Observium_CE/mibs/gude/GUDEADS-PDU8110-MIB

313 lines
6.4 KiB
Plaintext

GUDEADS-PDU8110-MIB DEFINITIONS ::= BEGIN
IMPORTS
enterprises,
MODULE-IDENTITY,
OBJECT-TYPE,
NOTIFICATION-TYPE,
Integer32,
Unsigned32
FROM SNMPv2-SMI
OBJECT-GROUP,
NOTIFICATION-GROUP
FROM SNMPv2-CONF;
gudeads MODULE-IDENTITY
LAST-UPDATED "200703051356Z"
ORGANIZATION "Gude Analog- und Digitalsysteme GmbH"
CONTACT-INFO
"http://www.gudeads.com/"
DESCRIPTION
""
REVISION "200703051356Z"
DESCRIPTION
"$Id: GUDEADS-PDU8110-MIB.txt 4232 2011-07-26 09:45:52Z petes1 $"
::= { enterprises 28507 }
pdu8110PowerIndex OBJECT-TYPE
SYNTAX Integer32 (1)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Index of Power Channel entries"
::= { pdu8110PowerEntry 1 }
pdu8110Current OBJECT-TYPE
SYNTAX Unsigned32
UNITS
"mA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual Curent on Power Channel."
::= { pdu8110PowerEntry 5 }
pdu8110PowerTable OBJECT-TYPE
SYNTAX SEQUENCE OF Enc2102PowerEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"All available Channel Interfaces."
::= { pdu8110PowerChan 2 }
pdu8110PowerEntry OBJECT-TYPE
SYNTAX Enc2102PowerEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing management information
applicable to a particular Power Channel."
INDEX {
pdu8110PowerIndex }
::= { pdu8110PowerTable 1 }
Enc2102PowerEntry ::= SEQUENCE {
pdu8110PowerIndex Integer32,
pdu8110ChanStatus Integer32,
pdu8110Current Unsigned32 }
pdu8110PowerChan OBJECT IDENTIFIER ::= { pdu8110IntSensors 1 }
pdu8110ChanStatus OBJECT-TYPE
SYNTAX Integer32 (0..1)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"0 = data not active, 1 = data valid"
::= { pdu8110PowerEntry 2 }
pdu8110ActivePowerChan OBJECT-TYPE
SYNTAX Unsigned32 (1..2)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of suppported Power Channels."
::= { pdu8110PowerChan 1 }
-- Notification Types
--
events OBJECT IDENTIFIER ::= { gadsPDU8110 0 }
pdu8110TrapIPTable OBJECT-TYPE
SYNTAX SEQUENCE OF Epc8TrapIPEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"list of all Trap receiver"
::= { pdu8110SNMPaccess 2 }
gadsPDU8110 OBJECT IDENTIFIER ::= { gudeads 23 }
pdu8110TrapIPEntry OBJECT-TYPE
SYNTAX Epc8TrapIPEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"an entry containing management
informations regarding the list of trap
receivers"
INDEX {
pdu8110TrapIPIndex }
::= { pdu8110TrapIPTable 1 }
Epc8TrapIPEntry ::= SEQUENCE {
pdu8110TrapIPIndex Integer32,
pdu8110TrapAddr OCTET STRING }
pdu8110TrapIPIndex OBJECT-TYPE
SYNTAX Integer32 (1..8)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A unique value, greater than zero, for each receiver slot."
::= { pdu8110TrapIPEntry 1 }
pdu8110DeviceConfig OBJECT IDENTIFIER ::= { pdu8110Objects 2 }
pdu8110ExtActors OBJECT IDENTIFIER ::= { pdu8110Objects 4 }
pdu8110ExtSensors OBJECT IDENTIFIER ::= { pdu8110Objects 6 }
pdu8110SensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF Pdu8110SensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION ""
::= { pdu8110ExtSensors 1 }
pdu8110SensorEntry OBJECT-TYPE
SYNTAX Pdu8110SensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION ""
INDEX {
pdu8110SensorIndex }
::= { pdu8110SensorTable 1 }
Pdu8110SensorEntry ::= SEQUENCE {
pdu8110SensorIndex Integer32,
pdu8110TempSensor Integer32,
pdu8110HygroSensor Integer32 }
pdu8110SensorIndex OBJECT-TYPE
SYNTAX Integer32 (1..2)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION ""
::= { pdu8110SensorEntry 1 }
pdu8110TempSensor OBJECT-TYPE
SYNTAX Integer32
UNITS
"0.1 degree Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"actual temperature, a value of -9999 indicates
that data is not available"
::= { pdu8110SensorEntry 2 }
pdu8110HygroSensor OBJECT-TYPE
SYNTAX Integer32
UNITS
"0.1 percent humidity"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"actual humidity, a value of -9999 indicates
that data is not available"
::= { pdu8110SensorEntry 3 }
pdu8110SNMPaccess OBJECT IDENTIFIER ::= { pdu8110CommonConfig 1 }
pdu8110TrapCtrl OBJECT-TYPE
SYNTAX Integer32 (0..2)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"0 = off
1 = Ver. 1
2 = Ver. 2c"
::= { pdu8110SNMPaccess 1 }
-- Scalars and Tables
--
pdu8110Objects OBJECT IDENTIFIER ::= { gadsPDU8110 1 }
pdu8110CommonConfig OBJECT IDENTIFIER ::= { pdu8110Objects 1 }
pdu8110IntActors OBJECT IDENTIFIER ::= { pdu8110Objects 3 }
pdu8110TrapAddr OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..99))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"DNS name or IP address specifying one Trap receiver slot.
A port can optionally be specified: 'name:port' An empty
string disables this slot."
::= { pdu8110TrapIPEntry 2 }
pdu8110IntSensors OBJECT IDENTIFIER ::= { pdu8110Objects 5 }
-- Conformance
--
pdu8110Conf OBJECT IDENTIFIER ::= { gadsPDU8110 2 }
-- Groups
--
pdu8110Groups OBJECT IDENTIFIER ::= { pdu8110Conf 1 }
-- Compliance
--
pdu8110Compls OBJECT IDENTIFIER ::= { pdu8110Conf 2 }
pdu8110TempEvtSen1 NOTIFICATION-TYPE
OBJECTS {
pdu8110TempSensor}
STATUS current
DESCRIPTION
"temperature limits exceeded"
::= { events 1 }
pdu8110TempEvtSen2 NOTIFICATION-TYPE
OBJECTS {
pdu8110TempSensor}
STATUS current
DESCRIPTION
"temperature limits exceeded"
::= { events 2 }
pdu8110HygroEvtSen1 NOTIFICATION-TYPE
OBJECTS {
pdu8110HygroSensor}
STATUS current
DESCRIPTION
"hygro limits exceeded"
::= { events 3 }
pdu8110HygroEvtSen2 NOTIFICATION-TYPE
OBJECTS {
pdu8110HygroSensor}
STATUS current
DESCRIPTION
"hygro limits exceeded"
::= { events 4 }
pdu8110BasicGroup OBJECT-GROUP
OBJECTS {
pdu8110TrapCtrl,
pdu8110TrapAddr,
pdu8110ActivePowerChan,
pdu8110ChanStatus,
pdu8110Current,
pdu8110TempSensor,
pdu8110HygroSensor }
STATUS current
DESCRIPTION
"Basic objects."
::= { pdu8110Groups 1 }
pdu8110NotificationGroup NOTIFICATION-GROUP
NOTIFICATIONS {
pdu8110TempEvtSen1,
pdu8110TempEvtSen2,
pdu8110HygroEvtSen1,
pdu8110HygroEvtSen2 }
STATUS current
DESCRIPTION ""
::= { pdu8110Groups 2 }