2692 lines
77 KiB
Plaintext
2692 lines
77 KiB
Plaintext
-- BAY TECHNICAL ASSOCIATES (BAYTECH) MIB
|
|
|
|
-- Copyright (c) Bay Technical Associates 2000.
|
|
-- Version : 4.01.4
|
|
|
|
-- Title: TOP LEVEL BAYTECH MIB for all baytech devices
|
|
|
|
-- *************************************************************************
|
|
-- ************************************************************************
|
|
-- Baytech-MIB { iso org(3) dod(6) internet(1) private(4)
|
|
-- enterprises(1) baytech(4779) }
|
|
|
|
--
|
|
-- Module/Port MIB definitions are included below. These have been commented
|
|
-- out. To access RPCs & outlets by module/port indexing, (in addition to
|
|
-- port indexing, the default method) uncomment this section prior to
|
|
-- compiling the MIB for your browser.
|
|
--
|
|
|
|
|
|
Baytech-MIB-401-4 DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
enterprises, IpAddress, Gauge, TimeTicks FROM RFC1155-SMI
|
|
DisplayString FROM RFC1213-MIB
|
|
OBJECT-TYPE FROM RFC-1212
|
|
TRAP-TYPE FROM RFC-1215;
|
|
|
|
|
|
baytech OBJECT IDENTIFIER ::= { enterprises 4779 }
|
|
|
|
btadevices OBJECT IDENTIFIER ::= { baytech 1 }
|
|
mtrapargs OBJECT IDENTIFIER ::= { baytech 3 }
|
|
|
|
sBTAIdent OBJECT IDENTIFIER ::= { btadevices 1 }
|
|
sBTANetworkConfig OBJECT IDENTIFIER ::= { btadevices 2 }
|
|
sBTAModules OBJECT IDENTIFIER ::= { btadevices 3 }
|
|
sBTAControl OBJECT IDENTIFIER ::= { btadevices 4 }
|
|
sBTAFileTransfer OBJECT IDENTIFIER ::= { btadevices 5 }
|
|
sBTAEnvironmental OBJECT IDENTIFIER ::= { btadevices 6 }
|
|
|
|
-- object types
|
|
|
|
-- the sBTAIdent group
|
|
|
|
sBTAIdentFirmwareRev OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An 8 byte ID string identifying the DS72 firmware revision.
|
|
This value is set at the factory."
|
|
::= { sBTAIdent 1 }
|
|
|
|
sBTAIdentSerialNumber OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A number identifying the serial number of the DS72.
|
|
This value is set at the factory."
|
|
::= { sBTAIdent 2 }
|
|
|
|
sBTAIdentUnitName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(64))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A 64-character string identifying the name (UnitID) of the DS72.
|
|
This value is set at the factory to a default of DS72."
|
|
::= { sBTAIdent 3 }
|
|
|
|
--sBTAIdentUnitDescription OBJECT-TYPE
|
|
-- SYNTAX DisplayString
|
|
-- ACCESS read-write
|
|
-- STATUS mandatory
|
|
-- DESCRIPTION
|
|
-- "A 64-character string that can be used by the user for aditional
|
|
-- information describing the unit.
|
|
-- This value is set at the factory to a default of NULL."
|
|
-- ::= { sBTAIdent 4 }
|
|
|
|
-- the sBTANetworkConfig group
|
|
|
|
sBTANetworkConfigBootpEnable OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enables/disables bootp. Bootp will not take effect until the unit is reseted."
|
|
::= { sBTANetworkConfig 1 }
|
|
|
|
sBTANetworkConfigDHCPEnable OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enables/disables DHCP. DHCP will not take effect until the unit is reseted."
|
|
::= { sBTANetworkConfig 2 }
|
|
|
|
sBTANetworkConfigSSHEnable OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enables/disables SSH logins.
|
|
Disable/enable SSH will take effect after the unit is reseted."
|
|
::= { sBTANetworkConfig 3 }
|
|
|
|
sBTANetworkConfigTelnetEnable OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enables/disables telnet. "
|
|
::= { sBTANetworkConfig 4 }
|
|
|
|
|
|
sBTANetworkConfigActivityTimeout OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A value from 0 to 120. 0 disables activity timeouts.
|
|
Value represents minutes of non-activity before telnet / SSH sessions are
|
|
automatically logged out.
|
|
Default is 0."
|
|
::= { sBTANetworkConfig 5 }
|
|
|
|
|
|
sBTANetworkConfigDirectConnEnable OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enables/disables direct port connection upon login."
|
|
::= { sBTANetworkConfig 6 }
|
|
|
|
|
|
sBTANetworkConfigSNMP OBJECT IDENTIFIER ::= { sBTANetworkConfig 8 }
|
|
sBTANetworkConfigRadius OBJECT IDENTIFIER ::= { sBTANetworkConfig 9 }
|
|
sBTANetworkConfigWEB OBJECT IDENTIFIER ::= { sBTANetworkConfig 10 }
|
|
|
|
|
|
|
|
-- the sBTANetworkConfigSNMP group
|
|
|
|
sBTANetworkConfigSNMPReadOnlyCommunity OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The community name to use for read only access. Maximum len 16 bytes."
|
|
::= { sBTANetworkConfigSNMP 1 }
|
|
|
|
sBTANetworkConfigSNMPReadWriteCommunity OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The community name to use for read-write access. Maximum len 16 bytes."
|
|
::= { sBTANetworkConfigSNMP 2 }
|
|
|
|
sBTANetworkConfigSNMPNumTrapReceivers OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The maximum number of managers to send traps to. Currently 4."
|
|
::= { sBTANetworkConfigSNMP 3 }
|
|
|
|
sBTANetworkConfigSNMPTrapReceiverTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF SDSNetworkConfigSNMPTrapReceiverEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of managers to send traps to. The number of
|
|
entries is given by the value of sBTANetworkConfigSNMPNumTrapReceivers.
|
|
Maximum number of Trap Receivers is four."
|
|
::= { sBTANetworkConfigSNMP 4 }
|
|
|
|
sBTANetworkConfigSNMPTrapReceiverEntry OBJECT-TYPE
|
|
SYNTAX SDSNetworkConfigSNMPTrapReceiverEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Table of managers to send traps to."
|
|
INDEX { trapIndex}
|
|
::= { sBTANetworkConfigSNMPTrapReceiverTable 1 }
|
|
|
|
SDSNetworkConfigSNMPTrapReceiverEntry ::=
|
|
SEQUENCE {
|
|
trapIndex
|
|
INTEGER,
|
|
receiverAddress
|
|
IpAddress
|
|
}
|
|
|
|
trapIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index to a trap receiver entry."
|
|
::= { sBTANetworkConfigSNMPTrapReceiverEntry 1 }
|
|
|
|
receiverAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The IP address of the manager to send traps to."
|
|
::= { sBTANetworkConfigSNMPTrapReceiverEntry 2 }
|
|
|
|
|
|
-- the sBTANetworkConfigRadius group
|
|
|
|
sBTANetworkConfigRadiusEnable OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable (0),
|
|
enable (1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enables / disables RADIUS telnet logins."
|
|
::= { sBTANetworkConfigRadius 1 }
|
|
|
|
|
|
sBTANetworkConfigRadiusPrimaryServer OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Ip address of the primary RADIUS server."
|
|
::= { sBTANetworkConfigRadius 2 }
|
|
|
|
sBTANetworkConfigRadiusSecondaryServer OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Ip address of the back-up RADIUS server."
|
|
::= { sBTANetworkConfigRadius 3 }
|
|
|
|
sBTANetworkConfigRadiusLocalLogin OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable (0),
|
|
enable (1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enables / disables the use of local (usernames stored in the DS72) logins
|
|
in the case that both the primary and secondary RADIUS server are not available."
|
|
::= { sBTANetworkConfigRadius 4 }
|
|
|
|
--------------------------------------------------
|
|
-- The sFNetworkConfigWEB Group --
|
|
--------------------------------------------------
|
|
|
|
sBTANetworkConfigWebEnable OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enables WEB."
|
|
::= { sBTANetworkConfigWEB 1 }
|
|
|
|
sBTANetworkConfigWebSecureEnable OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enables WEB Security."
|
|
::= { sBTANetworkConfigWEB 2 }
|
|
|
|
sBTANetworkConfigWebLoginEnable OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enables WEB Login."
|
|
::= { sBTANetworkConfigWEB 3 }
|
|
|
|
sBTANetworkConfigWebActivityTimeout OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A value from 0 to 120. 0 disables WEB activity timeouts.
|
|
Value represents minutes of non-activity before WEB sessions are
|
|
automatically logged out. Default is 0."
|
|
::= { sBTANetworkConfigWEB 4 }
|
|
|
|
|
|
-- the sBTAModules group
|
|
|
|
sBTAModulesNumberOfModules OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of modules installed into the DS unit."
|
|
::= { sBTAModules 1 }
|
|
|
|
sBTAModulesModulesInstalled OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A character string listing the modules installed seperated by commas.
|
|
Each module is identifed by a two digit number indicating the slot.
|
|
For example 02,03,04,06 means modules 2,3,4 and 6 are installed."
|
|
::= { sBTAModules 2 }
|
|
|
|
sBTAModulesResetModulesCmd OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"This command is no longer supported."
|
|
::= { sBTAModules 3 }
|
|
|
|
sBTAModulesNumberOfIntelligentModules OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of Intelligent Modules installed in the DS Unit."
|
|
::= { sBTAModules 4 }
|
|
|
|
sBTAModulesRPC OBJECT IDENTIFIER ::= { sBTAModules 5 }
|
|
sBTAModulesSerial OBJECT IDENTIFIER ::= { sBTAModules 6 }
|
|
sBTAModulesModem OBJECT IDENTIFIER ::= { sBTAModules 7 }
|
|
|
|
-- sBTAModulesRPC group
|
|
|
|
sBTAModulesNumberOfRPCModules OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of DS30 Modules installed in the DS Unit."
|
|
::= { sBTAModulesRPC 1 }
|
|
|
|
sBTAModulesRPCTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF SDSModulesRPCEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Allows for control of individual outlets and individual RPC modules. "
|
|
::= { sBTAModulesRPC 2 }
|
|
|
|
sBTAModulesRPCEntry OBJECT-TYPE
|
|
SYNTAX SDSModulesRPCEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The RPCs to control and get status on."
|
|
INDEX { sBTAModulesRPCIndex}
|
|
::= { sBTAModulesRPCTable 1 }
|
|
|
|
SDSModulesRPCEntry ::=
|
|
SEQUENCE {
|
|
sBTAModulesRPCIndex INTEGER,
|
|
sBTAModulesRPCName DisplayString,
|
|
sBTAModulesRPCFirmwareVersion DisplayString,
|
|
sBTAModulesRPCCurrent INTEGER,
|
|
sBTAModulesRPCMaxCurrent INTEGER,
|
|
sBTAModulesRPCVoltage INTEGER,
|
|
sBTAModulesRPCPower INTEGER,
|
|
sBTAModulesRPCTemperature INTEGER,
|
|
sBTAModulesRPCRebootTimeout INTEGER,
|
|
sBTAModulesRPCAllOutletsCmd INTEGER,
|
|
sBTAModulesRPCAllOutletsStatus DisplayString,
|
|
sBTAModulesRPCCurrentAlarmThreshold INTEGER,
|
|
sBTAModulesRPCOverVoltageThreshold INTEGER,
|
|
sBTAModulesRPCUnderVoltageThreshold INTEGER,
|
|
sBTAModulesRPCNumberOfOutlets INTEGER,
|
|
sBTAModulesRPCCircuitBreaker INTEGER,
|
|
sBTAModulesRPCOverTempThreshold INTEGER,
|
|
sBTAModulesRPCUnitVA INTEGER,
|
|
sBTAModulesRPCNumberOfBreakers INTEGER,
|
|
sBTAModulesRPCLowCurrentThreshold INTEGER,
|
|
sBTAModulesRPCVoltageSource INTEGER,
|
|
sBTAModulesRPCSourceSwitchCount INTEGER,
|
|
sBTAModulesRPCNumberOfSensors INTEGER,
|
|
sBTAModulesRPCType DisplayString
|
|
}
|
|
|
|
sBTAModulesRPCIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index into the RPC table. Indexes for rpcs attached to ds74 modules are calculate with the following formula:
|
|
((module - 2) * 4) + port. For example module 3 port 1 = index 5. "
|
|
::= { sBTAModulesRPCEntry 1 }
|
|
|
|
sBTAModulesRPCName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name (unit id) of the rpc."
|
|
::= { sBTAModulesRPCEntry 2 }
|
|
|
|
sBTAModulesRPCFirmwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The firware version of the rpc."
|
|
::= { sBTAModulesRPCEntry 3 }
|
|
|
|
sBTAModulesRPCCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current reading for the power strip.
|
|
If current measurement is not installed this value will always read 0."
|
|
::= { sBTAModulesRPCEntry 4 }
|
|
|
|
sBTAModulesRPCMaxCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The maximum detected current reading for the power strip.
|
|
If current measurement is not installed this value will always read 0.
|
|
Setting this value to 0 will clear the maximum current detected."
|
|
::= { sBTAModulesRPCEntry 5 }
|
|
|
|
sBTAModulesRPCVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The voltage reading for the power strip.
|
|
If voltage measurement is not installed this value will always read 0."
|
|
::= { sBTAModulesRPCEntry 6 }
|
|
|
|
sBTAModulesRPCPower OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The power reading for the power strip.
|
|
If power measurement is not installed this value will always read 0."
|
|
::= { sBTAModulesRPCEntry 7 }
|
|
|
|
sBTAModulesRPCTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The temperature reading for the power strip. Readings are in degrees C.
|
|
If temperature measurement is not installed this value will always read 0."
|
|
::= { sBTAModulesRPCEntry 8 }
|
|
|
|
sBTAModulesRPCRebootTimeout OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The length of off time for automatic reboot sequences.
|
|
Currently a read-only value set to the fixed reboot timeout."
|
|
::= { sBTAModulesRPCEntry 9 }
|
|
|
|
sBTAModulesRPCAllOutletsCmd OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off (0),
|
|
on (1),
|
|
reboot (2),
|
|
lockon (3),
|
|
lockoff (4),
|
|
unlock (5),
|
|
unknown (6)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Turns all outlets on, off or reboot.
|
|
0 = off
|
|
1 = on
|
|
2 = reboot
|
|
|
|
A get will return unknown (6)."
|
|
::= { sBTAModulesRPCEntry 10 }
|
|
|
|
sBTAModulesRPCAllOutletsStatus OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Reports status of outlets in a comma deliminated string.
|
|
0 = off
|
|
1 = on
|
|
2 = reboot
|
|
3 = locked on
|
|
4 = locked off"
|
|
::= { sBTAModulesRPCEntry 11 }
|
|
|
|
sBTAModulesRPCCurrentAlarmThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current alarm threshold level *10. A value of 105 will set the level to 10.5."
|
|
::= { sBTAModulesRPCEntry 12 }
|
|
|
|
sBTAModulesRPCOverVoltageThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The over voltage alarm threshold level *10. A value of 105 will set the level to 10.5."
|
|
::= { sBTAModulesRPCEntry 13 }
|
|
|
|
sBTAModulesRPCUnderVoltageThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The under voltage alarm threshold level *10. A value of 105 will set the level to 10.5."
|
|
::= { sBTAModulesRPCEntry 14 }
|
|
|
|
sBTAModulesRPCNumberOfOutlets OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of outlets for this RPC.
|
|
This will be the size of outlet table for this RPC index."
|
|
::= { sBTAModulesRPCEntry 15 }
|
|
|
|
sBTAModulesRPCCircuitBreaker OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off (0),
|
|
on (1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Status of circuit breaker in power strip. 0=off 1=on."
|
|
::= { sBTAModulesRPCEntry 16 }
|
|
|
|
sBTAModulesRPCOverTempThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The over temperature alarm threshold level *10. A value of 505 will set the level to 50.5."
|
|
::= { sBTAModulesRPCEntry 17 }
|
|
|
|
sBTAModulesRPCUnitVA OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Total Volt-Amps for this RPC. "
|
|
::= { sBTAModulesRPCEntry 18 }
|
|
|
|
sBTAModulesRPCNumberOfBreakers OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of breakers for this RPC. "
|
|
::= { sBTAModulesRPCEntry 19 }
|
|
|
|
sBTAModulesRPCLowCurrentThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Low current threshold for this RPC. "
|
|
::= { sBTAModulesRPCEntry 20 }
|
|
|
|
sBTAModulesRPCVoltageSource OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Voltage source for this RPC. "
|
|
::= { sBTAModulesRPCEntry 21 }
|
|
|
|
sBTAModulesRPCSourceSwitchCount OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Count of Voltage Source Switches for this RPC. "
|
|
::= { sBTAModulesRPCEntry 22 }
|
|
|
|
sBTAModulesRPCNumberOfSensors OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of environmental sensors for this RPC. "
|
|
::= { sBTAModulesRPCEntry 23 }
|
|
|
|
sBTAModulesRPCType OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The type of RPC installed at the indexed location."
|
|
::= { sBTAModulesRPCEntry 24 }
|
|
|
|
|
|
|
|
sBTAModulesRPCOutletTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF SDSModulesRPCOutletEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Allows for control of individual outlets. The number of
|
|
entries is contained in the sBTAModulesRPCOutletTableSize OID."
|
|
::= { sBTAModulesRPC 3 }
|
|
|
|
sBTAModulesRPCOutletEntry OBJECT-TYPE
|
|
SYNTAX SDSModulesRPCOutletEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The outlets to control and get status on."
|
|
INDEX { sBTAModulesRPCOutletModuleIndex, sBTAModulesRPCOutletIndex}
|
|
::= { sBTAModulesRPCOutletTable 1 }
|
|
|
|
SDSModulesRPCOutletEntry ::=
|
|
SEQUENCE {
|
|
sBTAModulesRPCOutletModuleIndex INTEGER,
|
|
sBTAModulesRPCOutletIndex INTEGER,
|
|
sBTAModulesRPCOutletState INTEGER,
|
|
sBTAModulesRPCOutletName DisplayString
|
|
}
|
|
|
|
sBTAModulesRPCOutletModuleIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index to the outlet entry."
|
|
::= { sBTAModulesRPCOutletEntry 1 }
|
|
|
|
sBTAModulesRPCOutletIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index to the outlet entry."
|
|
::= { sBTAModulesRPCOutletEntry 2 }
|
|
|
|
sBTAModulesRPCOutletState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off (0),
|
|
on (1),
|
|
reboot (2),
|
|
lockon (3),
|
|
lockoff (4),
|
|
unlock (5),
|
|
unknown (6)
|
|
}
|
|
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Getting this variable will return the state of the outlet.
|
|
Valid return states are unknown, on, off, lockon, lockoff.
|
|
0 = off
|
|
1 = on
|
|
2 = reboot
|
|
3 = lockon (outlet is on and no changes are allowed)
|
|
4 = lockoff (outlet is off and no changes are allowed)
|
|
5 = unlock."
|
|
|
|
::= { sBTAModulesRPCOutletEntry 3 }
|
|
|
|
|
|
sBTAModulesRPCOutletName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name of the outlet. Maximum size is 16 characters."
|
|
|
|
::= { sBTAModulesRPCOutletEntry 4 }
|
|
|
|
sBTAModulesRPCGroupCmd OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A character string listing the outlets that need to be controlled,
|
|
turned off, or turn on as a group. Command is the first character
|
|
followed by a space. Valid commads are 0=off,1=on, or 2=reboot. A
|
|
list follows the command in the format module.outlet. For example
|
|
2 2.1,2.12,3.1 will reboot module 2 outlet 2&12 module 3 outlet 1."
|
|
::= { sBTAModulesRPC 4 }
|
|
|
|
|
|
-- the sBTAModulesRPCCurrentGroup group
|
|
|
|
sBTAModulesRPCCurrentGroupsCurrentTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF SDSModulesRPCCurrentGroupsCurrentEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
" A list of total current for RPCs in each current group"
|
|
::= { sBTAModulesRPC 8 }
|
|
|
|
sBTAModulesRPCCurrentGroupsCurrentEntry OBJECT-TYPE
|
|
SYNTAX SDSModulesRPCCurrentGroupsCurrentEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Table of total current measurement by group"
|
|
INDEX { groupCurrentIndex}
|
|
::= { sBTAModulesRPCCurrentGroupsCurrentTable 1 }
|
|
|
|
SDSModulesRPCCurrentGroupsCurrentEntry ::=
|
|
SEQUENCE {
|
|
groupCurrentIndex INTEGER,
|
|
groupCurrent INTEGER,
|
|
rpcGroup DisplayString,
|
|
warningThreshold INTEGER,
|
|
emergencyThreshold INTEGER
|
|
}
|
|
|
|
groupCurrentIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index to a group total current."
|
|
::= { sBTAModulesRPCCurrentGroupsCurrentEntry 1 }
|
|
|
|
groupCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Current total for all RPCs in group."
|
|
::= { sBTAModulesRPCCurrentGroupsCurrentEntry 2 }
|
|
|
|
rpcGroup OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A character string listing the RPCs, by port index, that will be
|
|
included in a measurement of total current. For each group, a sum
|
|
will be periodically computed of currents of all listed RPCs, which
|
|
will be compared to warning and emergency thresholds, generating
|
|
appropriate traps as required by transit of a threshold. A maximum
|
|
of 8 RPCs may be monitored within a group. The RPC must be connected
|
|
and operating and the corresponding DS74 serial port must be configured
|
|
for an RPC-SNMP device type to be allowed group membership."
|
|
::= { sBTAModulesRPCCurrentGroupsCurrentEntry 3 }
|
|
|
|
warningThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current level, in tenths of an amp, that will cause a Current
|
|
Level Warning trap to be sent if the total current for the associated
|
|
group if exceeded. Conversely, a Current Level Warning Clear trap
|
|
will be sent whent the total group current falls below the threshold."
|
|
::= { sBTAModulesRPCCurrentGroupsCurrentEntry 4 }
|
|
|
|
emergencyThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current level, in tenths of an amp, that will cause a Current
|
|
Level Emergency trap to be sent if the total current for the associated
|
|
group if exceeded. Conversely, a Current Level Emergeny Clear trap
|
|
will be sent whent the total group current falls below the threshold."
|
|
::= { sBTAModulesRPCCurrentGroupsCurrentEntry 5}
|
|
|
|
|
|
-- Individual strip table (by breaker - for RPC 28 & other multi-breaker units)
|
|
|
|
sBTAModulesRPCBreakersTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF SDSModulesRPCBreakersEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Allows monitoring of individual outlet strips on RPCs. "
|
|
::= { sBTAModulesRPC 9 }
|
|
|
|
sBTAModulesRPCBreakersEntry OBJECT-TYPE
|
|
SYNTAX SDSModulesRPCBreakersEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Status organization by breaker."
|
|
INDEX { sBTAModulesRPCBreakersModulesIndex,sBTAModulesRPCBreakersBreakersIndex}
|
|
::= { sBTAModulesRPCBreakersTable 1 }
|
|
|
|
SDSModulesRPCBreakersEntry ::=
|
|
SEQUENCE {
|
|
sBTAModulesRPCBreakersModulesIndex INTEGER,
|
|
sBTAModulesRPCBreakersBreakersIndex INTEGER,
|
|
sBTAModulesRPCBreakersCircuitBreaker INTEGER,
|
|
sBTAModulesRPCBreakersCurrent INTEGER,
|
|
sBTAModulesRPCBreakersMaxCurrent INTEGER,
|
|
sBTAModulesRPCBreakersVoltage INTEGER,
|
|
sBTAModulesRPCBreakersPower INTEGER,
|
|
sBTAModulesRPCBreakersVA INTEGER,
|
|
sBTAModulesRPCBreakersCurrentAlarmThreshold INTEGER
|
|
}
|
|
|
|
|
|
sBTAModulesRPCBreakersModulesIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index into the RPC table."
|
|
::= { sBTAModulesRPCBreakersEntry 1 }
|
|
|
|
sBTAModulesRPCBreakersBreakersIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index into the RPC breaker table."
|
|
::= { sBTAModulesRPCBreakersEntry 2 }
|
|
|
|
sBTAModulesRPCBreakersCircuitBreaker OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off (0),
|
|
on (1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Status of circuit breaker in power strip. 0=off 1=on."
|
|
::= { sBTAModulesRPCBreakersEntry 3 }
|
|
|
|
sBTAModulesRPCBreakersCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The detected current reading for the power strip.
|
|
If current measurement is not installed this value will always read 0."
|
|
::= { sBTAModulesRPCBreakersEntry 4 }
|
|
|
|
sBTAModulesRPCBreakersMaxCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The maximum detected current reading for the power strip.
|
|
If current measurement is not installed this value will always read 0."
|
|
::= { sBTAModulesRPCBreakersEntry 5 }
|
|
|
|
sBTAModulesRPCBreakersVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The voltage reading for the power strip.
|
|
If voltage measurement is not installed this value will always read 0."
|
|
::= { sBTAModulesRPCBreakersEntry 6 }
|
|
|
|
sBTAModulesRPCBreakersPower OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The power reading for the power strip.
|
|
If voltage measurement is not installed this value will always read 0."
|
|
::= { sBTAModulesRPCBreakersEntry 7 }
|
|
|
|
sBTAModulesRPCBreakersVA OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The volt-amps reading for the power strip.
|
|
If voltage measurement is not installed this value will always read 0."
|
|
::= { sBTAModulesRPCBreakersEntry 8 }
|
|
|
|
sBTAModulesRPCBreakersCurrentAlarmThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current alarm threshold level *10. A value of 105 will set the level to 10.5."
|
|
::= { sBTAModulesRPCBreakersEntry 9 }
|
|
|
|
|
|
-- the sBTAControl group
|
|
|
|
sBTAControlResetUnit OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noreset (0),
|
|
reset (1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this value to 1 will cause the unit to reset.
|
|
A get of this OID will return 0."
|
|
::= { sBTAControl 1 }
|
|
|
|
sBTAControlResetModules OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noreset (0),
|
|
reset (1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this value to 1 will cause the unit to reset modules
|
|
simular to the telnet RM command. A get of this OID will return 0."
|
|
::= { sBTAControl 2 }
|
|
|
|
sBTAControlNumOfLoggedUsers OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of users logged in via telnet or SSH."
|
|
::= { sBTAControl 3 }
|
|
|
|
sBTAControlUserTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF SDSControlUserEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of users and user information.
|
|
The number of entries is contained in the sBTAControlNumOfLoggedUsers OID."
|
|
::= { sBTAControl 4 }
|
|
|
|
sBTAControlUserEntry OBJECT-TYPE
|
|
SYNTAX SDSControlUserEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The users to get status on."
|
|
INDEX { sBTAControlUserIndex}
|
|
::= { sBTAControlUserTable 1 }
|
|
|
|
SDSControlUserEntry ::=
|
|
SEQUENCE {
|
|
sBTAControlUserIndex INTEGER,
|
|
sBTAControlUserName DisplayString,
|
|
sBTAControlUserAddress IpAddress,
|
|
sBTAControlUserConnection INTEGER,
|
|
sBTAControlUserConnModule INTEGER,
|
|
sBTAControlUserConnPort INTEGER,
|
|
sBTAControlUserTerminateUser INTEGER
|
|
}
|
|
|
|
sBTAControlUserIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index to the user entry."
|
|
::= { sBTAControlUserEntry 1 }
|
|
|
|
sBTAControlUserName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The username of the user."
|
|
|
|
::= { sBTAControlUserEntry 2 }
|
|
|
|
sBTAControlUserAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The IP address of the user."
|
|
::= { sBTAControlUserEntry 3 }
|
|
|
|
sBTAControlUserConnection OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
serialport (0),
|
|
telnet (1),
|
|
ssh (2),
|
|
unknown (4)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Type of connection.
|
|
If unknown, user is logging out or the connection is invalid."
|
|
::= { sBTAControlUserEntry 4 }
|
|
|
|
sBTAControlUserConnModule OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"If the user is connected to a module, this value will
|
|
report the module number connected to.
|
|
If the value is 0 the user is not connected to a module."
|
|
::= { sBTAControlUserEntry 5 }
|
|
|
|
sBTAControlUserConnPort OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The port number with in a module that the user is connected to.
|
|
This usually only applies to connections to DS74 serial modules.
|
|
Intelligent modules connections are always made on port 1.
|
|
If value is 0 the user is not connected to a module."
|
|
::= { sBTAControlUserEntry 6 }
|
|
|
|
sBTAControlUserTerminateUser OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
terminate (1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Settings this OID to anything but 0 will terminate (log out) the user.
|
|
A get of this OID will return 0."
|
|
::= { sBTAControlUserEntry 7 }
|
|
|
|
-- the sBTAFileTransfer group
|
|
sBTAFileTransferEnableUpgradeFTPFileTransfer OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enableUpgradeFileTransferDownloadViaFTP (1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this OID to enableUpgradeFileTransferDownloadViaFTP (1)
|
|
will start the FTP server and place the DS72 in upgrade mode. An
|
|
FTP connection may then be established for the purpose of transmitting
|
|
a firmware upgrade file."
|
|
::= { sBTAFileTransfer 1 }
|
|
|
|
-- the mtrapargs group
|
|
|
|
mtrapargsInteger OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This OID allows baytech traps to be sent with an integer argument
|
|
that may not be defined in the baytech MIB.
|
|
|
|
A get of this OID will return 0."
|
|
::= { mtrapargs 1 }
|
|
|
|
mtrapargsIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This OID allows bayteh traps to be sent with an IP address argument
|
|
that may not be defined in the baytech MIB.
|
|
|
|
A get of this OID will return 0.0.0.0."
|
|
::= { mtrapargs 2 }
|
|
|
|
mtrapargsString OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This OID allows baytech traps to be sent with an octet string argument
|
|
that may not be defined in the baytech MIB.
|
|
|
|
A get of this OID will return a NULL string."
|
|
::= { mtrapargs 3 }
|
|
|
|
mtrapargsGauge OBJECT-TYPE
|
|
SYNTAX Gauge
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This OID allows baytech traps to be sent with a Gauge argument
|
|
that may not be defined in the baytech MIB.
|
|
|
|
A get of this OID will return 0."
|
|
::= { mtrapargs 4 }
|
|
|
|
mtrapargsTimeTicks OBJECT-TYPE
|
|
SYNTAX TimeTicks
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This OID allows baytech traps to be sent with a TimeTicks argument
|
|
that may not be defined in the baytech MIB.
|
|
|
|
A get of this OID will return 0."
|
|
::= { mtrapargs 5 }
|
|
|
|
sBTAModuleIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This OID allows baytech traps to be sent with an integer argument
|
|
that may not be defined in the baytech MIB. This is an index to a specific
|
|
DS module. Value will equal the slot of the module.
|
|
|
|
A get of this OID will return 0."
|
|
::= { mtrapargs 6 }
|
|
|
|
sBTAOutletIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This OID allows baytech traps to be sent with an integer argument
|
|
that may not be defined in the baytech MIB. This is an index to a specific
|
|
outlet in a DS module.
|
|
|
|
Value is 1 to number of outlets controlled by the ds module. 0 represents
|
|
all outlets.
|
|
|
|
A get of this OID will return 0."
|
|
::= { mtrapargs 7 }
|
|
|
|
sBTAPortIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This OID allows baytech traps to be sent with an integer argument
|
|
that may not be defined in the baytech MIB. This is an index to a specific
|
|
outlet in a DS module.
|
|
|
|
Value is 1 to number of outlets controlled by the ds module. 0 represents
|
|
all outlets.
|
|
|
|
A get of this OID will return 0."
|
|
::= { mtrapargs 8 }
|
|
|
|
sBTAVoltageSource OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This OID allows baytech traps to be sent with an integer argument
|
|
that may not be defined in the baytech MIB. This is the number associated
|
|
with the voltage source in an RPC.
|
|
|
|
Value is 1 or 2, depending on which voltage source is powering the RPC.
|
|
|
|
A get of this OID will return 0."
|
|
::= { mtrapargs 9 }
|
|
|
|
sBTASourceSwitchCount OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This OID allows baytech traps to be sent with an integer argument
|
|
that may not be defined in the baytech MIB. This is the number associated
|
|
with the number of voltage source transitions in an RPC.
|
|
|
|
Value is 0 to 255, an 8-bit w/rollover count of number of times voltage
|
|
source has been switched from one source to another.
|
|
|
|
A get of this OID will return 0."
|
|
::= { mtrapargs 10 }
|
|
|
|
sBTASensorIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This OID allows baytech traps to be sent with an integer argument
|
|
that may not be defined in the baytech MIB. This is an index to a specific
|
|
sensor in a DS module.
|
|
|
|
Value is 1 to number of sensors controlled by the ds module.
|
|
|
|
A get of this OID will return 0."
|
|
::= { mtrapargs 11 }
|
|
|
|
sBTABreakerIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This is an object which is sent along with a trap to designate a
|
|
breaker number pertinent to a particular trap. This value will
|
|
range from 1 to the total number of breakers
|
|
inside the particular RPC.
|
|
|
|
A get of this OID will return 0."
|
|
::= { mtrapargs 12 }
|
|
|
|
|
|
-- Module/Port MIB definitions - uncomment lines below until comment at end
|
|
-- of block prior to compiling.
|
|
|
|
sBTAModulesRPCModPortTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF SDSModulesRPCModPortEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Allows for control of individual outlets and individual RPC modules. The number of
|
|
entries is contained in the sBTAModulesNumberOfRPCModules OID."
|
|
::= { sBTAModulesRPC 5 }
|
|
|
|
sBTAModulesRPCModPortEntry OBJECT-TYPE
|
|
SYNTAX SDSModulesRPCModPortEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The RPCs to control and get status on."
|
|
INDEX { sRPCModuleIndex,sRPCPortIndex}
|
|
::= { sBTAModulesRPCModPortTable 1 }
|
|
|
|
SDSModulesRPCModPortEntry ::=
|
|
SEQUENCE {
|
|
sRPCModuleIndex INTEGER,
|
|
sRPCPortIndex INTEGER,
|
|
sRPCType DisplayString,
|
|
sRPCName DisplayString,
|
|
sRPCFirmwareVersion DisplayString,
|
|
sRPCCurrent INTEGER,
|
|
sRPCMaxCurrent INTEGER,
|
|
sRPCVoltage INTEGER,
|
|
sRPCPower INTEGER,
|
|
sRPCTemperature INTEGER,
|
|
sRPCRebootTimeout INTEGER,
|
|
sRPCAllOutletsCmd INTEGER,
|
|
sRPCAllOutletsStatus DisplayString,
|
|
sRPCCurrentAlarmThreshold INTEGER,
|
|
sRPCOverVoltageThreshold INTEGER,
|
|
sRPCUnderVoltageThreshold INTEGER,
|
|
sRPCNumberOfOutlets INTEGER,
|
|
sRPCCircuitBreaker INTEGER,
|
|
sRPCOverTempThreshold INTEGER,
|
|
sRPCUnitVA INTEGER,
|
|
sRPCNumberOfBreakers INTEGER,
|
|
sRPCLowCurrentThreshold INTEGER,
|
|
sRPCVoltageSource INTEGER,
|
|
sRPCSourceSwitchCount INTEGER,
|
|
sRPCNumberOfSensors INTEGER
|
|
}
|
|
|
|
sRPCModuleIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The module number index into the RPC table."
|
|
::= { sBTAModulesRPCModPortEntry 1 }
|
|
|
|
sRPCPortIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The port number index into the RPC table. In the case of ds30 modules this number is always 1."
|
|
::= { sBTAModulesRPCModPortEntry 2 }
|
|
|
|
sRPCType OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Type of RPC at the module, port index."
|
|
::= { sBTAModulesRPCModPortEntry 3 }
|
|
|
|
sRPCName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name (unit id) of the rpc module."
|
|
::= { sBTAModulesRPCModPortEntry 4 }
|
|
|
|
sRPCFirmwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The firware version of the rpc module."
|
|
::= { sBTAModulesRPCModPortEntry 5 }
|
|
|
|
sRPCCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current reading for the power strip.
|
|
If current measurement is not installed this value will always read 0."
|
|
::= { sBTAModulesRPCModPortEntry 6 }
|
|
|
|
sRPCMaxCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The maximum detected current reading for the power strip.
|
|
If current measurement is not installed this value will always read 0.
|
|
Setting this value to 0 will clear the maximum current detected."
|
|
::= { sBTAModulesRPCModPortEntry 7 }
|
|
|
|
sRPCVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The voltage reading for the power strip.
|
|
If voltage measurement is not installed this value will always read 0."
|
|
::= { sBTAModulesRPCModPortEntry 8 }
|
|
|
|
sRPCPower OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The power reading for the power strip.
|
|
If power measurement is not installed this value will always read 0."
|
|
::= { sBTAModulesRPCModPortEntry 9 }
|
|
|
|
sRPCTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The temperature reading for the power strip. Readings are in degrees C.
|
|
If temperature measurement is not installed this value will always read 0."
|
|
::= { sBTAModulesRPCModPortEntry 10 }
|
|
|
|
sRPCRebootTimeout OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The length of off time for automatic reboot sequences.
|
|
Currently a read-only value set to the fixed reboot timeout."
|
|
::= { sBTAModulesRPCModPortEntry 11 }
|
|
|
|
sRPCAllOutletsCmd OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off (0),
|
|
on (1),
|
|
reboot (2),
|
|
lockon (3),
|
|
lockoff (4),
|
|
unlock (5),
|
|
unknown (6)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Turns all outlets on, off or reboot.
|
|
0 = off
|
|
1 = on
|
|
2 = reboot
|
|
3 = lockon (will lock outlets to on state)
|
|
4 = lockoff (will lock outlets to off state)
|
|
5 = unlock (will unlock all outlets)
|
|
|
|
A get will return unknown (6)."
|
|
::= { sBTAModulesRPCModPortEntry 12 }
|
|
|
|
sRPCAllOutletsStatus OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Reports status of outlets in a comma deliminated string.
|
|
0 = off
|
|
1 = on
|
|
2 = reboot
|
|
3 = locked on
|
|
4 = locked off"
|
|
::= { sBTAModulesRPCModPortEntry 13 }
|
|
|
|
sRPCCurrentAlarmThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current alarm threshold level *10. A value of 105 will set the level to 10.5."
|
|
::= { sBTAModulesRPCModPortEntry 14 }
|
|
|
|
sRPCOverVoltageThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The over voltage alarm threshold level *10. A value of 105 will set the level to 10.5."
|
|
::= { sBTAModulesRPCModPortEntry 15 }
|
|
|
|
sRPCUnderVoltageThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The under voltage alarm threshold level *10. A value of 105 will set the level to 10.5."
|
|
::= { sBTAModulesRPCModPortEntry 16 }
|
|
sRPCNumberOfOutlets OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of outlets for this RPC.
|
|
This will be the size of outlet table for this RPC index."
|
|
::= { sBTAModulesRPCModPortEntry 17 }
|
|
|
|
|
|
sRPCCircuitBreaker OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off (0),
|
|
on (1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Status of circuit breaker in power strip. 0=off 1=on."
|
|
::= { sBTAModulesRPCModPortEntry 18 }
|
|
|
|
sRPCOverTempThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The over temperature alarm threshold level *10. A value of 505 will set the level to 50.5."
|
|
::= { sBTAModulesRPCModPortEntry 19 }
|
|
|
|
sRPCUnitVA OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of outlets for this RPC.
|
|
This will be the size of outlet table for this RPC index."
|
|
::= { sBTAModulesRPCModPortEntry 20 }
|
|
|
|
sRPCNumberOfBreakers OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of breakers for this RPC."
|
|
::= { sBTAModulesRPCModPortEntry 21 }
|
|
|
|
|
|
sRPCLowCurrentThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Low current threshold for this RPC."
|
|
::= { sBTAModulesRPCModPortEntry 22 }
|
|
|
|
sRPCVoltageSource OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Voltage source for this RPC."
|
|
::= { sBTAModulesRPCModPortEntry 23 }
|
|
|
|
sRPCSourceSwitchCount OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Voltage source switch count for this RPC."
|
|
::= { sBTAModulesRPCModPortEntry 24 }
|
|
|
|
sRPCNumberOfSensors OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of sensors for this RPC."
|
|
::= { sBTAModulesRPCModPortEntry 25 }
|
|
|
|
|
|
sBTAModulesRPCModPortOutletTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF SDSModulesRPCModPortOutletEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Allows for control of individual outlets. The number of
|
|
entries is contained in the sBTAModulesRPCOutletTableSize OID."
|
|
::= { sBTAModulesRPC 6 }
|
|
|
|
sBTAModulesRPCModPortOutletEntry OBJECT-TYPE
|
|
SYNTAX SDSModulesRPCModPortOutletEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The outlets to control and get status on."
|
|
INDEX { sRPCOutletModuleIndex, sRPCOutletPortIndex, sRPCOutletIndex}
|
|
::= { sBTAModulesRPCModPortOutletTable 1 }
|
|
|
|
SDSModulesRPCModPortOutletEntry ::=
|
|
SEQUENCE {
|
|
sRPCOutletModuleIndex INTEGER,
|
|
sRPCOutletPortIndex INTEGER,
|
|
sRPCOutletIndex INTEGER,
|
|
sRPCOutletState INTEGER,
|
|
sRPCOutletName DisplayString
|
|
}
|
|
|
|
sRPCOutletModuleIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The module index to the outlet entry."
|
|
::= { sBTAModulesRPCModPortOutletEntry 1 }
|
|
|
|
sRPCOutletPortIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The port index to the outlet entry. In the case of ds30s this number is always 1."
|
|
::= { sBTAModulesRPCModPortOutletEntry 2 }
|
|
|
|
sRPCOutletIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The outlet index to the outlet entry."
|
|
::= { sBTAModulesRPCModPortOutletEntry 3 }
|
|
|
|
sRPCOutletState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off (0),
|
|
on (1),
|
|
reboot (2),
|
|
lockon (3),
|
|
lockoff (4),
|
|
unlock (5),
|
|
unknown (6)
|
|
}
|
|
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Getting this variable will return the state of the outlet.
|
|
Valid return states are unknown, on, off, lockon, lockoff.
|
|
0 = off
|
|
1 = on
|
|
2 = reboot
|
|
3 = lockon (outlet is on and no changes are allowed)
|
|
4 = lockoff (outlet is off and no changes are allowed)
|
|
5 = unlock."
|
|
|
|
::= { sBTAModulesRPCModPortOutletEntry 4 }
|
|
|
|
|
|
sRPCOutletName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name of the outlet. Maximum size is 16 characters."
|
|
|
|
::= { sBTAModulesRPCModPortOutletEntry 5 }
|
|
|
|
sBTAModulesRPCModPortGroupCmd OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A character string listing the outlets that need to be rebooted,
|
|
turned off, or turn on as a group. Command is the first character
|
|
followed by a space. Valid commads are 0=off,1=on, or 2=reboot. A
|
|
list follows the command in the format module.port.outlet. For example
|
|
2 2.1.1,2.1.12,3.4.1 will reboot module 2 port 1 outlet 2&12 module 3 port 4 outlet 1."
|
|
::= { sBTAModulesRPC 7 }
|
|
|
|
|
|
-- Individual strip table (by breaker - for RPC 28 & other multi-breaker units)
|
|
|
|
sRPCModPortBreakersTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF SRPCModPortBreakersEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Allows monitoring of individual outlet strips on RPCs. "
|
|
::= { sBTAModulesRPC 10 }
|
|
|
|
sRPCModPortBreakersEntry OBJECT-TYPE
|
|
SYNTAX SRPCModPortBreakersEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Status organization by breaker."
|
|
INDEX { sRPCBreakersModIndex,sRPCBreakersPortIndex,sRPCBreakersBreakersIndex}
|
|
::= { sRPCModPortBreakersTable 1 }
|
|
|
|
SRPCModPortBreakersEntry ::=
|
|
SEQUENCE {
|
|
sRPCBreakersModIndex INTEGER,
|
|
sRPCBreakersPortIndex INTEGER,
|
|
sRPCBreakersBreakersIndex INTEGER,
|
|
sRPCBreakersCircuitBreaker INTEGER,
|
|
sRPCBreakersCurrent INTEGER,
|
|
sRPCBreakersMaxCurrent INTEGER,
|
|
sRPCBreakersVoltage INTEGER,
|
|
sRPCBreakersPower INTEGER,
|
|
sRPCBreakersVA INTEGER,
|
|
sRPCBreakersCurrentAlarmThreshold INTEGER
|
|
}
|
|
|
|
|
|
sRPCBreakersModIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The module index into the RPC breaker table."
|
|
::= { sRPCModPortBreakersEntry 1 }
|
|
|
|
sRPCBreakersPortIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The port index into the RPC breaker table."
|
|
::= { sRPCModPortBreakersEntry 2 }
|
|
|
|
sRPCBreakersBreakersIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The breaker index into the RPC breaker table."
|
|
::= { sRPCModPortBreakersEntry 3 }
|
|
|
|
sRPCBreakersCircuitBreaker OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off (0),
|
|
on (1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Status of circuit breaker in power strip. 0=off 1=on."
|
|
::= { sRPCModPortBreakersEntry 4 }
|
|
|
|
sRPCBreakersCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The detected current reading for the power strip.
|
|
If current measurement is not installed this value will always read 0."
|
|
::= { sRPCModPortBreakersEntry 5 }
|
|
|
|
sRPCBreakersMaxCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The maximum detected current reading for the power strip.
|
|
If current measurement is not installed this value will always read 0."
|
|
::= { sRPCModPortBreakersEntry 6 }
|
|
|
|
sRPCBreakersVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The voltage reading for the power strip.
|
|
If voltage measurement is not installed this value will always read 0."
|
|
::= { sRPCModPortBreakersEntry 7 }
|
|
|
|
sRPCBreakersPower OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The power reading for the power strip.
|
|
If voltage measurement is not installed this value will always read 0."
|
|
::= { sRPCModPortBreakersEntry 8 }
|
|
|
|
sRPCBreakersVA OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The volt-amps reading for the power strip.
|
|
If voltage measurement is not installed this value will always read 0."
|
|
::= { sRPCModPortBreakersEntry 9 }
|
|
|
|
sRPCBreakersCurrentAlarmThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current alarm threshold level x10. A value of 105 will set the level to 10.5."
|
|
::= { sRPCModPortBreakersEntry 10 }
|
|
|
|
-- the Environmental group
|
|
sBTAModulesEnvironmentalObjectsTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF SDSModulesEnvironmentalObjectsEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Allows monitoring of individual outlet strips on RPCs. "
|
|
::= { sBTAEnvironmental 1 }
|
|
|
|
sBTAModulesEnvironmentalObjectsEntry OBJECT-TYPE
|
|
SYNTAX SDSModulesEnvironmentalObjectsEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Status organization by sensor."
|
|
INDEX { sBTAModulesEnvironmentalModulesIndex, sBTAModulesEnvironmentalSensorsIndex}
|
|
::= { sBTAModulesEnvironmentalObjectsTable 1 }
|
|
|
|
|
|
SDSModulesEnvironmentalObjectsEntry ::=
|
|
SEQUENCE {
|
|
sBTAModulesEnvironmentalModulesIndex INTEGER,
|
|
sBTAModulesEnvironmentalSensorsIndex INTEGER,
|
|
sBTAModulesEnvironmentalType INTEGER,
|
|
sBTAModulesEnvironmentalName DisplayString,
|
|
sBTAModulesEnvironmentalMeasurement INTEGER,
|
|
sBTAModulesEnvironmentalHiThreshold INTEGER,
|
|
sBTAModulesEnvironmentalLoThreshold INTEGER,
|
|
sBTAModulesEnvironmentalMax INTEGER,
|
|
sBTAModulesEnvironmentalMin INTEGER,
|
|
sBTAModulesEnvironmentalHiThresholdEn INTEGER,
|
|
sBTAModulesEnvironmentalLoThresholdEn INTEGER,
|
|
sBTAModulesEnvironmentalStateTrapEn INTEGER
|
|
}
|
|
|
|
sBTAModulesEnvironmentalModulesIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Module Index for Environemntal table"
|
|
::= { sBTAModulesEnvironmentalObjectsEntry 1 }
|
|
|
|
sBTAModulesEnvironmentalSensorsIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Sensor Index for Environemntal table"
|
|
::= { sBTAModulesEnvironmentalObjectsEntry 2 }
|
|
|
|
sBTAModulesEnvironmentalType OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Environmental Object Type."
|
|
::= { sBTAModulesEnvironmentalObjectsEntry 3 }
|
|
|
|
sBTAModulesEnvironmentalName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name for the environmental object."
|
|
::= { sBTAModulesEnvironmentalObjectsEntry 4 }
|
|
|
|
sBTAModulesEnvironmentalMeasurement OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The measurement or state for the object."
|
|
::= { sBTAModulesEnvironmentalObjectsEntry 5 }
|
|
|
|
sBTAModulesEnvironmentalHiThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Hi threshold for object."
|
|
::= { sBTAModulesEnvironmentalObjectsEntry 6 }
|
|
|
|
sBTAModulesEnvironmentalLoThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Lo threshold for object."
|
|
::= { sBTAModulesEnvironmentalObjectsEntry 7 }
|
|
|
|
sBTAModulesEnvironmentalMax OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Max value recorded for object since last reset."
|
|
::= { sBTAModulesEnvironmentalObjectsEntry 8 }
|
|
|
|
sBTAModulesEnvironmentalMin OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Min value recorded for object since last reset."
|
|
::= { sBTAModulesEnvironmentalObjectsEntry 9 }
|
|
|
|
sBTAModulesEnvironmentalHiThresholdEn OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Hi threshold enable for object."
|
|
::= { sBTAModulesEnvironmentalObjectsEntry 10 }
|
|
|
|
sBTAModulesEnvironmentalLoThresholdEn OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Lo threshold enable for object."
|
|
::= { sBTAModulesEnvironmentalObjectsEntry 11 }
|
|
|
|
sBTAModulesEnvironmentalStateTrapEn OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Trap enable for environmental sensors with contacts."
|
|
::= { sBTAModulesEnvironmentalObjectsEntry 12 }
|
|
|
|
|
|
|
|
sRPCEnvironmentalObjectsTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF SRPCEnvironmentalObjectsEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Allows monitoring of individual outlet strips on RPCs. "
|
|
::= { sBTAEnvironmental 2 }
|
|
|
|
sRPCEnvironmentalObjectsEntry OBJECT-TYPE
|
|
SYNTAX SRPCEnvironmentalObjectsEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Status organization by sensor."
|
|
INDEX { sBTAEnvironmentalModuleIndex, sBTAEnvironmentalPortIndex, sBTAEnvironmentalSensorsIndex}
|
|
::= { sRPCEnvironmentalObjectsTable 1 }
|
|
|
|
|
|
SRPCEnvironmentalObjectsEntry ::=
|
|
SEQUENCE {
|
|
sRPCEnvironmentalModuleIndex INTEGER,
|
|
sRPCEnvironmentalPortIndex INTEGER,
|
|
sRPCEnvironmentalSensorsIndex INTEGER,
|
|
sRPCEnvironmentalType INTEGER,
|
|
sRPCEnvironmentalName DisplayString,
|
|
sRPCEnvironmentalMeasurement INTEGER,
|
|
sRPCEnvironmentalHiThreshold INTEGER,
|
|
sRPCEnvironmentalLoThreshold INTEGER,
|
|
sRPCEnvironmentalMax INTEGER,
|
|
sRPCEnvironmentalMin INTEGER,
|
|
sRPCEnvironmentalHiThresholdEn INTEGER,
|
|
sRPCEnvironmentalLoThresholdEn INTEGER,
|
|
sRPCEnvironmentalStateTrapEn INTEGER
|
|
}
|
|
|
|
sRPCEnvironmentalModuleIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Module Index for Environemntal table"
|
|
::= { sRPCEnvironmentalObjectsEntry 1 }
|
|
|
|
sRPCEnvironmentalPortIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Port Index for Environemntal table"
|
|
::= { sRPCEnvironmentalObjectsEntry 2 }
|
|
|
|
sRPCEnvironmentalSensorsIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Sensor Index for Environemntal table"
|
|
::= { sRPCEnvironmentalObjectsEntry 3 }
|
|
|
|
sRPCEnvironmentalType OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Environmental Object Type."
|
|
::= { sRPCEnvironmentalObjectsEntry 4 }
|
|
|
|
sRPCEnvironmentalName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name for the environmental object."
|
|
::= { sRPCEnvironmentalObjectsEntry 5 }
|
|
|
|
sRPCEnvironmentalMeasurement OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The measurement or state for the object."
|
|
::= { sRPCEnvironmentalObjectsEntry 6 }
|
|
|
|
sRPCEnvironmentalHiThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Hi threshold for object."
|
|
::= { sRPCEnvironmentalObjectsEntry 7 }
|
|
|
|
sRPCEnvironmentalLoThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Lo threshold for object."
|
|
::= { sRPCEnvironmentalObjectsEntry 8 }
|
|
|
|
sRPCEnvironmentalMax OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Max value recorded for object since last reset."
|
|
::= { sRPCEnvironmentalObjectsEntry 9 }
|
|
|
|
sRPCEnvironmentalMin OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Min value recorded for object since last reset."
|
|
::= { sRPCEnvironmentalObjectsEntry 10 }
|
|
|
|
sRPCEnvironmentalHiThresholdEn OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Hi threshold enable for object."
|
|
::= { sRPCEnvironmentalObjectsEntry 11 }
|
|
|
|
sRPCEnvironmentalLoThresholdEn OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Lo threshold enable for object."
|
|
::= { sRPCEnvironmentalObjectsEntry 12 }
|
|
|
|
sRPCEnvironmentalStateTrapEn OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Trap enable for environmental sensors with contacts."
|
|
::= { sRPCEnvironmentalObjectsEntry 13 }
|
|
|
|
sBTAEnvironmentalAllTemperatureSensorsHiThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Hi Threshold for all temperature sensors."
|
|
::= { sBTAEnvironmental 3 }
|
|
|
|
sBTAEnvironmentalAllTemperatureSensorsLoThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Lo Threshold for all temperature sensors."
|
|
::= { sBTAEnvironmental 4 }
|
|
|
|
sBTAEnvironmentalAllTemperatureSensorsHiThresholdTrapEnable OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Hi Threshold trap enable for all temperature sensors."
|
|
::= { sBTAEnvironmental 5 }
|
|
|
|
sBTAEnvironmentalAllTemperatureSensorsLoThresholdTrapEnable OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Lo Threshold trap enable for all temperature sensors."
|
|
::= { sBTAEnvironmental 6 }
|
|
|
|
sBTAEnvironmentalAllSensorsStateTrapEnable OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"State change environmental sensor (ex: contact) trap enable."
|
|
::= { sBTAEnvironmental 7 }
|
|
|
|
-- end of Module/Port MIB definitions
|
|
|
|
|
|
-- Traps
|
|
-- Annotations are provided for Novell's NMS product
|
|
|
|
communicationLost TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { mtrapargsTimeTicks }
|
|
DESCRIPTION
|
|
"SEVERE: Communication to the unit has been lost. Steps
|
|
to reestablish communication are in progress. Argument is timeTicks
|
|
when communication was lost."
|
|
--#TYPE "baytech: State change."
|
|
--#SUMMARY "The unit has lost communications."
|
|
--#SEVERITY SEVERE
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 1
|
|
|
|
communicationEstablished TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { mtrapargsString }
|
|
DESCRIPTION
|
|
"INFORMATION: Communication with the unit has been established.
|
|
Argument is timeTicks when communication was established."
|
|
--#TYPE "baytech: State change."
|
|
--#SUMMARY "The unit has established communications."
|
|
--#SEVERITY INFORMATION
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 2
|
|
|
|
outletOn TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { sBTAModuleIndex, sBTAOutletIndex }
|
|
DESCRIPTION
|
|
"WARNING: The specified RPC outlet has turned on.
|
|
If sBTAOutletIndex equals zero, then all outlets have turned on."
|
|
--#TYPE "baytech: State change."
|
|
--#SUMMARY "The specifed outlet is being rebooted."
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 3
|
|
|
|
outletOff TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { sBTAModuleIndex, sBTAOutletIndex }
|
|
DESCRIPTION
|
|
"WARNING: The specified RPC outlet has turned off.
|
|
If sBTAOutletIndex equals zero, then all outlets have turned off."
|
|
--#TYPE "baytech: State change."
|
|
--#SUMMARY "The specifed outlet is now on."
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 4
|
|
|
|
outletReboot TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { sBTAModuleIndex, sBTAOutletIndex }
|
|
DESCRIPTION
|
|
"WARNING: The specified RPC outlet has rebooted.
|
|
If sBTAOutletIndex equals zero, then all outlets have rebooted."
|
|
--#TYPE "baytech: State change."
|
|
--#SUMMARY "The specifed outlet is now off."
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 5
|
|
|
|
outletLocked TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { sBTAModuleIndex, sBTAOutletIndex }
|
|
DESCRIPTION
|
|
"WARNING: The specified RPC outlet has been locked.
|
|
If sBTAOutletIndex equals zero, then all outlets have been locked."
|
|
--#TYPE "baytech: State change."
|
|
--#SUMMARY "The specifed outlet has been locked."
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 6
|
|
|
|
outletUnlocked TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { sBTAModuleIndex, sBTAOutletIndex }
|
|
DESCRIPTION
|
|
"WARNING: The specified RPC outlet has been unlocked.
|
|
If sBTAOutletIndex equals zero, then all outlets have been unlocked."
|
|
--#TYPE "baytech: State change."
|
|
--#SUMMARY "The specifed outlet has been unlocked."
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 7
|
|
|
|
configChangeSNMP TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
DESCRIPTION
|
|
"WARNING: The SNMP configuration has been changed."
|
|
--#TYPE "baytech: State change."
|
|
--#SUMMARY "The SNMP configuration has been changed."
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 8
|
|
|
|
configChangeOutlet TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { sBTAModuleIndex, sBTAOutletIndex }
|
|
DESCRIPTION
|
|
"WARNING: The specified outlet has changed configuration."
|
|
--#TYPE "baytech: State change."
|
|
--#SUMMARY "An outlet configuration has been changed."
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 9
|
|
|
|
accessViolationConsole TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { mtrapargsString }
|
|
DESCRIPTION
|
|
"WARNING: Someone has attempted to login via the console with the incorrect password."
|
|
--#TYPE "baytech: Access violation."
|
|
--#SUMMARY "Three unsuccessful logins have been attempted."
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 10
|
|
|
|
accessViolationNetwork TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { mtrapargsString }
|
|
DESCRIPTION
|
|
"WARNING: Someone has attempted to login via the network with the incorrect password."
|
|
--#TYPE "baytech: Access violation."
|
|
--#SUMMARY "Three unsuccessful logins have been attempted."
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 11
|
|
|
|
userPasswordChange TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { mtrapargsString }
|
|
DESCRIPTION
|
|
"WARNING: The password for the specified user has been changed."
|
|
--#TYPE "baytech: Password change."
|
|
--#SUMMARY "Someone has changed the password for the specified user."
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 12
|
|
|
|
userAdded TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { mtrapargsString }
|
|
DESCRIPTION
|
|
"WARNING: The specified user has been added."
|
|
--#TYPE "baytech: Username change."
|
|
--#SUMMARY "Someone has added the specified user."
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 13
|
|
|
|
userLoggedIn TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { mtrapargsString }
|
|
DESCRIPTION
|
|
"INFORMATIONAL: The specified user has logged in. "
|
|
--#TYPE "baytech: User logged in."
|
|
--#SUMMARY "Someone has logged in as the specified user."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 14
|
|
|
|
temperatureThresholdViolation TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { mtrapargsInteger }
|
|
DESCRIPTION
|
|
"WARNING: A temperature threshold has been violated. The argument is the rpc index."
|
|
--#TYPE "baytech: Alarm."
|
|
--#SUMMARY "A temperature threshold has been violated."
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 15
|
|
|
|
temperatureThresholdViolationCleared TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { mtrapargsInteger }
|
|
DESCRIPTION
|
|
"INFORMATIONAL: A temperature threshold violated has been cleared. The argument is the rpc index."
|
|
--#TYPE "baytech: Alarm."
|
|
--#SUMMARY "A temperature threshold violation has been cleared."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 16
|
|
|
|
currentThresholdViolation TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { mtrapargsInteger }
|
|
DESCRIPTION
|
|
"WARNING: The preset current threshold has been violated. The argument is the rpc index."
|
|
--#TYPE "baytech: Alarm."
|
|
--#SUMMARY "A current threshold has been violated."
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 17
|
|
|
|
currentThresholdViolationCleared TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { mtrapargsString }
|
|
DESCRIPTION
|
|
"INFORMATIONAL: A current threshold violation has been cleared. The argument is the rpc index."
|
|
--#TYPE "baytech: Alarm."
|
|
--#SUMMARY "A current threshold violation has been cleared."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 18
|
|
|
|
resetModulesEvent TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { mtrapargsString }
|
|
DESCRIPTION
|
|
"WARNING: A reset modules (RM) command has been executed."
|
|
--#TYPE "baytech: Reset alert."
|
|
--#SUMMARY "Sent when a reset modules command is executed."
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 19
|
|
|
|
resetModulesComplete TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { mtrapargsString }
|
|
DESCRIPTION
|
|
"WARNING: A reset modules (RM) command has been completed."
|
|
--#TYPE "baytech: Reset alert."
|
|
--#SUMMARY "The reset module command is complete."
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 20
|
|
|
|
errorExecutingSNMPCommand TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { mtrapargsString }
|
|
DESCRIPTION
|
|
"WARNING: unable to execute SNMP command. String contains reason and command."
|
|
--#TYPE "baytech: Error."
|
|
--#SUMMARY "Unable to execute SNMP command."
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 21
|
|
|
|
fileTransferComplete TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
DESCRIPTION
|
|
"INFORMATIONAL: file transfer to unit complete."
|
|
--#TYPE "baytech: file transfer."
|
|
--#SUMMARY "The file transer is complete."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 22
|
|
|
|
userTerminated TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { mtrapargsInteger }
|
|
DESCRIPTION
|
|
"WARNING: user terminated. Argument specifies user."
|
|
--#TYPE "baytech: user terminated."
|
|
--#SUMMARY "User terminated."
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 23
|
|
|
|
voltageOverThresholdViolation TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { mtrapargsInteger }
|
|
DESCRIPTION
|
|
"WARNING: Over voltage. Argument specifies rpc."
|
|
--#TYPE "baytech: over voltage."
|
|
--#SUMMARY "Over voltage."
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 24
|
|
|
|
voltageOverThresholdViolationCleared TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { mtrapargsInteger }
|
|
DESCRIPTION
|
|
"INFORMATIONAL: Over voltage cleared. Argument specifies rpc."
|
|
--#TYPE "baytech: over voltage cleared."
|
|
--#SUMMARY "Over voltage cleared."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 25
|
|
|
|
voltageUnderThresholdViolation TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { mtrapargsInteger }
|
|
DESCRIPTION
|
|
"WARNING: Under voltage. Argument specifies rpc."
|
|
--#TYPE "baytech: under voltage."
|
|
--#SUMMARY "Under voltage."
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 26
|
|
|
|
voltageUnderThresholdViolationCleared TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { mtrapargsInteger }
|
|
DESCRIPTION
|
|
"INFORMATIONAL: Under voltage cleared. Argument specifies rpc."
|
|
--#TYPE "baytech: under voltage cleared."
|
|
--#SUMMARY "Under voltage cleared."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 27
|
|
|
|
circuitBreakerAlarm TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { mtrapargsInteger }
|
|
DESCRIPTION
|
|
"WARNING: Circuit breaker is blown. Argument specifies rpc."
|
|
--#TYPE "baytech: circuit breaker."
|
|
--#SUMMARY "circuit breaker."
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 28
|
|
|
|
rpcFailureAlarm TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { mtrapargsInteger }
|
|
DESCRIPTION
|
|
"WARNING: Unable to communicate to an RPC. Argument specifies port number of RPC."
|
|
--#TYPE "baytech: module failure."
|
|
--#SUMMARY "RPC failure."
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 29
|
|
|
|
userDeleted TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { mtrapargsString }
|
|
DESCRIPTION
|
|
"INFORMATIONAL: The specified user has logged in. "
|
|
--#TYPE "baytech: User logged in."
|
|
--#SUMMARY "Someone has logged in as the specified user."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 30
|
|
|
|
warningThresholdViolation TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { mtrapargsInteger }
|
|
DESCRIPTION
|
|
" "
|
|
--#TYPE "baytech: warning alarm"
|
|
--#SUMMARY "group current exceeds warning threshold"
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 31
|
|
|
|
warningThresholdViolationClear TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { mtrapargsInteger }
|
|
DESCRIPTION
|
|
" "
|
|
--#TYPE "baytech: warning alarm cleared"
|
|
--#SUMMARY "group current has dropped below warning threshold"
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 32
|
|
|
|
emergencyThresholdViolation TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { mtrapargsInteger }
|
|
DESCRIPTION
|
|
" "
|
|
--#TYPE "baytech: emergency alarm"
|
|
--#SUMMARY "group current exceeds emergency threshold"
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 33
|
|
|
|
emergencyThresholdViolationClear TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { mtrapargsInteger }
|
|
DESCRIPTION
|
|
" "
|
|
--#TYPE "baytech: emergency alarm cleared"
|
|
--#SUMMARY "group current has dropped below emergency threshold"
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 34
|
|
|
|
circuitBreakerAlarmClearTrap TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { mtrapargsInteger }
|
|
DESCRIPTION
|
|
"Circuit breaker has been reset. Argument specifies rpc."
|
|
--#TYPE "baytech: circuit breaker."
|
|
--#SUMMARY "circuit breaker reset."
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 35
|
|
|
|
currentUnderThresholdViolation TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { mtrapargsInteger }
|
|
DESCRIPTION
|
|
"WARNING: Low current. Argument specifies rpc."
|
|
--#TYPE "baytech: low current."
|
|
--#SUMMARY "Low current."
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 36
|
|
|
|
currentUnderThresholdViolationCleared TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { mtrapargsInteger }
|
|
DESCRIPTION
|
|
"INFORMATIONAL: Low current cleared. Argument specifies rpc."
|
|
--#TYPE "baytech: low current cleared."
|
|
--#SUMMARY "Low current cleared."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 37
|
|
|
|
voltageSourceChangeAlarm TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { sBTAModuleIndex, sBTAVoltageSource,sBTASourceSwitchCount }
|
|
DESCRIPTION
|
|
"WARNING: RPC voltage source has changed. Arguments specify modules index, current voltage source, and count of number of times source has been switched."
|
|
--#TYPE "baytech: voltage source."
|
|
--#SUMMARY "voltage source."
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 38
|
|
|
|
sensorTempThreshHiAlarmTrap TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { sBTAModuleIndex, sBTASensorIndex }
|
|
DESCRIPTION
|
|
"WARNING: Hi threshold exceeded. Arguments specify module, sensor number"
|
|
--#TYPE "baytech. Hi threshold exceeded"
|
|
--#SUMMARY "Hi sensor threshold exceeded"
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 39
|
|
|
|
sensorTempThreshHiAlarmClearedTrap TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { sBTAModuleIndex, sBTASensorIndex }
|
|
DESCRIPTION
|
|
"WARNING: Hi threshold alarm cleared. Arguments specify module, sensor number"
|
|
--#TYPE "baytech. Hi threshold alarm cleared"
|
|
--#SUMMARY "Hi sensor threshold alarm cleared"
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 40
|
|
|
|
sensorTempThreshLoAlarmTrap TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { sBTAModuleIndex, sBTASensorIndex }
|
|
DESCRIPTION
|
|
"WARNING: Lo threshold alarm cleared. Arguments specify module, sensor number"
|
|
--#TYPE "baytech. Lo threshold alarm cleared"
|
|
--#SUMMARY "Lo sensor threshold alarm cleared"
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 41
|
|
|
|
sensorTempThreshLoAlarmClearedTrap TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { sBTAModuleIndex, sBTASensorIndex }
|
|
DESCRIPTION
|
|
"WARNING: Lo threshold alarm cleared. Arguments specify module, sensor number"
|
|
--#TYPE "baytech. Lo threshold alarm cleared"
|
|
--#SUMMARY "Lo sensor threshold alarm cleared"
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 42
|
|
|
|
sensorStateChangeTrap TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { sBTAModuleIndex, sBTASensorIndex }
|
|
DESCRIPTION
|
|
"WARNING: Sensor state (contact, detector, etc) has changed. Arguments specify module, sensor number"
|
|
--#TYPE "baytech. Sensor state has changed"
|
|
--#SUMMARY "Sensor state has changed"
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 43
|
|
|
|
configChangeSensor TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { sBTAModuleIndex, sBTASensorIndex }
|
|
DESCRIPTION
|
|
"WARNING: The specified environmental sensor has changed configuration."
|
|
--#TYPE "baytech: State change."
|
|
--#SUMMARY "A sensor configuration has been changed."
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 44
|
|
|
|
sensorTypeChange TRAP-TYPE
|
|
ENTERPRISE baytech
|
|
VARIABLES { sBTAModuleIndex, sBTASensorIndex }
|
|
DESCRIPTION
|
|
"WARNING: The specified environmental sensor is now a different type."
|
|
--#TYPE "baytech: Type change."
|
|
--#SUMMARY "A sensor type has been changed."
|
|
--#SEVERITY WARNING
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 45
|
|
|
|
END
|
|
|