-- defines STS.mib for XPort-SNMP agent
|
||
--
|
||
-- Mib is used for STS Units
|
||
--
|
||
-- Eltek Valere Industrial GmbH - Enterprise 16640
|
||
-- renamed from CONVERTRONIC OIDs - Enterprise 16640
|
||
-- Version: 1.01
|
||
-- Date: 08 January, 2008
|
||
-- Developed By: Michael Schulz
|
||
-- Software Engineer
|
||
-- Eltek Valere Industrial GmbH
|
||
--
|
||
-- Version: 1.02
|
||
-- Date: 18 June, 2009
|
||
-- Developed By: Christian Fisch
|
||
-- Software Engineer
|
||
-- Eltek Valere Industrial GmbH
|
||
--
|
||
-- Update 18.06.2009:
|
||
-- Fix: trap definition string "" instead of "
|
||
--
|
||
--
|
||
-- Update 25.09.2008:
|
||
-- Change inv_OutVoltage to inv_InputVoltage
|
||
-- add text "Bit_" for direct info, this is a Bit-Information
|
||
-- inv_Bit_ShortCircuit, inv_Bit_OutputVoltage, inv_Bit_InputVoltLow, inv_Bit_InputVoltHigh,
|
||
-- inv_Bit_OutputVoltLow, inv_Bit_OutputVoltHigh, inv_Bit_OutputCurrHigh, inv_Bit_RemoteOff
|
||
-- inv_Bit_CentralAlarm
|
||
--
|
||
-- Update 07.10.2008:
|
||
-- Change trap-descriptions: Modification for HP OpenView
|
||
--
|
||
-- Version: 1.03
|
||
-- Date: 06 Jan., 2010
|
||
-- Developed By: Dirk Meise-Reckefuss
|
||
-- Software Engineer
|
||
-- Eltek Valere Industrial GmbH
|
||
--
|
||
-- Copyright (c) 2010 Eltek Valere Industrial GmbH.
|
||
--
|
||
|
||
STS_SEQUENZ-MIB DEFINITIONS ::= BEGIN
|
||
|
||
|
||
IMPORTS
|
||
enterprises, IpAddress, Counter, TimeTicks FROM RFC1155-SMI
|
||
OBJECT-TYPE FROM RFC-1212
|
||
TRAP-TYPE FROM RFC-1215
|
||
DisplayString FROM RFC1213-MIB;
|
||
|
||
|
||
convertronic OBJECT IDENTIFIER ::= { enterprises 16460 }
|
||
|
||
sts_system MODULE-IDENTITY
|
||
LAST-UPDATED "201001061200Z" -- Jan. 06 2010 12:00:00 EST
|
||
|
||
ORGANIZATION "Eltek Valere Industrial GmbH"
|
||
CONTACT-INFO
|
||
"Michael Schulz
|
||
|
||
Eltek Valere Industrial GmbH
|
||
Im Obrock 33
|
||
D-32278 Kirchlengern
|
||
|
||
Tel: +49 5223 7641 450
|
||
Fax: +49 5223 7641 222
|
||
|
||
E-mail: michael.schulz@eltekvalere.com"
|
||
DESCRIPTION
|
||
"The MIB module to describe all object of STS Unit "
|
||
|
||
-- sts_system OBJECT IDENTIFIER
|
||
::= { convertronic 4 }
|
||
|
||
measureValues OBJECT IDENTIFIER ::= { sts_system 1 }
|
||
settings OBJECT IDENTIFIER ::= { sts_system 2 }
|
||
extendedSettings OBJECT IDENTIFIER ::= { sts_system 3 }
|
||
tables OBJECT IDENTIFIER ::= { sts_system 4 }
|
||
traps OBJECT IDENTIFIER ::= { sts_system 5 }
|
||
|
||
sts_measureValues OBJECT IDENTIFIER ::= { measureValues 1 }
|
||
inverter_measureValues OBJECT IDENTIFIER ::= { measureValues 2 }
|
||
|
||
networkSettings OBJECT IDENTIFIER ::= { settings 1 }
|
||
unitSettings OBJECT IDENTIFIER ::= { settings 2 }
|
||
|
||
netSyncronisationSet OBJECT IDENTIFIER ::= { extendedSettings 1 }
|
||
adjustValues OBJECT IDENTIFIER ::= { extendedSettings 2 }
|
||
|
||
baseSettings OBJECT IDENTIFIER ::= { networkSettings 1 }
|
||
serviceSettings OBJECT IDENTIFIER ::= { networkSettings 2 }
|
||
|
||
basicSettings OBJECT IDENTIFIER ::= { unitSettings 1 }
|
||
advancedSettings OBJECT IDENTIFIER ::= { unitSettings 2 }
|
||
advancedSettings2 OBJECT IDENTIFIER ::= { unitSettings 3 }
|
||
|
||
|
||
-- ****************************************
|
||
-- ****************************************
|
||
-- ****************************************
|
||
|
||
sVal_UN OBJECT-TYPE
|
||
SYNTAX INTEGER(0..65535)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Mains voltage (V), Value: 230(230V)"
|
||
::= { sts_measureValues 1 }
|
||
|
||
sVal_FreqNetz OBJECT-TYPE
|
||
SYNTAX INTEGER(0..65535)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Mains frequency (Hz), Value: 50(50Hz)"
|
||
::= { sts_measureValues 2 }
|
||
|
||
sVal_UWR OBJECT-TYPE
|
||
SYNTAX INTEGER(0..65535)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Inverter voltage (V), Value: 230(230V)"
|
||
::= { sts_measureValues 3 }
|
||
|
||
sVal_FreqWR OBJECT-TYPE
|
||
SYNTAX INTEGER(0..65535)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Inverter frequency (Hz), Value: 50(50Hz)"
|
||
::= { sts_measureValues 4 }
|
||
|
||
sVal_UDC OBJECT-TYPE
|
||
SYNTAX INTEGER(0..65535)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Battery voltage (V), Value: 120(12V)"
|
||
::= { sts_measureValues 5 }
|
||
|
||
sVal_U10 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..65535)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "STS Output Voltage (V), Value: 230(230V)"
|
||
::= { sts_measureValues 6 }
|
||
|
||
sVal_IO1 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..65535)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "STS Output current (A), Value: 15(15A)"
|
||
::= { sts_measureValues 7 }
|
||
|
||
sVal_P OBJECT-TYPE
|
||
SYNTAX INTEGER(0..65535)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "STS active power (W), Value: 2105(2105W)"
|
||
::= { sts_measureValues 8 }
|
||
|
||
sVal_S OBJECT-TYPE
|
||
SYNTAX INTEGER(0..65535)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "STS apparent power (VA), Value: 495(495VA)"
|
||
::= { sts_measureValues 9 }
|
||
|
||
sVal_FAN1 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..65535)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Fan 1 speed (rpm), Value: 4200(4200rpm)"
|
||
::= { sts_measureValues 10 }
|
||
|
||
sVal_FAN2 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..65535)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Fan 2 speed (rpm), Value: 3800(3800rpm)"
|
||
::= { sts_measureValues 11 }
|
||
|
||
sVal_TK OBJECT-TYPE
|
||
SYNTAX INTEGER(0..65535)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "STS temperature (<28>C), Value: 301(30,1<>C)"
|
||
::= { sts_measureValues 12 }
|
||
|
||
sVal_IO2 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..65535)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "STS output current 2 (A), Value: 18(18A)"
|
||
::= { sts_measureValues 13 }
|
||
|
||
sVal_IDC OBJECT-TYPE
|
||
SYNTAX INTEGER(0..65535)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "battery output current (A), Value: 24(24A)"
|
||
::= { sts_measureValues 14 }
|
||
|
||
-- ****************************************
|
||
-- ****************************************
|
||
-- ****************************************
|
||
bETHSpeed OBJECT-TYPE
|
||
SYNTAX INTEGER(0..4)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Communication speed setting:
|
||
Value:
|
||
0= autonegotation
|
||
1= 10Mb Halfduplex
|
||
2= 10Mb Fullduplex
|
||
3= 100Mb Halfduplex
|
||
4= 100Mb Fullduplex"
|
||
::= { baseSettings 1 }
|
||
|
||
bLocalIP OBJECT-TYPE
|
||
SYNTAX IpAddress
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "IP-Adress of the Unit,
|
||
Value: xxx.xxx.xxx.xxx"
|
||
::= { baseSettings 2 }
|
||
|
||
bSubnetMask OBJECT-TYPE
|
||
SYNTAX IpAddress
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Used Subnetmask of the Unit,
|
||
Value: xxx.xxx.xxx.xxx"
|
||
::= { baseSettings 3 }
|
||
|
||
bGateway OBJECT-TYPE
|
||
SYNTAX IpAddress
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "IP of the used Gateway,
|
||
Value: xxx.xxx.xxx.xxx"
|
||
::= { baseSettings 4 }
|
||
|
||
bDNSServer OBJECT-TYPE
|
||
SYNTAX IpAddress
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "IP of the used Domain Name Service Server,
|
||
Value: xxx.xxx.xxx.xxx"
|
||
::= { baseSettings 5 }
|
||
|
||
bDHCPServer OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..16))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Name of the DHCP-Server to use,
|
||
Value: max. 16 char."
|
||
::= { baseSettings 6 }
|
||
|
||
bFixedIP_OnOff OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Use Fixed connection settings,
|
||
Value:
|
||
1= Use IP set with LocalIP
|
||
0= Use automatic IP-Configuration"
|
||
::= { baseSettings 7 }
|
||
|
||
bDefaultIP_OnOff OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Usue Fix IP,
|
||
Value:
|
||
0= off
|
||
1= Use IP 192.168.0.10"
|
||
::= { baseSettings 8 }
|
||
|
||
bDHCP_OnOff OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "
|
||
Value:
|
||
0= off
|
||
1= Use DHCP for automatic Network configuration"
|
||
::= { baseSettings 9 }
|
||
|
||
bBOOTP_OnOff OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "
|
||
Value:
|
||
0= off
|
||
1= Use BOOTP for automatic Network configuration"
|
||
::= { baseSettings 10 }
|
||
|
||
bLocation OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..16))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Location of the seen Unit,
|
||
Value:
|
||
max. 16 char."
|
||
::= { baseSettings 11 }
|
||
|
||
-- ****************************************
|
||
-- ****************************************
|
||
-- ****************************************
|
||
|
||
servSNMP_OnOff OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Use Simple Network Management Protocol,
|
||
Value:
|
||
0= off
|
||
1= on"
|
||
::= { serviceSettings 1 }
|
||
|
||
servTrapReceiver1 OBJECT-TYPE
|
||
SYNTAX IpAddress
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "IP of SNMP-Trapreceiver 1,
|
||
Value:
|
||
xxx.xxx.xxx.xxx"
|
||
::= { serviceSettings 2 }
|
||
|
||
servTrapReceiver2 OBJECT-TYPE
|
||
SYNTAX IpAddress
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "IP of SNMP-Trapreceiver 2,
|
||
Value:
|
||
xxx.xxx.xxx.xxx"
|
||
::= { serviceSettings 3 }
|
||
|
||
servTrapReceiver3 OBJECT-TYPE
|
||
SYNTAX IpAddress
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "IP of SNMP-Trapreceiver 3,
|
||
Value:
|
||
xxx.xxx.xxx.xxx"
|
||
::= { serviceSettings 4 }
|
||
|
||
servTrapReceiver4 OBJECT-TYPE
|
||
SYNTAX IpAddress
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "IP of SNMP-Trapreceiver 4,
|
||
Value:
|
||
xxx.xxx.xxx.xxx"
|
||
::= { serviceSettings 5 }
|
||
|
||
servReadCommunity OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..13))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "SNMP read community,
|
||
Value:
|
||
max. 13 char."
|
||
::= { serviceSettings 6 }
|
||
|
||
servWriteCommunity OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..13))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "SNMP write community,
|
||
Value:
|
||
max. 13 char."
|
||
::= { serviceSettings 7 }
|
||
|
||
servSMTP_OnOff OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Use Simple Mail Transfer Protocol,
|
||
Value:
|
||
0= off
|
||
1= on"
|
||
::= { serviceSettings 8 }
|
||
|
||
servMailServer OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..19))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Ip or Name of the used mailserver,
|
||
Value:
|
||
max. 19 char."
|
||
::= { serviceSettings 9 }
|
||
|
||
servMailUsername OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..10))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Username for the mailserver,
|
||
Value:
|
||
max. 10 char."
|
||
::= { serviceSettings 10 }
|
||
|
||
servMailPassword OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..10))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Password for the mailserver,
|
||
Value:
|
||
max. 10 char."
|
||
::= { serviceSettings 11 }
|
||
|
||
servMailReceiver1 OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..48))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "First receiver e-mail address,
|
||
Value:
|
||
max. 48 char."
|
||
::= { serviceSettings 12 }
|
||
|
||
servMailTrapLevel1 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..3)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Traplevel for first mailreceiver,
|
||
Value:
|
||
0= Off
|
||
...
|
||
3= send maximum Traps"
|
||
::= { serviceSettings 13 }
|
||
|
||
servMailReceiver2 OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..48))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "second receiver e-mail address,
|
||
Value:
|
||
max. 48 char."
|
||
::= { serviceSettings 14 }
|
||
|
||
servMailTrapLevel2 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..3)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Traplevel for second mailreceiver,
|
||
Value:
|
||
0= Off
|
||
...
|
||
3= send maximum Traps"
|
||
::= { serviceSettings 15 }
|
||
|
||
servSNTP_OnOff OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Simple Network Time Protocol,
|
||
Value:
|
||
0= off
|
||
1= on"
|
||
::= { serviceSettings 16 }
|
||
|
||
servSNTPServer1 OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..19))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "IP or name for first SNTP server,
|
||
Value:
|
||
max. 19 char."
|
||
::= { serviceSettings 17 }
|
||
|
||
servSNTPServer2 OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..19))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "IP or name for second SNTP server,
|
||
Value:
|
||
max. 19 char."
|
||
::= { serviceSettings 18 }
|
||
|
||
servTelnet_OnOff OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Configuration over Telnet,
|
||
Value:
|
||
0= off
|
||
1= on"
|
||
::= { serviceSettings 19 }
|
||
|
||
servSyslog_OnOff OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Syslog feature,
|
||
Value:
|
||
0= off
|
||
1= on"
|
||
::= { serviceSettings 20 }
|
||
|
||
-- ****************************************
|
||
-- ****************************************
|
||
-- ****************************************
|
||
|
||
sts_Version OBJECT-TYPE
|
||
SYNTAX INTEGER(0..65535)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "STS Software version,
|
||
Value:
|
||
99(Ver 0.99)"
|
||
::= { basicSettings 1 }
|
||
|
||
sts_Inverter OBJECT-TYPE
|
||
SYNTAX INTEGER(0..15)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "STS count of needed inverter,
|
||
Value:
|
||
0 - 15"
|
||
::= { basicSettings 2 }
|
||
|
||
sts_SigCF_b0 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Central failure signal: Source 1 failure,
|
||
Value:
|
||
0= off
|
||
1= on"
|
||
::= { basicSettings 3 }
|
||
|
||
sts_SigCF_b1 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Central failure signal: Source 2 failure,
|
||
Value:
|
||
0= off
|
||
1= on"
|
||
::= { basicSettings 4 }
|
||
|
||
sts_SigCF_b2 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Central failure signal: Syncronisation error,
|
||
Value:
|
||
0= off
|
||
1= on"
|
||
::= { basicSettings 5 }
|
||
|
||
sts_SigCF_b3 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Central failure signal: Inverter failure,
|
||
Value:
|
||
0= off
|
||
1= on"
|
||
::= { basicSettings 6 }
|
||
|
||
sts_SigCF_b4 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Central failure signal: STS overtemperature,
|
||
Value:
|
||
0= off
|
||
1= on"
|
||
::= { basicSettings 7 }
|
||
|
||
sts_SigCF_b5 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Central failure signal: STS overload,
|
||
Value:
|
||
0= off
|
||
1= on"
|
||
::= { basicSettings 8 }
|
||
|
||
sts_SigCF_b6 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Central failure signal: Inverter overload,
|
||
Value:
|
||
0= off
|
||
1= on"
|
||
::= { basicSettings 9 }
|
||
|
||
sts_SigCF_b7 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Central failure signal: DC voltage low,
|
||
Value:
|
||
0= off
|
||
1= on"
|
||
::= { basicSettings 10 }
|
||
|
||
sts_SigCF_b8 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Central failure signal: DC voltage high,
|
||
Value:
|
||
0= off
|
||
1= on"
|
||
::= { basicSettings 11 }
|
||
|
||
sts_SigCF_b9 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Central failure signal: U batterie< warning,
|
||
Value:
|
||
0= off
|
||
1= on"
|
||
::= { basicSettings 12 }
|
||
|
||
sts_SigCF_b10 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Central failure signal: U batterie> warning,
|
||
Value:
|
||
0= off
|
||
1= on"
|
||
::= { basicSettings 13 }
|
||
|
||
sts_SigCF_b11 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Central failure signal: Fan error,
|
||
Value:
|
||
0= off
|
||
1= on"
|
||
::= { basicSettings 14 }
|
||
|
||
sts_SigCF_b12 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Central failure signal: future use"
|
||
::= { basicSettings 15 }
|
||
|
||
sts_SigCF_b13 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Central failure signal: future use"
|
||
::= { basicSettings 16 }
|
||
|
||
sts_SigCF_b14 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Central failure signal: future use"
|
||
::= { basicSettings 17 }
|
||
|
||
sts_SigCF_b15 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Central failure signal: future use"
|
||
::= { basicSettings 18 }
|
||
|
||
sts_DelayRelCA OBJECT-TYPE
|
||
SYNTAX INTEGER(1..60)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Delay of the Central failure relay signaling,
|
||
Value:
|
||
1(1sec.)
|
||
...
|
||
60(60sec.)"
|
||
::= { basicSettings 19 }
|
||
|
||
sts_DelayLEDCA OBJECT-TYPE
|
||
SYNTAX INTEGER(1..60)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Delay of the Central failure LED signaling,
|
||
Value:
|
||
1(1sec.)
|
||
...
|
||
60(60sec.)"
|
||
::= { basicSettings 20 }
|
||
|
||
sts_LCDContrast OBJECT-TYPE
|
||
SYNTAX INTEGER(0..100)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "LCD contrast from 0% to 100%. Use 10% steps,
|
||
Value:
|
||
0(0%)
|
||
10 (10%)
|
||
20(20%)
|
||
...
|
||
90(90%)
|
||
100(100%)"
|
||
::= { basicSettings 21 }
|
||
|
||
sts_Language OBJECT-TYPE
|
||
SYNTAX INTEGER(0..4)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "LCD Language,
|
||
Value:
|
||
0= English
|
||
1= German
|
||
2= Polish
|
||
3= Swedish
|
||
4= Italian"
|
||
::= { basicSettings 22 }
|
||
|
||
-- ****************************************
|
||
-- ****************************************
|
||
-- ****************************************
|
||
|
||
sts_OpMode OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Operation mode,
|
||
Value:
|
||
0= Inverter priority
|
||
1= Mains priority"
|
||
::= { advancedSettings 1 }
|
||
|
||
sts_UpperSwitchLimS1 OBJECT-TYPE
|
||
SYNTAX INTEGER(5..20)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Source 1 upper switch limit in % of nominal voltage,
|
||
Value:
|
||
5(5%)
|
||
...
|
||
20(20%)"
|
||
::= { advancedSettings 2 }
|
||
|
||
sts_LowerSwitchLimS1 OBJECT-TYPE
|
||
SYNTAX INTEGER(5..20)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Source 1 lower switch limit in % of nominal voltage,
|
||
Value:
|
||
5(5%)
|
||
...
|
||
20(20%)"
|
||
::= { advancedSettings 3 }
|
||
|
||
sts_SwitchDelayS1 OBJECT-TYPE
|
||
SYNTAX INTEGER(1..8)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Source 1 switching delay, if source 1 leave limits,
|
||
Value:
|
||
1= 0.5ms
|
||
2= 1.0ms
|
||
3= 1.5ms
|
||
4= 2.0ms
|
||
5= 2.5ms
|
||
6= 3.0ms
|
||
7= 3.5ms
|
||
8= 4.0ms"
|
||
::= { advancedSettings 4 }
|
||
|
||
sts_UpperSwitchLimS2 OBJECT-TYPE
|
||
SYNTAX INTEGER(5..20)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Source 2 upper switch limit in % of nominal voltage,
|
||
Value:
|
||
5(5%)
|
||
...
|
||
20(20%)"
|
||
::= { advancedSettings 5 }
|
||
|
||
sts_LowerSwitchLimS2 OBJECT-TYPE
|
||
SYNTAX INTEGER(5..20)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Source 2 lower switch limit in % of nominal voltage,
|
||
Value:
|
||
5(5%)
|
||
...
|
||
20(20%)"
|
||
::= { advancedSettings 6 }
|
||
|
||
sts_SwitchDelayS2 OBJECT-TYPE
|
||
SYNTAX INTEGER(1..8)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Source 2 switching delay, if source 2 leave limits,
|
||
Value:
|
||
1= 0.5ms
|
||
2= 1.0ms
|
||
3= 1.5ms
|
||
4= 2.0ms
|
||
5= 2.5ms
|
||
6= 3.0ms
|
||
7= 3.5ms
|
||
8= 4.0ms"
|
||
::= { advancedSettings 7 }
|
||
|
||
sts_MaxCellVolt1 OBJECT-TYPE
|
||
SYNTAX INTEGER(200..300)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Umax1 voltage/cell 2,0V - 3,0V,
|
||
Value:
|
||
200(2,0V)
|
||
...
|
||
300(3,0V)"
|
||
::= { advancedSettings 8 }
|
||
|
||
sts_MinCellVolt1 OBJECT-TYPE
|
||
SYNTAX INTEGER(70..250)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Umin1 voltage/cell 0,7V - 2,5V,
|
||
Value:
|
||
70(0,7V)
|
||
...
|
||
250(2,5V)"
|
||
::= { advancedSettings 9 }
|
||
|
||
sts_MinCellVolt2 OBJECT-TYPE
|
||
SYNTAX INTEGER(60..250)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Umin2 voltage/cell 0,6V - 2,5V,
|
||
Value:
|
||
60(0,6V)
|
||
...
|
||
250(2,5V)"
|
||
::= { advancedSettings 10 }
|
||
|
||
sts_MinULimit OBJECT-TYPE
|
||
SYNTAX INTEGER(170..210)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Lower limit voltage/cell for generating error, 1,7V - 2,1V,
|
||
Value:
|
||
170(1,7V)
|
||
...
|
||
210(2,1V)"
|
||
::= { advancedSettings 11 }
|
||
|
||
sts_MaxULimit OBJECT-TYPE
|
||
SYNTAX INTEGER(220..250)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Upper limit voltage/cell for generating error, 2,2V - 2,5V,
|
||
Value:
|
||
220(2,2V)
|
||
...
|
||
250(2,5V)"
|
||
::= { advancedSettings 12 }
|
||
|
||
-- ****************************************
|
||
-- ****************************************
|
||
-- ****************************************
|
||
|
||
sts_NomPower OBJECT-TYPE
|
||
SYNTAX INTEGER(120..500)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Power 1,2KVA - 5KVA,
|
||
Value:
|
||
120(1,2KVA)
|
||
...
|
||
500(5KVA)"
|
||
::= { advancedSettings2 1 }
|
||
|
||
sts_NomVolt OBJECT-TYPE
|
||
SYNTAX INTEGER(200..250)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Nominal voltage 200VAC - 250VAC,
|
||
Value:
|
||
200(200VAC)
|
||
...
|
||
250(250VAC)"
|
||
::= { advancedSettings2 2 }
|
||
|
||
sts_NomFreq OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Nominal frequency 50Hz or 60Hz,
|
||
Value:
|
||
0= 50Hz
|
||
1= 60Hz"
|
||
::= { advancedSettings2 3 }
|
||
|
||
sts_FreqRange OBJECT-TYPE
|
||
SYNTAX INTEGER(1..20)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Frequency range 0,1Hz - 2,0Hz,
|
||
Value:
|
||
1(0,1Hz)
|
||
...
|
||
20(2,0Hz)"
|
||
::= { advancedSettings2 4 }
|
||
|
||
sts_MaxCurrent OBJECT-TYPE
|
||
SYNTAX INTEGER(10..2500)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Max output current 1,0A - 250A,
|
||
Value:
|
||
10(1,0A)
|
||
...
|
||
2500(250A)"
|
||
::= { advancedSettings2 5 }
|
||
|
||
sts_PresentCell OBJECT-TYPE
|
||
SYNTAX INTEGER(12..200)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Number of present battery cell 12 - 200,
|
||
Value:
|
||
12
|
||
...
|
||
200"
|
||
::= { advancedSettings2 6 }
|
||
|
||
sts_CellVoltage OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Voltage per Cell,
|
||
Value:
|
||
0=2.0V
|
||
1=1.2V"
|
||
::= { advancedSettings2 7 }
|
||
|
||
sts_Adress OBJECT-TYPE
|
||
SYNTAX INTEGER(0..31)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION ""
|
||
::= { advancedSettings2 8 }
|
||
|
||
sts_SigRel2_b0 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Relay 2 failure signal: Source 1 failure,
|
||
Value:
|
||
0= off
|
||
1= on"
|
||
::= { advancedSettings2 9 }
|
||
|
||
sts_SigRel2_b1 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Relay 2 failure signal: Source 2 failure,
|
||
Value:
|
||
0= off
|
||
1= on"
|
||
::= { advancedSettings2 10 }
|
||
|
||
sts_SigRel2_b2 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Relay 2 failure signal: Syncronisation error,
|
||
Value:
|
||
0= off
|
||
1= on"
|
||
::= { advancedSettings2 11 }
|
||
|
||
sts_SigRel2_b3 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Relay 2 failure signal: Inverter failure,
|
||
Value:
|
||
0= off
|
||
1= on"
|
||
::= { advancedSettings2 12 }
|
||
|
||
sts_SigRel2_b4 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Relay 2 failure signal: STS overtemperature,
|
||
Value:
|
||
0= off
|
||
1= on"
|
||
::= { advancedSettings2 13 }
|
||
|
||
sts_SigRel2_b5 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Relay 2 failure signal: STS overload,
|
||
Value:
|
||
0= off
|
||
1= on"
|
||
::= { advancedSettings2 14 }
|
||
|
||
sts_SigRel2_b6 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Relay 2 failure signal: Inverter overload,
|
||
Value:
|
||
0= off
|
||
1= on"
|
||
::= { advancedSettings2 15 }
|
||
|
||
sts_SigRel2_b7 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Relay 2 failure signal: DC voltage low,
|
||
Value:
|
||
0= off
|
||
1= on"
|
||
::= { advancedSettings2 16 }
|
||
|
||
sts_SigRel2_b8 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Relay 2 failure signal: DC voltage high,
|
||
Value:
|
||
0= off
|
||
1= on"
|
||
::= { advancedSettings2 17 }
|
||
|
||
sts_SigRel2_b9 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Relay 2 failure signal: U batterie< warning,
|
||
Value:
|
||
0= off
|
||
1= on"
|
||
::= { advancedSettings2 18 }
|
||
|
||
sts_SigRel2_b10 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Relay 2 failure signal: U batterie> warning,
|
||
Value:
|
||
0= off
|
||
1= on"
|
||
::= { advancedSettings2 19 }
|
||
|
||
sts_SigRel2_b11 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Relay 2 failure signal: Fan error,
|
||
Value:
|
||
0= off
|
||
1= on"
|
||
::= { advancedSettings2 20 }
|
||
|
||
sts_SigRel2_b12 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Relay 2 failure signal: future use"
|
||
::= { advancedSettings2 21 }
|
||
|
||
sts_SigRel2_b13 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Relay 2 failure signal: future use"
|
||
::= { advancedSettings2 22 }
|
||
|
||
sts_SigRel2_b14 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Relay 2 failure signal: future use"
|
||
::= { advancedSettings2 23 }
|
||
|
||
sts_SigRel2_b15 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Relay 2 failure signal: future use"
|
||
::= { advancedSettings2 24 }
|
||
|
||
sts_ModeRel2 OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Relay 2 mode,
|
||
Value:
|
||
0= normal operation
|
||
1= inverted operation"
|
||
::= { advancedSettings2 25 }
|
||
|
||
sts_DelayRel2 OBJECT-TYPE
|
||
SYNTAX INTEGER(1..60)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Delay of relay 2 signaling 1sec. - 60sec.,
|
||
Value:
|
||
1(1sec.)
|
||
...
|
||
60(60sec.)"
|
||
::= { advancedSettings2 26 }
|
||
|
||
sts_OverTemp OBJECT-TYPE
|
||
SYNTAX INTEGER(358..358)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "STS Overtemperature 85(<28>C),
|
||
Value:
|
||
85(85<38>C)"
|
||
::= { advancedSettings2 27 }
|
||
|
||
-- ****************************************
|
||
-- ****************************************
|
||
-- ****************************************
|
||
|
||
net_EdgeDetectionDelay OBJECT-TYPE
|
||
SYNTAX INTEGER(0..20)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Edge detection delay 0ms - 20ms,
|
||
Value:
|
||
0(0ms)
|
||
...
|
||
20(20ms)"
|
||
::= { netSyncronisationSet 1 }
|
||
|
||
net_TimeOutDelay OBJECT-TYPE
|
||
SYNTAX INTEGER(0..20)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Timeout delay 0ms - 20ms,
|
||
Value:
|
||
0(0ms)
|
||
...
|
||
20(20ms)"
|
||
::= { netSyncronisationSet 2 }
|
||
|
||
net_MaxCorrPhi OBJECT-TYPE
|
||
SYNTAX INTEGER(1..255)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Max correction cosinus Phi. 333ns - 84915ns (1dig.=>333ns),
|
||
Value:
|
||
1(333ns)
|
||
...
|
||
255(84915ns)"
|
||
::= { netSyncronisationSet 3 }
|
||
|
||
net_DivDeltaPhi OBJECT-TYPE
|
||
SYNTAX INTEGER(0..8)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "1 - 1/256,
|
||
Value:
|
||
0=1
|
||
1=1/2
|
||
2=1/4
|
||
3=1/8
|
||
4=1/16
|
||
5=1/32
|
||
6=1/64
|
||
7=1/128
|
||
8=1/256"
|
||
::= { netSyncronisationSet 4 }
|
||
|
||
net_DivCorrPhi_I OBJECT-TYPE
|
||
SYNTAX INTEGER(0..8)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION " 1 - 1/256,
|
||
Value:
|
||
0=1
|
||
1=1/2
|
||
2=1/4
|
||
3=1/8
|
||
4=1/16
|
||
5=1/32
|
||
6=1/64
|
||
7=1/128
|
||
8=1/256"
|
||
::= { netSyncronisationSet 5 }
|
||
|
||
net_MaxCorrT OBJECT-TYPE
|
||
SYNTAX INTEGER(1..255)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "333ns - 84915ns (1dig.=>333ns),
|
||
Value:
|
||
1(333ns)
|
||
...
|
||
255(84915ns)"
|
||
::= { netSyncronisationSet 6 }
|
||
|
||
net_DivDeltaT OBJECT-TYPE
|
||
SYNTAX INTEGER(0..8)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "1 - 1/256,
|
||
Value:
|
||
0=1
|
||
1=1/2
|
||
2=1/4
|
||
3=1/8
|
||
4=1/16
|
||
5=1/32
|
||
6=1/64
|
||
7=1/128
|
||
8=1/256"
|
||
::= { netSyncronisationSet 7 }
|
||
|
||
net_SyncOKNr OBJECT-TYPE
|
||
SYNTAX INTEGER(1..255)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "1 - 255,
|
||
Value:
|
||
1
|
||
...
|
||
255"
|
||
::= { netSyncronisationSet 8 }
|
||
|
||
net_SyncErrorNr OBJECT-TYPE
|
||
SYNTAX INTEGER(1..255)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "1 - 255,
|
||
Value:
|
||
1
|
||
...
|
||
255"
|
||
::= { netSyncronisationSet 9 }
|
||
|
||
net_P_Diff OBJECT-TYPE
|
||
SYNTAX INTEGER(150..15000)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "150 - 1500,
|
||
Value:
|
||
150
|
||
...
|
||
1500"
|
||
::= { netSyncronisationSet 10 }
|
||
|
||
-- ****************************************
|
||
-- ****************************************
|
||
-- ****************************************
|
||
|
||
adj_UMains OBJECT-TYPE
|
||
SYNTAX INTEGER(368..432)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION ""
|
||
::= { adjustValues 1 }
|
||
|
||
adj_UInv OBJECT-TYPE
|
||
SYNTAX INTEGER(368..432)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION ""
|
||
::= { adjustValues 2 }
|
||
|
||
adj_UDC OBJECT-TYPE
|
||
SYNTAX INTEGER(1372..1628)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION ""
|
||
::= { adjustValues 3 }
|
||
|
||
adj_Uout OBJECT-TYPE
|
||
SYNTAX INTEGER(368..432)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION ""
|
||
::= { adjustValues 4 }
|
||
|
||
adj_Iout OBJECT-TYPE
|
||
SYNTAX INTEGER(1988..3012)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION ""
|
||
::= { adjustValues 5 }
|
||
|
||
-- ****************************************
|
||
-- ****************************************
|
||
-- ****************************************
|
||
-- ****************************************
|
||
-- ****************************************
|
||
-- ****************************************
|
||
|
||
trapLastMessageStringTest OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "Message giving more detailed information on alarms."
|
||
::= { traps 1 }
|
||
|
||
trapLastMessageNbrTest OBJECT-TYPE
|
||
SYNTAX INTEGER(16..46)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "Referenced Trap number"
|
||
::= { traps 2 }
|
||
|
||
trapSourceIPTest OBJECT-TYPE
|
||
SYNTAX IpAddress
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "Alarm Source IP address"
|
||
::= { traps 3 }
|
||
|
||
-- source_mains_failue_present NOTIFICATION-TYPE
|
||
-- STATUS obsolete
|
||
-- DESCRIPTION "Error with Source mains present"
|
||
-- ::= { traps 17 }
|
||
|
||
trap_source_mains_failue_present OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "STS mains failure present"
|
||
::= { traps 17 }
|
||
|
||
source_mains_failue_present_trap TRAP-TYPE
|
||
ENTERPRISE convertronic
|
||
VARIABLES {
|
||
trap_source_mains_failue_present,
|
||
trapLastMessageStringTest,
|
||
trapLastMessageNbrTest,
|
||
trapSourceIPTest
|
||
}
|
||
DESCRIPTION
|
||
"Error with Source mains present"
|
||
-- NMS trap annotation
|
||
--#TYPE "Error with Source mains present"
|
||
--#SUMMARY "Failure %d, Text: %s, No: %d."
|
||
--#ARGUMENTS {0,1,2}
|
||
--#SEVERITY MAJOR
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 16
|
||
|
||
-- source_inverter_failure_present NOTIFICATION-TYPE
|
||
-- STATUS mandatory
|
||
-- DESCRIPTION "Error with Source inverter present"
|
||
-- ::= { traps 18 }
|
||
|
||
trap_source_inverter_failure_present OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "STS inverter source failure present"
|
||
::= { traps 18 }
|
||
|
||
source_inverter_failure_present TRAP-TYPE
|
||
ENTERPRISE convertronic
|
||
VARIABLES {
|
||
trap_source_inverter_failure_present,
|
||
trapLastMessageStringTest,
|
||
trapLastMessageNbrTest,
|
||
trapSourceIPTest
|
||
}
|
||
DESCRIPTION
|
||
"Error with Source inverter present"
|
||
-- NMS trap annotation
|
||
--#TYPE "Error with Source inverter present"
|
||
--#SUMMARY "Failure %d, Text: %s, No: %d."
|
||
--#ARGUMENTS {0,1,2}
|
||
--#SEVERITY MAJOR
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 17
|
||
|
||
--
|
||
-- syncronisation_error_present NOTIFICATION-TYPE
|
||
-- STATUS mandatory
|
||
-- DESCRIPTION "Syncronisation between Source Mains and Source Inverter lost"
|
||
-- ::= { traps 19 }
|
||
|
||
trap_syncronisation_error_present OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "STS syncronisation error present"
|
||
::= { traps 19 }
|
||
|
||
syncronisation_error_present TRAP-TYPE
|
||
ENTERPRISE convertronic
|
||
VARIABLES {
|
||
trap_syncronisation_error_present,
|
||
trapLastMessageStringTest,
|
||
trapLastMessageNbrTest,
|
||
trapSourceIPTest
|
||
}
|
||
DESCRIPTION
|
||
"Syncronisation between Source Mains and Source Inverter lost"
|
||
-- NMS trap annotation
|
||
--#TYPE "Syncronisation between Source Mains and Source Inverter lost"
|
||
--#SUMMARY "Failure %d, Text: %s, No: %d."
|
||
--#ARGUMENTS {0,1,2}
|
||
--#SEVERITY MAJOR
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 18
|
||
|
||
--
|
||
-- inverter_failure_present NOTIFICATION-TYPE
|
||
-- STATUS mandatory
|
||
-- DESCRIPTION "Inverter failure active"
|
||
-- ::= { traps 20 }
|
||
|
||
trap_inverter_failure_present OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "STS inverter failure present"
|
||
::= { traps 20 }
|
||
|
||
inverter_failure_present TRAP-TYPE
|
||
ENTERPRISE convertronic
|
||
VARIABLES {
|
||
trap_inverter_failure_present,
|
||
trapLastMessageStringTest,
|
||
trapLastMessageNbrTest,
|
||
trapSourceIPTest
|
||
}
|
||
DESCRIPTION
|
||
"Inverter failure active"
|
||
-- NMS trap annotation
|
||
--#TYPE "Inverter failure active"
|
||
--#SUMMARY "Failure %d, Text: %s, No: %d."
|
||
--#ARGUMENTS {0,1,2}
|
||
--#SEVERITY MAJOR
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 19
|
||
|
||
--
|
||
-- no_redundant_inverter_present NOTIFICATION-TYPE
|
||
-- STATUS mandatory
|
||
-- DESCRIPTION "No more redundant inverter present"
|
||
-- ::= { traps 21 }
|
||
|
||
trap_no_redundant_inverter_present OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "STS no redundant inverter present"
|
||
::= { traps 21 }
|
||
|
||
no_redundant_inverter_present TRAP-TYPE
|
||
ENTERPRISE convertronic
|
||
VARIABLES {
|
||
trap_no_redundant_inverter_present,
|
||
trapLastMessageStringTest,
|
||
trapLastMessageNbrTest,
|
||
trapSourceIPTest
|
||
}
|
||
DESCRIPTION
|
||
"No more redundant inverter present"
|
||
-- NMS trap annotation
|
||
--#TYPE "No more redundant inverter present"
|
||
--#SUMMARY "Failure %d, Text: %s, No: %d."
|
||
--#ARGUMENTS {0,1,2}
|
||
--#SEVERITY MINOR
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 20
|
||
|
||
--
|
||
-- critical_inverter_quantity_present NOTIFICATION-TYPE
|
||
-- STATUS mandatory
|
||
-- DESCRIPTION "Inverter quantity is lower than needed"
|
||
-- ::= { traps 22 }
|
||
|
||
trap_critical_inverter_quantity_present OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "STS critical inverter quantity present"
|
||
::= { traps 22 }
|
||
|
||
critical_inverter_quantity_present TRAP-TYPE
|
||
ENTERPRISE convertronic
|
||
VARIABLES {
|
||
trap_critical_inverter_quantity_present,
|
||
trapLastMessageStringTest,
|
||
trapLastMessageNbrTest,
|
||
trapSourceIPTest
|
||
}
|
||
DESCRIPTION
|
||
"Inverter quantity is lower than needed"
|
||
-- NMS trap annotation
|
||
--#TYPE "Inverter quantity is lower than needed"
|
||
--#SUMMARY "Failure %d, Text: %s, No: %d."
|
||
--#ARGUMENTS {0,1,2}
|
||
--#SEVERITY MAJOR
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 21
|
||
|
||
--
|
||
-- sts_overtemperature_present NOTIFICATION-TYPE
|
||
-- STATUS mandatory
|
||
-- DESCRIPTION "STS temperature warning is active"
|
||
-- ::= { traps 23 }
|
||
|
||
trap_sts_overtemperature_present OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "STS sts overtemperature present"
|
||
::= { traps 23 }
|
||
|
||
sts_overtemperature_present TRAP-TYPE
|
||
ENTERPRISE convertronic
|
||
VARIABLES {
|
||
trap_sts_overtemperature_present,
|
||
trapLastMessageStringTest,
|
||
trapLastMessageNbrTest,
|
||
trapSourceIPTest
|
||
}
|
||
DESCRIPTION
|
||
"STS temperature warning is active"
|
||
-- NMS trap annotation
|
||
--#TYPE "STS temperature warning is active"
|
||
--#SUMMARY "Failure %d, Text: %s, No: %d."
|
||
--#ARGUMENTS {0,1,2}
|
||
--#SEVERITY MAJOR
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 22
|
||
|
||
--
|
||
-- sts_overload_present NOTIFICATION-TYPE
|
||
-- STATUS mandatory
|
||
-- DESCRIPTION "STS overload is active"
|
||
-- ::= { traps 24 }
|
||
|
||
trap_sts_overload_present OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "STS sts overload present"
|
||
::= { traps 24 }
|
||
|
||
sts_overload_present TRAP-TYPE
|
||
ENTERPRISE convertronic
|
||
VARIABLES {
|
||
trap_sts_overload_present,
|
||
trapLastMessageStringTest,
|
||
trapLastMessageNbrTest,
|
||
trapSourceIPTest
|
||
}
|
||
DESCRIPTION
|
||
"STS overload is active"
|
||
-- NMS trap annotation
|
||
--#TYPE "STS overload is active"
|
||
--#SUMMARY "Failure %d, Text: %s, No: %d."
|
||
--#ARGUMENTS {0,1,2}
|
||
--#SEVERITY MAJOR
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 23
|
||
|
||
--
|
||
-- inverter_overload_present NOTIFICATION-TYPE
|
||
-- STATUS mandatory
|
||
-- DESCRIPTION "Inverter overload is active"
|
||
-- ::= { traps 25 }
|
||
|
||
trap_inverter_overload_present OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "STS inverter overload present"
|
||
::= { traps 25 }
|
||
|
||
inverter_overload_present TRAP-TYPE
|
||
ENTERPRISE convertronic
|
||
VARIABLES {
|
||
trap_inverter_overload_present,
|
||
trapLastMessageStringTest,
|
||
trapLastMessageNbrTest,
|
||
trapSourceIPTest
|
||
}
|
||
DESCRIPTION
|
||
"Inverter overload is active"
|
||
-- NMS trap annotation
|
||
--#TYPE "Inverter overload is active"
|
||
--#SUMMARY "Failure %d, Text: %s, No: %d."
|
||
--#ARGUMENTS {0,1,2}
|
||
--#SEVERITY MAJOR
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 24
|
||
|
||
--
|
||
-- sts_current_need_redandancy_present NOTIFICATION-TYPE
|
||
-- STATUS mandatory
|
||
-- DESCRIPTION "STS actual current need an redundant inverter"
|
||
-- ::= { traps 26 }
|
||
|
||
trap_sts_current_need_redandancy_present OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "STS current need redandancy present"
|
||
::= { traps 26 }
|
||
|
||
sts_current_need_redandancy_present TRAP-TYPE
|
||
ENTERPRISE convertronic
|
||
VARIABLES {
|
||
trap_sts_current_need_redandancy_present,
|
||
trapLastMessageStringTest,
|
||
trapLastMessageNbrTest,
|
||
trapSourceIPTest
|
||
}
|
||
DESCRIPTION
|
||
"STS actual current need an redundant inverter"
|
||
-- NMS trap annotation
|
||
--#TYPE "STS actual current need an redundant inverter"
|
||
--#SUMMARY "Failure %d, Text: %s, No: %d."
|
||
--#ARGUMENTS {0,1,2}
|
||
--#SEVERITY MINOR
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 25
|
||
--
|
||
-- dc_voltage_low_present NOTIFICATION-TYPE
|
||
-- STATUS mandatory
|
||
-- DESCRIPTION "DC voltage is low"
|
||
-- ::= { traps 27 }
|
||
|
||
trap_dc_voltage_low_present OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "STS dc voltage low present"
|
||
::= { traps 27 }
|
||
|
||
dc_voltage_low_present TRAP-TYPE
|
||
ENTERPRISE convertronic
|
||
VARIABLES {
|
||
trap_dc_voltage_low_present,
|
||
trapLastMessageStringTest,
|
||
trapLastMessageNbrTest,
|
||
trapSourceIPTest
|
||
}
|
||
DESCRIPTION
|
||
"DC voltage is low"
|
||
-- NMS trap annotation
|
||
--#TYPE "DC voltage is low"
|
||
--#SUMMARY "Failure %d, Text: %s, No: %d."
|
||
--#ARGUMENTS {0,1,2}
|
||
--#SEVERITY MAJOR
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 26
|
||
|
||
--
|
||
-- dc_voltage_high_present NOTIFICATION-TYPE
|
||
-- STATUS mandatory
|
||
-- DESCRIPTION "DC voltage is high"
|
||
-- ::= { traps 28 }
|
||
|
||
trap_dc_voltage_high_present OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "STS DC voltage is high"
|
||
::= { traps 28 }
|
||
|
||
dc_voltage_high_present TRAP-TYPE
|
||
ENTERPRISE convertronic
|
||
VARIABLES {
|
||
trap_dc_voltage_high_present,
|
||
trapLastMessageStringTest,
|
||
trapLastMessageNbrTest,
|
||
trapSourceIPTest
|
||
}
|
||
DESCRIPTION
|
||
"DC voltage is high"
|
||
-- NMS trap annotation
|
||
--#TYPE "DC voltage is high"
|
||
--#SUMMARY "Failure %d, Text: %s, No: %d."
|
||
--#ARGUMENTS {0,1,2}
|
||
--#SEVERITY MAJOR
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 27
|
||
|
||
--
|
||
-- fan_error_present NOTIFICATION-TYPE
|
||
-- STATUS mandatory
|
||
-- DESCRIPTION "Fan is in error-state"
|
||
-- ::= { traps 29 }
|
||
|
||
trap_fan_error_present OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "STS Fan is in error-state"
|
||
::= { traps 29 }
|
||
|
||
fan_error_present TRAP-TYPE
|
||
ENTERPRISE convertronic
|
||
VARIABLES {
|
||
trap_fan_error_present,
|
||
trapLastMessageStringTest,
|
||
trapLastMessageNbrTest,
|
||
trapSourceIPTest
|
||
}
|
||
DESCRIPTION
|
||
"Fan is in error-state"
|
||
-- NMS trap annotation
|
||
--#TYPE "Fan is in error-state"
|
||
--#SUMMARY "Failure %d, Text: %s, No: %d."
|
||
--#ARGUMENTS {0,1,2}
|
||
--#SEVERITY MAJOR
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 28
|
||
|
||
--
|
||
-- uout_low_present NOTIFICATION-TYPE
|
||
-- STATUS mandatory
|
||
-- DESCRIPTION "STS outputvoltage is low"
|
||
-- ::= { traps 30 }
|
||
|
||
trap_uout_low_present OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "STS outputvoltage is low"
|
||
::= { traps 30 }
|
||
|
||
uout_low_present TRAP-TYPE
|
||
ENTERPRISE convertronic
|
||
VARIABLES {
|
||
trap_uout_low_present,
|
||
trapLastMessageStringTest,
|
||
trapLastMessageNbrTest,
|
||
trapSourceIPTest
|
||
}
|
||
DESCRIPTION
|
||
"STS outputvoltage is low"
|
||
-- NMS trap annotation
|
||
--#TYPE "STS outputvoltage is low"
|
||
--#SUMMARY "Failure %d, Text: %s, No: %d."
|
||
--#ARGUMENTS {0,1,2}
|
||
--#SEVERITY MAJOR
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 29
|
||
|
||
--
|
||
-- u_batterie_lower_warning_present NOTIFICATION-TYPE
|
||
-- STATUS mandatory
|
||
-- DESCRIPTION "Battery voltage is lower warninglevel"
|
||
-- ::= { traps 31 }
|
||
|
||
trap_u_batterie_lower_warning_present OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "STS Battery voltage is lower warninglevel"
|
||
::= { traps 31 }
|
||
|
||
u_batterie_lower_warning_present TRAP-TYPE
|
||
ENTERPRISE convertronic
|
||
VARIABLES {
|
||
trap_u_batterie_lower_warning_present,
|
||
trapLastMessageStringTest,
|
||
trapLastMessageNbrTest,
|
||
trapSourceIPTest
|
||
}
|
||
DESCRIPTION
|
||
"Battery voltage is lower warninglevel"
|
||
-- NMS trap annotation
|
||
--#TYPE "Battery voltage is lower warninglevel"
|
||
--#SUMMARY "Failure %d, Text: %s, No: %d."
|
||
--#ARGUMENTS {0,1,2}
|
||
--#SEVERITY MINOR
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 30
|
||
|
||
--
|
||
-- u_batterie_higher_warning_present NOTIFICATION-TYPE
|
||
-- STATUS mandatory
|
||
-- DESCRIPTION "Battery voltage is higher warninglevel"
|
||
-- ::= { traps 32 }
|
||
|
||
trap_u_batterie_higher_warning_present OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "Battery voltage is higher warninglevel"
|
||
::= { traps 32 }
|
||
|
||
u_batterie_higher_warning_present TRAP-TYPE
|
||
ENTERPRISE convertronic
|
||
VARIABLES {
|
||
trap_u_batterie_higher_warning_present,
|
||
trapLastMessageStringTest,
|
||
trapLastMessageNbrTest,
|
||
trapSourceIPTest
|
||
}
|
||
DESCRIPTION
|
||
"Battery voltage is higher warninglevel"
|
||
-- NMS trap annotation
|
||
--#TYPE "Battery voltage is higher warninglevel"
|
||
--#SUMMARY "Failure %d, Text: %s, No: %d."
|
||
--#ARGUMENTS {0,1,2}
|
||
--#SEVERITY MINOR
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 31
|
||
|
||
--
|
||
-- source_mains_failure_removed NOTIFICATION-TYPE
|
||
-- STATUS mandatory
|
||
-- DESCRIPTION "Error with Source mains, state is not active"
|
||
-- ::= { traps 33 }
|
||
|
||
trap_source_mains_failure_removed OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "Error with Source mains, state is not active"
|
||
::= { traps 33 }
|
||
|
||
source_mains_failure_removed TRAP-TYPE
|
||
ENTERPRISE convertronic
|
||
VARIABLES {
|
||
trap_source_mains_failure_removed,
|
||
trapLastMessageStringTest,
|
||
trapLastMessageNbrTest,
|
||
trapSourceIPTest
|
||
}
|
||
DESCRIPTION
|
||
"Error with Source mains, state is not active"
|
||
-- NMS trap annotation
|
||
--#TYPE "Error with Source mains, state is not active"
|
||
--#SUMMARY "OK %d, Text: %s, No: %d."
|
||
--#ARGUMENTS {0,1,2}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 32
|
||
|
||
--
|
||
-- source_inverter_failure_removed NOTIFICATION-TYPE
|
||
-- STATUS mandatory
|
||
-- DESCRIPTION "Error with Source inverter present, state is not active"
|
||
-- ::= { traps 34 }
|
||
|
||
trap_source_inverter_failure_removed OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "Error with Source inverter present, state is not active"
|
||
::= { traps 34 }
|
||
|
||
source_inverter_failure_removed TRAP-TYPE
|
||
ENTERPRISE convertronic
|
||
VARIABLES {
|
||
trap_source_inverter_failure_removed,
|
||
trapLastMessageStringTest,
|
||
trapLastMessageNbrTest,
|
||
trapSourceIPTest
|
||
}
|
||
DESCRIPTION
|
||
"Error with Source inverter present, state is not active"
|
||
-- NMS trap annotation
|
||
--#TYPE "Error with Source inverter present, state is not active"
|
||
--#SUMMARY "OK %d, Text: %s, No: %d."
|
||
--#ARGUMENTS {0,1,2}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 33
|
||
|
||
--
|
||
-- syncronisation_error_removed NOTIFICATION-TYPE
|
||
-- STATUS mandatory
|
||
-- DESCRIPTION "Syncronisation between Source Mains and Source Inverter lost, state is not active"
|
||
-- ::= { traps 35 }
|
||
|
||
trap_syncronisation_error_removed OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "Syncronisation between Source Mains and Source Inverter lost, state is not active"
|
||
::= { traps 35 }
|
||
|
||
syncronisation_error_removed TRAP-TYPE
|
||
ENTERPRISE convertronic
|
||
VARIABLES {
|
||
trap_syncronisation_error_removed,
|
||
trapLastMessageStringTest,
|
||
trapLastMessageNbrTest,
|
||
trapSourceIPTest
|
||
}
|
||
DESCRIPTION
|
||
"Syncronisation between Source Mains and Source Inverter lost, state is not active"
|
||
-- NMS trap annotation
|
||
--#TYPE "Syncronisation between Source Mains and Source Inverter lost, state is not active"
|
||
--#SUMMARY "OK %d, Text: %s, No: %d."
|
||
--#ARGUMENTS {0,1,2}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 34
|
||
|
||
--
|
||
-- inverter_failure_removed NOTIFICATION-TYPE
|
||
-- STATUS mandatory
|
||
-- DESCRIPTION "Inverter failure, state is not active"
|
||
-- ::= { traps 36 }
|
||
|
||
trap_inverter_failure_removed OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "Inverter failure, state is not active"
|
||
::= { traps 36 }
|
||
|
||
inverter_failure_removed TRAP-TYPE
|
||
ENTERPRISE convertronic
|
||
VARIABLES {
|
||
trap_inverter_failure_removed,
|
||
trapLastMessageStringTest,
|
||
trapLastMessageNbrTest,
|
||
trapSourceIPTest
|
||
}
|
||
DESCRIPTION
|
||
"Inverter failure, state is not active"
|
||
-- NMS trap annotation
|
||
--#TYPE "Inverter failure, state is not active"
|
||
--#SUMMARY "OK %d, Text: %s, No: %d."
|
||
--#ARGUMENTS {0,1,2}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 35
|
||
|
||
--
|
||
-- no_redundant_inverter_removed NOTIFICATION-TYPE
|
||
-- STATUS mandatory
|
||
-- DESCRIPTION "No more redundant inverter present, state is not active"
|
||
-- ::= { traps 37 }
|
||
|
||
trap_no_redundant_inverter_removed OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "No more redundant inverter present, state is not active"
|
||
::= { traps 37 }
|
||
|
||
no_redundant_inverter_removed TRAP-TYPE
|
||
ENTERPRISE convertronic
|
||
VARIABLES {
|
||
trap_no_redundant_inverter_removed,
|
||
trapLastMessageStringTest,
|
||
trapLastMessageNbrTest,
|
||
trapSourceIPTest
|
||
}
|
||
DESCRIPTION
|
||
"No more redundant inverter present, state is not active"
|
||
-- NMS trap annotation
|
||
--#TYPE "No more redundant inverter present, state is not active"
|
||
--#SUMMARY "OK %d, Text: %s, No: %d."
|
||
--#ARGUMENTS {0,1,2}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 36
|
||
|
||
--
|
||
-- critical_inverter_quantity_removed NOTIFICATION-TYPE
|
||
-- STATUS mandatory
|
||
-- DESCRIPTION "Inverter quantity is lower than needed, state is not active"
|
||
-- ::= { traps 38 }
|
||
|
||
trap_critical_inverter_quantity_removed OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "Inverter quantity is lower than needed, state is not active"
|
||
::= { traps 38 }
|
||
|
||
critical_inverter_quantity_removed TRAP-TYPE
|
||
ENTERPRISE convertronic
|
||
VARIABLES {
|
||
trap_critical_inverter_quantity_removed,
|
||
trapLastMessageStringTest,
|
||
trapLastMessageNbrTest,
|
||
trapSourceIPTest
|
||
}
|
||
DESCRIPTION
|
||
"Inverter quantity is lower than needed, state is not active"
|
||
-- NMS trap annotation
|
||
--#TYPE "Inverter quantity is lower than needed, state is not active"
|
||
--#SUMMARY "OK %d, Text: %s, No: %d."
|
||
--#ARGUMENTS {0,1,2}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 37
|
||
|
||
--
|
||
-- sts_overtemperature_removed NOTIFICATION-TYPE
|
||
-- STATUS mandatory
|
||
-- DESCRIPTION "STS temperature warning is not active"
|
||
-- ::= { traps 39 }
|
||
|
||
trap_sts_overtemperature_removed OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "STS temperature warning is not active"
|
||
::= { traps 39 }
|
||
|
||
sts_overtemperature_removed TRAP-TYPE
|
||
ENTERPRISE convertronic
|
||
VARIABLES {
|
||
trap_sts_overtemperature_removed,
|
||
trapLastMessageStringTest,
|
||
trapLastMessageNbrTest,
|
||
trapSourceIPTest
|
||
}
|
||
DESCRIPTION
|
||
"STS temperature warning is not active"
|
||
-- NMS trap annotation
|
||
--#TYPE "STS temperature warning is not active"
|
||
--#SUMMARY "OK %d, Text: %s, No: %d."
|
||
--#ARGUMENTS {0,1,2}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 38
|
||
|
||
--
|
||
-- sts_overload_removed NOTIFICATION-TYPE
|
||
-- STATUS mandatory
|
||
-- DESCRIPTION "STS overload is not active"
|
||
-- ::= { traps 40 }
|
||
|
||
trap_sts_overload_removed OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "STS temperature warning is not active"
|
||
::= { traps 40 }
|
||
|
||
sts_overload_removed TRAP-TYPE
|
||
ENTERPRISE convertronic
|
||
VARIABLES {
|
||
trap_sts_overload_removed,
|
||
trapLastMessageStringTest,
|
||
trapLastMessageNbrTest,
|
||
trapSourceIPTest
|
||
}
|
||
DESCRIPTION
|
||
"STS overload is not active"
|
||
-- NMS trap annotation
|
||
--#TYPE "STS overload is not active"
|
||
--#SUMMARY "OK %d, Text: %s, No: %d."
|
||
--#ARGUMENTS {0,1,2}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 39
|
||
|
||
--
|
||
-- inverter_overload_removed NOTIFICATION-TYPE
|
||
-- STATUS mandatory
|
||
-- DESCRIPTION "Inverter overload is not active"
|
||
-- ::= { traps 41 }
|
||
|
||
trap_inverter_overload_removed OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "Inverter overload is not active"
|
||
::= { traps 41 }
|
||
|
||
inverter_overload_removed TRAP-TYPE
|
||
ENTERPRISE convertronic
|
||
VARIABLES {
|
||
trap_inverter_overload_removed,
|
||
trapLastMessageStringTest,
|
||
trapLastMessageNbrTest,
|
||
trapSourceIPTest
|
||
}
|
||
DESCRIPTION
|
||
"Inverter overload is not active"
|
||
-- NMS trap annotation
|
||
--#TYPE "Inverter overload is not active"
|
||
--#SUMMARY "OK %d, Text: %s, No: %d."
|
||
--#ARGUMENTS {0,1,2}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 40
|
||
|
||
--
|
||
-- sts_current_need_redandancy_removed NOTIFICATION-TYPE
|
||
-- STATUS mandatory
|
||
-- DESCRIPTION "STS actual current do not need an redundant inverter"
|
||
-- ::= { traps 42 }
|
||
|
||
trap_sts_current_need_redandancy_removed OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "STS actual current do not need an redundant inverter"
|
||
::= { traps 42 }
|
||
|
||
sts_current_need_redandancy_removed TRAP-TYPE
|
||
ENTERPRISE convertronic
|
||
VARIABLES {
|
||
trap_sts_current_need_redandancy_removed,
|
||
trapLastMessageStringTest,
|
||
trapLastMessageNbrTest,
|
||
trapSourceIPTest
|
||
}
|
||
DESCRIPTION
|
||
"STS actual current do not need an redundant inverter"
|
||
-- NMS trap annotation
|
||
--#TYPE "STS actual current do not need an redundant inverter"
|
||
--#SUMMARY "OK %d, Text: %s, No: %d."
|
||
--#ARGUMENTS {0,1,2}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 41
|
||
|
||
--
|
||
-- dc_voltage_low_removed NOTIFICATION-TYPE
|
||
-- STATUS mandatory
|
||
-- DESCRIPTION "DC voltage is low, state is not active"
|
||
-- ::= { traps 43 }
|
||
|
||
trap_dc_voltage_low_removed OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "DC voltage is low, state is not active"
|
||
::= { traps 43 }
|
||
|
||
dc_voltage_low_removed TRAP-TYPE
|
||
ENTERPRISE convertronic
|
||
VARIABLES {
|
||
trap_dc_voltage_low_removed,
|
||
trapLastMessageStringTest,
|
||
trapLastMessageNbrTest,
|
||
trapSourceIPTest
|
||
}
|
||
DESCRIPTION
|
||
"DC voltage is low, state is not active"
|
||
-- NMS trap annotation
|
||
--#TYPE "DC voltage is low, state is not active"
|
||
--#SUMMARY "OK %d, Text: %s, No: %d."
|
||
--#ARGUMENTS {0,1,2}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 42
|
||
|
||
--
|
||
-- dc_voltage_high_added_removed NOTIFICATION-TYPE
|
||
-- STATUS mandatory
|
||
-- DESCRIPTION "DC voltage is high, state is not active"
|
||
-- ::= { traps 44 }
|
||
|
||
trap_dc_voltage_high_added_removed OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "DC voltage is high, state is not active"
|
||
::= { traps 44 }
|
||
|
||
dc_voltage_high_added_removed TRAP-TYPE
|
||
ENTERPRISE convertronic
|
||
VARIABLES {
|
||
trap_dc_voltage_high_added_removed,
|
||
trapLastMessageStringTest,
|
||
trapLastMessageNbrTest,
|
||
trapSourceIPTest
|
||
}
|
||
DESCRIPTION
|
||
"DC voltage is high, state is not active"
|
||
-- NMS trap annotation
|
||
--#TYPE "DC voltage is high, state is not active"
|
||
--#SUMMARY "OK %d, Text: %s, No: %d."
|
||
--#ARGUMENTS {0,1,2}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 43
|
||
|
||
--
|
||
-- fan_error_removed NOTIFICATION-TYPE
|
||
-- STATUS mandatory
|
||
-- DESCRIPTION "Fan is not in error-state"
|
||
-- ::= { traps 45 }
|
||
|
||
trap_fan_error_removed OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "Fan is not in error-state"
|
||
::= { traps 45 }
|
||
|
||
fan_error_removed TRAP-TYPE
|
||
ENTERPRISE convertronic
|
||
VARIABLES {
|
||
trap_fan_error_removed,
|
||
trapLastMessageStringTest,
|
||
trapLastMessageNbrTest,
|
||
trapSourceIPTest
|
||
}
|
||
DESCRIPTION
|
||
"Fan is not in error-state"
|
||
-- NMS trap annotation
|
||
--#TYPE "Fan is not in error-state"
|
||
--#SUMMARY "OK %d, Text: %s, No: %d."
|
||
--#ARGUMENTS {0,1,2}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 44
|
||
|
||
--
|
||
-- uout_low_removed NOTIFICATION-TYPE
|
||
-- STATUS mandatory
|
||
-- DESCRIPTION "STS outputvoltage is low, state is not active"
|
||
-- ::= { traps 46 }
|
||
|
||
trap_uout_low_removed OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "STS outputvoltage is low, state is not active"
|
||
::= { traps 46 }
|
||
|
||
uout_low_removed TRAP-TYPE
|
||
ENTERPRISE convertronic
|
||
VARIABLES {
|
||
trap_uout_low_removed,
|
||
trapLastMessageStringTest,
|
||
trapLastMessageNbrTest,
|
||
trapSourceIPTest
|
||
}
|
||
DESCRIPTION
|
||
"STS outputvoltage is low, state is not active"
|
||
-- NMS trap annotation
|
||
--#TYPE "STS outputvoltage is low, state is not active"
|
||
--#SUMMARY "OK %d, Text: %s, No: %d."
|
||
--#ARGUMENTS {0,1,2}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 45
|
||
|
||
--
|
||
-- u_batterie_lower_warning_removed NOTIFICATION-TYPE
|
||
-- STATUS mandatory
|
||
-- DESCRIPTION "Battery voltage is lower warninglevel, state is not active"
|
||
-- ::= { traps 47 }
|
||
|
||
trap_u_batterie_lower_warning_removed OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "Battery voltage is lower warninglevel, state is not active"
|
||
::= { traps 47 }
|
||
|
||
u_batterie_lower_warning_removed TRAP-TYPE
|
||
ENTERPRISE convertronic
|
||
VARIABLES {
|
||
trap_u_batterie_lower_warning_removed,
|
||
trapLastMessageStringTest,
|
||
trapLastMessageNbrTest,
|
||
trapSourceIPTest
|
||
}
|
||
DESCRIPTION
|
||
"Battery voltage is lower warninglevel, state is not active"
|
||
-- NMS trap annotation
|
||
--#TYPE "Battery voltage is lower warninglevel, state is not active"
|
||
--#SUMMARY "OK %d, Text: %s, No: %d."
|
||
--#ARGUMENTS {0,1,2}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 46
|
||
|
||
--
|
||
-- u_batterie_higher_warning_removed NOTIFICATION-TYPE
|
||
-- STATUS mandatory
|
||
-- DESCRIPTION "Battery voltage is higher warninglevel, state is not active"
|
||
-- ::= { traps 48 }
|
||
|
||
trap_u_batterie_higher_warning_removed OBJECT-TYPE
|
||
SYNTAX INTEGER(0..1)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "Battery voltage is higher warninglevel, state is not active"
|
||
::= { traps 48 }
|
||
|
||
u_batterie_higher_warning_removed TRAP-TYPE
|
||
ENTERPRISE convertronic
|
||
VARIABLES {
|
||
trap_u_batterie_higher_warning_removed,
|
||
trapLastMessageStringTest,
|
||
trapLastMessageNbrTest,
|
||
trapSourceIPTest
|
||
}
|
||
DESCRIPTION
|
||
"Battery voltage is higher warninglevel, state is not active"
|
||
-- NMS trap annotation
|
||
--#TYPE "Battery voltage is higher warninglevel, state is not active"
|
||
--#SUMMARY "OK %d, Text: %s, No: %d."
|
||
--#ARGUMENTS {0,1,2}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 47
|
||
|
||
-- ****************************************
|
||
-- ****************************************
|
||
-- ****************************************
|
||
|
||
inverter_Table OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF Inverter_Entry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "Table of CAN-nodes."
|
||
::= { inverter_measureValues 1 }
|
||
|
||
inverter_Entry OBJECT-TYPE
|
||
SYNTAX Inverter_Entry
|
||
ACCESS not-accessible
|
||
STATUS optional
|
||
DESCRIPTION "CAN-node entries."
|
||
INDEX { inv_Index }
|
||
-- INDEX { index }
|
||
::= { inverter_Table 1 }
|
||
|
||
Inverter_Entry ::=
|
||
SEQUENCE {
|
||
inv_Index INTEGER,
|
||
inv_Nbr INTEGER,
|
||
inv_InCurrent INTEGER,
|
||
inv_OutCurrent INTEGER,
|
||
inv_Temperature INTEGER,
|
||
inv_InputVoltage INTEGER,
|
||
inv_STi_great INTEGER,
|
||
inv_Fan INTEGER,
|
||
inv_RemoteOffCan INTEGER,
|
||
inv_UoutOff INTEGER,
|
||
inv_Bit_ShortCircuit INTEGER,
|
||
inv_Bit_OutputVoltage INTEGER,
|
||
inv_Bit_InputVoltLow INTEGER,
|
||
inv_Bit_InputVoltHigh INTEGER,
|
||
inv_Bit_OutputVoltLow INTEGER,
|
||
inv_Bit_OutputVoltHigh INTEGER,
|
||
inv_Bit_OutputCurrHigh INTEGER,
|
||
inv_Bit_RemoteOff INTEGER,
|
||
inv_Bit_CentralAlarm INTEGER,
|
||
inv_Type DisplayString,
|
||
inv_Mat_CD DisplayString,
|
||
inv_SerialNo DisplayString,
|
||
inv_HardwareVersion DisplayString,
|
||
inv_SoftwareVersion DisplayString
|
||
}
|
||
|
||
inv_Index OBJECT-TYPE
|
||
SYNTAX INTEGER (1..16)
|
||
UNITS "NA"
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"NA"
|
||
::= { inverter_Entry 0 }
|
||
|
||
inv_Nbr OBJECT-TYPE
|
||
SYNTAX INTEGER (0..15)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Inverter Number,
|
||
Value:
|
||
1
|
||
...
|
||
15"
|
||
::= { inverter_Entry 1 }
|
||
|
||
inv_InCurrent OBJECT-TYPE
|
||
SYNTAX INTEGER(0..65535)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "In-Current of the Inverter,
|
||
Value:
|
||
todo"
|
||
::= { inverter_Entry 2 }
|
||
|
||
inv_OutCurrent OBJECT-TYPE
|
||
SYNTAX INTEGER (0..65535)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Out-Current of the Inverter,
|
||
Value:
|
||
todo"
|
||
::= { inverter_Entry 3 }
|
||
|
||
inv_Temperature OBJECT-TYPE
|
||
SYNTAX INTEGER (0..65535)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Temperature of the Inverter,
|
||
Value:
|
||
todo"
|
||
::= { inverter_Entry 4 }
|
||
|
||
inv_InputVoltage OBJECT-TYPE
|
||
SYNTAX INTEGER (0..65535)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Input Voltage of the Inverter,
|
||
Value:
|
||
todo"
|
||
::= { inverter_Entry 5 }
|
||
|
||
inv_STi_great OBJECT-TYPE
|
||
SYNTAX INTEGER (0..1)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Internal temperature high,
|
||
Value:
|
||
0= < limit
|
||
1= > limit"
|
||
::= { inverter_Entry 6 }
|
||
|
||
inv_Fan OBJECT-TYPE
|
||
SYNTAX INTEGER (0..1)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Fan error,
|
||
Value:
|
||
0= no Error
|
||
1= error active"
|
||
::= { inverter_Entry 7 }
|
||
|
||
inv_RemoteOffCan OBJECT-TYPE
|
||
SYNTAX INTEGER (0..1)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Far off via can-controll,
|
||
Value:
|
||
0= not off
|
||
1= far off is active"
|
||
::= { inverter_Entry 8 }
|
||
|
||
inv_UoutOff OBJECT-TYPE
|
||
SYNTAX INTEGER (0..1)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "State of Output voltage,
|
||
Value:
|
||
0= voltage is on
|
||
1= voltage shut down"
|
||
::= { inverter_Entry 9 }
|
||
|
||
inv_Bit_ShortCircuit OBJECT-TYPE
|
||
SYNTAX INTEGER (0..1)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Short circuit is present,
|
||
Value:
|
||
0= normal operation
|
||
1= Short circuit"
|
||
::= { inverter_Entry 10 }
|
||
|
||
inv_Bit_OutputVoltage OBJECT-TYPE
|
||
SYNTAX INTEGER (0..1)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "State of the output voltage,
|
||
Value:
|
||
0= voltage off, error state
|
||
1= voltage ok,normal operation"
|
||
::= { inverter_Entry 11 }
|
||
|
||
inv_Bit_InputVoltLow OBJECT-TYPE
|
||
SYNTAX INTEGER (0..1)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Input voltage reached lover limit,
|
||
Value:
|
||
0= normal operation
|
||
1= error present"
|
||
::= { inverter_Entry 12 }
|
||
|
||
inv_Bit_InputVoltHigh OBJECT-TYPE
|
||
SYNTAX INTEGER (0..1)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Input voltage reached upper limit,
|
||
Value:
|
||
0= normal operation
|
||
1= error present"
|
||
::= { inverter_Entry 13 }
|
||
|
||
inv_Bit_OutputVoltLow OBJECT-TYPE
|
||
SYNTAX INTEGER (0..1)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Output voltage reached lower limit,
|
||
Value:
|
||
0= normal operation
|
||
1= error present"
|
||
::= { inverter_Entry 14 }
|
||
|
||
inv_Bit_OutputVoltHigh OBJECT-TYPE
|
||
SYNTAX INTEGER (0..1)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Output voltage reached upper limit,
|
||
Value:
|
||
0= normal operation
|
||
1= error present"
|
||
::= { inverter_Entry 15 }
|
||
|
||
inv_Bit_OutputCurrHigh OBJECT-TYPE
|
||
SYNTAX INTEGER (0..1)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Output current reached upper limit,
|
||
Value:
|
||
0= normal operation
|
||
1= error present"
|
||
::= { inverter_Entry 16 }
|
||
|
||
inv_Bit_RemoteOff OBJECT-TYPE
|
||
SYNTAX INTEGER (0..1)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Inverter has shut-down,
|
||
Value:
|
||
0= normal operation
|
||
1= shut-down"
|
||
::= { inverter_Entry 17 }
|
||
|
||
inv_Bit_CentralAlarm OBJECT-TYPE
|
||
SYNTAX INTEGER (0..1)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Central alarm has triggert,
|
||
Value:
|
||
0= normal operation
|
||
1= error present"
|
||
::= { inverter_Entry 18 }
|
||
|
||
inv_Type OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..16))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Type description"
|
||
::= { inverter_Entry 19 }
|
||
|
||
inv_Mat_CD OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..16))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Order number"
|
||
::= { inverter_Entry 20 }
|
||
|
||
inv_SerialNo OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..16))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Serial number"
|
||
::= { inverter_Entry 21 }
|
||
|
||
inv_HardwareVersion OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..8))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Hardware version"
|
||
::= { inverter_Entry 22 }
|
||
|
||
inv_SoftwareVersion OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..8))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Software Version"
|
||
::= { inverter_Entry 23 }
|
||
-- ****************************************
|
||
-- ****************************************
|
||
-- ****************************************
|
||
-- History
|
||
|
||
historyTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HistoryEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "Table of last 20 history events."
|
||
::= { tables 1 }
|
||
|
||
historyEntry OBJECT-TYPE
|
||
SYNTAX HistoryEntry
|
||
ACCESS not-accessible
|
||
STATUS optional
|
||
DESCRIPTION "History values entries."
|
||
INDEX { histIndex }
|
||
-- INDEX { index }
|
||
::= { historyTable 1 }
|
||
|
||
HistoryEntry ::=
|
||
SEQUENCE {
|
||
histIndex INTEGER,
|
||
histInd INTEGER,
|
||
histDateTime INTEGER,
|
||
histEvent INTEGER,
|
||
histDescription DisplayString
|
||
}
|
||
|
||
histIndex OBJECT-TYPE
|
||
SYNTAX INTEGER (1..20)
|
||
UNITS "NA"
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION "Index"
|
||
::= { historyEntry 0 }
|
||
|
||
histInd OBJECT-TYPE
|
||
SYNTAX INTEGER (1..65535)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Index"
|
||
::= { historyEntry 1 }
|
||
|
||
histDateTime OBJECT-TYPE
|
||
SYNTAX INTEGER(0..400000000)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Date and time of event in UNIX notation"
|
||
::= { historyEntry 2 }
|
||
|
||
histEvent OBJECT-TYPE
|
||
SYNTAX INTEGER (1..65535)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "History event"
|
||
::= { historyEntry 3 }
|
||
|
||
--histDescription OBJECT-TYPE
|
||
-- SYNTAX DisplayString (SIZE (0..16))
|
||
-- ACCESS read-only
|
||
-- STATUS mandatory
|
||
-- DESCRIPTION "textual description of event"
|
||
--::= { historyEntry 4 }
|
||
|
||
END
|