EMAP-MIB DEFINITIONS ::= BEGIN
|
||
IMPORTS
|
||
huaweiUtility
|
||
FROM HUAWEI-MIB
|
||
OBJECT-GROUP, NOTIFICATION-GROUP
|
||
FROM SNMPv2-CONF
|
||
Integer32, Unsigned32, OBJECT-TYPE, MODULE-IDENTITY, NOTIFICATION-TYPE
|
||
FROM SNMPv2-SMI
|
||
TEXTUAL-CONVENTION
|
||
FROM SNMPv2-TC;
|
||
hwSiteMonitorMIB MODULE-IDENTITY
|
||
LAST-UPDATED "201210240000Z"
|
||
ORGANIZATION
|
||
"Huawei Technologies Co., Ltd."
|
||
CONTACT-INFO
|
||
"Floor 5, Block 4, R&D Building,
|
||
Huawei Longgang Production Base,
|
||
Shenzhen, P.R.C.
|
||
http: // www.huawei.com
|
||
Zip: 518129."
|
||
DESCRIPTION
|
||
"EMAP MIB defines MIB objects which provides load and backup management, patch management NMS interfaces.
|
||
The current version is v1.01"
|
||
REVISION "201210240000Z"
|
||
DESCRIPTION
|
||
"Huawei emap mib v1.00"
|
||
::= { huaweiUtility 164 }
|
||
|
||
DisplayString ::= TEXTUAL-CONVENTION
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
SYNTAX OCTET STRING (SIZE (1..64))
|
||
|
||
RowStatus ::= TEXTUAL-CONVENTION
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
SYNTAX INTEGER
|
||
{
|
||
active(1),
|
||
notInService(2),
|
||
notReady(3),
|
||
createAndGo(4),
|
||
createAndWait(5),
|
||
destroy(6)
|
||
}
|
||
|
||
DateAndTime ::= TEXTUAL-CONVENTION
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
SYNTAX OCTET STRING (SIZE (8..11))
|
||
|
||
RunStatus ::= TEXTUAL-CONVENTION
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This integer value represents running status of the system.
|
||
Depending on situation there may be limits on allowed values.
|
||
Operational values:
|
||
(1) unknown - status has not yet been defined
|
||
(2) normal - there are no activated alarms
|
||
(3) alarm - alarm status
|
||
"
|
||
SYNTAX INTEGER
|
||
{
|
||
unknow(1),
|
||
normal(2),
|
||
alarm(3)
|
||
}
|
||
|
||
MeasuresRange ::= TEXTUAL-CONVENTION
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
SYNTAX Integer32
|
||
|
||
TruthValue ::= TEXTUAL-CONVENTION
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
SYNTAX INTEGER
|
||
{
|
||
true(1),
|
||
false(2)
|
||
}
|
||
hwSiteMonitorMIBObjects OBJECT IDENTIFIER ::= { hwSiteMonitorMIB 1 }
|
||
|
||
hwSiteInfo OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 1 }
|
||
|
||
hwSiteSummary OBJECT IDENTIFIER ::= { hwSiteInfo 1 }
|
||
|
||
hwSiteId OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..64))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Site ID, default value: 000,000.Naming rule of the site device ID (six digits):
|
||
The first three digits indicate the device name and the last three digits indicate the serial number (SN) of the device.
|
||
If the last three digits are 000, it indicates a virtual device."
|
||
::= { hwSiteSummary 1 }
|
||
|
||
hwSiteName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Site name, which users can configure, is used to specify a site. Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwSiteSummary 2 }
|
||
|
||
hwSiteAdminAddr OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..65535)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Site administrant address, which users can assigned, is the unique ID of a site.
|
||
It is used for device management by NMS, and value range is 0 to 65535. "
|
||
::= { hwSiteSummary 3 }
|
||
|
||
hwSiteDescription OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Site description. It is of the character string type. It is used to describe the site information such as the site location, which users can configure.
|
||
Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwSiteSummary 4 }
|
||
|
||
hwNetIdentifier OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"NE ID. It is of the character string type. It is the unique ID of the site (an independent network element (NE)) on the network.
|
||
Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwSiteSummary 5 }
|
||
|
||
hwSiteIp OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (8..16))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Site IP address, default value is 192.168.0.10. Users need to configure the site IP address."
|
||
::= { hwSiteSummary 6 }
|
||
|
||
hwSiteNetmask OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (8..16))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Site netmask, default value is 255.255.255.0. Users need to configure the site netmask."
|
||
::= { hwSiteSummary 7 }
|
||
|
||
hwSiteGateway OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (8..16))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Site gateway, default value: 192.168.0.1. Users need to configure the site gateway."
|
||
::= { hwSiteSummary 8 }
|
||
|
||
hwSiteDGWorkStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
idle(1),
|
||
working(2),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the diesel working state. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the diesel is in the idle state;
|
||
If the enumeration value is 2, it indicates that the diesel is in the working state;
|
||
If the enumeration value is 255, it indicates diesel operation status unknown."
|
||
::= { hwSiteSummary 9 }
|
||
|
||
hwSiteRunningStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
alarm(2)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the site alarm state. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the site is in the normal state;
|
||
If the enumeration value is 2, it indicates that the site is in the alarm state."
|
||
::= { hwSiteSummary 10 }
|
||
|
||
hwSiteSystemEsn OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (8..16))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"System ESN Report Neteco"
|
||
::= { hwSiteSummary 12 }
|
||
|
||
hwSiteTime OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..64))
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Set Site date and time, YYYY-MM-DD HH:MM:SS"
|
||
::= { hwSiteSummary 13 }
|
||
|
||
hwSiteNetecoPrimaryServerIP OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (8..16))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Neteco Primary Server IP Address"
|
||
::= { hwSiteSummary 14 }
|
||
|
||
hwSiteNetecoBackupServerIP OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (8..16))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Neteco Backup Server IP Address"
|
||
::= { hwSiteSummary 15 }
|
||
|
||
hwSiteNetecoPortNumber OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Neteco Port Number"
|
||
::= { hwSiteSummary 16 }
|
||
|
||
hwSiteAlarms OBJECT IDENTIFIER ::= { hwSiteInfo 2 }
|
||
|
||
hwDeviceTrapOrdinalNumber OBJECT-TYPE
|
||
SYNTAX Unsigned32 ( 0..4294967295)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Site device event trap serial number (SN) is the unique ID of the device event trap. It is used to resend and synchronize event traps.
|
||
Its value range is 0 to 4294967295. When the value exceeds the maximum value, the system automatically clears the value and numbers the alarm from 0 to 4294967295.
|
||
If the network management system (NMS) recieve the alarm number is not consequential, in such case that it notifies the SNMP agent the event trap number required.
|
||
So the monitor send the 100 event trap messages in maximum, after consequencial number required by NMS again. Specially, if NMS set the value to 0, the agent would clear the alarm queue automatically."
|
||
::= { hwSiteAlarms 1 }
|
||
|
||
hwAlarmTrapOrdinalNumber OBJECT-TYPE
|
||
SYNTAX Unsigned32 ( 0..4294967295)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Site alarm serial number (SN) is the unique ID of the alarm Trap. It is used to resend and synchronize alarms. Its value range is 0 to 4294967295. When the value exceeds the maximum value, the system automatically clears the value and numbers the alarm from 0 to 4294967295.
|
||
If the network management system (NMS) recieve the alarm number is not consequential, in such case that it notifies the SNMP agent the alarm number required. So the monitor send the 100 alarm messages in maximum, after consequencial number required by NMS again. Specially, if NMS set the value to 0, the agent would clear the alarm queue automatically."
|
||
::= { hwSiteAlarms 2 }
|
||
|
||
hwAlarmQuantity OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..65535)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Alarm number in site alarm list which are support.
|
||
It is used for alarm list management by NMS, and value range is 0 to 65535. "
|
||
::= { hwSiteAlarms 3 }
|
||
|
||
hwSiteActiveAlarmTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwSiteActiveAlarmEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
""
|
||
::= { hwSiteAlarms 99 }
|
||
|
||
hwSiteActiveAlarmEntry OBJECT-TYPE
|
||
SYNTAX HwSiteActiveAlarmEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
""
|
||
INDEX { hwActiveAlarmIndex }
|
||
::= { hwSiteActiveAlarmTable 1 }
|
||
|
||
HwSiteActiveAlarmEntry ::= SEQUENCE {
|
||
hwActiveAlarmIndex
|
||
Integer32,
|
||
hwActiveAlarmText
|
||
OCTET STRING,
|
||
hwActiveAlarmLevel
|
||
INTEGER,
|
||
hwActiveAlarmSigDesc
|
||
OCTET STRING,
|
||
hwActiveAlarmTime
|
||
OCTET STRING,
|
||
hwActiveAlarmRowStatus
|
||
RowStatus,
|
||
hwSMUSiteName
|
||
OCTET STRING,
|
||
hwSMUSiteAdminAddr
|
||
Unsigned32,
|
||
hwSMUNetIdentifier
|
||
OCTET STRING,
|
||
hwSMUSiteDescription
|
||
OCTET STRING,
|
||
hwEquipId
|
||
Unsigned32,
|
||
hwEquipName
|
||
OCTET STRING
|
||
}
|
||
|
||
hwActiveAlarmIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (1..65535)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Site active alarm table index. It is the unique ID of the site alarm."
|
||
::= { hwSiteActiveAlarmEntry 1 }
|
||
|
||
hwActiveAlarmText OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Active alarm name. It is of the character string type, and used to specify the content of a specific alarm. "
|
||
::= { hwSiteActiveAlarmEntry 2 }
|
||
|
||
hwActiveAlarmLevel OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
critical(1),
|
||
major(2),
|
||
minor(3),
|
||
warning(4),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Active alarm level, which users can configure the alarm severity, is an enumeration type:
|
||
If the enumeration value is 1, it indicates a critical alarm;
|
||
If the enumeration value is 2, it indicates a major alarm;
|
||
If the enumeration value is 3, it indicates a minor alarm;
|
||
If the enumeration value is 4, it indicates a warning;
|
||
If the enumeration value is 255, it indicates a unknown;"
|
||
::= { hwSiteActiveAlarmEntry 3 }
|
||
|
||
hwActiveAlarmSigDesc OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..127))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Active alarm signal description. It is used to add and describe alarm content. Users can define the description of the alarm.
|
||
Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwSiteActiveAlarmEntry 4 }
|
||
|
||
hwActiveAlarmTime OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..127))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Active alarm time. It is of the character string type, and used to specify the content of a specific alarm. "
|
||
::= { hwSiteActiveAlarmEntry 5 }
|
||
|
||
hwActiveAlarmRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-create
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rowstatus of active alarm table."
|
||
::= { hwSiteActiveAlarmEntry 100 }
|
||
|
||
hwSMUSiteName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Site name, which users can configure, is used to specify a site. Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwSiteActiveAlarmEntry 6 }
|
||
|
||
hwSMUSiteAdminAddr OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..65535)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Site administrant address, which users can assigned, is the unique ID of a site. It is used for device management by NMS, and value range is 0 to 65535. "
|
||
::= { hwSiteActiveAlarmEntry 7 }
|
||
|
||
hwSMUNetIdentifier OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"NE ID. It is of the character string type. It is the unique ID of the site (an independent network element (NE)) on the network. Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwSiteActiveAlarmEntry 8 }
|
||
|
||
hwSMUSiteDescription OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Site description. It is of the character string type. It is used to describe the site information such as the site location, which users can configure. Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwSiteActiveAlarmEntry 9 }
|
||
|
||
hwEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Equipment ID. Value range: 000,000 to 000,100, in which the first three digits indicate the device type and the last three digits indicate the device SN. "
|
||
::= { hwSiteActiveAlarmEntry 10 }
|
||
|
||
hwEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Equipment name. It is of the character string type, and users can set the name of the monitor.
|
||
Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwSiteActiveAlarmEntry 11 }
|
||
|
||
hwSiteAlarmTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwSiteAlarmEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwSiteAlarms 100 }
|
||
|
||
hwSiteAlarmEntry OBJECT-TYPE
|
||
SYNTAX HwSiteAlarmEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
INDEX { hwAlarmIndex }
|
||
::= { hwSiteAlarmTable 1 }
|
||
|
||
HwSiteAlarmEntry ::= SEQUENCE {
|
||
hwAlarmIndex
|
||
Unsigned32,
|
||
hwAlarmText
|
||
OCTET STRING,
|
||
hwAlarmLevel
|
||
INTEGER,
|
||
hwAlarmSigDesc
|
||
OCTET STRING,
|
||
hwAlarmRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwAlarmIndex OBJECT-TYPE
|
||
SYNTAX Unsigned32 (1..4294967295)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Site alarm table index. It is the unique ID of the site alarm."
|
||
::= { hwSiteAlarmEntry 1 }
|
||
|
||
hwAlarmText OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Alarm name. It is of the character string type, and used to specify the content of a specific alarm. "
|
||
::= { hwSiteAlarmEntry 2 }
|
||
|
||
hwAlarmLevel OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
critical(1),
|
||
major(2),
|
||
minor(3),
|
||
warning(4),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Alarm level, which users can configure the alarm severity, is an enumeration type:
|
||
If the enumeration value is 1, it indicates a critical alarm;
|
||
If the enumeration value is 2, it indicates a major alarm;
|
||
If the enumeration value is 3, it indicates a minor alarm;
|
||
If the enumeration value is 4, it indicates a warning; "
|
||
::= { hwSiteAlarmEntry 3 }
|
||
|
||
hwAlarmSigDesc OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..127))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Alarm signal description. It is used to add and describe alarm content. Users can define the description of the alarm.
|
||
Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwSiteAlarmEntry 4 }
|
||
|
||
hwAlarmRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-create
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus of site alarms table."
|
||
::= { hwSiteAlarmEntry 100 }
|
||
|
||
hwSiteStatus OBJECT IDENTIFIER ::= { hwSiteInfo 3 }
|
||
|
||
hwAcInputStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
noalarm(0),
|
||
alarm(1),
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC fail
|
||
0: no alarm, 1:alarm"
|
||
::= { hwSiteStatus 1 }
|
||
|
||
hwRectifierStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
noalarm(0),
|
||
alarm(1),
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rectifier fault
|
||
0: no alarm, 1:alarm"
|
||
::= { hwSiteStatus 2 }
|
||
|
||
hwBatteryDischarge OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
noalarm(0),
|
||
alarm(1),
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery discharge
|
||
0: no alarm, 1:alarm"
|
||
::= { hwSiteStatus 3 }
|
||
|
||
hwBatteryLowVoltage OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
noalarm(0),
|
||
alarm(1),
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery low voltage
|
||
0: no alarm, 1:alarm"
|
||
::= { hwSiteStatus 4 }
|
||
|
||
hwBatteryUltraLowVoltage OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
noalarm(0),
|
||
alarm(1),
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery ultra-low voltage
|
||
0: no alarm, 1:alarm"
|
||
::= { hwSiteStatus 5 }
|
||
|
||
hwBatteryDisconnect OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
noalarm(0),
|
||
alarm(1),
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery disconnect
|
||
0: no alarm, 1:alarm"
|
||
::= { hwSiteStatus 6 }
|
||
|
||
hwFuseBroken OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
noalarm(0),
|
||
alarm(1),
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Load fuse or battery fuse broken
|
||
0: no alarm, 1:alarm"
|
||
::= { hwSiteStatus 7 }
|
||
|
||
hwLowRecitiferCapacity OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
noalarm(0),
|
||
alarm(1),
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"large load current and low rectifier capacity
|
||
0: no alarm, 1:alarm"
|
||
::= { hwSiteStatus 8 }
|
||
|
||
hwBatteryTestNegative OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
noalarm(0),
|
||
alarm(1),
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery test result negative
|
||
0: no alarm, 1:alarm"
|
||
::= { hwSiteStatus 9 }
|
||
|
||
hwUrgentAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
noalarm(0),
|
||
alarm(1),
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Urgent Alarm
|
||
0: no alarm, 1:alarm"
|
||
::= { hwSiteStatus 10 }
|
||
|
||
hwNonurgentAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
noalarm(0),
|
||
alarm(1),
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Non-Urgent Alarm
|
||
0: no alarm, 1:alarm"
|
||
::= { hwSiteStatus 11 }
|
||
|
||
hwSiteMonitors OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 2 }
|
||
|
||
hwMonitorsGroup OBJECT IDENTIFIER ::= { hwSiteMonitors 1 }
|
||
|
||
hwMonsGroupId OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Site monitor group ID, is the unique ID of the site monitors."
|
||
::= { hwMonitorsGroup 1 }
|
||
|
||
hwMonsGroupName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Site monitor group name is of the character string type, used to specify the monitor group. Users can configure it. Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwMonitorsGroup 2 }
|
||
|
||
hwMonsQuantity OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Total site intelligent monitors. Units:pcs."
|
||
::= { hwMonitorsGroup 3 }
|
||
|
||
hwMonitor OBJECT IDENTIFIER ::= { hwSiteMonitors 2 }
|
||
|
||
hwMonitorTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwMonitorEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwMonitor 1 }
|
||
|
||
hwMonitorEntry OBJECT-TYPE
|
||
SYNTAX HwMonitorEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
INDEX { hwMonIndex }
|
||
::= { hwMonitorTable 1 }
|
||
|
||
HwMonitorEntry ::= SEQUENCE {
|
||
hwMonIndex
|
||
Integer32,
|
||
hwMonEquipId
|
||
Unsigned32,
|
||
hwMonEquipName
|
||
OCTET STRING,
|
||
hwMonEquipDescription
|
||
OCTET STRING,
|
||
hwMonEquipSoftwareVersion
|
||
OCTET STRING,
|
||
hwMonEquipPcbVersion
|
||
OCTET STRING,
|
||
hwMonEquipManufacturer
|
||
OCTET STRING,
|
||
hwMonEquipManuDate
|
||
OCTET STRING,
|
||
hwMonEquipSerialNo
|
||
OCTET STRING,
|
||
hwMonEquipOperTotalTime
|
||
Unsigned32,
|
||
hwSetMonEquipCtrlState
|
||
INTEGER,
|
||
hwCtrlMonEquipReset
|
||
INTEGER,
|
||
hwMonitorOperStatus
|
||
INTEGER,
|
||
hwMonRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwMonIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (1..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Table index of the site monitors (hwSiteMonitorTable) is restricted by the quantity of the site monitors (hwMonsQuantity).
|
||
Value range: 1 to 100."
|
||
::= { hwMonitorEntry 1 }
|
||
|
||
hwMonEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Site monitor ID.
|
||
Value range: 001,001 to 001,100, in which the first three digits indicate the device type and the last three digits indicate the device SN. "
|
||
::= { hwMonitorEntry 2 }
|
||
|
||
hwMonEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Monitor name. It is of the character string type, and users can set the name of the monitor.
|
||
Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwMonitorEntry 3 }
|
||
|
||
hwMonEquipDescription OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Monitor description. It is of the character string type. Users can set the description of the monitor.
|
||
Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwMonitorEntry 4 }
|
||
|
||
hwMonEquipSoftwareVersion OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Monitor software version. It is of the character string type."
|
||
::= { hwMonitorEntry 5 }
|
||
|
||
hwMonEquipPcbVersion OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Monitor printed circuit board (PCB) hardware version. It is of the character string type."
|
||
::= { hwMonitorEntry 6 }
|
||
|
||
hwMonEquipManufacturer OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Monitor manufacture. It is of the character string type, and is an inherent attribute of the device."
|
||
::= { hwMonitorEntry 7 }
|
||
|
||
hwMonEquipManuDate OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..127))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Monitor production date. It is of the character string type, and is an inherent attribute of the device. "
|
||
::= { hwMonitorEntry 8 }
|
||
|
||
hwMonEquipSerialNo OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..127))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Production SN of the monitor. It is the electronic tag of the products."
|
||
::= { hwMonitorEntry 9 }
|
||
|
||
hwMonEquipOperTotalTime OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..65535)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Total monitor runtime. The monitor counts the data in real time.
|
||
Value range is 0 to 65535,
|
||
The value is an integer (1),
|
||
Units:hours. (h).
|
||
It is used for performance measurement and evaluation of the monitor."
|
||
::= { hwMonitorEntry 10 }
|
||
|
||
hwSetMonEquipCtrlState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
manualMode(1),
|
||
autoMode(2),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Monitor control status. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates the background control;
|
||
If the enumeration value is 2, it indicates the automatic control.
|
||
If the enumeration value is 255, it indicates monitor module operation status unknown.
|
||
In manual state, monitor works under background commands; while monitors runs well automatically in auto state.
|
||
For details, see the corresponding user manual of the monitor."
|
||
::= { hwMonitorEntry 11 }
|
||
|
||
hwCtrlMonEquipReset OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
reset(2),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Warm-reset control of the monitor. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates the Warm-reset control of the monitor is normal;
|
||
If the enumeration value is 2, it indicates the Warm-reset control of the monitor is reset.
|
||
If the enumeration value is 255, it indicates the Warm-reset control of the monito is unknown. "
|
||
::= { hwMonitorEntry 12 }
|
||
|
||
hwMonitorOperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
commRs485Fail(2),
|
||
commNetFail(3),
|
||
fault(4),
|
||
alarmResume(254),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the site monitor module. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the site monitor module is in the normal state;
|
||
If the enumeration value is 2, it indicates that the monitor module RS485 port communication failed;
|
||
If the enumeration value is 3, it indicates that the monitor module net port communication failed;
|
||
If the enumeration value is 4, it indicates that a fault occurs on the monitor module;
|
||
If the enumeration value is 254, it indicates monitor module alarm resume;
|
||
If the enumeration value is 255, it indicates monitor module operation status unknown. "
|
||
::= { hwMonitorEntry 99 }
|
||
|
||
hwMonRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-create
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus of site monitor."
|
||
::= { hwMonitorEntry 100 }
|
||
|
||
hwSiteRectifiers OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 3 }
|
||
|
||
hwRectsGroup OBJECT IDENTIFIER ::= { hwSiteRectifiers 1 }
|
||
|
||
hwRectsGroupId OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Device group ID of the rectifier module. It is the unique ID of the rectifier module group, and its default value: 002,000.
|
||
The first digits indicate the device type and the last three digits indicate the device SN. If the last three digits are 000, it indicates a virtual device. "
|
||
::= { hwRectsGroup 1 }
|
||
|
||
hwRectsGroupName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Name of the rectifier module group, character string type, is used to specify the rectifier module group. Users can configure it.
|
||
Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwRectsGroup 2 }
|
||
|
||
hwRectsTotalCurrent OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..200000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Total current of the rectifier module group on the site. It indicates the real-time statistics of the rectifier module group on the site.
|
||
Default value: 0 to 20000,
|
||
units: A,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwRectsGroup 3 }
|
||
|
||
hwRectsTotalQuantity OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..256)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Total quantity of the rectifier modules.
|
||
Value range: 0 to 256. Units:pcs."
|
||
::= { hwRectsGroup 4 }
|
||
|
||
hwRectsRatedVoltage OBJECT-TYPE
|
||
SYNTAX Unsigned32 (420..583)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rated voltage of the rectifier module group. It is an inherent attribute.
|
||
Value range: 42 to 58.3,
|
||
Units: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwRectsGroup 5 }
|
||
|
||
hwModifyRectsOutputVoltage OBJECT-TYPE
|
||
SYNTAX Unsigned32 (410..590)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Voltage adjustment of the rectifier module, which users can configure it.
|
||
Value range: 41 to 59,
|
||
Units: V,
|
||
and the value is accurate to one decimal space (.1).
|
||
Based on the actual requirements, users can modify the output voltage of the rectifier module by modifying the value of the node.
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
||
NOTES: Be cautious about changing the value of the node. Only the system in manual mode, this parameter can be configured successfully."
|
||
::= { hwRectsGroup 6 }
|
||
|
||
hwSetRectsRedundEnable OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
disable(1),
|
||
enable(2),
|
||
funcNotSupport(3)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Sleep function of the rectifier module group on the site. It is an enumeration value:
|
||
If the NMS notifies the SNMP agent that this node is set to 1, it means to disable the sleep function of the rectifier module group;
|
||
If the NMS notifies the SNMP agent that this node is set to 2, it means to enable the sleep function of the rectifier module group.
|
||
If NMS get the node value is 3, it indicates that this function is not support,
|
||
and in such case the value set to the agent is invalid.
|
||
Default value: to disable the sleep function of the rectifier module group. For details, see the corresponding user manual of the monitor."
|
||
::= { hwRectsGroup 7 }
|
||
|
||
hwCtrlRectsAllOnOff OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
on(1),
|
||
off(2),
|
||
nullOper(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Power-on or power-off of the rectifier module group (all the rectifier modules) on the site. It is an enumeration value:
|
||
If the NMS notifies the SNMP agent that this node is set to 1, it indicates power-on of all rectifier modules;
|
||
If the NMS notifies the SNMP agent that this node is set to 2, it indicates power-off of all the rectifier modules;
|
||
If the NMS notifies the SNMP agent that this node is set to 255, it indicates nullOper of all the rectifier modules.
|
||
NOTE: Only the system in manual mode, this parameter can be configured successfully."
|
||
::= { hwRectsGroup 8 }
|
||
|
||
hwRectsTotalDCPower OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100000000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Total power of the direct current output.
|
||
Value range: 0 to 100000000,
|
||
units: W,
|
||
and the value is an integer.
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwRectsGroup 9 }
|
||
|
||
hwRectsLoadUsage OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..150)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Load Usage.
|
||
Value range: 0 to 150,
|
||
units: %,
|
||
and the value is an integer.
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwRectsGroup 10 }
|
||
|
||
hwRectsTotalACInputPower OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100000000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Total power of the direct current output.
|
||
Value range: 0 to 100000000,
|
||
units: W,
|
||
and the value is an integer.
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwRectsGroup 11 }
|
||
|
||
hwRectsHighRectifierCapacity OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..150)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"High rectifier capacity.
|
||
Value range: 0 to 150,
|
||
units: %,
|
||
and the value is an integer.
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwRectsGroup 12 }
|
||
|
||
hwRectsLowRectifierCapacity OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..150)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Low rectifier capacity.
|
||
Value range: 0 to 150,
|
||
units: %,
|
||
and the value is an integer.
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwRectsGroup 13 }
|
||
|
||
hwRectsOverVoltProtThres OBJECT-TYPE
|
||
SYNTAX Unsigned32 (560..605)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Overvoltage protection threshold.
|
||
Value range: 56.0 to 60.5,
|
||
units: V,
|
||
and the value is accurate to one decimal space (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwRectsGroup 14 }
|
||
|
||
hwRectifier OBJECT IDENTIFIER ::= { hwSiteRectifiers 2 }
|
||
|
||
hwRectConfigTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwRectConfigEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rectifier config information table. Use this table to get rectifiers equipment ID, software version, manufacturer, rated current, efficency, AC input type, and to control equipment on or off.
|
||
This table's index is hwRectConfigIndex, clone Rectifier config information table."
|
||
::= { hwRectifier 1 }
|
||
|
||
hwRectConfigEntry OBJECT-TYPE
|
||
SYNTAX HwRectConfigEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rectifier config information table. Use this table to get rectifiers equipment ID, software version, manufacturer, rated current, efficency, AC input type, and to control equipment on or off.
|
||
This table's index is hwRectConfigIndex, clone Rectifier config information table."
|
||
INDEX { hwRectConfigIndex }
|
||
::= { hwRectConfigTable 1 }
|
||
|
||
HwRectConfigEntry ::= SEQUENCE {
|
||
hwRectConfigIndex
|
||
Integer32,
|
||
hwRectEquipId
|
||
Unsigned32,
|
||
hwRectEquipName
|
||
OCTET STRING,
|
||
hwRectType
|
||
INTEGER,
|
||
hwRectSoftwareVersion
|
||
OCTET STRING,
|
||
hwRectManufacturer
|
||
OCTET STRING,
|
||
hwRectManuDate
|
||
OCTET STRING,
|
||
hwRectSerialNo
|
||
OCTET STRING,
|
||
hwRectRatedCurrent
|
||
Unsigned32,
|
||
hwRectEfficency
|
||
Unsigned32,
|
||
hwRectInputAcType
|
||
INTEGER,
|
||
hwCtrlRectOnOff
|
||
INTEGER,
|
||
hwRectConfigRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwRectConfigIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (1..256)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Index of the device configuration list for the rectifier modules, which value range: 1 to 256(To the actual subject). Lines of the device list are restricted by the total quantity of the rectifier modules (hwRectsTotalQuantity)."
|
||
::= { hwRectConfigEntry 1 }
|
||
|
||
hwRectEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rectifier module ID. Value range: 002'001 to 002'255. The first digits indicate the device type and last three digits indicate the device SN. "
|
||
::= { hwRectConfigEntry 2 }
|
||
|
||
hwRectEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Device name of the rectifier module, character string type, is used to specify the rectifier module. Users can configure it.
|
||
Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwRectConfigEntry 3 }
|
||
|
||
hwRectType OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
eps5(1),
|
||
eps15(2),
|
||
eps30(3),
|
||
eps50(4),
|
||
eps100(5),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Specific type of the rectifier module. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates a 5A rectifier module;
|
||
If the enumeration value is 2, it indicates a 15A rectifier module;
|
||
If the enumeration value is 3, it indicates a 30A rectifier module;
|
||
If the enumeration value is 4, it indicates a 50A rectifier module;
|
||
If the enumeration value is 5, it indicates a 100A rectifier module."
|
||
::= { hwRectConfigEntry 4 }
|
||
|
||
hwRectSoftwareVersion OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Software version of the rectifier module. It indicates the software version ID of the module. "
|
||
::= { hwRectConfigEntry 5 }
|
||
|
||
hwRectManufacturer OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Manufacture of the rectifier module."
|
||
::= { hwRectConfigEntry 6 }
|
||
|
||
hwRectManuDate OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..127))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Manufacture date of rectifiers is of string type."
|
||
::= { hwRectConfigEntry 7 }
|
||
|
||
hwRectSerialNo OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..127))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rectifier module SN. It indicates the electronic tag of the product."
|
||
::= { hwRectConfigEntry 8 }
|
||
|
||
hwRectRatedCurrent OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..2000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rated voltage of the rectifier module, is an inherent attribute.
|
||
Value range: 0 to 200, Units: A, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. "
|
||
::= { hwRectConfigEntry 9 }
|
||
|
||
hwRectEfficency OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Efficiency of the rectifier module, is an inherent attribute.
|
||
Value range: 0 to 100,
|
||
Units: %,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwRectConfigEntry 10 }
|
||
|
||
hwRectInputAcType OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
single(1),
|
||
triple(2),
|
||
threeLivelines(3),
|
||
doubleLiveLines(4),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Input AC type of the rectifier module. It is an enumeration value:
|
||
If the value of the node is 1, it indicates single-phase AC input;
|
||
If the value of the node is 2, it indicates three-phase AC input;
|
||
If the value of the node is 3, it indicates three-livelines AC input;
|
||
If the value of the node is 4, it indicates double-liveLines AC input;
|
||
If the value of the node is 255, it indicates unknown AC input.
|
||
"
|
||
::= { hwRectConfigEntry 11 }
|
||
|
||
hwCtrlRectOnOff OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
on(1),
|
||
off(2),
|
||
nullOper(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Power-on or power-off of the rectifier module, is an enumeration value. Users can modify the enumeration value of this node, thus controlling of the power-on or power-off of the rectifier module:
|
||
If the NMS notifies the SNMP agent that this node is set to 1, it indicates power-on of the rectifier module;
|
||
If the NMS notifies the SNMP agent that this node is set to 2, it indicates power-off of the rectifier module. "
|
||
::= { hwRectConfigEntry 12 }
|
||
|
||
hwRectConfigRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-create
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus of rectifier config table."
|
||
::= { hwRectConfigEntry 100 }
|
||
|
||
hwRectOperTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwRectOperEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rectifier runing information table. Use this table to get rectifiers output current, output voltage, totle runing time, and current run status.
|
||
This table's index is hwRectRunIndex, clone rectifier runing information table."
|
||
::= { hwRectifier 2 }
|
||
|
||
hwRectOperEntry OBJECT-TYPE
|
||
SYNTAX HwRectOperEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rectifier runing information table. Use this table to get rectifiers output current, output voltage, totle runing time, and current run status.
|
||
This table's index is hwRectRunIndex, clone rectifier runing information table."
|
||
INDEX { hwRectOperIndex }
|
||
::= { hwRectOperTable 1 }
|
||
|
||
HwRectOperEntry ::= SEQUENCE {
|
||
hwRectOperIndex
|
||
Integer32,
|
||
hwRectOutputCurrent
|
||
Unsigned32,
|
||
hwRectOutputVoltage
|
||
Unsigned32,
|
||
hwRectTotalOperTime
|
||
Unsigned32,
|
||
hwRectDCOutputPower
|
||
Unsigned32,
|
||
hwRectACVoltage
|
||
Unsigned32,
|
||
hwRectRatedEfficiency
|
||
Unsigned32,
|
||
hwRectifierTemperature
|
||
Integer32,
|
||
hwRectOperStatus
|
||
INTEGER,
|
||
hwRectOperRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwRectOperIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (1..256)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Table index of the running rectifier modules,
|
||
which value range: 1 to 256(To the actual subject).
|
||
Lines of the device list are restricted by the total quantity of the rectifier modules (hwRectsTotalQuantity)."
|
||
::= { hwRectOperEntry 1 }
|
||
|
||
hwRectOutputCurrent OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..3000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Output current of the rectifier module. It is a real-time analog parameter.
|
||
Value range: 0 to 300,
|
||
Units: A,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwRectOperEntry 2 }
|
||
|
||
hwRectOutputVoltage OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..650)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Output voltage of the rectifier module. It is a real-time analog parameter.
|
||
Value range: 0 to 65,
|
||
Units: V,
|
||
the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. "
|
||
::= { hwRectOperEntry 3 }
|
||
|
||
hwRectTotalOperTime OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Total runtime of the rectifier module.
|
||
Value units: minute (m),
|
||
and the value is an integer (1). "
|
||
::= { hwRectOperEntry 4 }
|
||
|
||
hwRectDCOutputPower OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..30000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DC output power.
|
||
Value range: 0 to 30000,
|
||
units: W,
|
||
and the value is an integer.(1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwRectOperEntry 5 }
|
||
|
||
hwRectACVoltage OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..6000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC input voltage.
|
||
Value range: 0 to 600,
|
||
units: V,
|
||
and the value is accurate to one decimal space (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwRectOperEntry 6 }
|
||
|
||
hwRectRatedEfficiency OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rated Efficiency.
|
||
Value range: 0 to 100,
|
||
units: %,
|
||
and the value is an integer.(1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwRectOperEntry 7 }
|
||
|
||
hwRectifierTemperature OBJECT-TYPE
|
||
SYNTAX Integer32 (-3000..3000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rectifier Temperature.
|
||
Value range: -300 to 300,
|
||
units: degC,
|
||
and the value is accurate to one decimal space (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwRectOperEntry 8 }
|
||
|
||
hwRectOperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
fault(2),
|
||
protect(3),
|
||
commFail(4),
|
||
switchOff(5),
|
||
invalid(6),
|
||
noConfig(7),
|
||
acOff(8),
|
||
rectLost(9),
|
||
alarmResume(254),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the rectifier module. It is an enumeration type:
|
||
If the enumeration value is 1, the rectifier module is in the normal state;
|
||
If the enumeration value is 2, a fault occurs on the rectifier module;
|
||
If the enumeration value is 3, automatic protection of the rectifier module;
|
||
If the enumeration value is 4, communication of the rectifier module fails;
|
||
If the enumeration value is 5, the rectifier module is shut down;
|
||
If the enumeration value is 6, the rectifier module is invalid;
|
||
If the enumeration value is 7, this rectifier is not configured;
|
||
If the enumeration value is 8, this rectifier is ac off;
|
||
If the enumeration value is 9, this rectifier is rectLost;
|
||
If the enumeration value is 254, rectifier alarm resume;
|
||
If the enumeration value is 255, rectifier operation status unknown."
|
||
::= { hwRectOperEntry 99 }
|
||
|
||
hwRectOperRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-create
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus of rectifier runing table."
|
||
::= { hwRectOperEntry 100 }
|
||
|
||
hwSiteBatterys OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 4 }
|
||
|
||
hwBattsConfig OBJECT IDENTIFIER ::= { hwSiteBatterys 1 }
|
||
|
||
hwBattsGroupId OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery group ID. It is the unique ID of the battery group device.
|
||
The first digits indicate the device type and the last three digits indicate the device SN.
|
||
If the last three digits are 000, it indicates a virtual device. "
|
||
::= { hwBattsConfig 1 }
|
||
|
||
hwBattsGroupName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Device name of the battery group. It is of the character string type, which can be configured by users.
|
||
Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwBattsConfig 2 }
|
||
|
||
hwBattsTotalQuantity OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Total quantity of battery strings,
|
||
which value range: 0 to 100.
|
||
Units:strings."
|
||
::= { hwBattsConfig 3 }
|
||
|
||
hwSetBattsHighTempAction OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
blvd(1),
|
||
lowerDcOutput(2),
|
||
disable(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery high-temperature protection mode. It is an enumeration value, and can be configured.
|
||
If the enumeration value is 1, it indicates the power-off protection mode;
|
||
If the enumeration value is 2, it indicates the protection mode of lowering the output voltage of the rectifier module.
|
||
If the enumeration value is 255, it indicates do nothing. "
|
||
::= { hwBattsConfig 4 }
|
||
|
||
hwSetBattsHighTempVoltLimit OBJECT-TYPE
|
||
SYNTAX Unsigned32 (420..530)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery protection voltage under high temperature. It works with the low-voltage power-off protection in battery high-temperature protection mode, which can be configured by users.
|
||
If the low-voltage power-off protection mode (that is, the enumeration value is 1) is selected, the node is a low-voltage power-off node.
|
||
Value range: 42 to 53,
|
||
units: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwBattsConfig 5 }
|
||
|
||
hwSetBattsHTDLimit OBJECT-TYPE
|
||
SYNTAX Integer32 (25..80)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Upper threshold of the battery high temperature disconnection(HTD), can be configured by users.
|
||
Value range: 25 to 80,
|
||
Units: centigrade (degC),
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
||
NOTE: There is linkage between hwSetBattsHTDLimit and hwSetBattsTempUpperLimit"
|
||
::= { hwBattsConfig 6 }
|
||
|
||
hwSetBattsHTDEnable OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
enable(1),
|
||
disable(2)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery high temperature disconnection enable. It is an enumeration type:
|
||
If the enumeration value is 1, enable the operation of the battery disconnection in high temperature;
|
||
If the enumeration value is 2, disable the operation of the battery disconnection in high temperature.
|
||
The operation of the battery disconnection in high temperature is disabled by default. "
|
||
::= { hwBattsConfig 7 }
|
||
|
||
hwSetBattsFloatVoltage OBJECT-TYPE
|
||
SYNTAX Unsigned32 (420..583)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Float charge voltage of the batteries, can be configured by users.
|
||
Value range: 42 to 58.3,
|
||
units: V,
|
||
and the value is accurate to one decimal place (.1)
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
||
NOTE: There is linkage between hwSetBattsFloatVoltage and hwSetBattsBoostVoltage
|
||
"
|
||
::= { hwBattsConfig 8 }
|
||
|
||
hwSetBattsBoostVoltage OBJECT-TYPE
|
||
SYNTAX Unsigned32 (420..583)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Boostcharge voltage of the batteries, can be configured by users.
|
||
Value range: 42 to 58.3,
|
||
units: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
||
NOTE: There is linkage between hwSetBattsFloatVoltage and hwSetBattsBoostVoltage"
|
||
::= { hwBattsConfig 9 }
|
||
|
||
hwSetBattsCurrLimitCoefficient OBJECT-TYPE
|
||
SYNTAX Unsigned32 (5..50)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Current-limiting point coefficient of the batteries, can be configured by users.
|
||
Value range: 0.05 to 0.5,
|
||
units: C10,
|
||
and the value is accurate to two decimal places (.01).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
||
There is linkage between hwSetBattsChargeOvercurAlmThreshold and hwSetBattsCurrLimitCoefficient.
|
||
Current-limiting point coefficient must be less than or equal to the charge overcurrent alarm threshold."
|
||
::= { hwBattsConfig 10 }
|
||
|
||
hwSetBattsCompFactor OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..500)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temperature compensated coefficient of the batteries, can be configured by user.
|
||
Value range: 0 to 500,
|
||
units: mv per centigrade,
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwBattsConfig 11 }
|
||
|
||
hwCtrlBattsBoostFloat OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
floatCharge(1),
|
||
boostCharge(2),
|
||
nullOper(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Control batteries charge mode between boost and float. It is an enumeration value.
|
||
Users actively control the conversion.
|
||
If the NMS notifies the SNMP agent that this node is set to 1, it means to start the float charge mode of the batteries;
|
||
If the NMS notifies the SNMP agent that this node is set to 2, it means to start the boost charge mode of the batteries.
|
||
If the NMS notifies the SNMP agent that this node is set to 255, it means to start the mode of the batteries is nullOper. "
|
||
::= { hwBattsConfig 12 }
|
||
|
||
hwSetBattsRatedCapacity OBJECT-TYPE
|
||
SYNTAX Unsigned32 (5..10000)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Set batteries rated capacity. It is an analog parameter collected by the battery string in real time.
|
||
Value range: 5 to 10000,
|
||
units: Ah,
|
||
the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwBattsConfig 13 }
|
||
|
||
hwSetBattsTimedBoostChargeEnabled OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
disable(1),enable(2),unknown(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Timed Boost Charge Enabled. It is an enumeration value, and can be configured.
|
||
If the enumeration value is 1, it indicates timed boost charge is disabled;
|
||
If the enumeration value is 2, it indicates timed boost charge is enabled.
|
||
If the enumeration value is 255, it indicates timed boost charge is unknown. "
|
||
::= { hwBattsConfig 14 }
|
||
|
||
hwSetBattsTimedBoostChargePeriod OBJECT-TYPE
|
||
SYNTAX Unsigned32 (1..365)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Timed Boost Charge Interval.
|
||
Value range: 1 to 365,
|
||
units: Day,
|
||
and the value is an integer.(1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwBattsConfig 15 }
|
||
|
||
hwSetBattsMaxTimedBCDuration OBJECT-TYPE
|
||
SYNTAX Unsigned32 (1..24)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Maximum Timed Boost Charge Duration.
|
||
Value range: 1 to 24,
|
||
units: h,
|
||
and the value is an integer.(1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwBattsConfig 16 }
|
||
|
||
hwSetBattsChargeOvercurAlmThreshold OBJECT-TYPE
|
||
SYNTAX Unsigned32 (5..100)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Charge Overcurrent Alarm Threshold.
|
||
Value range: 0.05 to 1,
|
||
units: C10,
|
||
and the value is accurate to two decimal space (.01).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
||
There is linkage between hwSetBattsChargeOvercurAlmThreshold and hwSetBattsCurrLimitCoefficient.
|
||
Current-limiting point coefficient must be less than or equal to the charge overcurrent alarm threshold."
|
||
::= { hwBattsConfig 17 }
|
||
|
||
hwSetBattsLowCapacityAlarmThreshold OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..90)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Low Capacity Alarm Threshold.
|
||
Value range: 0 to 90,
|
||
units: %,
|
||
and the value is an integer. (1)
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwBattsConfig 18 }
|
||
|
||
hwBattsOperate OBJECT IDENTIFIER ::= { hwSiteBatterys 2 }
|
||
|
||
hwBattsTotalCurrent OBJECT-TYPE
|
||
SYNTAX Integer32 ( -4000000..4000000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Total current of the battery group. It indicates the real-time statistics of the battery group on the site.
|
||
Value range: -400000 to +400000,
|
||
units: A,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwBattsOperate 1 }
|
||
|
||
hwBattsPreDischargeTime OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..15360)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery group backup time. It indicates the real-time statistics of the battery group.
|
||
Value range: 0 to 15360,
|
||
Units: minutes (min),
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwBattsOperate 2 }
|
||
|
||
hwBattsChargeStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
floatCharge(1),
|
||
boostCharge(2),
|
||
disCharge(3),
|
||
hibernating(4),
|
||
offline(7),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery charging state, indicates the charging and discharging information about the battery group. It is an enumeration type.
|
||
If the enumeration value is 1, it indicates a battery group in the float charging state.
|
||
If the enumeration value is 2, it indicates a battery group in the boost charging state.
|
||
If the enumeration value is 3, it indicates a battery group in the discharging state.
|
||
If the enumeration value is 4, it indicates a battery group in the hibernating state.
|
||
If the enumeration value is 7, it indicates a battery group in the Offline state.
|
||
If the enumeration value is 7, it indicates a battery group in the Offline state. "
|
||
::= { hwBattsOperate 3 }
|
||
|
||
hwBattsCurrLimitStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
unlimited(1),
|
||
limited(2),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery group current-limiting state, indicates the state information about the battery group. It is an enumeration value.
|
||
If the enumeration value is 1, it indicates that the current of the battery group is not limited.
|
||
If the enumeration value is 2, it indicates the current of the battery group is limited.
|
||
If the enumeration value is 2, it indicates the current of the battery group is unknown. "
|
||
::= { hwBattsOperate 4 }
|
||
|
||
hwBattsTemprature1 OBJECT-TYPE
|
||
SYNTAX Integer32 ( -300..200)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery temperature. It is a battery parameter collected in real time.
|
||
Value range: -300 to 200,
|
||
unit: centigrade (degC),
|
||
and the value is an integer .
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that battery temperature sensor is not configured."
|
||
::= { hwBattsOperate 5 }
|
||
|
||
hwBattsTemprature2 OBJECT-TYPE
|
||
SYNTAX Integer32 ( -50..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery temperature. It is a battery parameter collected in real time.
|
||
Value range: -50 to +100,
|
||
unit: centigrade (degC),
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that battery temperature sensor is not configured."
|
||
::= { hwBattsOperate 6 }
|
||
|
||
hwBattsAlarmsClear OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
clearBattTestFailAlm(1),
|
||
clearBattTestCanceledAlm(2),
|
||
clearHighStrImpedanceAlm(3),
|
||
clearHighFloatCurrAlm(4),
|
||
clearCurrImbalanceAlm(5),
|
||
clearContactorFaultAlm(6),
|
||
nullOper(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery alarms clear. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates the clear batt test fail alarm ;
|
||
If the enumeration value is 2, it indicates the clear batt test canceled alarm .
|
||
If the enumeration value is 3, it indicates the clear high str impedance alarm .
|
||
If the enumeration value is 4, it indicates the clear high float current alarm .
|
||
If the enumeration value is 5, it indicates the clear current imbalance alarm .
|
||
If the enumeration value is 6, it indicates the clear contactor fault alarm .
|
||
If the enumeration value is 255, it indicates null oper(can't set to smu)."
|
||
::= { hwBattsOperate 7 }
|
||
|
||
hwBattsRatedCapacity OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..2147483647)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Batteries actual capacity.
|
||
It is an analog parameter collected by the battery string in real time.
|
||
Value range: 0 to 2147483647,
|
||
units: Ah,
|
||
the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwBattsOperate 8 }
|
||
|
||
hwBattsRemainCapacity OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..2147483647)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Remaining capacity of all of the battery.
|
||
It is an analog parameter collected by the battery string in real time.
|
||
Value range: 0 to 2147483647,
|
||
units: Ah,
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwBattsOperate 9 }
|
||
|
||
hwTotalRemainingCapacityPercent OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Total Remaining Capacity Percent.
|
||
Value range: 0 to 100, units: %,
|
||
and the value is an integer.(1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwBattsOperate 10 }
|
||
|
||
hwBattsTotalDischargeDepth OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery Total Discharge Depth Percent. Value range: 0 to 100, units: %, and the value is an integer. If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwBattsOperate 11 }
|
||
|
||
hwBattsTest OBJECT IDENTIFIER ::= { hwSiteBatterys 3 }
|
||
|
||
hwBattsTestRecordCount OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery test records number."
|
||
::= { hwBattsTest 1 }
|
||
|
||
hwSetBattsManuStdTestTime OBJECT-TYPE
|
||
SYNTAX Unsigned32 (1..6000)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery standard test time, It can be configured by users,
|
||
value range defines between 1 to 6000,
|
||
units: minutes(min).
|
||
and its value is an integer (1).
|
||
Here, if battery manual test is standard mode,
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwBattsTest 2 }
|
||
|
||
hwSetBattsManuStdTestEndVolt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (170..220)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Test end voltage of single battery, which can be configured by users.
|
||
value range defines between 1.7 to 2.2
|
||
Units: V/cell,
|
||
and the value is accurate to two decimal place (.01).
|
||
Here, if battery manual test is standard mode, . If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwBattsTest 3 }
|
||
|
||
hwSetBattsManuStdTestCellNum OBJECT-TYPE
|
||
SYNTAX Unsigned32 (1..50)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery cell number in each Group, which is used in the battery standard manual test, can be configured by users.
|
||
Units: psc or cell,
|
||
value range defines between 1 to 50.
|
||
and value is an integer (1)."
|
||
::= { hwBattsTest 4 }
|
||
|
||
hwSetBattsManuShortTestTime OBJECT-TYPE
|
||
SYNTAX Unsigned32 (1..240)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery short test time, It can be configured by users,
|
||
value range defines between 1 to 240,
|
||
units: minutes(min).
|
||
and its value is an integer (1).
|
||
If battery manual test is simple mode,
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwBattsTest 5 }
|
||
|
||
hwSetBattsManuShortTestEndVolt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (442..530)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Voltage when the battery short test is ended, can be configured by users. Here, if battery manual test is standard mode,
|
||
value range defines between 44.2 to 53,
|
||
Units: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwBattsTest 6 }
|
||
|
||
hwCtrlBattsTestStartStop OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
stdTestStart(1),
|
||
shortTestStart(2),
|
||
testStop(3),
|
||
nullOper(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery manualtest start and stop. It is an enumeration value.
|
||
If the value is 1, it means to start a standard manual test;
|
||
If the value is 2, it means to start a short manual test;
|
||
If the value is 3, it means to stop the battery test.
|
||
If the value is 255, it means null operate(can't set to smu);
|
||
Set the parameters, such as battery test time, and voltage when the battery test stops before the node controls the start of the battery test. If the parameters are not set this time, the system uses the configuration parameters by default; and if the battery test is started at the first time, the system uses the default value.
|
||
Battery test can only start up in some conditions, so that the reason of Start of battery short test failed may be as follow:
|
||
1. Interval between this test and the latest AC outage or test is longer than the preset duration.
|
||
2. No major alarm is raised.
|
||
3. The number of healthy modules is greater than 0.
|
||
4. The number of battery strings is greater than 0."
|
||
::= { hwBattsTest 7 }
|
||
|
||
hwBattsTestResultTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwBattsTestResultEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery test result record table.
|
||
Use this table to get battery test inital time, test result, battery efficiency, battery discharge time, terminated voltage, average current, discharge AH value, test temperature and test terminated course.
|
||
This table's index is hwBattsTestResultIndex, clone Battery test result record table."
|
||
::= { hwBattsTest 100 }
|
||
|
||
hwBattsTestResultEntry OBJECT-TYPE
|
||
SYNTAX HwBattsTestResultEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery test result record table.
|
||
Use this table to get battery test inital time, test result, battery efficiency, battery discharge time, terminated voltage, average current, discharge AH value, test temperature and test terminated course.
|
||
This table's index is hwBattsTestResultIndex, clone Battery test result record table."
|
||
INDEX { hwBattsTestResultIndex }
|
||
::= { hwBattsTestResultTable 1 }
|
||
|
||
HwBattsTestResultEntry ::= SEQUENCE {
|
||
hwBattsTestResultIndex
|
||
Integer32,
|
||
hwBattsTestType
|
||
INTEGER,
|
||
hwBattsTestStartTime
|
||
OCTET STRING,
|
||
hwBattsTestResult
|
||
INTEGER,
|
||
hwBattsEfficiency
|
||
Integer32,
|
||
hwBattsDischargeTime
|
||
Unsigned32,
|
||
hwBattsDischargeEndVoltage
|
||
Unsigned32,
|
||
hwBattsDischargeAvCurrent
|
||
Integer32,
|
||
hwBattsDischargeAhValue
|
||
Unsigned32,
|
||
hwBattsTestTemperature
|
||
Integer32,
|
||
hwBattsTestEndCourse
|
||
INTEGER,
|
||
hwBattsTestResultRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwBattsTestResultIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (1..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Table index of the battery test results. Currently up to 10 times of the battery test results are saved by default. "
|
||
::= { hwBattsTestResultEntry 1 }
|
||
|
||
hwBattsTestType OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
manualTest(1),
|
||
acOffAutoTest(2),
|
||
timedTest(3),
|
||
shortTest(4),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Record test type of the battery test. It is an enumeration value:
|
||
If the NMS notifies the SNMP agent that this node is set to 1, it indicates a manual test;
|
||
If the NMS notifies the SNMP agent that this node is set to 2, it indicates a simplified test;
|
||
If the NMS notifies the SNMP agent that this node is set to 3, it indicates a timed test;
|
||
If the NMS notifies the SNMP agent that this node is set to 4, it indicates a short test;
|
||
If the NMS notifies the SNMP agent that this node is set to 255, it indicates a other test."
|
||
::= { hwBattsTestResultEntry 2 }
|
||
|
||
hwBattsTestStartTime OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..127))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Test start time of the record in the battery test. It is of the character string type."
|
||
::= { hwBattsTestResultEntry 3 }
|
||
|
||
hwBattsTestResult OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
battNoResult(1),
|
||
battNormal(2),
|
||
battPreAlarm(3),
|
||
battAlarm(4),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery test result. It is an enumeration value.
|
||
If the enumeration value of the node is 1, it indicates that the battery test has no result:
|
||
If the enumeration value of the node is 2, it indicates that the battery is in the normal state:
|
||
If the enumeration value of the node is 3, it indicates that the battery is in the minor abnormal state,
|
||
If the enumeration value of the node is 4, it indicates that the battery is in the alarm state,
|
||
If the enumeration value of the node is 255, it indicates that the battery state is unknown,"
|
||
::= { hwBattsTestResultEntry 4 }
|
||
|
||
hwBattsEfficiency OBJECT-TYPE
|
||
SYNTAX Integer32 (0..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery efficiency test.
|
||
Value range: 0 to 100,
|
||
Units: %,
|
||
and the value is an integer (1).
|
||
If the value is -1, it indicates that the test value is inefficient.
|
||
If the value is 255, it indicates that the test value is invalid."
|
||
::= { hwBattsTestResultEntry 5 }
|
||
|
||
hwBattsDischargeTime OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Discharge time of the battery test records.
|
||
Value range: 0 to 100,
|
||
units: hour (h),
|
||
and the value is accurate to two decimal places (.01).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwBattsTestResultEntry 6 }
|
||
|
||
hwBattsDischargeEndVoltage OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..600)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Discharge termination voltage of the battery test.
|
||
Value range: 0 to 60,
|
||
units: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwBattsTestResultEntry 7 }
|
||
|
||
hwBattsDischargeAvCurrent OBJECT-TYPE
|
||
SYNTAX Integer32 ( -10000..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Average discharge current of the battery test.
|
||
Value range: -1000 to 1000,
|
||
units: A,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwBattsTestResultEntry 8 }
|
||
|
||
hwBattsDischargeAhValue OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..5000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Discharge ampere per hour the battery test.
|
||
Value range: 0 to 5000,
|
||
Units: Ah,
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwBattsTestResultEntry 9 }
|
||
|
||
hwBattsTestTemperature OBJECT-TYPE
|
||
SYNTAX Integer32 ( -50..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery temperature of the battery test termination.
|
||
Value range: -50 to +100,
|
||
Units: centigrade (degC),
|
||
and the value is an integer (1).
|
||
If the value is -1024, it indicates that no battery temperature value sensor is detected."
|
||
::= { hwBattsTestResultEntry 10 }
|
||
|
||
hwBattsTestEndCourse OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
voltageToEnd(1),
|
||
timeToEnd(2),
|
||
acOnToEnd(3),
|
||
manulToEnd(4),
|
||
faultAlarmToEnd(5),
|
||
lowCapacityToEnd(6),
|
||
lowTempToEnd(7),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Termination factors of the battery test. It is an enumeration value.
|
||
If the enumeration value is 1, it indicates that the voltage value of the battery test reaches the set termination voltage;
|
||
If the enumeration value is 2, it indicates that the voltage value of the battery test reaches the timing limit;
|
||
If the enumeration value is 3, it indicates that an alarm related to the battery leads to the stop of the battery test;
|
||
If the enumeration value is 4, it indicates that a battery test is stopped manually,
|
||
If the enumeration value is 5, it indicates that battery fault alarm happened,
|
||
If the enumeration value is 6, it indicates that battery low capacity happened,
|
||
If the enumeration value is 7, it indicates that battery low temp happened,
|
||
If the enumeration value is 255, it indicates that battery test end for other courses."
|
||
::= { hwBattsTestResultEntry 11 }
|
||
|
||
hwBattsTestResultRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-create
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus of battery test table."
|
||
::= { hwBattsTestResultEntry 100 }
|
||
|
||
hwSetBattsConsCurrTestEnable OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
disable(1),
|
||
enable(2)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery constant current test function enable or disable. It is an enumeration value.
|
||
If the value is 1, it means the function is disabled;
|
||
If the value is 2, it means the function is enabled."
|
||
::= { hwBattsTest 8 }
|
||
|
||
hwSetBattsConsCurrTestDischCurrent OBJECT-TYPE
|
||
SYNTAX Unsigned32 (1..9999)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The battery discharge current in the constant current test.
|
||
It is an integer value(range:1A~9999A) and the value is accurate to 1A."
|
||
::= { hwBattsTest 9 }
|
||
|
||
hwSetBattsTimeTestMode OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
disable(1),scheduledTest(3)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery constant current test function enable or disable.
|
||
It is an enumeration value.
|
||
If the value is 1, it means to disable the timed test of battery;
|
||
If the value is 3, it means to enable the scheduled test of battery."
|
||
::= { hwBattsTest 10 }
|
||
|
||
hwSetBattsScheduledTestPeriod OBJECT-TYPE
|
||
SYNTAX Unsigned32 (2..999)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Scheduled Test Period.
|
||
Value range: 2 to 999,
|
||
units: Day,
|
||
and the value is an integer.(1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwBattsTest 11 }
|
||
|
||
hwSetBattsTestEndCapacity OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..99)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Test End Capacity.
|
||
Value range: 0 to 99,
|
||
units: %,
|
||
and the value is an integer.
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwBattsTest 12 }
|
||
|
||
hwSetBattsTestEndTemperature OBJECT-TYPE
|
||
SYNTAX Integer32 (-5..15)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Test End Temperature.
|
||
Value range: -5 to 15,
|
||
units: degC,
|
||
and the value is an integer.(1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwBattsTest 13 }
|
||
|
||
hwSetBattsShortTestEnable OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
disable(1),enable(2)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery short test enable.
|
||
It is an enumeration value, and can be configured.
|
||
If the enumeration value is 1, it indicates battery short test is disabled;
|
||
If the enumeration value is 2, it indicates battery short test is enabled. "
|
||
::= { hwBattsTest 14 }
|
||
|
||
hwSetBattsShortTestPeriod OBJECT-TYPE
|
||
SYNTAX Unsigned32 (1..360)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Short Test Period.
|
||
Value range: 1 to 360,
|
||
units: Day,
|
||
and the value is an integer.(1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwBattsTest 15 }
|
||
|
||
hwBattString OBJECT IDENTIFIER ::= { hwSiteBatterys 4 }
|
||
|
||
hwBattStringConfigTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwBattStringConfigEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery string config table. Use this table to get battery string equipment ID and equipment name, to set battery standard capacity and battery install time as well. This table's index is hwBattStringConfigIndex, clone battery string config table."
|
||
::= { hwBattString 1 }
|
||
|
||
hwBattStringConfigEntry OBJECT-TYPE
|
||
SYNTAX HwBattStringConfigEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery string config table. Use this table to get battery string equipment ID and equipment name, to set battery standard capacity and battery install time as well. This table's index is hwBattStringConfigIndex, clone battery string config table."
|
||
INDEX { hwBattStringConfigIndex }
|
||
::= { hwBattStringConfigTable 1 }
|
||
|
||
HwBattStringConfigEntry ::= SEQUENCE {
|
||
hwBattStringConfigIndex
|
||
Integer32,
|
||
hwBattStringEquipId
|
||
Unsigned32,
|
||
hwBattStringEquipName
|
||
OCTET STRING,
|
||
hwSetBattsTempUpperLimit
|
||
Integer32,
|
||
hwSetBattsTempLowerLimit
|
||
Integer32,
|
||
hwSetBattsTempMeasureUpperLimit
|
||
Integer32,
|
||
hwSetBattsTempMeasureLowerLimit
|
||
Integer32,
|
||
hwSetBattStdCapacity
|
||
Integer32,
|
||
hwSetBattInstallTime
|
||
OCTET STRING,
|
||
hwBattStringConfigRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwBattStringConfigIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (1..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Device table index of the battery string,
|
||
value range: 1 to 100(To the actual subject)."
|
||
::= { hwBattStringConfigEntry 1 }
|
||
|
||
hwBattStringEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (3001..3100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Batteries device ID, can be configured by users. Value range: 003,001 to 003,100, in which the first three digits specify the device type and the last three specify the device SN."
|
||
::= { hwBattStringConfigEntry 2 }
|
||
|
||
hwBattStringEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Batteries device name, of the character string type, is used to specify the batteries. Users can configure it. Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwBattStringConfigEntry 3 }
|
||
|
||
hwSetBattsTempUpperLimit OBJECT-TYPE
|
||
SYNTAX Integer32 ( 25..80)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Upper threshold of the battery temperature alarm, can be configured by users.
|
||
Value range: 25 to 80,
|
||
Units: centigrade (degC),
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
||
NOTE: There is linkage between hwSetBattsHTDLimit and hwSetBattsTempUpperLimit"
|
||
::= { hwBattStringConfigEntry 4 }
|
||
|
||
hwSetBattsTempLowerLimit OBJECT-TYPE
|
||
SYNTAX Integer32 ( -20..20)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Lower threshold of the battery temperature alarm, can be configured by users.
|
||
Value range: -20 to 20,
|
||
Units: centigrade (degC),
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwBattStringConfigEntry 5 }
|
||
|
||
hwSetBattsTempMeasureUpperLimit OBJECT-TYPE
|
||
SYNTAX Integer32 (0..100)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Upper threshold of the battery temperature measurement, can be configured by users.
|
||
Value range: 0 to 100,
|
||
Units: centigrade (degC),
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwBattStringConfigEntry 6 }
|
||
|
||
hwSetBattsTempMeasureLowerLimit OBJECT-TYPE
|
||
SYNTAX Integer32 ( -50..0)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Lower threshold of the battery temperature measurement, can be configured by users.
|
||
Value range: -50 to 0,
|
||
Units: centigrade (degC),
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwBattStringConfigEntry 7 }
|
||
|
||
hwSetBattStdCapacity OBJECT-TYPE
|
||
SYNTAX Integer32 (5..10000)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Set battery standard capacity, is an inherent attribute of the device.
|
||
Value range: 5 to 10000,
|
||
units: Ah,
|
||
the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwBattStringConfigEntry 8 }
|
||
|
||
hwSetBattInstallTime OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..128))
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Set battery install time, of the character string type, can be configured by users. Otherwise, the configured character can not be any other languages except English. "
|
||
::= { hwBattStringConfigEntry 9 }
|
||
|
||
hwBattStringConfigRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-create
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus of battery string config table."
|
||
::= { hwBattStringConfigEntry 100 }
|
||
|
||
hwBattStringOperTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwBattStringOperEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery string runing table. Use this table to get battery string current, persent of remain capacity, battery remain capacity, battery actual capacity, as well as battery temperature.
|
||
This table's index is hwBattStringRunIndex, clone battery string runing table."
|
||
::= { hwBattString 2 }
|
||
|
||
hwBattStringOperEntry OBJECT-TYPE
|
||
SYNTAX HwBattStringOperEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery string runing table. Use this table to get battery string current, persent of remain capacity, battery remain capacity, battery actual capacity, as well as battery temperature.
|
||
This table's index is hwBattStringRunIndex, clone battery string runing table."
|
||
INDEX { hwBattStringOperIndex }
|
||
::= { hwBattStringOperTable 1 }
|
||
|
||
HwBattStringOperEntry ::= SEQUENCE {
|
||
hwBattStringOperIndex
|
||
Integer32,
|
||
hwBattStringCurrent
|
||
Integer32,
|
||
hwBattStringRemainCapacityPercent
|
||
Unsigned32,
|
||
hwBattStringRemainCapacity
|
||
Unsigned32,
|
||
hwBattStringActualCapacity
|
||
Unsigned32,
|
||
hwBattStringTemprature
|
||
Integer32,
|
||
hwBattStringMidpointVoltage
|
||
Integer32,
|
||
hwBattStringOperStatus
|
||
INTEGER,
|
||
hwBattStringOperRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwBattStringOperIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (1..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Device table index of the battery string,
|
||
which value range: 1 to 100(To the actual subject)."
|
||
::= { hwBattStringOperEntry 1 }
|
||
|
||
hwBattStringCurrent OBJECT-TYPE
|
||
SYNTAX Integer32 ( -10000..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Batteries current. It is an analog parameter collected by the battery string in real time.
|
||
Value range: -1000 to +1000,
|
||
units: A,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwBattStringOperEntry 2 }
|
||
|
||
hwBattStringRemainCapacityPercent OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Remaining capacity percentage of the battery string.
|
||
Value range: 0 to 100,
|
||
units: %,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwBattStringOperEntry 3 }
|
||
|
||
hwBattStringRemainCapacity OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Remaining capacity of the battery string. It is an analog parameter collected by the battery string in real time.
|
||
Value range: 0 to 1000,
|
||
units: Ah,
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwBattStringOperEntry 4 }
|
||
|
||
hwBattStringActualCapacity OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..5000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Batteries actual capacity. It is an analog parameter collected by the battery string in real time.
|
||
Value range: 0 to 5000,
|
||
units: Ah,
|
||
the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwBattStringOperEntry 5 }
|
||
|
||
hwBattStringTemprature OBJECT-TYPE
|
||
SYNTAX Integer32 ( -3000..2000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery temperature. It is a battery parameter collected in real time.
|
||
Value range: -300 to +200,
|
||
unit: centigrade (degC),
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that battery temperature sensor is not configured."
|
||
::= { hwBattStringOperEntry 6 }
|
||
|
||
hwBattStringMidpointVoltage OBJECT-TYPE
|
||
SYNTAX Integer32 ( -900..900)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Batteries midpoint voltage. It is an analog parameter collected by the battery string in real time.
|
||
Value range: -90 to +90,
|
||
unit: V,
|
||
and the value is accurate to one decimal place (.1)."
|
||
::= { hwBattStringOperEntry 7 }
|
||
|
||
hwBattStringOperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
tempHigh(2),
|
||
tempLow(3),
|
||
loopBreak(4),
|
||
overCurrent(5),
|
||
unbalance(6),
|
||
discharge(7),
|
||
fuseBreak(8),
|
||
alarmResume(254),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the site battery string module. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the site battery string is in the normal state;
|
||
If the enumeration value is 2, it indicates that the battery string is over upper alarm threshold of temperature;
|
||
If the enumeration value is 3, it indicates that the battery string is under lower alarm threshold of temperature;
|
||
If the enumeration value is 4, it indicates that battery string loop has disconnected;
|
||
If the enumeration value is 5, it indicates that the current of batery is over upper charging threshold;
|
||
If the enumeration value is 6, it indicates that the battery string is unbalance;
|
||
If the enumeration value is 7, it indicates that battery string is discharge;
|
||
If the enumeration value is 8, it indicates that battery string is fuseBreak;
|
||
If the enumeration value is 254, it indicates battery string alarm resume;
|
||
If the enumeration value is 255, it indicates battery string operation status unknown. "
|
||
::= { hwBattStringOperEntry 99 }
|
||
|
||
hwBattStringOperRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-create
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus of battery string runing table."
|
||
::= { hwBattStringOperEntry 100 }
|
||
|
||
hwSiteAcDistributions OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 5 }
|
||
|
||
hwAcDistributionsGroup OBJECT IDENTIFIER ::= { hwSiteAcDistributions 1 }
|
||
|
||
hwAcsGroupId OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC group ID, is the unique ID of the AC group. The first three digits indicate the device type and the last three indicate the device SN. If the last three digits are 000, it indicates a virtual device. "
|
||
::= { hwAcDistributionsGroup 1 }
|
||
|
||
hwAcsGroupName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Device name of the AC group. It is of the character string type, and can be configured by users. Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwAcDistributionsGroup 2 }
|
||
|
||
hwAcsTotalCurrent OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Total current of the AC group. It indicates the real-time statistics of the AC group.
|
||
Value range: 0 to 1000,
|
||
units: A,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcDistributionsGroup 3 }
|
||
|
||
hwAcsInputQuantity OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Total quantity of the site ACUs. Value range: 0 to 100. "
|
||
::= { hwAcDistributionsGroup 4 }
|
||
|
||
hwSetAcsUpperVoltLimit OBJECT-TYPE
|
||
SYNTAX Unsigned32 (50..600)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Upper threshold of the AC voltage alarm, can be configured by users.
|
||
Value range: 50 to 600,
|
||
units: V,
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
||
NOTE: There is linkage between hwSetAcsUpperVoltLimit and hwSetAcsLowerVoltLimit"
|
||
::= { hwAcDistributionsGroup 5 }
|
||
|
||
hwSetAcsLowerVoltLimit OBJECT-TYPE
|
||
SYNTAX Unsigned32 (50..600)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Lower threshold of the AC voltage alarm, can be configured by users.
|
||
Value range: 50 to 600,
|
||
units: V,
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
||
NOTE: There is linkage between hwSetAcsUpperVoltLimit and hwSetAcsLowerVoltLimit"
|
||
::= { hwAcDistributionsGroup 6 }
|
||
|
||
hwAcsPowerConsumption OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..4294967295)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Low 32bits of AC Active power Consumption. Value range:0 to 4294967295, resolution 10wh.
|
||
If GET value is 10, it means the real consumption is 10*10wh = 100wh (0.1kwh)"
|
||
::= { hwAcDistributionsGroup 7 }
|
||
|
||
hwAcsReactivePowerConsumption OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..4294967295)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Low 32bits of AC Reactive Power Consumption. Value range:0 to 4294967295, resolution 10varh.
|
||
If GET value is 10, it means the real consumption is 10*10varh = 100varh (0.1kvarh)"
|
||
::= { hwAcDistributionsGroup 9 }
|
||
|
||
hwAcsReactivePowerConsumptionHigh32b OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..4294967295)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"High 32bits of AC Reactive Power Consumption. Value range:0 to 4294967295, resolution 10varh."
|
||
::= { hwAcDistributionsGroup 10 }
|
||
|
||
hwAcsActivePowerConsumptionKw OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..4294967295)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC Active Power Consumption. Value range:0 to 4294967295, resolution 1kwh."
|
||
::= { hwAcDistributionsGroup 11 }
|
||
|
||
hwAcsReactivePowerConsumptionKvar OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..4294967295)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC Reactive Power Consumption. Value range:0 to 4294967295, resolution 1kwh."
|
||
::= { hwAcDistributionsGroup 12 }
|
||
|
||
hwAcsPowerConsumptionHigh32b OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..4294967295)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"High 32bits of AC Active Power Consumption. Value range:0 to 4294967295, resolution 10wh."
|
||
::= { hwAcDistributionsGroup 8 }
|
||
|
||
hwAcDistribution OBJECT IDENTIFIER ::= { hwSiteAcDistributions 2 }
|
||
|
||
hwAcInputTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwAcInputEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC input table. Use this table to get AC distribution unit ID, AC distribution unit name, A phase or AB line voltage, B phase or BC line voltage, C phase or CA line voltage, AC input breaker status,
|
||
as well as AC output breakers quantity, which defines hwAcOutputBreakerTable row number. This table's index is hwAcInputIndex, clone AC input table."
|
||
::= { hwAcDistribution 1 }
|
||
|
||
hwAcInputEntry OBJECT-TYPE
|
||
SYNTAX HwAcInputEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC input table. Use this table to get AC distribution unit ID, AC distribution unit name, A phase or AB line voltage, B phase or BC line voltage, C phase or CA line voltage, AC input breaker status,
|
||
as well as AC output breakers quantity, which defines hwAcOutputBreakerTable row number. This table's index is hwAcInputIndex, clone AC input table."
|
||
INDEX { hwAcInputIndex }
|
||
::= { hwAcInputTable 1 }
|
||
|
||
HwAcInputEntry ::= SEQUENCE {
|
||
hwAcInputIndex
|
||
Integer32,
|
||
hwAcEquipId
|
||
Unsigned32,
|
||
hwAcEquipName
|
||
OCTET STRING,
|
||
hwApOrAblVoltage
|
||
Unsigned32,
|
||
hwBpOrBclVoltage
|
||
Unsigned32,
|
||
hwCpOrCalVoltage
|
||
Unsigned32,
|
||
hwAphaseCurrent
|
||
Integer32,
|
||
hwBphaseCurrent
|
||
Integer32,
|
||
hwCphaseCurrent
|
||
Integer32,
|
||
hwAcInputBreakersQuantity
|
||
Unsigned32,
|
||
hwAcInputOperStatus
|
||
INTEGER,
|
||
hwAcRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwAcInputIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (1..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ACU device table index,
|
||
which value range: 1 to 100.
|
||
Lines of the device list are restricted by the total quantity of ACUs (hwAcsInputQuantity)."
|
||
::= { hwAcInputEntry 1 }
|
||
|
||
hwAcEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ACU device ID, which users can configure. Value range: 004,001 to 004,100,
|
||
in which The first digits indicate the device type and the last three digits indicate the device SN."
|
||
::= { hwAcInputEntry 2 }
|
||
|
||
hwAcEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ACU device name, of the character string type, is used to specify the alternating current unit (ACU).
|
||
Users can configure it. Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwAcInputEntry 3 }
|
||
|
||
hwApOrAblVoltage OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..6000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ACU A-phase or AB-line voltage.
|
||
Value range: 0 to 600,
|
||
units: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcInputEntry 4 }
|
||
|
||
hwBpOrBclVoltage OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..6000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ACU B-phase or BC-line voltage.
|
||
Value range: 0 to 600,
|
||
units: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcInputEntry 5 }
|
||
|
||
hwCpOrCalVoltage OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..6000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ACU C-phase or CA-line voltage.
|
||
Value range: 0 to 600,
|
||
units: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcInputEntry 6 }
|
||
|
||
hwAphaseCurrent OBJECT-TYPE
|
||
SYNTAX Integer32 (0..200000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ACU A-phase current. It is an analog parameter collected by the ACU in real time.
|
||
Value range: 0 to 20000,
|
||
units: A,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcInputEntry 7 }
|
||
|
||
hwBphaseCurrent OBJECT-TYPE
|
||
SYNTAX Integer32 (0..200000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ACU B-phase current. It is an analog parameter collected by the ACU in real time.
|
||
Value range: 0 to 20000,
|
||
units: A,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcInputEntry 8 }
|
||
|
||
hwCphaseCurrent OBJECT-TYPE
|
||
SYNTAX Integer32 (0..200000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ACU C-phase current. It is an analog parameter collected by the ACU in real time.
|
||
Value range: 0 to 20000,
|
||
units: A,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcInputEntry 9 }
|
||
|
||
hwAcInputBreakersQuantity OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Quantity of the AC air circuit breakers.
|
||
As the ACU lower-level subset, the node indicates the quantity of the output air circuit breakers contained by each ACU lower-level subset. Value range: 0 to 100. "
|
||
::= { hwAcInputEntry 10 }
|
||
|
||
hwAcInputOperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
acOff(2),
|
||
acAbsent(3),
|
||
voltHigh(4),
|
||
voltLow(5),
|
||
freqHigh(6),
|
||
freqLow(7),
|
||
alarmResume(254),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the site AC distribution uint. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the site AC distribution uint is in the normal state;
|
||
If the enumeration value is 2, it indicates that AC distribution uint power off;
|
||
If the enumeration value is 3, it indicates that AC input phase absent;
|
||
If the enumeration value is 4, it indicates that AC voltage is over upper alarm threshold;
|
||
If the enumeration value is 5, it indicates that AC voltage is under lower alarm threshold;
|
||
If the enumeration value is 6, it indicates that AC voltage is freqHigh;
|
||
If the enumeration value is 7, it indicates that AC voltage is freqLow;
|
||
If the enumeration value is 254, it indicates AC distribution uint alarm resume;
|
||
If the enumeration value is 255, it indicates AC distribution uint operation status unknown. "
|
||
::= { hwAcInputEntry 99 }
|
||
|
||
hwAcRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-create
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus of ACU."
|
||
::= { hwAcInputEntry 100 }
|
||
|
||
hwAcInputBreakerTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwAcInputBreakerEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac input breaker table. Use this table to get AC input breaker equipment ID, AC input breaker equipment name, and AC input breaker status. This table's index is hwAcInputBreakerIndex, which qualificated by hwAcInputBreakersQuantity in hwAcInputTable, clone Ac input breaker table."
|
||
::= { hwAcDistribution 2 }
|
||
|
||
hwAcInputBreakerEntry OBJECT-TYPE
|
||
SYNTAX HwAcInputBreakerEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac input breaker table. Use this table to get AC input breaker equipment ID, AC input breaker equipment name, and AC input breaker status. This table's index is hwAcInputBreakerIndex, which qualificated by hwAcInputBreakersQuantity in hwAcInputTable, clone Ac input breaker table."
|
||
INDEX { hwAcInputBreakerIndex }
|
||
::= { hwAcInputBreakerTable 1 }
|
||
|
||
HwAcInputBreakerEntry ::= SEQUENCE {
|
||
hwAcInputBreakerIndex
|
||
Integer32,
|
||
hwAcInputBreakerEquipId
|
||
Unsigned32,
|
||
hwAcInputBreakerEquipName
|
||
OCTET STRING,
|
||
hwAcInputBreakerOperStatus
|
||
INTEGER,
|
||
hwAcInputBreakerRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwAcInputBreakerIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (1..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Device table index of the AC air circuit breaker.
|
||
Value range: 1 to 100.
|
||
An input air circuit breaker device can be uniquely identified through the ACU table index and device index of the AC air circuit breaker. "
|
||
::= { hwAcInputBreakerEntry 1 }
|
||
|
||
hwAcInputBreakerEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (5001..5100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC input air circuit breaker ID.
|
||
Value range: 005,001 to 005,100.
|
||
The first digits indicate the device type and the last three digits indicate the device SN."
|
||
::= { hwAcInputBreakerEntry 2 }
|
||
|
||
hwAcInputBreakerEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC input air circuit breaker name, of the character string type, can configured by users. Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwAcInputBreakerEntry 3 }
|
||
|
||
hwAcInputBreakerOperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
disconnect(2),
|
||
alarmResume(254),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Operation state of the site AC input breaker. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the site AC input breaker is in the normal state;
|
||
If the enumeration value is 2, it indicates that the AC input breaker disconnect;
|
||
If the enumeration value is 254, it indicates AC input breaker alarm resume;
|
||
If the enumeration value is 255, it indicates AC input breaker operation status unknown. "
|
||
::= { hwAcInputBreakerEntry 99 }
|
||
|
||
hwAcInputBreakerRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-create
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus of AC input breaker."
|
||
::= { hwAcInputBreakerEntry 100 }
|
||
|
||
hwSiteDcDistributions OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 6 }
|
||
|
||
hwDcDistributionsGroup OBJECT IDENTIFIER ::= { hwSiteDcDistributions 1 }
|
||
|
||
hwDcsGroupId OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DC group ID: unique ID of the DC group. in which The first digits indicate the device type and the last three digits indicate the device SN. If the last three digits are 000, it indicates a virtual device."
|
||
::= { hwDcDistributionsGroup 1 }
|
||
|
||
hwDcsGroupName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Device name of the DC group, of the character string type, can be configured by users. Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwDcDistributionsGroup 2 }
|
||
|
||
hwDcsTotalVoltage OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Total voltage of the DC group.
|
||
Value range: 0 to 100,
|
||
units: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwDcDistributionsGroup 3 }
|
||
|
||
hwDcsTotalCurrent OBJECT-TYPE
|
||
SYNTAX Integer32 ( -300000..300000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Total current of the DC group.
|
||
Value range: -30000 to 30000,
|
||
units: A,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwDcDistributionsGroup 4 }
|
||
|
||
hwDcsTotalPower OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..3000000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Total power of the DC group.
|
||
Value range: 0 to 3000000,
|
||
units: W,
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwDcDistributionsGroup 5 }
|
||
|
||
hwDcsTotalQuantity OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Total quantity of the DC units, and its Value range: 0 to 100."
|
||
::= { hwDcDistributionsGroup 6 }
|
||
|
||
hwSetDcsUpperVoltLimit OBJECT-TYPE
|
||
SYNTAX Unsigned32 (530..600)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Upper threshold of the DC voltage alarm, can be configued by users.
|
||
Value range: 53 to 60,
|
||
units: V,
|
||
and the value is accurate to one decimal space (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
||
NOTE: There is linkage between hwSetDcsUpperVoltLimit and hwSetDcsLowerVoltLimit"
|
||
::= { hwDcDistributionsGroup 7 }
|
||
|
||
hwSetDcsLowerVoltLimit OBJECT-TYPE
|
||
SYNTAX Unsigned32 (350..570)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Lower threshold of the DC voltage alarm, can be configued by users.
|
||
Value range: 35 to 57,
|
||
units: V,
|
||
and the value is accurate to one decimal space (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
||
NOTE: There is linkage between hwSetDcsUpperVoltLimit and hwSetDcsLowerVoltLimit"
|
||
::= { hwDcDistributionsGroup 8 }
|
||
|
||
hwDcsPerfoLoadConsume OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..429467295)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"PerfoLoad Consume of the DC,
|
||
Value range: 0 to 429467295,
|
||
units: KWh,
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwDcDistributionsGroup 9 }
|
||
|
||
hwDcsLoadConsumptionLow32b OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..429467295)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Low 32bits of total DC Load Consumption,Value range: 0 to 429467295, resolution 10wh.
|
||
If GET value is 10, it means the real consumption is 10*10wh = 100wh (0.1kwh)"
|
||
::= { hwDcDistributionsGroup 12 }
|
||
|
||
hwDcsLoadConsumptionHigh32b OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..429467295)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"High 32bits of total DC Load Consumption,Value range: 0 to 429467295, resolution 10wh."
|
||
::= { hwDcDistributionsGroup 13 }
|
||
|
||
hwDcDistribution OBJECT IDENTIFIER ::= { hwSiteDcDistributions 2 }
|
||
|
||
hwDcOutputTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwDcOutputEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwDcDistribution 1 }
|
||
|
||
hwDcOutputEntry OBJECT-TYPE
|
||
SYNTAX HwDcOutputEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
INDEX { hwDcOutputIndex }
|
||
::= { hwDcOutputTable 1 }
|
||
|
||
HwDcOutputEntry ::= SEQUENCE {
|
||
hwDcOutputIndex
|
||
Integer32,
|
||
hwDcOutputEquipId
|
||
Unsigned32,
|
||
hwDcOutputEquipName
|
||
OCTET STRING,
|
||
hwDcOutputVoltage
|
||
Unsigned32,
|
||
hwDcOutputCurrent
|
||
Integer32,
|
||
hwDcOutputPower
|
||
Unsigned32,
|
||
hwLoadsQuantity
|
||
Unsigned32,
|
||
hwLoadUsage
|
||
Unsigned32,
|
||
hwDcOutputOperStatus
|
||
INTEGER,
|
||
hwDcOutputRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwDcOutputIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (1..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Device table index of the DC units, which value range: 1 to 100. Lines of the device list are restricted by the total quantity of DC units (hwDcsQuantity)."
|
||
::= { hwDcOutputEntry 1 }
|
||
|
||
hwDcOutputEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (6001..6100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DC unit device ID, which value range: 006,001 to 006,100. The first digits indicate the device type and the last three digits indicate the device SN. "
|
||
::= { hwDcOutputEntry 2 }
|
||
|
||
hwDcOutputEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DC unit device name, of the character string type, can be configued by users. Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwDcOutputEntry 3 }
|
||
|
||
hwDcOutputVoltage OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DC output voltage. It is an analog parameter collected by the DC power in real time.
|
||
Value range: 0 to 100,
|
||
units: V,
|
||
and the value is accurate to one decimal space (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwDcOutputEntry 4 }
|
||
|
||
hwDcOutputCurrent OBJECT-TYPE
|
||
SYNTAX Integer32 ( -300000..300000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DC output current. It is an analog parameter collected by the DC power in real time.
|
||
Value range: -30000 to 30000,
|
||
units: A,
|
||
and the value is accurate to one decimal space (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwDcOutputEntry 5 }
|
||
|
||
hwDcOutputPower OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..3000000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DC output power. It is an analog parameter collected by the DC power in real time.
|
||
Value range: 0 to 3000000,
|
||
units: W,
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwDcOutputEntry 6 }
|
||
|
||
hwLoadsQuantity OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Quantity of the DC load output branches,
|
||
which value range: 0 to 100.
|
||
As the DC unit lower-level subset, the node indicates the quantity of the DC load output branches contained by each DC unit lower-level subset."
|
||
::= { hwDcOutputEntry 7 }
|
||
|
||
hwLoadUsage OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The load usage of rated rectifier capacity.
|
||
Value range: 0 to 100,
|
||
units: %,
|
||
and the value is an integer (1)."
|
||
::= { hwDcOutputEntry 8 }
|
||
|
||
hwDcOutputOperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
voltHigh(2),
|
||
voltLow(3),
|
||
dcAbsent(4),
|
||
overload(5),
|
||
alarmResume(254),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the site DC distribution uint. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the site DC distribution uint is in the normal state;
|
||
If the enumeration value is 2, it indicates that DC voltage is over the upper alarm threshold;
|
||
If the enumeration value is 3, it indicates that DC voltage is under the lower alarm threshold;
|
||
If the enumeration value is 4, it indicates that DC voltage is dcAbsent;
|
||
If the enumeration value is 5, it indicates that DC voltage is overload;
|
||
If the enumeration value is 254, it indicates DC distribution uint alarm resume;
|
||
If the enumeration value is 255, it indicates DC distribution uint operation status unknown. "
|
||
::= { hwDcOutputEntry 99 }
|
||
|
||
hwDcOutputRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-create
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus of Dc output equipments."
|
||
::= { hwDcOutputEntry 100 }
|
||
|
||
hwLoadBranchTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwLoadBranchEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Loads output table. Use this table to get load branch equipment ID, load branch equipment name, load branch current, and load branch power. This table's index is hwLoadBranchIndex, which qualificated by hwloadsQuantity in hwDcOutputTable, clone loads output table."
|
||
::= { hwDcDistribution 2 }
|
||
|
||
hwLoadBranchEntry OBJECT-TYPE
|
||
SYNTAX HwLoadBranchEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Loads output table. Use this table to get load branch equipment ID, load branch equipment name, load branch current, and load branch power. This table's index is hwLoadBranchIndex, which qualificated by hwloadsQuantity in hwDcOutputTable, clone loads output table."
|
||
INDEX { hwLoadBranchIndex }
|
||
::= { hwLoadBranchTable 1 }
|
||
|
||
HwLoadBranchEntry ::= SEQUENCE {
|
||
hwLoadBranchIndex
|
||
Integer32,
|
||
hwLoadBranchEquipId
|
||
Unsigned32,
|
||
hwLoadBranchEquipName
|
||
OCTET STRING,
|
||
hwLoadBranchCurrent
|
||
Integer32,
|
||
hwLoadBranchPower
|
||
Unsigned32,
|
||
hwLoadBranchOperStatus
|
||
INTEGER,
|
||
hwLoadBranchRowStatus
|
||
RowStatus,
|
||
hwLoadBranchConsume
|
||
Unsigned32,
|
||
hwLoadBranchConsumption
|
||
Unsigned32,
|
||
hwLoadBranchConsumptionLow32b
|
||
Unsigned32,
|
||
hwLoadBranchConsumptionHigh32b
|
||
Unsigned32
|
||
}
|
||
|
||
hwLoadBranchIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (1..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Device table index of the DC load output branch,
|
||
which value range: 1 to 100.
|
||
A DC load output branch can be uniquely identified through the DC unit table index and device index of the DC load output branch."
|
||
::= { hwLoadBranchEntry 1 }
|
||
|
||
hwLoadBranchEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Device ID of the DC load output branch. Value range: 007,001 to 007,100. The first digits indicate the device type and the last three digits indicate the SN of the device. "
|
||
::= { hwLoadBranchEntry 2 }
|
||
|
||
hwLoadBranchEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Device name of the DC load output branch, of the character string type, can be configured by users. Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwLoadBranchEntry 3 }
|
||
|
||
hwLoadBranchCurrent OBJECT-TYPE
|
||
SYNTAX Integer32 (0..100000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DC load output branch current. It is an analog parameter collected by the load branch in real time.
|
||
Value range: 0 to 10000,
|
||
units: A,
|
||
and the value is accurate to one decimal space (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwLoadBranchEntry 4 }
|
||
|
||
hwLoadBranchPower OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..600000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DC load branch power. It is an analog parameter collected by the DC power in real time.
|
||
Value range: 0 to 600000,
|
||
units: W,
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwLoadBranchEntry 5 }
|
||
|
||
hwLoadBranchOperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
disconnect(2),
|
||
noresponse(3),
|
||
overload(4),
|
||
alarmResume(254),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the site load output branch. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the site load output branch is in the normal state;
|
||
If the enumeration value is 2, it indicates that the load output branch disconnect;
|
||
If the enumeration value is 3, it indicates that the site load output branch is in noresponse state;
|
||
If the enumeration value is 2, it indicates that the site load output branch is in the overload state;
|
||
If the enumeration value is 254, it indicates load output branch alarm resume;
|
||
If the enumeration value is 255, it indicates load output branch operation status unknown. "
|
||
::= { hwLoadBranchEntry 99 }
|
||
|
||
hwLoadBranchRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-create
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus of loads output branch."
|
||
::= { hwLoadBranchEntry 100 }
|
||
|
||
hwLoadBranchConsume OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..4294967295)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DC load branch power consumption,
|
||
Value range: 0 to 4294967295,
|
||
units: KWh,
|
||
and the value is accurate to one decimal space (.1)."
|
||
::= { hwLoadBranchEntry 6 }
|
||
|
||
hwLoadBranchConsumption OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..4294967295)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DC load branch power consumption,Value range: 0 to 4294967295, resolution:1 KWh."
|
||
::= { hwLoadBranchEntry 8 }
|
||
|
||
hwLoadBranchConsumptionLow32b OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..4294967295)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Low 32 bits of DC load branch power consumption,Value range: 0 to 4294967295, resolution:10Wh"
|
||
::= { hwLoadBranchEntry 9 }
|
||
|
||
hwLoadBranchConsumptionHigh32b OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..4294967295)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"High 32 bits of DC load branch power consumption,Value range: 0 to 4294967295, resolution:10Wh"
|
||
::= { hwLoadBranchEntry 10 }
|
||
|
||
hwLvdUnits OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 7 }
|
||
|
||
hwLvdsGroup OBJECT IDENTIFIER ::= { hwLvdUnits 1 }
|
||
|
||
hwLvdsGroupId OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"LVD unit group ID. It is the unique ID of the LVD unit group. The first digits indicate the device type. The last three digits indicate the device SN. If the last three digits are 000, it indicates a virtual device."
|
||
::= { hwLvdsGroup 1 }
|
||
|
||
hwLvdsGroupName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Low-voltage power-off unit group name, of the character string type, can be configured by users.
|
||
Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwLvdsGroup 2 }
|
||
|
||
hwLvdsTotalQuantity OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Total quantity of power-off units. Value range: 0 to 100."
|
||
::= { hwLvdsGroup 3 }
|
||
|
||
hwLvdUnit OBJECT IDENTIFIER ::= { hwLvdUnits 2 }
|
||
|
||
hwLvdBranchTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwLvdBranchEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Power-off unit table. Use this table to get Lvd unit equipment ID and power-off unit equipment name, set power-off enable and power-off voltage, as well as control power-off unit disconnected. This table's index is hwLvdBranchIndex, which qualificated by hwLvdsQuantity, clone power-off unit table."
|
||
::= { hwLvdUnit 1 }
|
||
|
||
hwLvdBranchEntry OBJECT-TYPE
|
||
SYNTAX HwLvdBranchEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Power-off unit table. Use this table to get Lvd unit equipment ID and power-off unit equipment name, set power-off enable and power-off voltage, as well as control power-off unit disconnected. This table's index is hwLvdBranchIndex, which qualificated by hwLvdsQuantity, clone power-off unit table."
|
||
INDEX { hwLvdBranchIndex }
|
||
::= { hwLvdBranchTable 1 }
|
||
|
||
HwLvdBranchEntry ::= SEQUENCE {
|
||
hwLvdBranchIndex
|
||
Integer32,
|
||
hwLvdUnitEquipId
|
||
Unsigned32,
|
||
hwLvdUnitEquipName
|
||
OCTET STRING,
|
||
hwSetLvdEnable
|
||
INTEGER,
|
||
hwSetLvdVoltage
|
||
Integer32,
|
||
hwCtrlLvd
|
||
INTEGER,
|
||
hwSetLvdMode
|
||
INTEGER,
|
||
hwSetLvdReconnectedVoltage
|
||
Integer32,
|
||
hwSetLvdDisconnectedTime
|
||
Integer32,
|
||
hwSetLvdDisconnectedCapacity
|
||
Integer32,
|
||
hwLvdBranchOperStatus
|
||
INTEGER,
|
||
hwLvdBranchRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwLvdBranchIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (1..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Device table index of a power-off unit.
|
||
Value range: 1 to 100. Lines of the device list are restricted by the total quantity of the power-off units (hwLvdsTotalQuantity). "
|
||
::= { hwLvdBranchEntry 1 }
|
||
|
||
hwLvdUnitEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (8001..8100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Device ID of a power-off unit. Value range: 8001 to 8100. The first digits indicate the device type and the last three digits indicate the device SN. "
|
||
::= { hwLvdBranchEntry 2 }
|
||
|
||
hwLvdUnitEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Device name of a power-off unit, of the character string type, is used to specify the low-voltage power-off unit. Users can configure it. Otherwise, the configured character can not be any other languages except English. "
|
||
::= { hwLvdBranchEntry 3 }
|
||
|
||
hwSetLvdEnable OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
enabled(1),
|
||
disabled(2)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Control power-off unit enabling. It is an enumeration value, and users actively set it.
|
||
If the enumeration value is 1, it means to enable the power-off unit;
|
||
If the enumeration value is 2, it means to disable the power-off unit.
|
||
When the power-off unit control is not configured, the power-off unit is enabled by default."
|
||
::= { hwLvdBranchEntry 4 }
|
||
|
||
hwSetLvdVoltage OBJECT-TYPE
|
||
SYNTAX Integer32 (350..560)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Low-voltage power-off voltage of a power-off unit can be configured by users.
|
||
Its value range: 35 to 56,
|
||
units: V,
|
||
and the value is accurate to one decimal space (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
||
NOTE: There is linkage between hwSetLvdVoltage and hwSetLvdReconnectedVoltage"
|
||
::= { hwLvdBranchEntry 5 }
|
||
|
||
hwCtrlLvd OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
powerOff(1),
|
||
powerOn(2),
|
||
nullOper(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Control of the power-off unit. It is an enumeration value, users control it manually.
|
||
If the NMS notifies the SNMP agent that the node is set to 1, it means to power off the power-off unit;
|
||
If the NMS notifies the SNMP agent that the node is set to 2, it means that the background controls the power-on of the LVD unit.
|
||
If the NMS notifies the SNMP agent that the node is set to 255, it means that the background controls the nulloper of the LVD unit.
|
||
NOTE: Only the system in manual mode, this parameter can be configured successfully.
|
||
"
|
||
::= { hwLvdBranchEntry 6 }
|
||
|
||
hwSetLvdMode OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
byVoltage(1),
|
||
byTime(2),
|
||
byCapacity(3),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Select the control mode of the power-off unit. It is an enumeration value, users can configure it manually.
|
||
If the NMS notifies the SNMP agent that the node is set to 1, it means to select the voltage power off mode;
|
||
If the NMS notifies the SNMP agent that the node is set to 2, it means to select the time power off mode;
|
||
If the NMS notifies the SNMP agent that the node is set to 3, it means to select the capacity power off mode;
|
||
If the NMS notifies the SNMP agent that the node is set to 255, it means to select the capacity power unknown mode;"
|
||
::= { hwLvdBranchEntry 7 }
|
||
|
||
hwSetLvdReconnectedVoltage OBJECT-TYPE
|
||
SYNTAX Integer32 (370..580)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Low-voltage power-off recover of a power-off unit can be configured by users.
|
||
Its value range: 37.0 to 58.0,
|
||
unit: V,
|
||
and the value is accurate to one decimal space (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
||
The default value is 51.5
|
||
NOTE: There is linkage between hwSetLvdVoltage and hwSetLvdReconnectedVoltage"
|
||
::= { hwLvdBranchEntry 8 }
|
||
|
||
hwSetLvdDisconnectedTime OBJECT-TYPE
|
||
SYNTAX Integer32 (5..1000)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Low-voltage power-off disconnected time, It can be configured by users,
|
||
value range defines between 5 to 1000,
|
||
unit: minutes(min) <20><>
|
||
and its value is an integer (1).
|
||
Here, if battery manual test is standard mode,
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
||
NOTE: Only the lvd in time power off mode, this parameter can be configured successfully."
|
||
::= { hwLvdBranchEntry 9 }
|
||
|
||
hwSetLvdDisconnectedCapacity OBJECT-TYPE
|
||
SYNTAX Integer32 (0..1000)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Power-off unit control the power off, when Remaining capacity percentage of the battery strings is below the calue.
|
||
Value range: 0 to 100,
|
||
unit: %,
|
||
and the value is accurate to one decimal space (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
||
NOTE: Only the lvd in capacity power off mode, this parameter can be configured successfully."
|
||
::= { hwLvdBranchEntry 10 }
|
||
|
||
hwLvdBranchOperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
lowVoltOff(2),
|
||
backgroundOff(3),
|
||
localManualOff(4),
|
||
lowTempOff(5),
|
||
highTempOff(6),
|
||
timeOff(7),
|
||
capacityOff(8),
|
||
forceOff(9),
|
||
maintenanceOff(10),
|
||
alarmResume(254),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the site LVD uint. It is an enumeration type:
|
||
If the enumeration value is 1, the site LVD uint is in the normal state;
|
||
If the enumeration value is 2, the power-off uint disconnect for low voltage;
|
||
If the enumeration value is 3, the power-off uint disconnect bakeground;
|
||
If the enumeration value is 4, the power-off uint local disconnect manually;
|
||
If the enumeration value is 5, the power-off uint disconnect for under temperature;
|
||
If the enumeration value is 6, the power-off uint disconnect for over temperature;
|
||
If the enumeration value is 7, the ower-off uint disconnect for time;
|
||
If the enumeration value is 8, the power-off uint disconnect for capacity;
|
||
If the enumeration value is 9, the power-off uint disconnect for force;
|
||
If the enumeration value is 10, the power-off uint disconnect for maintenance;
|
||
If the enumeration value is 254, the power-off uint alarm resume;
|
||
If the enumeration value is 255, it indicates LVD uint operation status unknown. "
|
||
::= { hwLvdBranchEntry 99 }
|
||
|
||
hwLvdBranchRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-create
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus of lvd table."
|
||
::= { hwLvdBranchEntry 100 }
|
||
|
||
hwSiteEnvUnits OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 8 }
|
||
|
||
hwEnvUnitsGroup OBJECT IDENTIFIER ::= { hwSiteEnvUnits 1 }
|
||
|
||
hwEnvUnitsGroupId OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Unit group ID of the site environment. It is the unique ID of the unit group on the site.
|
||
The first digits indicate the device type. The last three digits indicate the device SN. If the last three digits are 000, it indicates a virtual device. "
|
||
::= { hwEnvUnitsGroup 1 }
|
||
|
||
hwEnvUnitsGroupName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Unit group name of the site environment, of the character string type, can be configured by users.
|
||
Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwEnvUnitsGroup 2 }
|
||
|
||
hwCtrlSmokeReset OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
reset(2),
|
||
nullOper(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Smoke sensor reset. It manually controls clearance of the smoke sensor alarm, and this node is of the enumeration type.
|
||
If the enumeration value of the node is 1, it indicates that the reset of the smoke sensor is not required.
|
||
If the enumeration value of the node is 2, it indicates that the background controls the reset of the smoke sensor.
|
||
If the enumeration value of the node is 255, it indicates that the background controls the unknown of the smoke sensor. "
|
||
::= { hwEnvUnitsGroup 3 }
|
||
|
||
hwCtrlDoorReset OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
reset(2),
|
||
nullOper(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Door actuator reset control. It manually controls clearance of the door actuator alarm. This node is of the enumeration type.
|
||
If the enumeration value is 1, it indicates that clearance of the door actuator is not required;
|
||
If the enumeration value is 2, it indicates that the background controls clearance of the door actuator.
|
||
If the enumeration value is 255, it indicates that the background controls nulloper of the door actuator. "
|
||
::= { hwEnvUnitsGroup 4 }
|
||
|
||
hwCtrlBuzzerEnable OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
enable(1),
|
||
disable(2),
|
||
nullOper(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Buzzer enabling. It manually controls the enabling of the buzzer alarm. This node is of the enumeration type.
|
||
When the enumeration value is 1, it means to enable the buzzer;
|
||
When the enumeration value is 2, it means to disable the buzzer.
|
||
When the enumeration value is 255, it means to nulloper the buzzer.
|
||
"
|
||
::= { hwEnvUnitsGroup 5 }
|
||
|
||
hwEnvTempSensorsTotalQuantity OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..256)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Quantity of the environment temperature sensors, and its value range: 0 to 256."
|
||
::= { hwEnvUnitsGroup 6 }
|
||
|
||
hwEnvHumiSensorsTotalQuantity OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..256)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Quantity of the environment humidity sensors, and its value range: 0 to 256."
|
||
::= { hwEnvUnitsGroup 7 }
|
||
|
||
hwSpareDigitalsTotalQuantity OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..256)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Quantity of the Spare digitals, and its value range: 0 to 256."
|
||
::= { hwEnvUnitsGroup 8 }
|
||
|
||
hwSpareDigitalsOutputQuantity OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..256)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Quantity of the Spare digitals Output, and its value range: 0 to 256."
|
||
::= { hwEnvUnitsGroup 9 }
|
||
|
||
hwEnvSensor OBJECT IDENTIFIER ::= { hwSiteEnvUnits 2 }
|
||
|
||
hwEnvTempSensorTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwEnvTempSensorEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Site environment temperature table.
|
||
Use this table to get environment temperature equipment ID, environment temperature equipment name, and environment temperature, set environment temperature upper limit, environment temperature lower limit, and environment temperature alarm enable.
|
||
This table's index is hwEnvTempSensorIndex, which qualificated by hwEnvTempSensorsQuantity, clone site environment temperature table."
|
||
::= { hwEnvSensor 1 }
|
||
|
||
hwEnvTempSensorEntry OBJECT-TYPE
|
||
SYNTAX HwEnvTempSensorEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Site environment temperature table.
|
||
Use this table to get environment temperature equipment ID, environment temperature equipment name, and environment temperature, set environment temperature upper limit, environment temperature lower limit, and environment temperature alarm enable.
|
||
This table's index is hwEnvTempSensorIndex, which qualificated by hwEnvTempSensorsQuantity, clone site environment temperature table."
|
||
INDEX { hwEnvTempSensorIndex }
|
||
::= { hwEnvTempSensorTable 1 }
|
||
|
||
HwEnvTempSensorEntry ::= SEQUENCE {
|
||
hwEnvTempSensorIndex
|
||
Integer32,
|
||
hwEnvTempEquipId
|
||
Unsigned32,
|
||
hwEnvTempEquipName
|
||
OCTET STRING,
|
||
hwEnvTemperature
|
||
Integer32,
|
||
hwSetEnvTempUpperLimit
|
||
Integer32,
|
||
hwSetEnvTempLowerLimit
|
||
Integer32,
|
||
hwSetEnvTempMeasureUpperLimit
|
||
Integer32,
|
||
hwSetEnvTempMeasureLowerLimit
|
||
Integer32,
|
||
hwSetEnvTempAlarmEnable
|
||
INTEGER,
|
||
hwSetEnvTempUltraHighTempThreshold
|
||
Unsigned32,
|
||
hwEnvTempSensorOperStatus
|
||
INTEGER,
|
||
hwEnvTempSensorRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwEnvTempSensorIndex OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Table index of the environment temperature sensors."
|
||
::= { hwEnvTempSensorEntry 1 }
|
||
|
||
hwEnvTempEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Environment temperature sensor ID."
|
||
::= { hwEnvTempSensorEntry 2 }
|
||
|
||
hwEnvTempEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Environment temperature sensor name, of the character string type, is used to specify an environment temperature sensor.
|
||
Users can configure it. Otherwise, the configured character can not be any other languages except English. "
|
||
::= { hwEnvTempSensorEntry 3 }
|
||
|
||
hwEnvTemperature OBJECT-TYPE
|
||
SYNTAX Integer32 ( -50..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Environment temperature. It is an environment parameter collected in real time.
|
||
Value range: -50 to +100,
|
||
units: centigrade (degC),
|
||
and the value is an integer (1).
|
||
If the value is 2147483647, it indicates that the temperature sensor is not configured."
|
||
::= { hwEnvTempSensorEntry 4 }
|
||
|
||
hwSetEnvTempUpperLimit OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Upper threshold of the environment temperature alarm, can be configured by users.
|
||
units: centigrade (degC),
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
||
NOTE: There is linkage between hwSetEnvTempUpperLimit and hwSetEnvTempLowerLimit.
|
||
If the result of the setting returns an error, it means that it is not supported."
|
||
::= { hwEnvTempSensorEntry 5 }
|
||
|
||
hwSetEnvTempLowerLimit OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Lower threshold of the environment temperature alarm, can be configured by users.
|
||
units: centigrade (degC),
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
||
NOTE: There is linkage between hwSetEnvTempUpperLimit and hwSetEnvTempLowerLimit.
|
||
If the result of the setting returns an error, it means that it is not supported."
|
||
::= { hwEnvTempSensorEntry 6 }
|
||
|
||
hwSetEnvTempMeasureUpperLimit OBJECT-TYPE
|
||
SYNTAX Integer32 (0..100)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Upper threshold of the environment temperature measurement, can be configured by users.
|
||
Value range: 0 to 100,
|
||
unit: centigrade (degC),
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwEnvTempSensorEntry 7 }
|
||
|
||
hwSetEnvTempMeasureLowerLimit OBJECT-TYPE
|
||
SYNTAX Integer32 ( -50..0)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Lower threshold of the environment temperature measurement, can be configured by users.
|
||
Value range: -50 to 0,
|
||
unit: centigrade (degC),
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwEnvTempSensorEntry 8 }
|
||
|
||
hwSetEnvTempAlarmEnable OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
enable(1),
|
||
disable(2)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Environment temperature alarm. It is an enumeration type:
|
||
If the enumeration value is 1, enable the alarm of the environment temperature;
|
||
If the enumeration value is 2, disable the alarm of the environment temperature. "
|
||
::= { hwEnvTempSensorEntry 9 }
|
||
|
||
hwSetEnvTempUltraHighTempThreshold OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Threshold of the environment ultra high temperature measurement, can be configured by users.
|
||
unit: centigrade (degC),
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
||
If the result of the setting returns an error, it means that it is not supported.
|
||
"
|
||
::= { hwEnvTempSensorEntry 10 }
|
||
|
||
hwEnvTempSensorOperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
tempHigh(2),
|
||
tempLow(3),
|
||
notInslot(4),
|
||
alarmResume(254),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the site environment temperature sensor. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the site environment temperature sensor is in the normal state;
|
||
If the enumeration value is 2, it indicates that the environment temperature sensor is over temperature;
|
||
If the enumeration value is 3, it indicates that the environment temperature sensor is under temperature;
|
||
If the enumeration value is 4, it indicates that the environment temperature sensor is not in slot;
|
||
If the enumeration value is 254, it indicates that environment temperature alarm resume;
|
||
If the enumeration value is 255, it indicates environment temperature sensor operation status unknown. "
|
||
::= { hwEnvTempSensorEntry 99 }
|
||
|
||
hwEnvTempSensorRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-create
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus of Environment temperature table."
|
||
::= { hwEnvTempSensorEntry 100 }
|
||
|
||
hwEnvHumiSensorTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwEnvHumiSensorEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Environment humidity table. Use this table to get environment humidity equipment ID , environment humidity equipment name, and environment humidity, set environment humidity upper limit, environment humidity lower limit, and environment humidity alarm enable.
|
||
This table's index is hwEnvHumiSensorIndex, which qualificated by hwEnvHumiSensorIndex, clone site environment humidity table."
|
||
::= { hwEnvSensor 2 }
|
||
|
||
hwEnvHumiSensorEntry OBJECT-TYPE
|
||
SYNTAX HwEnvHumiSensorEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Environment humidity table. Use this table to get environment humidity equipment ID , environment humidity equipment name, and environment humidity, set environment humidity upper limit, environment humidity lower limit, and environment humidity alarm enable.
|
||
This table's index is hwEnvHumiSensorIndex, which qualificated by hwEnvHumiSensorIndex, clone site environment humidity table."
|
||
INDEX { hwEnvHumiSensorIndex }
|
||
::= { hwEnvHumiSensorTable 1 }
|
||
|
||
HwEnvHumiSensorEntry ::= SEQUENCE {
|
||
hwEnvHumiSensorIndex
|
||
Integer32,
|
||
hwEnvHumiEquipId
|
||
Unsigned32,
|
||
hwEnvHumiEquipName
|
||
OCTET STRING,
|
||
hwEnvHumidity
|
||
Integer32,
|
||
hwSetEnvHumidityUpperLimit
|
||
Integer32,
|
||
hwSetEnvHumidityLowerLimit
|
||
Integer32,
|
||
hwSetEnvHumidityMeasureUpperLimit
|
||
Integer32,
|
||
hwSetEnvHumidityMeasureLowerLimit
|
||
Integer32,
|
||
hwSetEnvHumiAlarmEnable
|
||
INTEGER,
|
||
hwEnvHumiSensorOperStatus
|
||
INTEGER,
|
||
hwEnvHumiSensorRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwEnvHumiSensorIndex OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Table index of the environment humility sensors.
|
||
"
|
||
::= { hwEnvHumiSensorEntry 1 }
|
||
|
||
hwEnvHumiEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Environment humility sensor ID"
|
||
::= { hwEnvHumiSensorEntry 2 }
|
||
|
||
hwEnvHumiEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Environment humility sensor name, of the character string type, is used to specify an environment humility sensor.
|
||
Users can configure it.Otherwise, the configured character can not be any other languages except English. "
|
||
::= { hwEnvHumiSensorEntry 3 }
|
||
|
||
hwEnvHumidity OBJECT-TYPE
|
||
SYNTAX Integer32 (0..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Environment humility. It is an environment parameter collected in real time.
|
||
Value range: 0 to 100,
|
||
units: %RH,
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the humidity sensor is not configured."
|
||
::= { hwEnvHumiSensorEntry 4 }
|
||
|
||
hwSetEnvHumidityUpperLimit OBJECT-TYPE
|
||
SYNTAX Integer32 (0..100)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Upper threshold of the environment humility alarm, can be configured by users.
|
||
Value range: 0 to 100,
|
||
units: %RH,
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwEnvHumiSensorEntry 5 }
|
||
|
||
hwSetEnvHumidityLowerLimit OBJECT-TYPE
|
||
SYNTAX Integer32 (0..100)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Lower threshold of the environment humility alarm, can be configured by users.
|
||
Value range: 0 to 100,
|
||
units: %RH,
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwEnvHumiSensorEntry 6 }
|
||
|
||
hwSetEnvHumidityMeasureUpperLimit OBJECT-TYPE
|
||
SYNTAX Integer32 (0..100)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Upper threshold of the environment humility measurement, can be configured by users.
|
||
Value range: 0 to 100,
|
||
units: %RH,
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwEnvHumiSensorEntry 7 }
|
||
|
||
hwSetEnvHumidityMeasureLowerLimit OBJECT-TYPE
|
||
SYNTAX Integer32 (0..100)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Lower threshold of the environment humility measurement, can be configured by users.
|
||
Value range: 0 to 100,
|
||
units: %RH,
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwEnvHumiSensorEntry 8 }
|
||
|
||
hwSetEnvHumiAlarmEnable OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
enable(1),
|
||
disable(2)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Environment humility alarm. It is an enumeration type:
|
||
If the enumeration value is 1, enable the alarm of the environment humility;
|
||
If the enumeration value is 2, disable the alarm of the environment humility.
|
||
The environment humility alarm is enabled by default. "
|
||
::= { hwEnvHumiSensorEntry 9 }
|
||
|
||
hwEnvHumiSensorOperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
humidityHigh(2),
|
||
humidityLow(3),
|
||
notInslot(4),
|
||
alarmResume(254),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the site environment humidity sensor. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the site environment humidity sensor is in the normal state;
|
||
If the enumeration value is 2, it indicates that the environment humidity sensor is over humidity;
|
||
If the enumeration value is 3, it indicates that the environment humidity sensor is under humidity;
|
||
If the enumeration value is 4, it indicates that the environment humidity sensor is not in slot;
|
||
If the enumeration value is 254, it indicates that environment humidity alarm resume;
|
||
If the enumeration value is 255, it indicates environment humidity sensor operation status unknown. "
|
||
::= { hwEnvHumiSensorEntry 99 }
|
||
|
||
hwEnvHumiSensorRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-create
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus of Environment humidity table."
|
||
::= { hwEnvHumiSensorEntry 100 }
|
||
|
||
hwSpareDigitalTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwSpareDigitalEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Spare digital table. Use this table to get Spare digital equipment ID , Spare digital equipment name, and current Spare digital alarm tension, ae well as to set Spare digital alarm enable. This table's index is hwSpareDigitalIndex, which qualificated by hwSpareDigitalsTotalQuantity, clone switch input table."
|
||
::= { hwEnvSensor 3 }
|
||
|
||
hwSpareDigitalEntry OBJECT-TYPE
|
||
SYNTAX HwSpareDigitalEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Spare digital table. Use this table to get Spare digital equipment ID , Spare digital equipment name, and current Spare digital alarm tension, ae well as to set Spare digital alarm enable. This table's index is hwSpareDigitalIndex, which qualificated by hwSpareDigitalsTotalQuantity, clone switch input table."
|
||
INDEX { hwSpareDigitalIndex }
|
||
::= { hwSpareDigitalTable 1 }
|
||
|
||
HwSpareDigitalEntry ::= SEQUENCE {
|
||
hwSpareDigitalIndex
|
||
Integer32,
|
||
hwSpareDigitalEquipId
|
||
Unsigned32,
|
||
hwSpareDigitalEquipName
|
||
OCTET STRING,
|
||
hwSpareDigitalAlarmTension
|
||
INTEGER,
|
||
hwSpareDigitalAlarmEnable
|
||
INTEGER,
|
||
hwSpareDigitalOperStatus
|
||
INTEGER,
|
||
hwSpareDigitalRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwSpareDigitalIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (1..256)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Spare digital table index, which
|
||
value range: 1 to 256.
|
||
Lines of the device list are restricted by the quantity of Spare digitals (hwSpareDigitalsTotalQuantity). "
|
||
::= { hwSpareDigitalEntry 1 }
|
||
|
||
hwSpareDigitalEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (11001..11255)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Spare digital device ID. Value range: 011'001 to 011'255, in which the first digits indicate the device type and the last three digits indicate the device SN. "
|
||
::= { hwSpareDigitalEntry 2 }
|
||
|
||
hwSpareDigitalEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..8))
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Spare digital name, of the character string type, is used to specify Spare digitals. Users can configure it. Otherwise, the configured character can not be any other languages except English. "
|
||
::= { hwSpareDigitalEntry 3 }
|
||
|
||
hwSpareDigitalAlarmTension OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
open(0),
|
||
close(1)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Spare digital alarm state. It is an enumeration value.
|
||
If the value of the node is 1, it indicates a low-tension alarm;
|
||
If the value of the node is 2, it indicates a high-tension alarm. "
|
||
::= { hwSpareDigitalEntry 4 }
|
||
|
||
hwSpareDigitalAlarmEnable OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
enable(1),
|
||
disable(2)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Spare digital alarm enabling. It is an enumeration type:
|
||
If the enumeration value is 1, it means to enable the alarm;
|
||
If the enumeration value is 2, it means to disable the alarm. "
|
||
::= { hwSpareDigitalEntry 5 }
|
||
|
||
hwSpareDigitalOperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
alarm(2),
|
||
alarmResume(254),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the site Spare digital. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the Spare digital operation state is normal;
|
||
If the enumeration value is 2, it indicates that a alarm occurs on the Spare digital;
|
||
If the enumeration value is 254, it indicates that spare digital alarm resume;
|
||
If the enumeration value is 255, it indicates Spare digital operation status unknown."
|
||
::= { hwSpareDigitalEntry 99 }
|
||
|
||
hwSpareDigitalRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-create
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus of of the site Spare digital. "
|
||
::= { hwSpareDigitalEntry 100 }
|
||
|
||
hwSpareDigitalOutputTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwSpareDigitalOutputEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Spare digital table. Use this table to get Spare digital equipment ID , Spare digital equipment name, and current Spare digital alarm tension, ae well as to set Spare digital alarm enable. This table's index is hwSpareDigitalIndex, which qualificated by hwSpareDigitalsTotalQuantity, clone switch input table."
|
||
::= { hwEnvSensor 4 }
|
||
|
||
hwSpareDigitalOutputEntry OBJECT-TYPE
|
||
SYNTAX HwSpareDigitalOutputEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Spare digital table. Use this table to get Spare digital equipment ID , Spare digital equipment name, and current Spare digital alarm tension, ae well as to set Spare digital alarm enable. This table's index is hwSpareDigitalIndex, which qualificated by hwSpareDigitalsTotalQuantity, clone switch input table."
|
||
INDEX { hwSpareDigitalOutputIndex }
|
||
::= { hwSpareDigitalOutputTable 1 }
|
||
|
||
HwSpareDigitalOutputEntry ::= SEQUENCE {
|
||
hwSpareDigitalOutputIndex
|
||
Integer32,
|
||
hwSpareDigitalOutputEquipId
|
||
Unsigned32,
|
||
hwSpareDigitalOutputEquipName
|
||
OCTET STRING,
|
||
hwSetSpareDigitalOutputAlarmCondition
|
||
INTEGER,
|
||
hwSetSpareDigitalOutputEnable
|
||
INTEGER,
|
||
hwSpareDigitalOutputOperStatus
|
||
INTEGER,
|
||
hwSpareDigitalOutputRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwSpareDigitalOutputIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (1..256)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Spare digital table index, which
|
||
value range: 1 to 256.
|
||
Lines of the device list are restricted by the quantity of Spare digitals (hwSpareDigitalsTotalQuantity). "
|
||
::= { hwSpareDigitalOutputEntry 1 }
|
||
|
||
hwSpareDigitalOutputEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (12001..12255)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Spare digital device ID. Value range: 012'001 to 012'255, in which the first digits indicate the device type and the last three digits indicate the device SN. "
|
||
::= { hwSpareDigitalOutputEntry 2 }
|
||
|
||
hwSpareDigitalOutputEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Spare digital name, of the character string type, is used to specify Spare digitals. Users can configure it. Otherwise, the configured character can not be any other languages except English. "
|
||
::= { hwSpareDigitalOutputEntry 3 }
|
||
|
||
hwSetSpareDigitalOutputAlarmCondition OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
open(1),
|
||
close(2)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Spare digital alarm state. It is an enumeration value.
|
||
If the value of the node is 1, it indicates a low-tension alarm;
|
||
If the value of the node is 2, it indicates a high-tension alarm. "
|
||
::= { hwSpareDigitalOutputEntry 4 }
|
||
|
||
hwSetSpareDigitalOutputEnable OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
enable(1),
|
||
disable(2)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Spare digital alarm enabling. It is an enumeration type:
|
||
If the enumeration value is 1, it means to enable the alarm;
|
||
If the enumeration value is 2, it means to disable the alarm. "
|
||
::= { hwSpareDigitalOutputEntry 5 }
|
||
|
||
hwSpareDigitalOutputOperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
open(1),
|
||
close(2),
|
||
alarmResume(254),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the site Spare digital. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the Spare digital operation state is normal;
|
||
If the enumeration value is 2, it indicates that a alarm occurs on the Spare digital;
|
||
If the enumeration value is 254, it indicates that spare digital alarm resume;
|
||
If the enumeration value is 255, it indicates Spare digital operation status unknown."
|
||
::= { hwSpareDigitalOutputEntry 99 }
|
||
|
||
hwSpareDigitalOutputRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-create
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus of Spare digital device table."
|
||
::= { hwSpareDigitalOutputEntry 100 }
|
||
|
||
hwTemp1Table OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwTemp1Entry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temp1 Table."
|
||
::= { hwEnvSensor 5 }
|
||
|
||
hwTemp1Entry OBJECT-TYPE
|
||
SYNTAX HwTemp1Entry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temp1 Table."
|
||
INDEX { hwTemp1Index }
|
||
::= { hwTemp1Table 1 }
|
||
|
||
HwTemp1Entry ::= SEQUENCE {
|
||
hwTemp1Index
|
||
Integer32,
|
||
hwTemp1EquipId
|
||
Unsigned32,
|
||
hwTemp1EquipName
|
||
OCTET STRING,
|
||
hwTemp1Value
|
||
Integer32,
|
||
hwTemp1HighLimit
|
||
Integer32,
|
||
hwTemp1LowLimit
|
||
Integer32,
|
||
hwTemp1OperStatus
|
||
INTEGER
|
||
}
|
||
|
||
hwTemp1Index OBJECT-TYPE
|
||
SYNTAX Integer32 (3394)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Table index of the temp1 sensors. Value range: 1 to 256. Lines of the device list are restricted by the quantity of temp1 sensors (hwEnvHumiSensorsTotalQuantity). "
|
||
::= { hwTemp1Entry 1 }
|
||
|
||
hwTemp1EquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (26000..26255)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temp1 sensor ID, can be configured by users. Value range: 026'000 to 026'255, in which the first digits indicate the device type and the last three digits indicate the device SN."
|
||
::= { hwTemp1Entry 2 }
|
||
|
||
hwTemp1EquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temp1 sensor name, of the character string type, is used to specify an temp1 sensor. Users can configure it. Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwTemp1Entry 3 }
|
||
|
||
hwTemp1Value OBJECT-TYPE
|
||
SYNTAX Integer32 ( -40..80)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temp1. It is an environment parameter collected in real time.
|
||
Value range: -40 to +80,
|
||
units: centigrade (degC),
|
||
and the value is an integer (1).
|
||
If the value is -1024, it indicates that the temperature sensor is not configured."
|
||
::= { hwTemp1Entry 4 }
|
||
|
||
hwTemp1HighLimit OBJECT-TYPE
|
||
SYNTAX Integer32 (25..80)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Upper threshold of the temp1 alarm, can be configured by users.
|
||
Value range: 25 to 80,
|
||
units: centigrade (degC),
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwTemp1Entry 5 }
|
||
|
||
hwTemp1LowLimit OBJECT-TYPE
|
||
SYNTAX Integer32 ( -20..20)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Lower threshold of the temp1 alarm, can be configured by users. Value range: -20 to 20, units: centigrade (degC), and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwTemp1Entry 6 }
|
||
|
||
hwTemp1OperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
tempHigh(2),
|
||
tempLow(3),
|
||
notInslot(4),
|
||
tempFault(5),
|
||
alarmResume(254),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the site temp1 sensor. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the site temp1 sensor is in the normal state;
|
||
If the enumeration value is 2, it indicates that the temp1 sensor is over temperature;
|
||
If the enumeration value is 3, it indicates that the temp1 sensor is under temperature;
|
||
If the enumeration value is 4, it indicates that the temp1 sensor is not in slot;
|
||
If the enumeration value is 5, it indicates that the temp1 sensor is fault;
|
||
If the enumeration value is 254, it indicates that temp1 alarm resume;
|
||
If the enumeration value is 255, it indicates temp1 sensor operation status unknown."
|
||
::= { hwTemp1Entry 99 }
|
||
|
||
hwTemp2Table OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwTemp2Entry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temp2 Table."
|
||
::= { hwEnvSensor 6 }
|
||
|
||
hwTemp2Entry OBJECT-TYPE
|
||
SYNTAX HwTemp2Entry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temp2 Table."
|
||
INDEX { hwTemp2Index }
|
||
::= { hwTemp2Table 1 }
|
||
|
||
HwTemp2Entry ::= SEQUENCE {
|
||
hwTemp2Index
|
||
Integer32,
|
||
hwTemp2EquipId
|
||
Unsigned32,
|
||
hwTemp2EquipName
|
||
OCTET STRING,
|
||
hwTemp2Value
|
||
Integer32,
|
||
hwTemp2HighLimit
|
||
Integer32,
|
||
hwTemp2LowLimit
|
||
Integer32,
|
||
hwTemp2OperStatus
|
||
INTEGER
|
||
}
|
||
|
||
hwTemp2Index OBJECT-TYPE
|
||
SYNTAX Integer32 (3394)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Table index of the temp2 sensors.
|
||
Value range: 1 to 256.
|
||
Lines of the device list are restricted by the quantity of temp2 sensors (hwEnvHumiSensorsTotalQuantity). "
|
||
::= { hwTemp2Entry 1 }
|
||
|
||
hwTemp2EquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (27000..27255)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temp2 sensor ID, can be configured by users. Value range: 027'000 to 027'255, in which the first digits indicate the device type and the last three digits indicate the device SN."
|
||
::= { hwTemp2Entry 2 }
|
||
|
||
hwTemp2EquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temp2 sensor name, of the character string type, is used to specify an temp2 sensor. Users can configure it. Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwTemp2Entry 3 }
|
||
|
||
hwTemp2Value OBJECT-TYPE
|
||
SYNTAX Integer32 ( -40..80)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temp2. It is an environment parameter collected in real time.
|
||
Value range: -40 to +80,
|
||
units: centigrade (degC),
|
||
and the value is an integer (1).
|
||
If the value is -1024, it indicates that the temperature sensor is not configured."
|
||
::= { hwTemp2Entry 4 }
|
||
|
||
hwTemp2HighLimit OBJECT-TYPE
|
||
SYNTAX Integer32 (25..80)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Upper threshold of the temp2 alarm, can be configured by users.
|
||
Value range: 25 to 80,
|
||
units: centigrade (degC),
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwTemp2Entry 5 }
|
||
|
||
hwTemp2LowLimit OBJECT-TYPE
|
||
SYNTAX Integer32 ( -20..20)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Lower threshold of the temp2 alarm, can be configured by users.
|
||
Value range: -20 to 20,
|
||
units: centigrade (degC),
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwTemp2Entry 6 }
|
||
|
||
hwTemp2OperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
tempHigh(2),
|
||
tempLow(3),
|
||
notInslot(4),
|
||
tempFault(5),
|
||
alarmResume(254),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the site temp2 sensor. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the site temp2 sensor is in the normal state;
|
||
If the enumeration value is 2, it indicates that the temp2 sensor is over temperature;
|
||
If the enumeration value is 3, it indicates that the temp2 sensor is under temperature;
|
||
If the enumeration value is 4, it indicates that the temp2 sensor is not in slot;
|
||
If the enumeration value is 5, it indicates that the temp2 sensor is fault;
|
||
If the enumeration value is 254, it indicates that temp2 alarm resume;
|
||
If the enumeration value is 255, it indicates temp2 sensor operation status unknown."
|
||
::= { hwTemp2Entry 99 }
|
||
|
||
hwSmokeSensorTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwSmokeSensorEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwEnvSensor 13 }
|
||
|
||
hwSmokeSensorEntry OBJECT-TYPE
|
||
SYNTAX HwSmokeSensorEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
INDEX { hwSmokeSensorIndex }
|
||
::= { hwSmokeSensorTable 1 }
|
||
|
||
HwSmokeSensorEntry ::= SEQUENCE {
|
||
hwSmokeSensorIndex
|
||
Unsigned32,
|
||
hwSmokeSensorEquipId
|
||
Unsigned32,
|
||
hwSmokeEquipName
|
||
OCTET STRING,
|
||
hwSmokeSensorStatus
|
||
INTEGER
|
||
}
|
||
|
||
hwSmokeSensorIndex OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The tem_hum equip Index."
|
||
::= { hwSmokeSensorEntry 1 }
|
||
|
||
hwSmokeSensorEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwSmokeSensorEntry 2 }
|
||
|
||
hwSmokeEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwSmokeSensorEntry 3 }
|
||
|
||
hwSmokeSensorStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(0),
|
||
alarm(1)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The smoke sensor status"
|
||
::= { hwSmokeSensorEntry 4 }
|
||
|
||
hwWaterSensorTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwWaterSensorEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwEnvSensor 14 }
|
||
|
||
hwWaterSensorEntry OBJECT-TYPE
|
||
SYNTAX HwWaterSensorEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
INDEX { hwWaterSensorIndex }
|
||
::= { hwWaterSensorTable 1 }
|
||
|
||
HwWaterSensorEntry ::= SEQUENCE {
|
||
hwWaterSensorIndex
|
||
Unsigned32,
|
||
hwWaterSensorEquipId
|
||
Unsigned32,
|
||
hwWaterEquipName
|
||
OCTET STRING,
|
||
hwWaterSensorStatus
|
||
INTEGER
|
||
}
|
||
|
||
hwWaterSensorIndex OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The tem_hum equip Index."
|
||
::= { hwWaterSensorEntry 1 }
|
||
|
||
hwWaterSensorEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwWaterSensorEntry 2 }
|
||
|
||
hwWaterEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwWaterSensorEntry 3 }
|
||
|
||
hwWaterSensorStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(0),
|
||
alarm(1)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The smoke sensor status"
|
||
::= { hwWaterSensorEntry 4 }
|
||
|
||
hwDoorSensorTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwDoorSensorEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwEnvSensor 15 }
|
||
|
||
hwDoorSensorEntry OBJECT-TYPE
|
||
SYNTAX HwDoorSensorEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
INDEX { hwDoorSensorIndex }
|
||
::= { hwDoorSensorTable 1 }
|
||
|
||
HwDoorSensorEntry ::= SEQUENCE {
|
||
hwDoorSensorIndex
|
||
Unsigned32,
|
||
hwDoorSensorEquipId
|
||
Unsigned32,
|
||
hwDoorEquipName
|
||
OCTET STRING,
|
||
hwDoorSensorStatus
|
||
INTEGER
|
||
}
|
||
|
||
hwDoorSensorIndex OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The tem_hum equip Index."
|
||
::= { hwDoorSensorEntry 1 }
|
||
|
||
hwDoorSensorEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwDoorSensorEntry 2 }
|
||
|
||
hwDoorEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwDoorSensorEntry 3 }
|
||
|
||
hwDoorSensorStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(0),
|
||
alarm(1)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The smoke sensor status"
|
||
::= { hwDoorSensorEntry 4 }
|
||
|
||
hwSiteInverters OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 9 }
|
||
|
||
hwInverterGroup OBJECT IDENTIFIER ::= { hwSiteInverters 1 }
|
||
|
||
hwInverterGroupId OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inverter unit group ID. It is the unique ID of the Inverter unit group.
|
||
The first digits indicate the device type. The last three digits indicate the device SN.
|
||
If the last three digits are 000, it indicates a virtual device."
|
||
::= { hwInverterGroup 1 }
|
||
|
||
hwInverterGroupName OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..63
|
||
)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inverter unit group name, of the character string type, can be configured by users.Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwInverterGroup 2 }
|
||
|
||
hwInverterQuantity OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Total site intelligent Inverters. "
|
||
::= { hwInverterGroup 3 }
|
||
|
||
hwInverter OBJECT IDENTIFIER ::= { hwSiteInverters 2 }
|
||
|
||
hwInverterTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwInverterEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwInverter 1 }
|
||
|
||
hwInverterEntry OBJECT-TYPE
|
||
SYNTAX HwInverterEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
INDEX { hwInverterIndex }
|
||
::= { hwInverterTable 1 }
|
||
|
||
HwInverterEntry ::= SEQUENCE {
|
||
hwInverterIndex
|
||
Unsigned32,
|
||
hwInverterEquipId
|
||
Unsigned32,
|
||
hwInverterEquipName
|
||
OCTET STRING,
|
||
hwInverterAcOutputVolt
|
||
Unsigned32,
|
||
hwInverterAcOutputCurr
|
||
Unsigned32,
|
||
hwInverterAcOutputFreq
|
||
Unsigned32,
|
||
hwInverterAcOutputActivePower
|
||
Unsigned32,
|
||
hwInverterAcOutputVA
|
||
Unsigned32,
|
||
hwInverterAcInputVolt
|
||
Unsigned32,
|
||
hwInverterAcInputCurr
|
||
Unsigned32,
|
||
hwInverterAcInputFreq
|
||
Unsigned32,
|
||
hwInverterAcInputActivePower
|
||
Unsigned32,
|
||
hwInverterAcInputVA
|
||
Unsigned32,
|
||
hwInverterDcInputVolt
|
||
Unsigned32,
|
||
hwInverterDcInputCurr
|
||
Unsigned32,
|
||
hwInverterDcInputPower
|
||
Unsigned32,
|
||
hwInverterRevision
|
||
OCTET STRING,
|
||
hwInverterPhaseNum
|
||
Unsigned32,
|
||
hwInverterAcGroupNum
|
||
Unsigned32,
|
||
hwInverterDcGroupNum
|
||
Unsigned32,
|
||
hwInverterMajorAlarmNum
|
||
Unsigned32,
|
||
hwInverterMinorAlarmNum
|
||
Unsigned32,
|
||
hwInverterT2SSerialNum
|
||
Unsigned32,
|
||
hwInverterModuleTemp
|
||
Integer32,
|
||
hwInverterOperStatus
|
||
INTEGER,
|
||
hwInverterRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwInverterIndex OBJECT-TYPE
|
||
SYNTAX Unsigned32 (1..256)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inverter table index,which value range:1 to 256.Lines of the device list are restricted by the quantity of Inverter."
|
||
::= { hwInverterEntry 1 }
|
||
|
||
hwInverterEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (18001..18255)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inverter device ID. Value range: 018'001 to 018'255, in which the first digits indicate the device type and the last three digits indicate the device SN. "
|
||
::= { hwInverterEntry 2 }
|
||
|
||
hwInverterEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inverter name, of the character string type, is used to specify Inverters. Users can configure it.Otherwise, the configured character can not be any other languages except English. "
|
||
::= { hwInverterEntry 3 }
|
||
|
||
hwInverterAcOutputVolt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inverter AC Output voltage,
|
||
Value range: 0.0 to 10000.0.
|
||
Unit: V.
|
||
and the value is accurate to one decimal space (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwInverterEntry 4 }
|
||
|
||
hwInverterAcOutputCurr OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inverter AC Output current,
|
||
Value range: 0.0 to 10000.0.
|
||
Unit: A.
|
||
and the value is accurate to one decimal space (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwInverterEntry 5 }
|
||
|
||
hwInverterAcOutputFreq OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inverter AC Output frequency,
|
||
Value range: 0 to 10000.
|
||
Unit: Hz.
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwInverterEntry 6 }
|
||
|
||
hwInverterAcOutputActivePower OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inverter AC Output power,
|
||
Value range: 0 to 10000000.
|
||
Unit: W.
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwInverterEntry 7 }
|
||
|
||
hwInverterAcOutputVA OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inverter AC Output power,
|
||
Value range: 0.0 to 100000.0.
|
||
Unit: VA.
|
||
and the value is accurate to one decimal space (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwInverterEntry 8 }
|
||
|
||
hwInverterAcInputVolt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inverter AC Input voltage,
|
||
Value range: 0.0 to 10000.0.
|
||
Unit: V.
|
||
and the value is accurate to one decimal space (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwInverterEntry 9 }
|
||
|
||
hwInverterAcInputCurr OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inverter AC Input current,
|
||
Value range: 0.0 to 10000.0.
|
||
Unit: A.
|
||
and the value is accurate to one decimal space (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwInverterEntry 10 }
|
||
|
||
hwInverterAcInputFreq OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inverter AC Input frequency,
|
||
Value range: 0 to 10000.
|
||
Unit: Hz.
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwInverterEntry 11 }
|
||
|
||
hwInverterAcInputActivePower OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inverter AC Input power,
|
||
Value range: 0 to 10000000.
|
||
Unit: W.
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwInverterEntry 12 }
|
||
|
||
hwInverterAcInputVA OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inverter AC Input power,
|
||
Value range: 0.0 to 10000.0.
|
||
Unit: VA.
|
||
and the value is accurate to one decimal space (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwInverterEntry 13 }
|
||
|
||
hwInverterDcInputVolt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inverter DC Input voltage,
|
||
Value range: 0.0 to 10000.0.
|
||
Unit: V.
|
||
and the value is accurate to one decimal space (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwInverterEntry 14 }
|
||
|
||
hwInverterDcInputCurr OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inverter DC Input current,
|
||
Value range: 0 to 10000.
|
||
Unit: A.
|
||
and the value is accurate to one decimal space (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwInverterEntry 15 }
|
||
|
||
hwInverterDcInputPower OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inverter DC Input power,
|
||
Value range: 0 to 10000000.
|
||
Unit: W.
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwInverterEntry 16 }
|
||
|
||
hwInverterRevision OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inverter software version number."
|
||
::= { hwInverterEntry 17 }
|
||
|
||
hwInverterPhaseNum OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inverter Number of the phase module, Value range: 0 to 10000. If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwInverterEntry 18 }
|
||
|
||
hwInverterAcGroupNum OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inverter Number of AC group,
|
||
Value range: 0 to 10000.
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwInverterEntry 19 }
|
||
|
||
hwInverterDcGroupNum OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inverter Number of DC group,
|
||
Value range: 0 to 10000.
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwInverterEntry 20 }
|
||
|
||
hwInverterMajorAlarmNum OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inverter Number of Major alarm,
|
||
Value range: 0 to 10000.
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwInverterEntry 21 }
|
||
|
||
hwInverterMinorAlarmNum OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inverter Number of Minor alarm,
|
||
Value range: 0 to 10000.
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwInverterEntry 22 }
|
||
|
||
hwInverterT2SSerialNum OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..4294967295)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inverter T2S serial number,
|
||
Value range: 0 to 4294967295.
|
||
If the value is 4294967295(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwInverterEntry 23 }
|
||
|
||
hwInverterModuleTemp OBJECT-TYPE
|
||
SYNTAX Integer32 (-300..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inverter module Temperature,
|
||
Value range: -300 to 10000.
|
||
Unit: degC.
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwInverterEntry 24 }
|
||
|
||
hwInverterOperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
alarm(2),
|
||
alarmResume(254),
|
||
unknow(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the Inverter. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the Inverter is in the normal state;
|
||
If the enumeration value is 2, it indicates that the Inverter is in the alarm state;
|
||
If the enumeration value is 254, it indicates that the Inverter is in the resume state;
|
||
If the enumeration value is 255, it indicates Inverter operation status unknown. "
|
||
::= { hwInverterEntry 99 }
|
||
|
||
hwInverterRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus of Inverter table."
|
||
::= { hwInverterEntry 100 }
|
||
|
||
hwSiteCoolingDevices OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 10 }
|
||
|
||
hwCoolingDevicesGroup OBJECT IDENTIFIER ::= { hwSiteCoolingDevices 1 }
|
||
|
||
hwCoolingDevicesEquipId OBJECT-TYPE
|
||
SYNTAX Integer32 (19001..19255)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"CoolingDevices unit group ID. Value range: 019'001 to 019'255, in which the first digits indicate the device type and the last three digits indicate the device SN. "
|
||
::= { hwCoolingDevicesGroup 1 }
|
||
|
||
hwCoolingDevicesEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"CoolingDevices unit group name, of the character string type, can be configured by users.
|
||
Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwCoolingDevicesGroup 2 }
|
||
|
||
hwCoolingDevicesMode OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
fanOnly(1),
|
||
acOnly(2),
|
||
smartMode(3),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the CoolingDevices TC mode. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the CoolingDeviecs is in fanOnly state;
|
||
If the enumeration value is 2, it indicates that the CoolingDeviecs is in acOnly state;
|
||
If the enumeration value is 3, it indicates that the CoolingDeviecs is in smartMode state;
|
||
If the enumeration value is 255, it indicates Inverter operation status unknown. "
|
||
::= { hwCoolingDevicesGroup 3 }
|
||
|
||
hwCoolingDevicesHighTempAlarmTreshold OBJECT-TYPE
|
||
SYNTAX Integer32 (25..80)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"CoolingDevices high temp alarm tres,
|
||
Value range: 25 to 80
|
||
Unit: degC.
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwCoolingDevicesGroup 4 }
|
||
|
||
hwCoolingDevicesHighTempAlarmClearTreshold OBJECT-TYPE
|
||
SYNTAX Integer32 (25..80)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"CoolingDevices high temp alarm clear tres,
|
||
Value range: 25 to 80
|
||
Unit: degC.
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwCoolingDevicesGroup 5 }
|
||
|
||
hwCoolingDevicesExpelHidry OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
no(1),
|
||
yes(2)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the CoolingDevices expel hidry. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the CoolingDeviecs is in no state;
|
||
If the enumeration value is 2, it indicates that the CoolingDeviecs is in yes state;
|
||
"
|
||
::= { hwCoolingDevicesGroup 6 }
|
||
|
||
hwCoolingDevicesEquip OBJECT IDENTIFIER ::= { hwSiteCoolingDevices 2 }
|
||
|
||
hwFanTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwFanEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwCoolingDevicesEquip 1 }
|
||
|
||
hwFanEntry OBJECT-TYPE
|
||
SYNTAX HwFanEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
INDEX { hwFanIndex }
|
||
::= { hwFanTable 1 }
|
||
|
||
HwFanEntry ::= SEQUENCE {
|
||
hwFanIndex
|
||
Unsigned32,
|
||
hwFanEquipId
|
||
Unsigned32,
|
||
hwFanEquipName
|
||
OCTET STRING,
|
||
hwFanCtrlMode
|
||
INTEGER,
|
||
hwFan1Status
|
||
INTEGER,
|
||
hwFan2Status
|
||
INTEGER,
|
||
hwFan3Status
|
||
INTEGER,
|
||
hwFan4Status
|
||
INTEGER,
|
||
hwFan1Speed
|
||
Integer32,
|
||
hwFan2Speed
|
||
Integer32,
|
||
hwFan3Speed
|
||
Integer32,
|
||
hwFan4Speed
|
||
Integer32,
|
||
hwFanOperStatus
|
||
INTEGER,
|
||
hwFanRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwFanIndex OBJECT-TYPE
|
||
SYNTAX Unsigned32 (1..256)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Fan table index,which
|
||
value range: 1 to 256.
|
||
Lines of the device list are restricted by the quantity of Fan."
|
||
::= { hwFanEntry 1 }
|
||
|
||
hwFanEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (20001..20255)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Fan device ID. Value range: 020'001 to 020'255, in which the first digits indicate the device type and the last three digits indicate the device SN. "
|
||
::= { hwFanEntry 2 }
|
||
|
||
hwFanEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Fan name, of the character string type, is used to specify Fans. Users can configure it.
|
||
Otherwise, the configured character can not be any other languages except English. "
|
||
::= { hwFanEntry 3 }
|
||
|
||
hwFanCtrlMode OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
autoControl(1),
|
||
manualControl(2),
|
||
other(3)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the Fan ctrl mode. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the fan is in autoControl state;
|
||
If the enumeration value is 2, it indicates that the fan is in manualControl state;
|
||
If the enumeration value is 3, it indicates that the fan is in other state;"
|
||
::= { hwFanEntry 4 }
|
||
|
||
hwFan1Status OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
fault(2),
|
||
inexistent(3),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the Fan1 status. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the fan is in normal state;
|
||
If the enumeration value is 2, it indicates that the fan is in fault state;
|
||
If the enumeration value is 3, it indicates that the fan is in inexistent state;
|
||
If the enumeration value is 255, it indicates that the fan is in unknown state;"
|
||
::= { hwFanEntry 5 }
|
||
|
||
hwFan2Status OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
fault(2),
|
||
inexistent(3),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the Fan2 status. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the fan is in normal state;
|
||
If the enumeration value is 2, it indicates that the fan is in fault state;
|
||
If the enumeration value is 3, it indicates that the fan is in inexistent state;
|
||
If the enumeration value is 255, it indicates that the fan is in unknown state;"
|
||
::= { hwFanEntry 6 }
|
||
|
||
hwFan3Status OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
fault(2),
|
||
inexistent(3),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the Fan3 status. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the fan is in normal state;
|
||
If the enumeration value is 2, it indicates that the fan is in fault state;
|
||
If the enumeration value is 3, it indicates that the fan is in inexistent state;
|
||
If the enumeration value is 255, it indicates that the fan is in unknown state;"
|
||
::= { hwFanEntry 7 }
|
||
|
||
hwFan4Status OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
fault(2),
|
||
inexistent(3),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the Fan4 status. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the fan is in normal state;
|
||
If the enumeration value is 2, it indicates that the fan is in fault state;
|
||
If the enumeration value is 3, it indicates that the fan is in inexistent state;
|
||
If the enumeration value is 255, it indicates that the fan is in unknown state;"
|
||
::= { hwFanEntry 8 }
|
||
|
||
hwFan1Speed OBJECT-TYPE
|
||
SYNTAX Integer32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Fan1 speed,
|
||
Value range: 0 to 10000.
|
||
Unit: rpm.
|
||
the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwFanEntry 9 }
|
||
|
||
hwFan2Speed OBJECT-TYPE
|
||
SYNTAX Integer32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Fan2 speed,
|
||
Value range: 0 to 10000.
|
||
Unit: rpm.
|
||
the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwFanEntry 10 }
|
||
|
||
hwFan3Speed OBJECT-TYPE
|
||
SYNTAX Integer32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Fan3 speed,
|
||
Value range: 0 to 10000.
|
||
Unit: rpm.
|
||
the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwFanEntry 11 }
|
||
|
||
hwFan4Speed OBJECT-TYPE
|
||
SYNTAX Integer32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Fan4 speed,
|
||
Value range: 0 to 10000.
|
||
Unit: rpm.
|
||
the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwFanEntry 12 }
|
||
|
||
hwFanOperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
fault(2),
|
||
alarmResume(254),
|
||
unknow(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the fan. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the Inverter is in the normal state;
|
||
If the enumeration value is 2, it indicates that the Inverter is in the fault state;
|
||
If the enumeration value is 254, it indicates that the Inverter is in the resume state;
|
||
If the enumeration value is 255, it indicates Inverter operation status unknown. "
|
||
::= { hwFanEntry 99 }
|
||
|
||
hwFanRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-create
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus fo fan table."
|
||
::= { hwFanEntry 100 }
|
||
|
||
hwDcAirConditionTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwDcAirConditionEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
""
|
||
::= { hwCoolingDevicesEquip 2 }
|
||
|
||
hwDcAirConditionEntry OBJECT-TYPE
|
||
SYNTAX HwDcAirConditionEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
""
|
||
INDEX { hwDcAirIndex }
|
||
::= { hwDcAirConditionTable 1 }
|
||
|
||
HwDcAirConditionEntry ::= SEQUENCE {
|
||
hwDcAirIndex
|
||
Unsigned32,
|
||
hwDcAirEquipId
|
||
Unsigned32,
|
||
hwDcAirEquipName
|
||
OCTET STRING,
|
||
hwDcAirCtrlMode
|
||
INTEGER,
|
||
hwDcAirCtrlOnOff
|
||
INTEGER,
|
||
hwDcAirRunStatus
|
||
INTEGER,
|
||
hwDcAirCompressorRunStatus
|
||
INTEGER,
|
||
hwDcAirInnrFanSpeed
|
||
Integer32,
|
||
hwDcAirOuterFanSpeed
|
||
Integer32,
|
||
hwDcAirCompressorRunTime
|
||
Integer32,
|
||
hwDcAirRunTime
|
||
Integer32,
|
||
hwDcAirEnterChannelTemp
|
||
Integer32,
|
||
hwDcAirPowerOnTempPoint
|
||
Integer32,
|
||
hwDcAirPowerOffTempPoint
|
||
Integer32,
|
||
hwAcOffEnergySaving
|
||
INTEGER,
|
||
hwDcAirPowerOnAcOffPoint
|
||
Integer32,
|
||
hwDcAirPowerOffAcOffPoint
|
||
Integer32,
|
||
hwDcAirEquipAddress
|
||
Unsigned32,
|
||
hwDcAirOperStatus
|
||
INTEGER,
|
||
hwDcAirRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwDcAirIndex OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Dc aircondition table index"
|
||
::= { hwDcAirConditionEntry 1 }
|
||
|
||
hwDcAirEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Dc aircondition device ID. "
|
||
::= { hwDcAirConditionEntry 2 }
|
||
|
||
hwDcAirEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Dc aircondition name, of the character string type, is used to specify Fans. Users can configure it.
|
||
Otherwise, the configured character can not be any other languages except English. "
|
||
::= { hwDcAirConditionEntry 3 }
|
||
|
||
hwDcAirCtrlMode OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
autoControl(1),
|
||
manualControl(2),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the Dc aircondition ctrl mode. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the Dc aircondition is in autoControl state;
|
||
If the enumeration value is 2, it indicates that the Dc aircondition is in manualControl state;
|
||
If the enumeration value is 255, it indicates that the Dc aircondition is in unknown state;"
|
||
::= { hwDcAirConditionEntry 4 }
|
||
|
||
hwDcAirCtrlOnOff OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
on(1),
|
||
off(2)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the Dc aircondition control on or off. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the Dc aircondition is in on state;
|
||
If the enumeration value is 2, it indicates that the Dc aircondition is in off state;"
|
||
::= { hwDcAirConditionEntry 5 }
|
||
|
||
hwDcAirRunStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
standby(1),
|
||
run(2),
|
||
fault(3),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the Dc aircondition run status. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the Dc aircondition is in standby state;
|
||
If the enumeration value is 2, it indicates that the Dc aircondition is in run state;
|
||
If the enumeration value is 3, it indicates that the Dc aircondition is in fault state;
|
||
If the enumeration value is 255, it indicates that the Dc aircondition is other state."
|
||
::= { hwDcAirConditionEntry 6 }
|
||
|
||
hwDcAirCompressorRunStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
standby(1),
|
||
run(2),
|
||
fault(3),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the Dc air compressor run status. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the Dc aircondition is in standby state;
|
||
If the enumeration value is 2, it indicates that the Dc aircondition is in run state;
|
||
If the enumeration value is 3, it indicates that the Dc aircondition is in fault state;
|
||
If the enumeration value is 255, it indicates that the Dc aircondition is unknown state."
|
||
::= { hwDcAirConditionEntry 7 }
|
||
|
||
hwDcAirInnrFanSpeed OBJECT-TYPE
|
||
SYNTAX Integer32 (0..60000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Dc aircondition innr speed,
|
||
Value range: 0 to 60000.
|
||
Unit: rpm,
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwDcAirConditionEntry 8 }
|
||
|
||
hwDcAirOuterFanSpeed OBJECT-TYPE
|
||
SYNTAX Integer32 (0..60000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Dc aircondition outer speed,
|
||
Value range: 0.0 to 60000.0.
|
||
Unit: rpm,
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwDcAirConditionEntry 9 }
|
||
|
||
hwDcAirCompressorRunTime OBJECT-TYPE
|
||
SYNTAX Integer32 (0..175200)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Dc aircondition compressor run time,
|
||
Value range: 0 to 175200.
|
||
Unit: h,
|
||
the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwDcAirConditionEntry 10 }
|
||
|
||
hwDcAirRunTime OBJECT-TYPE
|
||
SYNTAX Integer32 (0..175200)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Dc aircondition run time,
|
||
Value range: 0 to 175200.
|
||
Unit: H,
|
||
the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwDcAirConditionEntry 11 }
|
||
|
||
hwDcAirEnterChannelTemp OBJECT-TYPE
|
||
SYNTAX Integer32 ( -500..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Dc aircondition enter channel temperature,
|
||
Value range:-500.0 to 1000.0.
|
||
Unit: degC.
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwDcAirConditionEntry 13 }
|
||
|
||
hwDcAirPowerOnTempPoint OBJECT-TYPE
|
||
SYNTAX Integer32 ( -200..800)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Dc aircondition power on temperature point,
|
||
Value range:-200 to 800.
|
||
Unit: degC.
|
||
the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwDcAirConditionEntry 14 }
|
||
|
||
hwDcAirPowerOffTempPoint OBJECT-TYPE
|
||
SYNTAX Integer32 ( -200..800)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Dc aircondition power off temperature point,
|
||
Value range:-200 to 800
|
||
Unit: degC.
|
||
the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwDcAirConditionEntry 15 }
|
||
|
||
hwAcOffEnergySaving OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
disable(1),
|
||
enable(2)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the Dc air energy saving status. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the Dc aircondition is in disable state;
|
||
If the enumeration value is 2, it indicates that the Dc aircondition is in enable state;"
|
||
::= { hwDcAirConditionEntry 17 }
|
||
|
||
hwDcAirPowerOnAcOffPoint OBJECT-TYPE
|
||
SYNTAX Integer32 ( -200..800)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Dc aircondition power on ac fail temperature point,
|
||
Value range:-200 to 800.
|
||
Unit: degC.
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwDcAirConditionEntry 18 }
|
||
|
||
hwDcAirPowerOffAcOffPoint OBJECT-TYPE
|
||
SYNTAX Integer32 ( -200..800)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Dc aircondition compressor start temperature point,
|
||
Value range:-200 to 800.
|
||
Unit: degC.
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwDcAirConditionEntry 19 }
|
||
|
||
hwDcAirEquipAddress OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..255)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
" DC Air Device address
|
||
And the value is an integer (1)."
|
||
::= { hwDcAirConditionEntry 21 }
|
||
|
||
hwDcAirOperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
standby(1),
|
||
run(2),
|
||
fault(3),
|
||
alarmResume(254),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the dc aircondition. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the Inverter is in the standby state;
|
||
If the enumeration value is 2, it indicates that the Inverter is in the run state;
|
||
If the enumeration value is 3, it indicates that the Inverter is in the fault state;
|
||
If the enumeration value is 254, it indicates that the Inverter is in the resume state;
|
||
If the enumeration value is 255, it indicates Inverter operation status unknown. "
|
||
::= { hwDcAirConditionEntry 99 }
|
||
|
||
hwDcAirRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-create
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus fo dc aircondition table."
|
||
::= { hwDcAirConditionEntry 100 }
|
||
|
||
hwSiteAcAmmeters OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 11 }
|
||
|
||
hwSiteAcAmmeterEquip OBJECT IDENTIFIER ::= { hwSiteAcAmmeters 2 }
|
||
|
||
hwSiteAcAmmeterTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwSiteAcAmmeterEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwSiteAcAmmeterEquip 1 }
|
||
|
||
hwSiteAcAmmeterEntry OBJECT-TYPE
|
||
SYNTAX HwSiteAcAmmeterEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
INDEX { hwAcAmmeterIndex }
|
||
::= { hwSiteAcAmmeterTable 1 }
|
||
|
||
HwSiteAcAmmeterEntry ::= SEQUENCE {
|
||
hwAcAmmeterIndex
|
||
Unsigned32,
|
||
hwAcAmmeterEquipId
|
||
Unsigned32,
|
||
hwAcAmmeterEquipName
|
||
OCTET STRING,
|
||
hwAcAmmeterFrequency
|
||
Unsigned32,
|
||
hwAcAmmeterPhaseL1Voltage
|
||
Unsigned32,
|
||
hwAcAmmeterPhaseL2Voltage
|
||
Unsigned32,
|
||
hwAcAmmeterPhaseL3Voltage
|
||
Unsigned32,
|
||
hwAcAmmeterSetChannelNum
|
||
Unsigned32,
|
||
hwAcAmmeterClear
|
||
INTEGER,
|
||
hwAcAmmeterType
|
||
Unsigned32,
|
||
hwAcAmmeterVersion
|
||
OCTET STRING,
|
||
hwAcAmmeterPhaseL1CurrentCH1
|
||
Unsigned32,
|
||
hwAcAmmeterPhaseL2CurrentCH1
|
||
Unsigned32,
|
||
hwAcAmmeterPhaseL3CurrentCH1
|
||
Unsigned32,
|
||
hwAcAmmeterTotalActivePowerCH1
|
||
Integer32,
|
||
hwAcAmmeterTotalPowerFactorCH1
|
||
Integer32,
|
||
hwAcAmmeterTotalActiveEngryAccCH1
|
||
Unsigned32,
|
||
hwAcAmmeterPhaseL1CurrentCH2
|
||
Unsigned32,
|
||
hwAcAmmeterPhaseL2CurrentCH2
|
||
Unsigned32,
|
||
hwAcAmmeterPhaseL3CurrentCH2
|
||
Unsigned32,
|
||
hwAcAmmeterTotalActivePowerCH2
|
||
Integer32,
|
||
hwAcAmmeterTotalPowerFactorCH2
|
||
Integer32,
|
||
hwAcAmmeterTotalActiveEngryAccCH2
|
||
Unsigned32,
|
||
hwAcAmmeterPhaseL1CurrentCH3
|
||
Unsigned32,
|
||
hwAcAmmeterPhaseL2CurrentCH3
|
||
Unsigned32,
|
||
hwAcAmmeterPhaseL3CurrentCH3
|
||
Unsigned32,
|
||
hwAcAmmeterTotalActivePowerCH3
|
||
Integer32,
|
||
hwAcAmmeterTotalPowerFactorCH3
|
||
Integer32,
|
||
hwAcAmmeterTotalActiveEngryAccCH3
|
||
Unsigned32,
|
||
hwAcAmmeterPhaseL1CurrentCH4
|
||
Unsigned32,
|
||
hwAcAmmeterPhaseL2CurrentCH4
|
||
Unsigned32,
|
||
hwAcAmmeterPhaseL3CurrentCH4
|
||
Unsigned32,
|
||
hwAcAmmeterTotalActivePowerCH4
|
||
Integer32,
|
||
hwAcAmmeterTotalPowerFactorCH4
|
||
Integer32,
|
||
hwAcAmmeterTotalActiveEngryAccCH4
|
||
Unsigned32,
|
||
hwAcAmmeterOperStatus
|
||
INTEGER,
|
||
hwAcAmmeterRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwAcAmmeterIndex OBJECT-TYPE
|
||
SYNTAX Unsigned32 (4096..20479)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter table index,which value range:4096 to 20479. Lines of the device list are restricted by the quantity of AcAmmeter"
|
||
::= { hwSiteAcAmmeterEntry 1 }
|
||
|
||
hwAcAmmeterEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (22001..22255)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter device ID. Value range: 022'001 to 022'255, in which the first digits indicate the device type and the last three digits indicate the device SN."
|
||
::= { hwSiteAcAmmeterEntry 2 }
|
||
|
||
hwAcAmmeterEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter name, of the character string type, is used to specify Fans. Users can configure it.
|
||
Otherwise, the configured character can not be any other languages except English.
|
||
"
|
||
::= { hwSiteAcAmmeterEntry 3 }
|
||
|
||
hwAcAmmeterFrequency OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter frequency,
|
||
Value range: 0.00 to 1000.00.
|
||
Unit: Hz.
|
||
and the value is accurate to two decimal space (.01).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteAcAmmeterEntry 4 }
|
||
|
||
hwAcAmmeterPhaseL1Voltage OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..200000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter phase a voltage,
|
||
Value range: 0.00 to 2000.00.
|
||
Unit: V.
|
||
and the value is accurate to two decimal space (.01).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteAcAmmeterEntry 5 }
|
||
|
||
hwAcAmmeterPhaseL2Voltage OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..200000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter phase b voltage,
|
||
Value range: 0.00 to 2000.0.
|
||
Unit: V.
|
||
and the value is accurate to two decimal space (.01).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteAcAmmeterEntry 6 }
|
||
|
||
hwAcAmmeterPhaseL3Voltage OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..200000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter phase c voltage,
|
||
Value range: 0.00 to 2000.0.
|
||
Unit: V.
|
||
and the value is accurate to two decimal space (.01).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteAcAmmeterEntry 7 }
|
||
|
||
hwAcAmmeterSetChannelNum OBJECT-TYPE
|
||
SYNTAX Unsigned32 (1..4)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter set channel number,
|
||
Value range: 1 to 4.
|
||
Unit: NA.
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteAcAmmeterEntry 8 }
|
||
|
||
hwAcAmmeterClear OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
clear(1)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter clear communication failure . It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the ac ammeter clear communication failure alarm;"
|
||
::= { hwSiteAcAmmeterEntry 9 }
|
||
|
||
hwAcAmmeterType OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..65535)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter type, Value range: 0 to 65535. And the value is an integer(1)."
|
||
::= { hwSiteAcAmmeterEntry 10 }
|
||
|
||
hwAcAmmeterVersion OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..56))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter version, of the character string type, is used to specify Ac Ammeter. Users can not configure it."
|
||
::= { hwSiteAcAmmeterEntry 11 }
|
||
|
||
hwAcAmmeterPhaseL1CurrentCH1 OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter phase a current of channel 1,
|
||
Value range: 0.00 to 1000.0.
|
||
Unit: A.
|
||
and the value is accurate to two decimal space (.01).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteAcAmmeterEntry 12 }
|
||
|
||
hwAcAmmeterPhaseL2CurrentCH1 OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter phase b current of channel 1,
|
||
Value range: 0.00 to 1000.0.
|
||
Unit: A.
|
||
and the value is accurate to two decimal space (.01).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteAcAmmeterEntry 13 }
|
||
|
||
hwAcAmmeterPhaseL3CurrentCH1 OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter phase c current of channel 1,
|
||
Value range: 0.00 to 1000.0.
|
||
Unit: A.
|
||
and the value is accurate to two decimal space (.01).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteAcAmmeterEntry 14 }
|
||
|
||
hwAcAmmeterTotalActivePowerCH1 OBJECT-TYPE
|
||
SYNTAX Integer32 (-100000000..100000000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter phase c current of channel 1,
|
||
Value range: -1000000.00 to 1000000.00.
|
||
Unit: kW.
|
||
and the value is accurate to two decimal space (.01).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteAcAmmeterEntry 15 }
|
||
|
||
hwAcAmmeterTotalPowerFactorCH1 OBJECT-TYPE
|
||
SYNTAX Integer32 (-1000..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter total power factor of channel 1,
|
||
Value range: -10.00 to 10.00.
|
||
and the value is accurate to two decimal space (.01).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteAcAmmeterEntry 16 }
|
||
|
||
hwAcAmmeterTotalActiveEngryAccCH1 OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000000000000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter total active engry acc of channel 1,
|
||
Value range: 0.00 to 1000000000.00.
|
||
Unit: kWh.
|
||
and the value is accurate to two decimal space (.01).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteAcAmmeterEntry 17 }
|
||
|
||
hwAcAmmeterPhaseL1CurrentCH2 OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter phase a current of channel 2,
|
||
Value range: 0.00 to 1000.00.
|
||
Unit: A.
|
||
and the value is accurate to two decimal space (.01).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteAcAmmeterEntry 18 }
|
||
|
||
hwAcAmmeterPhaseL2CurrentCH2 OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter phase b current of channel 2,
|
||
Value range: 0.00 to 1000.00.
|
||
Unit: A.
|
||
and the value is accurate to two decimal space (.01).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteAcAmmeterEntry 19 }
|
||
|
||
hwAcAmmeterPhaseL3CurrentCH2 OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter phase c current of channel 2,
|
||
Value range: 0.00 to 1000.00.
|
||
Unit: A.
|
||
and the value is accurate to two decimal space (.01).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteAcAmmeterEntry 20 }
|
||
|
||
hwAcAmmeterTotalActivePowerCH2 OBJECT-TYPE
|
||
SYNTAX Integer32 (-100000000..100000000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter phase c current of channel 2,
|
||
Value range: -1000000.00 to 1000000.00.
|
||
Unit: kW.
|
||
and the value is accurate to two decimal space (.01).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteAcAmmeterEntry 21 }
|
||
|
||
hwAcAmmeterTotalPowerFactorCH2 OBJECT-TYPE
|
||
SYNTAX Integer32 (-1000..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter total power factor of channel 2,
|
||
Value range: -10.00 to 10.00.
|
||
and the value is accurate to two decimal space (.01).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteAcAmmeterEntry 22 }
|
||
|
||
hwAcAmmeterTotalActiveEngryAccCH2 OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100000000000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter total active engry acc of channel 2,
|
||
Value range: 0.00 to 1000000000.00.
|
||
Unit: A.
|
||
and the value is accurate to two decimal space (.01).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteAcAmmeterEntry 23 }
|
||
|
||
hwAcAmmeterPhaseL1CurrentCH3 OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter phase a current of channel 3,
|
||
Value range: 0.00 to 1000.00.
|
||
Unit: A.
|
||
and the value is accurate to two decimal space (.01).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteAcAmmeterEntry 24 }
|
||
|
||
hwAcAmmeterPhaseL2CurrentCH3 OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter phase b current of channel 3,
|
||
Value range: 0.00 to 1000.00.
|
||
Unit: A.
|
||
and the value is accurate to two decimal space (.01).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteAcAmmeterEntry 25 }
|
||
|
||
hwAcAmmeterPhaseL3CurrentCH3 OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter phase c current of channel 3,
|
||
Value range: 0.00 to 1000.00.
|
||
Unit: A.
|
||
and the value is accurate to two decimal space (.01).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteAcAmmeterEntry 26 }
|
||
|
||
hwAcAmmeterTotalActivePowerCH3 OBJECT-TYPE
|
||
SYNTAX Integer32 (-100000000..100000000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter phase c current of channel 3,
|
||
Value range: -1000000.00 to 1000000.00.
|
||
Unit: kW.
|
||
and the value is accurate to two decimal space (.01).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteAcAmmeterEntry 27 }
|
||
|
||
hwAcAmmeterTotalPowerFactorCH3 OBJECT-TYPE
|
||
SYNTAX Integer32 (-1000..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter total power factor of channel 3,
|
||
Value range: -10.00 to 10.00.
|
||
and the value is accurate to two decimal space (.01).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteAcAmmeterEntry 28 }
|
||
|
||
hwAcAmmeterTotalActiveEngryAccCH3 OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100000000000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter total active engry acc of channel 3,
|
||
Value range: 0.00 to 1000000000.00.
|
||
Unit: kWh.
|
||
and the value is accurate to two decimal space (.01).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteAcAmmeterEntry 29 }
|
||
|
||
hwAcAmmeterPhaseL1CurrentCH4 OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter phase a current of channel 4,
|
||
Value range: 0 to 1000.
|
||
Unit: A.
|
||
and the value is accurate to two decimal space (.01).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteAcAmmeterEntry 30 }
|
||
|
||
hwAcAmmeterPhaseL2CurrentCH4 OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter phase b current of channel 4,
|
||
Value range: 0 to 1000.
|
||
Unit: A.
|
||
and the value is accurate to two decimal space (.01).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteAcAmmeterEntry 31 }
|
||
|
||
hwAcAmmeterPhaseL3CurrentCH4 OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter phase c current of channel 4,
|
||
Value range: 0 to 1000.
|
||
Unit: A.
|
||
and the value is accurate to two decimal space (.01).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteAcAmmeterEntry 32 }
|
||
|
||
hwAcAmmeterTotalActivePowerCH4 OBJECT-TYPE
|
||
SYNTAX Integer32 (-100000000..100000000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter phase c current of channel 4,
|
||
Value range: -1000000 to 1000000.
|
||
Unit: kW.
|
||
and the value is accurate to two decimal space (.01).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteAcAmmeterEntry 33 }
|
||
|
||
hwAcAmmeterTotalPowerFactorCH4 OBJECT-TYPE
|
||
SYNTAX Integer32 (-1000..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter total power factor of channel 4,
|
||
Value range: -10.00 to 10.00.
|
||
and the value is accurate to two decimal space (.01).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteAcAmmeterEntry 34 }
|
||
|
||
hwAcAmmeterTotalActiveEngryAccCH4 OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100000000000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter total active engry acc of channel 4,
|
||
Value range: 0 to 1000000000.
|
||
Unit: kWh.
|
||
and the value is accurate to two decimal space (.01).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteAcAmmeterEntry 35 }
|
||
|
||
hwAcAmmeterOperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
fault(2),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the Ac Ammeter. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the Ac Ammeter is in the normal state;
|
||
If the enumeration value is 2, it indicates that the Ac Ammeter is in the fault state;
|
||
If the enumeration value is 255, it indicates that the Ac Ammeter is in the unknown state; "
|
||
::= { hwSiteAcAmmeterEntry 99 }
|
||
|
||
hwAcAmmeterRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-create
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus fo Ac Ammeter table."
|
||
::= { hwSiteAcAmmeterEntry 100 }
|
||
|
||
hwSiteDG OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 12 }
|
||
|
||
hwDGGroup OBJECT IDENTIFIER ::= { hwSiteDG 1 }
|
||
|
||
hwDGGroupId OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Device group ID of the DG module. It is the unique ID of the DG module group, and its default value: 023,000.
|
||
The first digits indicate the device type and the last three digits indicate the device SN.
|
||
If the last three digits are 000, it indicates a virtual device. "
|
||
::= { hwDGGroup 1 }
|
||
|
||
hwDGGroupName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..56))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Name of the DG module group, character string type, is used to specify the DG module group. Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwDGGroup 2 }
|
||
|
||
hwDGAmount OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..2)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Total quantity of the DG modules. Value range: 0 to 2. Units:pcs."
|
||
::= { hwDGGroup 3 }
|
||
|
||
hwDG OBJECT IDENTIFIER ::= { hwSiteDG 2 }
|
||
|
||
hwDGTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwDGEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwDG 1 }
|
||
|
||
hwDGEntry OBJECT-TYPE
|
||
SYNTAX HwDGEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
INDEX { hwDGIndex }
|
||
::= { hwDGTable 1 }
|
||
|
||
HwDGEntry ::= SEQUENCE {
|
||
hwDGIndex
|
||
Integer32,
|
||
hwDGEquipId
|
||
Unsigned32,
|
||
hwDGEquipName
|
||
OCTET STRING,
|
||
hwDGType
|
||
INTEGER,
|
||
hwDGAphaseVoltage
|
||
Unsigned32,
|
||
hwDGBphaseVoltage
|
||
Unsigned32,
|
||
hwDGCphaseVoltage
|
||
Unsigned32,
|
||
hwDGAphaseCurrent
|
||
Unsigned32,
|
||
hwDGBphaseCurrent
|
||
Unsigned32,
|
||
hwDGCphaseCurrent
|
||
Unsigned32,
|
||
hwDGOutputPower
|
||
Unsigned32,
|
||
hwDGFrequency
|
||
Unsigned32,
|
||
hwDGBatteryVoltage
|
||
Unsigned32,
|
||
hwDGTotalRuntime
|
||
Unsigned32,
|
||
hwDGAphasePowerFactor
|
||
Integer32,
|
||
hwDGBphasePowerFactor
|
||
Integer32,
|
||
hwDGCphasePowerFactor
|
||
Integer32,
|
||
hwDGLoadRate
|
||
Unsigned32,
|
||
hwDGOnOffControl
|
||
INTEGER,
|
||
hwDGFaultReset
|
||
INTEGER,
|
||
hwDGMaintenanceConfirm
|
||
INTEGER,
|
||
hwDGOperStatus
|
||
INTEGER,
|
||
hwDGRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwDGIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (0..256)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DG table index,which value range:1 to 256. Lines of the device list are restricted by the quantity of DG."
|
||
::= { hwDGEntry 1 }
|
||
|
||
hwDGEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (23001..23255)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DG device ID. Value range: 023'001 to 023'255, in which the first digits indicate the device type and the last three digits indicate the device SN."
|
||
::= { hwDGEntry 2 }
|
||
|
||
hwDGEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Device name of the DG module, character string type, is used to specify the DG module. Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwDGEntry 3 }
|
||
|
||
hwDGType OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
intelligent(1),
|
||
non_intelligent(2),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Specific type of the DG module. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates a intelligent DG module;
|
||
If the enumeration value is 2, it indicates a non_intelligent module;
|
||
If the enumeration value is 255, it indicates a unknown module; "
|
||
::= { hwDGEntry 4 }
|
||
|
||
hwDGAphaseVoltage OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..5000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"A-phase voltage.
|
||
Value range: 0 to 500,
|
||
units: V,
|
||
and the value is accurate to one decimal place (.1)."
|
||
::= { hwDGEntry 5 }
|
||
|
||
hwDGBphaseVoltage OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..5000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"B-phase voltage.
|
||
Value range: 0 to 500,
|
||
units: V,
|
||
and the value is accurate to one decimal place (.1)."
|
||
::= { hwDGEntry 6 }
|
||
|
||
hwDGCphaseVoltage OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..5000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"C-phase voltage.
|
||
Value range: 0 to 500,
|
||
units: V,
|
||
and the value is accurate to one decimal place (.1)."
|
||
::= { hwDGEntry 7 }
|
||
|
||
hwDGAphaseCurrent OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"A-phase current.
|
||
Value range: 0 to 100,
|
||
units: A,
|
||
and the value is an integer (1)."
|
||
::= { hwDGEntry 8 }
|
||
|
||
hwDGBphaseCurrent OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"B-phase current.
|
||
Value range: 0 to 100,
|
||
units: A,
|
||
and the value is an integer (1)."
|
||
::= { hwDGEntry 9 }
|
||
|
||
hwDGCphaseCurrent OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"C-phase current.
|
||
Value range: 0 to 100,
|
||
units: A,
|
||
and the value is an integer (1)."
|
||
::= { hwDGEntry 10 }
|
||
|
||
hwDGOutputPower OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DG output power.
|
||
Value range: 0 to 100,
|
||
units: kw,
|
||
and the value is one decimal space (.1)."
|
||
::= { hwDGEntry 11 }
|
||
|
||
hwDGFrequency OBJECT-TYPE
|
||
SYNTAX Unsigned32 (50..1200)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The frequency of DG.
|
||
Value range: 5 to 120,
|
||
units: Hz,
|
||
and the value is one decimal space (.1)."
|
||
::= { hwDGEntry 12 }
|
||
|
||
hwDGBatteryVoltage OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..240)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The voltage of DG battery.
|
||
Value range: 0 to 24,
|
||
units: V,
|
||
and the value is one decimal space (.1)."
|
||
::= { hwDGEntry 13 }
|
||
|
||
hwDGTotalRuntime OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..8760000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The total running time of DG,
|
||
Value range: 0 to 876000,
|
||
units: h,
|
||
and the value is one decimal space (.1)."
|
||
::= { hwDGEntry 14 }
|
||
|
||
hwDGAphasePowerFactor OBJECT-TYPE
|
||
SYNTAX Integer32 (-100..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"A phase power factor of DG,
|
||
Value range: -1 to 1,
|
||
units: ,
|
||
and the value is two decimal space (.01)."
|
||
::= { hwDGEntry 15 }
|
||
|
||
hwDGBphasePowerFactor OBJECT-TYPE
|
||
SYNTAX Integer32 (-100..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"B phase power factor of DG,
|
||
Value range: -1 to 1,
|
||
units: ,
|
||
and the value is two decimal space (.01)."
|
||
::= { hwDGEntry 16 }
|
||
|
||
hwDGCphasePowerFactor OBJECT-TYPE
|
||
SYNTAX Integer32 (-100..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"C phase power factor of DG,
|
||
Value range: -1 to 1,
|
||
units: ,
|
||
and the value is two decimal space (.01)."
|
||
::= { hwDGEntry 17 }
|
||
|
||
hwDGLoadRate OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The load rate of DG,
|
||
Value range: 0 to 100,
|
||
units: %,
|
||
and the value is one decimal space (.1). "
|
||
::= { hwDGEntry 18 }
|
||
|
||
hwDGOnOffControl OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
on(1),
|
||
off(2),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Power-on or power-off of the DG module, is an enumeration value. Users can modify the enumeration value of this node, thus controlling of the power-on or power-off of the DG module:
|
||
If the NMS notifies the SNMP agent that this node is set to 1, it indicates power-on of the DG module;
|
||
If the NMS notifies the SNMP agent that this node is set to 2, it indicates power-off of the DG module.
|
||
If the NMS notifies the SNMP agent that this node is set to 255, it indicates unknown of the DG module."
|
||
::= { hwDGEntry 19 }
|
||
|
||
hwDGFaultReset OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
reset(1),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DG fault reset."
|
||
::= { hwDGEntry 20 }
|
||
|
||
hwDGMaintenanceConfirm OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
reset(1),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DG maintenance confirm."
|
||
::= { hwDGEntry 21 }
|
||
|
||
hwDGOperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
stop(1),
|
||
running(2),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the DG. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the DG is in the normal state;
|
||
If the enumeration value is 2, it indicates that the DG is in the fault state;
|
||
If the enumeration value is 255, it indicates that the DG is in the unknown state; "
|
||
::= { hwDGEntry 99 }
|
||
|
||
hwDGRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-create
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus fo DG."
|
||
::= { hwDGEntry 100 }
|
||
|
||
hwSiteSSU OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 13 }
|
||
|
||
hwSSUGroup OBJECT IDENTIFIER ::= { hwSiteSSU 1 }
|
||
|
||
hwSSUGroupId OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Device group ID of the SSU module. It is the unique ID of the SSU module group, and its default value: 024,000.
|
||
The first digits indicate the device type and the last three digits indicate the device SN. If the last three digits are 000, it indicates a virtual device. "
|
||
::= { hwSSUGroup 1 }
|
||
|
||
hwSSUGroupName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..56))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Name of the SSU module group, character string type, is used to specify the SSU module group.
|
||
Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwSSUGroup 2 }
|
||
|
||
hwSSUTotalCurrent OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The total output current of SSU.
|
||
Value range: 0 to 1000,
|
||
units: A,
|
||
and the value is one decimal space (.1)."
|
||
::= { hwSSUGroup 3 }
|
||
|
||
hwSSUTotalOutputPower OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100000000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The total output current of SSU.
|
||
Value range: 0 to 10000000,
|
||
units: kWh,
|
||
and the value is one decimal space (.1)."
|
||
::= { hwSSUGroup 4 }
|
||
|
||
hwSSUClearLostAlarms OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
clear(2),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Clear the lost alarm of SSU."
|
||
::= { hwSSUGroup 5 }
|
||
|
||
hwSSUAmount OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Total quantity of the SSU modules. Value range: 0 to 100. Units:pcs."
|
||
::= { hwSSUGroup 6 }
|
||
|
||
hwSSU OBJECT IDENTIFIER ::= { hwSiteSSU 2 }
|
||
|
||
hwSSUTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwSSUEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwSSU 1 }
|
||
|
||
hwSSUEntry OBJECT-TYPE
|
||
SYNTAX HwSSUEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
INDEX { hwSSUIndex }
|
||
::= { hwSSUTable 1 }
|
||
|
||
HwSSUEntry ::= SEQUENCE {
|
||
hwSSUIndex
|
||
Integer32,
|
||
hwSSUEquipId
|
||
Unsigned32,
|
||
hwSSUEquipName
|
||
OCTET STRING,
|
||
hwSSURunningState
|
||
INTEGER,
|
||
hwSSUInputVoltage
|
||
Unsigned32,
|
||
hwSSUOutputVoltage
|
||
Unsigned32,
|
||
hwSSUOutputCurrent
|
||
Unsigned32,
|
||
hwSSUAddress
|
||
Unsigned32,
|
||
hwSSURowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwSSUIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (0..256)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"SSU table index,which value range:1 to 256. Lines of the device list are restricted by the quantity of SSU."
|
||
::= { hwSSUEntry 1 }
|
||
|
||
hwSSUEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (24001..24255)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"SSU device ID. Value range: 024'001 to 024'255, in which the first digits indicate the device type and the last three digits indicate the device SN."
|
||
::= { hwSSUEntry 2 }
|
||
|
||
hwSSUEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Device name of the SSU module, character string type, is used to specify the SSU module.
|
||
Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwSSUEntry 3 }
|
||
|
||
hwSSURunningState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
on(1),
|
||
off(2),
|
||
nullOper(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The running status of the SSU module. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the SSU module is power on ;
|
||
If the enumeration value is 2, it indicates that the SSU module is power off;
|
||
If the enumeration value is 255, it indicates that the SSU module is nulloper; "
|
||
::= { hwSSUEntry 4 }
|
||
|
||
hwSSUInputVoltage OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..2000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The input voltage of SSU,
|
||
Value range: 0 to 200,
|
||
units: V,
|
||
and the value is one decimal space (.1)."
|
||
::= { hwSSUEntry 5 }
|
||
|
||
hwSSUOutputVoltage OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..2000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The output voltage of SSU,
|
||
Value range: 0 to 200,
|
||
units: V,
|
||
and the value is one decimal space (.1)."
|
||
::= { hwSSUEntry 6 }
|
||
|
||
hwSSUOutputCurrent OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The output current of SSU,
|
||
Value range: 0 to 1000,
|
||
units: A,
|
||
and the value is one decimal space (.1)."
|
||
::= { hwSSUEntry 7 }
|
||
|
||
hwSSUAddress OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100 )
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The address of SSU,
|
||
Value range: 0 to 100,
|
||
units: ,
|
||
and the value is an integer (1)."
|
||
::= { hwSSUEntry 8 }
|
||
|
||
hwSSURowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-create
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus fo SSU."
|
||
::= { hwSSUEntry 100 }
|
||
|
||
hwSiteBatteryCabinets OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 14 }
|
||
|
||
hwSiteBatteryCabinetEquip OBJECT IDENTIFIER ::= { hwSiteBatteryCabinets 2 }
|
||
|
||
hwSiteBatteryCabinetTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwSiteBatteryCabinetEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwSiteBatteryCabinetEquip 1 }
|
||
|
||
hwSiteBatteryCabinetEntry OBJECT-TYPE
|
||
SYNTAX HwSiteBatteryCabinetEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
INDEX { hwBatteryCabinetIndex }
|
||
::= { hwSiteBatteryCabinetTable 1 }
|
||
|
||
HwSiteBatteryCabinetEntry ::= SEQUENCE {
|
||
hwBatteryCabinetIndex
|
||
Unsigned32,
|
||
hwBatteryCabinetEquipId
|
||
Unsigned32,
|
||
hwBatteryCabinetEquipName
|
||
OCTET STRING,
|
||
hwBatteryCabinetIndoorVentTemp
|
||
Integer32,
|
||
hwBatteryCabinetBattTemp
|
||
Integer32,
|
||
hwBatteryCabinetFan1Speed
|
||
Integer32,
|
||
hwBatteryCabinetFan2Speed
|
||
Integer32,
|
||
hwBatteryCabinetFan3Speed
|
||
Integer32,
|
||
hwBatteryCabinetFan4Speed
|
||
Integer32,
|
||
hwBatteryCabinetAirConditionerStatus
|
||
INTEGER,
|
||
hwBatteryCabinetCompressorStatus
|
||
INTEGER,
|
||
hwBatteryCabinetInternalFanSpeed
|
||
Integer32,
|
||
hwBatteryCabinetExternalFanSpeed
|
||
Integer32,
|
||
hwBatteryCabinetAirConditionerRuntime
|
||
Unsigned32,
|
||
hwBatteryCabinetCompressorRuntime
|
||
Unsigned32,
|
||
hwBatteryCabinetAirConWorkTemp
|
||
Integer32,
|
||
hwBatteryCabinetAirConStopTemp
|
||
Integer32,
|
||
hwBatteryCabinetOperStatus
|
||
INTEGER,
|
||
hwBatteryCabinetRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwBatteryCabinetIndex OBJECT-TYPE
|
||
SYNTAX Unsigned32 (4096..20479)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery Cabinet table index,which value is according to the actual subject. Lines of the device list are restricted by the quantity of Battery Cabinet"
|
||
::= { hwSiteBatteryCabinetEntry 1 }
|
||
|
||
hwBatteryCabinetEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (25000..25255)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery Cabinet device ID. Value range: 025'001 to 025'255, in which the first digits indicate the device type and the last three digits indicate the device SN."
|
||
::= { hwSiteBatteryCabinetEntry 2 }
|
||
|
||
hwBatteryCabinetEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery Cabinet name, of the character string type, is used to specify battery cabinet. Users can configure it.
|
||
Otherwise, the configured character can not be any other languages except English.
|
||
"
|
||
::= { hwSiteBatteryCabinetEntry 3 }
|
||
|
||
hwBatteryCabinetIndoorVentTemp OBJECT-TYPE
|
||
SYNTAX Integer32 ( -40..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Indoor vent temperature. It is an environment parameter collected in real time.
|
||
Value range: -40 to +100,
|
||
units: centigrade,
|
||
and the value is an integer (1).
|
||
If the value is -99999, it indicates that the temperature sensor is not configured."
|
||
::= { hwSiteBatteryCabinetEntry 4 }
|
||
|
||
hwBatteryCabinetBattTemp OBJECT-TYPE
|
||
SYNTAX Integer32 ( -40..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery temperature. It is an environment parameter collected in real time.
|
||
Value range: -40 to +100,
|
||
units: centigrade,
|
||
and the value is an integer (1).
|
||
If the value is -99999, it indicates that the temperature sensor is not configured."
|
||
::= { hwSiteBatteryCabinetEntry 5 }
|
||
|
||
hwBatteryCabinetFan1Speed OBJECT-TYPE
|
||
SYNTAX Integer32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Fan 1 speed,
|
||
Value range: 0.0 to 10000.0.
|
||
Unit: rpm,
|
||
the value is an integer (1).
|
||
If the value is -1, it indicates that the fan is not configured."
|
||
::= { hwSiteBatteryCabinetEntry 6 }
|
||
|
||
hwBatteryCabinetFan2Speed OBJECT-TYPE
|
||
SYNTAX Integer32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Fan 2 speed,
|
||
Value range: 0.0 to 10000.0.
|
||
Unit: rpm,
|
||
the value is an integer (1).
|
||
If the value is -1, it indicates that the fan is not configured."
|
||
::= { hwSiteBatteryCabinetEntry 7 }
|
||
|
||
hwBatteryCabinetFan3Speed OBJECT-TYPE
|
||
SYNTAX Integer32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Fan 3 speed,
|
||
Value range: 0.0 to 10000.0.
|
||
Unit: rpm,
|
||
the value is an integer (1).
|
||
If the value is -1, it indicates that the fan is not configured."
|
||
::= { hwSiteBatteryCabinetEntry 8 }
|
||
|
||
hwBatteryCabinetFan4Speed OBJECT-TYPE
|
||
SYNTAX Integer32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Fan 4 speed,
|
||
Value range: 0.0 to 10000.0.
|
||
Unit: rpm,
|
||
the value is an integer (1).
|
||
If the value is -1, it indicates that the fan is not configured."
|
||
::= { hwSiteBatteryCabinetEntry 9 }
|
||
|
||
hwBatteryCabinetAirConditionerStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
standby(1),
|
||
run(2),
|
||
fault(3),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the airconditioner. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the airconditioner is in the standby state;
|
||
If the enumeration value is 2, it indicates that the airconditioner is in the run state;
|
||
If the enumeration value is 3, it indicates that the airconditioner is in the fault state;
|
||
If the enumeration value is 255, it indicates airconditioner status unknown. "
|
||
::= { hwSiteBatteryCabinetEntry 10 }
|
||
|
||
hwBatteryCabinetCompressorStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
standby(1),
|
||
run(2),
|
||
fault(3),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the compressor. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the compressor is in the standby state;
|
||
If the enumeration value is 2, it indicates that the compressor is in the run state;
|
||
If the enumeration value is 3, it indicates that the compressor is in the fault state;
|
||
If the enumeration value is 255, it indicates compressor operation status unknown. "
|
||
::= { hwSiteBatteryCabinetEntry 11 }
|
||
|
||
hwBatteryCabinetInternalFanSpeed OBJECT-TYPE
|
||
SYNTAX Integer32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Internal Fan speed,
|
||
Value range: 0 to 10000.
|
||
Unit: rpm,
|
||
the value is an integer (1).
|
||
If the value is -1, it indicates that the fan is not configured."
|
||
::= { hwSiteBatteryCabinetEntry 12 }
|
||
|
||
hwBatteryCabinetExternalFanSpeed OBJECT-TYPE
|
||
SYNTAX Integer32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"External Fan speed,
|
||
Value range: 0 to 10000.
|
||
Unit: rpm,
|
||
the value is an integer (1).
|
||
If the value is -1, it indicates that the temperature sensor is not configured."
|
||
::= { hwSiteBatteryCabinetEntry 13 }
|
||
|
||
hwBatteryCabinetAirConditionerRuntime OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Total runtime of the air conditioner.
|
||
Value units: hour (h),
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteBatteryCabinetEntry 14 }
|
||
|
||
hwBatteryCabinetCompressorRuntime OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Total runtime of the compressor.
|
||
Value units: hour (h),
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteBatteryCabinetEntry 15 }
|
||
|
||
hwBatteryCabinetAirConWorkTemp OBJECT-TYPE
|
||
SYNTAX Integer32 ( -20..80)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery cabinet aircondition power on temperature point,
|
||
Value range:-20 to 80
|
||
Unit: degC.
|
||
and the value is an integer (1)."
|
||
::= { hwSiteBatteryCabinetEntry 16 }
|
||
|
||
hwBatteryCabinetAirConStopTemp OBJECT-TYPE
|
||
SYNTAX Integer32 ( -20..80)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery cabinet aircondition power off temperature point,
|
||
Value range:-20 to 80
|
||
Unit: degC.
|
||
and the value is an integer(1)."
|
||
::= { hwSiteBatteryCabinetEntry 17 }
|
||
|
||
hwBatteryCabinetOperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
fault(2),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the Battery Cabinet. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the Inverter is in the normal state;
|
||
If the enumeration value is 2, it indicates that the Inverter is in the fault state;
|
||
If the enumeration value is 255, it indicates that the Inverter is in the unknown state; "
|
||
::= { hwSiteBatteryCabinetEntry 99 }
|
||
|
||
hwBatteryCabinetRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-create
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus fo Battery Cabinet table."
|
||
::= { hwSiteBatteryCabinetEntry 100 }
|
||
|
||
hwSiteEsdu OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 15 }
|
||
|
||
hwEsduTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwEsduEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwSiteEsdu 2 }
|
||
|
||
hwEsduEntry OBJECT-TYPE
|
||
SYNTAX HwEsduEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
INDEX { hwEsduIndex }
|
||
::= { hwEsduTable 1 }
|
||
|
||
HwEsduEntry ::= SEQUENCE {
|
||
hwEsduIndex
|
||
Unsigned32,
|
||
hwEsduEquipId
|
||
Unsigned32,
|
||
hwEsduEquipName
|
||
OCTET STRING,
|
||
hwEsduSetDigitalInput1AlarmCondition
|
||
INTEGER,
|
||
hwEsduDigitalInput1OperStatus
|
||
INTEGER,
|
||
hwEsduSetDigitalInput2AlarmCondition
|
||
INTEGER,
|
||
hwEsduDigitalInput2OperStatus
|
||
INTEGER,
|
||
hwEsduSetDigitalInput3AlarmCondition
|
||
INTEGER,
|
||
hwEsduDigitalInput3OperStatus
|
||
INTEGER,
|
||
hwEsduSetDigitalInput4AlarmCondition
|
||
INTEGER,
|
||
hwEsduDigitalInput4OperStatus
|
||
INTEGER,
|
||
hwEsduSetDigitalInput5AlarmCondition
|
||
INTEGER,
|
||
hwEsduDigitalInput5OperStatus
|
||
INTEGER,
|
||
hwEsduSetDigitalInput6AlarmCondition
|
||
INTEGER,
|
||
hwEsduDigitalInput6OperStatus
|
||
INTEGER,
|
||
hwEsduSetDigitalInput7AlarmCondition
|
||
INTEGER,
|
||
hwEsduDigitalInput7OperStatus
|
||
INTEGER,
|
||
hwEsduSetDigitalInput8AlarmCondition
|
||
INTEGER,
|
||
hwEsduDigitalInput8OperStatus
|
||
INTEGER,
|
||
hwEsduSetDigitalInput9AlarmCondition
|
||
INTEGER,
|
||
hwEsduDigitalInput9OperStatus
|
||
INTEGER,
|
||
hwEsduSetDigitalInput10AlarmCondition
|
||
INTEGER,
|
||
hwEsduDigitalInput10OperStatus
|
||
INTEGER,
|
||
hwEsduSetDigitalInput11AlarmCondition
|
||
INTEGER,
|
||
hwEsduDigitalInput11OperStatus
|
||
INTEGER,
|
||
hwEsduSetDigitalInput12AlarmCondition
|
||
INTEGER,
|
||
hwEsduDigitalInput12OperStatus
|
||
INTEGER,
|
||
hwEsduBtempValue
|
||
Integer32,
|
||
hwEsduBtempOperStatus
|
||
INTEGER,
|
||
hwEsduTemp1Value
|
||
Integer32,
|
||
hwEsduTemp1HighLimit
|
||
Integer32,
|
||
hwEsduTemp1LowLimit
|
||
Integer32,
|
||
hwEsduTemp1OperStatus
|
||
INTEGER,
|
||
hwEsduTemp2Value
|
||
Integer32,
|
||
hwEsduTemp2HighLimit
|
||
Integer32,
|
||
hwEsduTemp2LowLimit
|
||
Integer32,
|
||
hwEsduTemp2OperStatus
|
||
INTEGER,
|
||
hwEsduDoorSensorConnect
|
||
INTEGER
|
||
}
|
||
|
||
hwEsduIndex OBJECT-TYPE
|
||
SYNTAX Unsigned32 (3428..3443)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ESDU equip index,which value is according to the actual subject. Lines of the device list are restricted by the quantity of Battery Cabinet"
|
||
::= { hwEsduEntry 1 }
|
||
|
||
hwEsduEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (28001..28255)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Esdu device ID. Value range: 028,001 to 028,255, in which the first digits indicate the device type and the last three digits indicate the device SN."
|
||
::= { hwEsduEntry 2 }
|
||
|
||
hwEsduEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwEsduEntry 3 }
|
||
|
||
hwEsduSetDigitalInput1AlarmCondition OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
close(1),
|
||
open(2),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Spare digital alarm state. It is an enumeration value.
|
||
If the value of the node is 1, it indicates a high-tension alarm;
|
||
If the value of the node is 2, it indicates a low-tension alarm;
|
||
If the value of the node is 255, it indicates airconditioner status unknown."
|
||
::= { hwEsduEntry 4 }
|
||
|
||
hwEsduDigitalInput1OperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
alarm(2),
|
||
alarmResume(254),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"It indicates the digital input operation status. It is an enumeration value.
|
||
If the value of the node is 1, it indicates that the diesel of state is normal;
|
||
If the value of the node is 2, it indicates that the diesel of state is alarm;
|
||
If the value of the node is 254, it indicates that the diesel of state is alarmResume;
|
||
If the value of the node is 255, it indicates that the diesel of state is unknown;"
|
||
::= { hwEsduEntry 5 }
|
||
|
||
hwEsduSetDigitalInput2AlarmCondition OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
close(1),
|
||
open(2),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Spare digital alarm state. It is an enumeration value.
|
||
If the value of the node is 1, it indicates a high-tension alarm;
|
||
If the value of the node is 2, it indicates a low-tension alarm;
|
||
If the value of the node is 255, it indicates airconditioner status unknown."
|
||
::= { hwEsduEntry 6 }
|
||
|
||
hwEsduDigitalInput2OperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
alarm(2),
|
||
alarmResume(254),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"It indicates the digital input operation status. It is an enumeration value.
|
||
If the value of the node is 1, it indicates that the diesel of state is normal;
|
||
If the value of the node is 2, it indicates that the diesel of state is alarm;
|
||
If the value of the node is 254, it indicates that the diesel of state is alarmResume;
|
||
If the value of the node is 255, it indicates that the diesel of state is unknown;"
|
||
::= { hwEsduEntry 7 }
|
||
|
||
hwEsduSetDigitalInput3AlarmCondition OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
close(1),
|
||
open(2),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Spare digital alarm state. It is an enumeration value.
|
||
If the value of the node is 1, it indicates a high-tension alarm;
|
||
If the value of the node is 2, it indicates a low-tension alarm;
|
||
If the value of the node is 255, it indicates airconditioner status unknown."
|
||
::= { hwEsduEntry 8 }
|
||
|
||
hwEsduDigitalInput3OperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
alarm(2),
|
||
alarmResume(254),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"It indicates the digital input operation status. It is an enumeration value.
|
||
If the value of the node is 1, it indicates that the diesel of state is normal;
|
||
If the value of the node is 2, it indicates that the diesel of state is alarm;
|
||
If the value of the node is 254, it indicates that the diesel of state is alarmResume;
|
||
If the value of the node is 255, it indicates that the diesel of state is unknown;"
|
||
::= { hwEsduEntry 9 }
|
||
|
||
hwEsduSetDigitalInput4AlarmCondition OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
close(1),
|
||
open(2),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Spare digital alarm state. It is an enumeration value.
|
||
If the value of the node is 1, it indicates a high-tension alarm;
|
||
If the value of the node is 2, it indicates a low-tension alarm;
|
||
If the value of the node is 255, it indicates airconditioner status unknown."
|
||
::= { hwEsduEntry 10 }
|
||
|
||
hwEsduDigitalInput4OperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
alarm(2),
|
||
alarmResume(254),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"It indicates the digital input operation status. It is an enumeration value.
|
||
If the value of the node is 1, it indicates that the diesel of state is normal;
|
||
If the value of the node is 2, it indicates that the diesel of state is alarm;
|
||
If the value of the node is 254, it indicates that the diesel of state is alarmResume;
|
||
If the value of the node is 255, it indicates that the diesel of state is unknown;"
|
||
::= { hwEsduEntry 11 }
|
||
|
||
hwEsduSetDigitalInput5AlarmCondition OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
close(1),
|
||
open(2),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Spare digital alarm state. It is an enumeration value.
|
||
If the value of the node is 1, it indicates a high-tension alarm;
|
||
If the value of the node is 2, it indicates a low-tension alarm;
|
||
If the value of the node is 255, it indicates airconditioner status unknown."
|
||
::= { hwEsduEntry 12 }
|
||
|
||
hwEsduDigitalInput5OperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
alarm(2),
|
||
alarmResume(254),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"It indicates the digital input operation status. It is an enumeration value.
|
||
If the value of the node is 1, it indicates that the diesel of state is normal;
|
||
If the value of the node is 2, it indicates that the diesel of state is alarm;
|
||
If the value of the node is 254, it indicates that the diesel of state is alarmResume;
|
||
If the value of the node is 255, it indicates that the diesel of state is unknown;"
|
||
::= { hwEsduEntry 13 }
|
||
|
||
hwEsduSetDigitalInput6AlarmCondition OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
close(1),
|
||
open(2),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Spare digital alarm state. It is an enumeration value.If the value of the node is 1, it indicates a high-tension alarm;If the value of the node is 2, it indicates a low-tension alarm;If the value of the node is 255, it indicates airconditioner status unknown."
|
||
::= { hwEsduEntry 14 }
|
||
|
||
hwEsduDigitalInput6OperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
alarm(2),
|
||
alarmResume(254),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"It indicates the digital input operation status. It is an enumeration value.
|
||
If the value of the node is 1, it indicates that the diesel of state is normal;
|
||
If the value of the node is 2, it indicates that the diesel of state is alarm;
|
||
If the value of the node is 254, it indicates that the diesel of state is alarmResume;
|
||
If the value of the node is 255, it indicates that the diesel of state is unknown;"
|
||
::= { hwEsduEntry 15 }
|
||
|
||
hwEsduSetDigitalInput7AlarmCondition OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
close(1),
|
||
open(2),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Spare digital alarm state. It is an enumeration value.
|
||
If the value of the node is 1, it indicates a high-tension alarm;
|
||
If the value of the node is 2, it indicates a low-tension alarm;
|
||
If the value of the node is 255, it indicates airconditioner status unknown."
|
||
::= { hwEsduEntry 16 }
|
||
|
||
hwEsduDigitalInput7OperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
alarm(2),
|
||
alarmResume(254),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"It indicates the digital input operation status. It is an enumeration value.
|
||
If the value of the node is 1, it indicates that the diesel of state is normal;
|
||
If the value of the node is 2, it indicates that the diesel of state is alarm;
|
||
If the value of the node is 254, it indicates that the diesel of state is alarmResume;
|
||
If the value of the node is 255, it indicates that the diesel of state is unknown;"
|
||
::= { hwEsduEntry 17 }
|
||
|
||
hwEsduSetDigitalInput8AlarmCondition OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
close(1),
|
||
open(2),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Spare digital alarm state. It is an enumeration value.
|
||
If the value of the node is 1, it indicates a high-tension alarm;
|
||
If the value of the node is 2, it indicates a low-tension alarm;
|
||
If the value of the node is 255, it indicates airconditioner status unknown."
|
||
::= { hwEsduEntry 18 }
|
||
|
||
hwEsduDigitalInput8OperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
alarm(2),
|
||
alarmResume(254),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"It indicates the digital input operation status. It is an enumeration value.
|
||
If the value of the node is 1, it indicates that the diesel of state is normal;
|
||
If the value of the node is 2, it indicates that the diesel of state is alarm;
|
||
If the value of the node is 254, it indicates that the diesel of state is alarmResume;
|
||
If the value of the node is 255, it indicates that the diesel of state is unknown;"
|
||
::= { hwEsduEntry 19 }
|
||
|
||
hwEsduSetDigitalInput9AlarmCondition OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
close(1),
|
||
open(2),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Spare digital alarm state. It is an enumeration value.
|
||
If the value of the node is 1, it indicates a high-tension alarm;
|
||
If the value of the node is 2, it indicates a low-tension alarm;
|
||
If the value of the node is 255, it indicates airconditioner status unknown."
|
||
::= { hwEsduEntry 20 }
|
||
|
||
hwEsduDigitalInput9OperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
alarm(2),
|
||
alarmResume(254),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"It indicates the digital input operation status. It is an enumeration value.
|
||
If the value of the node is 1, it indicates that the diesel of state is normal;
|
||
If the value of the node is 2, it indicates that the diesel of state is alarm;
|
||
If the value of the node is 254, it indicates that the diesel of state is alarmResume;
|
||
If the value of the node is 255, it indicates that the diesel of state is unknown;"
|
||
::= { hwEsduEntry 21 }
|
||
|
||
hwEsduSetDigitalInput10AlarmCondition OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
close(1),
|
||
open(2),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Spare digital alarm state. It is an enumeration value.
|
||
If the value of the node is 1, it indicates a high-tension alarm;
|
||
If the value of the node is 2, it indicates a low-tension alarm;
|
||
If the value of the node is 255, it indicates airconditioner status unknown."
|
||
::= { hwEsduEntry 22 }
|
||
|
||
hwEsduDigitalInput10OperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
alarm(2),
|
||
alarmResume(254),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"It indicates the digital input operation status. It is an enumeration value.
|
||
If the value of the node is 1, it indicates that the diesel of state is normal;
|
||
If the value of the node is 2, it indicates that the diesel of state is alarm;
|
||
If the value of the node is 254, it indicates that the diesel of state is alarmResume;
|
||
If the value of the node is 255, it indicates that the diesel of state is unknown;"
|
||
::= { hwEsduEntry 23 }
|
||
|
||
hwEsduSetDigitalInput11AlarmCondition OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
close(1),
|
||
open(2),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Spare digital alarm state. It is an enumeration value.
|
||
If the value of the node is 1, it indicates a high-tension alarm;
|
||
If the value of the node is 2, it indicates a low-tension alarm;
|
||
If the value of the node is 255, it indicates airconditioner status unknown."
|
||
::= { hwEsduEntry 24 }
|
||
|
||
hwEsduDigitalInput11OperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
alarm(2),
|
||
alarmResume(254),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"It indicates the digital input operation status. It is an enumeration value.
|
||
If the value of the node is 1, it indicates that the diesel of state is normal;
|
||
If the value of the node is 2, it indicates that the diesel of state is alarm;
|
||
If the value of the node is 254, it indicates that the diesel of state is alarmResume;
|
||
If the value of the node is 255, it indicates that the diesel of state is unknown;"
|
||
::= { hwEsduEntry 25 }
|
||
|
||
hwEsduSetDigitalInput12AlarmCondition OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
close(1),
|
||
open(2),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Spare digital alarm state. It is an enumeration value.
|
||
If the value of the node is 1, it indicates a high-tension alarm;
|
||
If the value of the node is 2, it indicates a low-tension alarm;
|
||
If the value of the node is 255, it indicates airconditioner status unknown."
|
||
::= { hwEsduEntry 26 }
|
||
|
||
hwEsduDigitalInput12OperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
alarm(2),
|
||
alarmResume(254),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"It indicates the digital input operation status. It is an enumeration value.
|
||
If the value of the node is 1, it indicates that the diesel of state is normal;
|
||
If the value of the node is 2, it indicates that the diesel of state is alarm;
|
||
If the value of the node is 254, it indicates that the diesel of state is alarmResume;
|
||
If the value of the node is 255, it indicates that the diesel of state is unknown;"
|
||
::= { hwEsduEntry 27 }
|
||
|
||
hwEsduBtempValue OBJECT-TYPE
|
||
SYNTAX Integer32 ( -40..80)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temp1. It is an environment parameter collected in real time.
|
||
Value range: -40 to +80,
|
||
Unit: degC
|
||
and the value is an integer (1).
|
||
If the value is -1024, it indicates that the temperature sensor is not configured."
|
||
::= { hwEsduEntry 28 }
|
||
|
||
hwEsduBtempOperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
tempHigh(2),
|
||
tempLow(3),
|
||
notInslot(4),
|
||
tempFault(5),
|
||
alarmResume(254),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the site temp1 sensor. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the site temp1 sensor is in the normal state;
|
||
If the enumeration value is 2, it indicates that the temp1 sensor is over temperature;
|
||
If the enumeration value is 3, it indicates that the temp1 sensor is under temperature;
|
||
If the enumeration value is 4, it indicates that the temp1 sensor is not in slot;
|
||
If the enumeration value is 5, it indicates that the temp1 sensor is fault;
|
||
If the enumeration value is 254, it indicates that temp1 alarm resume;
|
||
If the enumeration value is 255, it indicates temp1 sensor operation status unknown."
|
||
::= { hwEsduEntry 31 }
|
||
|
||
hwEsduTemp1Value OBJECT-TYPE
|
||
SYNTAX Integer32 ( -40..80)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temp1. It is an environment parameter collected in real time.
|
||
Value range: -40 to +80,
|
||
units: centigrade (degC),
|
||
and the value is an integer (1).
|
||
If the value is -1024, it indicates that the temperature sensor is not configured."
|
||
::= { hwEsduEntry 32 }
|
||
|
||
hwEsduTemp1HighLimit OBJECT-TYPE
|
||
SYNTAX Integer32 (25..80)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Upper threshold of the temp1 alarm, can be configured by users.
|
||
Value range: 25 to 80,
|
||
units: centigrade (degC),
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwEsduEntry 33 }
|
||
|
||
hwEsduTemp1LowLimit OBJECT-TYPE
|
||
SYNTAX Integer32 ( -20..20)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Lower threshold of the temp1 alarm, can be configured by users.
|
||
Value range: -20 to 20,
|
||
units: centigrade (degC),
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwEsduEntry 34 }
|
||
|
||
hwEsduTemp1OperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
tempHigh(2),
|
||
tempLow(3),
|
||
notInslot(4),
|
||
tempFault(5),
|
||
alarmResume(254),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the site temp1 sensor. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the site temp1 sensor is in the normal state;
|
||
If the enumeration value is 2, it indicates that the temp1 sensor is over temperature;
|
||
If the enumeration value is 3, it indicates that the temp1 sensor is under temperature;
|
||
If the enumeration value is 4, it indicates that the temp1 sensor is not in slot;
|
||
If the enumeration value is 5, it indicates that the temp1 sensor is fault;
|
||
If the enumeration value is 254, it indicates that temp1 alarm resume;
|
||
If the enumeration value is 255, it indicates temp1 sensor operation status unknown."
|
||
::= { hwEsduEntry 35 }
|
||
|
||
hwEsduTemp2Value OBJECT-TYPE
|
||
SYNTAX Integer32 ( -40..80)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temp2. It is an environment parameter collected in real time.
|
||
Value range: -40 to +80,
|
||
units: centigrade (degC),
|
||
and the value is an integer (1).
|
||
If the value is -1024, it indicates that the temperature sensor is not configured."
|
||
::= { hwEsduEntry 36 }
|
||
|
||
hwEsduTemp2HighLimit OBJECT-TYPE
|
||
SYNTAX Integer32 (25..80)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Upper threshold of the temp2 alarm, can be configured by users.
|
||
Value range: 25 to 80,
|
||
units: centigrade (degC),
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwEsduEntry 37 }
|
||
|
||
hwEsduTemp2LowLimit OBJECT-TYPE
|
||
SYNTAX Integer32 ( -20..20)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Lower threshold of the temp2 alarm, can be configured by users.
|
||
Value range: -20 to 20,
|
||
units: centigrade (degC),
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwEsduEntry 38 }
|
||
|
||
hwEsduTemp2OperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
tempHigh(2),
|
||
tempLow(3),
|
||
notInslot(4),
|
||
tempFault(5),
|
||
alarmResume(254),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the site temp2 sensor. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates that the site temp2 sensor is in the normal state;
|
||
If the enumeration value is 2, it indicates that the temp2 sensor is over temperature;
|
||
If the enumeration value is 3, it indicates that the temp2 sensor is under temperature;
|
||
If the enumeration value is 4, it indicates that the temp2 sensor is not in slot;
|
||
If the enumeration value is 5, it indicates that the temp2 sensor is fault;
|
||
If the enumeration value is 254, it indicates that temp2 alarm resume;
|
||
If the enumeration value is 255, it indicates temp2 sensor operation status unknown."
|
||
::= { hwEsduEntry 39 }
|
||
|
||
hwEsduDoorSensorConnect OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
disable(1),enable(2),unknown(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Door Sensor Connected; It is an enumeration value, and can be configured.
|
||
If the enumeration value is 1, it indicates Door Sensor is disable;
|
||
If the enumeration value is 2, it indicates Door Sensor is enalble;
|
||
If the enumeration value is 255, it indicates timed boost charge is unknown. "
|
||
::= { hwEsduEntry 40 }
|
||
|
||
hwSiteIbox OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 20 }
|
||
|
||
hwSiteIboxTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwSiteIboxEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwSiteIbox 1 }
|
||
|
||
hwSiteIboxEntry OBJECT-TYPE
|
||
SYNTAX HwSiteIboxEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
INDEX { hwIboxIndex }
|
||
::= { hwSiteIboxTable 1 }
|
||
|
||
HwSiteIboxEntry ::= SEQUENCE {
|
||
hwIboxIndex
|
||
Unsigned32,
|
||
hwIboxEquipId
|
||
Unsigned32,
|
||
hwIboxEquipName
|
||
OCTET STRING,
|
||
hwIbatEquipNum
|
||
Unsigned32
|
||
}
|
||
|
||
hwIboxIndex OBJECT-TYPE
|
||
SYNTAX Unsigned32 (560..575)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ibox table index,which value is according to the actual subject. Lines of the device list are restricted by the quantity of ibox"
|
||
::= { hwSiteIboxEntry 1 }
|
||
|
||
hwIboxEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (29001..29255)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ibox device ID. Value range: 029'001 to 029'255, in which the first digits indicate the device type and the last three digits indicate the device SN."
|
||
::= { hwSiteIboxEntry 2 }
|
||
|
||
hwIboxEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ibox name, of the character string type, is used to specify battery cabinet. Users can configure it.
|
||
Otherwise, the configured character can not be any other languages except English.
|
||
"
|
||
::= { hwSiteIboxEntry 3 }
|
||
|
||
hwIbatEquipNum OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..96)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Number of Batteries.
|
||
Value range: 0 to 96,
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
||
|
||
"
|
||
::= { hwSiteIboxEntry 4 }
|
||
|
||
hwSiteIbat OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 21 }
|
||
|
||
hwSiteIbatTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwSiteIbatEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwSiteIbat 1 }
|
||
|
||
hwSiteIbatEntry OBJECT-TYPE
|
||
SYNTAX HwSiteIbatEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
INDEX { hwIbatIndex }
|
||
::= { hwSiteIbatTable 1 }
|
||
|
||
HwSiteIbatEntry ::= SEQUENCE {
|
||
hwIbatIndex
|
||
Unsigned32,
|
||
hwIbatEquipId
|
||
Unsigned32,
|
||
hwIbatEquipName
|
||
OCTET STRING,
|
||
hwIbatTemperature
|
||
Integer32,
|
||
hwIbatVoltage
|
||
Unsigned32,
|
||
hwIbatResistance
|
||
Unsigned32
|
||
}
|
||
|
||
hwIbatIndex OBJECT-TYPE
|
||
SYNTAX Unsigned32 (24576..26112)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ibox table index,which value is according to the actual subject. Lines of the device list are restricted by the quantity of ibox"
|
||
::= { hwSiteIbatEntry 1 }
|
||
|
||
hwIbatEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (30001..31537)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ibat device ID. Value range: 030'001 to 031'537, in which the first digits indicate the device type and the last three digits indicate the device SN."
|
||
::= { hwSiteIbatEntry 2 }
|
||
|
||
hwIbatEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ibat name, of the character string type, is used to specify battery cabinet. Users can configure it.
|
||
Otherwise, the configured character can not be any other languages except English.
|
||
"
|
||
::= { hwSiteIbatEntry 3 }
|
||
|
||
hwIbatTemperature OBJECT-TYPE
|
||
SYNTAX Integer32 (-50..125)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ibat temperature. It is a ibat parameter collected in real time.
|
||
Value range: -50 to +125,
|
||
unit: centigrade (degC),
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that ibox temperature sensor is not configured.
|
||
"
|
||
::= { hwSiteIbatEntry 4 }
|
||
|
||
hwIbatVoltage OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ibat Voltage of the ibat. It is an inherent attribute.
|
||
Value range: 0 to 100,
|
||
Units: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
||
"
|
||
::= { hwSiteIbatEntry 5 }
|
||
|
||
hwIbatResistance OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100000000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"IbatResistance
|
||
Value range: 0 to 1000000,
|
||
units: (mohm),
|
||
and the value is accurate to two decimal place (.01).
|
||
"
|
||
::= { hwSiteIbatEntry 6 }
|
||
|
||
hwSiteCommExBoard OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 22 }
|
||
|
||
hwSiteCommExBoardTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwSiteCommExBoardEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwSiteCommExBoard 1 }
|
||
|
||
hwSiteCommExBoardEntry OBJECT-TYPE
|
||
SYNTAX HwSiteCommExBoardEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
INDEX { hwCommExBoardIndex }
|
||
::= { hwSiteCommExBoardTable 1 }
|
||
|
||
HwSiteCommExBoardEntry ::= SEQUENCE {
|
||
hwCommExBoardIndex
|
||
Unsigned32,
|
||
hwCommExBoardEquipId
|
||
Unsigned32,
|
||
hwCommExBoardEquipName
|
||
OCTET STRING
|
||
}
|
||
|
||
hwCommExBoardIndex OBJECT-TYPE
|
||
SYNTAX Unsigned32 (1297..1301)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Communication Expansion Board table index,which value is according to the actual subject. Lines of the device list are restricted by the quantity of Communication Expansion Board"
|
||
::= { hwSiteCommExBoardEntry 1 }
|
||
|
||
hwCommExBoardEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (32266..33049)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Communication Expansion Board device ID. Value range: 032,256 to 033,249, in which the first digits indicate the device type and the last three digits indicate the device SN."
|
||
::= { hwSiteCommExBoardEntry 2 }
|
||
|
||
hwCommExBoardEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Communication Expansion Board name, of the character string type, is used to specify battery cabinet. Users can configure it.
|
||
Otherwise, the configured character can not be any other languages except English.
|
||
"
|
||
::= { hwSiteCommExBoardEntry 3 }
|
||
|
||
hwSiteDGCommExBoard OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 23 }
|
||
|
||
hwSiteDGCommExBoardTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwSiteDGCommExBoardEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwSiteDGCommExBoard 1 }
|
||
|
||
hwSiteDGCommExBoardEntry OBJECT-TYPE
|
||
SYNTAX HwSiteDGCommExBoardEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
INDEX { hwDGCommExBoardIndex }
|
||
::= { hwSiteDGCommExBoardTable 1 }
|
||
|
||
HwSiteDGCommExBoardEntry ::= SEQUENCE {
|
||
hwDGCommExBoardIndex
|
||
Unsigned32,
|
||
hwDGCommExBoardEquipId
|
||
Unsigned32,
|
||
hwDGCommExBoardEquipName
|
||
OCTET STRING
|
||
}
|
||
|
||
hwDGCommExBoardIndex OBJECT-TYPE
|
||
SYNTAX Unsigned32 (2185)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DG Communication Expansion Board table index,which value is according to the actual subject. Lines of the device list are restricted by the quantity of DG Communication Expansion Board"
|
||
::= { hwSiteDGCommExBoardEntry 1 }
|
||
|
||
hwDGCommExBoardEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (34001)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DG Communication Expansion Board device ID. Value range: 034'001, in which the first digits indicate the device type and the last three digits indicate the device SN."
|
||
::= { hwSiteDGCommExBoardEntry 2 }
|
||
|
||
hwDGCommExBoardEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DG Communication Expansion Board name, of the character string type, is used to specify battery cabinet. Users can configure it.
|
||
Otherwise, the configured character can not be any other languages except English.
|
||
"
|
||
::= { hwSiteDGCommExBoardEntry 3 }
|
||
|
||
hwAcbGroupEquip OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 17 }
|
||
|
||
hwAcbGroupSampTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwAcbGroupSampEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwAcbGroupEquip 1 }
|
||
|
||
hwAcbGroupSampEntry OBJECT-TYPE
|
||
SYNTAX HwAcbGroupSampEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
INDEX { hwAcbGroupIndex }
|
||
::= { hwAcbGroupSampTable 1 }
|
||
|
||
HwAcbGroupSampEntry ::= SEQUENCE {
|
||
hwAcbGroupIndex
|
||
Unsigned32,
|
||
hwAcbGroupEquipId
|
||
Unsigned32,
|
||
hwAcbGroupEquipName
|
||
OCTET STRING,
|
||
hwAcbGroupBatRunningState
|
||
INTEGER,
|
||
hwAcbGroupBatVolt
|
||
Unsigned32,
|
||
hwAcbGroupBatCurr
|
||
Integer32,
|
||
hwAcbGroupTotalCapacity
|
||
Unsigned32,
|
||
hwAcbGroupTotalRemainCapacity
|
||
Unsigned32,
|
||
hwAcbGroupTemperature
|
||
Integer32,
|
||
hwAcbGroupBackupTime
|
||
Unsigned32,
|
||
hwAcbGroupEsmuCommNum
|
||
Unsigned32,
|
||
hwAcbGroupBatSoh
|
||
Unsigned32,
|
||
hwAcbGroupTotalDischargeDepth
|
||
Unsigned32
|
||
}
|
||
|
||
hwAcbGroupIndex OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..256)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The battery group equip Index."
|
||
::= { hwAcbGroupSampEntry 1 }
|
||
|
||
hwAcbGroupEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The battery group equip ID no."
|
||
::= { hwAcbGroupSampEntry 2 }
|
||
|
||
hwAcbGroupEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The battery group equip name."
|
||
::= { hwAcbGroupSampEntry 3 }
|
||
|
||
hwAcbGroupBatRunningState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
firstOn(1),
|
||
powerOff(2),
|
||
float(3),
|
||
equal(4),
|
||
dicharge(5),
|
||
charge(6),
|
||
test(7),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the Battery group unit running state. It is an enumeration type:
|
||
If the enumeration value is 1, it indicates the Battery is first on line,
|
||
If the enumeration value is 2, it indicates that Battery power off,
|
||
If the enumeration value is 3, it indicates that Battery is on float charging,
|
||
If the enumeration value is 4, it indicates that Battery is on equal charging,
|
||
If the enumeration value is 5, it indicates that Battery is on discharge,
|
||
If the enumeration value is 6, it indicates that Battery is on charge,
|
||
If the enumeration value is 7, it indicates that Battery is on test,
|
||
If the enumeration value is 255, it indicates Battery uint operation status unknown.
|
||
"
|
||
::= { hwAcbGroupSampEntry 4 }
|
||
|
||
hwAcbGroupBatVolt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The battery volt; Value range: 0 to 100,
|
||
units: V.
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbGroupSampEntry 5 }
|
||
|
||
hwAcbGroupBatCurr OBJECT-TYPE
|
||
SYNTAX Integer32 (-40000..40000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The battery current; Value range: -4000 to 4000,
|
||
units: A.
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbGroupSampEntry 6 }
|
||
|
||
hwAcbGroupTotalCapacity OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The battery total capacity; Value range: 0 to 10000,
|
||
units: Ah.
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbGroupSampEntry 7 }
|
||
|
||
hwAcbGroupTotalRemainCapacity OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The battery total remain capacity; Value range:0 to 100,
|
||
units: %.
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbGroupSampEntry 8 }
|
||
|
||
hwAcbGroupTemperature OBJECT-TYPE
|
||
SYNTAX Integer32 (-500..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The battery temperature; Value range:-50 to 100,
|
||
units: degC.
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbGroupSampEntry 9 }
|
||
|
||
hwAcbGroupBackupTime OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..2560)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The battery backup time; Value range: 0 to 256,
|
||
units: h.
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbGroupSampEntry 11 }
|
||
|
||
hwAcbGroupEsmuCommNum OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The esmu communicate number,
|
||
Value range: 0 to 100.
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbGroupSampEntry 12 }
|
||
|
||
hwAcbGroupBatSoh OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The battery soh: 0 to 100,
|
||
units: %.
|
||
and the value is accurate to one decimal place (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbGroupSampEntry 13 }
|
||
|
||
hwAcbGroupTotalDischargeDepth OBJECT-TYPE
|
||
SYNTAX Unsigned32 (10..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The battery total discharge depth,
|
||
units: %.
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbGroupSampEntry 22 }
|
||
|
||
hwAcbGroupSetTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwAcbGroupSetEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwAcbGroupEquip 2 }
|
||
|
||
hwAcbGroupSetEntry OBJECT-TYPE
|
||
SYNTAX HwAcbGroupSetEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
INDEX { hwAcbGroupCellNum }
|
||
::= { hwAcbGroupSetTable 1 }
|
||
|
||
HwAcbGroupSetEntry ::= SEQUENCE {
|
||
hwAcbGroupCellNum
|
||
Unsigned32,
|
||
hwAcbGroupSetTotalCapacity
|
||
Unsigned32,
|
||
hwAcbGroupEqualVolt
|
||
Unsigned32,
|
||
hwAcbGroupFloatVolt
|
||
Unsigned32,
|
||
hwAcbGroupChargeCurrLimitThr
|
||
Unsigned32,
|
||
hwAcbGroupOverCurThr
|
||
Unsigned32,
|
||
hwAcbGroupHighTempThr
|
||
Unsigned32,
|
||
hwAcbGroupLowTempThr
|
||
Integer32,
|
||
hwAcbGroupDodToAcidBattery
|
||
Unsigned32,
|
||
hwAcbGroupDefaultChargeCurrLimitThr
|
||
Unsigned32
|
||
}
|
||
|
||
hwAcbGroupCellNum OBJECT-TYPE
|
||
SYNTAX Unsigned32 (1..32)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery cell number.
|
||
Value range: 1 to 32,
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbGroupSetEntry 5 }
|
||
|
||
hwAcbGroupSetTotalCapacity OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..10000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The battery total capacity,
|
||
units: wh.
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbGroupSetEntry 6 }
|
||
|
||
hwAcbGroupEqualVolt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (420..580)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery equalcharge voltage, can be configued by users.
|
||
Value range: 42 to 58,
|
||
units: v,
|
||
and the value is accurate to one decimal space (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
||
"
|
||
::= { hwAcbGroupSetEntry 11 }
|
||
|
||
hwAcbGroupFloatVolt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (420..580)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery floatcharge voltage, can be configued by users.
|
||
Value range: 42 to 58,
|
||
units: v,
|
||
and the value is accurate to one decimal space (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
||
"
|
||
::= { hwAcbGroupSetEntry 12 }
|
||
|
||
hwAcbGroupChargeCurrLimitThr OBJECT-TYPE
|
||
SYNTAX Unsigned32 (5..200)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery charge limited threhold , can be configued by users.
|
||
Value range: 0.05 to 2,
|
||
units: C10,
|
||
and the value is accurate to two decimal space (.01).
|
||
If the setting value is beyond the current support range, it will fail.
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbGroupSetEntry 13 }
|
||
|
||
hwAcbGroupOverCurThr OBJECT-TYPE
|
||
SYNTAX Unsigned32 (15..120)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery over charge current limited threhold , can be configued by users.
|
||
Value range: 0.15 to 1.2,
|
||
units: C10,
|
||
and the value is accurate to two decimal space (.01).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbGroupSetEntry 14 }
|
||
|
||
hwAcbGroupHighTempThr OBJECT-TYPE
|
||
SYNTAX Unsigned32 (35..70)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Upper threshold of the environment temperature alarm, can be configured by users.
|
||
Value range: 35 to 70,
|
||
units: centigrade (<28><>C),
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbGroupSetEntry 21 }
|
||
|
||
hwAcbGroupLowTempThr OBJECT-TYPE
|
||
SYNTAX Integer32 (-50..0)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Lower threshold of the environment temperature alarm, can be configured by users.
|
||
Value range: -50 to 0,
|
||
units: centigrade (degC),
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbGroupSetEntry 22 }
|
||
|
||
hwAcbGroupDodToAcidBattery OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The lithium battery discharge depth for Acid Battery running; ,units: %."
|
||
::= { hwAcbGroupSetEntry 26 }
|
||
|
||
hwAcbGroupDefaultChargeCurrLimitThr OBJECT-TYPE
|
||
SYNTAX Unsigned32 (5..200)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery default charge limited threhold , can be configued by users.
|
||
Value range: 0.05 to 2,
|
||
units: C10,
|
||
and the value is accurate to two decimal space (.01).
|
||
If the setting value is beyond the current support range, it will fail.
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. "
|
||
::= { hwAcbGroupSetEntry 27 }
|
||
|
||
hwAcbEquip OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 18 }
|
||
|
||
hwAcbBaseTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwAcbBaseEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwAcbEquip 1 }
|
||
|
||
hwAcbBaseEntry OBJECT-TYPE
|
||
SYNTAX HwAcbBaseEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
INDEX { hwAcbIndex }
|
||
::= { hwAcbBaseTable 1 }
|
||
|
||
HwAcbBaseEntry ::= SEQUENCE {
|
||
hwAcbIndex
|
||
Unsigned32,
|
||
hwAcbEquipId
|
||
Unsigned32,
|
||
hwAcbEquipName
|
||
OCTET STRING,
|
||
hwAcbEquipAddr
|
||
Unsigned32,
|
||
hwAcbSoftVar
|
||
OCTET STRING
|
||
}
|
||
|
||
hwAcbIndex OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The battery equip Index."
|
||
::= { hwAcbBaseEntry 1 }
|
||
|
||
hwAcbEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The battery equip ID no."
|
||
::= { hwAcbBaseEntry 2 }
|
||
|
||
hwAcbEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The battery equip name."
|
||
::= { hwAcbBaseEntry 3 }
|
||
|
||
hwAcbEquipAddr OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..255)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The battery communica address."
|
||
::= { hwAcbBaseEntry 4 }
|
||
|
||
hwAcbSoftVar OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The Battery software version."
|
||
::= { hwAcbBaseEntry 5 }
|
||
|
||
hwAcbSampTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwAcbSampEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwAcbEquip 2 }
|
||
|
||
hwAcbSampEntry OBJECT-TYPE
|
||
SYNTAX HwAcbSampEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
INDEX { hwAcbBatVolt }
|
||
::= { hwAcbSampTable 1 }
|
||
|
||
HwAcbSampEntry ::= SEQUENCE {
|
||
hwAcbBatVolt
|
||
Unsigned32,
|
||
hwAcbBatCurr
|
||
Integer32,
|
||
hwAcbRunningStatus
|
||
INTEGER,
|
||
hwAcbBatSoh
|
||
Unsigned32,
|
||
hwAcbBatCapacity
|
||
Unsigned32,
|
||
hwAcbBatCell1Volt
|
||
Unsigned32,
|
||
hwAcbBatCell2Volt
|
||
Unsigned32,
|
||
hwAcbBatCell3Volt
|
||
Unsigned32,
|
||
hwAcbBatCell4Volt
|
||
Unsigned32,
|
||
hwAcbBatCell5Volt
|
||
Unsigned32,
|
||
hwAcbBatCell6Volt
|
||
Unsigned32,
|
||
hwAcbBatCell7Volt
|
||
Unsigned32,
|
||
hwAcbBatCell8Volt
|
||
Unsigned32,
|
||
hwAcbBatCell9Volt
|
||
Unsigned32,
|
||
hwAcbBatCell10Volt
|
||
Unsigned32,
|
||
hwAcbBatCell11Volt
|
||
Unsigned32,
|
||
hwAcbBatCell12Volt
|
||
Unsigned32,
|
||
hwAcbBatCell13Volt
|
||
Unsigned32,
|
||
hwAcbBatCell14Volt
|
||
Unsigned32,
|
||
hwAcbBatCell15Volt
|
||
Unsigned32,
|
||
hwAcbBatCell16Volt
|
||
Unsigned32,
|
||
hwAcbBatCell17Temp
|
||
Integer32,
|
||
hwAcbBatCell18Temp
|
||
Integer32,
|
||
hwAcbBatCell19Temp
|
||
Integer32,
|
||
hwAcbBatCell20Temp
|
||
Integer32,
|
||
hwAcbBatCell21Temp
|
||
Integer32,
|
||
hwAcbBatCell22Temp
|
||
Integer32,
|
||
hwAcbBatCell1Temp
|
||
Integer32,
|
||
hwAcbBatCell2Temp
|
||
Integer32,
|
||
hwAcbBatCell3Temp
|
||
Integer32,
|
||
hwAcbBatCell4Temp
|
||
Integer32,
|
||
hwAcbBatCell5Temp
|
||
Integer32,
|
||
hwAcbBatCell6Temp
|
||
Integer32,
|
||
hwAcbBatCell7Temp
|
||
Integer32,
|
||
hwAcbBatCell8Temp
|
||
Integer32,
|
||
hwAcbBatCell9Temp
|
||
Integer32,
|
||
hwAcbBatCell10Temp
|
||
Integer32,
|
||
hwAcbBatCell11Temp
|
||
Integer32,
|
||
hwAcbBatCell12Temp
|
||
Integer32,
|
||
hwAcbBatCell13Temp
|
||
Integer32,
|
||
hwAcbBatCell14Temp
|
||
Integer32,
|
||
hwAcbBatCell15Temp
|
||
Integer32,
|
||
hwAcbBatCell16Temp
|
||
Integer32,
|
||
hwAcbBatCell17Volt
|
||
Unsigned32,
|
||
hwAcbBatCell18Volt
|
||
Unsigned32,
|
||
hwAcbBatCell19Volt
|
||
Unsigned32,
|
||
hwAcbBatCell20Volt
|
||
Unsigned32,
|
||
hwAcbBatCell21Volt
|
||
Unsigned32,
|
||
hwAcbBatCell22Volt
|
||
Unsigned32
|
||
}
|
||
|
||
hwAcbBatVolt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..600)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"voltage of the battery. It indicates the real-time statistics of the battery on the site.
|
||
Value range: 0 to 60,
|
||
unit: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 1 }
|
||
|
||
hwAcbBatCurr OBJECT-TYPE
|
||
SYNTAX Integer32 (-2000..2000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Current of the battery. It indicates the real-time statistics of the battery on the site.
|
||
Value range: -200 to 200,
|
||
unit: A,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 2 }
|
||
|
||
hwAcbRunningStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
offline(1),
|
||
online(2),
|
||
sleep(3),
|
||
disconnect(4),
|
||
charge(5),
|
||
discharge(6),
|
||
standby(7),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery charging state, indicates the charging and discharging information about the battery group. It is an enumeration type.
|
||
If the enumeration value is 1, it indicates a battery in the Offline state.
|
||
If the enumeration value is 2, it indicates a battery in the online state.
|
||
If the enumeration value is 3, it indicates a battery in the Sleep state.
|
||
If the enumeration value is 4, it indicates a battery in the disconnect state.
|
||
If the enumeration value is 5, it indicates a battery in the Charge state.
|
||
If the enumeration value is 6, it indicates a battery in the Discharge state.
|
||
If the enumeration value is 7, it indicates a battery in the Standby state.
|
||
If the enumeration value is 255, it indicates a battery group in the unknown state."
|
||
::= { hwAcbSampEntry 3 }
|
||
|
||
hwAcbBatSoh OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Soh of the battery. It indicates the real-time statistics of the battery on the site.
|
||
Value range: 0 to 100,
|
||
unit: %,
|
||
and the value is accurate to two decimal place (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 4 }
|
||
|
||
hwAcbBatCapacity OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Capacity of the battery.
|
||
Value range: 0 to 10000,
|
||
unit: Ah,
|
||
and the value is accurate to two decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 5 }
|
||
|
||
hwAcbBatCell1Volt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..50)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: 0 to 5,
|
||
unit: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 6 }
|
||
|
||
hwAcbBatCell2Volt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..50)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: 0 to 5,
|
||
unit: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 7 }
|
||
|
||
hwAcbBatCell3Volt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..50)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: 0 to 5,
|
||
unit: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 8 }
|
||
|
||
hwAcbBatCell4Volt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..50)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: 0 to 5,
|
||
unit: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 9 }
|
||
|
||
hwAcbBatCell5Volt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..50)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: 0 to 5,
|
||
unit: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 10 }
|
||
|
||
hwAcbBatCell6Volt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..50)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: 0 to 5,
|
||
unit: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 11 }
|
||
|
||
hwAcbBatCell7Volt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..50)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: 0 to 5,
|
||
unit: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 12 }
|
||
|
||
hwAcbBatCell8Volt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..50)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: 0 to 5,
|
||
unit: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 13 }
|
||
|
||
hwAcbBatCell9Volt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..50)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: 0 to 5,
|
||
unit: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 14 }
|
||
|
||
hwAcbBatCell10Volt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..50)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: 0 to 5,
|
||
unit: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 15 }
|
||
|
||
hwAcbBatCell11Volt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..50)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: 0 to 5,
|
||
unit: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 16 }
|
||
|
||
hwAcbBatCell12Volt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..50)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: 0 to 5,
|
||
unit: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 17 }
|
||
|
||
hwAcbBatCell13Volt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..50)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: 0 to 5,
|
||
unit: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 18 }
|
||
|
||
hwAcbBatCell14Volt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..50)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: 0 to 5,
|
||
unit: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 19 }
|
||
|
||
hwAcbBatCell15Volt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..50)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: 0 to 5,
|
||
unit: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 20 }
|
||
|
||
hwAcbBatCell16Volt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..50)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: 0 to 5,
|
||
unit: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 21 }
|
||
|
||
hwAcbBatCell17Temp OBJECT-TYPE
|
||
SYNTAX Integer32 (-1000..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: -100 to 100,
|
||
units: centigrade(degC),
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 38 }
|
||
|
||
hwAcbBatCell18Temp OBJECT-TYPE
|
||
SYNTAX Integer32 (-1000..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: -100 to 100,
|
||
units: centigrade(degC),
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 39 }
|
||
|
||
hwAcbBatCell19Temp OBJECT-TYPE
|
||
SYNTAX Integer32 (-1000..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: -100 to 100,
|
||
units: centigrade(degC),
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 40 }
|
||
|
||
hwAcbBatCell20Temp OBJECT-TYPE
|
||
SYNTAX Integer32 (-1000..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: -100 to 100,
|
||
units: centigrade(degC),
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 41 }
|
||
|
||
hwAcbBatCell21Temp OBJECT-TYPE
|
||
SYNTAX Integer32 (-1000..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: -100 to 100,
|
||
units: centigrade(degC),
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 42 }
|
||
|
||
hwAcbBatCell22Temp OBJECT-TYPE
|
||
SYNTAX Integer32 (-1000..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: -100 to 100,
|
||
units: centigrade(degC),
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 43 }
|
||
|
||
hwAcbBatCell1Temp OBJECT-TYPE
|
||
SYNTAX Integer32 (-1000..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: -100 to 100,
|
||
units: centigrade(degC),
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 22 }
|
||
|
||
hwAcbBatCell2Temp OBJECT-TYPE
|
||
SYNTAX Integer32 (-1000..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: -100 to 100,
|
||
units: centigrade(degC),
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 23 }
|
||
|
||
hwAcbBatCell3Temp OBJECT-TYPE
|
||
SYNTAX Integer32 (-1000..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: -100 to 100,
|
||
units: centigrade(degC),
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 24 }
|
||
|
||
hwAcbBatCell4Temp OBJECT-TYPE
|
||
SYNTAX Integer32 (-1000..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: -100 to 100,
|
||
units: centigrade(degC),
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 25 }
|
||
|
||
hwAcbBatCell5Temp OBJECT-TYPE
|
||
SYNTAX Integer32 (-1000..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: -100 to 100,
|
||
units: centigrade(degC),
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 26 }
|
||
|
||
hwAcbBatCell6Temp OBJECT-TYPE
|
||
SYNTAX Integer32 (-1000..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: -100 to 100,
|
||
units: centigrade(degC),
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 27 }
|
||
|
||
hwAcbBatCell7Temp OBJECT-TYPE
|
||
SYNTAX Integer32 (-1000..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: -100 to 100,
|
||
units: centigrade(degC),
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 28 }
|
||
|
||
hwAcbBatCell8Temp OBJECT-TYPE
|
||
SYNTAX Integer32 (-1000..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: -100 to 100,
|
||
units: centigrade(degC),
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 29 }
|
||
|
||
hwAcbBatCell9Temp OBJECT-TYPE
|
||
SYNTAX Integer32 (-1000..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: -100 to 100,
|
||
units: centigrade(degC),
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 30 }
|
||
|
||
hwAcbBatCell10Temp OBJECT-TYPE
|
||
SYNTAX Integer32 (-1000..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: -100 to 100,
|
||
units: centigrade(degC),
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 31 }
|
||
|
||
hwAcbBatCell11Temp OBJECT-TYPE
|
||
SYNTAX Integer32 (-1000..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: -100 to 100,
|
||
units: centigrade(degC),
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 32 }
|
||
|
||
hwAcbBatCell12Temp OBJECT-TYPE
|
||
SYNTAX Integer32 (-1000..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: -100 to 100,
|
||
units: centigrade(degC),
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 33 }
|
||
|
||
hwAcbBatCell13Temp OBJECT-TYPE
|
||
SYNTAX Integer32 (-1000..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: -100 to 100,
|
||
units: centigrade(degC),
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 34 }
|
||
|
||
hwAcbBatCell14Temp OBJECT-TYPE
|
||
SYNTAX Integer32 (-1000..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: -100 to 100,
|
||
units: centigrade(degC),
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 35 }
|
||
|
||
hwAcbBatCell15Temp OBJECT-TYPE
|
||
SYNTAX Integer32 (-1000..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: -100 to 100,
|
||
units: centigrade(degC),
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 36 }
|
||
|
||
hwAcbBatCell16Temp OBJECT-TYPE
|
||
SYNTAX Integer32 (-1000..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: -100 to 100,
|
||
units: centigrade(degC),
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 37 }
|
||
|
||
hwAcbBatCell17Volt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..50)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: 0 to 5,
|
||
unit: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 44 }
|
||
|
||
hwAcbBatCell18Volt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..50)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: 0 to 5,
|
||
unit: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 45 }
|
||
|
||
hwAcbBatCell19Volt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..50)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: 0 to 5,
|
||
unit: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 46 }
|
||
|
||
hwAcbBatCell20Volt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..50)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: 0 to 5,
|
||
unit: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 47 }
|
||
|
||
hwAcbBatCell21Volt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..50)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: 0 to 5,
|
||
unit: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 48 }
|
||
|
||
hwAcbBatCell22Volt OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..50)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
|
||
Value range: 0 to 5,
|
||
unit: V,
|
||
and the value is accurate to one decimal place (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwAcbSampEntry 49 }
|
||
|
||
hwAcbSetTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwAcbSetEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwAcbEquip 3 }
|
||
|
||
hwAcbSetEntry OBJECT-TYPE
|
||
SYNTAX HwAcbSetEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
INDEX { hwAcbGyroEnable }
|
||
::= { hwAcbSetTable 1 }
|
||
|
||
HwAcbSetEntry ::= SEQUENCE {
|
||
hwAcbGyroEnable
|
||
INTEGER,
|
||
hwAcbGyroSensitivityLevel
|
||
INTEGER
|
||
}
|
||
|
||
hwAcbGyroEnable OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
disable(1),
|
||
enable(2),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Gyro Function Enable,
|
||
Restricted use in special areas. If the value of the device is within the range, but the setting fails, the function is not supported.
|
||
It is an enumeration value:
|
||
If the enumeration value is 1, it means to gyro function disable,
|
||
If the enumeration value is 2, it means to gyro function enable,
|
||
If the enumeration value is 255, it indicates gyro in the unknown state."
|
||
::= { hwAcbSetEntry 5 }
|
||
|
||
hwAcbGyroSensitivityLevel OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
low(1),
|
||
midium(2),
|
||
high(3),
|
||
unknown(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Gyro Level of Sensitivity.
|
||
Restricted use in special areas. If the value of the device is within the range, but the setting fails, the function is not supported.
|
||
It is an enumeration value:
|
||
If the enumeration value is 1, it means to low sensitivity,
|
||
If the enumeration value is 2, it means to medium sensitivity,
|
||
If the enumeration value is 3, it means to high sensitivity,
|
||
If the enumeration value is 255, it indicates gyro in the unknown level."
|
||
::= { hwAcbSetEntry 6 }
|
||
|
||
hwElockEquip OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 27 }
|
||
|
||
hwElockEquipTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwElockEquipEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwElockEquip 1 }
|
||
|
||
hwElockEquipEntry OBJECT-TYPE
|
||
SYNTAX HwElockEquipEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
INDEX { hwElockEquipIndex }
|
||
::= { hwElockEquipTable 1 }
|
||
|
||
HwElockEquipEntry ::= SEQUENCE {
|
||
hwElockEquipIndex
|
||
Unsigned32,
|
||
hwElockEquipId
|
||
Unsigned32,
|
||
hwElockEquipName
|
||
OCTET STRING
|
||
}
|
||
|
||
hwElockEquipIndex OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The elock equip Index."
|
||
::= { hwElockEquipEntry 1 }
|
||
|
||
hwElockEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The elock equip ID no."
|
||
::= { hwElockEquipEntry 2 }
|
||
|
||
hwElockEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
" The elock equip name."
|
||
::= { hwElockEquipEntry 3 }
|
||
|
||
hwTemHumEquip OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 28 }
|
||
|
||
hwTemHumEquipTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwTemHumEquipEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwTemHumEquip 1 }
|
||
|
||
hwTemHumEquipEntry OBJECT-TYPE
|
||
SYNTAX HwTemHumEquipEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
INDEX { hwTemHumEquipIndex }
|
||
::= { hwTemHumEquipTable 1 }
|
||
|
||
HwTemHumEquipEntry ::= SEQUENCE {
|
||
hwTemHumEquipIndex
|
||
Unsigned32,
|
||
hwTemHumEquipId
|
||
Unsigned32,
|
||
hwTemHumEquipName
|
||
OCTET STRING,
|
||
hwTemHumEquipAmbientTemp
|
||
Integer32,
|
||
hwTemHumEquipAmbientHumidity
|
||
Unsigned32,
|
||
hwSetHumTempUpperLimit
|
||
Integer32,
|
||
hwSetHumTempLowerLimit
|
||
Integer32,
|
||
hwSetHumidityUpperLimit
|
||
Integer32,
|
||
hwSetHumidityLowerLimit
|
||
Integer32,
|
||
hwTemHumEquipAddress
|
||
Unsigned32
|
||
}
|
||
|
||
hwTemHumEquipIndex OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The tem_hum equip Index."
|
||
::= { hwTemHumEquipEntry 1 }
|
||
|
||
hwTemHumEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The tem_hum equip ID no."
|
||
::= { hwTemHumEquipEntry 2 }
|
||
|
||
hwTemHumEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
" The tem_hum equip name."
|
||
::= { hwTemHumEquipEntry 3 }
|
||
|
||
hwTemHumEquipAmbientTemp OBJECT-TYPE
|
||
SYNTAX Integer32 (-20..80)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"the environment temperature.
|
||
units: centigrade (degC),
|
||
and the value is an integer (1). "
|
||
::= { hwTemHumEquipEntry 4 }
|
||
|
||
hwTemHumEquipAmbientHumidity OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"environment temperature ,
|
||
units: %RH,
|
||
and the value is an integer (1). "
|
||
::= { hwTemHumEquipEntry 5 }
|
||
|
||
hwSetHumTempUpperLimit OBJECT-TYPE
|
||
SYNTAX Integer32 ( 25..80)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Upper threshold of the environment temperature alarm, can be configured by users.
|
||
Value range: 25 to 80,
|
||
units: centigrade (degC),
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
||
NOTE: There is linkage between hwSetHumTempUpperLimit and hwSetHumTempLowerLimit"
|
||
::= { hwTemHumEquipEntry 6 }
|
||
|
||
hwSetHumTempLowerLimit OBJECT-TYPE
|
||
SYNTAX Integer32 ( -20..20)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Lower threshold of the environment temperature alarm, can be configured by users.
|
||
Value range: -20 to 20,
|
||
units: centigrade (degC),
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
||
NOTE: There is linkage between hwSetHumTempUpperLimit and hwSetHumTempLowerLimit"
|
||
::= { hwTemHumEquipEntry 7 }
|
||
|
||
hwSetHumidityUpperLimit OBJECT-TYPE
|
||
SYNTAX Integer32 (0..100)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Upper threshold of the environment humility alarm, can be configured by users.
|
||
Value range: 0 to 100,
|
||
units: %RH,
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwTemHumEquipEntry 8 }
|
||
|
||
hwSetHumidityLowerLimit OBJECT-TYPE
|
||
SYNTAX Integer32 (0..100)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Lower threshold of the environment humility alarm, can be configured by users.
|
||
Value range: 0 to 100,
|
||
units: %RH,
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwTemHumEquipEntry 9 }
|
||
|
||
hwTemHumEquipAddress OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..255)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Device address
|
||
And the value is an integer (1)."
|
||
::= { hwTemHumEquipEntry 10 }
|
||
|
||
hwHeaterEquip OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 29 }
|
||
|
||
hwHeaterDeviceTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwHeaterDeviceEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
""
|
||
::= { hwHeaterEquip 1 }
|
||
|
||
hwHeaterDeviceEntry OBJECT-TYPE
|
||
SYNTAX HwHeaterDeviceEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
""
|
||
INDEX { hwHeaterDeviceIndex }
|
||
::= { hwHeaterDeviceTable 1 }
|
||
|
||
HwHeaterDeviceEntry ::= SEQUENCE {
|
||
hwHeaterDeviceIndex
|
||
Unsigned32,
|
||
hwHeaterDeviceEquipId
|
||
Unsigned32,
|
||
hwHeaterDeviceEquipName
|
||
OCTET STRING,
|
||
hwHeaterStartTemperature
|
||
Integer32,
|
||
hwHeaterStopTemperature
|
||
Integer32
|
||
}
|
||
|
||
hwHeaterDeviceIndex OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"heater device table index."
|
||
::= { hwHeaterDeviceEntry 1 }
|
||
|
||
hwHeaterDeviceEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"heater device equipid."
|
||
::= { hwHeaterDeviceEntry 2 }
|
||
|
||
hwHeaterDeviceEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..63))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"heater device equipname."
|
||
::= { hwHeaterDeviceEntry 3 }
|
||
|
||
hwHeaterStartTemperature OBJECT-TYPE
|
||
SYNTAX Integer32 (-10..15)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"heater start temperature;
|
||
Value range:-10 to 15.Unit: degC.
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
||
note: hwHeaterStartTemperature's set value must below hwHeaterStopTemperature's value."
|
||
::= { hwHeaterDeviceEntry 4 }
|
||
|
||
hwHeaterStopTemperature OBJECT-TYPE
|
||
SYNTAX Integer32 (5..20)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"heater stop temperature;
|
||
Value range: 5 to 20.Unit: degC.
|
||
and the value is an integer (1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
||
note: hwHeaterStartTemperature's set value must below hwHeaterStopTemperature's value."
|
||
::= { hwHeaterDeviceEntry 5 }
|
||
|
||
hwSiteDMU OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 31 }
|
||
|
||
hwSiteDMUSampTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwSiteDMUSampEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
""
|
||
::= { hwSiteDMU 1 }
|
||
|
||
hwSiteDMUSampEntry OBJECT-TYPE
|
||
SYNTAX HwSiteDMUSampEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
""
|
||
INDEX { hwDMUIndex }
|
||
::= { hwSiteDMUSampTable 1 }
|
||
|
||
HwSiteDMUSampEntry ::= SEQUENCE {
|
||
hwDMUIndex
|
||
Unsigned32,
|
||
hwDMUEquipId
|
||
Unsigned32,
|
||
hwDMUEquipName
|
||
OCTET STRING,
|
||
hwDMUDCOutputVoltage
|
||
Unsigned32,
|
||
hwDMULoadCurrent
|
||
Unsigned32,
|
||
hwDMUTotalLoadConsumption
|
||
Unsigned32
|
||
}
|
||
|
||
hwDMUIndex OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..256)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DMU table index,
|
||
which value range:1 to 256.
|
||
Lines of the device list are restricted by the quantity of DMU."
|
||
::= { hwSiteDMUSampEntry 1 }
|
||
|
||
hwDMUEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32 (33001..33255)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DMU device ID.
|
||
Value range: 033'001 to 033'255,
|
||
in which the first digits indicate the device type and the last three digits indicate the device SN."
|
||
::= { hwSiteDMUSampEntry 2 }
|
||
|
||
hwDMUEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..56))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Device name of the DMU module,
|
||
character string type, is used to specify the DMU module. Otherwise, the configured character can not be any other languages except English."
|
||
::= { hwSiteDMUSampEntry 3 }
|
||
|
||
hwDMUDCOutputVoltage OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..1000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DC output voltage: 0 to 100,
|
||
units: V,
|
||
and the value is one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteDMUSampEntry 4 }
|
||
|
||
hwDMULoadCurrent OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..300000)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Load current: 0 to 30000,
|
||
units: A,
|
||
and the value is one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteDMUSampEntry 5 }
|
||
|
||
hwDMUTotalLoadConsumption OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..4294967295)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Total load consumption: 0 to 4294967295,
|
||
units: kWh,
|
||
and the value is one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteDMUSampEntry 6 }
|
||
|
||
hwSiteDMUSetTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwSiteDMUSetEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
""
|
||
::= { hwSiteDMU 2 }
|
||
|
||
hwSiteDMUSetEntry OBJECT-TYPE
|
||
SYNTAX HwSiteDMUSetEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
""
|
||
INDEX { hwSiteDMULoad1LvdEn }
|
||
::= { hwSiteDMUSetTable 1 }
|
||
|
||
HwSiteDMUSetEntry ::= SEQUENCE {
|
||
hwSiteDMULoad1LvdEn
|
||
INTEGER,
|
||
hwSiteDMULoad1LvdMode
|
||
INTEGER,
|
||
hwSiteDMULoad1LvdVoltage
|
||
Unsigned32,
|
||
hwSiteDMULoad1LvdReconVoltage
|
||
Unsigned32,
|
||
hwSiteDMULoad1LvdTime
|
||
Integer32,
|
||
hwSiteDMULoad1LvdCapacity
|
||
Integer32,
|
||
hwSiteDMULoad2LvdEn
|
||
INTEGER,
|
||
hwSiteDMULoad2LvdMode
|
||
INTEGER,
|
||
hwSiteDMULoad2LvdVoltage
|
||
Unsigned32,
|
||
hwSiteDMULoad2LvdReconVoltage
|
||
Unsigned32,
|
||
hwSiteDMULoad2LvdTime
|
||
Integer32,
|
||
hwSiteDMULoad2LvdCapacity
|
||
Integer32
|
||
}
|
||
|
||
hwSiteDMULoad1LvdEn OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
disable(1),
|
||
enable(2)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"load1 lvd enable :It is an enumeration type:
|
||
If the enumeration value is 1, it means to disable the lvd control;
|
||
If the enumeration value is 2, it means to enable the lvd control "
|
||
::= { hwSiteDMUSetEntry 1 }
|
||
|
||
hwSiteDMULoad1LvdMode OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
voltagemode(1),
|
||
timemode(2)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"load1 lvd mode :It is an enumeration type:
|
||
If the enumeration value is 1, it means the voltage mode;
|
||
If the enumeration value is 2, it means the time mode "
|
||
::= { hwSiteDMUSetEntry 2 }
|
||
|
||
hwSiteDMULoad1LvdVoltage OBJECT-TYPE
|
||
SYNTAX Unsigned32 (360..560)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Low-voltage power-off voltage of the DMU unit can be configured by users.
|
||
Its value range: 36 to 56,
|
||
units: V,
|
||
and the value is accurate to one decimal space (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteDMUSetEntry 3 }
|
||
|
||
hwSiteDMULoad1LvdReconVoltage OBJECT-TYPE
|
||
SYNTAX Unsigned32 (370..580)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Low-voltage power-off recover of the DMU unit can be configured by users.
|
||
Its value range: 37.0 to 58.0,
|
||
unit: V,
|
||
and the value is accurate to one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
||
NOTE: There is linkage between hwSiteDMULoad1LvdVoltage and hwSiteDMULoad1LvdReconVoltage"
|
||
::= { hwSiteDMUSetEntry 4 }
|
||
|
||
hwSiteDMULoad1LvdTime OBJECT-TYPE
|
||
SYNTAX Integer32 (0..6000)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Low-voltage power-off disconnected time, It can be configured by users, and its value is an integer (1).
|
||
Here, if lvd mode is time mode, value range defines between 0 to 6000,
|
||
unit: minutes(min).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
||
NOTE: Only the lvd in time power off mode, this parameter can be configured successfully."
|
||
::= { hwSiteDMUSetEntry 5 }
|
||
|
||
hwSiteDMULoad1LvdCapacity OBJECT-TYPE
|
||
SYNTAX Integer32 (0..99)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Power-off unit control the power off, when Remaining capacity percentage of the battery strings is below the calue.
|
||
Value range: 0 to 99,
|
||
unit: %,
|
||
and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
||
NOTE: Only the lvd in capacity power off mode, this parameter can be configured successfully."
|
||
::= { hwSiteDMUSetEntry 6 }
|
||
|
||
hwSiteDMULoad2LvdEn OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
disable(1),
|
||
enable(2)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"load1 lvd enable :It is an enumeration type:
|
||
If the enumeration value is 1, it means to disable the lvd control;
|
||
If the enumeration value is 2, it means to enable the lvd control "
|
||
::= { hwSiteDMUSetEntry 7 }
|
||
|
||
hwSiteDMULoad2LvdMode OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
voltagemode(1),
|
||
timemode(2)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"load1 lvd mode :It is an enumeration type:
|
||
If the enumeration value is 1, it means the voltage mode;
|
||
If the enumeration value is 2, it means the time mode "
|
||
::= { hwSiteDMUSetEntry 8 }
|
||
|
||
hwSiteDMULoad2LvdVoltage OBJECT-TYPE
|
||
SYNTAX Unsigned32 (360..560)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Low-voltage power-off voltage of the DMU unit can be configured by users.
|
||
Its value range: 36 to 56,
|
||
units: V,
|
||
and the value is accurate to one decimal space (.1).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid."
|
||
::= { hwSiteDMUSetEntry 9 }
|
||
|
||
hwSiteDMULoad2LvdReconVoltage OBJECT-TYPE
|
||
SYNTAX Unsigned32 (370..580)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Low-voltage power-off recover of the DMU unit can be configured by users.
|
||
Its value range: 37.0 to 58.0,
|
||
unit: V,
|
||
and the value is accurate to one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
||
NOTE: There is linkage between hwSiteDMULoad2LvdVoltage and hwSiteDMULoad2LvdReconVoltage"
|
||
::= { hwSiteDMUSetEntry 10 }
|
||
|
||
hwSiteDMULoad2LvdTime OBJECT-TYPE
|
||
SYNTAX Integer32 (0..6000)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Low-voltage power-off disconnected time, It can be configured by users, and its value is an integer (1).
|
||
Here, if lvd mode is time mode, value range defines between 0 to 6000,
|
||
unit: minutes(min).
|
||
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
||
NOTE: Only the lvd in time power off mode, this parameter can be configured successfully."
|
||
::= { hwSiteDMUSetEntry 11 }
|
||
|
||
hwSiteDMULoad2LvdCapacity OBJECT-TYPE
|
||
SYNTAX Integer32 (0..99)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Power-off unit control the power off, when Remaining capacity percentage of the battery strings is below the calue.
|
||
Value range: 0 to 99,
|
||
unit: %,
|
||
and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
||
NOTE: Only the lvd in capacity power off mode, this parameter can be configured successfully."
|
||
::= { hwSiteDMUSetEntry 12 }
|
||
|
||
hwSiteAts OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 33 }
|
||
|
||
hwAtsSampTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwAtsSampEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
""
|
||
::= { hwSiteAts 1 }
|
||
|
||
hwAtsSampEntry OBJECT-TYPE
|
||
SYNTAX HwAtsSampEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
""
|
||
INDEX { hwAtsIndex }
|
||
::= { hwAtsSampTable 1 }
|
||
|
||
HwAtsSampEntry ::= SEQUENCE {
|
||
hwAtsIndex
|
||
Unsigned32,
|
||
hwAtsEquipId
|
||
Unsigned32,
|
||
hwAtsEquipName
|
||
OCTET STRING
|
||
}
|
||
|
||
hwAtsIndex OBJECT-TYPE
|
||
SYNTAX Unsigned32 (0..256)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Table index of the running ATS modules"
|
||
::= { hwAtsSampEntry 1 }
|
||
|
||
hwAtsEquipId OBJECT-TYPE
|
||
SYNTAX Unsigned32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ATS module ID. "
|
||
::= { hwAtsSampEntry 2 }
|
||
|
||
hwAtsEquipName OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (0..56))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Device name of the ATS module"
|
||
::= { hwAtsSampEntry 3 }
|
||
|
||
hwSiteMonitorMIBTraps OBJECT IDENTIFIER ::= { hwSiteMonitorMIB 2 }
|
||
|
||
hwSiteAlarmTraps OBJECT IDENTIFIER ::= { hwSiteMonitorMIBTraps 1 }
|
||
|
||
hwSiteAlarmTrapsPrefix OBJECT IDENTIFIER ::= { hwSiteAlarmTraps 0 }
|
||
|
||
hwRectifierFaultAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwRectEquipId,hwRectEquipName,hwRectOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"When rectifiers fault alarms happen, a alarm trap will be send. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN.
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 1 }
|
||
|
||
hwRectifierFaultAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwRectEquipId,hwRectEquipName,hwRectOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rectifier Fault alarm resolved.Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 2 }
|
||
|
||
hwRectifierAbnormalAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwRectEquipId,hwRectEquipName,hwRectOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rectifier abnormal alarm, because of communication failure, module protection, or turnoff. Its correlation binding parameters:
|
||
Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 3 }
|
||
|
||
hwRectifierAbnormalAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwRectEquipId,hwRectEquipName,hwRectOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rectifier abnormal alarm resume. Description.Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 4 }
|
||
|
||
hwBattLoopBreakAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattStringEquipId,hwBattStringEquipName,hwBattStringOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery loop disconnect. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery string equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 5 }
|
||
|
||
hwBattLoopBreakAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattStringEquipId,hwBattStringEquipName,hwBattStringOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery loop break alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery string equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 6 }
|
||
|
||
hwBattLvdAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwLvdUnitEquipId,hwLvdUnitEquipName,hwLvdBranchOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery disconnect for low voltage. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN.
|
||
Additionally, in order to identify the device, battery LVD unit equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 7 }
|
||
|
||
hwBattLvdAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwLvdUnitEquipId,hwLvdUnitEquipName,hwLvdBranchOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery LVD alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery LVD unit equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 8 }
|
||
|
||
hwBattOverCurrAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattStringEquipId,hwBattStringEquipName,hwBattStringOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Batterys charge in over current. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery string equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 9 }
|
||
|
||
hwBattOverCurrAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattStringEquipId,hwBattStringEquipName,hwBattStringOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Batterys over current alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery string equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 10 }
|
||
|
||
hwBattStringTempAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattStringEquipId,hwBattStringEquipName,hwBattStringOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery string temperature is too high or too low. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery group ID and group name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 11 }
|
||
|
||
hwBattStringTempAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattStringEquipId,hwBattStringEquipName,hwBattStringOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery string temperature alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery group ID and group name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 12 }
|
||
|
||
hwBattDischargeAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattsGroupId,hwBattsGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery group discharge alarm. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery group ID and group name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 13 }
|
||
|
||
hwBattDischargeAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattsGroupId,hwBattsGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery group discharge alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery group ID and group name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 14 }
|
||
|
||
hwAcInputAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwAcEquipId,hwAcEquipName,hwAcInputOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC absent or AC power off alarms happened. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 15 }
|
||
|
||
hwAcInputAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwAcEquipId,hwAcEquipName,hwAcInputOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC input alarm resumed. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 16 }
|
||
|
||
hwAcVoltAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwAcEquipId,hwAcEquipName,hwAcInputOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC voltage too high or too low. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 17 }
|
||
|
||
hwAcVoltAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwAcEquipId,hwAcEquipName,hwAcInputOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC voltage alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 18 }
|
||
|
||
hwDcVoltAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwDcOutputEquipId,hwDcOutputEquipName,hwDcOutputOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DC voltage alarm. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 19 }
|
||
|
||
hwDcVoltAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwDcOutputEquipId,hwDcOutputEquipName,hwDcOutputOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DC voltage alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, DC equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 20 }
|
||
|
||
hwLoadLvdAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwLvdUnitEquipId,hwLvdUnitEquipName,hwLvdBranchOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Loads disconnect for low voltage. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, load LVD unit equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 21 }
|
||
|
||
hwLoadLvdAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwLvdUnitEquipId,hwLvdUnitEquipName,hwLvdBranchOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Load LVD alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, load LVD unit equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 22 }
|
||
|
||
hwLoadFuseAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwLoadBranchEquipId,hwLoadBranchEquipName,hwLoadBranchOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Load fuse broken down. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery string equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 23 }
|
||
|
||
hwLoadFuseAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwLoadBranchEquipId,hwLoadBranchEquipName,hwLoadBranchOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Load fuse alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery string equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 24 }
|
||
|
||
hwEnvTempAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEnvTempEquipId,hwEnvTempEquipName,hwEnvTempSensorOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Environment temperature is too high or too low. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment temperature sensor equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 25 }
|
||
|
||
hwEnvTempAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEnvTempEquipId,hwEnvTempEquipName,hwEnvTempSensorOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Environment temperature alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment temperature sensor equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 26 }
|
||
|
||
hwEnvHumiAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEnvHumiEquipId,hwEnvHumiEquipName,hwEnvHumiSensorOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Environment humidity is too high or too low. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment humidity sensor equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 27 }
|
||
|
||
hwEnvHumiAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEnvHumiEquipId,hwEnvHumiEquipName,hwEnvHumiSensorOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Environment humidity alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment humidity sensor equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 28 }
|
||
|
||
hwSpareDigitalAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwSpareDigitalEquipId,hwSpareDigitalEquipName,hwSpareDigitalOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Spare digital fault. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, Spare digital equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 29 }
|
||
|
||
hwSpareDigitalAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwSpareDigitalEquipId,hwSpareDigitalEquipName,hwSpareDigitalOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Spare digital alarm resume.Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, Spare digital equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 30 }
|
||
|
||
hwDoorAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEnvUnitsGroupId,hwEnvUnitsGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Door open. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment unit group ID and group name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 31 }
|
||
|
||
hwDoorAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEnvUnitsGroupId,hwEnvUnitsGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Door alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment unit group ID and group name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 32 }
|
||
|
||
hwWaterAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEnvUnitsGroupId,hwEnvUnitsGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Water alarm. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment unit group ID and group name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 33 }
|
||
|
||
hwWaterAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEnvUnitsGroupId,hwEnvUnitsGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Water alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment unit group ID and group name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 34 }
|
||
|
||
hwSmokeAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEnvUnitsGroupId,hwEnvUnitsGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Site is on fire, which is detected by smoke sensors. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment unit group ID and group name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 35 }
|
||
|
||
hwSmokeAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEnvUnitsGroupId,hwEnvUnitsGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Smoke alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment unit group ID and group name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 36 }
|
||
|
||
hwWireAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEnvUnitsGroupId,hwEnvUnitsGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Wire alarm.Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment unit group ID and group name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 37 }
|
||
|
||
hwWireAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEnvUnitsGroupId,hwEnvUnitsGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Wire alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment unit group ID and group name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 38 }
|
||
|
||
hwAcBreakerAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwAcInputBreakerEquipId,hwAcInputBreakerEquipName,hwAcInputBreakerOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC breaker alarm.Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC distribution unit ID and its name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 39 }
|
||
|
||
hwAcBreakerAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwAcInputBreakerEquipId,hwAcInputBreakerEquipName,hwAcInputBreakerOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC breaker alarm resume.Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC distribution unit ID and its name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 40 }
|
||
|
||
hwMultiRectFailureAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwRectsGroupId,hwRectsGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"More than one rectifier reported fault alarms in the same time. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, rectifier group ID and group name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 41 }
|
||
|
||
hwMultiRectFailureAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwRectsGroupId,hwRectsGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Multi-rectifiers fault alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, rectifier group ID and group name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 42 }
|
||
|
||
hwRectRedundAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwRectsGroupId,hwRectsGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rectifiers work redundantly, in this case that some of rectifiers will going to sleep. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, rectifier group ID and group name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 43 }
|
||
|
||
hwRectRedundAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwRectsGroupId,hwRectsGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rectifiers redundant alarm resume, when the power supply and requirement were in balance. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, rectifier group ID and group name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 44 }
|
||
|
||
hwBattUnbalanceAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattStringEquipId,hwBattStringEquipName,hwBattStringOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery works in unbalance state. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery string equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 45 }
|
||
|
||
hwBattUnbalanceAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattStringEquipId,hwBattStringEquipName,hwBattStringOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery unbalance alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery string equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 46 }
|
||
|
||
hwAcFreqFaultAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwAcEquipId,hwAcEquipName,hwAcInputOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC frequency is fault. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 47 }
|
||
|
||
hwAcFreqFaultAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwAcEquipId,hwAcEquipName,hwAcInputOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC frequency alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 48 }
|
||
|
||
hwXmuSelfFaultAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwMonEquipId,hwMonEquipName,hwMonitorOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"There are some fault in XMU itself. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, monitor equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 49 }
|
||
|
||
hwXmuSelfFaultAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwMonEquipId,hwMonEquipName,hwMonitorOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"XMU fault alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, monitor equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 50 }
|
||
|
||
hwRs485CommAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwMonEquipId,hwMonEquipName,hwMonitorOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RS485 communication of monitors disconnect. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, monitor equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 51 }
|
||
|
||
hwRs485CommAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwMonEquipId,hwMonEquipName,hwMonitorOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RS485 communication alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, monitor equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 52 }
|
||
|
||
hwNetCommAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwMonEquipId,hwMonEquipName,hwMonitorOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Network communication of monitors disconnect. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, monitor equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 53 }
|
||
|
||
hwNetCommAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwMonEquipId,hwMonEquipName,hwMonitorOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Network communication alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, monitor equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 54 }
|
||
|
||
hwAcOffLongTimeAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwAcEquipId,hwAcEquipName,hwAcInputOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC power off for a long time alarms happened. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 55 }
|
||
|
||
hwAcOffLongTimeAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwAcEquipId,hwAcEquipName,hwAcInputOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC power off for a long time alarms resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 56 }
|
||
|
||
hwSpdAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEnvUnitsGroupId,hwEnvUnitsGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 57 }
|
||
|
||
hwSpdAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEnvUnitsGroupId,hwEnvUnitsGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 58 }
|
||
|
||
hwBadBatteryTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattsGroupId,hwBattsGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 59 }
|
||
|
||
hwBadBatteryResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattsGroupId,hwBattsGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 60 }
|
||
|
||
hwLvd2DisconnectingTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwLvdUnitEquipId,hwLvdUnitEquipName,hwLvdBranchOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 61 }
|
||
|
||
hwLvd2DisconnectingResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwLvdUnitEquipId,hwLvdUnitEquipName,hwLvdBranchOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 62 }
|
||
|
||
hwBattHighTempTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattStringEquipId,hwBattStringEquipName,hwBattStringOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 63 }
|
||
|
||
hwBattHighTempResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattStringEquipId,hwBattStringEquipName,hwBattStringOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 64 }
|
||
|
||
hwBattLowTempTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattStringEquipId,hwBattStringEquipName,hwBattStringOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 65 }
|
||
|
||
hwBattLowTempResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattStringEquipId,hwBattStringEquipName,hwBattStringOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 66 }
|
||
|
||
hwDcUltraOverVoltageTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwDcOutputEquipId,hwDcOutputEquipName,hwDcOutputOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 67 }
|
||
|
||
hwDcUltraOverVoltageResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwDcOutputEquipId,hwDcOutputEquipName,hwDcOutputOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 68 }
|
||
|
||
hwDcUltraUnderVoltageTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwDcOutputEquipId,hwDcOutputEquipName,hwDcOutputOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 69 }
|
||
|
||
hwDcUltraUnderVoltageResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwDcOutputEquipId,hwDcOutputEquipName,hwDcOutputOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 70 }
|
||
|
||
hwUmiCommFailTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEnvUnitsGroupId,hwEnvUnitsGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 71 }
|
||
|
||
hwUmiCommFailResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEnvUnitsGroupId,hwEnvUnitsGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 72 }
|
||
|
||
hwShortTestFailTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattsGroupId,hwBattsGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 73 }
|
||
|
||
hwShortTestFailResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattsGroupId,hwBattsGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 74 }
|
||
|
||
hwMissingBattTempSensorTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattsGroupId,hwBattsGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 75 }
|
||
|
||
hwMissingBattTempSensorResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattsGroupId,hwBattsGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 76 }
|
||
|
||
hwBattTempSensorFaultTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattsGroupId,hwBattsGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 77 }
|
||
|
||
hwBattTempSensorFaultResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattsGroupId,hwBattsGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 78 }
|
||
|
||
hwAcOverVoltageTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwAcEquipId,hwAcEquipName,hwAcInputOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 79 }
|
||
|
||
hwAcOverVoltageResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwAcEquipId,hwAcEquipName,hwAcInputOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 80 }
|
||
|
||
hwAcUnderVoltageTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwAcEquipId,hwAcEquipName,hwAcInputOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 81 }
|
||
|
||
hwAcUnderVoltageResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwAcEquipId,hwAcEquipName,hwAcInputOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 82 }
|
||
|
||
hwTcuFanAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwFanEquipId,hwFanEquipName,hwFanOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 83 }
|
||
|
||
hwTcuFanAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwFanEquipId,hwFanEquipName,hwFanOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 84 }
|
||
|
||
hwTcuDcAirAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwDcAirEquipId,hwDcAirEquipName,hwDcAirOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 85 }
|
||
|
||
hwTcuDcAirAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwDcAirEquipId,hwDcAirEquipName,hwDcAirOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 86 }
|
||
|
||
hwTripBreakAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwAcInputBreakerEquipId,hwAcInputBreakerEquipName,hwAcInputBreakerOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 87 }
|
||
|
||
hwTripBreakAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwAcInputBreakerEquipId,hwAcInputBreakerEquipName,hwAcInputBreakerOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 88 }
|
||
|
||
hwTripBatteryCabinetAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBatteryCabinetEquipId,hwBatteryCabinetEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 89 }
|
||
|
||
hwTripBattCabAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBatteryCabinetEquipId,hwBatteryCabinetEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 90 }
|
||
|
||
hwBattTestAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattsGroupId,hwBattsGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 103 }
|
||
|
||
hwBattTestAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattsGroupId,hwBattsGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 104 }
|
||
|
||
hwBattContactorFaultTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwDcOutputEquipId,hwDcOutputEquipName,hwDcOutputOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 105 }
|
||
|
||
hwBattContactorFaultResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwDcOutputEquipId,hwDcOutputEquipName,hwDcOutputOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 106 }
|
||
|
||
hwBattFuseBreakAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattStringEquipId,hwBattStringEquipName,hwBattStringOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 107 }
|
||
|
||
hwBattFuseBreakAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattStringEquipId,hwBattStringEquipName,hwBattStringOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 108 }
|
||
|
||
hwDCDAbnormalAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwDcOutputEquipId,hwDcOutputEquipName,hwDcOutputOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 109 }
|
||
|
||
hwDCDAbnormalAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwDcOutputEquipId,hwDcOutputEquipName,hwDcOutputOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 110 }
|
||
|
||
hwACDAbnormalAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwAcEquipId,hwAcEquipName,hwAcInputOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 111 }
|
||
|
||
hwACDAbnormalAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwAcEquipId,hwAcEquipName,hwAcInputOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 112 }
|
||
|
||
hwLoadOverCurrentAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwDcOutputEquipId,hwDcOutputEquipName,hwDcOutputOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 113 }
|
||
|
||
hwLoadOverCurrentAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwDcOutputEquipId,hwDcOutputEquipName,hwDcOutputOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 114 }
|
||
|
||
hwEOSNoResponseAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwLoadBranchEquipId,hwLoadBranchEquipName,hwLoadBranchOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 115 }
|
||
|
||
hwEOSNoResponseAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwLoadBranchEquipId,hwLoadBranchEquipName,hwLoadBranchOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 116 }
|
||
|
||
hwEOSOverLoadAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwLoadBranchEquipId,hwLoadBranchEquipName,hwLoadBranchOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 117 }
|
||
|
||
hwEOSOverLoadAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwLoadBranchEquipId,hwLoadBranchEquipName,hwLoadBranchOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 118 }
|
||
|
||
hwInverterAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName,hwInverterOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 119 }
|
||
|
||
hwInveterAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName,hwInverterOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 120 }
|
||
|
||
hwDGAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwDGEquipId,hwDGEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DG Alarm. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, Spare digital equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 121 }
|
||
|
||
hwDGAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwDGEquipId,hwDGEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DG Alarm Resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, Spare digital equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 122 }
|
||
|
||
hwSSUSummaryAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwSSUGroupId,hwSSUGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"SSU Group Alarm. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, Spare digital equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 123 }
|
||
|
||
hwSSUSummaryAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwSSUGroupId,hwSSUGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"SSU Group Resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, Spare digital equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 124 }
|
||
|
||
hwSSUAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwSSUEquipId,hwSSUEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"SSU Alarm. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, Spare digital equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 125 }
|
||
|
||
hwSSUAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwSSUEquipId,hwSSUEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"SSU Alarm Resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, Spare digital equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 126 }
|
||
|
||
hwTemp1SensorAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwTemp1EquipId,hwTemp1EquipName,hwTemp1OperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 127 }
|
||
|
||
hwTemp1SensorAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwTemp1EquipId,hwTemp1EquipName,hwTemp1OperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 128 }
|
||
|
||
hwTemp2SensorAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwTemp2EquipId,hwTemp2EquipName,hwTemp2OperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 129 }
|
||
|
||
hwTemp2SensorAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwTemp2EquipId,hwTemp2EquipName,hwTemp2OperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwSiteAlarmTrapsPrefix 130 }
|
||
|
||
hwEsduDigitalInputAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEsduEquipId,hwEsduEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The ESDU Spare digital fault. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, Spare digital equipment ID and equipment name are also include in VB(variable bondings). "
|
||
::= { hwSiteAlarmTrapsPrefix 147 }
|
||
|
||
hwEsduDigitalInputAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEsduEquipId,hwEsduEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The ESDU Spare digital alarm resume.Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, Spare digital equipment ID and equipment name are also include in VB(variable bondings). "
|
||
::= { hwSiteAlarmTrapsPrefix 148 }
|
||
|
||
hwEsduDoorOpenAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEsduEquipId,hwEsduEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The ESDU door is open."
|
||
::= { hwSiteAlarmTrapsPrefix 149 }
|
||
|
||
hwEsduDoorOpenAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEsduEquipId,hwEsduEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The ESDU door open alarm resumed."
|
||
::= { hwSiteAlarmTrapsPrefix 150 }
|
||
|
||
hwEsduTemp1SensorFaultAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEsduEquipId,hwEsduEquipName,hwEsduTemp1OperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The ESDU TEMP1 sensor is faulty."
|
||
::= { hwSiteAlarmTrapsPrefix 151 }
|
||
|
||
hwEsduTemp1SensorFaultAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEsduEquipId,hwEsduEquipName,hwEsduTemp1OperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The ESDU TEMP1 sensor fault alarm recovers."
|
||
::= { hwSiteAlarmTrapsPrefix 152 }
|
||
|
||
hwEsduTemp1SensorMissAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEsduEquipId,hwEsduEquipName,hwEsduTemp1OperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The ESDU TEMP1 sensor is missing."
|
||
::= { hwSiteAlarmTrapsPrefix 153 }
|
||
|
||
hwEsduTemp1SensorMissAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEsduEquipId,hwEsduEquipName,hwEsduTemp1OperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The ESDU TEMP1 sensor missing alarm recovers."
|
||
::= { hwSiteAlarmTrapsPrefix 154 }
|
||
|
||
hwEsduTemp2SensorFaultAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEsduEquipId,hwEsduEquipName,hwEsduTemp1OperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The ESDU TEMP2 sensor is faulty."
|
||
::= { hwSiteAlarmTrapsPrefix 155 }
|
||
|
||
hwEsduTemp2SensorFaultAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEsduEquipId,hwEsduEquipName,hwEsduTemp2OperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The ESDU TEMP2 sensor fault alarm recovers."
|
||
::= { hwSiteAlarmTrapsPrefix 156 }
|
||
|
||
hwEsduTemp2SensorMissAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEsduEquipId,hwEsduEquipName,hwEsduTemp2OperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The ESDU TEMP2 sensor is missing."
|
||
::= { hwSiteAlarmTrapsPrefix 157 }
|
||
|
||
hwEsduTemp2SensorMissAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEsduEquipId,hwEsduEquipName,hwEsduTemp2OperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The ESDU TEMP2 sensor missing alarm recovers."
|
||
::= { hwSiteAlarmTrapsPrefix 158 }
|
||
|
||
hwEsduBtempSensorFaultAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEsduEquipId,hwEsduEquipName,hwEsduBtempOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The ESDU BTEMP sensor is faulty."
|
||
::= { hwSiteAlarmTrapsPrefix 159 }
|
||
|
||
hwEsduBtempSensorFaultAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEsduEquipId,hwEsduEquipName,hwEsduBtempOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The ESDU BTEMP sensor fault alarm recovers."
|
||
::= { hwSiteAlarmTrapsPrefix 160 }
|
||
|
||
hwEsduBtempSensorMissAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEsduEquipId,hwEsduEquipName,hwEsduBtempOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The ESDU BTEMP sensor is missing."
|
||
::= { hwSiteAlarmTrapsPrefix 161 }
|
||
|
||
hwEsduBtempSensorMissAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEsduEquipId,hwEsduEquipName,hwEsduBtempOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The ESDU BTEMP sensor missing alarm recovers."
|
||
::= { hwSiteAlarmTrapsPrefix 162 }
|
||
|
||
hwEsduTemp1AlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEsduEquipId,hwEsduEquipName,hwEsduTemp1OperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The ESDU TEMP1 temperature is out of range<67><65>too high or too low<6F><77>. "
|
||
::= { hwSiteAlarmTrapsPrefix 163 }
|
||
|
||
hwEsduTemp1AlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEsduEquipId,hwEsduEquipName,hwEsduTemp1OperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The ESDU TEMP1 temperature alarm resume. "
|
||
::= { hwSiteAlarmTrapsPrefix 164 }
|
||
|
||
hwEsduTemp2AlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEsduEquipId,hwEsduEquipName,hwEsduTemp2OperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The ESDU TEMP2 temperature is out of range<67><65>too high or too low<6F><77>. "
|
||
::= { hwSiteAlarmTrapsPrefix 165 }
|
||
|
||
hwEsduTemp2AlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEsduEquipId,hwEsduEquipName,hwEsduTemp2OperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The ESDU TEMP2 temperature alarm resume. "
|
||
::= { hwSiteAlarmTrapsPrefix 166 }
|
||
|
||
hwEsduCommAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEsduEquipId,hwEsduEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The Moniter cannot commuicate with the ESDU."
|
||
::= { hwSiteAlarmTrapsPrefix 167 }
|
||
|
||
hwEsduCommAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEsduEquipId,hwEsduEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The communication between monitor and ESDU recovers."
|
||
::= { hwSiteAlarmTrapsPrefix 168 }
|
||
|
||
hwBatteryLowCapacityAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattsGroupId,hwBattsGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The capacity of batteries is low."
|
||
::= { hwSiteAlarmTrapsPrefix 169 }
|
||
|
||
hwBatteryLowCapacityAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattsGroupId,hwBattsGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The alarm of low capacity resumed."
|
||
::= { hwSiteAlarmTrapsPrefix 170 }
|
||
|
||
hwBatteryLostAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattStringEquipId,hwBattStringEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Some battery strings could be lost, when the alarm happened."
|
||
::= { hwSiteAlarmTrapsPrefix 171 }
|
||
|
||
hwBatteryLostAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattStringEquipId,hwBattStringEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"If all the battery strings can be detected, the alarm of battery losting resume."
|
||
::= { hwSiteAlarmTrapsPrefix 172 }
|
||
|
||
hwRectCapacityAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwRectsGroupId,hwRectsGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Low Rectifier Capacity or High Rectifier Capacity Alarm happened."
|
||
::= { hwSiteAlarmTrapsPrefix 131 }
|
||
|
||
hwRectCapacityAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwRectsGroupId,hwRectsGroupName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Low Rectifier Capacity or High Rectifier Capacity Alarm Resumed."
|
||
::= { hwSiteAlarmTrapsPrefix 132 }
|
||
|
||
hwPvLostAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription }
|
||
STATUS current
|
||
DESCRIPTION
|
||
""
|
||
::= { hwSiteAlarmTrapsPrefix 181 }
|
||
|
||
hwPvLostAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription }
|
||
STATUS current
|
||
DESCRIPTION
|
||
""
|
||
::= { hwSiteAlarmTrapsPrefix 182 }
|
||
|
||
hwTcucTempSensorFaultAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The TCUC cabient temperature sensor fault alarm happened."
|
||
::= { hwSiteAlarmTrapsPrefix 133 }
|
||
|
||
hwTcucTempSensorFaultAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The TCUC cabient temperature sensor fault alarm resumed."
|
||
::= { hwSiteAlarmTrapsPrefix 134 }
|
||
|
||
hwTcucFanFaultAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The TCUC cabient fan fault alarm happened."
|
||
::= { hwSiteAlarmTrapsPrefix 135 }
|
||
|
||
hwTcucFanFaultAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The TCUC cabient fan fault alarm resumed."
|
||
::= { hwSiteAlarmTrapsPrefix 136 }
|
||
|
||
hwTcucTempAbnormalAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The TCUC cabinet temperature is too high or too low"
|
||
::= { hwSiteAlarmTrapsPrefix 137 }
|
||
|
||
hwTcucTempAbnormalAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The TCUC cabinet temperature abnormal alarm resumed."
|
||
::= { hwSiteAlarmTrapsPrefix 138 }
|
||
|
||
hwTcucDoorOpenAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The TCUC cabinet door is open."
|
||
::= { hwSiteAlarmTrapsPrefix 139 }
|
||
|
||
hwTcucDoorOpenAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The TCUC cabient door open alarm resumed."
|
||
::= { hwSiteAlarmTrapsPrefix 140 }
|
||
|
||
hwTcucSmokeAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The TCUC cabient smoke alarm happened."
|
||
::= { hwSiteAlarmTrapsPrefix 141 }
|
||
|
||
hwTcucSmokeAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The TCUC cabient smoke alarm resumed"
|
||
::= { hwSiteAlarmTrapsPrefix 142 }
|
||
|
||
hwTcucWaterAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The TCUC cabient water alarm happend."
|
||
::= { hwSiteAlarmTrapsPrefix 143 }
|
||
|
||
hwTcucWaterAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The TCUC cabient water alarm resumed."
|
||
::= { hwSiteAlarmTrapsPrefix 144 }
|
||
|
||
hwTcucCommFailAlarmTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The TCUC cabient failed communicate with the monitor."
|
||
::= { hwSiteAlarmTrapsPrefix 145 }
|
||
|
||
hwTcucCommFailAlarmResumeTraps NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The TCUC cabient communication fail alarm resumed."
|
||
::= { hwSiteAlarmTrapsPrefix 146 }
|
||
|
||
hwAtsAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwAtsEquipId,hwAtsEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ATS Alarm. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, Spare digital equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 187 }
|
||
|
||
hwAtsAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwAtsEquipId,hwAtsEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ATS Alarm Resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, Spare digital equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwSiteAlarmTrapsPrefix 188 }
|
||
|
||
hwInverterTrapTable OBJECT IDENTIFIER ::= { hwSiteAlarmTraps 4 }
|
||
|
||
hwInverterTrapPrefix OBJECT IDENTIFIER ::= { hwInverterTrapTable 0 }
|
||
|
||
hwInverterCommFailAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Communication Failure.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 1 }
|
||
|
||
hwInverterCommFailAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Communication Failure Resume.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 2 }
|
||
|
||
hwInverterFanFaultAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Fan Failure.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 3 }
|
||
|
||
hwInverterFanFaultAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Fan Failure Resume.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 4 }
|
||
|
||
hwInverterACOutLowAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC Output Undervoltage.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 5 }
|
||
|
||
hwInverterACOutLowAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC Output Undervoltage Resume.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 6 }
|
||
|
||
hwInverterACOutHighAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC Output Overvoltage.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 7 }
|
||
|
||
hwInverterACOutHighAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC Output Overvoltage Resume.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 8 }
|
||
|
||
hwInverterModFaultAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Module Fault.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 9 }
|
||
|
||
hwInverterModFaultAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Module Fault Resume.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 10 }
|
||
|
||
hwInverterModTempHighAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temperature Too High.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 11 }
|
||
|
||
hwInverterModTempHighAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temperature Too High Resume.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 12 }
|
||
|
||
hwInverterModTempLowAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temperature Too Low.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 13 }
|
||
|
||
hwInverterModTempLowAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temperature Too Low Resume.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 14 }
|
||
|
||
hwInvertersACPhaseShortAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC Input Phase Not Ready.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 15 }
|
||
|
||
hwInvertersACPhaseShortAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC Input Phase Not Ready Resume.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 16 }
|
||
|
||
hwInverterModOffAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Module Off.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 17 }
|
||
|
||
hwInverterModOffAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Module Off Resume.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 18 }
|
||
|
||
hwInverterACInAbnAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC Input Abnormal.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 19 }
|
||
|
||
hwInverterACInAbnAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC Input Abnormal Resume.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 20 }
|
||
|
||
hwInverterDCInLowAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DC Input Undervoltage.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 21 }
|
||
|
||
hwInverteDCInLowAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DC Input Undervoltage Resume.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 22 }
|
||
|
||
hwInverterDCInHighAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DC Input Overvoltage.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 23 }
|
||
|
||
hwInverterDCInHighAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DC Input Overvoltage Resume.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 24 }
|
||
|
||
hwInverterModCommFailAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Module Communication Failure.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 25 }
|
||
|
||
hwInverterModCommFailAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Module Communication Failure Resume.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 26 }
|
||
|
||
hwInverterNoACInAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"No AC In.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 27 }
|
||
|
||
hwInverterNoACInAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"No AC In Resume.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 28 }
|
||
|
||
hwInverterNoDCInAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"No DC In.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 29 }
|
||
|
||
hwInverterNoDCInAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"No DC In Resume.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 30 }
|
||
|
||
hwInverterT2SFaultAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"T2S Fault.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 31 }
|
||
|
||
hwInverterT2SFaultAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"T2S Fault Resume.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 32 }
|
||
|
||
hwInvertModMissAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Missing Module.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 33 }
|
||
|
||
hwInvertModMissAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Missing Module Resume.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwInverterTrapPrefix 34 }
|
||
|
||
hwIboxAlmTrapTable OBJECT IDENTIFIER ::= { hwSiteAlarmTraps 6 }
|
||
|
||
hwIboxAlmTrapPrefix OBJECT IDENTIFIER ::= { hwIboxAlmTrapTable 0 }
|
||
|
||
hwIboxCommFailAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwIboxEquipId,hwIboxEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ibox Communication Failure.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwIboxAlmTrapPrefix 1 }
|
||
|
||
hwIboxCommFailAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwIboxEquipId,hwIboxEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ibox Communication Failure Resume.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwIboxAlmTrapPrefix 2 }
|
||
|
||
hwIbatAlmTrapTable OBJECT IDENTIFIER ::= { hwSiteAlarmTraps 7 }
|
||
|
||
hwIbatAlmTrapPrefix OBJECT IDENTIFIER ::= { hwIbatAlmTrapTable 0 }
|
||
|
||
hwIbatAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwIbatEquipId,hwIbatEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ibat Communication Failure.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwIbatAlmTrapPrefix 1 }
|
||
|
||
hwIbatAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwIbatEquipId,hwIbatEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ibat Communication Failure Resume.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwIbatAlmTrapPrefix 2 }
|
||
|
||
hwAcAmmeterAlmTrapTable OBJECT IDENTIFIER ::= { hwSiteAlarmTraps 8 }
|
||
|
||
hwAcAmmeterAlmTrapPrefix OBJECT IDENTIFIER ::= { hwAcAmmeterAlmTrapTable 0 }
|
||
|
||
hwAcAmmeterAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwAcAmmeterEquipId,hwAcAmmeterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwAcAmmeterAlmTrapPrefix 1 }
|
||
|
||
hwAcAmmeterAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwAcAmmeterEquipId,hwAcAmmeterEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Ac Ammeter .
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwAcAmmeterAlmTrapPrefix 2 }
|
||
|
||
hwCommExBoardAlmTrapTable OBJECT IDENTIFIER ::= { hwSiteAlarmTraps 9 }
|
||
|
||
hwCommExBoardAlmTrapPrefix OBJECT IDENTIFIER ::= { hwCommExBoardAlmTrapTable 0 }
|
||
|
||
hwCommExBoardCommFailAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwCommExBoardEquipId,hwCommExBoardEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Communication Expansion Board Communication Failure
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwCommExBoardAlmTrapPrefix 1 }
|
||
|
||
hwCommExBoardCommFailAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwCommExBoardEquipId,hwCommExBoardEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Communication Expansion Board Communication Failure Resume.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwCommExBoardAlmTrapPrefix 2 }
|
||
|
||
hwDGCommExBoardAlmTrapTable OBJECT IDENTIFIER ::= { hwSiteAlarmTraps 10 }
|
||
|
||
hwDGCommExBoardAlmTrapPrefix OBJECT IDENTIFIER ::= { hwDGCommExBoardAlmTrapTable 0 }
|
||
|
||
hwDGCommExBoardCommFailAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwDGCommExBoardEquipId,hwDGCommExBoardEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DG Comm Ex Board Communication Failure.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwDGCommExBoardAlmTrapPrefix 1 }
|
||
|
||
hwDGCommExBoardCommFailAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwDGCommExBoardEquipId,hwDGCommExBoardEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DG Comm Ex Board Communication Failure Resume.
|
||
Its correlation binding parameters:
|
||
Site alarm serial number (SN),
|
||
Alarm name,
|
||
Alarm level,
|
||
Site name,
|
||
Site administrant address,
|
||
NE ID,
|
||
Site description,
|
||
Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings)."
|
||
::= { hwDGCommExBoardAlmTrapPrefix 2 }
|
||
|
||
hwAcbGroupAlmTrapTable OBJECT IDENTIFIER ::= { hwSiteAlarmTraps 2 }
|
||
|
||
hwAcbGroupAlmTrapTablePrefix OBJECT IDENTIFIER ::= { hwAcbGroupAlmTrapTable 0 }
|
||
|
||
hwAcbGroupAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwAcbGroupEquipId,hwAcbGroupEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwAcbGroupAlmTrapTablePrefix 99 }
|
||
|
||
hwAcbGroupAarlmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwAcbGroupEquipId,hwAcbGroupEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwAcbGroupAlmTrapTablePrefix 100 }
|
||
|
||
hwAcbAlmTrapTable OBJECT IDENTIFIER ::= { hwSiteAlarmTraps 3 }
|
||
|
||
hwAcbAlmTrapTablePrefix OBJECT IDENTIFIER ::= { hwAcbAlmTrapTable 0 }
|
||
|
||
hwAcbAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwAcbEquipId,hwAcbEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwAcbAlmTrapTablePrefix 99 }
|
||
|
||
hwAcbAarlmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwAcbEquipId,hwAcbEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwAcbAlmTrapTablePrefix 100 }
|
||
|
||
hwElockAlmTrapTable OBJECT IDENTIFIER ::= { hwSiteAlarmTraps 13 }
|
||
|
||
hwElockAlmTrapTablePrefix OBJECT IDENTIFIER ::= { hwElockAlmTrapTable 0 }
|
||
|
||
hwElockAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwElockEquipId,hwElockEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwElockAlmTrapTablePrefix 1 }
|
||
|
||
hwElockAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwElockEquipId,hwElockEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwElockAlmTrapTablePrefix 2 }
|
||
|
||
hwTemHumAlmTrapTable OBJECT IDENTIFIER ::= { hwSiteAlarmTraps 14 }
|
||
|
||
hwTemHumAlmTrapTablePrefix OBJECT IDENTIFIER ::= { hwTemHumAlmTrapTable 0 }
|
||
|
||
hwTemHumAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwTemHumEquipId,hwTemHumEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwTemHumAlmTrapTablePrefix 1 }
|
||
|
||
hwTemHumAlarmResumeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwTemHumEquipId,hwTemHumEquipName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwTemHumAlmTrapTablePrefix 2 }
|
||
|
||
hwSiteDevicesTraps OBJECT IDENTIFIER ::= { hwSiteMonitorMIBTraps 2 }
|
||
|
||
hwDevicesTrapsPrefix OBJECT IDENTIFIER ::= { hwSiteDevicesTraps 0 }
|
||
|
||
hwRectifiersInslotChange NOTIFICATION-TYPE
|
||
OBJECTS { hwDeviceTrapOrdinalNumber,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwRectEquipId,hwRectEquipName,hwRectOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"When the presence status of a rectifier changes, the node reports an event. Then the NMS adds or deletes the corresponding entry to or from hwRectConfigTable or hwRectOperTable. The bound information includes the site address, site name, site description, and NE identifier. In addition, the ID, name, and status of the rectifier are bound to identify the specific rectifier and its operation type. When an entry is added, the device status is reported as normal (1); when an entry is deleted, the device status is reported as commFail (4).
|
||
This trap is the unique trigger condition that causes the NMS to add or delete entries to or from hwRectConfigTable or hwRectOperTable.
|
||
"
|
||
::= { hwDevicesTrapsPrefix 1 }
|
||
|
||
hwBatterysInslotChange NOTIFICATION-TYPE
|
||
OBJECTS { hwDeviceTrapOrdinalNumber,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattStringEquipId,hwBattStringEquipName,hwBattStringOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"When the presence status of a battery string changes, the node reports an event. Then the NMS adds or deletes the corresponding entry to or from hwBatttConfigTable or hwBatttOperTable. The bound information includes the site address, site name, site description, and NE identifier.
|
||
In addition, the ID, name, and status of the battery string are bound to identify the specific battery string and its operation type.
|
||
When an entry is added, the device status is reported as normal (1);
|
||
when an entry is deleted, the device status is reported as loopBreak (4).
|
||
This trap is the unique trigger condition that causes the NMS to add or delete entries to or from hwBatttConfigTable or hwBatttOperTable."
|
||
::= { hwDevicesTrapsPrefix 2 }
|
||
|
||
hwBattTestRecordsAdd NOTIFICATION-TYPE
|
||
OBJECTS { hwDeviceTrapOrdinalNumber,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"After a new discharge test is conducted on a battery group, the node reports an event. The bound information includes the site address, site name, site description, and NE identifier. The NMS needs to add the corresponding entry to the battery test table. The test records are sorted by time in descending order. The battery test table holds a maximum of 10 test records. If the number of test records exceeds 10, the earlier records starting from the last but one record are deleted at a time because the last record is saved permanently.
|
||
This trap is the unique trigger condition that causes the NMS to add entries from hwBattsTestResultTable.
|
||
The battery test table allows you only to add entries."
|
||
::= { hwDevicesTrapsPrefix 3 }
|
||
|
||
hwEnvTempSensInslotChange NOTIFICATION-TYPE
|
||
OBJECTS { hwDeviceTrapOrdinalNumber,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEnvTempEquipId,hwEnvTempEquipName,hwEnvTempSensorOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"When the presence status of an environment temperature sensor changes, the node reports an event. Then the NMS adds or deletes the corresponding entry to or from hwEvnTempSensorTable. The bound information includes the site address, site name, site description, and NE identifier. In addition, the ID, name, and status of the environment temperature sensor are bound to identify the specific environment temperature sensor and its operation type. When an entry is added, the device status is reported as normal (1); when an entry is deleted, the device status is reported as notInslot (4).
|
||
This trap is the unique trigger condition that causes the NMS to add or delete entries to or from hwEnvTempSensorTable."
|
||
::= { hwDevicesTrapsPrefix 4 }
|
||
|
||
hwEnvHumiSensInslotChange NOTIFICATION-TYPE
|
||
OBJECTS { hwDeviceTrapOrdinalNumber,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwEnvHumiEquipId,hwEnvHumiEquipName,hwEnvHumiSensorOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"When the presence status of an environment humidity sensor changes, the trap reports an event. Then the NMS adds or deletes the corresponding entry to or from hwEvnHumiSensorTable. The bound information includes the site address, site name, site description, and NE identifier. In addition, the ID, name, and status of the environment humidity sensor are bound to identify the specific environment humidity sensor and its operation type. When an entry is added, the device status is reported as normal (1); when an entry is deleted, the device status is reported as notInslot (4).
|
||
This trap is the unique trigger condition that causes the NMS to add or delete entries to or from hwEnvHumiSensorTable."
|
||
::= { hwDevicesTrapsPrefix 5 }
|
||
|
||
hwPDEsInslotChange NOTIFICATION-TYPE
|
||
OBJECTS { hwDeviceTrapOrdinalNumber,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwDevicesTrapsPrefix 6 }
|
||
|
||
hwInvertersInslotChange NOTIFICATION-TYPE
|
||
OBJECTS { hwDeviceTrapOrdinalNumber,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwInverterEquipId,hwInverterEquipName,hwInverterOperStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Description."
|
||
::= { hwDevicesTrapsPrefix 7 }
|
||
|
||
hwSiteStatusTrap OBJECT IDENTIFIER ::= { hwSiteMonitorMIBTraps 3 }
|
||
|
||
hwSiteStatusTrapPrefix OBJECT IDENTIFIER ::= { hwSiteStatusTrap 0 }
|
||
|
||
hwAcInputFaultTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwAcEquipId,hwAcEquipName,hwAcInputOperStatus,hwAcInputStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
""
|
||
::= { hwSiteStatusTrapPrefix 1 }
|
||
|
||
hwRectifierFaultTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwRectifierStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
""
|
||
::= { hwSiteStatusTrapPrefix 2 }
|
||
|
||
hwBatteryDischargeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattsGroupId,hwBattsGroupName,hwBatteryDischarge }
|
||
STATUS current
|
||
DESCRIPTION
|
||
""
|
||
::= { hwSiteStatusTrapPrefix 3 }
|
||
|
||
hwBatteryLowVoltageTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBatteryLowVoltage }
|
||
STATUS current
|
||
DESCRIPTION
|
||
""
|
||
::= { hwSiteStatusTrapPrefix 4 }
|
||
|
||
hwBatteryUltraLowVoltageTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBatteryUltraLowVoltage }
|
||
STATUS current
|
||
DESCRIPTION
|
||
""
|
||
::= { hwSiteStatusTrapPrefix 5 }
|
||
|
||
hwBatteryDisconnectTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBatteryDisconnect }
|
||
STATUS current
|
||
DESCRIPTION
|
||
""
|
||
::= { hwSiteStatusTrapPrefix 6 }
|
||
|
||
hwFuseBrokenTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwFuseBroken }
|
||
STATUS current
|
||
DESCRIPTION
|
||
""
|
||
::= { hwSiteStatusTrapPrefix 7 }
|
||
|
||
hwLowRecitiferCapacityTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwRectsGroupId,hwRectsGroupName,hwLowRecitiferCapacity }
|
||
STATUS current
|
||
DESCRIPTION
|
||
""
|
||
::= { hwSiteStatusTrapPrefix 8 }
|
||
|
||
hwBatteryTestNegativeTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwBattsGroupId,hwBattsGroupName,hwBatteryTestNegative }
|
||
STATUS current
|
||
DESCRIPTION
|
||
""
|
||
::= { hwSiteStatusTrapPrefix 9 }
|
||
|
||
hwUrgentAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwUrgentAlarmStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
""
|
||
::= { hwSiteStatusTrapPrefix 10 }
|
||
|
||
hwNonurgentAlarmTrap NOTIFICATION-TYPE
|
||
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,hwNetIdentifier,hwSiteDescription,hwNonurgentAlarmStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
""
|
||
::= { hwSiteStatusTrapPrefix 11 }
|
||
|
||
hwSiteEquip OBJECT IDENTIFIER ::= { hwSiteMonitorMIB 3 }
|
||
|
||
hwSiteCameraTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwSiteCameraEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
::= { hwSiteEquip 1 }
|
||
|
||
hwSiteCameraEntry OBJECT-TYPE
|
||
SYNTAX HwSiteCameraEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"/"
|
||
INDEX { hwSiteCameraIp }
|
||
::= { hwSiteCameraTable 1 }
|
||
|
||
HwSiteCameraEntry ::= SEQUENCE {
|
||
hwSiteCameraIp
|
||
OCTET STRING,
|
||
hwSiteCameraPort
|
||
INTEGER,
|
||
hwSiteCameraPhotSetAlarmType
|
||
INTEGER,
|
||
hwSiteCameraAssociatedAlarmPicture1
|
||
OCTET STRING,
|
||
hwSiteCameraAssociatedAlarmPicture2
|
||
OCTET STRING,
|
||
hwSiteCameraAssociatedAlarmPicture3
|
||
OCTET STRING,
|
||
hwSiteCameraAssociatedAlarmPicture4
|
||
OCTET STRING,
|
||
hwSiteCameraAssociatedAlarmPicture5
|
||
OCTET STRING,
|
||
hwSiteCameraAssociatedAlarmPicture6
|
||
OCTET STRING,
|
||
hwSiteCameraAssociatedAlarmPicture7
|
||
OCTET STRING,
|
||
hwSiteCameraAssociatedAlarmPicture8
|
||
OCTET STRING,
|
||
hwSiteCameraAssociatedAlarmPicture9
|
||
OCTET STRING,
|
||
hwSiteCameraAssociatedAlarmPicture10
|
||
OCTET STRING,
|
||
hwSiteCameraAdditionalAssociatedAlarmPictures
|
||
OCTET STRING
|
||
}
|
||
|
||
hwSiteCameraIp OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"the camera ip adress."
|
||
::= { hwSiteCameraEntry 1 }
|
||
|
||
hwSiteCameraPort OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
nim1com1(1),
|
||
nim1com2(2),
|
||
nim2com1(3),
|
||
nim2com2(4)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"camera connect port number."
|
||
::= { hwSiteCameraEntry 2 }
|
||
|
||
hwSiteCameraPhotSetAlarmType OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
dooralarm(1),
|
||
smokealarm(2),
|
||
wateralarm(3),
|
||
motiondetectalarm(4)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"You can set the alarm type to obtain the historical picture of the camera-related alarm shooting."
|
||
::= { hwSiteCameraEntry 5 }
|
||
|
||
hwSiteCameraAssociatedAlarmPicture1 OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Associated alarm picture 1."
|
||
::= { hwSiteCameraEntry 6 }
|
||
|
||
hwSiteCameraAssociatedAlarmPicture2 OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Associated alarm picture 2."
|
||
::= { hwSiteCameraEntry 7 }
|
||
|
||
hwSiteCameraAssociatedAlarmPicture3 OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Associated alarm picture 3."
|
||
::= { hwSiteCameraEntry 8 }
|
||
|
||
hwSiteCameraAssociatedAlarmPicture4 OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Associated alarm picture 4."
|
||
::= { hwSiteCameraEntry 9 }
|
||
|
||
hwSiteCameraAssociatedAlarmPicture5 OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Associated alarm picture 5."
|
||
::= { hwSiteCameraEntry 10 }
|
||
|
||
hwSiteCameraAssociatedAlarmPicture6 OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Associated alarm picture 6."
|
||
::= { hwSiteCameraEntry 11 }
|
||
|
||
hwSiteCameraAssociatedAlarmPicture7 OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Associated alarm picture 7."
|
||
::= { hwSiteCameraEntry 12 }
|
||
|
||
hwSiteCameraAssociatedAlarmPicture8 OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Associated alarm picture 8."
|
||
::= { hwSiteCameraEntry 13 }
|
||
|
||
hwSiteCameraAssociatedAlarmPicture9 OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Associated alarm picture 9."
|
||
::= { hwSiteCameraEntry 14 }
|
||
|
||
hwSiteCameraAssociatedAlarmPicture10 OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Associated alarm picture 10."
|
||
::= { hwSiteCameraEntry 15 }
|
||
|
||
hwSiteCameraAdditionalAssociatedAlarmPictures OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Additional associated alarm pictures."
|
||
::= { hwSiteCameraEntry 16 }
|
||
|
||
END
|