741 lines
17 KiB
Plaintext
741 lines
17 KiB
Plaintext
-- DuraComm RMCU control MIB. Import this into your MIB Browser software.
|
|
-- This is for RMCU Rev2 Board
|
|
|
|
RMCU DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
--enterprises, IpAddress, Gauge, TimeTicks FROM RFC1155-SMI
|
|
DisplayString FROM RFC1213-MIB
|
|
OBJECT-TYPE FROM RFC-1212
|
|
TEXTUAL-CONVENTION FROM SNMPv2-TC
|
|
NOTIFICATION-TYPE, Gauge32, enterprises, MODULE-IDENTITY FROM SNMPv2-SMI
|
|
TRAP-TYPE FROM RFC-1215;
|
|
|
|
rmcu-r2v3 MODULE-IDENTITY
|
|
LAST-UPDATED "201710111300Z"
|
|
ORGANIZATION "Duracomm"
|
|
CONTACT-INFO "www.duracomm.com"
|
|
DESCRIPTION "RMCU Rev2 Board"
|
|
REVISION "201710111300Z"
|
|
DESCRIPTION "Revision"
|
|
::= { enterprises 15116 3 }
|
|
|
|
duracomm OBJECT IDENTIFIER ::= { enterprises 15116 }
|
|
|
|
product OBJECT IDENTIFIER ::= { rmcu-r2v3 1 }
|
|
control OBJECT IDENTIFIER ::= { rmcu-r2v3 2 }
|
|
control-ints OBJECT IDENTIFIER ::= { rmcu-r2v3 4 }
|
|
traps OBJECT IDENTIFIER ::= { rmcu-r2v3 3 }
|
|
|
|
-- ON-OFF ::= INTEGER { ON(1), OFF(0) }
|
|
|
|
FixedDiv1000 ::= TEXTUAL-CONVENTION
|
|
DISPLAY-HINT "d-3"
|
|
STATUS current
|
|
DESCRIPTION "Fixed point, thousandths"
|
|
SYNTAX Gauge32
|
|
|
|
name OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit name"
|
|
::= { product 1 }
|
|
|
|
|
|
version OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Software and hardware version"
|
|
::= { product 2 }
|
|
|
|
build-date OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Date of software was built"
|
|
::= { product 3 }
|
|
|
|
|
|
|
|
analog1name OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of analog input #1"
|
|
::= { control 1 }
|
|
|
|
analog1val OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Value of analog input #1"
|
|
::= { control 2 }
|
|
|
|
analog2name OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of analog input #2"
|
|
::= { control 3 }
|
|
|
|
analog2val OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Value of analog input #2"
|
|
::= { control 4 }
|
|
|
|
analog3name OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of analog input #3"
|
|
::= { control 5 }
|
|
|
|
analog3val OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Value of analog input #3"
|
|
::= { control 6 }
|
|
|
|
analog4name OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of analog input #4"
|
|
::= { control 7 }
|
|
|
|
analog4val OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Value of analog input #4"
|
|
::= { control 8 }
|
|
|
|
analog5name OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of analog input #5"
|
|
::= { control 9 }
|
|
|
|
analog5val OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Value of analog input #5"
|
|
::= { control 10 }
|
|
|
|
analog6name OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of analog input #6"
|
|
::= { control 11 }
|
|
|
|
analog6val OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Value of analog input #6"
|
|
::= { control 12 }
|
|
|
|
|
|
digin1name OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of digital input #1"
|
|
::= { control 33 }
|
|
|
|
digin1val OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Value of digital input #1"
|
|
::= { control 34 }
|
|
|
|
digin2name OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of digital input #2"
|
|
::= { control 35 }
|
|
|
|
digin2val OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Value of digital input #2"
|
|
::= { control 36 }
|
|
|
|
digin3name OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of digital input #3"
|
|
::= { control 37 }
|
|
|
|
digin3val OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Value of digital input #3"
|
|
::= { control 38 }
|
|
|
|
digin4name OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of digital input #4"
|
|
::= { control 39 }
|
|
|
|
digin4val OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Value of digital input #4"
|
|
::= { control 40 }
|
|
|
|
|
|
digout1name OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of digital output #1"
|
|
::= { control 65 }
|
|
|
|
digout1val OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Value of digital output #1"
|
|
::= { control 66 }
|
|
|
|
digout2name OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of digital output #2"
|
|
::= { control 67 }
|
|
|
|
digout2val OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Value of digital output #2"
|
|
::= { control 68 }
|
|
|
|
digout3name OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of digital output #3"
|
|
::= { control 69 }
|
|
|
|
digout3val OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Value of digital output #3"
|
|
::= { control 70 }
|
|
|
|
digout4name OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of digital output #4"
|
|
::= { control 71 }
|
|
|
|
digout4val OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Value of digital output #4"
|
|
::= { control 72 }
|
|
|
|
|
|
temperature OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature"
|
|
::= { control 97 }
|
|
|
|
acval OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"AC Line voltage"
|
|
::= { control 98 }
|
|
|
|
|
|
|
|
analog1val-int OBJECT-TYPE
|
|
SYNTAX FixedDiv1000
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Value of analog input #1"
|
|
::= { control-ints 1 }
|
|
|
|
analog2val-int OBJECT-TYPE
|
|
SYNTAX FixedDiv1000
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Value of analog input #2"
|
|
::= { control-ints 2 }
|
|
|
|
analog3val-int OBJECT-TYPE
|
|
SYNTAX FixedDiv1000
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Value of analog input #3"
|
|
::= { control-ints 3 }
|
|
|
|
analog4val-int OBJECT-TYPE
|
|
SYNTAX FixedDiv1000
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Value of analog input #4"
|
|
::= { control-ints 4 }
|
|
|
|
analog5val-int OBJECT-TYPE
|
|
SYNTAX FixedDiv1000
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Value of analog input #5"
|
|
::= { control-ints 5 }
|
|
|
|
analog6val-int OBJECT-TYPE
|
|
SYNTAX FixedDiv1000
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Value of analog input #6"
|
|
::= { control-ints 6 }
|
|
|
|
|
|
acval-int OBJECT-TYPE
|
|
SYNTAX FixedDiv1000
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"AC Line voltage"
|
|
::= { control-ints 17 }
|
|
|
|
temperature-int OBJECT-TYPE
|
|
SYNTAX FixedDiv1000
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature"
|
|
::= { control-ints 18 }
|
|
|
|
trap-auth NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by authorization failure"
|
|
::= {traps 1}
|
|
|
|
trap-analog-over1 NOTIFICATION-TYPE
|
|
OBJECTS {name, analog1val}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by analog input #1 being over threshold"
|
|
::= {traps 2}
|
|
|
|
trap-analog-over2 NOTIFICATION-TYPE
|
|
OBJECTS {name, analog2val}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by analog input #2 being over threshold"
|
|
::= {traps 3}
|
|
|
|
trap-analog-over3 NOTIFICATION-TYPE
|
|
OBJECTS {name, analog3val}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by analog input #3 being over threshold"
|
|
::= {traps 4}
|
|
|
|
trap-analog-over4 NOTIFICATION-TYPE
|
|
OBJECTS {name, analog4val}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by analog input #4 being over threshold"
|
|
::= {traps 5}
|
|
|
|
trap-analog-over5 NOTIFICATION-TYPE
|
|
OBJECTS {name, analog5val}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by analog input #5 being over threshold"
|
|
::= {traps 6}
|
|
|
|
trap-analog-over6 NOTIFICATION-TYPE
|
|
OBJECTS {name, analog6val}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by analog input #6 being over threshold"
|
|
::= {traps 7}
|
|
|
|
|
|
trap-analog-under1 NOTIFICATION-TYPE
|
|
OBJECTS {name, analog1val}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by analog input #1 being under threshold"
|
|
::= {traps 18}
|
|
|
|
trap-analog-under2 NOTIFICATION-TYPE
|
|
OBJECTS {name, analog2val}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by analog input #2 being under threshold"
|
|
::= {traps 19}
|
|
|
|
trap-analog-under3 NOTIFICATION-TYPE
|
|
OBJECTS {name, analog3val}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by analog input #3 being under threshold"
|
|
::= {traps 20}
|
|
|
|
trap-analog-under4 NOTIFICATION-TYPE
|
|
OBJECTS {name, analog4val}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by analog input #4 being under threshold"
|
|
::= {traps 21}
|
|
|
|
trap-analog-under5 NOTIFICATION-TYPE
|
|
OBJECTS {name, analog5val}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by analog input #5 being under threshold"
|
|
::= {traps 22}
|
|
|
|
trap-analog-under6 NOTIFICATION-TYPE
|
|
OBJECTS {name, analog6val}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by analog input #6 being under threshold"
|
|
::= {traps 23}
|
|
|
|
|
|
trap-poweron NOTIFICATION-TYPE
|
|
OBJECTS {name}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by power-on"
|
|
::= {traps 34}
|
|
|
|
trap-temp-over NOTIFICATION-TYPE
|
|
OBJECTS {name, temperature}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by temperature being over threshold"
|
|
::= {traps 35}
|
|
|
|
trap-dig-close1 NOTIFICATION-TYPE
|
|
OBJECTS {name, digin1val}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by digital input #1 closed"
|
|
::= {traps 36}
|
|
|
|
trap-dig-close2 NOTIFICATION-TYPE
|
|
OBJECTS {name, digin2val}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by digital input #2 closed"
|
|
::= {traps 37}
|
|
|
|
trap-dig-close3 NOTIFICATION-TYPE
|
|
OBJECTS {name, digin3val}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by digital input #3 closed"
|
|
::= {traps 38}
|
|
|
|
trap-dig-close4 NOTIFICATION-TYPE
|
|
OBJECTS {name, digin4val}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by digital input #4 closed"
|
|
::= {traps 39}
|
|
|
|
|
|
trap-test NOTIFICATION-TYPE
|
|
OBJECTS {name}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by user test"
|
|
::= {traps 52}
|
|
|
|
trap-dig-open1 NOTIFICATION-TYPE
|
|
OBJECTS {name, digin1val}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by digital input #1 open"
|
|
::= {traps 53}
|
|
|
|
trap-dig-open2 NOTIFICATION-TYPE
|
|
OBJECTS {name, digin2val}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by digital input #2 open"
|
|
::= {traps 54}
|
|
|
|
trap-dig-open3 NOTIFICATION-TYPE
|
|
OBJECTS {name, digin3val}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by digital input #3 open"
|
|
::= {traps 55}
|
|
|
|
trap-dig-open4 NOTIFICATION-TYPE
|
|
OBJECTS {name, digin4val}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by digital input #4 open"
|
|
::= {traps 56}
|
|
|
|
|
|
trap-ac-under NOTIFICATION-TYPE
|
|
OBJECTS {name, acval}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by AC under threshold"
|
|
::= {traps 69}
|
|
|
|
trap-ac-over NOTIFICATION-TYPE
|
|
OBJECTS {name, acval}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by AC over threshold"
|
|
::= {traps 70}
|
|
|
|
trap-temp-under NOTIFICATION-TYPE
|
|
OBJECTS {name, temperature}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by temperature being under threshold"
|
|
::= {traps 71}
|
|
|
|
trap-digout-inactive1 NOTIFICATION-TYPE
|
|
OBJECTS {name}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by digitout output #1 going inactive"
|
|
::= {traps 72}
|
|
|
|
trap-digout-inactive2 NOTIFICATION-TYPE
|
|
OBJECTS {name}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by digitout output #2 going inactive"
|
|
::= {traps 73}
|
|
|
|
trap-digout-inactive3 NOTIFICATION-TYPE
|
|
OBJECTS {name}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by digitout output #3 going inactive"
|
|
::= {traps 74}
|
|
|
|
trap-digout-inactive4 NOTIFICATION-TYPE
|
|
OBJECTS {name}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by digitout output #4 going inactive"
|
|
::= {traps 75}
|
|
|
|
|
|
trap-digout-active1 NOTIFICATION-TYPE
|
|
OBJECTS {name}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by digitout output #1 going active"
|
|
::= {traps 88}
|
|
|
|
trap-digout-active2 NOTIFICATION-TYPE
|
|
OBJECTS {name}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by digitout output #2 going active"
|
|
::= {traps 89}
|
|
|
|
trap-digout-active3 NOTIFICATION-TYPE
|
|
OBJECTS {name}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by digitout output #3 going active"
|
|
::= {traps 90}
|
|
|
|
trap-digout-active4 NOTIFICATION-TYPE
|
|
OBJECTS {name}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by digitout output #4 going active"
|
|
::= {traps 91}
|
|
|
|
|
|
trap-analog-urecover1 NOTIFICATION-TYPE
|
|
OBJECTS {name, analog1val}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by analog input #1 recovering from under alarm"
|
|
::= {traps 104}
|
|
|
|
trap-analog-urecover2 NOTIFICATION-TYPE
|
|
OBJECTS {name, analog2val}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by analog input #2 recovering from under alarm"
|
|
::= {traps 105}
|
|
|
|
trap-analog-urecover3 NOTIFICATION-TYPE
|
|
OBJECTS {name, analog3val}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by analog input #3 recovering from under alarm"
|
|
::= {traps 106}
|
|
|
|
trap-analog-urecover4 NOTIFICATION-TYPE
|
|
OBJECTS {name, analog4val}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by analog input #4 recovering from under alarm"
|
|
::= {traps 107}
|
|
|
|
trap-analog-urecover5 NOTIFICATION-TYPE
|
|
OBJECTS {name, analog5val}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by analog input #5 recovering from under alarm"
|
|
::= {traps 108}
|
|
|
|
trap-analog-urecover6 NOTIFICATION-TYPE
|
|
OBJECTS {name, analog6val}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by analog input #6 recovering from under alarm"
|
|
::= {traps 109}
|
|
|
|
|
|
trap-analog-orecover1 NOTIFICATION-TYPE
|
|
OBJECTS {name, analog1val}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by analog input #1 recovering from over alarm"
|
|
::= {traps 120}
|
|
|
|
trap-analog-orecover2 NOTIFICATION-TYPE
|
|
OBJECTS {name, analog2val}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by analog input #2 recovering from over alarm"
|
|
::= {traps 121}
|
|
|
|
trap-analog-orecover3 NOTIFICATION-TYPE
|
|
OBJECTS {name, analog3val}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by analog input #3 recovering from over alarm"
|
|
::= {traps 122}
|
|
|
|
trap-analog-orecover4 NOTIFICATION-TYPE
|
|
OBJECTS {name, analog4val}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by analog input #4 recovering from over alarm"
|
|
::= {traps 123}
|
|
|
|
trap-analog-orecover5 NOTIFICATION-TYPE
|
|
OBJECTS {name, analog5val}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by analog input #5 recovering from over alarm"
|
|
::= {traps 124}
|
|
|
|
trap-analog-orecover6 NOTIFICATION-TYPE
|
|
OBJECTS {name, analog6val}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by analog input #6 recovering from over alarm"
|
|
::= {traps 125}
|
|
|
|
|
|
trap-temp-urecover NOTIFICATION-TYPE
|
|
OBJECTS {name, temperature}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by temperature recovering from under threshold alarm"
|
|
::= {traps 136}
|
|
|
|
trap-temp-orecover NOTIFICATION-TYPE
|
|
OBJECTS {name, temperature}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by temperature recovering from over threshold alarm"
|
|
::= {traps 137}
|
|
|
|
trap-ac-urecover NOTIFICATION-TYPE
|
|
OBJECTS {name, acval}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by AC recovering from under threshold alarm"
|
|
::= {traps 138}
|
|
|
|
trap-ac-orecover NOTIFICATION-TYPE
|
|
OBJECTS {name, acval}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap caused by AC recovering from over threshold alarm"
|
|
::= {traps 139}
|
|
|
|
|
|