-- Jacarta interSeptor Pro MIB
-- MIB for interSeptor Pro Environmental Monitoring System
--
-- { iso org(3) dod(6) internet(1) private(4) enterprises(1) jacarta(19011)
-- product(1) webAppliance(3) ispro(2) }
-- ==========================================================================
--
ISPRO-MIB DEFINITIONS ::= BEGIN
IMPORTS
enterprises, IpAddress
FROM RFC1155-SMI
OBJECT-TYPE
FROM RFC-1212
DisplayString
FROM RFC1213-MIB;
jacarta OBJECT IDENTIFIER ::= { enterprises 19011 }
product OBJECT IDENTIFIER ::= { jacarta 1 }
webAppliance OBJECT IDENTIFIER ::= { product 3 }
ispro OBJECT IDENTIFIER ::= { webAppliance 2 }
-- ==========================================================================
-- top level structure
-- ==========================================================================
isObjects OBJECT IDENTIFIER ::= { ispro 1 }
isTraps OBJECT IDENTIFIER ::= { ispro 2 }
isIdent OBJECT IDENTIFIER ::= { isObjects 1 }
isConfig OBJECT IDENTIFIER ::= { isObjects 2 }
isDevice OBJECT IDENTIFIER ::= { isObjects 3 }
isDeviceMonitor OBJECT IDENTIFIER ::= { isDevice 1 }
isDeviceConfig OBJECT IDENTIFIER ::= { isDevice 2 }
-- ==========================================================================
-- Enumeration Data Type Declaration
-- ==========================================================================
IsproEnuEnable ::= INTEGER {
enabled(1),
disabled(2)
}
IsproEnuReset ::= INTEGER {
reset(1),
nothing(2)
}
IsproEnuRestart ::= INTEGER {
restart(1),
nothing(2)
}
IsproEnuSeverity ::= INTEGER {
information(1),
warning(2),
severe(3)
}
IsproEnuAccess ::= INTEGER {
noAccess(1),
readonly(2),
readwrite(3)
}
IsproEnuTempUnit ::= INTEGER {
celsius(1),
fahrenheit(2)
}
IsproEnuDateFormat ::= INTEGER {
dd-mm-yyyy(1),
mm-dd-yyyy(2)
}
IsproEnuTimeZone ::= INTEGER {
gMT-1200(1),
gMT-1100(2),
gMT-1000(3),
gMT-0900(4),
gMT-0800(5),
gMT-0700(6),
gMT-0600(7),
gMT-0500(8),
gMT-0400(9),
gMT-0330(10),
gMT-0300(11),
gMT-0200(12),
gMT-0100(13),
gMT-0000(14),
gMT0100(15),
gMT0200(16),
gMT0300(17),
gMT0330(18),
gMT0400(19),
gMT0500(20),
gMT0530(21),
gMT0600(22),
gMT0700(23),
gMT0800(24),
gMT0900(25),
gMT1000(26),
gMT1100(27),
gMT1200(28)
}
IsproEnuSensorType ::= INTEGER {
unknown(1),
sensorHT(2)
}
IsproEnuThresholdStatus ::= INTEGER {
unknown(1),
disable(2),
normal(3),
below-low-warning(4),
below-low-critical(5),
above-high-warning(6),
above-high-critical(7)
}
IsproEnuDigitalStatus ::= INTEGER {
active(1),
inactive(2)
}
IsproTriggerStatus ::= INTEGER {
normal(1),
triggered(2)
}
IsproEnuSensorState ::= INTEGER {
auto(1),
disable(2)
}
IsproEnuTempCalibration ::= INTEGER {
temperatureIncrease0Point0(1),
temperatureIncrease0Point5(2),
temperatureIncrease1Point0(3),
temperatureIncrease1Point5(4),
temperatureIncrease2Point0(5),
temperatureIncrease2Point5(6),
temperatureIncrease3Point0(7),
temperatureDecrease0Point5(8),
temperatureDecrease1Point0(9),
temperatureDecrease1Point5(10),
temperatureDecrease2Point0(11),
temperatureDecrease2Point5(12),
temperatureDecrease3Point0(13)
}
IsproEnuHumidityCalibration ::= INTEGER {
humidityIncrease0Point0(1),
humidityIncrease0Point5(2),
humidityIncrease1Point0(3),
humidityIncrease1Point5(4),
humidityIncrease2Point0(5),
humidityIncrease2Point5(6),
humidityIncrease3Point0(7),
humidityDecrease0Point5(8),
humidityDecrease1Point0(9),
humidityDecrease1Point5(10),
humidityDecrease2Point0(11),
humidityDecrease2Point5(12),
humidityDecrease3Point0(13)
}
IsproEnuAlarmState ::= INTEGER {
disabled(1),
normalOpen(2),
normalClose(3)
}
IsproEnuOnOff ::= INTEGER {
on(1),
off(2)
}
IsproEnuTurnOnOff ::= INTEGER {
turnOn(1),
turnOff(2)
}
IsproEnuPresent ::= INTEGER {
present(1),
absent(2)
}
IsproEnuDO ::= INTEGER {
none(1),
digitalOutput1(2),
digitalOutput2(3)
}
IsproEnuHighLow ::= INTEGER {
high(1),
low(2)
}
IsproLogType ::= INTEGER {
historyLog(1),
extendedLog(2),
deviceEventLog(3),
systemEventLog(4)
}
-- ===========================================================================
--
-- isIdent
-- Contains the identification of ispro device
-- 1.3.6.1.4.1.2468.1.3.2.1.1
--
-- ===========================================================================
isIdentManufacturer OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..31))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The name of the ispro manufacturer."
::= { isIdent 1 }
isIdentModel OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..31))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The ispro Model designation."
::= { isIdent 2 }
isIdentAgentSoftwareVersion OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The ispro software/firmware version. This variable may or
may not have the same value as upsIdentUPSSoftwareVersion in some
implementations."
::= { isIdent 3 }
isIdentName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A string identifying the ispro. This object should be
set by the administrator."
::= { isIdent 4 }
-- ===========================================================================
--
-- isConfig
-- Provides the overall information and configuration of ispro device.
-- .1.3.6.1.4.1.2468.1.3.2.1.2
--
-- ===========================================================================
isConfigMibVersion OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The version of MIB spec."
::= { isConfig 1}
--
-- isConfigNetwork Group
--
isConfigNetwork OBJECT IDENTIFIER ::= { isConfig 2 }
isConfigIpAddress OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
" The ip address that NMS can identify the managed
device"
::= { isConfigNetwork 1 }
isConfigGateway OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
" The default gateway that allow device managed
through routers "
::= { isConfigNetwork 2 }
isConfigSubnetMask OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
" Internet address subnet mask"
::= { isConfigNetwork 3 }
--
-- end of isConfigNetwork Group
--
--
-- isConfigDateTime Group
--
isConfigDateTime OBJECT IDENTIFIER ::= { isConfig 3 }
isConfigDate OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..10))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The date in ispro, format ask the Date Format of references "
::= { isConfigDateTime 1}
isConfigTime OBJECT-TYPE
SYNTAX DisplayString(SIZE (0..8))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The time of ispro, format is (hh:mm:ss)"
::= { isConfigDateTime 2}
isConfigTimeFromNtp OBJECT-TYPE
SYNTAX IsproEnuEnable
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable update date/time from NTP server."
::= { isConfigDateTime 3}
isConfigNtpIpAddress OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"NTP IP address."
::= { isConfigDateTime 4}
isConfigNtpTimeZone OBJECT-TYPE
SYNTAX IsproEnuTimeZone
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Configure the time zone of ispro to access NTP server."
::= { isConfigDateTime 5}
isConfigDayLightSaving OBJECT-TYPE
SYNTAX IsproEnuEnable
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable daylight saving for NTP time, if enabled, the time get from NTP will be set
set one hour in advance to reflect daylight saving status."
::= { isConfigDateTime 6}
--
-- end of isConfigDateTime Group
--
--
-- isConfigLog Group
--
isConfigLog OBJECT IDENTIFIER ::= { isConfig 4 }
isConfigHistoryLogFrequency OBJECT-TYPE
SYNTAX INTEGER (5..3600) -- in seconds
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The frequency of the history log updates. The value
is in seconds"
::= { isConfigLog 1}
isConfigExtHistoryLogFrequency OBJECT-TYPE
SYNTAX INTEGER (1..720) -- in minutes
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The frequency of the extended history log updates.
The value is in seconds"
::= { isConfigLog 2}
isConfigConfigurationLog OBJECT-TYPE
SYNTAX IsproEnuEnable
ACCESS read-write
STATUS mandatory
DESCRIPTION
" Enable/disable ispro to log parameters change."
::= { isConfigLog 3}
isConfigLogType OBJECT-TYPE
SYNTAX IsproLogType
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The type of log in agent"
::= { isConfigLog 4}
--
-- end of isConfigLog Group
--
isConfigDhcpState OBJECT-TYPE
SYNTAX IsproEnuEnable
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable or disable DHCP/BootP capability"
::= { isConfig 5}
isConfigPingState OBJECT-TYPE
SYNTAX IsproEnuEnable
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable or disable Ping Echo capability"
::= { isConfig 6}
isConfigTftpState OBJECT-TYPE
SYNTAX IsproEnuEnable
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable or disable TFTP network upgrade capability"
::= { isConfig 7}
--
-- isConfigTelnet Group
--
isConfigTelnet OBJECT IDENTIFIER ::= { isConfig 8 }
isConfigTelnetState OBJECT-TYPE
SYNTAX IsproEnuEnable
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable or disable telnet access"
::= { isConfigTelnet 1}
isConfigTelnetPortNumber OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting the server port of telnet."
::= { isConfigTelnet 2}
--
-- end of isConfigTelnet Group
--
--
-- isConfigHttp Group
--
isConfigHttp OBJECT IDENTIFIER ::= { isConfig 9 }
isConfigHttpState OBJECT-TYPE
SYNTAX IsproEnuEnable
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable or disable HTTP access"
::= { isConfigHttp 1}
isConfigHttpPortNumber OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting the server port of HTTP."
::= { isConfigHttp 2}
isConfigHttpSecurity OBJECT-TYPE
SYNTAX IsproEnuEnable
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable HTTP access for read-only users"
::= { isConfigHttp 3}
--
-- end of isConfigHttp Group
--
--
-- isConfigSnmp Group
--
isConfigSnmp OBJECT IDENTIFIER ::= { isConfig 10 }
isConfigSnmpState OBJECT-TYPE
SYNTAX IsproEnuEnable
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable or disable SNMP access"
::= { isConfigSnmp 1}
isConfigSnmpPortNumber OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting the server port of SNMP."
::= { isConfigSnmp 2}
--
-- end of isConfigSnmp Group
--
--
-- isConfigControl Group
--
isConfigControl OBJECT IDENTIFIER ::= { isConfig 11 }
isConfigResetToDefault OBJECT-TYPE
SYNTAX IsproEnuReset
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Reset all parameters of ispro to default value"
::= { isConfigControl 1}
isConfigRestart OBJECT-TYPE
SYNTAX IsproEnuRestart
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Restart ispro"
::= { isConfigControl 2}
--
-- end of isConfigControl Group
--
--
-- isConfigTrap Group
--
isConfigTrap OBJECT IDENTIFIER ::= { isConfig 12 }
isConfigTrapRetryCount OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The count of repeat traps to send to NMS before trap
acknowledge received."
::= { isConfigTrap 1}
isConfigTrapRetryTime OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The time between retry traps send to NMS."
::= { isConfigTrap 2}
isConfigTrapAckSignature OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The signature of trap acknowledge."
::= { isConfigTrap 3}
--
-- end of isConfigTrap Group
--
isConfigRefreshRate OBJECT-TYPE
SYNTAX INTEGER (1..60)
ACCESS read-write
STATUS mandatory
DESCRIPTION
" The frequency that ispro refresh web page from agent
(unit : second)."
::= { isConfig 13}
--
-- isConfigTrapReceiverTable
--
isConfigTrapReceiverTable OBJECT-TYPE
SYNTAX SEQUENCE OF IsproReceiverEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of managers to send traps to. The number of
entries is given by the value of isConfigNumTrapReceivers"
::= { isConfig 14 }
isConfigTrapReceiverEntry OBJECT-TYPE
SYNTAX IsproReceiverEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The managers to send traps to."
INDEX { isReceiverIndex}
::= { isConfigTrapReceiverTable 1 }
IsproReceiverEntry ::=
SEQUENCE {
isReceiverIndex
INTEGER,
isReceiverAddr
IpAddress,
isReceiverCommunityString
DisplayString,
isReceiverSeverityLevel
INTEGER,
isReceiverDescription
DisplayString
}
isReceiverIndex OBJECT-TYPE
SYNTAX INTEGER (1..8)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a trap receiver entry."
::= { isConfigTrapReceiverEntry 1 }
isReceiverAddr OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The IP address of the manager to send a trap to."
::= { isConfigTrapReceiverEntry 2 }
isReceiverCommunityString OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..19))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The community name to use in the trap when
sent to the manager."
::= { isConfigTrapReceiverEntry 3 }
isReceiverSeverityLevel OBJECT-TYPE
SYNTAX IsproEnuSeverity
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The severity level of traps to be received by this manager."
::= { isConfigTrapReceiverEntry 4 }
isReceiverDescription OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..24))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Description of trap receivers"
::= { isConfigTrapReceiverEntry 5 }
--
-- end of isConfigTrapReceiverTable
--
--
-- isConfigAccessControlTable
--
isConfigAccessControlTable OBJECT-TYPE
SYNTAX SEQUENCE OF IsproAccessEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of managers which can access ispro with private
community string."
::= { isConfig 15}
isConfigAccessControlEntry OBJECT-TYPE
SYNTAX IsproAccessEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The managers."
INDEX { isAccessIndex}
::= { isConfigAccessControlTable 1 }
IsproAccessEntry ::=
SEQUENCE {
isAccessIndex
INTEGER,
isAccessControlAddr
IpAddress,
isAccessCommunityString
DisplayString,
isAccessControlMode
INTEGER,
isAccessAccount
DisplayString
}
isAccessIndex OBJECT-TYPE
SYNTAX INTEGER (1..8)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to an access control entry."
::= { isConfigAccessControlEntry 1 }
isAccessControlAddr OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The IP address of the manager to access ispro"
::= { isConfigAccessControlEntry 2 }
isAccessCommunityString OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..15))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The community name to use in the manager when
access ispro"
::= { isConfigAccessControlEntry 3 }
isAccessControlMode OBJECT-TYPE
SYNTAX IsproEnuAccess
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Access type, only read/Write access type can change parameter
of ispro"
::= { isConfigAccessControlEntry 4 }
isAccessAccount OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Access account, the account for web login to
access ispro"
::= { isConfigAccessControlEntry 5 }
--
-- end of isConfigAccessControlTable
--
isConfigTemperatureUnit OBJECT-TYPE
SYNTAX IsproEnuTempUnit
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The temperature unit of the system, can be Celsius or Fahrenheit"
::= { isConfig 16}
isConfigDateFormat OBJECT-TYPE
SYNTAX IsproEnuDateFormat
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The date format of the system, can be dd/mm/yyyy or mm/dd/yyyy"
::= { isConfig 17}
-- ===========================================================================
--
-- isDevice
-- Monitor and Configure the sensors of ispro device.
-- 1.3.6.1.4.1.2468.1.3.2.1.3
--
-- ===========================================================================
-- Monitor
-- 1.3.6.1.4.1.2468.1.3.2.1.3.1
-- Temperature
isDeviceMonitorTemperatureTable OBJECT-TYPE
SYNTAX SEQUENCE OF IsproDeviceMonitorTemperatureEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The temperature monitoring table, to provides
overall status of temperature."
::= { isDeviceMonitor 1}
isDeviceMonitorTemperatureEntry OBJECT-TYPE
SYNTAX IsproDeviceMonitorTemperatureEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The temperature monitoring table, to provides
overall status of temperature."
INDEX { isDeviceMonitorTemperatureIndex}
::= { isDeviceMonitorTemperatureTable 1 }
IsproDeviceMonitorTemperatureEntry ::=
SEQUENCE {
isDeviceMonitorTemperatureIndex
INTEGER,
isDeviceMonitorTemperatureName
DisplayString,
isDeviceMonitorTemperature
INTEGER,
isDeviceMonitorTemperatureAlarm
INTEGER
}
isDeviceMonitorTemperatureIndex OBJECT-TYPE
SYNTAX INTEGER (1..24)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a temperature entry."
::= { isDeviceMonitorTemperatureEntry 1 }
isDeviceMonitorTemperatureName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The temperature sensor name."
::= { isDeviceMonitorTemperatureEntry 2 }
isDeviceMonitorTemperature OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The temperature of sensor on device Ispro, the unit is 0.01 degree."
::= { isDeviceMonitorTemperatureEntry 3 }
isDeviceMonitorTemperatureAlarm OBJECT-TYPE
SYNTAX IsproEnuThresholdStatus
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The status of temperature sensor in Ispro."
::= { isDeviceMonitorTemperatureEntry 4 }
-- Humidity
isDeviceMonitorHumidityTable OBJECT-TYPE
SYNTAX SEQUENCE OF IsproDeviceMonitorHumidityEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The humidity monitoring table, to provides
overall status of humidity."
::= { isDeviceMonitor 2 }
isDeviceMonitorHumidityEntry OBJECT-TYPE
SYNTAX IsproDeviceMonitorHumidityEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The humidity monitoring table, to provides
overall status of humidity."
INDEX { isDeviceMonitorHumidityIndex}
::= { isDeviceMonitorHumidityTable 1 }
IsproDeviceMonitorHumidityEntry ::=
SEQUENCE {
isDeviceMonitorHumidityIndex
INTEGER,
isDeviceMonitorHumidityName
DisplayString,
isDeviceMonitorHumidity
INTEGER,
isDeviceMonitorHumidityAlarm
INTEGER
}
isDeviceMonitorHumidityIndex OBJECT-TYPE
SYNTAX INTEGER (1..24)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a humidity entry."
::= { isDeviceMonitorHumidityEntry 1 }
isDeviceMonitorHumidityName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The humidity sensor name."
::= { isDeviceMonitorHumidityEntry 2 }
isDeviceMonitorHumidity OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The humidity of sensor on device Ispro, the unit is 0.01 %."
::= { isDeviceMonitorHumidityEntry 3 }
isDeviceMonitorHumidityAlarm OBJECT-TYPE
SYNTAX IsproEnuThresholdStatus
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The status of humidity sensor in Ispro."
::= { isDeviceMonitorHumidityEntry 4 }
-- Digital Input
isDeviceMonitorDigitalInTable OBJECT-TYPE
SYNTAX SEQUENCE OF IsproDeviceMonitorDigitalInEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The digital input monitoring table, to provides
overall status of digital input."
::= { isDeviceMonitor 3}
isDeviceMonitorDigitalInEntry OBJECT-TYPE
SYNTAX IsproDeviceMonitorDigitalInEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The digital input monitoring table, to provides
overall status of digital input."
INDEX { isDeviceMonitorDigitalInIndex}
::= { isDeviceMonitorDigitalInTable 1 }
IsproDeviceMonitorDigitalInEntry ::=
SEQUENCE {
isDeviceMonitorDigitalInIndex
INTEGER,
isDeviceMonitorDigitalInName
DisplayString,
isDeviceMonitorDigitalIn
INTEGER,
isDeviceMonitorDigitalInAlarm
INTEGER
}
isDeviceMonitorDigitalInIndex OBJECT-TYPE
SYNTAX INTEGER (1..48)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a digital input entry."
::= { isDeviceMonitorDigitalInEntry 1 }
isDeviceMonitorDigitalInName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The digital input sensor name."
::= { isDeviceMonitorDigitalInEntry 2 }
isDeviceMonitorDigitalIn OBJECT-TYPE
SYNTAX IsproEnuDigitalStatus
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The digital input of sensor on device Ispro."
::= { isDeviceMonitorDigitalInEntry 3 }
isDeviceMonitorDigitalInAlarm OBJECT-TYPE
SYNTAX IsproTriggerStatus
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The status of digital alarm sensor."
::= { isDeviceMonitorDigitalInEntry 4 }
-- Device Configuration
-- 1.3.6.1.4.1.2468.1.3.2.1.3.2
isDeviceConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF IsproDeviceConfigEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The device configuration table."
::= { isDeviceConfig 1}
isDeviceConfigEntry OBJECT-TYPE
SYNTAX IsproDeviceConfigEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The device configuration table."
INDEX { isDeviceConfigIndex }
::= { isDeviceConfigTable 1 }
IsproDeviceConfigEntry ::=
SEQUENCE {
isDeviceConfigIndex
INTEGER,
isDeviceConfigName
DisplayString,
isDeviceConfigState
INTEGER,
isDeviceConfigDisplay
INTEGER
}
isDeviceConfigIndex OBJECT-TYPE
SYNTAX INTEGER (1..24)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a sensor entry."
::= { isDeviceConfigEntry 1 }
isDeviceConfigName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The name of sensor device."
::= { isDeviceConfigEntry 2}
isDeviceConfigState OBJECT-TYPE
SYNTAX IsproEnuSensorState
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The setup of device type."
::= { isDeviceConfigEntry 3 }
isDeviceConfigDisplay OBJECT-TYPE
SYNTAX IsproEnuEnable
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable or disable of displaying this sensor in Comprehensive
webpage."
::= { isDeviceConfigEntry 4 }
-- Temperature
isDeviceConfigTemperatureTable OBJECT-TYPE
SYNTAX SEQUENCE OF IsproDeviceConfigTemperatureEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The temperature configuration table of Device."
::= { isDeviceConfig 2}
isDeviceConfigTemperatureEntry OBJECT-TYPE
SYNTAX IsproDeviceConfigTemperatureEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The sensor configuration table of Device."
INDEX { isDeviceConfigTemperatureIndex}
::= { isDeviceConfigTemperatureTable 1 }
IsproDeviceConfigTemperatureEntry ::=
SEQUENCE {
isDeviceConfigTemperatureIndex
INTEGER,
isDeviceConfigTemperatureName
DisplayString,
isDeviceConfigTemperatureLowWarning
INTEGER,
isDeviceConfigTemperatureLowCritical
INTEGER,
isDeviceConfigTemperatureHighWarning
INTEGER,
isDeviceConfigTemperatureHighCritical
INTEGER,
isDeviceConfigTemperatureHysteresis
INTEGER,
isDeviceConfigTemperatureCalibration
INTEGER,
isDeviceConfigTemperatureLowWarningState
INTEGER,
isDeviceConfigTemperatureLowCriticalState
INTEGER,
isDeviceConfigTemperatureHighWarningState
INTEGER,
isDeviceConfigTemperatureHighCriticalState
INTEGER,
isDeviceConfigTemperatureEventDO
INTEGER
}
isDeviceConfigTemperatureIndex OBJECT-TYPE
SYNTAX INTEGER (1..24)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a temperature device entry."
::= { isDeviceConfigTemperatureEntry 1 }
isDeviceConfigTemperatureName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The temperature sensor name."
::= { isDeviceConfigTemperatureEntry 2 }
isDeviceConfigTemperatureLowWarning OBJECT-TYPE
SYNTAX INTEGER (-1500..6500)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set point to trigger low warning alarm. the unit is 0.01 degree."
::= { isDeviceConfigTemperatureEntry 3 }
isDeviceConfigTemperatureLowCritical OBJECT-TYPE
SYNTAX INTEGER (-1500..6500)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The threshold to trigger low critical alarm. the unit is 0.01 degree."
::= { isDeviceConfigTemperatureEntry 4 }
isDeviceConfigTemperatureHighWarning OBJECT-TYPE
SYNTAX INTEGER (-1500..6500)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The threshold to trigger high warning alarm. the unit is 0.01 degree."
::= { isDeviceConfigTemperatureEntry 5 }
isDeviceConfigTemperatureHighCritical OBJECT-TYPE
SYNTAX INTEGER (-1500..6500)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The threshold to trigger high critical alarm. the unit is 0.01 degree."
::= { isDeviceConfigTemperatureEntry 6 }
isDeviceConfigTemperatureHysteresis OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set value to prevent too many alarms when temperature is hovering around the
set threshold. The unit is 0.01"
::= { isDeviceConfigTemperatureEntry 7 }
isDeviceConfigTemperatureCalibration OBJECT-TYPE
SYNTAX IsproEnuTempCalibration
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set value to get the correct temperature according to your reference temperature."
::= { isDeviceConfigTemperatureEntry 8 }
isDeviceConfigTemperatureLowWarningState OBJECT-TYPE
SYNTAX IsproEnuEnable
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable the set point to trigger low warning alarm."
::= { isDeviceConfigTemperatureEntry 9 }
isDeviceConfigTemperatureLowCriticalState OBJECT-TYPE
SYNTAX IsproEnuEnable
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable the set point to trigger low critical alarm."
::= { isDeviceConfigTemperatureEntry 10 }
isDeviceConfigTemperatureHighWarningState OBJECT-TYPE
SYNTAX IsproEnuEnable
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable the set point to trigger high warning alarm."
::= { isDeviceConfigTemperatureEntry 11 }
isDeviceConfigTemperatureHighCriticalState OBJECT-TYPE
SYNTAX IsproEnuEnable
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable the set point to trigger high critical alarm."
::= { isDeviceConfigTemperatureEntry 12 }
isDeviceConfigTemperatureEventDO OBJECT-TYPE
SYNTAX IsproEnuDO
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set the trigger action of temperature events. If event asserted,
this will invert the digital output #1 or #2."
::= { isDeviceConfigTemperatureEntry 13 }
-- Humidity
isDeviceConfigHumidityTable OBJECT-TYPE
SYNTAX SEQUENCE OF IsproDeviceConfigHumidityEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The humidity configuration table of Device."
::= { isDeviceConfig 3}
isDeviceConfigHumidityEntry OBJECT-TYPE
SYNTAX IsproDeviceConfigHumidityEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The humidity configuration table of Device."
INDEX { isDeviceConfigHumidityIndex}
::= { isDeviceConfigHumidityTable 1 }
IsproDeviceConfigHumidityEntry ::=
SEQUENCE {
isDeviceConfigHumidityIndex
INTEGER,
isDeviceConfigHumidityName
DisplayString,
isDeviceConfigHumidityLowWarning
INTEGER,
isDeviceConfigHumidityLowCritical
INTEGER,
isDeviceConfigHumidityHighWarning
INTEGER,
isDeviceConfigHumidityHighCritical
INTEGER,
isDeviceConfigHumidityHysteresis
INTEGER,
isDeviceConfigHumidityCalibration
INTEGER,
isDeviceConfigHumidityLowWarningState
INTEGER,
isDeviceConfigHumidityLowCriticalState
INTEGER,
isDeviceConfigHumidityHighWarningState
INTEGER,
isDeviceConfigHumidityHighCriticalState
INTEGER,
isDeviceConfigHumidityEventDO
INTEGER
}
isDeviceConfigHumidityIndex OBJECT-TYPE
SYNTAX INTEGER (1..24)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a humidity device entry."
::= { isDeviceConfigHumidityEntry 1 }
isDeviceConfigHumidityName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The humidity sensor name."
::= { isDeviceConfigHumidityEntry 2 }
isDeviceConfigHumidityLowWarning OBJECT-TYPE
SYNTAX INTEGER (500..9500)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set point to trigger low warning alarm. the unit is 0.01 %."
::= { isDeviceConfigHumidityEntry 3 }
isDeviceConfigHumidityLowCritical OBJECT-TYPE
SYNTAX INTEGER (500..9500)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The threshold to trigger low critical alarm. the unit is 0.01 %."
::= { isDeviceConfigHumidityEntry 4 }
isDeviceConfigHumidityHighWarning OBJECT-TYPE
SYNTAX INTEGER (500..9500)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The threshold to trigger high warning alarm. the unit is 0.01 %."
::= { isDeviceConfigHumidityEntry 5 }
isDeviceConfigHumidityHighCritical OBJECT-TYPE
SYNTAX INTEGER (500..9500)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The threshold to trigger high critical alarm. the unit is 0.01 %."
::= { isDeviceConfigHumidityEntry 6 }
isDeviceConfigHumidityHysteresis OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set value to prevent too many alarms when Humidity
is hovering around the set threshold. The unit is 0.01"
::= { isDeviceConfigHumidityEntry 7 }
isDeviceConfigHumidityCalibration OBJECT-TYPE
SYNTAX IsproEnuHumidityCalibration
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set value to get the correct temperature according
to your reference temperature."
::= { isDeviceConfigHumidityEntry 8 }
isDeviceConfigHumidityLowWarningState OBJECT-TYPE
SYNTAX IsproEnuEnable
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable the set point to trigger low warning alarm."
::= { isDeviceConfigHumidityEntry 9 }
isDeviceConfigHumidityLowCriticalState OBJECT-TYPE
SYNTAX IsproEnuEnable
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable the set point to trigger low critical alarm."
::= { isDeviceConfigHumidityEntry 10 }
isDeviceConfigHumidityHighWarningState OBJECT-TYPE
SYNTAX IsproEnuEnable
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable the set point to trigger high warning alarm."
::= { isDeviceConfigHumidityEntry 11 }
isDeviceConfigHumidityHighCriticalState OBJECT-TYPE
SYNTAX IsproEnuEnable
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable the set point to trigger high critical alarm."
::= { isDeviceConfigHumidityEntry 12 }
isDeviceConfigHumidityEventDO OBJECT-TYPE
SYNTAX IsproEnuDO
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set the trigger action of humidity events. If event asserted,
this will invert the digital output #1 or #2."
::= { isDeviceConfigHumidityEntry 13 }
-- Digital Input
isDeviceConfigDigitalInTable OBJECT-TYPE
SYNTAX SEQUENCE OF IsproDeviceConfigDigitalInEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The digital input configuration table of Device."
::= { isDeviceConfig 4}
isDeviceConfigDigitalInEntry OBJECT-TYPE
SYNTAX IsproDeviceConfigDigitalInEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The digital input configuration table of Device."
INDEX { isDeviceConfigDigitalInIndex}
::= { isDeviceConfigDigitalInTable 1 }
IsproDeviceConfigDigitalInEntry ::=
SEQUENCE {
isDeviceConfigDigitalInIndex
INTEGER,
isDeviceConfigDigitalInName
DisplayString,
isDeviceConfigDigitalInState
INTEGER,
isDeviceConfigDigitalInHysteresis
INTEGER,
isDeviceConfigDigitalInEventDO
INTEGER
}
isDeviceConfigDigitalInIndex OBJECT-TYPE
SYNTAX INTEGER (1..48)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a digital input device entry."
::= { isDeviceConfigDigitalInEntry 1 }
isDeviceConfigDigitalInName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The name of digital input."
::= { isDeviceConfigDigitalInEntry 2 }
isDeviceConfigDigitalInState OBJECT-TYPE
SYNTAX IsproEnuAlarmState
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setup the signal type to trigger alarm."
::= { isDeviceConfigDigitalInEntry 3 }
isDeviceConfigDigitalInHysteresis OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set value to delay the alarm triggered when event occurs."
::= { isDeviceConfigDigitalInEntry 4 }
isDeviceConfigDigitalInEventDO OBJECT-TYPE
SYNTAX IsproEnuDO
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set the trigger action of digital alarm #1 events. If event asserted,
this will invert the digital output #1 or #2."
::= { isDeviceConfigDigitalInEntry 5 }
-- Digital Output
isDeviceDigitalOutTable OBJECT-TYPE
SYNTAX SEQUENCE OF IsproDeviceDigitalOutEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The configuration table of Device digital output."
::= { isDeviceConfig 5}
isDeviceID OBJECT-TYPE
SYNTAX INTEGER (1..3)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The device board id."
::= { isDevice 3}
isDeviceDigitalOutEntry OBJECT-TYPE
SYNTAX IsproDeviceDigitalOutEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The configuration table of Device digital output."
INDEX { isDeviceDigitalOutIndex }
::= { isDeviceDigitalOutTable 1 }
IsproDeviceDigitalOutEntry ::=
SEQUENCE {
isDeviceDigitalOutIndex
INTEGER,
isDeviceDigitalOutStartState
INTEGER,
isDeviceDigitalOutEventAction
INTEGER,
isDeviceDigitalOutManualControl
INTEGER
}
isDeviceDigitalOutIndex OBJECT-TYPE
SYNTAX INTEGER (1..24)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index is 1 and 2, it maps to digital output 1 and 2."
::= { isDeviceDigitalOutEntry 1 }
isDeviceDigitalOutStartState OBJECT-TYPE
SYNTAX IsproEnuOnOff
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Turn power on/off specific digital output when system
start up."
::= { isDeviceDigitalOutEntry 2 }
isDeviceDigitalOutEventAction OBJECT-TYPE
SYNTAX IsproEnuEnable
ACCESS read-write
STATUS mandatory
DESCRIPTION
"If select yes, it will invert the current status of
specific digital output when Ispro event occurred."
::= { isDeviceDigitalOutEntry 3 }
isDeviceDigitalOutManualControl OBJECT-TYPE
SYNTAX IsproEnuTurnOnOff
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Invert current status of specific digital output manually."
::= { isDeviceDigitalOutEntry 4 }
-- ===========================================================================
--
-- isTraps
-- Grouping all ispro traps here.
--
-- ===========================================================================
isTrapsDescription OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The description of current trap"
::= { isTraps 1 }
--isCommunicationRestored TRAP-TYPE
-- ENTERPRISE isTraps
-- VARIABLES {
-- isTrapsDescription,
-- isDeviceConfigIndex,
-- isDeviceConfigName
-- }
-- DESCRIPTION
-- "INFORMATION: Communication between ispro and sensor had
-- established."
-- ::= 1
--
--isCommunicationLost TRAP-TYPE
-- ENTERPRISE isTraps
-- VARIABLES {
-- isTrapsDescription,
-- isDeviceConfigIndex,
-- isDeviceConfigName
-- }
-- DESCRIPTION
-- "WARNING: Communication between ispro and sensor had
-- lost."
-- ::= 2
--
--isDigitalAlarmInactive TRAP-TYPE
-- ENTERPRISE isTraps
-- VARIABLES {
-- isTrapsDescription,
-- isDeviceMonitorDigitalInIndex,
-- isDeviceMonitorDigitalInName
-- }
-- DESCRIPTION
-- "INFORMATION: Digital input of sensor had return from active state."
-- ::= 3
--
--isDigitalAlarmActive TRAP-TYPE
-- ENTERPRISE isTraps
-- VARIABLES {
-- isTrapsDescription,
-- isDeviceMonitorDigitalInIndex,
-- isDeviceMonitorDigitalInName
-- }
-- DESCRIPTION
-- "WARNING: Digital input had become active."
-- ::= 4
--
--isTemperatureNotHighWarning TRAP-TYPE
-- ENTERPRISE isTraps
-- VARIABLES {
-- isTrapsDescription,
-- isDeviceMonitorTemperatureIndex,
-- isDeviceMonitorTemperatureName,
-- isDeviceMonitorTemperature,
-- isDeviceConfigTemperatureHighWarning
-- }
-- DESCRIPTION
-- "INFORMATION: The temperature of sensor had return from High warning to normal."
-- ::= 5
--
--isTemperatureHighWarning TRAP-TYPE
-- ENTERPRISE isTraps
-- VARIABLES {
-- isTrapsDescription,
-- isDeviceMonitorTemperatureIndex,
-- isDeviceMonitorTemperatureName,
-- isDeviceMonitorTemperature,
-- isDeviceConfigTemperatureHighWarning
-- }
-- DESCRIPTION
-- "WARNING: The temperature of sensor was higher than High warning set point."
-- ::= 6
--
--isTemperatureNotLowWarning TRAP-TYPE
-- ENTERPRISE isTraps
-- VARIABLES {
-- isTrapsDescription,
-- isDeviceMonitorTemperatureIndex,
-- isDeviceMonitorTemperatureName,
-- isDeviceMonitorTemperature,
-- isDeviceConfigTemperatureLowWarning
-- }
-- DESCRIPTION
-- "INFORMATION: The temperature of sensor had return from low warning to normal."
-- ::= 7
--
--isTemperatureLowWarning TRAP-TYPE
-- ENTERPRISE isTraps
-- VARIABLES {
-- isTrapsDescription,
-- isDeviceMonitorTemperatureIndex,
-- isDeviceMonitorTemperatureName,
-- isDeviceMonitorTemperature,
-- isDeviceConfigTemperatureLowWarning
-- }
-- DESCRIPTION
-- "WARNING: The temperature of sensor was lower than low warning set point."
-- ::= 8
--
--isTemperatureNotHighCritical TRAP-TYPE
-- ENTERPRISE isTraps
-- VARIABLES {
-- isTrapsDescription,
-- isDeviceMonitorTemperatureIndex,
-- isDeviceMonitorTemperatureName,
-- isDeviceMonitorTemperature,
-- isDeviceConfigTemperatureHighCritical
-- }
-- DESCRIPTION
-- "INFORMATION: The temperature of sensor lower than high critical set point."
-- ::= 9
--
--isTemperatureHighCritical TRAP-TYPE
-- ENTERPRISE isTraps
-- VARIABLES {
-- isTrapsDescription,
-- isDeviceMonitorTemperatureIndex,
-- isDeviceMonitorTemperatureName,
-- isDeviceMonitorTemperature,
-- isDeviceConfigTemperatureHighCritical
-- }
-- DESCRIPTION
-- "CRITICAL: The temperature of sensor was higher than high critical set point."
-- ::= 10
--
--isTemperatureNotLowCritical TRAP-TYPE
-- ENTERPRISE isTraps
-- VARIABLES {
-- isTrapsDescription,
-- isDeviceMonitorTemperatureIndex,
-- isDeviceMonitorTemperatureName,
-- isDeviceMonitorTemperature,
-- isDeviceConfigTemperatureLowCritical
-- }
-- DESCRIPTION
-- "INFORMATION: The temperature of sensor was higher than low critical set point."
-- ::= 11
--
--isTemperatureLowCritical TRAP-TYPE
-- ENTERPRISE isTraps
-- VARIABLES {
-- isTrapsDescription,
-- isDeviceMonitorTemperatureIndex,
-- isDeviceMonitorTemperatureName,
-- isDeviceMonitorTemperature,
-- isDeviceConfigTemperatureLowCritical
-- }
-- DESCRIPTION
-- "CRITICAL: The temperature of sensor was lower than low critical set point."
-- ::= 12
--isHumidityNotHighWarning TRAP-TYPE
-- ENTERPRISE isTraps
-- VARIABLES {
-- isTrapsDescription,
-- isDeviceMonitorHumidityIndex,
-- isDeviceMonitorHumidityName,
-- isDeviceMonitorHumidity,
-- isDeviceConfigHumidityHighWarning
-- }
-- DESCRIPTION
-- "INFORMATION: The humidity of sensor had return from High warning to normal."
-- ::= 13
--
--isHumidityHighWarning TRAP-TYPE
-- ENTERPRISE isTraps
-- VARIABLES {
-- isTrapsDescription,
-- isDeviceMonitorHumidityIndex,
-- isDeviceMonitorHumidityName,
-- isDeviceMonitorHumidity,
-- isDeviceConfigHumidityHighWarning
-- }
-- DESCRIPTION
-- "WARNING: The humidity of sensor was higher than High warning set point."
-- ::= 14
--
--isHumidityNotLowWarning TRAP-TYPE
-- ENTERPRISE isTraps
-- VARIABLES {
-- isTrapsDescription,
-- isDeviceMonitorHumidityIndex,
-- isDeviceMonitorHumidityName,
-- isDeviceMonitorHumidity,
-- isDeviceConfigHumidityLowWarning
-- }
-- DESCRIPTION
-- "INFORMATION: The humidity of sensor had return from low warning to normal."
-- ::= 15
--
--isHumidityLowWarning TRAP-TYPE
-- ENTERPRISE isTraps
-- VARIABLES {
-- isTrapsDescription,
-- isDeviceMonitorHumidityIndex,
-- isDeviceMonitorHumidityName,
-- isDeviceMonitorHumidity,
-- isDeviceConfigHumidityLowWarning
-- }
-- DESCRIPTION
-- "WARNING: The humidity of sensor was lower than low warning set point."
-- ::= 16
--
--isHumidityNotHighCritical TRAP-TYPE
-- ENTERPRISE isTraps
-- VARIABLES {
-- isTrapsDescription,
-- isDeviceMonitorHumidityIndex,
-- isDeviceMonitorHumidityName,
-- isDeviceMonitorHumidity,
-- isDeviceConfigHumidityHighCritical
-- }
-- DESCRIPTION
-- "INFORMATION: The humidity of sensor lower than high critical set point."
-- ::= 17
--
--isHumidityHighCritical TRAP-TYPE
-- ENTERPRISE isTraps
-- VARIABLES {
-- isTrapsDescription,
-- isDeviceMonitorHumidityIndex,
-- isDeviceMonitorHumidityName,
-- isDeviceMonitorHumidity,
-- isDeviceConfigHumidityHighCritical
-- }
-- DESCRIPTION
-- "CRITICAL: The humidity of sensor was higher than high critical set point."
-- ::= 18
--
--isHumidityNotLowCritical TRAP-TYPE
-- ENTERPRISE isTraps
-- VARIABLES {
-- isTrapsDescription,
-- isDeviceMonitorHumidityIndex,
-- isDeviceMonitorHumidityName,
-- isDeviceMonitorHumidity,
-- isDeviceConfigHumidityLowCritical
-- }
-- DESCRIPTION
-- "INFORMATION: The humidity of sensor was higher than low critical set point."
-- ::= 19
--
--isHumidityLowCritical TRAP-TYPE
-- ENTERPRISE isTraps
-- VARIABLES {
-- isTrapsDescription,
-- isDeviceMonitorHumidityIndex,
-- isDeviceMonitorHumidityName,
-- isDeviceMonitorHumidity,
-- isDeviceConfigHumidityLowCritical
-- }
-- DESCRIPTION
-- "CRITICAL: The humidity of sensor was lower than low critical set point."
-- ::= 20
END