Observium_CE/mibs/monnit/MONNIT-EGW-MIB

295 lines
6.9 KiB
Plaintext

--$Author: klewis $
--$Date: 09/01/2013 $
--Revision 1.0
--
-- MONNIT-EGW-MIB
-- Title: MONNIT TOP LEVEL MIB FOR EGW
-- ************************************************************************
-- ************************************************************************
-- ************************************************************************
-- MONNIT-EGW-MIB { iso org(3) dod(6) internet(1) private(4)
-- enterprises(1) Monnit(41542) Product(1) EGW512(10)/TRAPARGS(110)}
-- 3.6.1.4.1.41542.1.10/110
MONNIT-EGW-MIB DEFINITIONS ::= BEGIN
IMPORTS
OBJECT-TYPE FROM RFC-1212
TRAP-TYPE FROM RFC-1215
enterprises FROM RFC1155-SMI
DisplayString FROM RFC1213-MIB;
Monnit OBJECT IDENTIFIER ::= { enterprises 41542 }
EGW512 OBJECT IDENTIFIER ::= { Monnit 1 }
EGWData OBJECT IDENTIFIER ::= { EGW512 10 }
EGWTrapArgs OBJECT IDENTIFIER ::= { EGW512 20 }
-- ************************************************************************
-- Sections
-- ************************************************************************
GW-Section OBJECT IDENTIFIER ::= { EGWData 1 }
WNet-Section OBJECT IDENTIFIER ::= { EGWData 2 }
-- ************************************************************************
-- Gateway table
-- ************************************************************************
GWSerial OBJECT-TYPE
SYNTAX GAUGE
ACCESS read-only
STATUS mandatory
DESCRIPTION "Serial number of the Wireless Ethernet Gateway"
::= { GW-Section 1 }
Version OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "Gateway firmware version"
::= { GW-Section 2 }
WDCount OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "Total number of sensors registered on this gateway's data interfaces"
::= { GW-Section 3 }
-- ************************************************************************
-- Sensor array table
-- ************************************************************************
WDTable OBJECT-TYPE
SYNTAX SEQUENCE OF WDEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "A List of Wireless Device Entries"
::= { WNet-Section 1 }
WD-Entry OBJECT-TYPE
SYNTAX WDEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "A Wireless Device Entry"
INDEX { Index }
::= { WDTable 1 }
WDEntry ::=
SEQUENCE {
Index INTEGER,
Serial INTEGER,
Type INTEGER,
Age INTEGER,
Active INTEGER,
Alarming INTEGER,
Voltage INTEGER,
RFSignal INTEGER,
Data1 INTEGER,
Data2 INTEGER,
Data3 INTEGER,
Data4 INTEGER,
Data5 INTEGER,
Data6 INTEGER,
Data7 INTEGER,
Data8 INTEGER
}
Index OBJECT-TYPE
SYNTAX INTEGER (1..512)
ACCESS read-only
STATUS mandatory
DEFVAL { 0 }
DESCRIPTION "The index for the specific wireless device 1..512"
::= { WD-Entry 1 }
Serial OBJECT-TYPE
SYNTAX GAUGE
ACCESS read-only
STATUS mandatory
DEFVAL { 0 }
DESCRIPTION "Serial number of wireless device"
::= { WD-Entry 2 }
Type OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DEFVAL { 0 }
DESCRIPTION "Numerical NodeType of the of wireless device"
::= { WD-Entry 3 }
Age OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DEFVAL { 0 }
DESCRIPTION "Number of seconds from the last wireless communication"
::= { WD-Entry 4 }
Active OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DEFVAL { 0 }
DESCRIPTION "Value depicting if the Wireless device is actively connected (1) and delivering data."
::= { WD-Entry 5 }
Alarming OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DEFVAL { 0 }
DESCRIPTION "Value depicting if the Wireless device is actively alarming(1)."
::= { WD-Entry 6 }
Voltage OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "Battery voltage on the wireless device in mV"
DEFVAL { 0 }
::= { WD-Entry 7 }
RFSignal OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "Percentage of available wireless signal"
DEFVAL { 0 }
::= { WD-Entry 8 }
Data1 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "Data value 1 on wireless device"
DEFVAL { 0 }
::= { WD-Entry 9 }
Data2 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "Data value 2 on wireless device"
DEFVAL { 0 }
::= { WD-Entry 10 }
Data3 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "Data value 3 on wireless device"
DEFVAL { 0 }
::= { WD-Entry 11 }
Data4 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "Data value 4 on wireless device"
DEFVAL { 0 }
::= { WD-Entry 12 }
Data5 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "Data value 5 on wireless device"
DEFVAL { 0 }
::= { WD-Entry 13 }
Data6 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "Data value 6 on wireless device"
DEFVAL { 0 }
::= { WD-Entry 14 }
Data7 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "Data value 7 on wireless device"
DEFVAL { 0 }
::= { WD-Entry 15 }
Data8 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "Data value 8 on wireless device"
DEFVAL { 0 }
::= { WD-Entry 16 }
-- ************************************************************************
-- Trap Identifiers
-- ************************************************************************
egw512trap-desc OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "This OID defines a Trap String"
::= { EGWTrapArgs 1 }
GW-online TRAP-TYPE
ENTERPRISE Monnit
VARIABLES { egw512trap-desc }
DESCRIPTION "EGW SNMP Interface Active"
--#TYPE "EGW Active"
--#SUMMARY "Ethernet Gateway SNMP Interface Online"
--#SEVERITY NORMAL
--#TIMEINDEX 1
--#HELP ""
--#HELPTAG 0
--#STATE OPERATIONAL
::= 1
WD-online TRAP-TYPE
ENTERPRISE Monnit
VARIABLES { egw512trap-desc }
DESCRIPTION "Wireless Device Active"
--#TYPE "WD Active"
--#SUMMARY "Wireless Device Active"
--#SEVERITY NORMAL
--#TIMEINDEX 1
--#HELP ""
--#HELPTAG 0
--#STATE OPERATIONAL
::= 2
WD-report-alarm TRAP-TYPE
ENTERPRISE Monnit
VARIABLES { egw512trap-desc }
DESCRIPTION "Description of environmental input alarm"
--#TYPE "WD Environmental Alarm"
--#SUMMARY "wireless device is alarming"
--#SEVERITY MAJOR
--#TIMEINDEX 1
--#HELP ""
--#HELPTAG 0
--#STATE OPERATIONAL
::= 3
WD-report-normal TRAP-TYPE
ENTERPRISE Monnit
VARIABLES { egw512trap-desc }
DESCRIPTION "Description of environmental input alarm"
--#TYPE "WD Environmental REPORT"
--#SUMMARY "Wireless device has returned to normal"
--#SEVERITY NORMAL
--#TIMEINDEX 1
--#HELP ""
--#HELPTAG 0
--#STATE OPERATIONAL
::= 4
END