-- Copyright 2014 Electroline Equipment Inc
|
|
-- All Rights Reserved
|
|
--
|
|
--
|
|
--**************************************************************************
|
|
-- Filename : ELECTROLINE-DHT-BATTERY-MANAGER.mib
|
|
-- Author : Anass El bahri
|
|
-- Creation Date : 2014.05.26
|
|
--
|
|
--**************************************************************************
|
|
-- Description:
|
|
--
|
|
-- This MIB contains all battery manager extension
|
|
--
|
|
--**************************************************************************
|
|
-- Revision History:
|
|
-- 2014.05.26 Anass El bahri First Draft
|
|
-- 2015.03.19 Emilian Bajenaru Added support for the new coordinator fields
|
|
-- and new environmental data command
|
|
-- 2015.04.20 Alain Leclerc Modification following code review
|
|
-- 2015.05.28 Hugues Bielinski Changed hyphens ( - ) lines that may be illegals
|
|
-- in ASN1 for stars ( * ) lines
|
|
-- 2015.08.18 Emilian Bajenaru Added Electroline Identity to Cyberpower; added log
|
|
--
|
|
--**************************************************************************
|
|
|
|
ELECTROLINE-DHT-BATTERIES-CONTROLLER-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
MODULE-IDENTITY,
|
|
OBJECT-TYPE,
|
|
Integer32, Counter32
|
|
FROM SNMPv2-SMI
|
|
DisplayString
|
|
FROM RFC1213-MIB
|
|
TruthValue, DateAndTime
|
|
FROM SNMPv2-TC
|
|
dhtExtensionsMibObjects
|
|
FROM ELECTROLINE-DHT-EXTENSIONS-MIB;
|
|
|
|
-- Textual Conventions
|
|
HundredthmOhm ::= TEXTUAL-CONVENTION
|
|
DISPLAY-HINT "d-2"
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This data type represents impedance values that are normally
|
|
expressed in mOhms. Units are in hundredths of a mOhm;
|
|
for example, 5.12 mOhms will be represented as 512."
|
|
SYNTAX Integer32
|
|
|
|
HundredthkS ::= TEXTUAL-CONVENTION
|
|
DISPLAY-HINT "d-2"
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This data type represents conductance values that are normally
|
|
expressed in kiloSiemens. Units are in hundredths of a kS;
|
|
for example, 1.23 kS will be represented as 123."
|
|
SYNTAX Integer32
|
|
|
|
battManIdentMIB MODULE-IDENTITY
|
|
LAST-UPDATED "201508200000Z"
|
|
ORGANIZATION "Electroline Equipment Inc"
|
|
CONTACT-INFO
|
|
"Electroline Equipment Inc.
|
|
E-mail: support@electroline.com
|
|
Telephone:
|
|
(514) 374-6335
|
|
(800)-461-3344 (Toll-free - North America)
|
|
"
|
|
DESCRIPTION
|
|
"This set of objects monitor and control vendors battery manager that may be present and connected to the DHT.
|
|
This file includes control objects and status objects.
|
|
"
|
|
REVISION "201503190000Z"
|
|
DESCRIPTION
|
|
"Improved Env. support version of this MIB module."
|
|
REVISION "201504200000Z"
|
|
DESCRIPTION
|
|
"Added control table"
|
|
REVISION "201508200000Z"
|
|
DESCRIPTION
|
|
"Added Log table"
|
|
|
|
::= { dhtExtensionsMibObjects 16 }
|
|
|
|
--******************************
|
|
-- battery manager objects
|
|
--******************************
|
|
|
|
battManIdentObjects OBJECT IDENTIFIER ::= { battManIdentMIB 1 }
|
|
|
|
-- batteries managers monitored
|
|
|
|
battManMonitored OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of battery managers connected to this NE."
|
|
::= { battManIdentObjects 1 }
|
|
|
|
--******************************
|
|
-- battery managers device table
|
|
--******************************
|
|
|
|
-- battery managers table
|
|
|
|
battManDeviceTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF BattManDeviceEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Table containing information about the individual
|
|
battery manager being monitored."
|
|
::= { battManIdentObjects 2 }
|
|
|
|
-- battery managers table entry
|
|
|
|
battManDeviceEntry OBJECT-TYPE
|
|
SYNTAX BattManDeviceEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"List of information about each battery manager being monitored."
|
|
INDEX { battManDeviceAddress }
|
|
::= { battManDeviceTable 1 }
|
|
|
|
-- battery managers entry sequence
|
|
|
|
BattManDeviceEntry ::=
|
|
SEQUENCE
|
|
{
|
|
battManDeviceAddress
|
|
INTEGER,
|
|
|
|
battManProtocolVersion
|
|
INTEGER,
|
|
|
|
battManSoftwareVersion
|
|
OCTET STRING,
|
|
|
|
battManDeviceId
|
|
OCTET STRING,
|
|
|
|
battManVendorIdentity
|
|
OCTET STRING,
|
|
|
|
battManStringVoltage
|
|
INTEGER,
|
|
|
|
battManBatteries
|
|
INTEGER,
|
|
|
|
battManBatteryStrings
|
|
INTEGER,
|
|
|
|
battManBatteriesPerStrings
|
|
INTEGER,
|
|
|
|
battManVoltageSupport
|
|
INTEGER,
|
|
|
|
battManTemperatureSupport
|
|
INTEGER,
|
|
|
|
battManImpedanceSupport
|
|
INTEGER,
|
|
|
|
battManEqualPercentSupport
|
|
INTEGER,
|
|
|
|
battManBatteryStatusSupport
|
|
INTEGER,
|
|
|
|
battManDiagSupport
|
|
INTEGER,
|
|
|
|
battManEnvDataSupport
|
|
INTEGER,
|
|
|
|
battManManualMeasurementSupport
|
|
INTEGER
|
|
|
|
}
|
|
|
|
-- battery Manager device address
|
|
|
|
battManDeviceAddress OBJECT-TYPE
|
|
SYNTAX INTEGER ( 17..127 )
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Index into the battManDeviceTable.Address of this device on the RS-485 path"
|
|
::= { battManDeviceEntry 1 }
|
|
|
|
-- battery Manager protocol version
|
|
|
|
battManProtocolVersion OBJECT-TYPE
|
|
SYNTAX INTEGER ( 1..254 )
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Version of the protocol implemented in the monitored equipment."
|
|
|
|
::= { battManDeviceEntry 2 }
|
|
|
|
-- battery Manager software version
|
|
|
|
battManSoftwareVersion OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The content of this field is vendor specific. The intent is to provide
|
|
a text representation of the monitored device system software
|
|
version. Any printable ASCII characters can be included in this field.
|
|
NULL (0x00) characters are non-printable and are used to fill any unused
|
|
locations following the text data"
|
|
|
|
::= { battManDeviceEntry 3 }
|
|
|
|
-- battery Manager ID
|
|
|
|
battManDeviceId OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(32))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The content of this field is vendor specific. The intent is to provide
|
|
manufacturer and/or product specific ASCII text information."
|
|
::= { battManDeviceEntry 4 }
|
|
|
|
-- battery Manager vendor identity
|
|
|
|
battManVendorIdentity OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(10))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The content of this field is vendor specific. The intent is to provide
|
|
a text representation of the battery manager vendor identity. Any
|
|
printable ASCII characters can be included in this field. NULL (0x00)
|
|
characters are non-printable and are used to fill any unused locations
|
|
following the text data."
|
|
|
|
::= { battManDeviceEntry 5 }
|
|
|
|
|
|
-- battery Manager string voltage
|
|
|
|
battManStringVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Current string voltage configuration."
|
|
::= { battManDeviceEntry 6 }
|
|
|
|
-- battery Manager number of batteries
|
|
|
|
battManBatteries OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Current number of batteries."
|
|
::= { battManDeviceEntry 7 }
|
|
|
|
-- battery Manager number of strings
|
|
|
|
battManBatteryStrings OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Current number of strings."
|
|
::= { battManDeviceEntry 8 }
|
|
|
|
-- battery Manager number of batteries per string
|
|
|
|
battManBatteriesPerStrings OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Current number of batteries per string."
|
|
::= { battManDeviceEntry 9 }
|
|
|
|
-- battery Manager voltage support
|
|
|
|
battManVoltageSupport OBJECT-TYPE
|
|
SYNTAX INTEGER { none(1), supported(2)}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Defines if the voltage measurement is supported
|
|
1 = No support.
|
|
2 = Field is supported in this installation."
|
|
::= { battManDeviceEntry 10 }
|
|
|
|
-- battery Manager temperature support
|
|
|
|
battManTemperatureSupport OBJECT-TYPE
|
|
SYNTAX INTEGER { none(1), supported(2)}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Defines if the temperature measurement is supported
|
|
1 = No support.
|
|
2 = Field is supported in this installation."
|
|
::= { battManDeviceEntry 11 }
|
|
|
|
-- battery Manager impedance support
|
|
|
|
battManImpedanceSupport OBJECT-TYPE
|
|
SYNTAX INTEGER { none(1), supported(2)}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Defines if the impedance measurement is supported
|
|
1 = No support.
|
|
2 = Field is supported in this installation."
|
|
::= { battManDeviceEntry 12 }
|
|
|
|
-- battery Manager equalization percent support
|
|
|
|
battManEqualPercentSupport OBJECT-TYPE
|
|
SYNTAX INTEGER { none(1), supported(2)}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Defines if the equlization percent measurement is supported
|
|
1 = No support.
|
|
2 = Field is supported in this installation."
|
|
::= { battManDeviceEntry 13 }
|
|
|
|
-- battery Manager status support
|
|
|
|
battManBatteryStatusSupport OBJECT-TYPE
|
|
SYNTAX INTEGER { none(1), supported(2)}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Defines if the battery status monitoring is supported
|
|
1 = No support.
|
|
2 = Field is supported in this installation."
|
|
::= { battManDeviceEntry 14 }
|
|
|
|
-- battery manager modules diagnostics support
|
|
|
|
battManDiagSupport OBJECT-TYPE
|
|
SYNTAX INTEGER { none(1), supported(2)}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Defines if the battery manager modules diagnostics monitoring is supported
|
|
1 = No support.
|
|
2 = Field is supported in this installation."
|
|
::= { battManDeviceEntry 15 }
|
|
|
|
-- battery manager environment data feature
|
|
|
|
battManEnvDataSupport OBJECT-TYPE
|
|
SYNTAX INTEGER { none(1), supported(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Defines if the battery manager environment data is supported
|
|
1 = No support.
|
|
2 = The Environment Data table is supported in this installation."
|
|
::= { battManDeviceEntry 16 }
|
|
|
|
-- battery manager manual measurement feature
|
|
|
|
battManManualMeasurementSupport OBJECT-TYPE
|
|
SYNTAX INTEGER { none(1), supported(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Defines if the battery manager manualy triggered measurement is supported
|
|
1 = No support.
|
|
2 = The Manual Measurement table is supported in this installation."
|
|
::= { battManDeviceEntry 17 }
|
|
|
|
--******************************
|
|
-- string table
|
|
--******************************
|
|
|
|
-- string table
|
|
|
|
battManStringTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF BattManStringEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Table containing strings data"
|
|
::= { battManIdentObjects 3 }
|
|
|
|
-- string table entry
|
|
|
|
battManStringEntry OBJECT-TYPE
|
|
SYNTAX BattManStringEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"List of information about each string. Indexed by string number"
|
|
INDEX { battManStringDeviceAddress, battManString }
|
|
::= { battManStringTable 1 }
|
|
|
|
-- string table entry sequence
|
|
|
|
BattManStringEntry ::=
|
|
SEQUENCE
|
|
{
|
|
battManStringDeviceAddress
|
|
INTEGER,
|
|
|
|
battManString
|
|
INTEGER,
|
|
|
|
battManStringBatteries
|
|
INTEGER,
|
|
|
|
battManStringTotalVoltage
|
|
INTEGER
|
|
}
|
|
|
|
-- string device address
|
|
|
|
battManStringDeviceAddress OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Index into the battManStringTable. Corresponds to battManDeviceAddress in battManDeviceTable "
|
|
::= { battManStringEntry 1 }
|
|
|
|
-- string index
|
|
|
|
battManString OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Index into the battManStringTable."
|
|
::= { battManStringEntry 2 }
|
|
|
|
-- string number of batteries
|
|
|
|
battManStringBatteries OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"number of batteries."
|
|
::= { battManStringEntry 3 }
|
|
|
|
-- total string voltage
|
|
|
|
battManStringTotalVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Scaled representation of an individual string total voltage in 1/100 Volts
|
|
|
|
This item requires an entry in the properties MIB."
|
|
::= { battManStringEntry 4 }
|
|
|
|
--******************************
|
|
-- battery table
|
|
--******************************
|
|
|
|
-- battery table
|
|
|
|
battManBatteryTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF BattManBatteryEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Table containing batteries data"
|
|
::= { battManIdentObjects 4 }
|
|
|
|
-- battery table entry
|
|
|
|
battManBatteryEntry OBJECT-TYPE
|
|
SYNTAX BattManBatteryEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"List of information about each battery. Indexed by battery number"
|
|
INDEX { battManBatteryDeviceAddress,battManBatteryStringID, battManBattery }
|
|
::= { battManBatteryTable 1 }
|
|
|
|
-- battery table sequence
|
|
|
|
BattManBatteryEntry ::=
|
|
SEQUENCE
|
|
{
|
|
battManBatteryDeviceAddress
|
|
INTEGER,
|
|
|
|
battManBattery
|
|
INTEGER,
|
|
|
|
battManBatteryStringID
|
|
INTEGER,
|
|
|
|
battManBatteryVersion
|
|
INTEGER,
|
|
|
|
battManBatteryHwVersion
|
|
OCTET STRING,
|
|
|
|
battManBatterySwVersion
|
|
OCTET STRING,
|
|
|
|
battManBatteryVoltage
|
|
INTEGER,
|
|
|
|
battManBatteryTemperature
|
|
INTEGER,
|
|
|
|
battManBatteryImpedance
|
|
INTEGER,
|
|
|
|
battManBatteryEqualizationPercent
|
|
INTEGER,
|
|
|
|
battManBatteryStatus
|
|
INTEGER,
|
|
|
|
battManBatteryDatasetID
|
|
Unsigned32
|
|
}
|
|
|
|
-- battery string index
|
|
|
|
battManBatteryDeviceAddress OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Index into the battManBatteryTable. Corresponds to battManDeviceAddress in battManDeviceTable "
|
|
::= { battManBatteryEntry 1 }
|
|
|
|
-- battery index
|
|
|
|
battManBattery OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Index into the battManBatteryTable."
|
|
::= { battManBatteryEntry 2 }
|
|
|
|
-- battery string id
|
|
|
|
battManBatteryStringID OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"id of the string that this battery belongs to."
|
|
::= { battManBatteryEntry 3 }
|
|
|
|
-- battery version
|
|
|
|
battManBatteryVersion OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"battery module version."
|
|
::= { battManBatteryEntry 4 }
|
|
|
|
-- battery hardware version
|
|
|
|
battManBatteryHwVersion OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The content of this field is vendor specific. The intent is to provide
|
|
a text representation of the battery system hardware version. Any printable
|
|
ASCII characters can be included in this field. NULL (0x00) characters
|
|
are non-printable and are used to fill any unused locations following the text data."
|
|
::= { battManBatteryEntry 5 }
|
|
|
|
-- battery software version
|
|
|
|
battManBatterySwVersion OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The content of this field is vendor specific. The intent is to provide
|
|
a text representation of the battery system software version. Any printable
|
|
ASCII characters can be included in this field. NULL (0x00) characters
|
|
are non-printable and are used to fill any unused locations following the text data."
|
|
::= { battManBatteryEntry 6 }
|
|
|
|
-- battery voltage
|
|
|
|
battManBatteryVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Scaled representation of an individual battery voltage in 1/100 Volts
|
|
with a range of 0 to 16.000 volts
|
|
|
|
This item requires an entry in the properties MIB."
|
|
::= { battManBatteryEntry 7 }
|
|
|
|
-- battery temperature
|
|
|
|
battManBatteryTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Scaled representation of temperature in degrees C
|
|
with a range of -40 to + 80 degrees C.
|
|
|
|
This item requires an entry in the properties MIB."
|
|
::= { battManBatteryEntry 8 }
|
|
|
|
-- battery impedance
|
|
|
|
battManBatteryImpedance OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Scaled representation of an individual battery impedance in 1/100 mOhm
|
|
with a range of 0 to 99.99 mOhm.
|
|
|
|
This item requires an entry in the properties MIB."
|
|
::= { battManBatteryEntry 9 }
|
|
|
|
-- battery equalization percent
|
|
|
|
battManBatteryEqualizationPercent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Reports the battery equalization percent with a range of 0 to 100%.
|
|
|
|
This item requires an entry in the properties MIB."
|
|
::= { battManBatteryEntry 10 }
|
|
|
|
-- battery status
|
|
|
|
battManBatteryStatus OBJECT-TYPE
|
|
SYNTAX INTEGER { ok(1), alarm(2)}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Reports the status of the battery
|
|
|
|
1. ok
|
|
2. alarm
|
|
|
|
This item requires an entry in the discrete properties MIB."
|
|
::= { battManBatteryEntry 11 }
|
|
|
|
-- battery DatasetID
|
|
|
|
battManBatteryDatasetID OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The DatasetID of the measurement done for this battery."
|
|
::= { battManBatteryEntry 12 }
|
|
|
|
--******************************
|
|
-- battery diagnostics table
|
|
--******************************
|
|
|
|
-- battery diagnostics table
|
|
|
|
battManBatteryDiagTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF BattManBatteryDiagEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Table containing battery diagnostic data"
|
|
::= { battManIdentObjects 5 }
|
|
|
|
-- battery diagnostics table entry
|
|
|
|
battManBatteryDiagEntry OBJECT-TYPE
|
|
SYNTAX BattManBatteryDiagEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"List of diagnostic information about each battery. Indexed by battery number"
|
|
INDEX { battManBatteryDiagDeviceAddress, battManBatteryDiagModuleID }
|
|
::= { battManBatteryDiagTable 1 }
|
|
|
|
-- battery diagnostics table sequence
|
|
|
|
BattManBatteryDiagEntry ::=
|
|
SEQUENCE
|
|
{
|
|
battManBatteryDiagDeviceAddress
|
|
INTEGER,
|
|
|
|
battManBatteryDiagModuleID
|
|
INTEGER,
|
|
|
|
battManBatteryDiagPageNumber
|
|
INTEGER,
|
|
|
|
battManBatteryDiagPageData
|
|
OCTET STRING
|
|
}
|
|
|
|
-- battery diagnostics device address
|
|
|
|
battManBatteryDiagDeviceAddress OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Index into the battManBatteryDiagTable. Corresponds to battManDeviceAddress in battManDeviceTable "
|
|
::= { battManBatteryDiagEntry 1 }
|
|
|
|
-- battery module ID
|
|
|
|
battManBatteryDiagModuleID OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Index into the battManBatteryDiagTable."
|
|
::= { battManBatteryDiagEntry 2 }
|
|
|
|
-- battery diagnostics page number
|
|
|
|
battManBatteryDiagPageNumber OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"the data page number."
|
|
::= { battManBatteryDiagEntry 3 }
|
|
|
|
-- battery diagnostics data
|
|
|
|
battManBatteryDiagPageData OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(20))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The content of this field is vendor specific. The intent is to provide
|
|
a text representation of the particular information of the identified module.
|
|
when an invalid page number is requested, this field will be returned with a length of 0."
|
|
::= { battManBatteryDiagEntry 4 }
|
|
|
|
|
|
--******************************
|
|
-- battery manager control/config table
|
|
--******************************
|
|
|
|
-- battery manager control/config table
|
|
|
|
battManControlTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF BattManControlEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Table containing battery managers control settings."
|
|
::= { battManIdentObjects 6 }
|
|
|
|
-- battery manager control/configuration entry
|
|
|
|
battManControlEntry OBJECT-TYPE
|
|
SYNTAX BattManControlEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"List of controls about each battery manager. Indexed by battManControlDeviceAddress"
|
|
INDEX { battManControlDeviceAddress }
|
|
::= { battManControlTable 1 }
|
|
|
|
-- battery manager control/config sequence
|
|
|
|
BattManControlEntry ::=
|
|
SEQUENCE
|
|
{
|
|
battManControlDeviceAddress
|
|
INTEGER,
|
|
|
|
battManControlEqualizationSetting
|
|
INTEGER,
|
|
|
|
battManControlAutoInterval
|
|
INTEGER,
|
|
|
|
battManControlSensorsRestart
|
|
INTEGER
|
|
}
|
|
|
|
-- battery manager control/config device address
|
|
|
|
battManControlDeviceAddress OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Index into the battManControlStatusTable. Corresponds to battManDeviceAddress in battManDeviceTable "
|
|
::= { battManControlEntry 1 }
|
|
|
|
-- battery manager equalization
|
|
|
|
battManControlEqualizationSetting OBJECT-TYPE
|
|
SYNTAX INTEGER { activated(1), deactivated(2)}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Represents the equalization status.
|
|
|
|
1 means equalization activated
|
|
2 means equalization deactivated
|
|
"
|
|
::= { battManControlEntry 2 }
|
|
|
|
-- battery manager status automeasurement interval
|
|
|
|
battManControlAutoInterval OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Represents the period (in hours) used to take automated measurements
|
|
The value 0 deactivates the automated measurements"
|
|
::= { battManControlEntry 3 }
|
|
|
|
-- battery manager status sensors restart
|
|
|
|
battManControlSensorsRestart OBJECT-TYPE
|
|
SYNTAX INTEGER { true(1), false(2) }
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Restart the sensors. Reading the object returns false(2), and has no effect on the unit."
|
|
::= { battManControlEntry 4 }
|
|
|
|
|
|
|
|
--------------------------------------
|
|
-- battery manager status table
|
|
--------------------------------------
|
|
|
|
-- battery manager status table
|
|
|
|
battManStatusTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF BattManStatusEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Table containing battery managers status data."
|
|
::= { battManIdentObjects 7 }
|
|
|
|
-- battery manager status entry
|
|
|
|
battManStatusEntry OBJECT-TYPE
|
|
SYNTAX BattManStatusEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"List of status information about each battery manager. Indexed by battManEnvDeviceAddress"
|
|
INDEX { battManStatusDeviceAddress }
|
|
::= { battManStatusTable 1 }
|
|
|
|
-- battery manager status sequence
|
|
|
|
BattManStatusEntry ::=
|
|
SEQUENCE
|
|
{
|
|
battManStatusDeviceAddress
|
|
INTEGER,
|
|
|
|
battManStatusTimeToMeasurement
|
|
Unsigned32
|
|
}
|
|
|
|
-- battery manager status device address
|
|
|
|
battManStatusDeviceAddress OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Index into the battManStatusTable. Corresponds to battManDeviceAddress in battManDeviceTable "
|
|
::= { battManStatusEntry 1 }
|
|
|
|
-- battery manager status equalization
|
|
|
|
-- battery manager status time before next measurement
|
|
battManStatusTimeToMeasurement OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the remaining time (in seconds) before next automated measurement.
|
|
If the automated measurement is deactivated, then the return value is always 0."
|
|
::= { battManStatusEntry 2 }
|
|
|
|
--***********************************************
|
|
-- battery manager EnvironmentalStatus table
|
|
--***********************************************
|
|
|
|
-- battery manager EnvironmentalStatus table
|
|
|
|
battManEnvStatusTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF BattManEnvStatusEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Table containing battery manager's Environmental Status data."
|
|
::= { battManIdentObjects 8 }
|
|
|
|
-- battery manager status entry
|
|
|
|
battManEnvStatusEntry OBJECT-TYPE
|
|
SYNTAX BattManEnvStatusEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"List of Environmental Status information about each battery manager. Indexed by battManEnvDeviceAddress"
|
|
INDEX { battManEnvStatusDeviceAddress }
|
|
::= { battManEnvStatusTable 1 }
|
|
|
|
-- battery manager EnvironmentalStatus sequence
|
|
|
|
BattManEnvStatusEntry ::=
|
|
SEQUENCE
|
|
{
|
|
battManEnvStatusDeviceAddress
|
|
INTEGER,
|
|
|
|
battManEnvStatusTemperature
|
|
INTEGER,
|
|
|
|
battManEnvStatusHumidity
|
|
INTEGER,
|
|
|
|
battManEnvStatusDryContact
|
|
INTEGER
|
|
}
|
|
|
|
-- battery manager EnvironmentalStatus device address
|
|
|
|
battManEnvStatusDeviceAddress OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Index into the battManEnvStatusTable. Corresponds to battManDeviceAddress in battManDeviceTable "
|
|
::= { battManEnvStatusEntry 1 }
|
|
|
|
-- battery manager EnvironmentalStatus temperature
|
|
|
|
battManEnvStatusTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Scaled representation of battery manager temperature in degrees C
|
|
|
|
This item requires an entry in the properties MIB."
|
|
::= { battManEnvStatusEntry 2 }
|
|
|
|
-- battery manager EnvironmentalStatus humidity
|
|
|
|
battManEnvStatusHumidity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Scaled representation of battery manager humidity percent. "
|
|
::= { battManEnvStatusEntry 3 }
|
|
|
|
-- battery manager status dry contact
|
|
|
|
battManEnvStatusDryContact OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"bit map that indicates the state of the dry contacts. bit set means the corresponding dry contact is closed
|
|
Bits Dry Contact
|
|
0 dry contact1
|
|
1 dry contact2
|
|
2 dry contact3
|
|
3 dry contact4
|
|
"
|
|
::= { battManEnvStatusEntry 4 }
|
|
|
|
--*******************************************
|
|
-- battery manager ManualMeasurement table
|
|
--*******************************************
|
|
|
|
-- battery manager ManualMeasurement table
|
|
|
|
battManManualMeasTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF BattManManualMeasEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Table containing battery manager's Manual Measurement trigger command and response data."
|
|
::= { battManIdentObjects 9 }
|
|
|
|
-- battery manager ManualMeasurement status entry
|
|
|
|
battManManualMeasEntry OBJECT-TYPE
|
|
SYNTAX BattManManualMeasEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"List of ManualMeasurement Status information about each battery manager. Indexed by battManEnvDeviceAddress"
|
|
INDEX { battManManualMeasDeviceAddress }
|
|
::= { battManManualMeasTable 1 }
|
|
|
|
-- battery manager ManualMeasurementStatus sequence
|
|
|
|
BattManManualMeasEntry ::=
|
|
SEQUENCE
|
|
{
|
|
battManManualMeasDeviceAddress
|
|
INTEGER,
|
|
|
|
battManManualMeasStatusText
|
|
OCTET STRING,
|
|
|
|
battManManualMeasStatusCode
|
|
Unsigned32,
|
|
|
|
battManManualMeasDatasetID
|
|
Unsigned32,
|
|
|
|
battManManualMeasTimeToMeasurement
|
|
Unsigned32,
|
|
|
|
battManManualMeasurementTrigger
|
|
INTEGER
|
|
}
|
|
|
|
-- battery manager ManualMeasurement device address
|
|
|
|
battManManualMeasDeviceAddress OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Index into the battManManualMeasStatusTable. Corresponds to battManDeviceAddress in battManDeviceTable "
|
|
::= { battManManualMeasEntry 1 }
|
|
|
|
-- battery manager ManualMeasurement Human Readable Status Code
|
|
|
|
battManManualMeasStatusText OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(80))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Short phrase describing the manual measurement status."
|
|
::= { battManManualMeasEntry 2 }
|
|
|
|
-- battery manager ManualMeasurement Status Code
|
|
|
|
battManManualMeasStatusCode OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"0: Taking measurement now.
|
|
1: Equalizer on, the measurement will be ready in 5 minutes.
|
|
2: NACK, cannot take measurement now.
|
|
3: Waiting for controller information
|
|
"
|
|
::= { battManManualMeasEntry 3 }
|
|
|
|
-- battery manager ManualMeasurement DatasetID
|
|
|
|
battManManualMeasDatasetID OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Dataset ID of this measurement (When Status code 0 and 1 was returned by the trigger command). Reset to negative value when not applicable."
|
|
::= { battManManualMeasEntry 4 }
|
|
|
|
-- battery manager ManualMeasurement Time Before Allowed to do a Manual Measurement
|
|
|
|
battManManualMeasTimeToMeasurement OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"(When Status code 2 was returned by the trigger command): remaining time in seconds before a measurement can be done. Reset to negative value when not applicable."
|
|
::= { battManManualMeasEntry 5 }
|
|
|
|
|
|
-- battery manager ManualMeasurement Trigger Command
|
|
|
|
battManManualMeasurementTrigger OBJECT-TYPE
|
|
SYNTAX INTEGER { true(1), false(2) }
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Measurement manual trigger command. Then check the battManManualMeasTimeToMeasurement. When read always returns false(2)."
|
|
::= { battManManualMeasEntry 6 }
|
|
|
|
|
|
--***************************
|
|
-- battery manger settings
|
|
--***************************
|
|
|
|
battManDeviceSettings OBJECT IDENTIFIER ::= { battManIdentObjects 10 }
|
|
|
|
-- battery Manager string voltage settings
|
|
|
|
battManDevStringVoltsSetting OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"typical string voltage setting : 12,24,36,48.
|
|
both of battManStringCountSetting & battManStringVoltsSetting
|
|
are sent the battery manager. this object is maintained in non-volatile memory.
|
|
|
|
IMPORTANT : The system needs to reboot after each new setting. "
|
|
::= { battManDeviceSettings 1 }
|
|
|
|
-- battery Manager string count settings
|
|
|
|
battManDevStringCountSetting OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"the number of strings setting. both of battManStringCountSetting & battManStringVoltsSetting
|
|
are sent the battery manager. this object is maintained in non-volatile memory.
|
|
|
|
IMPORTANT : The system needs to reboot after each new setting. "
|
|
::= { battManDeviceSettings 2 }
|
|
|
|
-- modules diagnostics enable
|
|
|
|
battManDevDiagnoscticsSetting OBJECT-TYPE
|
|
SYNTAX INTEGER { true(1), false(2)}
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"enable or disable modules data diagnostics process. "
|
|
::= { battManDeviceSettings 3 }
|
|
|
|
--*******************************************
|
|
-- battery manager BatteryLog table
|
|
--*******************************************
|
|
|
|
-- battery log table
|
|
|
|
battManBatteryLogTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF BattManBatteryLogEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Table containing batteries data"
|
|
::= { battManIdentObjects 11 }
|
|
|
|
-- battery log entry
|
|
|
|
battManBatteryLogEntry OBJECT-TYPE
|
|
SYNTAX BattManBatteryLogEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"List of information about each battery. Indexed by battery number"
|
|
INDEX { battManBattLogDeviceAddress, battManBattLogDatasetID, battManBattLogStringID, battManBattLogBatteryID }
|
|
::= { battManBatteryLogTable 1 }
|
|
|
|
-- battery log sequence
|
|
|
|
BattManBatteryLogEntry ::=
|
|
SEQUENCE
|
|
{
|
|
battManBattLogDeviceAddress
|
|
INTEGER,
|
|
|
|
battManBattLogDatasetID
|
|
Unsigned32,
|
|
|
|
battManBattLogBatteryID
|
|
INTEGER,
|
|
|
|
battManBattLogStringID
|
|
INTEGER,
|
|
|
|
battManBattLogVoltage
|
|
INTEGER,
|
|
|
|
battManBattLogTemperature
|
|
INTEGER,
|
|
|
|
battManBattLogImpedance
|
|
HundredthmOhm,
|
|
|
|
battManBattLogConductance
|
|
HundredthkS,
|
|
|
|
battManBattLogTimestamp
|
|
DateAndTime
|
|
}
|
|
|
|
-- battery string index
|
|
|
|
battManBattLogDeviceAddress OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Index into the battManBatteryLog. Corresponds to battManDeviceAddress in battManDeviceTable "
|
|
::= { battManBatteryLogEntry 1 }
|
|
|
|
-- battery DatasetID
|
|
|
|
battManBattLogDatasetID OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The DatasetID of the measurement done for this battery."
|
|
::= { battManBatteryLogEntry 2 }
|
|
|
|
-- battery index
|
|
|
|
battManBattLogBatteryID OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Index into the battManBatteryLog."
|
|
::= { battManBatteryLogEntry 3 }
|
|
|
|
-- battery string id
|
|
|
|
battManBattLogStringID OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"id of the string that this battery belongs to."
|
|
::= { battManBatteryLogEntry 4 }
|
|
|
|
-- battery voltage
|
|
|
|
battManBattLogVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Scaled representation of an individual battery voltage in 1/100 Volts
|
|
with a range of 0 to 16.000 volts
|
|
|
|
This item requires an entry in the properties MIB."
|
|
::= { battManBatteryLogEntry 5 }
|
|
|
|
-- battery temperature
|
|
|
|
battManBattLogTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Scaled representation of temperature in degrees C
|
|
with a range of -40 to + 80 degrees C.
|
|
|
|
This item requires an entry in the properties MIB."
|
|
::= { battManBatteryLogEntry 6 }
|
|
|
|
-- battery impedance
|
|
|
|
battManBattLogImpedance OBJECT-TYPE
|
|
SYNTAX HundredthmOhm
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Scaled representation of an individual battery impedance in 1/100 mOhm
|
|
with a range of 0 to 99.99 mOhm.
|
|
|
|
This item requires an entry in the properties MIB."
|
|
::= { battManBatteryLogEntry 7 }
|
|
|
|
-- battery conductance
|
|
|
|
battManBattLogConductance OBJECT-TYPE
|
|
SYNTAX HundredthkS
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Scaled representation of an individual battery cell conductance in in 1/100 of Siemens
|
|
with a range of 6000 to 60000 Siemens (tbd)
|
|
|
|
This item requires an entry in the properties MIB."
|
|
::= { battManBatteryLogEntry 8 }
|
|
|
|
-- battery timestamp
|
|
|
|
battManBattLogTimestamp OBJECT-TYPE
|
|
SYNTAX DateAndTime
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Date and time when the measurement was taken.
|
|
|
|
This item requires an entry in the discrete properties MIB."
|
|
::= { battManBatteryLogEntry 9 }
|
|
|
|