-- MIB table for T4511
|
|
--
|
|
-- v3.0 for firmware 1-5-7-2, 2016-04-11
|
|
-----------------------------------------------------------------------
|
|
T4511-MIB DEFINITIONS ::= BEGIN
|
|
|
|
|
|
IMPORTS
|
|
enterprises
|
|
FROM RFC1155-SMI
|
|
OBJECT-TYPE
|
|
FROM RFC-1212
|
|
TRAP-TYPE
|
|
FROM RFC-1215;
|
|
|
|
DisplayString ::= OCTET STRING
|
|
|
|
|
|
comet OBJECT IDENTIFIER ::= { enterprises 22626 }
|
|
products OBJECT IDENTIFIER ::= { comet 1 }
|
|
t4511 OBJECT IDENTIFIER ::= { products 2 }
|
|
values OBJECT IDENTIFIER ::= { t4511 1 }
|
|
global OBJECT IDENTIFIER ::= { t4511 2 }
|
|
valuesInt OBJECT IDENTIFIER ::= { t4511 3 }
|
|
settings OBJECT IDENTIFIER ::= { t4511 4 }
|
|
traps OBJECT IDENTIFIER ::= { t4511 5 }
|
|
tables OBJECT IDENTIFIER ::= { t4511 6 }
|
|
|
|
|
|
-----------------------------------------------------------------------
|
|
-- Measured values - String
|
|
-----------------------------------------------------------------------
|
|
temp OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Temperature"
|
|
::= { values 1 }
|
|
|
|
tempAlarm OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm on Temperature; none, high, low"
|
|
::= { values 5 }
|
|
|
|
tempUnit OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Temperature Unit"
|
|
::= { values 9 }
|
|
|
|
tempMin OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Minimal temperature"
|
|
::= { values 13 }
|
|
|
|
tempMax OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Maximal temperature"
|
|
::= { values 17 }
|
|
|
|
|
|
-----------------------------------------------------------------------
|
|
-- Device informations
|
|
-----------------------------------------------------------------------
|
|
sensorName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..68))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Device name"
|
|
::= { global 1 }
|
|
|
|
serialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..16))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Serial number"
|
|
::= { global 2 }
|
|
|
|
deviceType OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65534)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Device type"
|
|
::= { global 3 }
|
|
|
|
|
|
-----------------------------------------------------------------------
|
|
-- Measured values - Integer
|
|
-----------------------------------------------------------------------
|
|
tempInt OBJECT-TYPE
|
|
SYNTAX INTEGER (-5000..20000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Temperature (value*10)"
|
|
::= { valuesInt 1 }
|
|
|
|
tempAlarmInt OBJECT-TYPE
|
|
SYNTAX INTEGER (0..2)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm on Temperature; 0 - No, 1 - High, 2 - Low"
|
|
::= { valuesInt 5 }
|
|
|
|
|
|
-----------------------------------------------------------------------
|
|
-- Alarm settings
|
|
-----------------------------------------------------------------------
|
|
tempLowInt OBJECT-TYPE
|
|
SYNTAX INTEGER (-5000..20000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Temperature Limit Low (value*10)"
|
|
::= { settings 1 }
|
|
|
|
tempHighInt OBJECT-TYPE
|
|
SYNTAX INTEGER (-5000..20000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Temperature Limit High (value*10)"
|
|
::= { settings 2 }
|
|
|
|
tempDelayInt OBJECT-TYPE
|
|
SYNTAX INTEGER (0..4500)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Temperature alaram delay [sec]"
|
|
::= { settings 7 }
|
|
|
|
tempHystInt OBJECT-TYPE
|
|
SYNTAX INTEGER (0..10000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Temperature hysteresis (value*10)"
|
|
::= { settings 10 }
|
|
|
|
|
|
-----------------------------------------------------------------------
|
|
-- Trap message
|
|
-----------------------------------------------------------------------
|
|
messageString OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..32))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Message giving more detailed information on alarms"
|
|
::= { traps 1 }
|
|
|
|
|
|
-----------------------------------------------------------------------
|
|
-- Tables
|
|
-----------------------------------------------------------------------
|
|
historyTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF HistoryEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Table of the history values"
|
|
::= { tables 1 }
|
|
|
|
historyEntry OBJECT-TYPE
|
|
SYNTAX HistoryEntry
|
|
ACCESS not-accessible
|
|
STATUS optional
|
|
DESCRIPTION "History values entries"
|
|
INDEX { histTemp }
|
|
::= { historyTable 1 }
|
|
|
|
HistoryEntry ::=
|
|
SEQUENCE {
|
|
histTemp
|
|
INTEGER
|
|
}
|
|
|
|
histTemp OBJECT-TYPE
|
|
SYNTAX INTEGER(-5000..20000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Temperature reading"
|
|
::= { historyEntry 1 }
|
|
|
|
|
|
-----------------------------------------------------------------------
|
|
-- Traps definition
|
|
-----------------------------------------------------------------------
|
|
|
|
trapTest TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString }
|
|
DESCRIPTION
|
|
"Testing trap, testing trap by TSensor software"
|
|
::= 0
|
|
|
|
trapNTPError TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString }
|
|
DESCRIPTION
|
|
"Error on time synchronisation via NTP"
|
|
::= 1
|
|
|
|
trapEmailErrLogin TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString }
|
|
DESCRIPTION
|
|
"SMTP error - unknown server"
|
|
::= 2
|
|
|
|
trapEmailErrAuth TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString }
|
|
DESCRIPTION
|
|
"SMTP error - authentication error"
|
|
::= 3
|
|
|
|
trapEmailErrSome TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString }
|
|
DESCRIPTION
|
|
"SMTP error - error during communication with server, unexpected return code"
|
|
::= 4
|
|
|
|
trapEmailErrSocket TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString }
|
|
DESCRIPTION
|
|
"SMTP error - socket error, server is not available"
|
|
::= 5
|
|
|
|
trapEmailErrDNS TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString }
|
|
DESCRIPTION
|
|
"SMTP error - DNS error"
|
|
::= 6
|
|
|
|
trapSOAPErrFile TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString }
|
|
DESCRIPTION
|
|
"SOAP error - file SOAP not found"
|
|
::= 7
|
|
|
|
trapSOAPErrDNS TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString }
|
|
DESCRIPTION
|
|
"SOAP error - DNS error"
|
|
::= 8
|
|
|
|
trapSOAPErrSocket TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString }
|
|
DESCRIPTION
|
|
"SOAP error - socket error, server is not available"
|
|
::= 9
|
|
|
|
trapSOAPErrDelivery TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString }
|
|
DESCRIPTION
|
|
"SOAP error - delivery error, wrong return code from server"
|
|
::= 10
|
|
|
|
trapTempHighAlarm TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString, temp, tempAlarmInt }
|
|
DESCRIPTION
|
|
"Trap for high alarm on temperature"
|
|
::= 11
|
|
|
|
trapTempLowAlarm TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString, temp, tempAlarmInt }
|
|
DESCRIPTION
|
|
"Trap for low alarm on temperature"
|
|
::= 21
|
|
|
|
trapTempClrAlarm TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString, temp, tempAlarmInt }
|
|
DESCRIPTION
|
|
"Trap for clearing alarm on temperature"
|
|
::= 31
|
|
|
|
trapTempError TRAP-TYPE
|
|
ENTERPRISE comet
|
|
VARIABLES { sensorName, messageString, temp, tempAlarmInt }
|
|
DESCRIPTION
|
|
"Trap for error on temperature"
|
|
::= 41
|
|
|
|
|
|
END
|