Observium_CE/mibs/eta/ETA-RCI10-MIB

1897 lines
49 KiB
Plaintext

ETA-RCI10-MIB DEFINITIONS ::= BEGIN
IMPORTS
OBJECT-TYPE, IpAddress, MODULE-IDENTITY, NOTIFICATION-TYPE, enterprises, Integer32 FROM SNMPv2-SMI;
-- 1.3.6.1.4.1.44086.4.1
rci10 MODULE-IDENTITY
LAST-UPDATED "201810081546Z" -- October 08, 2018 at 15:46 GMT
ORGANIZATION
"E-T-A Elektrotechnische Apparate GmbH"
CONTACT-INFO
"www.e-t-a.de"
DESCRIPTION
"Copyright notice
(c) E-T-A Elektrotechnische Apparate GmbH
2014-2015 Florian Pfanner, Michael Haerteis
This MIB file was created for a RCI10. Via
SNMP the slave states can be retrieved and device actions can initiated."
REVISION "201810081546Z" -- October 08, 2018 at 15:46 GMT
DESCRIPTION
"Version 1.020 (added fuse objects for device type 0x70)"
REVISION "201703031052Z" -- March 03, 2017 at 10:52 GMT
DESCRIPTION
"Version 1.010 (added exernal alarms)"
REVISION "201502021303Z" -- February 02, 2015 at 13:03 GMT
DESCRIPTION
"Initial version"
::= { etaProp 1 }
eta OBJECT IDENTIFIER ::= { enterprises 44086 }
etaProp OBJECT IDENTIFIER ::= { eta 4 }
system OBJECT IDENTIFIER ::= { rci10 1 }
snmp OBJECT IDENTIFIER ::= { system 1 }
ethernet OBJECT IDENTIFIER ::= { system 2 }
ipv4 OBJECT IDENTIFIER ::= { ethernet 1 }
ipv6 OBJECT IDENTIFIER ::= { ethernet 2 }
dateTime OBJECT IDENTIFIER ::= { system 3 }
fuses OBJECT IDENTIFIER ::= { rci10 10 }
feedA OBJECT IDENTIFIER ::= { fuses 1 }
feedB OBJECT IDENTIFIER ::= { fuses 2 }
externalAlarms OBJECT IDENTIFIER ::= { rci10 20 }
eaFeedA OBJECT IDENTIFIER ::= { externalAlarms 1 }
eaFeedB OBJECT IDENTIFIER ::= { externalAlarms 2 }
notifications OBJECT IDENTIFIER ::= { rci10 100 }
prefix OBJECT IDENTIFIER ::= { notifications 1 }
systemNotifications OBJECT IDENTIFIER ::= { prefix 1 }
fusesNotifications OBJECT IDENTIFIER ::= { prefix 10 }
externalAlarmNotifications OBJECT IDENTIFIER ::= { prefix 20 }
objects OBJECT IDENTIFIER ::= { notifications 2 }
systemObjects OBJECT IDENTIFIER ::= { objects 1 }
fusesObjects OBJECT IDENTIFIER ::= { objects 10 }
externalAlarmObjects OBJECT IDENTIFIER ::= { objects 20 }
snmpTrapsEnable OBJECT-TYPE
SYNTAX Integer32 (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"If 1 sending of SNMP traps is enabled. Else no traps will be sent"
::= { snmp 1 }
snmpTrapTarget OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (1..100))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Traps are sent to the destination given here. This could be an IP address or a host name."
::= { snmp 2 }
snmpProtocol OBJECT-TYPE
SYNTAX OCTET STRING
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SNMP protocol version currently used. The value can only be changed using the SSH configuration."
::= { snmp 3 }
snmpCommunityString OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (1..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"SNMP community string used to access the values. Also the SNMP traps are sent using this community string. Only valid if SNMPv2c is used."
::= { snmp 10 }
snmpLogin OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (1..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Login name used to access the SNMP data values. Only valid if SNMPv3 is used."
::= { snmp 20 }
snmpPassword OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (1..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Password used to access the SNMP data values. The password have to be at least eight characters long. Only valid if SNMPv3 is used."
::= { snmp 21 }
snmpAuthentication OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (3))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Authentication method used to encrypt the SNMP data transmission. Valid entries are 'MD5' and 'SHA'. Only valid if SNMPv3 is used."
::= { snmp 22 }
snmpEncryption OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (3))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Encryption method used for the SNMP data transmission. Valid entries are 'AES', 'DES' and 'off'. Only valid if SNMPv3 is used."
::= { snmp 23 }
snmpEncryptionKey OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (1..500))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Encryption key used for the SNMP data transmission. Only valid if SNMPv3 is used."
::= { snmp 24 }
dnsServer OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Address of DNS server, for example 192.168.0.1. The address given here can be either an IPv4 or an IPv6 address."
::= { ethernet 10 }
dhcpv4Enable OBJECT-TYPE
SYNTAX Integer32 (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"If 1 the IPv4 settings are automatically obtained using DHCP."
::= { ipv4 1 }
ip4Address OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"IPv4 adress of the RCI10, for example 192.168.1.25."
::= { ipv4 10 }
ip4NetMask OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"IPv4 network mask, for example 255.255.255.0."
::= { ipv4 11 }
ip4Gateway OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"IPv4 gateway address, for example 192.168.1.1."
::= { ipv4 12 }
dhcpv6Enable OBJECT-TYPE
SYNTAX Integer32 (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"If 1 the IPv6 settings are automatically obtained using DHCP."
::= { ipv6 1 }
ip6Address OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"IPv6 adress of the RCI10, for example 2001:0db8:85a3::1000."
::= { ipv6 10 }
ip6PrefixLength OBJECT-TYPE
SYNTAX Integer32 (1..128)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"IPv6 network prefix length. Valid range is from 1 to 128."
::= { ipv6 11 }
time OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (8))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Current system time. Write to this object to update the system time, use the format HH:MM:SS."
::= { dateTime 1 }
date OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (10))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Current date of the RCI10. Write to this object to update the system date, use the format dd.mm.yyyy."
::= { dateTime 2 }
timezone OBJECT-TYPE
SYNTAX Integer32 (-12..12)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Timezone of the RCI10. The timezone gives the difference between UTC and local time in hours."
::= { dateTime 3 }
dstEn OBJECT-TYPE
SYNTAX Integer32 (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"If 1 the daylight saving time is enabled."
::= { dateTime 4 }
hwVersion OBJECT-TYPE
SYNTAX OCTET STRING
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RCI10 hardware version"
::= { system 11 }
hwSerial OBJECT-TYPE
SYNTAX OCTET STRING
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RCI10 hardware serial number"
::= { system 12 }
swVersion OBJECT-TYPE
SYNTAX OCTET STRING
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RCI10 software version"
::= { system 13 }
systemName OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (1..100))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"RCI10 System Name"
::= { system 14 }
systemContact OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (1..100))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Name of the person which is responsible for the system"
::= { system 15 }
systemLocation OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (1..100))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Location of this RCI10"
::= { system 16 }
reboot OBJECT-TYPE
SYNTAX Integer32 (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Write 1 to this value will cause a reboot of the RCI10."
::= { system 50 }
sumCurrentA OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current of the whole feed in milliampere"
::= { feedA 1 }
sumCurrentB OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current of the whole feed in milliampere"
::= { feedB 1 }
switchAllFuses OBJECT-TYPE
SYNTAX Integer32 (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets the output state of all fuses: 0=output off, 1=output on"
::= { fuses 20 }
monitorEnabled OBJECT-TYPE
SYNTAX Integer32 (0..1)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"If 1 is returned any automatic feed or fuse monitor is enabled."
::= { fuses 40 }
fusesATable OBJECT-TYPE
SYNTAX SEQUENCE OF FusesAEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
" "
::= { feedA 10 }
fusesAEntry OBJECT-TYPE
SYNTAX FusesAEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
" "
INDEX {indexA}
::= { fusesATable 1 }
FusesAEntry ::= SEQUENCE {
indexA Integer32,
availableA Integer32,
deviceTypeA Integer32,
serialA Integer32,
hwVersionA Integer32,
swVersionA Integer32,
nominalCurrentA Integer32,
errNoSysParA Integer32,
errCrcParamA Integer32,
errCrcProgA Integer32,
errIntMemA Integer32,
errControllerA Integer32,
errWatchdogA Integer32,
voltageA Integer32,
temperatureA Integer32,
loadOutputA Integer32,
statusShortA Integer32,
statusOverloadA Integer32,
statusUvltA Integer32,
statusOvltA Integer32,
statusOtmpA Integer32,
statusNoVccA Integer32,
loadA Integer32,
labelA OCTET STRING,
nominalVoltageA OCTET STRING,
multiEsxA Integer32
}
indexA OBJECT-TYPE
SYNTAX Integer32 (1..20)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Fuse index"
::= { fusesAEntry 1 }
availableA OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status of fuse: 0=no fuse, 1=fuse available"
::= { fusesAEntry 2 }
deviceTypeA OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Type number of the fuse"
::= { fusesAEntry 3 }
serialA OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial number of the fuse"
::= { fusesAEntry 4 }
hwVersionA OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Hardware version number of the fuse"
::= { fusesAEntry 5 }
swVersionA OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Software version number of the fuse"
::= { fusesAEntry 6 }
nominalCurrentA OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Nominal current of the fuse in milliampere"
::= { fusesAEntry 7 }
errNoSysParA OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"No systemparameter available fault: 0=no fault, 1=fault"
::= { fusesAEntry 8 }
errCrcParamA OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Parameter CRC fault: 0=no fault, 1=fault"
::= { fusesAEntry 9 }
errCrcProgA OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Program memory CRC fault: 0=no fault, 1=fault"
::= { fusesAEntry 10 }
errIntMemA OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Internal memory fault: 0=no fault, 1=fault"
::= { fusesAEntry 11 }
errControllerA OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Controller fault: 0=no fault, 1=fault"
::= { fusesAEntry 12 }
errWatchdogA OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Watchdog reset fault: 0=no fault, 1=fault"
::= { fusesAEntry 13 }
voltageA OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Power supply voltage in millivolt"
::= { fusesAEntry 14 }
temperatureA OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current temperature of the fuse in millivolt"
::= { fusesAEntry 15 }
loadOutputA OBJECT-TYPE
SYNTAX Integer32 (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Output status of the fuse: 0=output off, 1=output on"
::= { fusesAEntry 16 }
statusShortA OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Short is detected by this fuse: 0=no fault, 1=fault"
::= { fusesAEntry 17 }
statusOverloadA OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Overload status: 0=no overload, 1=overload"
::= { fusesAEntry 18 }
statusUvltA OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Undervoltage status: 0=no undervoltage, 1=undervoltage"
::= { fusesAEntry 19 }
statusOvltA OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Overvoltage status: 0=no overvoltage, 1=overvoltage"
::= { fusesAEntry 20 }
statusOtmpA OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Overtemperature status: 0=no overtemperature, 1=overtemperature"
::= { fusesAEntry 21 }
statusNoVccA OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"No VCC status: 0=no VCC, 1=VCC ok"
::= { fusesAEntry 22 }
loadA OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current in milliampere which flows throuth the fuse"
::= { fusesAEntry 23 }
labelA OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Label given for this fuse"
::= { fusesAEntry 24 }
nominalVoltageA OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..9))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Polarity and nominal voltage of the fuse in volt. E.g.: -48"
::= { fusesAEntry 25 }
multiEsxA OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"MultiEsx: Fuses are connected in parallel to protect higher nominal loads: 0=not connected, 1=connected to a lower slot index, 2=connected as first"
::= { fusesAEntry 26 }
fusesBTable OBJECT-TYPE
SYNTAX SEQUENCE OF FusesBEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
" "
::= { feedB 10 }
fusesBEntry OBJECT-TYPE
SYNTAX FusesBEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
" "
INDEX {indexB}
::= { fusesBTable 1 }
FusesBEntry ::= SEQUENCE {
indexB Integer32,
availableB Integer32,
deviceTypeB Integer32,
serialB Integer32,
hwVersionB Integer32,
swVersionB Integer32,
nominalCurrentB Integer32,
errNoSysParB Integer32,
errCrcParamB Integer32,
errCrcProgB Integer32,
errIntMemB Integer32,
errControllerB Integer32,
errWatchdogB Integer32,
voltageB Integer32,
temperatureB Integer32,
loadOutputB Integer32,
statusShortB Integer32,
statusOverloadB Integer32,
statusUvltB Integer32,
statusOvltB Integer32,
statusOtmpB Integer32,
statusNoVccB Integer32,
loadB Integer32,
labelB OCTET STRING
nominalVoltageB OCTET STRING,
multiEsxB Integer32
}
indexB OBJECT-TYPE
SYNTAX Integer32 (11..20)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Fuse index"
::= { fusesBEntry 1 }
availableB OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status of fuse: 0=no fuse, 1=fuse available"
::= { fusesBEntry 2 }
deviceTypeB OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Type number of the fuse"
::= { fusesBEntry 3 }
serialB OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial number of the fuse"
::= { fusesBEntry 4 }
hwVersionB OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Hardware version number of the fuse"
::= { fusesBEntry 5 }
swVersionB OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Software version number of the fuse"
::= { fusesBEntry 6 }
nominalCurrentB OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Nominal current of the fuse in milliampere"
::= { fusesBEntry 7 }
errNoSysParB OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"No systemparameter available fault: 0=no fault, 1=fault"
::= { fusesBEntry 8 }
errCrcParamB OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Parameter CRC fault: 0=no fault, 1=fault"
::= { fusesBEntry 9 }
errCrcProgB OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Program memory CRC fault: 0=no fault, 1=fault"
::= { fusesBEntry 10 }
errIntMemB OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Internal memory fault: 0=no fault, 1=fault"
::= { fusesBEntry 11 }
errControllerB OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Controller fault: 0=no fault, 1=fault"
::= { fusesBEntry 12 }
errWatchdogB OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Watchdog reset fault: 0=no fault, 1=fault"
::= { fusesBEntry 13 }
voltageB OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Power supply voltage in millivolt"
::= { fusesBEntry 14 }
temperatureB OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current temperature of the fuse in millivolt"
::= { fusesBEntry 15 }
loadOutputB OBJECT-TYPE
SYNTAX Integer32 (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Output status of the fuse: 0=output off, 1=output on"
::= { fusesBEntry 16 }
statusShortB OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Short is detected by this fuse: 0=no fault, 1=fault"
::= { fusesBEntry 17 }
statusOverloadB OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Overload status: 0=no overload, 1=overload"
::= { fusesBEntry 18 }
statusUvltB OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Undervoltage status: 0=no undervoltage, 1=undervoltage"
::= { fusesBEntry 19 }
statusOvltB OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Overvoltage status: 0=no overvoltage, 1=overvoltage"
::= { fusesBEntry 20 }
statusOtmpB OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Overtemperature status: 0=no overtemperature, 1=overtemperature"
::= { fusesBEntry 21 }
statusNoVccB OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"No VCC status: 0=no VCC, 1=VCC ok"
::= { fusesBEntry 22 }
loadB OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Load current in milliampere which flows throuth the fuse"
::= { fusesBEntry 23 }
labelB OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Label given for this fuse"
::= { fusesBEntry 24 }
nominalVoltageB OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..9))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Polarity and nominal voltage of the fuse in volt. E.g.: -48"
::= { fusesBEntry 25 }
multiEsxB OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"MultiEsx: Fuses are connected in parallel to protect higher nominal loads: 0=not connected, 1=connected to a lower slot index, 2=connected as first"
::= { fusesBEntry 26 }
-- externalAlarms:
-- 1.3.6.1.4.1.44086.4.1.20.1.1
eaATable OBJECT-TYPE
SYNTAX SEQUENCE OF EaAEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
" "
::= { eaFeedA 1 }
eaAEntry OBJECT-TYPE
SYNTAX EaAEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
" "
INDEX {eaIndexA}
::= { eaATable 1 }
EaAEntry ::= SEQUENCE {
eaIndexA Integer32,
eaAvailableA Integer32,
eaDeviceTypeA Integer32,
eaSerialA Integer32,
eaHwVersionA Integer32,
eaSwVersionA Integer32,
eaOutput1A Integer32,
eaOutput2A Integer32,
eaInput1A Integer32,
eaInput2A Integer32,
eaInput3A Integer32,
eaInput4A Integer32,
eaInput5A Integer32,
eaInput6A Integer32,
eaInput7A Integer32,
eaInput8A Integer32,
eaAnalogInputA Integer32,
eaLabelOutput1A OCTET STRING,
eaLabelOutput2A OCTET STRING,
eaLabelInput1A OCTET STRING,
eaLabelInput2A OCTET STRING,
eaLabelInput3A OCTET STRING,
eaLabelInput4A OCTET STRING,
eaLabelInput5A OCTET STRING,
eaLabelInput6A OCTET STRING,
eaLabelInput7A OCTET STRING,
eaLabelInput8A OCTET STRING,
eaLabelAnalogInputA OCTET STRING,
eaSignallingGroupOutput1A OCTET STRING,
eaSignallingActiveOutput1A Integer32,
eaSignallingGroupOutput2A OCTET STRING,
eaSignallingActiveOutput2A Integer32,
eaLogicFunctionOutput1A OCTET STRING,
eaLogicFunctionActiveOutput1A Integer32,
eaLogicFunctionOutput2A OCTET STRING,
eaLogicFunctionActiveOutput2A Integer32
}
eaIndexA OBJECT-TYPE
SYNTAX Integer32 (1..20)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Device index (slot number)"
::= { eaAEntry 1 }
eaAvailableA OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status of the device: 0=no EAI device, 1=EEAI device available"
::= { eaAEntry 2 }
eaDeviceTypeA OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Type number of the device"
::= { eaAEntry 3 }
eaSerialA OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial number of the device"
::= { eaAEntry 4 }
eaHwVersionA OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Hardware version number of the device"
::= { eaAEntry 5 }
eaSwVersionA OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Software version number of the device"
::= { eaAEntry 6 }
eaOutput1A OBJECT-TYPE
SYNTAX Integer32 (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Status of the relay output1: 0=output off, 1=output on (contact to normaly close is closed)"
::= { eaAEntry 7 }
eaOutput2A OBJECT-TYPE
SYNTAX Integer32 (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Status of the relay output2: 0=output off, 1=output on (contact to normaly close is closed)"
::= { eaAEntry 8 }
eaInput1A OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status digital input1: 0=low, 1=high"
::= { eaAEntry 9 }
eaInput2A OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status digital input2: 0=low, 1=high"
::= { eaAEntry 10 }
eaInput3A OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status digital input3: 0=low, 1=high"
::= { eaAEntry 11 }
eaInput4A OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status digital input4: 0=low, 1=high"
::= { eaAEntry 12 }
eaInput5A OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status digital input5: 0=low, 1=high"
::= { eaAEntry 13 }
eaInput6A OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status digital input6: 0=low, 1=high"
::= { eaAEntry 14 }
eaInput7A OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status digital input7: 0=low, 1=high"
::= { eaAEntry 15 }
eaInput8A OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status digital input8: 0=low, 1=high"
::= { eaAEntry 16 }
eaAnalogInputA OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Analog current input in mA"
::= { eaAEntry 17 }
eaLabelOutput1A OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Label for output1 of this EAI device"
::= { eaAEntry 18 }
eaLabelOutput2A OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Label for output2 of this EAI device"
::= { eaAEntry 19 }
eaLabelInput1A OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Label for input1 of this EAI device"
::= { eaAEntry 20 }
eaLabelInput2A OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Label for input2 of this EAI device"
::= { eaAEntry 21 }
eaLabelInput3A OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Label for input3 of this EAI device"
::= { eaAEntry 22 }
eaLabelInput4A OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Label for input4 of this EAI device"
::= { eaAEntry 23 }
eaLabelInput5A OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Label for input5 of this EAI device"
::= { eaAEntry 24 }
eaLabelInput6A OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Label for input6 of this EAI device"
::= { eaAEntry 25 }
eaLabelInput7A OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Label for input7 of this EAI device"
::= { eaAEntry 26 }
eaLabelInput8A OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Label for input8 of this EAI device"
::= { eaAEntry 27 }
eaLabelAnalogInputA OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Label for the analog input of this EAI device"
::= { eaAEntry 28 }
eaSignallingGroupOutput1A OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Signalling function for output1.
Syntax: 20 (for 20 slots) characters '0' or '1'.
'0'= signalling not active for this slot; '0'= signalling is active for this slot"
::= { eaAEntry 29 }
eaSignallingActiveOutput1A OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status of signalling function for output1: 0=not active, 1=active"
::= { eaAEntry 30 }
eaSignallingGroupOutput2A OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Signalling function for output2.
Syntax: 20 (for 20 slots) characters '0' or '1'.
'0'= signalling not active for this slot; '0'= signalling is active for this slot"
::= { eaAEntry 31 }
eaSignallingActiveOutput2A OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status of signalling function for output2: 0=not active, 1=active"
::= { eaAEntry 32 }
eaLogicFunctionOutput1A OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..40))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Logic function for output1.
Length: 40 characters. Syntax: Logic connections '*'=AND, '+'=OR, '!'=Negation;
Signals: EAI digital input 'eai<slot address>in<input number>', ESX state 'esx<slot address><state>'"
::= { eaAEntry 33 }
eaLogicFunctionActiveOutput1A OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status of logic function for output1: 0=not active, 1=active"
::= { eaAEntry 34 }
eaLogicFunctionOutput2A OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..40))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Logic function for output2.
Length: 40 characters. Syntax: Logic connections '*'=AND, '+'=OR, '!'=Negation;
Signals: EAI digital input 'eai<slot address>in<input number>', ESX state 'esx<slot address><state>'"
::= { eaAEntry 35 }
eaLogicFunctionActiveOutput2A OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status of logic function for output2: 0=not active, 1=active"
::= { eaAEntry 36 }
-- 1.3.6.1.4.1.44086.4.1.20.2.1
eaBTable OBJECT-TYPE
SYNTAX SEQUENCE OF EaBEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
" "
::= { eaFeedB 1 }
eaBEntry OBJECT-TYPE
SYNTAX EaBEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
" "
INDEX {eaIndexB}
::= { eaBTable 1 }
EaBEntry ::= SEQUENCE {
eaIndexB Integer32,
eaAvailableB Integer32,
eaDeviceTypeB Integer32,
eaSerialB Integer32,
eaHwVersionB Integer32,
eaSwVersionB Integer32,
eaOutput1B Integer32,
eaOutput2B Integer32,
eaInput1B Integer32,
eaInput2B Integer32,
eaInput3B Integer32,
eaInput4B Integer32,
eaInput5B Integer32,
eaInput6B Integer32,
eaInput7B Integer32,
eaInput8B Integer32,
eaAnalogInputB Integer32,
eaLabelOutput1B OCTET STRING,
eaLabelOutput2B OCTET STRING,
eaLabelInput1B OCTET STRING,
eaLabelInput2B OCTET STRING,
eaLabelInput3B OCTET STRING,
eaLabelInput4B OCTET STRING,
eaLabelInput5B OCTET STRING,
eaLabelInput6B OCTET STRING,
eaLabelInput7B OCTET STRING,
eaLabelInput8B OCTET STRING,
eaLabelAnalogInputB OCTET STRING,
eaSignallingGroupOutput1B OCTET STRING,
eaSignallingActiveOutput1B Integer32,
eaSignallingGroupOutput2B OCTET STRING,
eaSignallingActiveOutput2B Integer32,
eaLogicFunctionOutput1B OCTET STRING,
eaLogicFunctionActiveOutput1B Integer32,
eaLogicFunctionOutput2B OCTET STRING,
eaLogicFunctionActiveOutput2B Integer32
}
eaIndexB OBJECT-TYPE
SYNTAX Integer32 (1..20)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Device index (slot number)"
::= { eaBEntry 1 }
eaAvailableB OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status of the device: 0=no EAI device, 1=EEAI device available"
::= { eaBEntry 2 }
eaDeviceTypeB OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Type number of the device"
::= { eaBEntry 3 }
eaSerialB OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial number of the device"
::= { eaBEntry 4 }
eaHwVersionB OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Hardware version number of the device"
::= { eaBEntry 5 }
eaSwVersionB OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Software version number of the device"
::= { eaBEntry 6 }
eaOutput1B OBJECT-TYPE
SYNTAX Integer32 (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Status of the relay output1: 0=output off, 1=output on (contact to normaly close is closed)"
::= { eaBEntry 7 }
eaOutput2B OBJECT-TYPE
SYNTAX Integer32 (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Status of the relay output2: 0=output off, 1=output on (contact to normaly close is closed)"
::= { eaBEntry 8 }
eaInput1B OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status digital input1: 0=low, 1=high"
::= { eaBEntry 9 }
eaInput2B OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status digital input2: 0=low, 1=high"
::= { eaBEntry 10 }
eaInput3B OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status digital input3: 0=low, 1=high"
::= { eaBEntry 11 }
eaInput4B OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status digital input4: 0=low, 1=high"
::= { eaBEntry 12 }
eaInput5B OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status digital input5: 0=low, 1=high"
::= { eaBEntry 13 }
eaInput6B OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status digital input6: 0=low, 1=high"
::= { eaBEntry 14 }
eaInput7B OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status digital input7: 0=low, 1=high"
::= { eaBEntry 15 }
eaInput8B OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status digital input8: 0=low, 1=high"
::= { eaBEntry 16 }
eaAnalogInputB OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Analog current input in mA"
::= { eaBEntry 17 }
eaLabelOutput1B OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Label for output1 of this EAI device"
::= { eaBEntry 18 }
eaLabelOutput2B OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Label for output2 of this EAI device"
::= { eaBEntry 19 }
eaLabelInput1B OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Label for input1 of this EAI device"
::= { eaBEntry 20 }
eaLabelInput2B OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Label for input2 of this EAI device"
::= { eaBEntry 21 }
eaLabelInput3B OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Label for input3 of this EAI device"
::= { eaBEntry 22 }
eaLabelInput4B OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Label for input4 of this EAI device"
::= { eaBEntry 23 }
eaLabelInput5B OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Label for input5 of this EAI device"
::= { eaBEntry 24 }
eaLabelInput6B OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Label for input6 of this EAI device"
::= { eaBEntry 25 }
eaLabelInput7B OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Label for input7 of this EAI device"
::= { eaBEntry 26 }
eaLabelInput8B OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Label for input8 of this EAI device"
::= { eaBEntry 27 }
eaLabelAnalogInputB OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Label for the analog input of this EAI device"
::= { eaBEntry 28 }
eaSignallingGroupOutput1B OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Signalling function for output1.
Syntax: 20 (for 20 slots) characters '0' or '1'.
'0'= signalling not active for this slot; '0'= signalling is active for this slot"
::= { eaBEntry 29 }
eaSignallingActiveOutput1B OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status of signalling function for output1: 0=not active, 1=active"
::= { eaBEntry 30 }
eaSignallingGroupOutput2B OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Signalling function for output2.
Syntax: 20 (for 20 slots) characters '0' or '1'.
'0'= signalling not active for this slot; '0'= signalling is active for this slot"
::= { eaBEntry 31 }
eaSignallingActiveOutput2B OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status of signalling function for output2: 0=not active, 1=active"
::= { eaBEntry 32 }
eaLogicFunctionOutput1B OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..40))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Logic function for output1.
Length: 40 characters. Syntax: Logic connections '*'=AND, '+'=OR, '!'=Negation;
Signals: EAI digital input 'eai<slot address>in<input number>', ESX state 'esx<slot address><state>'"
::= { eaBEntry 33 }
eaLogicFunctionActiveOutput1B OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status of logic function for output1: 0=not active, 1=active"
::= { eaBEntry 34 }
eaLogicFunctionOutput2B OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..40))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Logic function for output2.
Length: 40 characters. Syntax: Logic connections '*'=AND, '+'=OR, '!'=Negation;
Signals: EAI digital input 'eai<slot address>in<input number>', ESX state 'esx<slot address><state>'"
::= { eaBEntry 35 }
eaLogicFunctionActiveOutput2B OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status of logic function for output2: 0=not active, 1=active"
::= { eaBEntry 36 }
-- Traps object types
resetReason OBJECT-TYPE
SYNTAX OCTET STRING
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Holds a human readable text which gives the reason for reset. Possible
values are coldstart, warmstart or watchdog"
::= { systemObjects 1 }
failureReason OBJECT-TYPE
SYNTAX OCTET STRING
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Holds a human readable text which gives the reason for system failure."
::= { systemObjects 2 }
fuseNr OBJECT-TYPE
SYNTAX OCTET STRING
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Gives the number of a fuse"
::= { fusesObjects 1}
fuseLabel OBJECT-TYPE
SYNTAX OCTET STRING
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Gives the label of a fuse"
::= { fusesObjects 2}
fuseOutputState OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Defines the output state of a fuse. 0 = Output off, 1 = Output on"
::= { fusesObjects 5}
fuseErrorRegister OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Defines the error register data type."
::= { fusesObjects 10}
fuseStatusShortCircuit OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Status register flag for short circuit"
::= { fusesObjects 20}
fuseStatusOverload OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Status register flag for overload"
::= { fusesObjects 21}
fuseStatusUndervoltage OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Status register flag for undervoltage"
::= { fusesObjects 22}
fuseStatusOvervoltage OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Status register flag for overvoltage"
::= { fusesObjects 23}
fuseStatusOvertemperature OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Status register flag for overtemperature"
::= { fusesObjects 24}
fuseStatusNoPowerSupply OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Status register flag for no power supply"
::= { fusesObjects 25}
fuseOldNominalCurrent OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The nominal current of the fuse which was located in this slot before."
::= { fusesObjects 30}
fuseNewNominalCurrent OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The nominal current of the new fuse"
::= { fusesObjects 31}
-- Trap object types for external alarm interface
eaSlotNr OBJECT-TYPE
SYNTAX OCTET STRING
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Gives the slot number of a external alarm device"
::= { externalAlarmObjects 1}
eaInputStates OBJECT-TYPE
SYNTAX OCTET STRING
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Gives the input states of the external alarm device. [Left -> right: output 1 .. output n]"
::= { externalAlarmObjects 2}
eaOutputStates OBJECT-TYPE
SYNTAX OCTET STRING
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Gives the output states of the external alarm device. [Left -> right: output 1 .. output n]"
::= { externalAlarmObjects 3}
eaFailureMsg OBJECT-TYPE
SYNTAX OCTET STRING
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Gives a human readable text for a external alarm device failure."
::= { externalAlarmObjects 4}
eaMsg OBJECT-TYPE
SYNTAX OCTET STRING
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Gives a human readable text for a external alarm device notification."
::= { externalAlarmObjects 5}
eaInputNr OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Gives the input Nr. of a external alarm device input. [1-8]"
::= { externalAlarmObjects 6}
eaInputLabel OBJECT-TYPE
SYNTAX OCTET STRING
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Gives the label of a external alarm device input."
::= { externalAlarmObjects 7}
eaInputState OBJECT-TYPE
SYNTAX OCTET STRING
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Gives the state of an external alarm device input. [raise/clear]"
::= { externalAlarmObjects 8}
eaOutputNr OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Gives the output Nr. of a external alarm device output. [1-2]"
::= { externalAlarmObjects 9}
eaOutputLabel OBJECT-TYPE
SYNTAX OCTET STRING
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Gives the label of a external alarm device output."
::= { externalAlarmObjects 10}
eaOutputState OBJECT-TYPE
SYNTAX OCTET STRING
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Gives the state of an external alarm device output. [raise/clear]"
::= { externalAlarmObjects 11}
-- Traps
powerUp NOTIFICATION-TYPE
OBJECTS { resetReason }
STATUS current
DESCRIPTION
"This notification is sent after a successful power up"
::= { systemNotifications 1 }
systemFailure NOTIFICATION-TYPE
OBJECTS { failureReason }
STATUS current
DESCRIPTION
"If the system enters failure mode this Trap is sent"
::= { systemNotifications 2 }
fuseNew NOTIFICATION-TYPE
OBJECTS { fuseNr, fuseLabel }
STATUS current
DESCRIPTION
"This Trap is sent if a new fuse was found"
::= { fusesNotifications 1 }
fuseGone NOTIFICATION-TYPE
OBJECTS { fuseNr, fuseLabel }
STATUS current
DESCRIPTION
"Informs that a fuse which responds onto requests in the past does no longer
respond."
::= { fusesNotifications 2 }
fuseWrong NOTIFICATION-TYPE
OBJECTS { fuseNr, fuseLabel, fuseNewNominalCurrent, fuseOldNominalCurrent }
STATUS current
DESCRIPTION
"A recently added fuse has a different nominal current as the fuse in the same
slot had before."
::= { fusesNotifications 3 }
fuseOutputStateChanged NOTIFICATION-TYPE
OBJECTS { fuseNr, fuseLabel, fuseOutputState }
STATUS current
DESCRIPTION
"Informs that the output state of a fuse had changed his status."
::= { fusesNotifications 4 }
fuseFailure NOTIFICATION-TYPE
OBJECTS { fuseNr, fuseLabel, fuseStatusShortCircuit, fuseStatusOverload, fuseStatusUndervoltage, fuseStatusOvervoltage, fuseStatusOvertemperature, fuseStatusNoPowerSupply, fuseErrorRegister }
STATUS current
DESCRIPTION
"If any status or error flag changes, this trap is sent."
::= { fusesNotifications 5 }
-- Traps for external alarm interface
eaNew NOTIFICATION-TYPE
OBJECTS { eaSlotNr }
STATUS current
DESCRIPTION
"This Trap is sent if a new external alarm device was found"
::= { externalAlarmNotifications 1 }
eaGone NOTIFICATION-TYPE
OBJECTS { eaSlotNr }
STATUS current
DESCRIPTION
"Informs that a external alarm device, which responded onto requests in the past, does no longer
respond."
::= { externalAlarmNotifications 2 }
eaActiveFunctionWarning NOTIFICATION-TYPE
OBJECTS { eaSlotNr, eaMsg }
STATUS current
DESCRIPTION
"Informs that a logic- or signalling function is configured for a new plugged or pulled external alarm device."
::= { externalAlarmNotifications 3 }
eaInternalError NOTIFICATION-TYPE
OBJECTS { eaSlotNr, eaFailureMsg }
STATUS current
DESCRIPTION
"Informs that a internal error of external alarm device occured"
::= { externalAlarmNotifications 4 }
eaMasterWasNotAvailable NOTIFICATION-TYPE
OBJECTS { eaMsg }
STATUS current
DESCRIPTION
"Informs (one time) that a external alarm device detected, that the master device was not available for some time."
::= { externalAlarmNotifications 5 }
eaInputChanged NOTIFICATION-TYPE
OBJECTS { eaSlotNr, eaInputStates }
STATUS current
DESCRIPTION
"Informs that a external alarm device input has changed its state; Summary for all inputs of one external alarm device."
::= { externalAlarmNotifications 6 }
eaOutputChanged NOTIFICATION-TYPE
OBJECTS { eaSlotNr, eaOutputStates }
STATUS current
DESCRIPTION
"Informs that a external alarm device output has changed its state; Summary for all outputs of one external alarm device."
::= { externalAlarmNotifications 7 }
eaSingleInputChanged NOTIFICATION-TYPE
OBJECTS { eaSlotNr, eaInputNr, eaInputLabel, eaInputState }
STATUS current
DESCRIPTION
"Informs that a external alarm device input has changed its state; Is sent for every changed input.
If input changed high: 'raise'; If input changed low: 'clear'"
::= { externalAlarmNotifications 8 }
eaSingleOutputChanged NOTIFICATION-TYPE
OBJECTS { eaSlotNr, eaOutputNr, eaOutputLabel, eaOutputState }
STATUS current
DESCRIPTION
"Informs that a external alarm device output has changed its state; Is sent for every changed output.
If output changed high: 'raise'; If output changed low: 'clear'"
::= { externalAlarmNotifications 9 }
END