Observium_CE/mibs/aten/ATEN-PE2-CFG

2946 lines
105 KiB
Plaintext

-- MIB version: 1.1.104
-- MIB release note
-- | date | MIB version | note
---------------------------------------------------------------------------------------------------
-- | 2018/02/13 | 1.1.101 | Initial version
---------------------------------------------------------------------------------------------------
-- | 2018/03/01 | 1.1.102 | Modify descriptions of bankStatusRatedCur, outletStatusRatedCur, and outletStatusSwitchable
---------------------------------------------------------------------------------------------------
-- | 2019/09/09 | 1.1.103 | Add staStatusHasAutoPing, outletStatusAutoPing, outletConfigAutoPing. Modify sensorConfigTable, sensorReadingTable to support port-address indexing
---------------------------------------------------------------------------------------------------
-- | 2019/10/08 | 1.1.104 | Add trapNotification. Add netConfigTable to support port indexing for dual-network
---------------------------------------------------------------------------------------------------
-- | 2020/11/23 | 1.1.105 | Add deviceLock to change password of SNMP for California passes law
---------------------------------------------------------------------------------------------------
-- | 2021/05/06 | 1.1.106 | Add phase layout of outlet and bank
---------------------------------------------------------------------------------------------------
-- | 2021/08/24 | 1.1.107 | Add inlet entry and inlet number
---------------------------------------------------------------------------------------------------
-- | 2021/10/01 | 1.1.108 | Add smoke sensor in dry contact
---------------------------------------------------------------------------------------------------
-- | 2021/11/02 | 1.1.109 | Add InetAddress and InetAddressType for support ipv4/ipv6
---------------------------------------------------------------------------------------------------
-- ATEN International Co., Ltd.
-- This file defines the mib struct of Management in PE series
-- We attach this mib node on enterprises.aten.atenProducts.overip.poweroverip.pe2 subtree
ATEN-PE2-CFG DEFINITIONS ::= BEGIN
IMPORTS
enterprises, IpAddress, Gauge, TimeTicks FROM RFC1155-SMI
DisplayString FROM RFC1213-MIB
OBJECT-TYPE FROM RFC-1212
TRAP-TYPE FROM RFC-1215
MODULE-IDENTITY, NOTIFICATION-TYPE FROM SNMPv2-SMI
KeyChange FROM SNMP-USER-BASED-SM-MIB
MacAddress FROM SNMPv2-TC
poweroverip FROM ATEN-PRODUCTS-MIB
InetAddressType, InetAddress, InetPortNumber FROM INET-ADDRESS-MIB;
pe2 MODULE-IDENTITY
LAST-UPDATED "201801231200Z"
ORGANIZATION "ATEN"
CONTACT-INFO "Aten, Inc."
DESCRIPTION "ATEN PE MIB"
REVISION "201801231200Z"
DESCRIPTION "support stations"
::= { poweroverip 3 }
management OBJECT IDENTIFIER ::= { pe2 1 }
energy OBJECT IDENTIFIER ::= { pe2 2 }
device OBJECT IDENTIFIER ::= { energy 1 }
bank OBJECT IDENTIFIER ::= { energy 2 }
outlet OBJECT IDENTIFIER ::= { energy 3 }
line OBJECT IDENTIFIER ::= { energy 4 }
inlet OBJECT IDENTIFIER ::= { energy 5 }
environment OBJECT IDENTIFIER ::= { pe2 3 }
sensor OBJECT IDENTIFIER ::= { environment 1 }
dryContact OBJECT IDENTIFIER ::= { environment 2 }
network OBJECT IDENTIFIER ::= { pe2 4 }
event OBJECT IDENTIFIER ::= { pe2 5 }
trap OBJECT IDENTIFIER ::= { event 1 }
trapNotification OBJECT IDENTIFIER ::= { pe2 50 }
deviceLock OBJECT IDENTIFIER ::= { pe2 150 }
---------------------------------------------------------------------------------------------------
-- Management
---------------------------------------------------------------------------------------------------
staCount OBJECT-TYPE
SYNTAX INTEGER (1..16)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The available station count which includes master and slave stations."
::= { management 1 }
staStatusTable OBJECT-TYPE
SYNTAX SEQUENCE OF StaStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Station status table."
::= { management 2 }
staStatusEntry OBJECT-TYPE
SYNTAX StaStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing station status info."
INDEX { staId }
::= { staStatusTable 1 }
StaStatusEntry ::=
SEQUENCE {
staId INTEGER,
staStatusFWVer DisplayString,
staStatusModelName DisplayString,
staStatusSwitchable INTEGER,
staStatusPerPortReading INTEGER,
staStatusBankCount INTEGER,
staStatusOutletCount INTEGER,
staStatusSensorCount INTEGER,
staStatusHasAutoPing INTEGER,
staStatusInletCount INTEGER
}
staId OBJECT-TYPE
SYNTAX INTEGER (1..16)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Station ID."
::= { staStatusEntry 1 }
staStatusFWVer OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Station FW version.
If the station is not available, it returns 'station N/A'."
::= { staStatusEntry 2 }
staStatusModelName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Station model name.
If the station is not available, it returns 'station N/A'"
::= { staStatusEntry 3 }
staStatusSwitchable OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2), mix(3) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Outlets of the station are switchable or not.
If the station is not available, it returns value -3000000."
::= { staStatusEntry 4 }
staStatusPerPortReading OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Outlets of the station are per-port reading or not.
If the station is not available, it returns value -3000000."
::= { staStatusEntry 5 }
staStatusBankCount OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Station bank count.
If the station is not available, it returns value -3000000."
::= { staStatusEntry 6 }
staStatusOutletCount OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Station outlet count.
If the station is not available, it returns value -3000000."
::= { staStatusEntry 7 }
staStatusSensorCount OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Station sensor count.
If the station is not available, it returns value -3000000."
::= { staStatusEntry 8 }
staStatusHasAutoPing OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The station supports auto-ping or not.
If the station is not available, it returns value -3000000."
::= { staStatusEntry 9 }
staStatusInletCount OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Station inlet count.
If the station is not available, it returns value -3000000."
::= { staStatusEntry 10 }
---------------------------------------------------------------------------------------------------
-- staControlTable
---------------------------------------------------------------------------------------------------
staControlTable OBJECT-TYPE
SYNTAX SEQUENCE OF StaControlEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Station control table."
::= { management 3 }
staControlEntry OBJECT-TYPE
SYNTAX StaControlEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing station control info."
INDEX { staId }
::= { staControlTable 1 }
StaControlEntry ::=
SEQUENCE {
staControlReboot
INTEGER
}
staControlReboot OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2), not-support(4) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Reboot the station.
If the station is not available, it returns value -3000000."
::= { staControlEntry 1 }
---------------------------------------------------------------------------------------------------
-- rackConfigTable
---------------------------------------------------------------------------------------------------
rackConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF RackConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Rack config table."
::= { management 4 }
rackConfigEntry OBJECT-TYPE
SYNTAX RackConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing rack config info."
INDEX { staId }
::= { rackConfigTable 1 }
RackConfigEntry ::=
SEQUENCE {
rackConfigName DisplayString,
rackConfigRow INTEGER,
rackConfigColumn INTEGER
}
rackConfigName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set station's rack name.
string length: 1~32
If the station is not available, it returns 'station N/A'.
NOTE: Input string as /empty to set this object to NULL."
::= { rackConfigEntry 1 }
rackConfigRow OBJECT-TYPE
SYNTAX INTEGER (1..26)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set station's rack row number.
If the station is not available, it returns value -3000000."
::= { rackConfigEntry 2 }
rackConfigColumn OBJECT-TYPE
SYNTAX INTEGER (1..26)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set station's rack column number.
If the station is not available, it returns value -3000000."
::= { rackConfigEntry 3 }
staState OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Cascade stations' state. Return string length equals to the MAX support stations.
If station N is alive, display 1 at the N's character, else, display 0.
The first character is always 1 as it belongs to the Master."
::= { management 5 }
---------------------------------------------------------------------------------------------------
-- devStatusTable
---------------------------------------------------------------------------------------------------
devStatusTable OBJECT-TYPE
SYNTAX SEQUENCE OF DevStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Device status table."
::= { device 1 }
devStatusEntry OBJECT-TYPE
SYNTAX DevStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing device status info."
INDEX { staId }
::= { devStatusTable 1 }
DevStatusEntry ::=
SEQUENCE {
devStatusRatedCur INTEGER,
devStatusRatedVol INTEGER,
devStatusRatedPower INTEGER,
devStatusWiredType INTEGER
}
devStatusRatedCur OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Device input Current value. unit:(0.1mA)
If the station does not support this OID, we show value 0.
If the station is not available, it returns value -3000000."
::= { devStatusEntry 1 }
devStatusRatedVol OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Device input Voltage value. unit:(0.1mV)
If the station does not support this OID, we show value 0.
If the station is not available, it returns value -3000000."
::= { devStatusEntry 2 }
devStatusRatedPower OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Device power Capacity value. unit:(0.1mVA)
If the station does not support this OID, we show value 0.
If the station is not available, it returns value -3000000."
::= { devStatusEntry 3 }
devStatusWiredType OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Device circuit wired type
Example: 1 for 1 phase, 2 for 3 phase wye, 3 for 3 phase delta
If the station does not support this OID, we show value 0.
If the station is not available, it returns value -3000000."
::= { devStatusEntry 4 }
---------------------------------------------------------------------------------------------------
-- devConfigTable
---------------------------------------------------------------------------------------------------
devConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF DevConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Device config table."
::= { device 2 }
devConfigEntry OBJECT-TYPE
SYNTAX DevConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing device config info."
INDEX { staId }
::= { devConfigTable 1 }
DevConfigEntry ::=
SEQUENCE {
devConfigDevName DisplayString,
devConfigPowerOnScheduleEn INTEGER,
devConfigOutletsSequentialRebootEn INTEGER,
devConfigMinCurThresh INTEGER,
devConfigMaxCurThresh INTEGER,
devConfigMinVolThresh INTEGER,
devConfigMaxVolThresh INTEGER,
devConfigMinPowerThresh INTEGER,
devConfigMaxPowerThresh INTEGER,
devConfigMaxPDThresh INTEGER
}
devConfigDevName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The name of the device.
string length: 1~39
If the station is not available, it returns 'station N/A'.
NOTE: Input string as /empty to set this object to NULL."
::= { devConfigEntry 1 }
devConfigPowerOnScheduleEn OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), no-delaytime(1), delaytime(2), not-support(3) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set whether power on schedule or not.
If the station is not available, it returns value -3000000."
::= { devConfigEntry 2 }
devConfigOutletsSequentialRebootEn OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2), not-support(3) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This function is used to enable or disable all outlet ports to sequential reboot.
If the station is not available, it returns value -3000000."
::= { devConfigEntry 3 }
devConfigMinCurThresh OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set device minimum electric current measurement threshold.
Example: range 0.0~32.0 represents 0~320.
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { devConfigEntry 4 }
devConfigMaxCurThresh OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set device maximum electric current measurement threshold.
Example: range 0.0~32.0 represents 0~320
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { devConfigEntry 5 }
devConfigMinVolThresh OBJECT-TYPE
SYNTAX INTEGER (-3000 | 900..2600)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set device minimum voltage measurement threshold.
Example: range 90.0~260.0 represents 900~2600
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { devConfigEntry 6 }
devConfigMaxVolThresh OBJECT-TYPE
SYNTAX INTEGER (-3000 | 900..2600)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set device maximum voltage measurement threshold.
Example: range 90.0~260.0 represents 900~2600
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { devConfigEntry 7 }
devConfigMinPowerThresh OBJECT-TYPE
SYNTAX INTEGER (-3000 | 0..99999)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set device minimum power measurement threshold.
Example: range 0.0 ~ 9999.9 represents 0~99999
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { devConfigEntry 8 }
devConfigMaxPowerThresh OBJECT-TYPE
SYNTAX INTEGER (-3000 | 0..99999)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set device maximum power measurement threshold.
Example: range 0.0 ~ 9999.9 represents 0~99999
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { devConfigEntry 9 }
devConfigMaxPDThresh OBJECT-TYPE
SYNTAX INTEGER (-3000 | 0..999990)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set device maximum power dissipation measurement threshold.
Example: range 0.0 ~ 99999.0 represents 0~999990
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { devConfigEntry 10 }
---------------------------------------------------------------------------------------------------
-- devControlTable
---------------------------------------------------------------------------------------------------
devControlTable OBJECT-TYPE
SYNTAX SEQUENCE OF DevControlEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Device control table."
::= { device 3 }
devControlEntry OBJECT-TYPE
SYNTAX DevControlEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing device control info."
INDEX { staId }
::= { devControlTable 1 }
DevControlEntry ::=
SEQUENCE {
devControlOperation
INTEGER
}
devControlOperation OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), off(1), on(2), reboot(3), nostatus(4), not-support(5) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This function is used for outlet control of device.
Set off(1) to turn off for outlet control of device.
Set on(2) to turn on for all outlet control of device.
Set reboot(3) to reboot for outlet control of device.
Get this object always return nostatus(3), because there is no device status.
If the station is not available, it returns value -3000000."
::= { devControlEntry 1 }
---------------------------------------------------------------------------------------------------
-- devReadingTable
---------------------------------------------------------------------------------------------------
devReadingTable OBJECT-TYPE
SYNTAX SEQUENCE OF DevReadingEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Device reading table."
::= { device 4 }
devReadingEntry OBJECT-TYPE
SYNTAX DevReadingEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing device reading info."
INDEX { staId }
::= { devReadingTable 1 }
DevReadingEntry ::=
SEQUENCE {
devReadingCur INTEGER,
devReadingVol INTEGER,
devReadingPower INTEGER,
devReadingPD INTEGER,
devReadingPF INTEGER
}
devReadingCur OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Device electric current value.
This value indicates that 10,000 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { devReadingEntry 1 }
devReadingVol OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Device voltage value.
This value indicates that 10,000 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { devReadingEntry 2 }
devReadingPower OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Device power value.
This value indicates that 10,000 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { devReadingEntry 3 }
devReadingPD OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Device power dissipation value.
This value indicates that 10,000 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { devReadingEntry 4 }
devReadingPF OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Device power factor value.
This value indicates that 100 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { devReadingEntry 5 }
---------------------------------------------------------------------------------------------------
-- popConfigTable
---------------------------------------------------------------------------------------------------
popConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF PopConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"POP config table."
::= { device 5 }
popConfigEntry OBJECT-TYPE
SYNTAX PopConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing POP config info."
INDEX { staId }
::= { popConfigTable 1 }
PopConfigEntry ::=
SEQUENCE {
popConfigOutletModeEn INTEGER,
popConfigLIFOModeEn INTEGER,
popConfigPriorityModeEn INTEGER,
popConfigPriorityList DisplayString
}
popConfigOutletModeEn OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2), not-support(3) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set whether outlet POP mode is enabled or not.
If the station is not available, it returns value -3000000."
::= { popConfigEntry 1 }
popConfigLIFOModeEn OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2), not-support(3) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set whether LIFO POP mode is enabled or not.
If the station is not available, it returns value -3000000."
::= { popConfigEntry 2 }
popConfigPriorityModeEn OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2), not-support(3) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set whether priority POP mode is enabled or not.
If the station is not available, it returns value -3000000."
::= { popConfigEntry 3 }
popConfigPriorityList OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Indicate Outlets' power OFF priorities under Priority POP mode.
Outlet Separator ','
Bank Separator '#'
Assign each priority in each bank by Outlet index or zero (indicate N/A) with separators in ascendant order.
e.g. for model PE8324 ( Bank1: outlet 1 ~ 16, Bank2: outlet 17 ~ 24 )
If you want to assign priority 2, 5 of Bank 1 with Outlet 14, 3,
and priority 2, 6, 8 with of Bank 2 with Outlet 17, 23, 24 and left the rest with N/A,
please type: 0,14,0,0,3,0,0,0,0,0,0,0,0,0,0,0#0,17,0,0,0,23,0,24.
If the station is not available, it returns 'station N/A'."
::= { popConfigEntry 4 }
---------------------------------------------------------------------------------------------------
-- capConfigTable
---------------------------------------------------------------------------------------------------
capConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF CapConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"CAP config table."
::= { device 6 }
capConfigEntry OBJECT-TYPE
SYNTAX CapConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing CAP config info."
INDEX { staId, outletId }
::= { capConfigTable 1 }
CapConfigEntry ::=
SEQUENCE {
capConfigModeEn INTEGER
}
capConfigModeEn OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set whether CAP mode is enabled or not.
If the station is not available, it returns value -3000000."
::= { capConfigEntry 1 }
---------------------------------------------------------------------------------------------------
-- capPriorityConfigTable
---------------------------------------------------------------------------------------------------
capPriorityConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF CapPriorityConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"CAP priority config table."
::= { device 7 }
capPriorityConfigEntry OBJECT-TYPE
SYNTAX CapPriorityConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing CAP priority config info."
INDEX { staId, outletId }
::= { capPriorityConfigTable 1 }
CapPriorityConfigEntry ::=
SEQUENCE {
capPriorityConfigOutlet INTEGER
}
capPriorityConfigOutlet OBJECT-TYPE
SYNTAX INTEGER (0..99)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the CAP Priority of outlet.
Priority 0 means this outlet does not support this OID.
If the station is not available, it returns value -3000000."
::= { capPriorityConfigEntry 1 }
---------------------------------------------------------------------------------------------------
-- bankStatusTable
---------------------------------------------------------------------------------------------------
bankStatusTable OBJECT-TYPE
SYNTAX SEQUENCE OF BankStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Bank status table."
::= { bank 1 }
bankStatusEntry OBJECT-TYPE
SYNTAX BankStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing bank status info."
INDEX { staId, bankId }
::= { bankStatusTable 1 }
BankStatusEntry ::=
SEQUENCE {
bankId INTEGER,
bankStatusRatedCur INTEGER,
bankStatusAttachStatus INTEGER,
bankStatusBreakerStatus INTEGER,
bankStatusPhaseLayout INTEGER
}
bankId OBJECT-TYPE
SYNTAX INTEGER (1..30)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Bank ID."
::= { bankStatusEntry 1 }
bankStatusRatedCur OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The Bank Max Current value. unit: (0.1mA).
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { bankStatusEntry 2 }
bankStatusAttachStatus OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), noattached(1), attached(2), error(3), noexisted(4) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The bank attached status.
If the station is not available, it returns value -3000000."
::= { bankStatusEntry 3 }
bankStatusBreakerStatus OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), off(1), on(2), not-support(3) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The breaker status.
If the station is not available, it returns value -3000000."
::= { bankStatusEntry 4 }
bankStatusPhaseLayout OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), not-support(-2000000), l1-n(1), l2-n(2), l3-n(3), l1-l2(4), l2-l3(5), l3-l1(6) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Display the phase layout of bank.
Example: range 1 ~ 3 represents Line1-LineNeutral ~ Line3-lineNeutral.
4 ~ 6 represents Line1-Line2, Line2-Line3, Line3-Line1.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { bankStatusEntry 5 }
---------------------------------------------------------------------------------------------------
-- bankConfigTable
---------------------------------------------------------------------------------------------------
bankConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF BankConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Bank config table."
::= { bank 2 }
bankConfigEntry OBJECT-TYPE
SYNTAX BankConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing bank config info."
INDEX { staId, bankId }
::= { bankConfigTable 1 }
BankConfigEntry ::=
SEQUENCE {
bankConfigName DisplayString,
bankConfigMinCurThresh INTEGER,
bankConfigMaxCurThresh INTEGER,
bankConfigMinVolThresh INTEGER,
bankConfigMaxVolThresh INTEGER,
bankConfigMinPowerThresh INTEGER,
bankConfigMaxPowerThresh INTEGER,
bankConfigMaxPDThresh INTEGER
}
bankConfigName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the name of the bank.
When this model does not support the OID, we show n/a.
string length: 0~15
If the station is not available, it returns 'station N/A'.
NOTE: Input string as /empty to set this object to NULL."
::= { bankConfigEntry 1 }
bankConfigMinCurThresh OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the bank minimum electric current measurement threshold.
Example: range 0.0 ~16.0 represents 0~160
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { bankConfigEntry 2 }
bankConfigMaxCurThresh OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the bank maximum electric current measurement threshold.
Example: range 0.0 ~16.0 represents 0~160
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { bankConfigEntry 3 }
bankConfigMinVolThresh OBJECT-TYPE
SYNTAX INTEGER (-2000000 | -3000 | 900..2600)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the bank minimum voltage measurement threshold.
Example: range 90.0 ~260.0 represents 900~2600
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { bankConfigEntry 4 }
bankConfigMaxVolThresh OBJECT-TYPE
SYNTAX INTEGER (-2000000 | -3000 | 900..2600)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the bank maximum voltage measurement threshold.
Example: range 90.0 ~260.0 represents 900~2600
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { bankConfigEntry 5 }
bankConfigMinPowerThresh OBJECT-TYPE
SYNTAX INTEGER (-2000000 | -3000 | 0..99999)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the bank minimum power measurement threshold.
Example: range 0.0 ~ 9999.9 represents 0~99999
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { bankConfigEntry 6 }
bankConfigMaxPowerThresh OBJECT-TYPE
SYNTAX INTEGER (-2000000 | -3000 | 0..99999)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the bank maximum power measurement threshold.
Example: range 0.0 ~ 9999.9 represents 0~99999
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { bankConfigEntry 7 }
bankConfigMaxPDThresh OBJECT-TYPE
SYNTAX INTEGER (-2000000 | -3000 | 0..999990)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the bank maximum power dissipation measurement threshold.
Example: range 0.0 ~ 99999.0 represents 0~999990
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { bankConfigEntry 8 }
---------------------------------------------------------------------------------------------------
-- bankControlTable
---------------------------------------------------------------------------------------------------
bankControlTable OBJECT-TYPE
SYNTAX SEQUENCE OF BankControlEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Bank control table."
::= { bank 3 }
bankControlEntry OBJECT-TYPE
SYNTAX BankControlEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing bank control info."
INDEX { staId, bankId }
::= { bankControlTable 1 }
BankControlEntry ::=
SEQUENCE {
bankControlOperation
INTEGER
}
bankControlOperation OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), off(1), on(2), reboot(3), nostatus(4), not-support(5) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This function is used for outlet control of bank.
Set off(1) to turn off for outlet control of bank.
Set on(2) to turn on for all outlet control of bank.
Set reboot(3) to reboot for outlet control of bank.
Get this object always return nostatus(3), because there is no bank status.
If the station is not available, it returns value -3000000."
::= { bankControlEntry 1 }
---------------------------------------------------------------------------------------------------
-- bankReadingTable
---------------------------------------------------------------------------------------------------
bankReadingTable OBJECT-TYPE
SYNTAX SEQUENCE OF BankReadingEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Bank reading table."
::= { bank 4 }
bankReadingEntry OBJECT-TYPE
SYNTAX BankReadingEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing bank reading info."
INDEX { staId, bankId }
::= { bankReadingTable 1 }
BankReadingEntry ::=
SEQUENCE {
bankReadingCur INTEGER,
bankReadingVol INTEGER,
bankReadingPower INTEGER,
bankReadingPD INTEGER,
bankReadingPF INTEGER
}
bankReadingCur OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Bank electric current value.
This value indicates that 10,000 times.
If this measurement value is not available, it returns value -1000000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { bankReadingEntry 1 }
bankReadingVol OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Bank voltage value.
This value indicates that 10,000 times.
If this measurement value is not available, it returns value -1000000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { bankReadingEntry 2 }
bankReadingPower OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Bank power value.
This value indicates that 10,000 times.
If this measurement value is not available, it returns value -1000000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { bankReadingEntry 3 }
bankReadingPD OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Bank power dissipation value.
This value indicates that 10,000 times.
If this measurement value is not available, it returns value -1000000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { bankReadingEntry 4 }
bankReadingPF OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Bank power Factor value.
This value indicates that 100 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { bankReadingEntry 5 }
---------------------------------------------------------------------------------------------------
-- outletStatusTable
---------------------------------------------------------------------------------------------------
outletStatusTable OBJECT-TYPE
SYNTAX SEQUENCE OF OutletStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Outlet status table."
::= { outlet 1 }
outletStatusEntry OBJECT-TYPE
SYNTAX OutletStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing outlet status info."
INDEX { staId, outletId }
::= { outletStatusTable 1 }
OutletStatusEntry ::=
SEQUENCE {
outletId INTEGER,
outletStatusRatedCur INTEGER,
outletStatusSwitchable INTEGER,
outletStatusAutoPing INTEGER,
outletStatusPhaseLayout INTEGER
}
outletId OBJECT-TYPE
SYNTAX INTEGER (1..42)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Outlet ID."
::= { outletStatusEntry 1 }
outletStatusRatedCur OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Outlet Max Current value. unit: (0.1mA).
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { outletStatusEntry 2 }
outletStatusSwitchable OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), not-support(-2000000), no(1), yes(2) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Outlet switchable.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { outletStatusEntry 3 }
outletStatusAutoPing OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), not-support(-2000000), na(1), online(2), not-reachable(3) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Outlet latest auto-ping result.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { outletStatusEntry 4 }
outletStatusPhaseLayout OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), not-support(-2000000), l1-n(1), l2-n(2), l3-n(3), l1-l2(4), l2-l3(5), l3-l1(6) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Display the phase layout of outlet.
Example: range 1 ~ 3 represents Line1-LineNeutral ~ Line3-lineNeutral.
4 ~ 6 represents Line1-Line2, Line2-Line3, Line3-Line1.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { outletStatusEntry 5 }
---------------------------------------------------------------------------------------------------
-- outletConfigTable
---------------------------------------------------------------------------------------------------
outletConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF OutletConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Outlet config table."
::= { outlet 2 }
outletConfigEntry OBJECT-TYPE
SYNTAX OutletConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing outlet config info."
INDEX { staId, outletId }
::= { outletConfigTable 1 }
OutletConfigEntry ::=
SEQUENCE {
outletConfigName DisplayString,
outletConfigConfirmationEn INTEGER,
outletConfigOnDelayTime INTEGER,
outletConfigOffDelayTime INTEGER,
outletConfigShutdownMethod INTEGER,
outletConfigMAC MacAddress,
outletConfigLocalAccessLock INTEGER,
outletConfigMinCurThresh INTEGER,
outletConfigMaxCurThresh INTEGER,
outletConfigMinVolThresh INTEGER,
outletConfigMaxVolThresh INTEGER,
outletConfigMinPowerThresh INTEGER,
outletConfigMaxPowerThresh INTEGER,
outletConfigMaxPDThresh INTEGER,
outletConfigAutoPingContFailTimes INTEGER,
outletConfigAutoPingIntervalSec INTEGER,
outletConfigAutoPingRetryTimes INTEGER,
outletConfigAutoPingPowerUpDelaySec INTEGER,
outletConfigAutoPingRemoteIPAddr IpAddress,
outletConfigAutoPingEnable INTEGER,
outletConfigAutoPingEnableReboot INTEGER
}
outletConfigName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the name of the outlet.
If the station does not support this OID, we show n/a.
string length: 0~48
If the station is not available, it returns 'station N/A'.
NOTE: Input string as /empty to set this object to NULL."
::= { outletConfigEntry 1 }
outletConfigConfirmationEn OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2) , noauth(3), not-support(4) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the confirmation of the outlet.
If the station is not available, it returns value -3000000."
::= { outletConfigEntry 2 }
outletConfigOnDelayTime OBJECT-TYPE
SYNTAX INTEGER (-1 | 0..999)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the ON delay time of the outlet.
When this model does not support the OID, we show value -1.
If the station is not available, it returns value -3000000."
::= { outletConfigEntry 3 }
outletConfigOffDelayTime OBJECT-TYPE
SYNTAX INTEGER (-1 | 0..999)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the OFF delay time of the outlet.
When this model does not support the OID, we show value -1.
If the station is not available, it returns value -3000000."
::= { outletConfigEntry 4 }
outletConfigShutdownMethod OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), kill-the-power(1), wake-on-lan(2), after-ac-back(3), not-support(4) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the shutdown method of the outlet.
If the station is not available, it returns value -3000000."
::= { outletConfigEntry 5 }
outletConfigMAC OBJECT-TYPE
SYNTAX MacAddress
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the MAC address of shutdown method.
The value is hex format with length 12.
If the station does not support this OID, it return '00-00-00-00-00-00'.
If the station is not available, it returns '00-00-00-00-00-00'."
::= { outletConfigEntry 6 }
outletConfigLocalAccessLock OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), unlocked(1), locked(2), not-support(3) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set whether the local access of the outlet is locked by remote or not.
If the station is not available, it returns value -3000000."
::= { outletConfigEntry 7 }
outletConfigMinCurThresh OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the outlet minimum electric current measurement threshold.
Example: range 0.0 ~16.0 represents 0~160
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { outletConfigEntry 8 }
outletConfigMaxCurThresh OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the outlet maximum electric current measurement threshold.
Example: range 0.0 ~16.0 represents 0~160
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { outletConfigEntry 9 }
outletConfigMinVolThresh OBJECT-TYPE
SYNTAX INTEGER (-2000000 | -3000 | 900..2600)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the outlet minimum voltage measurement threshold.
Example: range 90.0 ~260.0 represents 900~2600
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { outletConfigEntry 10 }
outletConfigMaxVolThresh OBJECT-TYPE
SYNTAX INTEGER (-2000000 | -3000 | 900..2600)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the outlet maximum voltage measurement threshold.
Example: range 90.0 ~260.0 represents 900~2600
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { outletConfigEntry 11 }
outletConfigMinPowerThresh OBJECT-TYPE
SYNTAX INTEGER (-2000000 | -3000 | 0..99999)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the outlet minimum power measurement threshold.
Example: range 0.0 ~ 9999.9 represents 0~99999
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { outletConfigEntry 12 }
outletConfigMaxPowerThresh OBJECT-TYPE
SYNTAX INTEGER (-2000000 | -3000 | 0..99999)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the outlet maximum power measurement threshold.
Example: range 0.0 ~ 9999.9 represents 0~99999
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { outletConfigEntry 13 }
outletConfigMaxPDThresh OBJECT-TYPE
SYNTAX INTEGER (-2000000 | -3000 | 0..999990)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the outlet maximum power dissipation measurement threshold.
Example: range 0.0 ~ 99999.0 represents 0~999990
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { outletConfigEntry 14 }
outletConfigAutoPingContFailTimes OBJECT-TYPE
SYNTAX INTEGER (-2000000 | -3000 | 0..10)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the outlet auto-ping continuously-failed time to reset outlet.
Example: range 0 ~ 5
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { outletConfigEntry 15 }
outletConfigAutoPingIntervalSec OBJECT-TYPE
SYNTAX INTEGER (-2000000 | -3000 | 0..60)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the outlet auto-ping pinging interval in seconds.
Example: range 10 ~ 600
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { outletConfigEntry 16 }
outletConfigAutoPingRetryTimes OBJECT-TYPE
SYNTAX INTEGER (-2000000 | -3000 | 0..10)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the outlet auto-ping max retry times.
Example: range 0 ~ 5
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { outletConfigEntry 17 }
outletConfigAutoPingPowerUpDelaySec OBJECT-TYPE
SYNTAX INTEGER (-2000000 | -3000 | 0..60)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the outlet auto-ping first-ping-delay in seconds after outlet switches on.
Example: range 10 ~ 600
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { outletConfigEntry 18 }
outletConfigAutoPingRemoteIPAddr OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Outlet auto-ping destination IP address.
If the station does not support this OID, it returns value '0.0.0.0'.
If the station is not available, it returns '0.0.0.0'."
::= { outletConfigEntry 19 }
outletConfigAutoPingEnable OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), not-support(-2000000), disable(1), enable(2) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the outlet auto-ping enable state.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { outletConfigEntry 20 }
outletConfigAutoPingEnableReboot OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), not-support(-2000000), disable(1), enable(2) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the outlet auto-ping reboot enable state.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { outletConfigEntry 21 }
---------------------------------------------------------------------------------------------------
-- outletControlTable
---------------------------------------------------------------------------------------------------
outletControlTable OBJECT-TYPE
SYNTAX SEQUENCE OF OutletControlEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Outlet control table."
::= { outlet 3 }
outletControlEntry OBJECT-TYPE
SYNTAX OutletControlEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing outlet control info."
INDEX { staId, outletId }
::= { outletControlTable 1 }
OutletControlEntry ::=
SEQUENCE {
outletControlOperation INTEGER
}
outletControlOperation OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This function is used for the outlet control.
Set off(1) to turn off the outlet.
Set on(2) to turn on the outlet.
Set reboot(3) to reboot the outlet.
pending(3), fault(5), noauth(6), not-suport(7), pop(8) can't be set.
If the station is not available, it returns value -3000000."
::= { outletControlEntry 1 }
---------------------------------------------------------------------------------------------------
-- outletReadingTable
---------------------------------------------------------------------------------------------------
outletReadingTable OBJECT-TYPE
SYNTAX SEQUENCE OF OutletReadingEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Outlet reading table."
::= { outlet 4 }
outletReadingEntry OBJECT-TYPE
SYNTAX OutletReadingEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing outlet reading info."
INDEX { staId, outletId }
::= { outletReadingTable 1 }
OutletReadingEntry ::=
SEQUENCE {
outletReadingCur INTEGER,
outletReadingVol INTEGER,
outletReadingPower INTEGER,
outletReadingPD INTEGER,
outletReadingPF INTEGER
}
outletReadingCur OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Outlet electric current value.
This value indicates that 10,000 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { outletReadingEntry 1 }
outletReadingVol OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Outlet voltage value.
This value indicates that 10,000 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { outletReadingEntry 2 }
outletReadingPower OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Outlet power value.
This value indicates that 10,000 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { outletReadingEntry 3 }
outletReadingPD OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Outlet power dissipation value.
This value indicates that 10,000 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { outletReadingEntry 4 }
outletReadingPF OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Outlet Power Factor value.
This value indicates that 100 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { outletReadingEntry 5 }
---------------------------------------------------------------------------------------------------
-- outletAutoPingIpTable
---------------------------------------------------------------------------------------------------
outletAutoPingIpTable OBJECT-TYPE
SYNTAX SEQUENCE OF OutletAutoPingIpEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Outlet auto-ping table."
::= { outlet 5 }
outletAutoPingIpEntry OBJECT-TYPE
SYNTAX OutletAutoPingIpEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing outlet auto-ping ip info."
INDEX { staId, outletId }
::= { outletAutoPingIpTable 1 }
OutletAutoPingIpEntry ::=
SEQUENCE {
outletConfigAutoPingRemoteIPType InetAddressType,
outletConfigAutoPingRemoteIP InetAddress
}
outletConfigAutoPingRemoteIPType OBJECT-TYPE
SYNTAX InetAddressType {ipv4(1), ipv6(2)}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Represents the type of the corresponding instance
of outletConfigAutoPingRemoteIP object.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { outletAutoPingIpEntry 1 }
outletConfigAutoPingRemoteIP OBJECT-TYPE
SYNTAX InetAddress
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Outlet auto-ping destination IP address.
If the station does not support this OID, it returns value '0.0.0.0'.
If the station is not available, it returns '0.0.0.0'."
::= { outletAutoPingIpEntry 2 }
---------------------------------------------------------------------------------------------------
-- lineStatusTable
---------------------------------------------------------------------------------------------------
lineStatusTable OBJECT-TYPE
SYNTAX SEQUENCE OF LineStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Line status table."
::= { line 1 }
lineStatusEntry OBJECT-TYPE
SYNTAX LineStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing line status info."
INDEX { staId, lineId }
::= { lineStatusTable 1 }
LineStatusEntry ::=
SEQUENCE {
lineId INTEGER,
lineStatusRatedCur INTEGER
}
lineId OBJECT-TYPE
SYNTAX INTEGER (1..3)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Line ID."
::= { lineStatusEntry 1 }
lineStatusRatedCur OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The Max Line Current value. unit: (0.1mA)
If the station is not available, it returns value -3000000."
::= { lineStatusEntry 2 }
---------------------------------------------------------------------------------------------------
-- lineConfigTable
---------------------------------------------------------------------------------------------------
lineConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF LineConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Line config table."
::= { line 2 }
lineConfigEntry OBJECT-TYPE
SYNTAX LineConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing line config info."
INDEX { staId, lineId }
::= { lineConfigTable 1 }
LineConfigEntry ::=
SEQUENCE {
lineConfigMinCurThresh INTEGER,
lineConfigMaxCurThresh INTEGER,
lineConfigMinVolThresh INTEGER,
lineConfigMaxVolThresh INTEGER,
lineConfigMinPowerThresh INTEGER,
lineConfigMaxPowerThresh INTEGER
}
lineConfigMinCurThresh OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the line Minimum current measurement threshold.
Example: range 0.0 ~16.0 represents 0~160
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { lineConfigEntry 1 }
lineConfigMaxCurThresh OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the line Maximum electric current measurement threshold.
Example: range 0.0 ~16.0 represents 0~160
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { lineConfigEntry 2 }
lineConfigMinVolThresh OBJECT-TYPE
SYNTAX INTEGER (-2000000 | -3000 | 900..3800)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the line minimum voltage measurement threshold.
Example: range 90.0 ~380.0 represents 900~3800
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { lineConfigEntry 3 }
lineConfigMaxVolThresh OBJECT-TYPE
SYNTAX INTEGER (-2000000 | -3000 | 900..3800)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the line maximum voltage measurement threshold.
Example: range 90.0 ~380.0 represents 900~3800
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { lineConfigEntry 4 }
lineConfigMinPowerThresh OBJECT-TYPE
SYNTAX INTEGER (-2000000 | -3000 | 0..99999)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the line minimum power measurement threshold.
Example: range 0.0 ~ 9999.9 represents 0~99999
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { lineConfigEntry 5 }
lineConfigMaxPowerThresh OBJECT-TYPE
SYNTAX INTEGER (-2000000 | -3000 | 0..99999)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the line maximum power measurement threshold.
Example: range 0.0 ~ 9999.9 represents 0~99999
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { lineConfigEntry 6 }
---------------------------------------------------------------------------------------------------
-- lineReadingTable
---------------------------------------------------------------------------------------------------
lineReadingTable OBJECT-TYPE
SYNTAX SEQUENCE OF LineReadingEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Line reading table."
::= { line 3 }
lineReadingEntry OBJECT-TYPE
SYNTAX LineReadingEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing line reading info."
INDEX { staId, lineId }
::= { lineReadingTable 1 }
LineReadingEntry ::=
SEQUENCE {
lineReadingCur INTEGER,
lineReadingVol INTEGER,
lineReadingPower INTEGER
}
lineReadingCur OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Line current value.
This value indicates that 10,000 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { lineReadingEntry 1 }
lineReadingVol OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Line voltage value.
This value indicates that 10,000 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { lineReadingEntry 2 }
lineReadingPower OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Line power value.
This value indicates that 10,000 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { lineReadingEntry 3 }
---------------------------------------------------------------------------------------------------
-- neutralStatusTable
---------------------------------------------------------------------------------------------------
neutralStatusTable OBJECT-TYPE
SYNTAX SEQUENCE OF NeutralStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Line reading table."
::= { line 4 }
neutralStatusEntry OBJECT-TYPE
SYNTAX NeutralStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing line reading info."
INDEX { staId }
::= { neutralStatusTable 1 }
NeutralStatusEntry ::=
SEQUENCE {
neutralStatusLeakageCur INTEGER
}
neutralStatusLeakageCur OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), no-detection(1), detection(2), not-support(3) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Neutral leakage current status.
If the station is not available, it returns value -3000000."
::= { neutralStatusEntry 1 }
---------------------------------------------------------------------------------------------------
-- inletStatusTable
---------------------------------------------------------------------------------------------------
inletStatusTable OBJECT-TYPE
SYNTAX SEQUENCE OF InletStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Inlet status table."
::= { inlet 1 }
inletStatusEntry OBJECT-TYPE
SYNTAX InletStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing inlet status info."
INDEX { staId, inletId }
::= { inletStatusTable 1 }
InletStatusEntry ::=
SEQUENCE {
inletId INTEGER,
inletStatusRatedCur INTEGER
}
inletId OBJECT-TYPE
SYNTAX INTEGER (1..3)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Line ID."
::= { inletStatusEntry 1 }
inletStatusRatedCur OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The Inlet Max Current value. unit: (0.1mA).
If device is phase wye, then means L1 or L2 or L3 current.
If device is phase delta, then means L1L2 or L2L3 or L3L1 current.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { inletStatusEntry 2 }
---------------------------------------------------------------------------------------------------
-- inletConfigTable
---------------------------------------------------------------------------------------------------
inletConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF InletConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Inlet config table."
::= { inlet 2 }
inletConfigEntry OBJECT-TYPE
SYNTAX InletConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing inlet config info."
INDEX { staId, inletId }
::= { inletConfigTable 1 }
InletConfigEntry ::=
SEQUENCE {
inletConfigMinCurThresh INTEGER,
inletConfigMaxCurThresh INTEGER,
inletConfigMinVolThresh INTEGER,
inletConfigMaxVolThresh INTEGER,
inletConfigMinPowerThresh INTEGER,
inletConfigMaxPowerThresh INTEGER,
inletConfigMaxPDThresh INTEGER
}
inletConfigMinCurThresh OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the inlet Minimum current measurement threshold.
Example: range 0.0 ~16.0 represents 0~160
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { inletConfigEntry 1 }
inletConfigMaxCurThresh OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the inlet Maximum electric current measurement threshold.
Example: range 0.0 ~16.0 represents 0~160
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { inletConfigEntry 2 }
inletConfigMinVolThresh OBJECT-TYPE
SYNTAX INTEGER (-2000000 | -3000 | 900..3800)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the inlet minimum voltage measurement threshold.
Example: range 90.0 ~380.0 represents 900~3800
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { inletConfigEntry 3 }
inletConfigMaxVolThresh OBJECT-TYPE
SYNTAX INTEGER (-2000000 | -3000 | 900..3800)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the inlet maximum voltage measurement threshold.
Example: range 90.0 ~380.0 represents 900~3800
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { inletConfigEntry 4 }
inletConfigMinPowerThresh OBJECT-TYPE
SYNTAX INTEGER (-2000000 | -3000 | 0..99999)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the inlet minimum power measurement threshold.
Example: range 0.0 ~ 9999.9 represents 0~99999
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { inletConfigEntry 5 }
inletConfigMaxPowerThresh OBJECT-TYPE
SYNTAX INTEGER (-2000000 | -3000 | 0..99999)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the inlet maximum power measurement threshold.
Example: range 0.0 ~ 9999.9 represents 0~99999
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { inletConfigEntry 6 }
inletConfigMaxPDThresh OBJECT-TYPE
SYNTAX INTEGER (-2000000 | -3000 | 0..999990)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the inlet maximum power dissipation measurement threshold.
Example: range 0.0 ~ 99999.0 represents 0~999990
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { inletConfigEntry 7 }
---------------------------------------------------------------------------------------------------
-- inletReadingTable
---------------------------------------------------------------------------------------------------
inletReadingTable OBJECT-TYPE
SYNTAX SEQUENCE OF InletReadingEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Inlet reading table."
::= { inlet 3 }
inletReadingEntry OBJECT-TYPE
SYNTAX InletReadingEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing inlet reading info."
INDEX { staId, inletId }
::= { inletReadingTable 1 }
InletReadingEntry ::=
SEQUENCE {
inletReadingCur INTEGER,
inletReadingVol INTEGER,
inletReadingPower INTEGER,
inletReadingPD INTEGER
}
inletReadingCur OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Inlet current value.
If device is phase wye, then means L1 or L2 or L3 current.
If device is phase delta, then means L1L2 or L2L3 or L3L1 current.
This value indicates that 10,000 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { inletReadingEntry 1 }
inletReadingVol OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Inlet voltage value.
If device is phase wye, then means L1 or L2 or L3 voltage.
If device is phase delta, then means L1L2 or L2L3 or L3L1 voltage.
This value indicates that 10,000 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { inletReadingEntry 2 }
inletReadingPower OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Inlet power value.
If device is phase wye, then means L1 or L2 or L3 power.
If device is phase delta, then means L1L2 or L2L3 or L3L1 power.
This value indicates that 10,000 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { inletReadingEntry 3 }
inletReadingPD OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Inlet power value.
If device is phase wye, then means L1 or L2 or L3 power dissipation.
If device is phase delta, then means L1L2 or L2L3 or L3L1 power dissipation.
This value indicates that 10,000 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { inletReadingEntry 4 }
---------------------------------------------------------------------------------------------------
-- sensorConfigTable
---------------------------------------------------------------------------------------------------
sensorConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF SensorConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Sensor config table.
Use port/addr as indexes to access sensor configurations."
::= { sensor 3 }
sensorConfigEntry OBJECT-TYPE
SYNTAX SensorConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing sensor config info."
INDEX { staId, sensorPort, sensorAddr }
::= { sensorConfigTable 1 }
SensorConfigEntry ::=
SEQUENCE {
sensorPort INTEGER,
sensorAddr INTEGER,
sensorConfigMinTempThresh INTEGER,
sensorConfigMaxTempThresh INTEGER,
sensorConfigMinHumThresh INTEGER,
sensorConfigMaxHumThresh INTEGER,
sensorConfigMinPressThresh INTEGER,
sensorConfigMaxPressThresh INTEGER
}
sensorPort OBJECT-TYPE
SYNTAX INTEGER (1..4)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Sensor Port Number."
::= { sensorConfigEntry 1 }
sensorAddr OBJECT-TYPE
SYNTAX INTEGER (1..31)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Sensor Address."
::= { sensorConfigEntry 2 }
sensorConfigMinTempThresh OBJECT-TYPE
SYNTAX INTEGER (-3000 | -200..600)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set sensor minimum temperature measurement threshold.
Example: range -20.0 ~ 60.0 represents -200~600
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { sensorConfigEntry 3 }
sensorConfigMaxTempThresh OBJECT-TYPE
SYNTAX INTEGER (-3000 | -200..600)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set sensor maximum temperature measurement threshold.
Example: range -20.0 ~ 60.0 represents -200~600
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { sensorConfigEntry 4 }
sensorConfigMinHumThresh OBJECT-TYPE
SYNTAX INTEGER (-3000 | 100..950)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set sensor minimum humidity measurement threshold.
Example: range 10.0 ~ 95.0 represents 100~950
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { sensorConfigEntry 5 }
sensorConfigMaxHumThresh OBJECT-TYPE
SYNTAX INTEGER (-3000 | 100..950)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set sensor maximum humidity measurement threshold.
Example: range 10.0 ~ 95.0 represents 100~950
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { sensorConfigEntry 6 }
sensorConfigMinPressThresh OBJECT-TYPE
SYNTAX INTEGER (-3000 | -2500..2500)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set sensor minimum pressure measurement threshold.
Example: range -250.0 ~ 250.0 represents -2500 ~ 2500
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { sensorConfigEntry 7 }
sensorConfigMaxPressThresh OBJECT-TYPE
SYNTAX INTEGER (-3000 | -2500..2500)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set sensor maximum pressure measurement threshold.
Example: range -250.0 ~ 250.0 represents -2500 ~ 2500
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { sensorConfigEntry 8 }
---------------------------------------------------------------------------------------------------
-- sensorReadingTable
---------------------------------------------------------------------------------------------------
sensorReadingTable OBJECT-TYPE
SYNTAX SEQUENCE OF SensorReadingEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Sensor reading table.
Use port/addr as indexes to access sensor readings."
::= { sensor 4 }
sensorReadingEntry OBJECT-TYPE
SYNTAX SensorReadingEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing sensor reading info."
INDEX { staId, sensorPort, sensorAddr }
::= { sensorReadingTable 1 }
SensorReadingEntry ::=
SEQUENCE {
sensorReadingTemp INTEGER,
sensorReadingHum INTEGER,
sensorReadingPress INTEGER
}
sensorReadingTemp OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Sensor's Temperature value.
This value indicates that 1,000 times.
If this measurement value is not available, it returns value -1000000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { sensorReadingEntry 1 }
sensorReadingHum OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Sensor's Humidity value.
This value indicates that 1,000 times.
If this measurement value is not available, it returns value -1000000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { sensorReadingEntry 2 }
sensorReadingPress OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Sensor's Pressure value.
This value indicates that 1,000 times.
If this measurement value is not available, it returns value -1000000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { sensorReadingEntry 3 }
---------------------------------------------------------------------------------------------------
-- dryContactStatusTable
---------------------------------------------------------------------------------------------------
dryContactStatusTable OBJECT-TYPE
SYNTAX SEQUENCE OF DryContactStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Dry contact status table."
::= { dryContact 1 }
dryContactStatusEntry OBJECT-TYPE
SYNTAX DryContactStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing dry contact status info."
INDEX { staId, dryContactId }
::= { dryContactStatusTable 1 }
DryContactStatusEntry ::=
SEQUENCE {
dryContactId INTEGER,
dryContactStatus INTEGER
}
dryContactId OBJECT-TYPE
SYNTAX INTEGER (1..2)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Dry contact ID."
::= { dryContactStatusEntry 1 }
dryContactStatus OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), close(0), open(1), not-attached(2), not-support(10) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Display dry contact status.
close(0) represents door close.
open(1) represents door open.
not-attached(2) represents door sensor don't attach to device.
If the station is not available, it returns value -3000000."
::= { dryContactStatusEntry 2 }
---------------------------------------------------------------------------------------------------
-- dryContactConfigTable
---------------------------------------------------------------------------------------------------
dryContactConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF DryContactConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Dry contact config table."
::= { dryContact 2 }
dryContactConfigEntry OBJECT-TYPE
SYNTAX DryContactConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing dry contact config info."
INDEX { staId, dryContactId }
::= { dryContactConfigTable 1 }
DryContactConfigEntry ::=
SEQUENCE {
dryContactConfigType INTEGER
}
dryContactConfigType OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), notinstalled(0), photo(1), inductiveproximity(2), reed(3), waterleakage(4), smoke(5), not-support(10) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set dry contact type.
If the station is not available, it returns value -3000000."
::= { dryContactConfigEntry 1 }
---------------------------------------------------------------------------------------------------
-- netStatusTable
---------------------------------------------------------------------------------------------------
netStatusTable OBJECT-TYPE
SYNTAX SEQUENCE OF NetStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Net status table."
::= { network 1 }
netStatusEntry OBJECT-TYPE
SYNTAX NetStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing net status info."
INDEX { staId }
::= { netStatusTable 1 }
NetStatusEntry ::=
SEQUENCE {
netStatusMAC MacAddress
}
netStatusMAC OBJECT-TYPE
SYNTAX MacAddress
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Station MAC address.
The value is hex format with length 12.
If the station does not support this OID, it return '00-00-00-00-00-00'.
If the station is not available, it returns '00-00-00-00-00-00'."
::= { netStatusEntry 1 }
---------------------------------------------------------------------------------------------------
-- httpConfigTable
---------------------------------------------------------------------------------------------------
httpConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF HttpConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"HTTP config table."
::= { network 2 }
httpConfigEntry OBJECT-TYPE
SYNTAX HttpConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing HTTP config info."
INDEX { staId }
::= { httpConfigTable 1 }
HttpConfigEntry ::=
SEQUENCE {
httpConfigHttpPort INTEGER,
httpConfigHttpsPort INTEGER,
httpConfigHttpsOnlyEn INTEGER
}
httpConfigHttpPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the HTTP port of the station.
If the station is not available, it returns value -3000000."
::= { httpConfigEntry 1 }
httpConfigHttpsPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set the HTTPs port of the station.
If the station is not available, it returns value -3000000."
::= { httpConfigEntry 2 }
httpConfigHttpsOnlyEn OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set whether to use HTTPS only or HTTP/HTTPS for the web page.
If the station is not available, it returns value -3000000."
::= { httpConfigEntry 3 }
---------------------------------------------------------------------------------------------------
-- netConfigTable
---------------------------------------------------------------------------------------------------
netConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF NetConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Net config table."
::= { network 3 }
netConfigEntry OBJECT-TYPE
SYNTAX NetConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing net config info."
INDEX { staId, netCablePort }
::= { netConfigTable 1 }
NetConfigEntry ::=
SEQUENCE {
netCablePort INTEGER,
netConfigAutoIP INTEGER,
netConfigIPv4 IpAddress,
netConfigSubMask IpAddress,
netConfigGateway IpAddress,
netConfigAutoDNS INTEGER,
netConfigPreferDNSIPv4 IpAddress,
netConfigAlterDNSIPv4 IpAddress
}
netCablePort OBJECT-TYPE
SYNTAX INTEGER (1..2)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Network Port Number."
::= { netConfigEntry 1 }
netConfigAutoIP OBJECT-TYPE
SYNTAX INTEGER { no(1), yes(2) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set IPv4 address automatically or not"
::= { netConfigEntry 2 }
netConfigIPv4 OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set fixed IPv4 address"
::= { netConfigEntry 3 }
netConfigSubMask OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set subnet mask address"
::= { netConfigEntry 4 }
netConfigGateway OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set gateway address"
::= { netConfigEntry 5 }
netConfigAutoDNS OBJECT-TYPE
SYNTAX INTEGER { no(1), yes(2) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set DNS address automatically or not"
::= { netConfigEntry 6 }
netConfigPreferDNSIPv4 OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set prefer DNS address"
::= { netConfigEntry 7 }
netConfigAlterDNSIPv4 OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set alternate DNS address"
::= { netConfigEntry 8 }
---------------------------------------------------------------------------------------------------
-- trapConfigTable
---------------------------------------------------------------------------------------------------
trapConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF TrapConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Trap config table."
::= { trap 1 }
trapConfigEntry OBJECT-TYPE
SYNTAX TrapConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing trap config info."
INDEX { staId }
::= { trapConfigTable 1 }
TrapConfigEntry ::=
SEQUENCE {
trapConfigEn INTEGER,
trapConfigVer INTEGER
}
trapConfigEn OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set whether this trap entry is enabled or not.
You should set the username/auth-password/priv-password first, when choosing snmpv3.
You should set the community string first, when choosing snmpv1/v2c.
If the station is not available, it returns value -3000000."
::= { trapConfigEntry 1 }
trapConfigVer OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), v1(1), v2c(2), v3(3) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set SNMP trap version for sending trap.
You should set the username/auth-password/priv-password first, when choosing snmpv3.
You should set the community string first, when choosing snmpv1/v2c.
If the station is not available, it returns value -3000000."
::= { trapConfigEntry 2 }
---------------------------------------------------------------------------------------------------
-- trapReceiverConfigTable
---------------------------------------------------------------------------------------------------
trapReceiverConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF TrapReceiverConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"SNMP agent trap setup table. If users want to use trap,
they must set enable trap, IP and community first."
::= { trap 2 }
trapReceiverConfigEntry OBJECT-TYPE
SYNTAX TrapReceiverConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing trap receiver config info."
INDEX { staId, trapReceiverConfigIdx }
::= { trapReceiverConfigTable 1 }
TrapReceiverConfigEntry ::=
SEQUENCE {
trapReceiverConfigIdx INTEGER,
trapReceiverConfigIp IpAddress,
trapReceiverConfigPort INTEGER,
trapReceiverConfigCommunity DisplayString,
trapReceiverConfigUsername DisplayString,
trapReceiverConfigAuthPwd DisplayString,
trapReceiverConfigPrivacyPwd DisplayString
}
trapReceiverConfigIdx OBJECT-TYPE
SYNTAX INTEGER (1..2)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Index of trap receiver."
::= { trapReceiverConfigEntry 1 }
trapReceiverConfigIp OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Trap receiver IP address.
If the station does not support this OID, it returns value '0.0.0.0'.
If the station is not available, it returns '0.0.0.0'."
::= { trapReceiverConfigEntry 2 }
trapReceiverConfigPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"NMS trap port to be used by agent to send trap.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { trapReceiverConfigEntry 3 }
trapReceiverConfigCommunity OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"If use SNMPv1/v2c to receive trap should set this community string.
MAX string length: 20
If the station does not support this OID, it returns value 'not-support'.
If the station is not available, it returns 'station N/A'.
NOTE: Input string as /empty to set this object to NULL."
::= { trapReceiverConfigEntry 4 }
trapReceiverConfigUsername OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"If use SNMPv3 to receive trap should set this username string.
MAX string length: 20.
If the station does not support this OID, it returns value 'not-support'.
If the station is not available, it returns 'station N/A'.
NOTE: Input string as /empty to set this object to NULL."
::= { trapReceiverConfigEntry 5 }
trapReceiverConfigAuthPwd OBJECT-TYPE
SYNTAX DisplayString (SIZE (8..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"If use SNMPv3 to receive trap should set this auth password string.
MAX string length: 20
If the station does not support this OID, it returns value 'not-support'.
If the station is not available, it returns 'station N/A'.
NOTE: Input string as /empty to set this object to NULL."
::= { trapReceiverConfigEntry 6 }
trapReceiverConfigPrivacyPwd OBJECT-TYPE
SYNTAX DisplayString (SIZE (8..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"If use SNMPv3 to receive trap should set this privacy password string.
MAX string length: 20
If the station does not support this OID, it returns value 'not-support'.
If the station is not available, it returns 'station N/A'.
NOTE: Input string as /empty to set this object to NULL."
::= { trapReceiverConfigEntry 7 }
---------------------------------------------------------------------------------------------------
-- trapReceiverIpTable
---------------------------------------------------------------------------------------------------
trapReceiverIpTable OBJECT-TYPE
SYNTAX SEQUENCE OF TrapReceiverIpEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Trap Receiver Ip table."
::= { trap 3 }
trapReceiverIpEntry OBJECT-TYPE
SYNTAX TrapReceiverIpEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing trap receiver ip info."
INDEX { staId, trapReceiverIpIdx }
::= { trapReceiverIpTable 1 }
TrapReceiverIpEntry ::=
SEQUENCE {
trapReceiverIpIdx INTEGER,
trapReceiverIpType InetAddressType,
trapReceiverIp InetAddress
}
trapReceiverIpIdx OBJECT-TYPE
SYNTAX INTEGER (1..2)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Index of trap receiver."
::= { trapReceiverIpEntry 1 }
trapReceiverIpType OBJECT-TYPE
SYNTAX InetAddressType {ipv4(1), ipv6(2)}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Represents the type of the corresponding instance
of trapReceiverIp object.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000."
::= { trapReceiverIpEntry 2 }
trapReceiverIp OBJECT-TYPE
SYNTAX InetAddress
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Outlet auto-ping destination IP address.
If the station does not support this OID, it returns value '0.0.0.0'.
If the station is not available, it returns '0.0.0.0'."
::= { trapReceiverIpEntry 3 }
---------------------------------------------------------------------------------------------------
-- trapNotifConfigTable
---------------------------------------------------------------------------------------------------
trapNotifConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF TrapNotifConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Trap notification config table."
::= { trapNotification 1 }
trapNotifConfigEntry OBJECT-TYPE
SYNTAX TrapNotifConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Single entry containing trap notification config info."
INDEX { staId }
::= { trapNotifConfigTable 1 }
TrapNotifConfigEntry ::=
SEQUENCE {
trapNotifConfigEn INTEGER
}
trapNotifConfigEn OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display or set whether this trap entry is enabled or not.
You should set the username/auth-password/priv-password first, when choosing snmpv3.
You should set the community string first, when choosing snmpv1/v2c.
If the station is not available, it returns value -3000000."
::= { trapNotifConfigEntry 1 }
---------------------------------------------------------------------------------------------------
-- trapNotifAlarmTable
---------------------------------------------------------------------------------------------------
trapNotifAlarmTable OBJECT-TYPE
SYNTAX SEQUENCE OF TrapNotifAlarmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Trap notification alarm table."
::= { trapNotification 2 }
trapNotifAlarmEntry OBJECT-TYPE
SYNTAX TrapNotifAlarmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Single entry containing trap notification alarm info."
INDEX { staId }
::= { trapNotifAlarmTable 1 }
TrapNotifAlarmEntry ::=
SEQUENCE {
trapNotifAlarmBreakerStatus INTEGER,
trapNotifAlarmCurrentStatus INTEGER,
trapNotifAlarmVoltageStatus INTEGER,
trapNotifAlarmPowerStatus INTEGER,
trapNotifAlarmSensorStatus INTEGER
}
trapNotifAlarmBreakerStatus OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), normal(0), alarm(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Station breaker alarm status.
If the station is not available, it returns value -3000000."
::= { trapNotifAlarmEntry 1 }
trapNotifAlarmCurrentStatus OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), normal(0), alarm(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Station current alarm status.
If the station is not available, it returns value -3000000."
::= { trapNotifAlarmEntry 2 }
trapNotifAlarmVoltageStatus OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), normal(0), alarm(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Station voltage alarm status.
If the station is not available, it returns value -3000000."
::= { trapNotifAlarmEntry 3 }
trapNotifAlarmPowerStatus OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), normal(0), alarm(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Station power alarm status.
If the station is not available, it returns value -3000000."
::= { trapNotifAlarmEntry 4 }
trapNotifAlarmSensorStatus OBJECT-TYPE
SYNTAX INTEGER { staNotAvailable(-3000000), normal(0), alarm(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Station sensor alarm status.
If the station is not available, it returns value -3000000."
::= { trapNotifAlarmEntry 5 }
---------------------------------------------------------------------------------------------------
-- trapNotifEvent
---------------------------------------------------------------------------------------------------
trapNotifEvent NOTIFICATION-TYPE
STATUS current
DESCRIPTION "Display trap notification alarm status."
::= { trapNotification 3 }
---------------------------------------------------------------------------------------------------
-- deviceLock
---------------------------------------------------------------------------------------------------
staCommunityLock OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Change SNMPV1 or SNMPV2 community for California passes law.
Please follow the format as readcommunity||writecommunity"
::= { deviceLock 1 }
staPasswordLock OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Change SNMPV3 password for California passes law.
Please follow the format as authpassword||privpassword"
::= { deviceLock 2 }
END