GUDEADS-ENC2191-MIB DEFINITIONS ::= BEGIN
IMPORTS
enterprises,
MODULE-IDENTITY,
OBJECT-TYPE,
NOTIFICATION-TYPE,
Integer32,
Unsigned32
FROM SNMPv2-SMI
OBJECT-GROUP,
NOTIFICATION-GROUP
FROM SNMPv2-CONF;
gudeads MODULE-IDENTITY
LAST-UPDATED "200703051356Z" -- Mar 5, 2007 1:56:00 PM
ORGANIZATION "Gude Analog- und Digitalsysteme GmbH"
CONTACT-INFO
"http://www.gudeads.com/"
DESCRIPTION
""
REVISION "200703051356Z" -- Mar 5, 2007 1:56:00 PM
DESCRIPTION
"$Id:$"
-- 1.3.6.1.4.1.28507
::= { enterprises 28507 }
enc2191POE OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "0 = no POE, 1 = POE available"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"signals POE availability"
-- 1.3.6.1.4.1.28507.61.1.5.10
::= { enc2191IntSensors 10 }
gadsENC2191 OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.61
::= { gudeads 61 }
-- Notification Types
--
events OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.61.3
::= { gadsENC2191 3 }
-- Scalars and Tables
--
enc2191Objects OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.61.1
::= { gadsENC2191 1 }
enc2191CommonConfig OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.61.1.1
::= { enc2191Objects 1 }
enc2191SNMPaccess OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.61.1.1.1
::= { enc2191CommonConfig 1 }
enc2191TrapCtrl OBJECT-TYPE
SYNTAX Integer32 (0..3)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"0 = off
1 = Ver. 1
2 = Ver. 2c
3 = Ver. 3"
-- 1.3.6.1.4.1.28507.61.1.1.1.1
::= { enc2191SNMPaccess 1 }
enc2191TrapIPTable OBJECT-TYPE
SYNTAX SEQUENCE OF Enc2191TrapIPEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"list of all Trap receiver"
-- 1.3.6.1.4.1.28507.61.1.1.1.2
::= { enc2191SNMPaccess 2 }
enc2191TrapIPEntry OBJECT-TYPE
SYNTAX Enc2191TrapIPEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"an entry containing management
informations regarding the list of trap
receivers"
INDEX {
enc2191TrapIPIndex }
-- 1.3.6.1.4.1.28507.61.1.1.1.2.1
::= { enc2191TrapIPTable 1 }
Enc2191TrapIPEntry ::= SEQUENCE {
enc2191TrapIPIndex Integer32,
enc2191TrapAddr OCTET STRING }
enc2191TrapIPIndex OBJECT-TYPE
SYNTAX Integer32 (1..8)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A unique value, greater than zero, for each receiver slot."
-- 1.3.6.1.4.1.28507.61.1.1.1.2.1.1
::= { enc2191TrapIPEntry 1 }
enc2191TrapAddr OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..99))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"DNS name or IP address specifying one Trap receiver slot.
A port can optionally be specified: 'name:port' An empty
string disables this slot."
-- 1.3.6.1.4.1.28507.61.1.1.1.2.1.2
::= { enc2191TrapIPEntry 2 }
enc2191DeviceConfig OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.61.1.2
::= { enc2191Objects 2 }
enc2191IntActors OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.61.1.3
::= { enc2191Objects 3 }
enc2191relayports OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.61.1.3.1
::= { enc2191IntActors 1 }
enc2191portNumber OBJECT-TYPE
SYNTAX Integer32 (1..12)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of Relay Ports"
-- 1.3.6.1.4.1.28507.61.1.3.1.1
::= { enc2191relayports 1 }
-- the Interfaces table
-- The Interfaces table contains information on the entity's
-- interfaces. Each sub-layer below the internetwork-layer
-- of a network interface is considered to be an interface.
enc2191portTable OBJECT-TYPE
SYNTAX SEQUENCE OF Enc2191portEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"list of all EPC Relay Ports"
-- 1.3.6.1.4.1.28507.61.1.3.1.2
::= { enc2191relayports 2 }
enc2191portEntry OBJECT-TYPE
SYNTAX Enc2191portEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing management information applicable to a
particular relay port."
INDEX {
enc2191PortIndex }
-- 1.3.6.1.4.1.28507.61.1.3.1.2.1
::= { enc2191portTable 1 }
Enc2191portEntry ::= SEQUENCE {
enc2191PortIndex Integer32,
enc2191PortName OCTET STRING,
enc2191PortState INTEGER,
enc2191PortSwitchCount Integer32,
enc2191PortStartupMode INTEGER,
enc2191PortStartupDelay Integer32,
enc2191PortRepowerTime Integer32 }
enc2191PortIndex OBJECT-TYPE
SYNTAX Integer32 (1..4)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A unique value, greater than zero, for each Relay Port."
-- 1.3.6.1.4.1.28507.61.1.3.1.2.1.1
::= { enc2191portEntry 1 }
enc2191PortName OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..15))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A textual string containing name of a Relay Port."
-- 1.3.6.1.4.1.28507.61.1.3.1.2.1.2
::= { enc2191portEntry 2 }
enc2191PortState OBJECT-TYPE
SYNTAX INTEGER {
off(0),
on(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"current state of a Relay Port"
-- 1.3.6.1.4.1.28507.61.1.3.1.2.1.3
::= { enc2191portEntry 3 }
enc2191PortSwitchCount OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total number of switch actions ocurred on a Relay Port.
Does not count switch commands which will not switch
the ralay state, so just real relay switches are displayed here."
-- 1.3.6.1.4.1.28507.61.1.3.1.2.1.4
::= { enc2191portEntry 4 }
enc2191PortStartupMode OBJECT-TYPE
SYNTAX INTEGER {
off(0),
on(1),
laststate(2) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"set Mode of startup sequence (off, on , remember last state)"
DEFVAL { off }
-- 1.3.6.1.4.1.28507.61.1.3.1.2.1.5
::= { enc2191portEntry 5 }
enc2191PortStartupDelay OBJECT-TYPE
SYNTAX Integer32
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Delay in sec for startup action"
DEFVAL { 0 }
-- 1.3.6.1.4.1.28507.61.1.3.1.2.1.6
::= { enc2191portEntry 6 }
enc2191PortRepowerTime OBJECT-TYPE
SYNTAX Integer32 (0..65535)
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Delay in sec for repower port after switching off"
DEFVAL { 0 }
-- 1.3.6.1.4.1.28507.61.1.3.1.2.1.7
::= { enc2191portEntry 7 }
enc2191ExtActors OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.61.1.4
::= { enc2191Objects 4 }
enc2191IntSensors OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.61.1.5
::= { enc2191Objects 5 }
enc2191VoltageInfo OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.61.1.5.7
::= { enc2191IntSensors 7 }
enc2191ExtSensors OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.61.1.6
::= { enc2191Objects 6 }
enc2191SensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF Enc2191SensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION ""
-- 1.3.6.1.4.1.28507.61.1.6.1
::= { enc2191ExtSensors 1 }
enc2191SensorEntry OBJECT-TYPE
SYNTAX Enc2191SensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION ""
INDEX {
enc2191SensorIndex }
-- 1.3.6.1.4.1.28507.61.1.6.1.1
::= { enc2191SensorTable 1 }
Enc2191SensorEntry ::= SEQUENCE {
enc2191SensorIndex Integer32,
enc2191TempSensor Integer32,
enc2191HygroSensor Integer32,
enc2191InputSensor INTEGER,
enc2191AirPressure Integer32,
enc2191DewPoint Integer32,
enc2191DewPointDiff Integer32 }
enc2191SensorIndex OBJECT-TYPE
SYNTAX Integer32 (1..4)
MAX-ACCESS read-only
STATUS current
DESCRIPTION ""
-- 1.3.6.1.4.1.28507.61.1.6.1.1.1
::= { enc2191SensorEntry 1 }
enc2191State3V OBJECT-TYPE
SYNTAX INTEGER {
on(1),
error(3) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Show state of internal 3.3V"
-- 1.3.6.1.4.1.28507.61.1.5.7.2
::= { enc2191VoltageInfo 2 }
enc2191TempSensor OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degree Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"actual temperature"
-- 1.3.6.1.4.1.28507.61.1.6.1.1.2
::= { enc2191SensorEntry 2 }
enc2191HygroSensor OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 percent humidity"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"actual humidity"
-- 1.3.6.1.4.1.28507.61.1.6.1.1.3
::= { enc2191SensorEntry 3 }
enc2191InputSensor OBJECT-TYPE
SYNTAX INTEGER {
off(0),
on(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"logical state of input sensor"
-- 1.3.6.1.4.1.28507.61.1.6.1.1.4
::= { enc2191SensorEntry 4 }
-- Conformance
--
enc2191Conf OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.61.2
::= { gadsENC2191 2 }
-- Groups
--
enc2191Groups OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.61.2.1
::= { enc2191Conf 1 }
-- Compliance
--
enc2191Compls OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.61.2.2
::= { enc2191Conf 2 }
enc2191BasicGroup OBJECT-GROUP
OBJECTS {
enc2191TrapCtrl,
enc2191TrapIPIndex,
enc2191TrapAddr,
enc2191portNumber,
enc2191PortIndex,
enc2191PortName,
enc2191PortState,
enc2191PortSwitchCount,
enc2191PortStartupMode,
enc2191PortStartupDelay,
enc2191PortRepowerTime,
enc2191ActiveInputs,
enc2191InputIndex,
enc2191Input,
enc2191State12V,
enc2191State3V,
enc2191POE,
enc2191SensorIndex,
enc2191TempSensor,
enc2191HygroSensor,
enc2191InputSensor,
enc2191AirPressure,
enc2191DewPoint,
enc2191DewPointDiff }
STATUS current
DESCRIPTION
"Basic objects."
-- 1.3.6.1.4.1.28507.61.2.1.1
::= { enc2191Groups 1 }
enc2191NotificationGroup NOTIFICATION-GROUP
NOTIFICATIONS {
enc2191SwitchEvtPort,
enc2191InputEvt,
enc2191TempEvtSen,
enc2191HygroEvtSen,
enc2191InputEvtSen,
enc2191AirPressureEvtSen,
enc2191DewPtDiffEvtSen,
enc2191POEEvt }
STATUS current
DESCRIPTION ""
-- 1.3.6.1.4.1.28507.61.2.1.2
::= { enc2191Groups 2 }
enc2191Inputs OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.61.1.5.6
::= { enc2191IntSensors 6 }
enc2191InputEntry OBJECT-TYPE
SYNTAX Enc2191InputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION ""
INDEX {
enc2191InputIndex }
-- 1.3.6.1.4.1.28507.61.1.5.6.2.1
::= { enc2191InputTable 1 }
Enc2191InputEntry ::= SEQUENCE {
enc2191InputIndex Integer32,
enc2191Input INTEGER }
enc2191Input OBJECT-TYPE
SYNTAX INTEGER {
lo(0),
hi(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Input state of device"
-- 1.3.6.1.4.1.28507.61.1.5.6.2.1.2
::= { enc2191InputEntry 2 }
enc2191ActiveInputs OBJECT-TYPE
SYNTAX Unsigned32 (1..12)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of suppported Input Channels."
-- 1.3.6.1.4.1.28507.61.1.5.6.1
::= { enc2191Inputs 1 }
enc2191InputTable OBJECT-TYPE
SYNTAX SEQUENCE OF Enc2191InputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION ""
-- 1.3.6.1.4.1.28507.61.1.5.6.2
::= { enc2191Inputs 2 }
enc2191InputIndex OBJECT-TYPE
SYNTAX Integer32 (1..12)
MAX-ACCESS read-only
STATUS current
DESCRIPTION ""
-- 1.3.6.1.4.1.28507.61.1.5.6.2.1.1
::= { enc2191InputEntry 1 }
enc2191State12V OBJECT-TYPE
SYNTAX INTEGER {
off(0),
low(1),
high(2),
error(3) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Show state of internal 12V"
-- 1.3.6.1.4.1.28507.61.1.5.7.1
::= { enc2191VoltageInfo 1 }
enc2191AirPressure OBJECT-TYPE
SYNTAX Integer32
UNITS "1 hPA (hectopascal) ~ 1 milibar"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"actual air pressure"
-- 1.3.6.1.4.1.28507.61.1.6.1.1.5
::= { enc2191SensorEntry 5 }
enc2191DewPoint OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degree Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"dew point for actual temperature and humidity"
-- 1.3.6.1.4.1.28507.61.1.6.1.1.6
::= { enc2191SensorEntry 6 }
enc2191DewPointDiff OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degree Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"difference between dew point and actual
temperature (Temp - DewPoint)"
-- 1.3.6.1.4.1.28507.61.1.6.1.1.7
::= { enc2191SensorEntry 7 }
enc2191POEEvt NOTIFICATION-TYPE
OBJECTS {
enc2191POE}
STATUS current
DESCRIPTION
"Power over Ethernet changed"
-- 1.3.6.1.4.1.28507.61.3.8
::= { events 8 }
enc2191InputEvt NOTIFICATION-TYPE
OBJECTS {
enc2191InputIndex,
enc2191Input}
STATUS current
DESCRIPTION
"Change of device input."
-- 1.3.6.1.4.1.28507.61.3.2
::= { events 2 }
enc2191HygroEvtSen NOTIFICATION-TYPE
OBJECTS {
enc2191SensorIndex,
enc2191HygroSensor}
STATUS current
DESCRIPTION
"hygro limits exceeded"
-- 1.3.6.1.4.1.28507.61.3.4
::= { events 4 }
enc2191InputEvtSen NOTIFICATION-TYPE
OBJECTS {
enc2191SensorIndex,
enc2191InputSensor}
STATUS current
DESCRIPTION
"change of logical input sensor state"
-- 1.3.6.1.4.1.28507.61.3.5
::= { events 5 }
enc2191AirPressureEvtSen NOTIFICATION-TYPE
OBJECTS {
enc2191SensorIndex,
enc2191AirPressure}
STATUS current
DESCRIPTION
"Air Pressure limits exceeded
"
-- 1.3.6.1.4.1.28507.61.3.6
::= { events 6 }
enc2191DewPtDiffEvtSen NOTIFICATION-TYPE
OBJECTS {
enc2191SensorIndex,
enc2191DewPointDiff}
STATUS current
DESCRIPTION
"Dew Point Difference limits exceeded"
-- 1.3.6.1.4.1.28507.61.3.7
::= { events 7 }
enc2191TempEvtSen NOTIFICATION-TYPE
OBJECTS {
enc2191SensorIndex,
enc2191TempSensor}
STATUS current
DESCRIPTION
"temperature limits exceeded"
-- 1.3.6.1.4.1.28507.61.3.3
::= { events 3 }
enc2191SwitchEvtPort NOTIFICATION-TYPE
OBJECTS {
enc2191PortIndex,
enc2191PortName,
enc2191PortState,
enc2191PortSwitchCount}
STATUS current
DESCRIPTION
"Event is triggered when a port is switched"
-- 1.3.6.1.4.1.28507.61.3.1
::= { events 1 }
END