensorRegisOrderSensDevReadingAge OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The age of the sensor report received most recently from a sensor.
|
|
That time is reported as the number of seconds between the time of
|
|
the sensor report and the time this information is requested."
|
|
INDEX { POEXSensorRegistrationIndex }
|
|
::= {POEXSensorInfoBySensorRegisOrderEntry 4 }
|
|
|
|
POEXSensorInfoBySensorRegisOrderSensDevActive OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Either 1 (active) or 0 (inactive). A sensor will be reported active
|
|
if it has recently communicated with the gateway since the last
|
|
reboot. If a sensor device does not show active, it is likely because
|
|
(1) the sensor lacks a power source, (2) the sensor is not in
|
|
proximity to the gateway, or (3) the gateway has recently been
|
|
powered on, and the sensor hasn't yet communicated."
|
|
INDEX { POEXSensorRegistrationIndex }
|
|
::= {POEXSensorInfoBySensorRegisOrderEntry 5 }
|
|
|
|
POEXSensorInfoBySensorRegisOrderSensDevAlarming OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Either 1 (alarming) or 0 (not alarming)'. A device will report an
|
|
alarm if it is programmed with a threshold found to be exceeded.
|
|
Examples: a temperature sensor for a refrigeration unit can be
|
|
programmed to alarm if the measured temperature rises above a
|
|
threshold, and a door sensor might alarm if a security door is opened."
|
|
INDEX { POEXSensorRegistrationIndex }
|
|
::= {POEXSensorInfoBySensorRegisOrderEntry 6 }
|
|
|
|
POEXSensorInfoBySensorRegisOrderSensDevVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER(0..255)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A value representing the voltage of the supply powering a sensor
|
|
device. Ordinarily this will report the voltage at the battery
|
|
terminals of a sensor. It is provided mainly so batteries can be
|
|
changed when depleted. The formula for calculating the voltage from
|
|
this number is: voltage=(150 + v) / 10.0."
|
|
INDEX { POEXSensorRegistrationIndex }
|
|
::= {POEXSensorInfoBySensorRegisOrderEntry 7 }
|
|
|
|
POEXSensorInfoBySensorRegisOrderSensDevRFStrength OBJECT-TYPE
|
|
SYNTAX INTEGER(-128..127)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The signal strength, in percent, of the radio link between the gateway
|
|
and the particular sensor, as measured at the time of the most recent
|
|
sensor report."
|
|
INDEX { POEXSensorRegistrationIndex }
|
|
::= {POEXSensorInfoBySensorRegisOrderEntry 8 }
|
|
|
|
POEXSensorInfoBySensorRegisOrderSensDevRptUT OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The untranslated data block received from a sensor, in hexadecimal
|
|
format. This may be used where a translating function isn't yet
|
|
present, and for development purposes. Most users should use the
|
|
translated values delivered in the format of
|
|
POEXSensorDeviceReadingValuesAll."
|
|
INDEX { POEXSensorRegistrationIndex }
|
|
::= {POEXSensorInfoBySensorRegisOrderEntry 9 }
|
|
|
|
POEXSensorInfoBySensorRegisOrderSensDevReadingVl1 OBJECT-TYPE
|
|
SYNTAX POEXSensorDeviceReadingU32Value
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The value of a single sensor reading, or one half of a 64-bit reading,
|
|
in integer format, not translated to human-readable form. See
|
|
POEXSensorDeviceReadingU32Value for further explanation."
|
|
::= {POEXSensorInfoBySensorRegisOrderEntry 10 }
|
|
|
|
POEXSensorInfoBySensorRegisOrderSensDevReadingVl2 OBJECT-TYPE
|
|
SYNTAX POEXSensorDeviceReadingU32Value
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The value of a single sensor reading, or one half of a 64-bit reading,
|
|
in integer format, not translated to human-readable form. See
|
|
POEXSensorDeviceReadingU32Value for further explanation."
|
|
::= {POEXSensorInfoBySensorRegisOrderEntry 11 }
|
|
|
|
POEXSensorInfoBySensorRegisOrderSensDevReadingVl3 OBJECT-TYPE
|
|
SYNTAX POEXSensorDeviceReadingU32Value
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The value of a single sensor reading, or one half of a 64-bit reading,
|
|
in integer format, not translated to human-readable form. See
|
|
POEXSensorDeviceReadingU32Value for further explanation."
|
|
::= {POEXSensorInfoBySensorRegisOrderEntry 12 }
|
|
|
|
POEXSensorInfoBySensorRegisOrderSensDevReadingVl4 OBJECT-TYPE
|
|
SYNTAX POEXSensorDeviceReadingU32Value
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The value of a single sensor reading, or one half of a 64-bit reading,
|
|
in integer format, not translated to human-readable form. See
|
|
POEXSensorDeviceReadingU32Value for further explanation."
|
|
::= {POEXSensorInfoBySensorRegisOrderEntry 13 }
|
|
|
|
POEXSensorInfoBySensorRegisOrderSensDevReadingVl5 OBJECT-TYPE
|
|
SYNTAX POEXSensorDeviceReadingU32Value
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The value of a single sensor reading, or one half of a 64-bit reading,
|
|
in integer format, not translated to human-readable form. See
|
|
POEXSensorDeviceReadingU32Value for further explanation."
|
|
::= {POEXSensorInfoBySensorRegisOrderEntry 14 }
|
|
|
|
POEXSensorInfoBySensorRegisOrderSensDevReadingVl6 OBJECT-TYPE
|
|
SYNTAX POEXSensorDeviceReadingU32Value
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The value of a single sensor reading, or one half of a 64-bit reading,
|
|
in integer format, not translated to human-readable form. See
|
|
POEXSensorDeviceReadingU32Value for further explanation."
|
|
::= {POEXSensorInfoBySensorRegisOrderEntry 15 }
|
|
|
|
POEXSensorInfoBySensorRegisOrderSensDevReadingVl7 OBJECT-TYPE
|
|
SYNTAX POEXSensorDeviceReadingU32Value
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The value of a single sensor reading, or one half of a 64-bit reading,
|
|
in integer format, not translated to human-readable form. See
|
|
POEXSensorDeviceReadingU32Value for further explanation."
|
|
::= {POEXSensorInfoBySensorRegisOrderEntry 16 }
|
|
|
|
POEXSensorInfoBySensorRegisOrderSensDevReadingVl8 OBJECT-TYPE
|
|
SYNTAX POEXSensorDeviceReadingU32Value
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The value of a single sensor reading, or one half of a 64-bit reading,
|
|
in integer format, not translated to human-readable form. See
|
|
POEXSensorDeviceReadingU32Value for further explanation."
|
|
::= {POEXSensorInfoBySensorRegisOrderEntry 17 }
|
|
|
|
--
|
|
-- Traps
|
|
--
|
|
|
|
--Map of types used in traps to those used in requests
|
|
-- POEX-Trap-DevIDReported ::= POEX-GatewayID
|
|
-- POEX-Trap-AllValuesReported ::=
|
|
-- CHOICE {
|
|
-- POEX-trap-values-translatable POEX-SensorDeviceReadingValuesAll,
|
|
-- POEX-trap-values-unknown POEX-SensorDeviceReadingUntranslated
|
|
-- }
|
|
-- POEX-Trap-AllUnitsReported ::= POEX-SensorDeviceReadingUnitsAll
|
|
-- POEX-Trap-AgeReported ::= POEX-SensorDeviceReadingUnitsAll
|
|
-- POEX-Trap-AlarmingReported ::= POEX-SensorDeviceReadingUnitsAll
|
|
|
|
POEXTrapDevIDReported ::= TEXTUAL-CONVENTION
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The serial number identifier of the sensor device assigned and
|
|
programmed by the manufacturer. This will ordinarily be printed
|
|
on a label on the housing of the device. POEXTrapDevIDReported
|
|
is the same as POEXSensorID."
|
|
SYNTAX Unsigned32(1..2147483631)
|
|
|
|
POEXTrapAllValuesReported ::= TEXTUAL-CONVENTION
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This will make one of two reports. For the case the sensor type is
|
|
known to the gateway, this will be all of the datums for the most
|
|
recent reading of the sensor device, separated by commas, in textual
|
|
format, using the POEXSensorDeviceReadingValuesAll format.
|
|
Where the sensor type is not known to the gateway, this will be
|
|
the untranslated data block received from a sensor, in hexadecimal
|
|
format. This POEXTrapAllValuesReported is the same as either
|
|
POEXSensorDeviceReadingValuesAll or
|
|
POEXSensorDeviceReadingUntranslated."
|
|
SYNTAX OCTET STRING
|
|
|
|
POEXTrapAllUnitsReported ::= TEXTUAL-CONVENTION
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"All of the units corresponding to the datums for the most recent
|
|
reading of the sensor device, separated by commas, in textual
|
|
format. For example, for a sensor reporting temperature and
|
|
humidity this might read 'degrees C, %RH'.
|
|
POEXTrapAllUnitsReported is the same as
|
|
POEXSensorDeviceReadingUnitsAll."
|
|
SYNTAX OCTET STRING
|
|
|
|
POEXTrapAgeReported ::= TEXTUAL-CONVENTION
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The age of the sensor report received most recently from a sensor.
|
|
That time is reported as the number of seconds between the time of
|
|
the sensor report and the time this information is requested.
|
|
POEXTrapAgeReported is the same as
|
|
POEXSensorDeviceReadingAge."
|
|
SYNTAX OCTET STRING
|
|
|
|
POEXTrapAlarmingReported ::= TEXTUAL-CONVENTION
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Either 'Alarming' or 'Not alarming'. A device will report an alarm
|
|
if it is programmed with a threshold found to be exceeded. Examples:
|
|
a temperature sensor for a refrigeration unit can be programmed to
|
|
alarm if the measured temperature rises above a threshold, and
|
|
a door sensor might alarm if a security door is opened.
|
|
POEXTrapAlarmingReported is the same as
|
|
POEXSensorDeviceReadingAlarming."
|
|
SYNTAX OCTET STRING
|
|
|
|
POEXNewSensorTraffic TRAP-TYPE
|
|
ENTERPRISE POEX
|
|
VARIABLES {
|
|
POEXSensorInfoTranslatedFormatSensorDeviceID, POEXTrapDevIDReported,
|
|
POEXSensorInfoTranslatedFormatSensorDeviceReadingValuesAll, POEXTrapAllValuesReported,
|
|
POEXSensorInfoTranslatedFormatSensorDeviceReadingUnitsAll, POEXTrapAllUnitsReported,
|
|
POEXSensorInfoTranslatedFormatSensorDeviceReadingAge, POEXTrapAgeReported,
|
|
POEXSensorInfoTranslatedFormatSensorDeviceAlarming, POEXTrapAlarmingReported
|
|
}
|
|
DESCRIPTION
|
|
"This trap, when enabled, will generate a report corresponding to new
|
|
data from any registered sensor as it is received. Included with the
|
|
trap message are the sensor ID, all values the sensor reports, units for
|
|
all those values, the age, and whether the sensor is alarming."
|
|
::= 1
|
|
|
|
POEXDeviceAlarming TRAP-TYPE
|
|
ENTERPRISE POEX
|
|
VARIABLES {
|
|
POEXSensorInfoTranslatedFormatSensorDeviceID, POEXTrapDevIDReported,
|
|
POEXSensorInfoTranslatedFormatSensorDeviceReadingValuesAll, POEXTrapAllValuesReported,
|
|
POEXSensorInfoTranslatedFormatSensorDeviceReadingUnitsAll, POEXTrapAllUnitsReported,
|
|
POEXSensorInfoTranslatedFormatSensorDeviceReadingAge, POEXTrapAgeReported,
|
|
POEXSensorInfoTranslatedFormatSensorDeviceAlarming, POEXTrapAlarmingReported
|
|
}
|
|
DESCRIPTION
|
|
"This trap, when enabled, will generate a report corresponding to new
|
|
data from any registered sensor as it is received, but only if that
|
|
sensor is alarming and the POEXNewSensorTraffic trap is disabled.
|
|
(That trap will generate the same message, rendering this trap redundant.)
|
|
Included with the trap message are the sensor ID, all values the sensor
|
|
reports, units for all those values, the age, and whether the sensor
|
|
is alarming."
|
|
::= 2
|
|
|
|
END
|