GUDEADS-ENC2111-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
enterprises,
|
|
MODULE-IDENTITY,
|
|
OBJECT-TYPE,
|
|
NOTIFICATION-TYPE,
|
|
Integer32,
|
|
Unsigned32
|
|
FROM SNMPv2-SMI
|
|
OBJECT-GROUP,
|
|
NOTIFICATION-GROUP
|
|
FROM SNMPv2-CONF;
|
|
|
|
gudeads MODULE-IDENTITY
|
|
LAST-UPDATED "200703051356Z" -- Mar 5, 2007 1:56:00 PM
|
|
ORGANIZATION "Gude Analog- und Digitalsysteme GmbH"
|
|
CONTACT-INFO
|
|
"http://www.gudeads.com/"
|
|
DESCRIPTION
|
|
""
|
|
REVISION "200703051356Z" -- Mar 5, 2007 1:56:00 PM
|
|
DESCRIPTION
|
|
"$Id:$"
|
|
-- 1.3.6.1.4.1.28507
|
|
::= { enterprises 28507 }
|
|
|
|
|
|
enc2111POE OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "0 = no POE, 1 = POE available"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"signals POE availability"
|
|
-- 1.3.6.1.4.1.28507.60.1.5.10
|
|
::= { enc2111IntSensors 10 }
|
|
|
|
|
|
gadsENC2111 OBJECT IDENTIFIER
|
|
-- 1.3.6.1.4.1.28507.60
|
|
::= { gudeads 60 }
|
|
|
|
-- Notification Types
|
|
--
|
|
|
|
events OBJECT IDENTIFIER
|
|
-- 1.3.6.1.4.1.28507.60.3
|
|
::= { gadsENC2111 3 }
|
|
|
|
-- Scalars and Tables
|
|
--
|
|
|
|
enc2111Objects OBJECT IDENTIFIER
|
|
-- 1.3.6.1.4.1.28507.60.1
|
|
::= { gadsENC2111 1 }
|
|
|
|
enc2111CommonConfig OBJECT IDENTIFIER
|
|
-- 1.3.6.1.4.1.28507.60.1.1
|
|
::= { enc2111Objects 1 }
|
|
|
|
enc2111SNMPaccess OBJECT IDENTIFIER
|
|
-- 1.3.6.1.4.1.28507.60.1.1.1
|
|
::= { enc2111CommonConfig 1 }
|
|
|
|
enc2111TrapCtrl OBJECT-TYPE
|
|
SYNTAX Integer32 (0..3)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"0 = off
|
|
1 = Ver. 1
|
|
2 = Ver. 2c
|
|
3 = Ver. 3"
|
|
-- 1.3.6.1.4.1.28507.60.1.1.1.1
|
|
::= { enc2111SNMPaccess 1 }
|
|
|
|
|
|
enc2111TrapIPTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF Enc2111TrapIPEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"list of all Trap receiver"
|
|
-- 1.3.6.1.4.1.28507.60.1.1.1.2
|
|
::= { enc2111SNMPaccess 2 }
|
|
|
|
|
|
enc2111TrapIPEntry OBJECT-TYPE
|
|
SYNTAX Enc2111TrapIPEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"an entry containing management
|
|
informations regarding the list of trap
|
|
receivers"
|
|
INDEX {
|
|
enc2111TrapIPIndex }
|
|
-- 1.3.6.1.4.1.28507.60.1.1.1.2.1
|
|
::= { enc2111TrapIPTable 1 }
|
|
|
|
|
|
Enc2111TrapIPEntry ::= SEQUENCE {
|
|
|
|
enc2111TrapIPIndex Integer32,
|
|
enc2111TrapAddr OCTET STRING }
|
|
|
|
|
|
enc2111TrapIPIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..8)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value, greater than zero, for each receiver slot."
|
|
-- 1.3.6.1.4.1.28507.60.1.1.1.2.1.1
|
|
::= { enc2111TrapIPEntry 1 }
|
|
|
|
|
|
enc2111TrapAddr OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..99))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"DNS name or IP address specifying one Trap receiver slot.
|
|
A port can optionally be specified: 'name:port' An empty
|
|
string disables this slot."
|
|
-- 1.3.6.1.4.1.28507.60.1.1.1.2.1.2
|
|
::= { enc2111TrapIPEntry 2 }
|
|
|
|
|
|
enc2111DeviceConfig OBJECT IDENTIFIER
|
|
-- 1.3.6.1.4.1.28507.60.1.2
|
|
::= { enc2111Objects 2 }
|
|
|
|
enc2111IntActors OBJECT IDENTIFIER
|
|
-- 1.3.6.1.4.1.28507.60.1.3
|
|
::= { enc2111Objects 3 }
|
|
|
|
enc2111relayports OBJECT IDENTIFIER
|
|
-- 1.3.6.1.4.1.28507.60.1.3.1
|
|
::= { enc2111IntActors 1 }
|
|
|
|
enc2111portNumber OBJECT-TYPE
|
|
SYNTAX Integer32 (1..12)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of Relay Ports"
|
|
-- 1.3.6.1.4.1.28507.60.1.3.1.1
|
|
::= { enc2111relayports 1 }
|
|
|
|
|
|
-- the Interfaces table
|
|
-- The Interfaces table contains information on the entity's
|
|
-- interfaces. Each sub-layer below the internetwork-layer
|
|
-- of a network interface is considered to be an interface.
|
|
|
|
enc2111portTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF Enc2111portEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"list of all EPC Relay Ports"
|
|
-- 1.3.6.1.4.1.28507.60.1.3.1.2
|
|
::= { enc2111relayports 2 }
|
|
|
|
|
|
enc2111portEntry OBJECT-TYPE
|
|
SYNTAX Enc2111portEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing management information applicable to a
|
|
particular relay port."
|
|
INDEX {
|
|
enc2111PortIndex }
|
|
-- 1.3.6.1.4.1.28507.60.1.3.1.2.1
|
|
::= { enc2111portTable 1 }
|
|
|
|
|
|
Enc2111portEntry ::= SEQUENCE {
|
|
|
|
enc2111PortIndex Integer32,
|
|
enc2111PortName OCTET STRING,
|
|
enc2111PortState INTEGER,
|
|
enc2111PortSwitchCount Integer32,
|
|
enc2111PortStartupMode INTEGER,
|
|
enc2111PortStartupDelay Integer32,
|
|
enc2111PortRepowerTime Integer32 }
|
|
|
|
|
|
enc2111PortIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..4)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value, greater than zero, for each Relay Port."
|
|
-- 1.3.6.1.4.1.28507.60.1.3.1.2.1.1
|
|
::= { enc2111portEntry 1 }
|
|
|
|
|
|
enc2111PortName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..15))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A textual string containing name of a Relay Port."
|
|
-- 1.3.6.1.4.1.28507.60.1.3.1.2.1.2
|
|
::= { enc2111portEntry 2 }
|
|
|
|
|
|
enc2111PortState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(0),
|
|
on(1) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"current state of a Relay Port"
|
|
-- 1.3.6.1.4.1.28507.60.1.3.1.2.1.3
|
|
::= { enc2111portEntry 3 }
|
|
|
|
|
|
enc2111PortSwitchCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The total number of switch actions ocurred on a Relay Port.
|
|
Does not count switch commands which will not switch
|
|
the ralay state, so just real relay switches are displayed here."
|
|
-- 1.3.6.1.4.1.28507.60.1.3.1.2.1.4
|
|
::= { enc2111portEntry 4 }
|
|
|
|
|
|
enc2111PortStartupMode OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(0),
|
|
on(1),
|
|
laststate(2) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"set Mode of startup sequence (off, on , remember last state)"
|
|
DEFVAL { off }
|
|
-- 1.3.6.1.4.1.28507.60.1.3.1.2.1.5
|
|
::= { enc2111portEntry 5 }
|
|
|
|
|
|
enc2111PortStartupDelay OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Delay in sec for startup action"
|
|
DEFVAL { 0 }
|
|
-- 1.3.6.1.4.1.28507.60.1.3.1.2.1.6
|
|
::= { enc2111portEntry 6 }
|
|
|
|
|
|
enc2111PortRepowerTime OBJECT-TYPE
|
|
SYNTAX Integer32 (0..65535)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Delay in sec for repower port after switching off"
|
|
DEFVAL { 0 }
|
|
-- 1.3.6.1.4.1.28507.60.1.3.1.2.1.7
|
|
::= { enc2111portEntry 7 }
|
|
|
|
|
|
enc2111ExtActors OBJECT IDENTIFIER
|
|
-- 1.3.6.1.4.1.28507.60.1.4
|
|
::= { enc2111Objects 4 }
|
|
|
|
enc2111IntSensors OBJECT IDENTIFIER
|
|
-- 1.3.6.1.4.1.28507.60.1.5
|
|
::= { enc2111Objects 5 }
|
|
|
|
enc2111VoltageInfo OBJECT IDENTIFIER
|
|
-- 1.3.6.1.4.1.28507.60.1.5.7
|
|
::= { enc2111IntSensors 7 }
|
|
|
|
enc2111ExtSensors OBJECT IDENTIFIER
|
|
-- 1.3.6.1.4.1.28507.60.1.6
|
|
::= { enc2111Objects 6 }
|
|
|
|
enc2111SensorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF Enc2111SensorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION ""
|
|
-- 1.3.6.1.4.1.28507.60.1.6.1
|
|
::= { enc2111ExtSensors 1 }
|
|
|
|
|
|
enc2111SensorEntry OBJECT-TYPE
|
|
SYNTAX Enc2111SensorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION ""
|
|
INDEX {
|
|
enc2111SensorIndex }
|
|
-- 1.3.6.1.4.1.28507.60.1.6.1.1
|
|
::= { enc2111SensorTable 1 }
|
|
|
|
|
|
Enc2111SensorEntry ::= SEQUENCE {
|
|
|
|
enc2111SensorIndex Integer32,
|
|
enc2111TempSensor Integer32,
|
|
enc2111HygroSensor Integer32,
|
|
enc2111InputSensor INTEGER,
|
|
enc2111AirPressure Integer32,
|
|
enc2111DewPoint Integer32,
|
|
enc2111DewPointDiff Integer32 }
|
|
|
|
|
|
enc2111SensorIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..4)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION ""
|
|
-- 1.3.6.1.4.1.28507.60.1.6.1.1.1
|
|
::= { enc2111SensorEntry 1 }
|
|
|
|
|
|
enc2111State3V OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on(1),
|
|
error(3) }
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Show state of internal 3.3V"
|
|
-- 1.3.6.1.4.1.28507.60.1.5.7.2
|
|
::= { enc2111VoltageInfo 2 }
|
|
|
|
|
|
enc2111TempSensor OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 degree Celsius"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"actual temperature"
|
|
-- 1.3.6.1.4.1.28507.60.1.6.1.1.2
|
|
::= { enc2111SensorEntry 2 }
|
|
|
|
|
|
enc2111HygroSensor OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 percent humidity"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"actual humidity"
|
|
-- 1.3.6.1.4.1.28507.60.1.6.1.1.3
|
|
::= { enc2111SensorEntry 3 }
|
|
|
|
|
|
enc2111InputSensor OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(0),
|
|
on(1) }
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"logical state of input sensor"
|
|
-- 1.3.6.1.4.1.28507.60.1.6.1.1.4
|
|
::= { enc2111SensorEntry 4 }
|
|
|
|
|
|
-- Conformance
|
|
--
|
|
|
|
enc2111Conf OBJECT IDENTIFIER
|
|
-- 1.3.6.1.4.1.28507.60.2
|
|
::= { gadsENC2111 2 }
|
|
|
|
-- Groups
|
|
--
|
|
|
|
enc2111Groups OBJECT IDENTIFIER
|
|
-- 1.3.6.1.4.1.28507.60.2.1
|
|
::= { enc2111Conf 1 }
|
|
|
|
-- Compliance
|
|
--
|
|
|
|
enc2111Compls OBJECT IDENTIFIER
|
|
-- 1.3.6.1.4.1.28507.60.2.2
|
|
::= { enc2111Conf 2 }
|
|
|
|
enc2111BasicGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
enc2111TrapCtrl,
|
|
enc2111TrapIPIndex,
|
|
enc2111TrapAddr,
|
|
enc2111portNumber,
|
|
enc2111PortIndex,
|
|
enc2111PortName,
|
|
enc2111PortState,
|
|
enc2111PortSwitchCount,
|
|
enc2111PortStartupMode,
|
|
enc2111PortStartupDelay,
|
|
enc2111PortRepowerTime,
|
|
enc2111ActiveInputs,
|
|
enc2111InputIndex,
|
|
enc2111Input,
|
|
enc2111State12V,
|
|
enc2111State3V,
|
|
enc2111POE,
|
|
enc2111SensorIndex,
|
|
enc2111TempSensor,
|
|
enc2111HygroSensor,
|
|
enc2111InputSensor,
|
|
enc2111AirPressure,
|
|
enc2111DewPoint,
|
|
enc2111DewPointDiff }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Basic objects."
|
|
-- 1.3.6.1.4.1.28507.60.2.1.1
|
|
::= { enc2111Groups 1 }
|
|
|
|
enc2111NotificationGroup NOTIFICATION-GROUP
|
|
NOTIFICATIONS {
|
|
enc2111SwitchEvtPort,
|
|
enc2111InputEvt,
|
|
enc2111TempEvtSen,
|
|
enc2111HygroEvtSen,
|
|
enc2111InputEvtSen,
|
|
enc2111AirPressureEvtSen,
|
|
enc2111DewPtDiffEvtSen,
|
|
enc2111POEEvt }
|
|
STATUS current
|
|
DESCRIPTION ""
|
|
-- 1.3.6.1.4.1.28507.60.2.1.2
|
|
::= { enc2111Groups 2 }
|
|
|
|
enc2111Inputs OBJECT IDENTIFIER
|
|
-- 1.3.6.1.4.1.28507.60.1.5.6
|
|
::= { enc2111IntSensors 6 }
|
|
|
|
enc2111InputEntry OBJECT-TYPE
|
|
SYNTAX Enc2111InputEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION ""
|
|
INDEX {
|
|
enc2111InputIndex }
|
|
-- 1.3.6.1.4.1.28507.60.1.5.6.2.1
|
|
::= { enc2111InputTable 1 }
|
|
|
|
|
|
Enc2111InputEntry ::= SEQUENCE {
|
|
|
|
enc2111InputIndex Integer32,
|
|
enc2111Input INTEGER }
|
|
|
|
|
|
enc2111Input OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
lo(0),
|
|
hi(1) }
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Input state of device"
|
|
-- 1.3.6.1.4.1.28507.60.1.5.6.2.1.2
|
|
::= { enc2111InputEntry 2 }
|
|
|
|
|
|
enc2111ActiveInputs OBJECT-TYPE
|
|
SYNTAX Unsigned32 (1..12)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of suppported Input Channels."
|
|
-- 1.3.6.1.4.1.28507.60.1.5.6.1
|
|
::= { enc2111Inputs 1 }
|
|
|
|
|
|
enc2111InputTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF Enc2111InputEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION ""
|
|
-- 1.3.6.1.4.1.28507.60.1.5.6.2
|
|
::= { enc2111Inputs 2 }
|
|
|
|
|
|
enc2111InputIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..12)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION ""
|
|
-- 1.3.6.1.4.1.28507.60.1.5.6.2.1.1
|
|
::= { enc2111InputEntry 1 }
|
|
|
|
|
|
enc2111State12V OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(0),
|
|
low(1),
|
|
high(2),
|
|
error(3) }
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Show state of internal 12V"
|
|
-- 1.3.6.1.4.1.28507.60.1.5.7.1
|
|
::= { enc2111VoltageInfo 1 }
|
|
|
|
|
|
enc2111AirPressure OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "1 hPA (hectopascal) ~ 1 milibar"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"actual air pressure"
|
|
-- 1.3.6.1.4.1.28507.60.1.6.1.1.5
|
|
::= { enc2111SensorEntry 5 }
|
|
|
|
|
|
enc2111DewPoint OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 degree Celsius"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"dew point for actual temperature and humidity"
|
|
-- 1.3.6.1.4.1.28507.60.1.6.1.1.6
|
|
::= { enc2111SensorEntry 6 }
|
|
|
|
|
|
enc2111DewPointDiff OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 degree Celsius"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"difference between dew point and actual
|
|
temperature (Temp - DewPoint)"
|
|
-- 1.3.6.1.4.1.28507.60.1.6.1.1.7
|
|
::= { enc2111SensorEntry 7 }
|
|
|
|
|
|
|
|
enc2111POEEvt NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
enc2111POE}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power over Ethernet changed"
|
|
-- 1.3.6.1.4.1.28507.60.3.8
|
|
::= { events 8 }
|
|
|
|
|
|
enc2111InputEvt NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
enc2111InputIndex,
|
|
enc2111Input}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Change of device input."
|
|
-- 1.3.6.1.4.1.28507.60.3.2
|
|
::= { events 2 }
|
|
|
|
|
|
enc2111HygroEvtSen NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
enc2111SensorIndex,
|
|
enc2111HygroSensor}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"hygro limits exceeded"
|
|
-- 1.3.6.1.4.1.28507.60.3.4
|
|
::= { events 4 }
|
|
|
|
|
|
enc2111InputEvtSen NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
enc2111SensorIndex,
|
|
enc2111InputSensor}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"change of logical input sensor state"
|
|
-- 1.3.6.1.4.1.28507.60.3.5
|
|
::= { events 5 }
|
|
|
|
|
|
enc2111AirPressureEvtSen NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
enc2111SensorIndex,
|
|
enc2111AirPressure}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Air Pressure limits exceeded
|
|
|
|
"
|
|
-- 1.3.6.1.4.1.28507.60.3.6
|
|
::= { events 6 }
|
|
|
|
|
|
enc2111DewPtDiffEvtSen NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
enc2111SensorIndex,
|
|
enc2111DewPointDiff}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Dew Point Difference limits exceeded"
|
|
-- 1.3.6.1.4.1.28507.60.3.7
|
|
::= { events 7 }
|
|
|
|
|
|
enc2111TempEvtSen NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
enc2111SensorIndex,
|
|
enc2111TempSensor}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"temperature limits exceeded"
|
|
-- 1.3.6.1.4.1.28507.60.3.3
|
|
::= { events 3 }
|
|
|
|
|
|
enc2111SwitchEvtPort NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
enc2111PortIndex,
|
|
enc2111PortName,
|
|
enc2111PortState,
|
|
enc2111PortSwitchCount}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Event is triggered when a port is switched"
|
|
-- 1.3.6.1.4.1.28507.60.3.1
|
|
::= { events 1 }
|
|
|
|
END
|