Observium_CE/mibs/gude/GUDEADS-PDU818X-MIB

446 lines
9.2 KiB
Plaintext

GUDEADS-PDU818X-MIB DEFINITIONS ::= BEGIN
IMPORTS
enterprises,
MODULE-IDENTITY,
OBJECT-TYPE,
NOTIFICATION-TYPE,
Integer32,
Unsigned32
FROM SNMPv2-SMI
OBJECT-GROUP,
NOTIFICATION-GROUP
FROM SNMPv2-CONF;
gudeads MODULE-IDENTITY
LAST-UPDATED "200703051356Z" -- Mar 5, 2007 1:56:00 PM
ORGANIZATION "Gude Analog- und Digitalsysteme GmbH"
CONTACT-INFO
"http://www.gudeads.com/"
DESCRIPTION
""
REVISION "200703051356Z" -- Mar 5, 2007 1:56:00 PM
DESCRIPTION
"$Id:$"
-- 1.3.6.1.4.1.28507
::= { enterprises 28507 }
-- Notification Types
--
events OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.35.0
::= { gadsPDU818X 0 }
pdu818XPowerIndex OBJECT-TYPE
SYNTAX Integer32 (1..4)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Index of Power Channel entries"
-- 1.3.6.1.4.1.28507.35.1.5.1.2.1.1
::= { pdu818XPowerEntry 1 }
pdu818XTrapIPTable OBJECT-TYPE
SYNTAX SEQUENCE OF Epc8TrapIPEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"list of all Trap receiver"
-- 1.3.6.1.4.1.28507.35.1.1.1.2
::= { pdu818XSNMPaccess 2 }
pdu818XCurrent OBJECT-TYPE
SYNTAX Unsigned32
UNITS
"mA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual Curent on Power Channel."
-- 1.3.6.1.4.1.28507.35.1.5.1.2.1.5
::= { pdu818XPowerEntry 5 }
gadsPDU818X OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.35
::= { gudeads 35 }
pdu818XVoltage OBJECT-TYPE
SYNTAX Unsigned32
UNITS
"V"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual Voltage on Power Channel"
-- 1.3.6.1.4.1.28507.35.1.5.1.2.1.6
::= { pdu818XPowerEntry 6 }
pdu818XTrapIPEntry OBJECT-TYPE
SYNTAX Epc8TrapIPEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"an entry containing management
informations regarding the list of trap
receivers"
INDEX {
pdu818XTrapIPIndex }
-- 1.3.6.1.4.1.28507.35.1.1.1.2.1
::= { pdu818XTrapIPTable 1 }
Epc8TrapIPEntry ::= SEQUENCE {
pdu818XTrapIPIndex Integer32,
pdu818XTrapAddr OCTET STRING }
pdu818XPowerTable OBJECT-TYPE
SYNTAX SEQUENCE OF Pdu818XPowerEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"All available Channel Interfaces."
-- 1.3.6.1.4.1.28507.35.1.5.1.2
::= { pdu818XPowerChan 2 }
pdu818XPowerEntry OBJECT-TYPE
SYNTAX Pdu818XPowerEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing management information
applicable to a particular Power Channel."
INDEX {
pdu818XPowerIndex }
-- 1.3.6.1.4.1.28507.35.1.5.1.2.1
::= { pdu818XPowerTable 1 }
Pdu818XPowerEntry ::= SEQUENCE {
pdu818XPowerIndex Integer32,
pdu818XChanStatus Integer32,
pdu818XEnergyActive Unsigned32,
pdu818XPowerActive Unsigned32,
pdu818XCurrent Unsigned32,
pdu818XVoltage Unsigned32 }
pdu818XTrapIPIndex OBJECT-TYPE
SYNTAX Integer32 (1..8)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A unique value, greater than zero, for each receiver slot."
-- 1.3.6.1.4.1.28507.35.1.1.1.2.1.1
::= { pdu818XTrapIPEntry 1 }
pdu818XDeviceConfig OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.35.1.2
::= { pdu818XObjects 2 }
pdu818XExtActors OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.35.1.4
::= { pdu818XObjects 4 }
pdu818XExtSensors OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.35.1.6
::= { pdu818XObjects 6 }
pdu818XSensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF Pdu818XSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION ""
-- 1.3.6.1.4.1.28507.35.1.6.1
::= { pdu818XExtSensors 1 }
pdu818XSensorEntry OBJECT-TYPE
SYNTAX Pdu818XSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION ""
INDEX {
pdu818XSensorIndex }
-- 1.3.6.1.4.1.28507.35.1.6.1.1
::= { pdu818XSensorTable 1 }
Pdu818XSensorEntry ::= SEQUENCE {
pdu818XSensorIndex Integer32,
pdu818XTempSensor Integer32,
pdu818XHygroSensor Integer32 }
pdu818XPowerDataEvt1 NOTIFICATION-TYPE
OBJECTS {
pdu818XEnergyActive,
pdu818XPowerActive,
pdu818XCurrent,
pdu818XVoltage}
STATUS current
DESCRIPTION
"Event is triggered when a data
for a Power Channel is incoming"
-- 1.3.6.1.4.1.28507.35.0.1
::= { events 1 }
pdu818XPowerDataEvt2 NOTIFICATION-TYPE
OBJECTS {
pdu818XEnergyActive,
pdu818XPowerActive,
pdu818XCurrent,
pdu818XVoltage}
STATUS current
DESCRIPTION
"Event is triggered when a data
for a Power Channel is incoming"
-- 1.3.6.1.4.1.28507.35.0.2
::= { events 2 }
pdu818XPowerDataEvt3 NOTIFICATION-TYPE
OBJECTS {
pdu818XEnergyActive,
pdu818XPowerActive,
pdu818XCurrent,
pdu818XVoltage}
STATUS current
DESCRIPTION
"Event is triggered when a data
for a Power Channel is incoming"
-- 1.3.6.1.4.1.28507.35.0.3
::= { events 3 }
pdu818XPowerDataEvt4 NOTIFICATION-TYPE
OBJECTS {
pdu818XEnergyActive,
pdu818XPowerActive,
pdu818XCurrent,
pdu818XVoltage}
STATUS current
DESCRIPTION
"Event is triggered when a data
for a Power Channel is incoming"
-- 1.3.6.1.4.1.28507.35.0.4
::= { events 4 }
pdu818XSensorIndex OBJECT-TYPE
SYNTAX Integer32 (1)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION ""
-- 1.3.6.1.4.1.28507.35.1.6.1.1.1
::= { pdu818XSensorEntry 1 }
pdu818XTempSensor OBJECT-TYPE
SYNTAX Integer32
UNITS
"10th of degree Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"actual temperature, a value of -9999 indicates
that data is not available"
-- 1.3.6.1.4.1.28507.35.1.6.1.1.2
::= { pdu818XSensorEntry 2 }
pdu818XHygroSensor OBJECT-TYPE
SYNTAX Integer32
UNITS
"10th of percentage humidity"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"actual humidity, a value of -9999 indicates
that data is not available"
-- 1.3.6.1.4.1.28507.35.1.6.1.1.3
::= { pdu818XSensorEntry 3 }
pdu818XSNMPaccess OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.35.1.1.1
::= { pdu818XCommonConfig 1 }
pdu818XTrapCtrl OBJECT-TYPE
SYNTAX Integer32 (0..2)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"0 = off
1 = Ver. 1
2 = Ver. 2c"
-- 1.3.6.1.4.1.28507.35.1.1.1.1
::= { pdu818XSNMPaccess 1 }
-- Scalars and Tables
--
pdu818XObjects OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.35.1
::= { gadsPDU818X 1 }
pdu818XCommonConfig OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.35.1.1
::= { pdu818XObjects 1 }
pdu818XPowerChan OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.35.1.5.1
::= { pdu818XIntSensors 1 }
pdu818XIntActors OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.35.1.3
::= { pdu818XObjects 3 }
pdu818XChanStatus OBJECT-TYPE
SYNTAX Integer32 (0..1)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"0 = data not active, 1 = data valid"
-- 1.3.6.1.4.1.28507.35.1.5.1.2.1.2
::= { pdu818XPowerEntry 2 }
pdu818XActivePowerChan OBJECT-TYPE
SYNTAX Unsigned32 (1..2)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of suppported Power Channels."
-- 1.3.6.1.4.1.28507.35.1.5.1.1
::= { pdu818XPowerChan 1 }
pdu818XEnergyActive OBJECT-TYPE
SYNTAX Unsigned32
UNITS
"Wh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total accumulated Active Energy of Power Channel."
-- 1.3.6.1.4.1.28507.35.1.5.1.2.1.3
::= { pdu818XPowerEntry 3 }
pdu818XTrapAddr OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..99))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"DNS name or IP address specifying one Trap receiver slot.
A port can optionally be specified: 'name:port' An empty
string disables this slot."
-- 1.3.6.1.4.1.28507.35.1.1.1.2.1.2
::= { pdu818XTrapIPEntry 2 }
pdu818XPowerActive OBJECT-TYPE
SYNTAX Unsigned32
UNITS
"W"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Active Power"
-- 1.3.6.1.4.1.28507.35.1.5.1.2.1.4
::= { pdu818XPowerEntry 4 }
pdu818XIntSensors OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.35.1.5
::= { pdu818XObjects 5 }
-- Conformance
--
pdu818XConf OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.35.2
::= { gadsPDU818X 2 }
-- Groups
--
pdu818XGroups OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.35.2.1
::= { pdu818XConf 1 }
-- Compliance
--
pdu818XCompls OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.35.2.2
::= { pdu818XConf 2 }
pdu818XTempEvtSen1 NOTIFICATION-TYPE
OBJECTS {
pdu818XTempSensor}
STATUS current
DESCRIPTION
"temperature limits exceeded"
-- 1.3.6.1.4.1.28507.35.0.6
::= { events 6 }
pdu818XHygroEvtSen1 NOTIFICATION-TYPE
OBJECTS {
pdu818XHygroSensor}
STATUS current
DESCRIPTION
"hygro limits exceeded"
-- 1.3.6.1.4.1.28507.35.0.7
::= { events 7 }
pdu818XBasicGroup OBJECT-GROUP
OBJECTS {
pdu818XTrapCtrl,
pdu818XTrapAddr,
pdu818XTempSensor,
pdu818XHygroSensor,
pdu818XActivePowerChan,
pdu818XChanStatus,
pdu818XEnergyActive,
pdu818XPowerActive,
pdu818XCurrent,
pdu818XVoltage }
STATUS current
DESCRIPTION
"Basic objects."
-- 1.3.6.1.4.1.28507.35.2.1.1
::= { pdu818XGroups 1 }
pdu818XNotificationGroup NOTIFICATION-GROUP
NOTIFICATIONS {
pdu818XTempEvtSen1,
pdu818XHygroEvtSen1,
pdu818XPowerDataEvt1,
pdu818XPowerDataEvt2,
pdu818XPowerDataEvt3,
pdu818XPowerDataEvt4 }
STATUS current
DESCRIPTION
""
-- 1.3.6.1.4.1.28507.35.2.1.2
::= { pdu818XGroups 2 }
END