Observium_CE/mibs/geist/VERTIV-QUETZAL-MIB

1421 lines
35 KiB
Plaintext

VERTIV-QUETZAL-MIB DEFINITIONS ::= BEGIN
IMPORTS
DisplayString, TEXTUAL-CONVENTION FROM SNMPv2-TC
MODULE-IDENTITY, OBJECT-TYPE, enterprises, Gauge32,
Integer32, Unsigned32, OBJECT-IDENTITY FROM SNMPv2-SMI;
vertiv MODULE-IDENTITY
LAST-UPDATED "201908300000Z"
ORGANIZATION "Vertiv"
CONTACT-INFO "support@geistglobal.com"
DESCRIPTION
"Vertiv Quetzal MIB (legacy)
Note: This MIB is deprecated and will be replaced by VERTIV-V5-MIB"
REVISION "201908300000Z"
DESCRIPTION
"Removed all pdu amps max and volts max fields"
REVISION "201906060000Z"
DESCRIPTION
"Updated pduOutletSwitchControl description"
REVISION "201801190000Z"
DESCRIPTION
"Changed fields in pduOutletSwitchTable to read-write, allowing for
configuration of outlet delays and Power-On Actions."
REVISION "201606290000Z"
DESCRIPTION
"MIB revisions to reflect SNMP changes for new architecture. In
particular, the STATUS of all fields have been changed to deprecated."
REVISION "201209210000Z"
DESCRIPTION
"Initial version"
::= { enterprises 21239 }
DeviceSerial ::= TEXTUAL-CONVENTION
STATUS deprecated
DESCRIPTION
"Unique serial number used to identify a device. A serial number is a
string, with a length of 16. The string will only contain the
characters 0 to 9, and A to F."
SYNTAX OCTET STRING (SIZE (1..16))
DeviceStatus ::= TEXTUAL-CONVENTION
STATUS deprecated
DESCRIPTION
"Indicates the condition of the device"
SYNTAX INTEGER {
ok(1),
notFound(2),
ioError(3),
unknown(4),
deleted(5)
}
DeviceLabel ::= TEXTUAL-CONVENTION
STATUS deprecated
DESCRIPTION
"User-defined device name"
SYNTAX OCTET STRING (SIZE (0..32))
TemperatureUnits ::= TEXTUAL-CONVENTION
STATUS deprecated
DESCRIPTION
"Used to tell the units of a temperature reading"
SYNTAX INTEGER {
fahrenheit(1),
celsius(2)
}
TemperatureValue ::= TEXTUAL-CONVENTION
DISPLAY-HINT "d-1"
STATUS deprecated
DESCRIPTION
"0.1 degree"
SYNTAX Integer32
DeciAmps ::= TEXTUAL-CONVENTION
DISPLAY-HINT "d-1"
STATUS deprecated
DESCRIPTION
"0.1 Amps"
SYNTAX Gauge32
quetzal OBJECT IDENTIFIER ::= { vertiv 6 }
devices OBJECT IDENTIFIER ::= { quetzal 1 }
legacyPDU OBJECT IDENTIFIER ::= { devices 99 }
rtafhd3 OBJECT IDENTIFIER ::= { devices 3 }
rt OBJECT IDENTIFIER ::= { devices 8 }
t3hd OBJECT IDENTIFIER ::= { devices 9 }
thd OBJECT IDENTIFIER ::= { devices 10 }
--###########################################################################################--
--pduBaseDeltaTable--
--###########################################################################################--
pduBaseDeltaTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduBaseDeltaEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"Base table for a delta-wired PDU. It contains general information
about the PDU. Entries in sub-tables provide data for channels, groups
and outlets. The system creates these sub-table entries based on
hardware and configuration options, set at the factory."
::= { legacyPDU 1 }
pduBaseDeltaEntry OBJECT-TYPE
SYNTAX PduBaseDeltaEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"Entry for a delta PDU device. This table will only have an entry if
the main device is a delta-wired PDU."
INDEX { pduBaseDeltaIndex }
::= { pduBaseDeltaTable 1 }
PduBaseDeltaEntry ::= SEQUENCE {
pduBaseDeltaIndex Unsigned32,
pduBaseDeltaSerial DeviceSerial,
pduBaseDeltaLabel DeviceLabel,
pduBaseDeltaStatus DeviceStatus,
pduBaseDeltaKWattHrsTotal Gauge32,
pduBaseDeltaRealPowerTotal Gauge32,
pduBaseDeltaAmpsA DeciAmps,
pduBaseDeltaAmpsB DeciAmps,
pduBaseDeltaAmpsC DeciAmps
}
pduBaseDeltaIndex OBJECT-TYPE
SYNTAX Unsigned32(1..64)
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"Table entry index value"
::= { pduBaseDeltaEntry 1 }
pduBaseDeltaSerial OBJECT-TYPE
SYNTAX DeviceSerial
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"PDU's unique ID, used as a reference for channels, groups and outlets"
::= { pduBaseDeltaEntry 2 }
pduBaseDeltaLabel OBJECT-TYPE
SYNTAX DeviceLabel
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"User-defined name for the delta PDU device"
::= { pduBaseDeltaEntry 3 }
pduBaseDeltaStatus OBJECT-TYPE
SYNTAX DeviceStatus
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Condition of the device"
::= { pduBaseDeltaEntry 4 }
pduBaseDeltaKWattHrsTotal OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Total kilowatt hours for the delta PDU"
::= { pduBaseDeltaEntry 5 }
pduBaseDeltaRealPowerTotal OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Total real power for the delta PDU"
::= { pduBaseDeltaEntry 6 }
pduBaseDeltaAmpsA OBJECT-TYPE
SYNTAX DeciAmps
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Current reading for A"
::= { pduBaseDeltaEntry 7 }
pduBaseDeltaAmpsB OBJECT-TYPE
SYNTAX DeciAmps
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Current reading for B"
::= { pduBaseDeltaEntry 8 }
pduBaseDeltaAmpsC OBJECT-TYPE
SYNTAX DeciAmps
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Current reading for C"
::= { pduBaseDeltaEntry 9 }
--###########################################################################################--
--pduBaseWyeTable--
--###########################################################################################--
pduBaseWyeTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduBaseWyeEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"Base table for a Wye-wired PDU. It contains general information about
the PDU. Entries in sub-tables provide data for channels, groups and
outlets. The system creates these sub-table entries based on hardware,
wiring, and configuration options, set at the factory."
::= { legacyPDU 2 }
pduBaseWyeEntry OBJECT-TYPE
SYNTAX PduBaseWyeEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"Entry for a Wye-wired PDU device. This table will only have an entry
if the PDU uses a Wye wiring."
INDEX { pduBaseWyeIndex }
::= { pduBaseWyeTable 1 }
PduBaseWyeEntry ::= SEQUENCE {
pduBaseWyeIndex Unsigned32,
pduBaseWyeSerial DeviceSerial,
pduBaseWyeLabel DeviceLabel,
pduBaseWyeStatus DeviceStatus,
pduBaseWyeKWattHrsTotal Gauge32,
pduBaseWyeRealPowerTotal Gauge32,
pduBaseWyeChannelCount Unsigned32
}
pduBaseWyeIndex OBJECT-TYPE
SYNTAX Unsigned32(1..64)
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"Table entry index value"
::= { pduBaseWyeEntry 1 }
pduBaseWyeSerial OBJECT-TYPE
SYNTAX DeviceSerial
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"PDU's unique ID, used as a reference for channels, groups and outlets"
::= { pduBaseWyeEntry 2 }
pduBaseWyeLabel OBJECT-TYPE
SYNTAX DeviceLabel
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"User-defined name for the PDU"
::= { pduBaseWyeEntry 3 }
pduBaseWyeStatus OBJECT-TYPE
SYNTAX DeviceStatus
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Condition of the device"
::= { pduBaseWyeEntry 4 }
pduBaseWyeKWattHrsTotal OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Total kilowatt hours for the PDU"
::= { pduBaseWyeEntry 5 }
pduBaseWyeRealPowerTotal OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Total real power used by the PDU"
::= { pduBaseWyeEntry 6 }
pduBaseWyeChannelCount OBJECT-TYPE
SYNTAX Unsigned32(1..3)
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Count of the total number of Wye channels. Data for these channels is
found in the pduChannelWyeTable."
::= { pduBaseWyeEntry 7 }
--###########################################################################################--
--pduChannelDeltaTable--
--###########################################################################################--
pduChannelDeltaTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduChannelDeltaEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"The pduChannelDeltaTable contains specific channel information for a
delta PDU."
::= { legacyPDU 3 }
pduChannelDeltaEntry OBJECT-TYPE
SYNTAX PduChannelDeltaEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"Each entry represents a delta channel. Entries are indexed by the PDU
instance number and a channel id number. This table will only have
entries if a corresponding delta PDU exists."
INDEX { pduBaseDeltaIndex, pduChannelDeltaID }
::= { pduChannelDeltaTable 1 }
PduChannelDeltaEntry ::= SEQUENCE {
pduChannelDeltaID Unsigned32,
pduChannelDeltaLabel DeviceLabel,
pduChannelDeltaName DisplayString,
pduChannelDeltaKWattHrs Gauge32,
pduChannelDeltaVolts Gauge32,
pduChannelDeltaRealPower Gauge32,
pduChannelDeltaApparentPower Gauge32,
pduChannelDeltaPowerFactor Gauge32,
pduChannelDeltaAmps DeciAmps
}
pduChannelDeltaID OBJECT-TYPE
SYNTAX Unsigned32(1..3)
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Delta channel id number"
::= { pduChannelDeltaEntry 1 }
pduChannelDeltaLabel OBJECT-TYPE
SYNTAX DeviceLabel
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"User-defined name for this channel"
::= { pduChannelDeltaEntry 2 }
pduChannelDeltaName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Factory-assigned name for this channel"
::= { pduChannelDeltaEntry 3 }
pduChannelDeltaKWattHrs OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Kilowatt hours for this channel"
::= { pduChannelDeltaEntry 4 }
pduChannelDeltaVolts OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Volt reading"
::= { pduChannelDeltaEntry 5 }
pduChannelDeltaRealPower OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Real power"
::= { pduChannelDeltaEntry 7 }
pduChannelDeltaApparentPower OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Apparent Power"
::= { pduChannelDeltaEntry 8 }
pduChannelDeltaPowerFactor OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Power Factor"
::= { pduChannelDeltaEntry 9 }
pduChannelDeltaAmps OBJECT-TYPE
SYNTAX DeciAmps
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Current reading"
::= { pduChannelDeltaEntry 10 }
--###########################################################################################--
--pduChannelWyeTable--
--###########################################################################################--
pduChannelWyeTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduChannelWyeEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"The pduChannelWyeTable contains specific channel information for a
wye-wired PDU."
::= { legacyPDU 4 }
pduChannelWyeEntry OBJECT-TYPE
SYNTAX PduChannelWyeEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"Each entry represents a wye channel. Entries are indexed by the
instance number of a PDU and a channel id number. This table will only
have entries if a corresponding wye-wired PDU exists."
INDEX { pduBaseWyeIndex, pduChannelWyeID }
::= { pduChannelWyeTable 1 }
PduChannelWyeEntry ::= SEQUENCE {
pduChannelWyeID Unsigned32,
pduChannelWyeLabel DeviceLabel,
pduChannelWyeName DisplayString,
pduChannelWyeKWattHrs Gauge32,
pduChannelWyeVolts Gauge32,
pduChannelWyeAmps DeciAmps,
pduChannelWyeRealPower Gauge32,
pduChannelWyeApparentPower Gauge32,
pduChannelWyePowerFactor Gauge32
}
pduChannelWyeID OBJECT-TYPE
SYNTAX Unsigned32(1..3)
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Wye channel id"
::= { pduChannelWyeEntry 1 }
pduChannelWyeLabel OBJECT-TYPE
SYNTAX DeviceLabel
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"User-defined name for this channel"
::= { pduChannelWyeEntry 2 }
pduChannelWyeName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Factory-assigned name for this channel"
::= { pduChannelWyeEntry 3 }
pduChannelWyeKWattHrs OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Kilowatt hours"
::= { pduChannelWyeEntry 4 }
pduChannelWyeVolts OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Volt reading"
::= { pduChannelWyeEntry 5 }
pduChannelWyeAmps OBJECT-TYPE
SYNTAX DeciAmps
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Current reading"
::= { pduChannelWyeEntry 7 }
pduChannelWyeRealPower OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Real power"
::= { pduChannelWyeEntry 9 }
pduChannelWyeApparentPower OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Apparent power"
::= { pduChannelWyeEntry 10 }
pduChannelWyePowerFactor OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Power factor"
::= { pduChannelWyeEntry 11 }
--###########################################################################################--
--pduGroupTable--
--###########################################################################################--
pduGroupTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduGroupEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"Contains meter readings per outlet group"
::= { legacyPDU 5 }
pduGroupEntry OBJECT-TYPE
SYNTAX PduGroupEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"Each entry represents an outlet group for a specific PDU. Groups are
indexed by a PDU instance number and a group id number. The
pduGroupIndex corresponds to a matching instance number in a base PDU
table. For group entries to exist, a PDU that supports groups must
also exist."
INDEX { pduGroupIndex, pduGroupID }
::= { pduGroupTable 1 }
PduGroupEntry ::= SEQUENCE {
pduGroupIndex Unsigned32,
pduGroupSerial DeviceSerial,
pduGroupID Unsigned32,
pduGroupLabel DeviceLabel,
pduGroupName DisplayString,
pduGroupAmps DeciAmps,
pduGroupApparentPower Gauge32,
pduGroupPowerFactor Gauge32,
pduGroupRealPower Gauge32,
pduGroupVolts Gauge32,
pduGroupWattHours Gauge32
}
pduGroupIndex OBJECT-TYPE
SYNTAX Unsigned32(1..64)
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"Table entry index value"
::= { pduGroupEntry 1 }
pduGroupSerial OBJECT-TYPE
SYNTAX DeviceSerial
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Serial number of an existing base PDU"
::= { pduGroupEntry 2 }
pduGroupID OBJECT-TYPE
SYNTAX Unsigned32(1..8)
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Group id number"
::= { pduGroupEntry 3 }
pduGroupLabel OBJECT-TYPE
SYNTAX DeviceLabel
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"User-defined name for this group"
::= { pduGroupEntry 4 }
pduGroupName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Factory-assigned name for this group"
::= { pduGroupEntry 5 }
pduGroupAmps OBJECT-TYPE
SYNTAX DeciAmps
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Total amps for outlet group"
::= { pduGroupEntry 6 }
pduGroupApparentPower OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Total apparent-power for outlet group"
::= { pduGroupEntry 8 }
pduGroupPowerFactor OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Total power-factor for outlet group"
::= { pduGroupEntry 9 }
pduGroupRealPower OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Total real-power for outlet group"
::= { pduGroupEntry 10 }
pduGroupVolts OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Volts reading for outlet group"
::= { pduGroupEntry 11 }
pduGroupWattHours OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Watt-hours reading for outlet group"
::= { pduGroupEntry 13 }
--###########################################################################################--
--pduOutletMainTable--
--###########################################################################################--
pduOutletMainTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduOutletMainEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"Outlet data common to all outlet types. Other tables provide
additional data, based on the outlet type."
::= { legacyPDU 6 }
pduOutletMainEntry OBJECT-TYPE
SYNTAX PduOutletMainEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"One entry per outlet. Each entry corresponds to an outlet on a PDU, so
they are indexed by the PDU's instance number and an outlet id number.
The pduOutletMainIndex corresponds to an instance number for an
existing PDU."
INDEX { pduOutletMainIndex, pduOutletMainID }
::= { pduOutletMainTable 1 }
PduOutletMainEntry ::= SEQUENCE {
pduOutletMainIndex Unsigned32,
pduOutletMainSerial DeviceSerial,
pduOutletMainID Unsigned32,
pduOutletMainLabel DeviceLabel,
pduOutletMainName DisplayString,
pduOutletMainGroup DisplayString,
pduOutletMainURL DisplayString
}
pduOutletMainIndex OBJECT-TYPE
SYNTAX Unsigned32(1..64)
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"Table entry index value"
::= { pduOutletMainEntry 1 }
pduOutletMainSerial OBJECT-TYPE
SYNTAX DeviceSerial
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Serial number of an existing PDU device"
::= { pduOutletMainEntry 2 }
pduOutletMainID OBJECT-TYPE
SYNTAX Unsigned32(1..64)
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Outlet id number"
::= { pduOutletMainEntry 3 }
pduOutletMainLabel OBJECT-TYPE
SYNTAX DeviceLabel
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"User-defined outlet name"
::= { pduOutletMainEntry 4 }
pduOutletMainName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Factory-assigned outlet name"
::= { pduOutletMainEntry 5 }
pduOutletMainGroup OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Outlet's group name"
::= { pduOutletMainEntry 6 }
pduOutletMainURL OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Link info for outlet"
::= { pduOutletMainEntry 7 }
--###########################################################################################--
--pduOutletSwitchTable--
--###########################################################################################--
pduOutletSwitchTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduOutletSwitchEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"Contains entries for outlets that support switching. This table
supplements the corresponding entries in pduOutletMainTable."
::= { legacyPDU 7 }
pduOutletSwitchEntry OBJECT-TYPE
SYNTAX PduOutletSwitchEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"One entry is created per switching outlet. These entries correspond to
an outlet entry in pduOutletMainTable. Each entry in this table uses
the index and outlet id from the pduOutletMainTable."
INDEX { pduOutletMainIndex, pduOutletMainID }
::= { pduOutletSwitchTable 1 }
PduOutletSwitchEntry ::= SEQUENCE {
pduOutletSwitchState INTEGER,
pduOutletSwitchStateChangeTime Unsigned32,
pduOutletSwitchCurrentAction INTEGER,
pduOutletSwitchOnDelay Unsigned32,
pduOutletSwitchOffDelay Unsigned32,
pduOutletSwitchRebootDelay Unsigned32,
pduOutletSwitchRebootHold Unsigned32,
pduOutletSwitchStartupAction INTEGER,
pduOutletSwitchStartupStateDelay Unsigned32,
pduOutletSwitchControl INTEGER
}
pduOutletSwitchState OBJECT-TYPE
SYNTAX INTEGER {
outletOff(0),
outletOn(1),
outletError(2)
}
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Switch state of the outlet"
::= { pduOutletSwitchEntry 1 }
pduOutletSwitchStateChangeTime OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Seconds until an action will occur"
::= { pduOutletSwitchEntry 2 }
pduOutletSwitchCurrentAction OBJECT-TYPE
SYNTAX INTEGER {
manual(1),
reboot(2),
startUp(3),
other(4)
}
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Outlet action in progress"
::= { pduOutletSwitchEntry 3 }
pduOutletSwitchOnDelay OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Delay used in turning the outlet on"
::= { pduOutletSwitchEntry 4 }
pduOutletSwitchOffDelay OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Delay used in turning the outlet off"
::= { pduOutletSwitchEntry 5 }
pduOutletSwitchRebootDelay OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Delay used prior to outlet reboot"
::= { pduOutletSwitchEntry 6 }
pduOutletSwitchRebootHold OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Time the outlet is kept off during a reboot"
::= { pduOutletSwitchEntry 7 }
pduOutletSwitchStartupAction OBJECT-TYPE
SYNTAX INTEGER {
startOff(0),
startOn(1),
lastKnown(2)
}
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"State the outlet should take at startup (first powered)"
::= { pduOutletSwitchEntry 8 }
pduOutletSwitchStartupStateDelay OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Delay from startup before the outlet changes to the StartupAction"
::= { pduOutletSwitchEntry 9 }
pduOutletSwitchControl OBJECT-TYPE
SYNTAX INTEGER {
none(0),
cancelActions(1),
onNoDelay(2),
onDelay(3),
offNoDelay(4),
offDelay(5),
rebootNoDelay(6),
rebootDelay(7)
}
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Used for manual control of the outlet. The default is none(0). When
set, it keeps this value until the operation is complete. Then the
value goes back to none(0). Outlet must be in manual mode to set,
otherwise it causes an inconsistentValue error. Can be set to one of
the following:
1 = Cancel pending action
2 = Turn outlet on without delay
3 = After delay, turn outlet on
4 = Turn outlet off without delay
5 = After delay, turn outlet off
6 = Reboot outlet without delay
7 = After delay, reboot outlet"
::= { pduOutletSwitchEntry 10 }
--###########################################################################################--
--pduOutletMeterTable--
--###########################################################################################--
pduOutletMeterTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduOutletMeterEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"Contains entries for outlets that support metering. This table
supplements the corresponding entries in pduOutletMainTable."
::= { legacyPDU 8 }
pduOutletMeterEntry OBJECT-TYPE
SYNTAX PduOutletMeterEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"One entry is created per metering outlet. These entries correspond to
an outlet entry in pduOutletMainTable. Each entry in this table uses
the index and outlet id from the pduOutletMainTable."
INDEX { pduOutletMainIndex, pduOutletMainID }
::= { pduOutletMeterTable 1 }
PduOutletMeterEntry ::= SEQUENCE {
pduOutletMeterKWattHrs Gauge32,
pduOutletMeterAmps DeciAmps,
pduOutletMeterPower Gauge32
}
pduOutletMeterKWattHrs OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Kilowatt hours for outlet"
::= { pduOutletMeterEntry 1 }
pduOutletMeterAmps OBJECT-TYPE
SYNTAX DeciAmps
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Current reading for outlet"
::= { pduOutletMeterEntry 2 }
pduOutletMeterPower OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Power measurement for outlet"
::= { pduOutletMeterEntry 3 }
--###########################################################################################--
--rtafhd3Table--
--###########################################################################################--
rtafhd3Table OBJECT-TYPE
SYNTAX SEQUENCE OF Rtafhd3Entry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"Combo airflow, temp, humidity and dewpoint sensor"
::= { rtafhd3 1 }
rtafhd3Entry OBJECT-TYPE
SYNTAX Rtafhd3Entry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"One entry per device. Indexed by an instance number."
INDEX { rtafhd3Index }
::= { rtafhd3Table 1 }
Rtafhd3Entry ::= SEQUENCE {
rtafhd3Index Unsigned32,
rtafhd3Serial DeviceSerial,
rtafhd3Label DeviceLabel,
rtafhd3Status DeviceStatus,
rtafhd3Airflow Gauge32,
rtafhd3Humidity Gauge32,
rtafhd3Temp TemperatureValue,
rtafhd3DewPoint TemperatureValue,
rtafhd3TDUnits TemperatureUnits
}
rtafhd3Index OBJECT-TYPE
SYNTAX Unsigned32(1..64)
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"Table entry index value"
::= { rtafhd3Entry 1 }
rtafhd3Serial OBJECT-TYPE
SYNTAX DeviceSerial
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Unique device id"
::= { rtafhd3Entry 2 }
rtafhd3Label OBJECT-TYPE
SYNTAX DeviceLabel
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"User-defined name"
::= { rtafhd3Entry 3 }
rtafhd3Status OBJECT-TYPE
SYNTAX DeviceStatus
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Sensor condition"
::= { rtafhd3Entry 4 }
rtafhd3Airflow OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Airflow reading"
::= { rtafhd3Entry 5 }
rtafhd3Humidity OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Humidity reading"
::= { rtafhd3Entry 6 }
rtafhd3Temp OBJECT-TYPE
SYNTAX TemperatureValue
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Temperature reading in units indicated by rtafhd3TDUnits."
::= { rtafhd3Entry 7 }
rtafhd3DewPoint OBJECT-TYPE
SYNTAX TemperatureValue
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Dewpoint reading in units indicated by rtafhd3TDUnits."
::= { rtafhd3Entry 8 }
rtafhd3TDUnits OBJECT-TYPE
SYNTAX TemperatureUnits
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Tells what units are used for temperature and dewpoint."
::= { rtafhd3Entry 9 }
--###########################################################################################--
--rtTable--
--###########################################################################################--
rtTable OBJECT-TYPE
SYNTAX SEQUENCE OF RtEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"Contains entries for remote temperature devices"
::= { rt 1 }
rtEntry OBJECT-TYPE
SYNTAX RtEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"One entry per device. Indexed by an instance number."
INDEX { rtIndex }
::= { rtTable 1 }
RtEntry ::= SEQUENCE {
rtIndex Unsigned32,
rtSerial DeviceSerial,
rtLabel DeviceLabel,
rtStatus DeviceStatus,
rtTemp TemperatureValue,
rtUnits TemperatureUnits
}
rtIndex OBJECT-TYPE
SYNTAX Unsigned32(1..64)
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"Table entry index value"
::= { rtEntry 1 }
rtSerial OBJECT-TYPE
SYNTAX DeviceSerial
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Unique device id"
::= { rtEntry 2 }
rtLabel OBJECT-TYPE
SYNTAX DeviceLabel
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"User-defined name"
::= { rtEntry 3 }
rtStatus OBJECT-TYPE
SYNTAX DeviceStatus
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Device condition"
::= { rtEntry 4 }
rtTemp OBJECT-TYPE
SYNTAX TemperatureValue
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Temperature reading. The units for this measurement are given by
rtUnits."
::= { rtEntry 5 }
rtUnits OBJECT-TYPE
SYNTAX TemperatureUnits
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Indicates what units rtTemp will be given in."
::= { rtEntry 6 }
--###########################################################################################--
--t3hdTable--
--###########################################################################################--
t3hdTable OBJECT-TYPE
SYNTAX SEQUENCE OF T3hdEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"Contains entries for T3HD devices"
::= { t3hd 1 }
t3hdEntry OBJECT-TYPE
SYNTAX T3hdEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"Each entry represents a T3HD device. They are indexed by an instance
number."
INDEX { t3hdIndex }
::= { t3hdTable 1 }
T3hdEntry ::= SEQUENCE {
t3hdIndex Unsigned32,
t3hdSerial DeviceSerial,
t3hdLabel DeviceLabel,
t3hdStatus DeviceStatus,
t3hdMainLabel DeviceLabel,
t3hdMainTemp TemperatureValue,
t3hdMainHumidity Gauge32,
t3hdMainDewPoint TemperatureValue,
t3hdExt1Status INTEGER,
t3hdExt1Label DeviceLabel,
t3hdExt1Temp TemperatureValue,
t3hdExt2Status INTEGER,
t3hdExt2Label DeviceLabel,
t3hdExt2Temp TemperatureValue,
t3hdTDUnits TemperatureUnits
}
t3hdIndex OBJECT-TYPE
SYNTAX Unsigned32(1..64)
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"Table entry index value"
::= { t3hdEntry 1 }
t3hdSerial OBJECT-TYPE
SYNTAX DeviceSerial
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Unique device id"
::= { t3hdEntry 2 }
t3hdLabel OBJECT-TYPE
SYNTAX DeviceLabel
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"User-defined name"
::= { t3hdEntry 3 }
t3hdStatus OBJECT-TYPE
SYNTAX DeviceStatus
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Device condition"
::= { t3hdEntry 4 }
t3hdMainLabel OBJECT-TYPE
SYNTAX DeviceLabel
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"User-defined label for measurements from the main device"
::= { t3hdEntry 5 }
t3hdMainTemp OBJECT-TYPE
SYNTAX TemperatureValue
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Temperature reading from the main device"
::= { t3hdEntry 6 }
t3hdMainHumidity OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Humidity reading from the main device"
::= { t3hdEntry 7 }
t3hdMainDewPoint OBJECT-TYPE
SYNTAX TemperatureValue
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Dew Point value from the main device"
::= { t3hdEntry 8 }
t3hdExt1Status OBJECT-TYPE
SYNTAX INTEGER {
unplugged(0),
normal(1),
error(2)
}
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Sensor status for external temp 1. The status is one of the following
values:
0 = Sensor unplugged
1 = Normal operation
2 = Sensor error"
::= { t3hdEntry 9 }
t3hdExt1Label OBJECT-TYPE
SYNTAX DeviceLabel
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"User-defined name for external temp 1"
::= { t3hdEntry 10 }
t3hdExt1Temp OBJECT-TYPE
SYNTAX TemperatureValue
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Temperature reading from external temp 1"
::= { t3hdEntry 11 }
t3hdExt2Status OBJECT-TYPE
SYNTAX INTEGER {
unplugged(0),
normal(1),
error(2)
}
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Sensor status for external temp 2. The status is one of the following
values:
0 = Sensor unplugged
1 = Normal operation
2 = Sensor error"
::= { t3hdEntry 12 }
t3hdExt2Label OBJECT-TYPE
SYNTAX DeviceLabel
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"User-defined name for external temp 2"
::= { t3hdEntry 13 }
t3hdExt2Temp OBJECT-TYPE
SYNTAX TemperatureValue
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Temperature reading from external temp 2"
::= { t3hdEntry 14 }
t3hdTDUnits OBJECT-TYPE
SYNTAX TemperatureUnits
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Tells what units are used for temperatures and dewpoint."
::= { t3hdEntry 15 }
--###########################################################################################--
--thdTable--
--###########################################################################################--
thdTable OBJECT-TYPE
SYNTAX SEQUENCE OF ThdEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"Contains entries for THD devices"
::= { thd 1 }
thdEntry OBJECT-TYPE
SYNTAX ThdEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"Each entry represents a THD device. They are indexed by an instance
number."
INDEX { thdIndex }
::= { thdTable 1 }
ThdEntry ::= SEQUENCE {
thdIndex Unsigned32,
thdSerial DeviceSerial,
thdLabel DeviceLabel,
thdStatus DeviceStatus,
thdTemp TemperatureValue,
thdHumidity Gauge32,
thdDewPoint TemperatureValue,
thdTDUnits TemperatureUnits
}
thdIndex OBJECT-TYPE
SYNTAX Unsigned32(1..64)
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"Table entry index value"
::= { thdEntry 1 }
thdSerial OBJECT-TYPE
SYNTAX DeviceSerial
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Unique device id"
::= { thdEntry 2 }
thdLabel OBJECT-TYPE
SYNTAX DeviceLabel
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"User-defined name"
::= { thdEntry 3 }
thdStatus OBJECT-TYPE
SYNTAX DeviceStatus
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Device condition"
::= { thdEntry 4 }
thdTemp OBJECT-TYPE
SYNTAX TemperatureValue
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Temperature reading"
::= { thdEntry 5 }
thdHumidity OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Humidity reading"
::= { thdEntry 6 }
thdDewPoint OBJECT-TYPE
SYNTAX TemperatureValue
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Dew Point value"
::= { thdEntry 7 }
thdTDUnits OBJECT-TYPE
SYNTAX TemperatureUnits
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Units used for temperature and dew point."
::= { thdEntry 8 }
--###########################################################################################--
--common group--
--###########################################################################################--
common OBJECT IDENTIFIER ::= { vertiv 42 }
identity OBJECT IDENTIFIER ::= { common 1 }
r05 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Value given for sysObjectID on R-Series units"
::= { identity 15 }
i03 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Value given for sysObjectID on IMD3 units"
::= { identity 53 }
END