2722 lines
86 KiB
Plaintext
2722 lines
86 KiB
Plaintext
AlphaPowerSystem-MIB DEFINITIONS ::= BEGIN
|
|
|
|
--==========================================================================
|
|
-- ALPHA.MIB
|
|
--
|
|
-- NOTE: Refer to RFC2578 for the formal definition of the SNMPv2-SMI MIB.
|
|
--
|
|
-- Changes:
|
|
-- September 23 2014
|
|
-- Added LPS alarms
|
|
--
|
|
-- February 22, 2011
|
|
--
|
|
-- Changed the property of Custom Signals to be Read and Write to
|
|
-- support SNMP Set feature.
|
|
--
|
|
-- June 03, 2010
|
|
--
|
|
-- Added inverter alarms.
|
|
--
|
|
-- January 25, 2010
|
|
--
|
|
-- Company name changed from Argus to Alpha.
|
|
-- All references changed accordingly.
|
|
--
|
|
-- November 3, 2008
|
|
--
|
|
-- The following new definitions were added:
|
|
-- Resync
|
|
-- Alarm Trigger
|
|
-- Time stamp
|
|
--
|
|
-- Subtyping removed from sequence definitions.
|
|
--==========================================================================
|
|
|
|
IMPORTS
|
|
MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE, enterprises
|
|
FROM SNMPv2-SMI
|
|
DisplayString
|
|
FROM SNMPv2-TC;
|
|
|
|
alpha MODULE-IDENTITY
|
|
LAST-UPDATED "201409230000Z"
|
|
ORGANIZATION "Alpha Technologies"
|
|
CONTACT-INFO
|
|
"Alpha Technologies
|
|
7700 Riverfront Gate
|
|
Burnaby, BC V5J 5M4
|
|
Canada
|
|
|
|
Tel: 1-604-436-5900
|
|
Fax: 1-604-436-1233"
|
|
DESCRIPTION
|
|
"This MIB defines the information block(s) available in system controllers
|
|
as defined by the following list:
|
|
- dcPwrSysDevice: Cordex series of Controllers"
|
|
::= { enterprises 7309 }
|
|
|
|
dcpower OBJECT IDENTIFIER ::= { alpha 4 }
|
|
dcPwrSysDevice OBJECT IDENTIFIER ::= { dcpower 1 }
|
|
dcPwrSysVariable OBJECT IDENTIFIER ::= { dcPwrSysDevice 1 }
|
|
dcPwrSysString OBJECT IDENTIFIER ::= { dcPwrSysDevice 2 }
|
|
dcPwrSysTraps OBJECT IDENTIFIER ::= { dcPwrSysDevice 3 }
|
|
|
|
dcPwrSysOutputsTbl OBJECT IDENTIFIER ::= { dcPwrSysDevice 4 }
|
|
dcPwrSysRelayTbl OBJECT IDENTIFIER ::= { dcPwrSysOutputsTbl 1 }
|
|
dcPwrSysAnalogOpTbl OBJECT IDENTIFIER ::= { dcPwrSysOutputsTbl 2 }
|
|
|
|
dcPwrSysAlrmsTbl OBJECT IDENTIFIER ::= { dcPwrSysDevice 5 }
|
|
dcPwrSysRectAlrmTbl OBJECT IDENTIFIER ::= { dcPwrSysAlrmsTbl 1 }
|
|
dcPwrSysDigAlrmTbl OBJECT IDENTIFIER ::= { dcPwrSysAlrmsTbl 2 }
|
|
dcPwrSysCurrAlrmTbl OBJECT IDENTIFIER ::= { dcPwrSysAlrmsTbl 3 }
|
|
dcPwrSysVoltAlrmTbl OBJECT IDENTIFIER ::= { dcPwrSysAlrmsTbl 4 }
|
|
dcPwrSysBattAlrmTbl OBJECT IDENTIFIER ::= { dcPwrSysAlrmsTbl 5 }
|
|
dcPwrSysTempAlrmTbl OBJECT IDENTIFIER ::= { dcPwrSysAlrmsTbl 6 }
|
|
dcPwrSysCustomAlrmTbl OBJECT IDENTIFIER ::= { dcPwrSysAlrmsTbl 7 }
|
|
dcPwrSysMiscAlrmTbl OBJECT IDENTIFIER ::= { dcPwrSysAlrmsTbl 8 }
|
|
dcPwrSysCtrlAlrmTbl OBJECT IDENTIFIER ::= { dcPwrSysAlrmsTbl 9 }
|
|
dcPwrSysAdioAlrmTbl OBJECT IDENTIFIER ::= { dcPwrSysAlrmsTbl 10 }
|
|
dcPwrSysConvAlrmTbl OBJECT IDENTIFIER ::= { dcPwrSysAlrmsTbl 11 }
|
|
|
|
dcPwrSysInvAlrmTbl OBJECT IDENTIFIER ::= { dcPwrSysAlrmsTbl 12 }
|
|
dcPwrSysLpsAlrmTbl OBJECT IDENTIFIER ::= { dcPwrSysAlrmsTbl 13 }
|
|
|
|
dcPwrSysInputsTbl OBJECT IDENTIFIER ::= { dcPwrSysDevice 6 }
|
|
dcPwrSysDigIpTbl OBJECT IDENTIFIER ::= { dcPwrSysInputsTbl 1 }
|
|
dcPwrSysCntrlrIpTbl OBJECT IDENTIFIER ::= { dcPwrSysInputsTbl 2 }
|
|
dcPwrSysRectIpTbl OBJECT IDENTIFIER ::= { dcPwrSysInputsTbl 3 }
|
|
dcPwrSysCustomIpTbl OBJECT IDENTIFIER ::= { dcPwrSysInputsTbl 4 }
|
|
dcPwrSysConvIpTbl OBJECT IDENTIFIER ::= { dcPwrSysInputsTbl 5 }
|
|
dcPwrSysTimerIpTbl OBJECT IDENTIFIER ::= { dcPwrSysInputsTbl 6 }
|
|
dcPwrSysCounterIpTbl OBJECT IDENTIFIER ::= { dcPwrSysInputsTbl 7 }
|
|
dcPwrSysLpsTbl OBJECT IDENTIFIER ::= { dcPwrSysInputsTbl 8 }
|
|
|
|
dcPwrExternalControls OBJECT IDENTIFIER ::= { dcPwrSysDevice 8 }
|
|
dcPwrVarbindNameReference OBJECT IDENTIFIER ::= { dcPwrSysDevice 9 }
|
|
|
|
|
|
--==========================================================================
|
|
-- Start of variables
|
|
--==========================================================================
|
|
|
|
dcPwrSysChargeVolts OBJECT-TYPE
|
|
SYNTAX INTEGER (-1000000000..1000000000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "This value indicates the present battery voltage.
|
|
|
|
The integer value represent a two digit fix decimal (Value = real voltage * 100) in Volts."
|
|
::= { dcPwrSysVariable 1 }
|
|
|
|
dcPwrSysDischargeVolts OBJECT-TYPE
|
|
SYNTAX INTEGER (-1000000000..1000000000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "This value indicates the present load voltage.
|
|
|
|
The integer value represent a two digit fix decimal (Value = real voltage * 100) in Volts."
|
|
::= { dcPwrSysVariable 2 }
|
|
|
|
dcPwrSysChargeAmps OBJECT-TYPE
|
|
SYNTAX INTEGER (-1000000000..1000000000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "This value indicates the present battery currrent.
|
|
|
|
The integer value represent a two digit fix decimal (Value = real current * 100) in Amps."
|
|
::= { dcPwrSysVariable 3 }
|
|
|
|
dcPwrSysDischargeAmps OBJECT-TYPE
|
|
SYNTAX INTEGER (-1000000000..1000000000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "This value indicates the present load current.
|
|
|
|
The integer value represent a two digit fix decimal (Value = real current * 100) in Amps."
|
|
::= { dcPwrSysVariable 4 }
|
|
|
|
dcPwrSysMajorAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Major Alarm"
|
|
::= { dcPwrSysVariable 5 }
|
|
|
|
dcPwrSysMinorAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Minor Alarm"
|
|
::= { dcPwrSysVariable 6 }
|
|
|
|
--==========================================================================
|
|
-- Start of Strings
|
|
--==========================================================================
|
|
|
|
dcPwrSysSiteName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Site Name"
|
|
::= { dcPwrSysString 1 }
|
|
|
|
dcPwrSysSiteCity OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Site City"
|
|
::= { dcPwrSysString 2 }
|
|
|
|
dcPwrSysSiteRegion OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Site Region"
|
|
::= { dcPwrSysString 3 }
|
|
|
|
dcPwrSysSiteCountry OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Site Country"
|
|
::= { dcPwrSysString 4 }
|
|
|
|
dcPwrSysContactName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Contact Name"
|
|
::= { dcPwrSysString 5 }
|
|
|
|
dcPwrSysPhoneNumber OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Phone Number"
|
|
::= { dcPwrSysString 6 }
|
|
|
|
dcPwrSysSiteNumber OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Site Number"
|
|
::= { dcPwrSysString 7 }
|
|
|
|
dcPwrSysSystemType OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The type of system being monitored by the agent."
|
|
::= { dcPwrSysString 8 }
|
|
|
|
dcPwrSysSystemSerial OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The serial number of the monitored system."
|
|
::= { dcPwrSysString 9 }
|
|
|
|
dcPwrSysSystemNumber OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The number of the monitored system."
|
|
::= { dcPwrSysString 10 }
|
|
|
|
dcPwrSysSoftwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The version of software running on the monitored system."
|
|
::= { dcPwrSysString 11 }
|
|
|
|
dcPwrSysSoftwareTimestamp OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The time stamp of the software running on the monitored system."
|
|
::= { dcPwrSysString 12 }
|
|
|
|
--==========================================================================
|
|
-- Start of Tables Information
|
|
--==========================================================================
|
|
--=================
|
|
-- Output table
|
|
--=================
|
|
--========================
|
|
-- Relay output sub table
|
|
--=========================
|
|
dcPwrSysRelayCount OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of relay variables in system controller relay table."
|
|
::= { dcPwrSysRelayTbl 1 }
|
|
|
|
dcPwrSysRelayTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DcPwrSysRelayEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A table of DC power system controller rectifier relay output variables."
|
|
::= { dcPwrSysRelayTbl 2 }
|
|
|
|
dcPwrSysRelayEntry OBJECT-TYPE
|
|
SYNTAX DcPwrSysRelayEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "An entry into the DC power system controller relay output group."
|
|
INDEX { dcPwrSysRelayIndex }
|
|
::= { dcPwrSysRelayTable 1 }
|
|
|
|
DcPwrSysRelayEntry
|
|
::= SEQUENCE {
|
|
dcPwrSysRelayIndex INTEGER,
|
|
dcPwrSysRelayName DisplayString,
|
|
dcPwrSysRelayIntegerValue INTEGER,
|
|
dcPwrSysRelayStringValue DisplayString,
|
|
dcPwrSysRelaySeverity INTEGER
|
|
}
|
|
|
|
dcPwrSysRelayIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The index of the relay variable in the power system controller relay output group."
|
|
::= { dcPwrSysRelayEntry 1 }
|
|
|
|
dcPwrSysRelayName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..30))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The description of the relay variable as reported by the DC power system controller relay output group."
|
|
::= { dcPwrSysRelayEntry 2 }
|
|
|
|
dcPwrSysRelayIntegerValue OBJECT-TYPE
|
|
SYNTAX INTEGER (-1000000000..1000000000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of the relay variable as reported by the DC power system controller relay output group."
|
|
::= { dcPwrSysRelayEntry 3 }
|
|
|
|
dcPwrSysRelayStringValue OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The string value of the relay variable as reported by the DC power system controller relay output group."
|
|
::= { dcPwrSysRelayEntry 4 }
|
|
|
|
dcPwrSysRelaySeverity OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of relay severity level of the extra variable as reported by the DC power system controller relay output group."
|
|
::= { dcPwrSysRelayEntry 5 }
|
|
|
|
--========================
|
|
-- Analog output sub table
|
|
--=========================
|
|
dcPwrSysAnalogOpCount OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of analog output variables in system controller analog output table."
|
|
::= { dcPwrSysAnalogOpTbl 1 }
|
|
|
|
dcPwrSysAnalogOpTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DcPwrSysAnalogOpEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A table of DC power system controller analog output variables."
|
|
::= { dcPwrSysAnalogOpTbl 2 }
|
|
|
|
dcPwrSysAnalogOpEntry OBJECT-TYPE
|
|
SYNTAX DcPwrSysAnalogOpEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "An entry into the DC power system controller analog output group."
|
|
INDEX { dcPwrSysAnalogOpIndex }
|
|
::= { dcPwrSysAnalogOpTable 1 }
|
|
|
|
DcPwrSysAnalogOpEntry
|
|
::= SEQUENCE {
|
|
dcPwrSysAnalogOpIndex INTEGER,
|
|
dcPwrSysAnalogOpName DisplayString,
|
|
dcPwrSysAnalogOpIntegerValue INTEGER,
|
|
dcPwrSysAnalogOpStringValue DisplayString,
|
|
dcPwrSysAnalogOpSeverity INTEGER
|
|
}
|
|
|
|
dcPwrSysAnalogOpIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The index of the analog variable in the power system controller analog output group."
|
|
::= { dcPwrSysAnalogOpEntry 1 }
|
|
|
|
dcPwrSysAnalogOpName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..30))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The description of the analog variable as reported by the DC power system controller analog output group."
|
|
::= { dcPwrSysAnalogOpEntry 2 }
|
|
|
|
dcPwrSysAnalogOpIntegerValue OBJECT-TYPE
|
|
SYNTAX INTEGER (-1000000000..1000000000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of the analog variable as reported by the DC power system controller analog output group."
|
|
::= { dcPwrSysAnalogOpEntry 3 }
|
|
|
|
dcPwrSysAnalogOpStringValue OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The string value of the analog variable as reported by the DC power system controller analog output group."
|
|
::= { dcPwrSysAnalogOpEntry 4 }
|
|
|
|
dcPwrSysAnalogOpSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of analog severity level of the extra variable as reported by the DC power system controller analog output group."
|
|
::= { dcPwrSysAnalogOpEntry 5 }
|
|
|
|
--=================
|
|
-- Alarm table
|
|
--=================
|
|
--============================
|
|
-- Rectifier alarm group
|
|
--============================
|
|
dcPwrSysRectAlrmCount OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of rectifier alarm variables in system controller alarm table."
|
|
::= { dcPwrSysRectAlrmTbl 1 }
|
|
|
|
dcPwrSysRectAlrmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DcPwrSysRectAlrmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A table of DC power system controller rectifier alarm variables."
|
|
::= { dcPwrSysRectAlrmTbl 2 }
|
|
|
|
dcPwrSysRectAlrmEntry OBJECT-TYPE
|
|
SYNTAX DcPwrSysRectAlrmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "An entry into the DC power system controller rectifier alarm group."
|
|
INDEX { dcPwrSysRectAlrmIndex }
|
|
::= { dcPwrSysRectAlrmTable 1 }
|
|
|
|
DcPwrSysRectAlrmEntry
|
|
::= SEQUENCE {
|
|
dcPwrSysRectAlrmIndex INTEGER,
|
|
dcPwrSysRectAlrmName DisplayString,
|
|
dcPwrSysRectAlrmIntegerValue INTEGER,
|
|
dcPwrSysRectAlrmStringValue DisplayString,
|
|
dcPwrSysRectAlrmSeverity INTEGER
|
|
}
|
|
|
|
dcPwrSysRectAlrmIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The index of the alarm variable in the DC power system controller table rectifier alarm group."
|
|
::= { dcPwrSysRectAlrmEntry 1 }
|
|
|
|
dcPwrSysRectAlrmName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..30))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The description of the alarm variable as reported by the DC power system controller rectifier alarm group."
|
|
::= { dcPwrSysRectAlrmEntry 2 }
|
|
|
|
dcPwrSysRectAlrmIntegerValue OBJECT-TYPE
|
|
SYNTAX INTEGER (-1000000000..1000000000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of the alarm variable as reported by the DC power system controller rectifier alarm group."
|
|
::= { dcPwrSysRectAlrmEntry 3 }
|
|
|
|
dcPwrSysRectAlrmStringValue OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The string value of the alarm variable as reported by the DC power system controller rectifier alarm group."
|
|
::= { dcPwrSysRectAlrmEntry 4 }
|
|
|
|
dcPwrSysRectAlrmSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of alarm severity level of the extra variable as reported by the DC power system controller rectifier alarm group."
|
|
::= { dcPwrSysRectAlrmEntry 5 }
|
|
|
|
--============================
|
|
-- Digital alarm group
|
|
--============================
|
|
dcPwrSysDigAlrmCount OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of digital alarm variables in system controller alarm table."
|
|
::= { dcPwrSysDigAlrmTbl 1 }
|
|
|
|
dcPwrSysDigAlrmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DcPwrSysDigAlrmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A table of DC power system controller digital alarm variables."
|
|
::= { dcPwrSysDigAlrmTbl 2 }
|
|
|
|
dcPwrSysDigAlrmEntry OBJECT-TYPE
|
|
SYNTAX DcPwrSysDigAlrmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "An entry into the DC power system controller digital alarm group."
|
|
INDEX { dcPwrSysDigAlrmIndex }
|
|
::= { dcPwrSysDigAlrmTable 1 }
|
|
|
|
DcPwrSysDigAlrmEntry
|
|
::= SEQUENCE {
|
|
dcPwrSysDigAlrmIndex INTEGER,
|
|
dcPwrSysDigAlrmName DisplayString,
|
|
dcPwrSysDigAlrmIntegerValue INTEGER,
|
|
dcPwrSysDigAlrmStringValue DisplayString,
|
|
dcPwrSysDigAlrmSeverity INTEGER
|
|
}
|
|
|
|
dcPwrSysDigAlrmIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The index of the alarm variable in the DC power system controller table digital alarm group."
|
|
::= { dcPwrSysDigAlrmEntry 1 }
|
|
|
|
dcPwrSysDigAlrmName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..30))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The description of the alarm variable as reported by the DC power system controller digital alarm group."
|
|
::= { dcPwrSysDigAlrmEntry 2 }
|
|
|
|
dcPwrSysDigAlrmIntegerValue OBJECT-TYPE
|
|
SYNTAX INTEGER (-1000000000..1000000000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of the alarm variable as reported by the DC power system controller digital alarm group."
|
|
::= { dcPwrSysDigAlrmEntry 3 }
|
|
|
|
dcPwrSysDigAlrmStringValue OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The string value of the alarm variable as reported by the DC power system controller digital alarm group."
|
|
::= { dcPwrSysDigAlrmEntry 4 }
|
|
|
|
dcPwrSysDigAlrmSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of alarm severity level of the extra variable as reported by the DC power system controller digital alarm group."
|
|
::= { dcPwrSysDigAlrmEntry 5 }
|
|
|
|
--============================
|
|
-- Current alarm group
|
|
--============================
|
|
dcPwrSysCurrAlrmCount OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of current alarm variables in system controller alarm table."
|
|
::= { dcPwrSysCurrAlrmTbl 1 }
|
|
|
|
dcPwrSysCurrAlrmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DcPwrSysCurrAlrmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A table of DC power system controller current alarm variables."
|
|
::= { dcPwrSysCurrAlrmTbl 2 }
|
|
|
|
dcPwrSysCurrAlrmEntry OBJECT-TYPE
|
|
SYNTAX DcPwrSysCurrAlrmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "An entry into the DC power system controller current alarm group."
|
|
INDEX { dcPwrSysCurrAlrmIndex }
|
|
::= { dcPwrSysCurrAlrmTable 1 }
|
|
|
|
DcPwrSysCurrAlrmEntry
|
|
::= SEQUENCE {
|
|
dcPwrSysCurrAlrmIndex INTEGER,
|
|
dcPwrSysCurrAlrmName DisplayString,
|
|
dcPwrSysCurrAlrmIntegerValue INTEGER,
|
|
dcPwrSysCurrAlrmStringValue DisplayString,
|
|
dcPwrSysCurrAlrmSeverity INTEGER
|
|
}
|
|
|
|
dcPwrSysCurrAlrmIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The index of the alarm variable in the DC power system controller table current alarm group."
|
|
::= { dcPwrSysCurrAlrmEntry 1 }
|
|
|
|
dcPwrSysCurrAlrmName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..30))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The description of the alarm variable as reported by the DC power system controller current alarm group."
|
|
::= { dcPwrSysCurrAlrmEntry 2 }
|
|
|
|
dcPwrSysCurrAlrmIntegerValue OBJECT-TYPE
|
|
SYNTAX INTEGER (-1000000000..1000000000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of the alarm variable as reported by the DC power system controller current alarm group."
|
|
::= { dcPwrSysCurrAlrmEntry 3 }
|
|
|
|
dcPwrSysCurrAlrmStringValue OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The string value of the alarm variable as reported by the DC power system controller current alarm group."
|
|
::= { dcPwrSysCurrAlrmEntry 4 }
|
|
|
|
dcPwrSysCurrAlrmSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of alarm severity level of the extra variable as reported by the DC power system controller current alarm group."
|
|
::= { dcPwrSysCurrAlrmEntry 5 }
|
|
|
|
--============================
|
|
-- Voltage alarm group
|
|
--============================
|
|
dcPwrSysVoltAlrmCount OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of voltage alarm variables in system controller alarm table."
|
|
::= { dcPwrSysVoltAlrmTbl 1 }
|
|
|
|
dcPwrSysVoltAlrmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DcPwrSysVoltAlrmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A table of DC power system controller voltage alarm variables."
|
|
::= { dcPwrSysVoltAlrmTbl 2 }
|
|
|
|
dcPwrSysVoltAlrmEntry OBJECT-TYPE
|
|
SYNTAX DcPwrSysVoltAlrmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "An entry into the DC power system controller voltage alarm group."
|
|
INDEX { dcPwrSysVoltAlrmIndex }
|
|
::= { dcPwrSysVoltAlrmTable 1 }
|
|
|
|
DcPwrSysVoltAlrmEntry
|
|
::= SEQUENCE {
|
|
dcPwrSysVoltAlrmIndex INTEGER,
|
|
dcPwrSysVoltAlrmName DisplayString,
|
|
dcPwrSysVoltAlrmIntegerValue INTEGER,
|
|
dcPwrSysVoltAlrmStringValue DisplayString,
|
|
dcPwrSysVoltAlrmSeverity INTEGER
|
|
}
|
|
|
|
dcPwrSysVoltAlrmIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The index of the alarm variable in the DC power system controller table voltage alarm group."
|
|
::= { dcPwrSysVoltAlrmEntry 1 }
|
|
|
|
dcPwrSysVoltAlrmName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..30))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The description of the alarm variable as reported by the DC power system controller voltage alarm group."
|
|
::= { dcPwrSysVoltAlrmEntry 2 }
|
|
|
|
dcPwrSysVoltAlrmIntegerValue OBJECT-TYPE
|
|
SYNTAX INTEGER (-1000000000..1000000000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of the alarm variable as reported by the DC power system controller voltage alarm group."
|
|
::= { dcPwrSysVoltAlrmEntry 3 }
|
|
|
|
dcPwrSysVoltAlrmStringValue OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The string value of the alarm variable as reported by the DC power system controller voltage alarm group."
|
|
::= { dcPwrSysVoltAlrmEntry 4 }
|
|
|
|
dcPwrSysVoltAlrmSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of alarm severity level of the extra variable as reported by the DC power system controller voltage alarm group."
|
|
::= { dcPwrSysVoltAlrmEntry 5 }
|
|
|
|
--============================
|
|
-- Battery alarm group
|
|
--============================
|
|
dcPwrSysBattAlrmCount OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of battery alarm variables in system controller alarm table."
|
|
::= { dcPwrSysBattAlrmTbl 1 }
|
|
|
|
dcPwrSysBattAlrmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DcPwrSysBattAlrmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A table of DC power system controller battery alarm variables."
|
|
::= { dcPwrSysBattAlrmTbl 2 }
|
|
|
|
dcPwrSysBattAlrmEntry OBJECT-TYPE
|
|
SYNTAX DcPwrSysBattAlrmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "An entry into the DC power system controller battery alarm group."
|
|
INDEX { dcPwrSysBattAlrmIndex }
|
|
::= { dcPwrSysBattAlrmTable 1 }
|
|
|
|
DcPwrSysBattAlrmEntry
|
|
::= SEQUENCE {
|
|
dcPwrSysBattAlrmIndex INTEGER,
|
|
dcPwrSysBattAlrmName DisplayString,
|
|
dcPwrSysBattAlrmIntegerValue INTEGER,
|
|
dcPwrSysBattAlrmStringValue DisplayString,
|
|
dcPwrSysBattAlrmSeverity INTEGER
|
|
}
|
|
|
|
dcPwrSysBattAlrmIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The index of the alarm variable in the DC power system controller table battery alarm group."
|
|
::= { dcPwrSysBattAlrmEntry 1 }
|
|
|
|
dcPwrSysBattAlrmName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..30))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The description of the alarm variable as reported by the DC power system controller battery alarm group."
|
|
::= { dcPwrSysBattAlrmEntry 2 }
|
|
|
|
dcPwrSysBattAlrmIntegerValue OBJECT-TYPE
|
|
SYNTAX INTEGER (-1000000000..1000000000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of the alarm variable as reported by the DC power system controller battery alarm group."
|
|
::= { dcPwrSysBattAlrmEntry 3 }
|
|
|
|
dcPwrSysBattAlrmStringValue OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The string value of the alarm variable as reported by the DC power system controller battery alarm group."
|
|
::= { dcPwrSysBattAlrmEntry 4 }
|
|
|
|
dcPwrSysBattAlrmSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of alarm severity level of the extra variable as reported by the DC power system controller battery alarm group."
|
|
::= { dcPwrSysBattAlrmEntry 5 }
|
|
|
|
--============================
|
|
-- Temperature alarm group
|
|
--============================
|
|
dcPwrSysTempAlrmCount OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of temperature alarm variables in system controller alarm table."
|
|
::= { dcPwrSysTempAlrmTbl 1 }
|
|
|
|
dcPwrSysTempAlrmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DcPwrSysTempAlrmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A table of DC power system controller temperature alarm variables."
|
|
::= { dcPwrSysTempAlrmTbl 2 }
|
|
|
|
dcPwrSysTempAlrmEntry OBJECT-TYPE
|
|
SYNTAX DcPwrSysTempAlrmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "An entry into the DC power system controller temperature alarm group."
|
|
INDEX { dcPwrSysTempAlrmIndex }
|
|
::= { dcPwrSysTempAlrmTable 1 }
|
|
|
|
DcPwrSysTempAlrmEntry
|
|
::= SEQUENCE {
|
|
dcPwrSysTempAlrmIndex INTEGER,
|
|
dcPwrSysTempAlrmName DisplayString,
|
|
dcPwrSysTempAlrmIntegerValue INTEGER,
|
|
dcPwrSysTempAlrmStringValue DisplayString,
|
|
dcPwrSysTempAlrmSeverity INTEGER
|
|
}
|
|
|
|
dcPwrSysTempAlrmIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The index of the alarm variable in the DC power system controller table temperature alarm group."
|
|
::= { dcPwrSysTempAlrmEntry 1 }
|
|
|
|
dcPwrSysTempAlrmName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..30))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The description of the alarm variable as reported by the DC power system controller temperature alarm group."
|
|
::= { dcPwrSysTempAlrmEntry 2 }
|
|
|
|
dcPwrSysTempAlrmIntegerValue OBJECT-TYPE
|
|
SYNTAX INTEGER (-1000000000..1000000000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of the alarm variable as reported by the DC power system controller temperature alarm group."
|
|
::= { dcPwrSysTempAlrmEntry 3 }
|
|
|
|
dcPwrSysTempAlrmStringValue OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The string value of the alarm variable as reported by the DC power system controller temperature alarm group."
|
|
::= { dcPwrSysTempAlrmEntry 4 }
|
|
|
|
dcPwrSysTempAlrmSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of alarm severity level of the extra variable as reported by the DC power system controller temperature alarm group."
|
|
::= { dcPwrSysTempAlrmEntry 5 }
|
|
|
|
--============================
|
|
-- Custom alarm group
|
|
--============================
|
|
dcPwrSysCustomAlrmCount OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of custom alarm variables in system controller alarm table."
|
|
::= { dcPwrSysCustomAlrmTbl 1 }
|
|
|
|
dcPwrSysCustomAlrmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DcPwrSysCustomAlrmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A table of DC power system controller custom alarm variables."
|
|
::= { dcPwrSysCustomAlrmTbl 2 }
|
|
|
|
dcPwrSysCustomAlrmEntry OBJECT-TYPE
|
|
SYNTAX DcPwrSysCustomAlrmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "An entry into the DC power system controller custom alarm group."
|
|
INDEX { dcPwrSysCustomAlrmIndex }
|
|
::= { dcPwrSysCustomAlrmTable 1 }
|
|
|
|
DcPwrSysCustomAlrmEntry
|
|
::= SEQUENCE {
|
|
dcPwrSysCustomAlrmIndex INTEGER,
|
|
dcPwrSysCustomAlrmName DisplayString,
|
|
dcPwrSysCustomAlrmIntegerValue INTEGER,
|
|
dcPwrSysCustomAlrmStringValue DisplayString,
|
|
dcPwrSysCustomAlrmSeverity INTEGER
|
|
}
|
|
|
|
dcPwrSysCustomAlrmIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The index of the alarm variable in the DC power system controller table custom alarm group."
|
|
::= { dcPwrSysCustomAlrmEntry 1 }
|
|
|
|
dcPwrSysCustomAlrmName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..30))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The description of the alarm variable as reported by the DC power system controller custom alarm group."
|
|
::= { dcPwrSysCustomAlrmEntry 2 }
|
|
|
|
dcPwrSysCustomAlrmIntegerValue OBJECT-TYPE
|
|
SYNTAX INTEGER (-1000000000..1000000000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of the alarm variable as reported by the DC power system controller custom alarm group."
|
|
::= { dcPwrSysCustomAlrmEntry 3 }
|
|
|
|
dcPwrSysCustomAlrmStringValue OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The string value of the alarm variable as reported by the DC power system controller custom alarm group."
|
|
::= { dcPwrSysCustomAlrmEntry 4 }
|
|
|
|
dcPwrSysCustomAlrmSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of alarm severity level of the extra variable as reported by the DC power system controller custom alarm group."
|
|
::= { dcPwrSysCustomAlrmEntry 5 }
|
|
|
|
--============================
|
|
-- Misc alarm group
|
|
--============================
|
|
dcPwrSysMiscAlrmCount OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of misc alarm variables in system controller alarm table."
|
|
::= { dcPwrSysMiscAlrmTbl 1 }
|
|
|
|
dcPwrSysMiscAlrmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DcPwrSysMiscAlrmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A table of DC power system controller misc alarm variables."
|
|
::= { dcPwrSysMiscAlrmTbl 2 }
|
|
|
|
dcPwrSysMiscAlrmEntry OBJECT-TYPE
|
|
SYNTAX DcPwrSysMiscAlrmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "An entry into the DC power system controller misc alarm group."
|
|
INDEX { dcPwrSysMiscAlrmIndex }
|
|
::= { dcPwrSysMiscAlrmTable 1 }
|
|
|
|
DcPwrSysMiscAlrmEntry
|
|
::= SEQUENCE {
|
|
dcPwrSysMiscAlrmIndex INTEGER,
|
|
dcPwrSysMiscAlrmName DisplayString,
|
|
dcPwrSysMiscAlrmIntegerValue INTEGER,
|
|
dcPwrSysMiscAlrmStringValue DisplayString,
|
|
dcPwrSysMiscAlrmSeverity INTEGER
|
|
}
|
|
|
|
dcPwrSysMiscAlrmIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The index of the alarm variable in the DC power system controller table misc alarm group."
|
|
::= { dcPwrSysMiscAlrmEntry 1 }
|
|
|
|
dcPwrSysMiscAlrmName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..30))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The description of the alarm variable as reported by the DC power system controller misc alarm group."
|
|
::= { dcPwrSysMiscAlrmEntry 2 }
|
|
|
|
dcPwrSysMiscAlrmIntegerValue OBJECT-TYPE
|
|
SYNTAX INTEGER (-1000000000..1000000000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of the alarm variable as reported by the DC power system controller misc alarm group."
|
|
::= { dcPwrSysMiscAlrmEntry 3 }
|
|
|
|
dcPwrSysMiscAlrmStringValue OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The string value of the alarm variable as reported by the DC power system controller misc alarm group."
|
|
::= { dcPwrSysMiscAlrmEntry 4 }
|
|
|
|
dcPwrSysMiscAlrmSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of alarm severity level of the extra variable as reported by the DC power system controller misc alarm group."
|
|
::= { dcPwrSysMiscAlrmEntry 5 }
|
|
|
|
--============================
|
|
-- Control alarm group
|
|
--============================
|
|
dcPwrSysCtrlAlrmCount OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The number of control alarm variables."
|
|
::= { dcPwrSysCtrlAlrmTbl 1 }
|
|
|
|
dcPwrSysCtrlAlrmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DcPwrSysCtrlAlrmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A table of control alarm variables."
|
|
::= { dcPwrSysCtrlAlrmTbl 2 }
|
|
|
|
dcPwrSysCtrlAlrmEntry OBJECT-TYPE
|
|
SYNTAX DcPwrSysCtrlAlrmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "An entry of the control alarm group"
|
|
INDEX { dcPwrSysCtrlAlrmIndex }
|
|
::= { dcPwrSysCtrlAlrmTable 1 }
|
|
|
|
DcPwrSysCtrlAlrmEntry
|
|
::= SEQUENCE {
|
|
dcPwrSysCtrlAlrmIndex INTEGER,
|
|
dcPwrSysCtrlAlrmName DisplayString,
|
|
dcPwrSysCtrlAlrmIntegerValue INTEGER,
|
|
dcPwrSysCtrlAlrmStringValue DisplayString,
|
|
dcPwrSysCtrlAlrmSeverity INTEGER
|
|
}
|
|
|
|
dcPwrSysCtrlAlrmIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The index of the alarm variable in the control alarm group."
|
|
::= { dcPwrSysCtrlAlrmEntry 1 }
|
|
|
|
dcPwrSysCtrlAlrmName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..30))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The description of the alarm variable as reported by the control alarm group."
|
|
::= { dcPwrSysCtrlAlrmEntry 2 }
|
|
|
|
dcPwrSysCtrlAlrmIntegerValue OBJECT-TYPE
|
|
SYNTAX INTEGER (-1000000000..1000000000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of the alarm variable as reported by the control alarm group."
|
|
::= { dcPwrSysCtrlAlrmEntry 3 }
|
|
|
|
dcPwrSysCtrlAlrmStringValue OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The string value of the alarm variable as reported by the control alarm group."
|
|
::= { dcPwrSysCtrlAlrmEntry 4 }
|
|
|
|
dcPwrSysCtrlAlrmSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of alarm severity level of the extra variable as reported by the control alarm group."
|
|
::= { dcPwrSysCtrlAlrmEntry 5 }
|
|
|
|
|
|
--============================
|
|
-- ADIO alarm group
|
|
--============================
|
|
|
|
dcPwrSysAdioAlrmCount OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of control alarm variables in Adio alarm table."
|
|
::= { dcPwrSysAdioAlrmTbl 1 }
|
|
|
|
dcPwrSysAdioAlrmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DcPwrSysAdioAlrmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A table of Adio alarm variables."
|
|
::= { dcPwrSysAdioAlrmTbl 2 }
|
|
|
|
dcPwrSysAdioAlrmEntry OBJECT-TYPE
|
|
SYNTAX DcPwrSysAdioAlrmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "An entry into the Adio alarm group."
|
|
INDEX { dcPwrSysAdioAlrmIndex }
|
|
::= { dcPwrSysAdioAlrmTable 1 }
|
|
|
|
DcPwrSysAdioAlrmEntry
|
|
::= SEQUENCE {
|
|
dcPwrSysAdioAlrmIndex INTEGER,
|
|
dcPwrSysAdioAlrmName DisplayString,
|
|
dcPwrSysAdioAlrmIntegerValue INTEGER,
|
|
dcPwrSysAdioAlrmStringValue DisplayString,
|
|
dcPwrSysAdioAlrmSeverity INTEGER
|
|
}
|
|
|
|
dcPwrSysAdioAlrmIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The index of the alarm variable in the table Adio alarm group."
|
|
::= { dcPwrSysAdioAlrmEntry 1 }
|
|
|
|
dcPwrSysAdioAlrmName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..30))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The description of the alarm variable as reported by the Adio alarm group."
|
|
::= { dcPwrSysAdioAlrmEntry 2 }
|
|
|
|
dcPwrSysAdioAlrmIntegerValue OBJECT-TYPE
|
|
SYNTAX INTEGER (-1000000000..1000000000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of the alarm variable as reported by the Adio alarm group."
|
|
::= { dcPwrSysAdioAlrmEntry 3 }
|
|
|
|
dcPwrSysAdioAlrmStringValue OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The string value of the alarm variable as reported by the Adio alarm group."
|
|
::= { dcPwrSysAdioAlrmEntry 4 }
|
|
|
|
dcPwrSysAdioAlrmSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of alarm severity level of the extra variable as reported by the control alarm group."
|
|
::= { dcPwrSysAdioAlrmEntry 5 }
|
|
|
|
|
|
|
|
|
|
|
|
--============================
|
|
-- Converter alarm group
|
|
--============================
|
|
dcPwrSysConvAlrmCount OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of Converter alarm variables in system controller alarm table."
|
|
::= { dcPwrSysConvAlrmTbl 1 }
|
|
|
|
dcPwrSysConvAlrmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DcPwrSysConvAlrmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A table of Converter alarm variables."
|
|
::= { dcPwrSysConvAlrmTbl 2 }
|
|
|
|
dcPwrSysConvAlrmEntry OBJECT-TYPE
|
|
SYNTAX DcPwrSysConvAlrmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "An entry into the Converter alarm group."
|
|
INDEX { dcPwrSysConvAlrmIndex }
|
|
::= { dcPwrSysConvAlrmTable 1 }
|
|
|
|
DcPwrSysConvAlrmEntry
|
|
::= SEQUENCE {
|
|
dcPwrSysConvAlrmIndex INTEGER,
|
|
dcPwrSysConvAlrmName DisplayString,
|
|
dcPwrSysConvAlrmIntegerValue INTEGER,
|
|
dcPwrSysConvAlrmStringValue DisplayString,
|
|
dcPwrSysConvAlrmSeverity INTEGER
|
|
}
|
|
|
|
dcPwrSysConvAlrmIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The index of the alarm variable in the DC power system controller table Converter alarm group."
|
|
::= { dcPwrSysConvAlrmEntry 1 }
|
|
|
|
dcPwrSysConvAlrmName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..30))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The description of the alarm variable as reported by the Converter alarm group."
|
|
::= { dcPwrSysConvAlrmEntry 2 }
|
|
|
|
dcPwrSysConvAlrmIntegerValue OBJECT-TYPE
|
|
SYNTAX INTEGER (-1000000000..1000000000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of the alarm variable as reported by the Converter alarm group."
|
|
::= { dcPwrSysConvAlrmEntry 3 }
|
|
|
|
dcPwrSysConvAlrmStringValue OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The string value of the alarm variable as reported by the Converter alarm group."
|
|
::= { dcPwrSysConvAlrmEntry 4 }
|
|
|
|
dcPwrSysConvAlrmSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of alarm severity level of the extra variable as reported by the Converter alarm group."
|
|
::= { dcPwrSysConvAlrmEntry 5 }
|
|
|
|
|
|
|
|
|
|
|
|
|
|
--============================
|
|
-- alarm group
|
|
--============================
|
|
dcPwrSysInvAlrmCount OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of alarm variables in system controller alarm table"
|
|
::= { dcPwrSysInvAlrmTbl 1 }
|
|
|
|
dcPwrSysInvAlrmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DcPwrSysInvAlrmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A table of power system controller Inv alarm variables"
|
|
::= { dcPwrSysInvAlrmTbl 2 }
|
|
|
|
dcPwrSysInvAlrmEntry OBJECT-TYPE
|
|
SYNTAX DcPwrSysInvAlrmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "An entry into the power system controller Inv alarm group"
|
|
INDEX { dcPwrSysInvAlrmIndex }
|
|
::= { dcPwrSysInvAlrmTable 1 }
|
|
|
|
DcPwrSysInvAlrmEntry
|
|
::= SEQUENCE {
|
|
dcPwrSysInvAlrmIndex INTEGER,
|
|
dcPwrSysInvAlrmName DisplayString,
|
|
dcPwrSysInvAlrmIntegerValue INTEGER,
|
|
dcPwrSysInvAlrmStringValue DisplayString,
|
|
dcPwrSysInvAlrmSeverity INTEGER
|
|
}
|
|
|
|
dcPwrSysInvAlrmIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION ""
|
|
::= { dcPwrSysInvAlrmEntry 1 }
|
|
|
|
dcPwrSysInvAlrmName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..30))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION ""
|
|
::= { dcPwrSysInvAlrmEntry 2 }
|
|
|
|
dcPwrSysInvAlrmIntegerValue OBJECT-TYPE
|
|
SYNTAX INTEGER (-1000000000..1000000000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION ""
|
|
::= { dcPwrSysInvAlrmEntry 3 }
|
|
|
|
dcPwrSysInvAlrmStringValue OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION ""
|
|
::= { dcPwrSysInvAlrmEntry 4 }
|
|
|
|
dcPwrSysInvAlrmSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION ""
|
|
::= { dcPwrSysInvAlrmEntry 5 }
|
|
|
|
|
|
|
|
--============================
|
|
-- Lps alarm group
|
|
--============================
|
|
dcPwrSysLpsAlrmCount OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of LPS alarm variables in system controller alarm table."
|
|
::= { dcPwrSysLpsAlrmTbl 1 }
|
|
|
|
dcPwrSysLpsAlrmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DcPwrSysLpsAlrmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A table of LPS alarm variables."
|
|
::= { dcPwrSysLpsAlrmTbl 2 }
|
|
|
|
dcPwrSysLpsAlrmEntry OBJECT-TYPE
|
|
SYNTAX DcPwrSysLpsAlrmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "An entry into the LPS alarm group."
|
|
INDEX { dcPwrSysLpsAlrmIndex }
|
|
::= { dcPwrSysLpsAlrmTable 1 }
|
|
|
|
DcPwrSysLpsAlrmEntry
|
|
::= SEQUENCE {
|
|
dcPwrSysLpsAlrmIndex INTEGER,
|
|
dcPwrSysLpsAlrmName DisplayString,
|
|
dcPwrSysLpsAlrmIntegerValue INTEGER,
|
|
dcPwrSysLpsAlrmStringValue DisplayString,
|
|
dcPwrSysLpsAlrmSeverity INTEGER
|
|
}
|
|
|
|
dcPwrSysLpsAlrmIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The index of the alarm variable in the DC power system controller table LPS alarm group."
|
|
::= { dcPwrSysLpsAlrmEntry 1 }
|
|
|
|
dcPwrSysLpsAlrmName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..30))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The description of the alarm variable as reported by the LPS alarm group."
|
|
::= { dcPwrSysLpsAlrmEntry 2 }
|
|
|
|
dcPwrSysLpsAlrmIntegerValue OBJECT-TYPE
|
|
SYNTAX INTEGER (-1000000000..1000000000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of the alarm variable as reported by the LPS alarm group."
|
|
::= { dcPwrSysLpsAlrmEntry 3 }
|
|
|
|
dcPwrSysLpsAlrmStringValue OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The string value of the alarm variable as reported by the LPS alarm group."
|
|
::= { dcPwrSysLpsAlrmEntry 4 }
|
|
|
|
dcPwrSysLpsAlrmSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of alarm severity level of the extra variable as reported by the LPS alarm group."
|
|
::= { dcPwrSysLpsAlrmEntry 5 }
|
|
|
|
|
|
|
|
|
|
--============
|
|
-- Input table
|
|
--============
|
|
--=====================
|
|
-- Digital input group
|
|
--=====================
|
|
dcPwrSysDigIpCount OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of digital input variables in system controller digital input table."
|
|
::= { dcPwrSysDigIpTbl 1 }
|
|
|
|
dcPwrSysDigIpTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DcPwrSysDigIpEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A table of digital input variables."
|
|
::= { dcPwrSysDigIpTbl 2 }
|
|
|
|
dcPwrSysDigIpEntry OBJECT-TYPE
|
|
SYNTAX DcPwrSysDigIpEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "An entry into the digital input group."
|
|
INDEX { dcPwrSysDigIpIndex }
|
|
::= { dcPwrSysDigIpTable 1 }
|
|
|
|
DcPwrSysDigIpEntry
|
|
::= SEQUENCE {
|
|
dcPwrSysDigIpIndex INTEGER,
|
|
dcPwrSysDigIpName DisplayString,
|
|
dcPwrSysDigIpIntegerValue INTEGER,
|
|
dcPwrSysDigIpStringValue DisplayString
|
|
}
|
|
|
|
dcPwrSysDigIpIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The index of the digital input variable in the table digital input group."
|
|
::= { dcPwrSysDigIpEntry 1 }
|
|
|
|
dcPwrSysDigIpName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..30))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The description of the digital input variable as reported by the digital input group."
|
|
::= { dcPwrSysDigIpEntry 2 }
|
|
|
|
dcPwrSysDigIpIntegerValue OBJECT-TYPE
|
|
SYNTAX INTEGER (-1000000000..1000000000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of the digital input variable as reported by the digital input group."
|
|
::= { dcPwrSysDigIpEntry 3 }
|
|
|
|
dcPwrSysDigIpStringValue OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The string value of the digital input variable as reported by the digital input group."
|
|
::= { dcPwrSysDigIpEntry 4 }
|
|
|
|
--=========================
|
|
-- Controller input group
|
|
--=========================
|
|
dcPwrSysCntrlrIpCount OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of controller input variables in system controller controller input table."
|
|
::= { dcPwrSysCntrlrIpTbl 1 }
|
|
|
|
dcPwrSysCntrlrIpTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DcPwrSysCntrlrIpEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A table of controller input variables."
|
|
::= { dcPwrSysCntrlrIpTbl 2 }
|
|
|
|
dcPwrSysCntrlrIpEntry OBJECT-TYPE
|
|
SYNTAX DcPwrSysCntrlrIpEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "An entry into the controller input group."
|
|
INDEX { dcPwrSysCntrlrIpIndex }
|
|
::= { dcPwrSysCntrlrIpTable 1 }
|
|
|
|
DcPwrSysCntrlrIpEntry
|
|
::= SEQUENCE {
|
|
dcPwrSysCntrlrIpIndex INTEGER,
|
|
dcPwrSysCntrlrIpName DisplayString,
|
|
dcPwrSysCntrlrIpIntegerValue INTEGER,
|
|
dcPwrSysCntrlrIpStringValue DisplayString
|
|
}
|
|
|
|
dcPwrSysCntrlrIpIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The index of the controller input variable in the table controller input group."
|
|
::= { dcPwrSysCntrlrIpEntry 1 }
|
|
|
|
dcPwrSysCntrlrIpName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..30))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The description of the controller input variable as reported by the controller input group."
|
|
::= { dcPwrSysCntrlrIpEntry 2 }
|
|
|
|
dcPwrSysCntrlrIpIntegerValue OBJECT-TYPE
|
|
SYNTAX INTEGER (-1000000000..1000000000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of the controller input variable as reported by the controller input group."
|
|
::= { dcPwrSysCntrlrIpEntry 3 }
|
|
|
|
dcPwrSysCntrlrIpStringValue OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The string value of the controller input variable as reported by the controller input group."
|
|
::= { dcPwrSysCntrlrIpEntry 4 }
|
|
|
|
--========================
|
|
-- Rectifier input group
|
|
--========================
|
|
dcPwrSysRectIpCount OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of rectifier input variables in system controller rectifier input table."
|
|
::= { dcPwrSysRectIpTbl 1 }
|
|
|
|
dcPwrSysRectIpTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DcPwrSysRectIpEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A table of rectifier input variables."
|
|
::= { dcPwrSysRectIpTbl 2 }
|
|
|
|
dcPwrSysRectIpEntry OBJECT-TYPE
|
|
SYNTAX DcPwrSysRectIpEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "An entry into the rectifier input group."
|
|
INDEX { dcPwrSysRectIpIndex }
|
|
::= { dcPwrSysRectIpTable 1 }
|
|
|
|
DcPwrSysRectIpEntry
|
|
::= SEQUENCE {
|
|
dcPwrSysRectIpIndex INTEGER,
|
|
dcPwrSysRectIpName DisplayString,
|
|
dcPwrSysRectIpIntegerValue INTEGER,
|
|
dcPwrSysRectIpStringValue DisplayString
|
|
}
|
|
|
|
dcPwrSysRectIpIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The index of the rectifier input variable in the table rectifier input group."
|
|
::= { dcPwrSysRectIpEntry 1 }
|
|
|
|
dcPwrSysRectIpName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..30))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The description of the rectifier input variable as reported by the rectifier input group."
|
|
::= { dcPwrSysRectIpEntry 2 }
|
|
|
|
dcPwrSysRectIpIntegerValue OBJECT-TYPE
|
|
SYNTAX INTEGER (-1000000000..1000000000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of the rectifier input variable as reported by the rectifier input group."
|
|
::= { dcPwrSysRectIpEntry 3 }
|
|
|
|
dcPwrSysRectIpStringValue OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The string value of the rectifier input variable as reported by the rectifier input group."
|
|
::= { dcPwrSysRectIpEntry 4 }
|
|
|
|
--======================
|
|
-- Custom input group
|
|
--======================
|
|
dcPwrSysCustomIpCount OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of custom input variables in system controller custom input table."
|
|
::= { dcPwrSysCustomIpTbl 1 }
|
|
|
|
dcPwrSysCustomIpTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DcPwrSysCustomIpEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A table of digital custom variables."
|
|
::= { dcPwrSysCustomIpTbl 2 }
|
|
|
|
dcPwrSysCustomIpEntry OBJECT-TYPE
|
|
SYNTAX DcPwrSysCustomIpEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "An entry into the custom input group."
|
|
INDEX { dcPwrSysCustomIpIndex }
|
|
::= { dcPwrSysCustomIpTable 1 }
|
|
|
|
DcPwrSysCustomIpEntry
|
|
::= SEQUENCE {
|
|
dcPwrSysCustomIpIndex INTEGER,
|
|
dcPwrSysCustomIpName DisplayString,
|
|
dcPwrSysgCustomIpIntegerValue INTEGER,
|
|
dcPwrSysCustomIpStringValue DisplayString
|
|
}
|
|
|
|
dcPwrSysCustomIpIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The index of the custom input variable in the table custom input group."
|
|
::= { dcPwrSysCustomIpEntry 1 }
|
|
|
|
dcPwrSysCustomIpName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..30))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The description of the custom input variable as reported by the custom input group."
|
|
::= { dcPwrSysCustomIpEntry 2 }
|
|
|
|
dcPwrSysgCustomIpIntegerValue OBJECT-TYPE
|
|
SYNTAX INTEGER (-1000000000..1000000000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The integer value of the custom input variable as reported by the custom input group."
|
|
::= { dcPwrSysCustomIpEntry 3 }
|
|
|
|
dcPwrSysCustomIpStringValue OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The string value of the custom input variable as reported by the custom input group."
|
|
::= { dcPwrSysCustomIpEntry 4 }
|
|
|
|
|
|
|
|
--========================
|
|
-- Converter input group
|
|
--========================
|
|
dcPwrSysConvIpCount OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of Converter input variables in system controller Converter input table."
|
|
::= { dcPwrSysConvIpTbl 1 }
|
|
|
|
dcPwrSysConvIpTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DcPwrSysConvIpEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A table of Converter input variables."
|
|
::= { dcPwrSysConvIpTbl 2 }
|
|
|
|
dcPwrSysConvIpEntry OBJECT-TYPE
|
|
SYNTAX DcPwrSysConvIpEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "An entry into the Converter input group."
|
|
INDEX { dcPwrSysConvIpIndex }
|
|
::= { dcPwrSysConvIpTable 1 }
|
|
|
|
DcPwrSysConvIpEntry
|
|
::= SEQUENCE {
|
|
dcPwrSysConvIpIndex INTEGER,
|
|
dcPwrSysConvIpName DisplayString,
|
|
dcPwrSysConvIpIntegerValue INTEGER,
|
|
dcPwrSysConvIpStringValue DisplayString
|
|
}
|
|
|
|
dcPwrSysConvIpIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The index of the Converter input variable in the table Converter input group."
|
|
::= { dcPwrSysConvIpEntry 1 }
|
|
|
|
dcPwrSysConvIpName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..30))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The description of the Converter input variable as reported by the Converter input group."
|
|
::= { dcPwrSysConvIpEntry 2 }
|
|
|
|
dcPwrSysConvIpIntegerValue OBJECT-TYPE
|
|
SYNTAX INTEGER (-1000000000..1000000000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of the Converter input variable as reported by the Converter input group."
|
|
::= { dcPwrSysConvIpEntry 3 }
|
|
|
|
dcPwrSysConvIpStringValue OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The string value of the Converter input variable as reported by the Converter input group."
|
|
::= { dcPwrSysConvIpEntry 4 }
|
|
|
|
--========================
|
|
-- Timer input group
|
|
--========================
|
|
dcPwrSysTimerIpCount OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of Timer input variables in system controller Timer input table."
|
|
::= { dcPwrSysTimerIpTbl 1 }
|
|
|
|
dcPwrSysTimerIpTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DcPwrSysTimerIpEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A table of Timer input variables"
|
|
::= { dcPwrSysTimerIpTbl 2 }
|
|
|
|
dcPwrSysTimerIpEntry OBJECT-TYPE
|
|
SYNTAX DcPwrSysTimerIpEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "An entry into the Timer input group"
|
|
INDEX { dcPwrSysTimerIpIndex }
|
|
::= { dcPwrSysTimerIpTable 1 }
|
|
|
|
DcPwrSysTimerIpEntry
|
|
::= SEQUENCE {
|
|
dcPwrSysTimerIpIndex INTEGER,
|
|
dcPwrSysTimerIpName DisplayString,
|
|
dcPwrSysTimerIpIntegerValue INTEGER,
|
|
dcPwrSysTimerIpStringValue DisplayString
|
|
}
|
|
|
|
dcPwrSysTimerIpIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The index of the Timer input variable in the table Timer input group."
|
|
::= { dcPwrSysTimerIpEntry 1 }
|
|
|
|
dcPwrSysTimerIpName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..30))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The description of the Timer input variable as reported by the Timer input group."
|
|
::= { dcPwrSysTimerIpEntry 2 }
|
|
|
|
dcPwrSysTimerIpIntegerValue OBJECT-TYPE
|
|
SYNTAX INTEGER (-1000000000..1000000000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of the Timer input variable as reported by the Timer input group."
|
|
::= { dcPwrSysTimerIpEntry 3 }
|
|
|
|
dcPwrSysTimerIpStringValue OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The string value of the Timer input variable as reported by the Timer input group."
|
|
::= { dcPwrSysTimerIpEntry 4 }
|
|
|
|
|
|
--========================
|
|
-- Counter input group
|
|
--========================
|
|
dcPwrSysCounterIpCount OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of Counter input variables in system controller Counter input table."
|
|
::= { dcPwrSysCounterIpTbl 1 }
|
|
|
|
dcPwrSysCounterIpTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DcPwrSysCounterIpEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A table of Counter input variables."
|
|
::= { dcPwrSysCounterIpTbl 2 }
|
|
|
|
dcPwrSysCounterIpEntry OBJECT-TYPE
|
|
SYNTAX DcPwrSysCounterIpEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "An entry into the Counter input group."
|
|
INDEX { dcPwrSysCounterIpIndex }
|
|
::= { dcPwrSysCounterIpTable 1 }
|
|
|
|
DcPwrSysCounterIpEntry
|
|
::= SEQUENCE {
|
|
dcPwrSysCounterIpIndex INTEGER,
|
|
dcPwrSysCounterIpName DisplayString,
|
|
dcPwrSysCounterIpIntegerValue INTEGER,
|
|
dcPwrSysCounterIpStringValue DisplayString
|
|
}
|
|
|
|
dcPwrSysCounterIpIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The index of the Counter input variable in the table Counter input group."
|
|
::= { dcPwrSysCounterIpEntry 1 }
|
|
|
|
dcPwrSysCounterIpName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..30))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The description of the Counter input variable as reported by the Counter input group."
|
|
::= { dcPwrSysCounterIpEntry 2 }
|
|
|
|
dcPwrSysCounterIpIntegerValue OBJECT-TYPE
|
|
SYNTAX INTEGER (-1000000000..1000000000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The integer value of the Counter input variable as reported by the Counter input group."
|
|
::= { dcPwrSysCounterIpEntry 3 }
|
|
|
|
dcPwrSysCounterIpStringValue OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The string value of the Counter input variable as reported by the Counter input group."
|
|
::= { dcPwrSysCounterIpEntry 4 }
|
|
|
|
|
|
--==========================================================================
|
|
-- LPS Data
|
|
--==========================================================================
|
|
|
|
lpsModuleCount OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The number of LPS modules acquired by the CXC."
|
|
::= { dcPwrSysLpsTbl 1 }
|
|
|
|
lpsModuleTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LpsModuleEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A table of LPS modules."
|
|
::= { dcPwrSysLpsTbl 2 }
|
|
|
|
lpsModuleEntry OBJECT-TYPE
|
|
SYNTAX LpsModuleEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "An entry in the table of LPS modules."
|
|
INDEX { lpsModuleIndex }
|
|
::= { lpsModuleTable 1 }
|
|
|
|
LpsModuleEntry
|
|
::= SEQUENCE {
|
|
lpsModuleIndex INTEGER,
|
|
lpsShelfId INTEGER,
|
|
lpsPosition INTEGER,
|
|
lpsInputVoltage INTEGER,
|
|
lpsHeatsinkTemperature INTEGER,
|
|
lpsAmbientTemperature INTEGER,
|
|
lpsSerialNumber DisplayString,
|
|
lpsDeviceName DisplayString,
|
|
lpsSoftwareVersionNumber DisplayString
|
|
}
|
|
|
|
lpsModuleIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The index of the LPS module."
|
|
::= { lpsModuleEntry 1 }
|
|
|
|
lpsShelfId OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Shelf ID - identifies the shelf in which this LPS is located."
|
|
::= { lpsModuleEntry 2 }
|
|
|
|
lpsPosition OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Position (slot ID) - identifies the position within the shelf."
|
|
::= { lpsModuleEntry 3 }
|
|
|
|
lpsInputVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Input Voltage"
|
|
::= { lpsModuleEntry 4 }
|
|
|
|
lpsHeatsinkTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Heatsink Temperature."
|
|
::= { lpsModuleEntry 5 }
|
|
|
|
lpsAmbientTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Ambient Temperature"
|
|
::= { lpsModuleEntry 6 }
|
|
|
|
lpsSerialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..16))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS module serial number"
|
|
::= { lpsModuleEntry 7 }
|
|
|
|
lpsDeviceName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..16))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Device name."
|
|
::= { lpsModuleEntry 8 }
|
|
|
|
lpsSoftwareVersionNumber OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..16))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS software version number."
|
|
::= { lpsModuleEntry 9 }
|
|
|
|
|
|
lpsModuleAlarmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LpsModuleAlarmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A table containing LPS alarms."
|
|
::= { dcPwrSysLpsTbl 3 }
|
|
|
|
lpsModuleAlarmEntry OBJECT-TYPE
|
|
SYNTAX LpsModuleAlarmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "An entry in the table of LPS alarms."
|
|
INDEX { lpsModuleIndex }
|
|
::= { lpsModuleAlarmTable 1 }
|
|
|
|
LpsModuleAlarmEntry
|
|
::= SEQUENCE {
|
|
lpsModuleAlarmEntryIndex INTEGER,
|
|
lpsHighInputVoltageAlarm INTEGER,
|
|
lpsLowInputVoltageAlarm INTEGER,
|
|
lpsAmbientHighAlarm INTEGER,
|
|
lpsHeatsinkHighAlarm INTEGER,
|
|
lpsMajorAlarm INTEGER,
|
|
lpsMinorAlarm INTEGER,
|
|
lpsOOTAlarm INTEGER,
|
|
lpsCommsLostAlarm INTEGER
|
|
}
|
|
|
|
lpsModuleAlarmEntryIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The index of the LPS module."
|
|
::= { lpsModuleAlarmEntry 1 }
|
|
|
|
|
|
lpsHighInputVoltageAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Input voltage is too high."
|
|
::= { lpsModuleAlarmEntry 2 }
|
|
|
|
lpsLowInputVoltageAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Input voltage is too low."
|
|
::= { lpsModuleAlarmEntry 3 }
|
|
|
|
lpsAmbientHighAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Ambient temperature is too high."
|
|
::= { lpsModuleAlarmEntry 4 }
|
|
|
|
lpsHeatsinkHighAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Heatsink temperature is too high."
|
|
::= { lpsModuleAlarmEntry 5 }
|
|
|
|
lpsMajorAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Multiple LPS outputs have failed."
|
|
::= { lpsModuleAlarmEntry 6 }
|
|
|
|
lpsMinorAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "A single LPS output has failed."
|
|
::= { lpsModuleAlarmEntry 7 }
|
|
|
|
lpsOOTAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The LPS settings do not match those required by the controller."
|
|
::= { lpsModuleAlarmEntry 8 }
|
|
|
|
lpsCommsLostAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The controller has lost communication with the LPS."
|
|
::= { lpsModuleAlarmEntry 9 }
|
|
|
|
lpsOutputVoltageTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LpsOutputVoltageEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A table containing the output voltage of the LPS channels."
|
|
::= { dcPwrSysLpsTbl 4 }
|
|
|
|
lpsOutputVoltageEntry OBJECT-TYPE
|
|
SYNTAX LpsOutputVoltageEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "An entry in the table containing the output voltage of the LPS channels."
|
|
INDEX { lpsModuleIndex }
|
|
::= { lpsOutputVoltageTable 1 }
|
|
|
|
LpsOutputVoltageEntry
|
|
::= SEQUENCE {
|
|
lpsOutputVoltageEntryIndex INTEGER,
|
|
lpsOutputVoltageChannel1 INTEGER,
|
|
lpsOutputVoltageChannel2 INTEGER,
|
|
lpsOutputVoltageChannel3 INTEGER,
|
|
lpsOutputVoltageChannel4 INTEGER,
|
|
}
|
|
|
|
lpsOutputVoltageEntryIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "index"
|
|
::= { lpsOutputVoltageEntry 1 }
|
|
|
|
|
|
lpsOutputVoltageChannel1 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The output voltage of LPS Channel 1."
|
|
::= { lpsOutputVoltageEntry 2 }
|
|
|
|
lpsOutputVoltageChannel2 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The output voltage of LPS Channel 2."
|
|
::= { lpsOutputVoltageEntry 3 }
|
|
|
|
lpsOutputVoltageChannel3 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The output voltage of LPS Channel 3."
|
|
::= { lpsOutputVoltageEntry 4 }
|
|
|
|
lpsOutputVoltageChannel4 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The output voltage of LPS Channel 4."
|
|
::= { lpsOutputVoltageEntry 5 }
|
|
|
|
|
|
lpsOutputCurrentTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LpsOutputCurrentEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A table containing the output current of the LPS channels."
|
|
::= { dcPwrSysLpsTbl 5 }
|
|
|
|
lpsOutputCurrentEntry OBJECT-TYPE
|
|
SYNTAX LpsOutputCurrentEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "An entry in the table containing the output voltage of the LPS channels."
|
|
INDEX { lpsModuleIndex }
|
|
::= { lpsOutputCurrentTable 1 }
|
|
|
|
LpsOutputCurrentEntry
|
|
::= SEQUENCE {
|
|
lpsOutputCurrentEntryIndex INTEGER,
|
|
lpsOutputCurrentChannel1 INTEGER,
|
|
lpsOutputCurrentChannel2 INTEGER,
|
|
lpsOutputCurrentChannel3 INTEGER,
|
|
lpsOutputCurrentChannel4 INTEGER
|
|
}
|
|
|
|
lpsOutputCurrentEntryIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "index"
|
|
::= { lpsOutputCurrentEntry 1 }
|
|
|
|
|
|
lpsOutputCurrentChannel1 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The output current of LPS Channel 1."
|
|
::= { lpsOutputCurrentEntry 2 }
|
|
|
|
lpsOutputCurrentChannel2 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The output current of LPS Channel 2."
|
|
::= { lpsOutputCurrentEntry 3 }
|
|
|
|
lpsOutputCurrentChannel3 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The output current of LPS Channel 3."
|
|
::= { lpsOutputCurrentEntry 4 }
|
|
|
|
lpsOutputCurrentChannel4 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The output current of LPS Channel 4."
|
|
::= { lpsOutputCurrentEntry 5 }
|
|
|
|
lpsChannelStatusFaultsTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LpsChannelStatusFaultsEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A table containing the faults for each LPS channel."
|
|
::= { dcPwrSysLpsTbl 6 }
|
|
|
|
lpsChannelStatusFaultsEntry OBJECT-TYPE
|
|
SYNTAX LpsChannelStatusFaultsEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "An entry in the table containing the faults for each LPS channel."
|
|
INDEX { lpsModuleIndex }
|
|
::= { lpsChannelStatusFaultsTable 1 }
|
|
|
|
LpsChannelStatusFaultsEntry
|
|
::= SEQUENCE {
|
|
lpsChannelStatusFaultsEntryIndex INTEGER,
|
|
lpsGfiChannel1 INTEGER,
|
|
lpsFuseChannel1 INTEGER,
|
|
lpsOvpChannel1 INTEGER,
|
|
lpsOverCurrentChannel1 INTEGER,
|
|
lpsLowOutputVoltageChannel1 INTEGER,
|
|
lpsRemoteShutdownChannel1 INTEGER,
|
|
|
|
lpsGfiChannel2 INTEGER,
|
|
lpsFuseChannel2 INTEGER,
|
|
lpsOvpChannel2 INTEGER,
|
|
lpsOverCurrentChannel2 INTEGER,
|
|
lpsLowOutputVoltageChannel2 INTEGER,
|
|
lpsRemoteShutdownChannel2 INTEGER,
|
|
|
|
lpsGfiChannel3 INTEGER,
|
|
lpsFuseChannel3 INTEGER,
|
|
lpsOvpChannel3 INTEGER,
|
|
lpsOverCurrentChannel3 INTEGER,
|
|
lpsLowOutputVoltageChannel3 INTEGER,
|
|
lpsRemoteShutdownChannel3 INTEGER,
|
|
|
|
lpsGfiChannel4 INTEGER,
|
|
lpsFuseChannel4 INTEGER,
|
|
lpsOvpChannel4 INTEGER,
|
|
lpsOverCurrentChannel4 INTEGER,
|
|
lpsLowOutputVoltageChannel4 INTEGER,
|
|
lpsRemoteShutdownChannel4 INTEGER,
|
|
|
|
lpsLowCurrent1 INTEGER,
|
|
lpsTransientOVP1 INTEGER,
|
|
lpsTransientGFI1 INTEGER,
|
|
lpsTransientVoutLow1 INTEGER,
|
|
|
|
lpsLowCurrent2 INTEGER,
|
|
lpsTransientOVP2 INTEGER,
|
|
lpsTransientGFI2 INTEGER,
|
|
lpsTransientVoutLow2 INTEGER,
|
|
|
|
lpsLowCurrent3 INTEGER,
|
|
lpsTransientOVP3 INTEGER,
|
|
lpsTransientGFI3 INTEGER,
|
|
lpsTransientVoutLow3 INTEGER,
|
|
|
|
lpsLowCurrent4 INTEGER,
|
|
lpsTransientOVP4 INTEGER,
|
|
lpsTransientGFI4 INTEGER,
|
|
lpsTransientVoutLow4 INTEGER,
|
|
|
|
lpsCurrentSensorShorted1 INTEGER,
|
|
lpsCurrentSensorShorted2 INTEGER,
|
|
lpsCurrentSensorShorted3 INTEGER,
|
|
lpsCurrentSensorShorted4 INTEGER
|
|
|
|
}
|
|
|
|
lpsChannelStatusFaultsEntryIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "index"
|
|
::= { lpsChannelStatusFaultsEntry 1 }
|
|
|
|
lpsGfiChannel1 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 1 has a GFI fault."
|
|
::= { lpsChannelStatusFaultsEntry 2 }
|
|
|
|
lpsFuseChannel1 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 1 has a fuse fault."
|
|
::= { lpsChannelStatusFaultsEntry 3 }
|
|
|
|
lpsOvpChannel1 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 1 has an OVP fault."
|
|
::= { lpsChannelStatusFaultsEntry 4 }
|
|
|
|
lpsOverCurrentChannel1 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 1 has a Over-Current (OCP) fault."
|
|
::= { lpsChannelStatusFaultsEntry 5 }
|
|
|
|
lpsLowOutputVoltageChannel1 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 1 has low output voltage."
|
|
::= { lpsChannelStatusFaultsEntry 6 }
|
|
|
|
lpsRemoteShutdownChannel1 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 1 has been remotely shut down."
|
|
::= { lpsChannelStatusFaultsEntry 7 }
|
|
|
|
lpsGfiChannel2 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 2 has a GFI fault."
|
|
::= { lpsChannelStatusFaultsEntry 8 }
|
|
|
|
lpsFuseChannel2 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 2 has a fuse fault."
|
|
::= { lpsChannelStatusFaultsEntry 9 }
|
|
|
|
lpsOvpChannel2 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 2 has an OVP fault."
|
|
::= { lpsChannelStatusFaultsEntry 10 }
|
|
|
|
lpsOverCurrentChannel2 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 2 has a Over-Current (OCP) fault."
|
|
::= { lpsChannelStatusFaultsEntry 11 }
|
|
|
|
lpsLowOutputVoltageChannel2 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 2 has low output voltage."
|
|
::= { lpsChannelStatusFaultsEntry 12 }
|
|
|
|
lpsRemoteShutdownChannel2 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 2 has been remotely shut down."
|
|
::= { lpsChannelStatusFaultsEntry 13 }
|
|
|
|
lpsGfiChannel3 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 3 has a GFI fault."
|
|
::= { lpsChannelStatusFaultsEntry 14 }
|
|
|
|
lpsFuseChannel3 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 3 has a fuse fault."
|
|
::= { lpsChannelStatusFaultsEntry 15 }
|
|
|
|
lpsOvpChannel3 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 3 has an OVP fault."
|
|
::= { lpsChannelStatusFaultsEntry 16 }
|
|
|
|
lpsOverCurrentChannel3 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 3 has a Over-Current (OCP) fault."
|
|
::= { lpsChannelStatusFaultsEntry 17 }
|
|
|
|
lpsLowOutputVoltageChannel3 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 3 has low output voltage."
|
|
::= { lpsChannelStatusFaultsEntry 18 }
|
|
|
|
lpsRemoteShutdownChannel3 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 3 has been remotely shut down."
|
|
::= { lpsChannelStatusFaultsEntry 19 }
|
|
|
|
lpsGfiChannel4 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 4 has a GFI fault."
|
|
::= { lpsChannelStatusFaultsEntry 20 }
|
|
|
|
lpsFuseChannel4 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 4 has a fuse fault."
|
|
::= { lpsChannelStatusFaultsEntry 21 }
|
|
|
|
lpsOvpChannel4 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 4 has an OVP fault."
|
|
::= { lpsChannelStatusFaultsEntry 22 }
|
|
|
|
lpsOverCurrentChannel4 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 4 has a Over-Current (OCP) fault."
|
|
::= { lpsChannelStatusFaultsEntry 23 }
|
|
|
|
lpsLowOutputVoltageChannel4 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 4 has low output voltage."
|
|
::= { lpsChannelStatusFaultsEntry 24 }
|
|
|
|
lpsRemoteShutdownChannel4 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 4 has been remotely shut down."
|
|
::= { lpsChannelStatusFaultsEntry 25 }
|
|
|
|
lpsLowCurrent1 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 1 has a low current fault."
|
|
::= { lpsChannelStatusFaultsEntry 26 }
|
|
|
|
lpsTransientOVP1 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 1 had a transient OVP event."
|
|
::= { lpsChannelStatusFaultsEntry 27 }
|
|
|
|
lpsTransientGFI1 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 1 had a transient GFI event."
|
|
::= { lpsChannelStatusFaultsEntry 28 }
|
|
|
|
lpsTransientVoutLow1 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 1 had a transient Vout Low event."
|
|
::= { lpsChannelStatusFaultsEntry 29 }
|
|
|
|
lpsLowCurrent2 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 2 has a low current fault."
|
|
::= { lpsChannelStatusFaultsEntry 30 }
|
|
|
|
lpsTransientOVP2 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 2 had a transient OVP event."
|
|
::= { lpsChannelStatusFaultsEntry 31 }
|
|
|
|
lpsTransientGFI2 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 2 had a transient GFI event."
|
|
::= { lpsChannelStatusFaultsEntry 32 }
|
|
|
|
lpsTransientVoutLow2 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 2 had a transient Vout Low event."
|
|
::= { lpsChannelStatusFaultsEntry 33 }
|
|
|
|
lpsLowCurrent3 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 3 has a low current fault."
|
|
::= { lpsChannelStatusFaultsEntry 34 }
|
|
|
|
lpsTransientOVP3 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 3 had a transient OVP event."
|
|
::= { lpsChannelStatusFaultsEntry 35 }
|
|
|
|
lpsTransientGFI3 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 3 had a transient GFI event."
|
|
::= { lpsChannelStatusFaultsEntry 36 }
|
|
|
|
lpsTransientVoutLow3 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 3 had a transient Vout Low event."
|
|
::= { lpsChannelStatusFaultsEntry 37 }
|
|
|
|
lpsLowCurrent4 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 4 has a low current fault."
|
|
::= { lpsChannelStatusFaultsEntry 38 }
|
|
|
|
lpsTransientOVP4 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 4 had a transient OVP event."
|
|
::= { lpsChannelStatusFaultsEntry 39 }
|
|
|
|
lpsTransientGFI4 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 4 had a transient GFI event."
|
|
::= { lpsChannelStatusFaultsEntry 40 }
|
|
|
|
lpsTransientVoutLow4 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 4 had a transient Vout Low event."
|
|
::= { lpsChannelStatusFaultsEntry 41 }
|
|
|
|
lpsCurrentSensorShorted1 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 1 had a transient Current Sensor Shorted event."
|
|
::= { lpsChannelStatusFaultsEntry 42 }
|
|
|
|
lpsCurrentSensorShorted2 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 2 had a transient Current Sensor Shorted event."
|
|
::= { lpsChannelStatusFaultsEntry 43 }
|
|
|
|
lpsCurrentSensorShorted3 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 3 had a transient Current Sensor Shorted event."
|
|
::= { lpsChannelStatusFaultsEntry 44 }
|
|
|
|
lpsCurrentSensorShorted4 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "LPS Channel 4 had a transient Current Sensor Shorted event."
|
|
::= { lpsChannelStatusFaultsEntry 45 }
|
|
|
|
lpsChannelInfoTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LpsChannelInfoEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A table containing extra info about the LPS channels."
|
|
::= { dcPwrSysLpsTbl 7 }
|
|
|
|
lpsChannelInfoEntry OBJECT-TYPE
|
|
SYNTAX LpsChannelInfoEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "An entry in the table containing extra info about the LPS channels."
|
|
INDEX { lpsModuleIndex }
|
|
::= { lpsChannelInfoTable 1 }
|
|
|
|
LpsChannelInfoEntry
|
|
::= SEQUENCE {
|
|
lpsChannelInfoEntryIndex INTEGER,
|
|
lpsGroupChannel1 DisplayString,
|
|
lpsCustomText1Channel1 DisplayString,
|
|
lpsCustomText2Channel1 DisplayString,
|
|
lpsGroupChannel2 DisplayString,
|
|
lpsCustomText1Channel2 DisplayString,
|
|
lpsCustomText2Channel2 DisplayString,
|
|
lpsGroupChannel3 DisplayString,
|
|
lpsCustomText1Channel3 DisplayString,
|
|
lpsCustomText2Channel3 DisplayString,
|
|
lpsGroupChannel4 DisplayString,
|
|
lpsCustomText1Channel4 DisplayString,
|
|
lpsCustomText2Channel4 DisplayString
|
|
}
|
|
|
|
lpsChannelInfoEntryIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "index"
|
|
::= { lpsChannelInfoEntry 1 }
|
|
|
|
lpsGroupChannel1 OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..25))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The assigned group of LPS Channel 1."
|
|
::= { lpsChannelInfoEntry 2 }
|
|
|
|
lpsCustomText1Channel1 OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..50))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Custom Text 1 for LPS Channel 1."
|
|
::= { lpsChannelInfoEntry 3 }
|
|
|
|
lpsCustomText2Channel1 OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..50))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Custom Text 2 for LPS Channel 1."
|
|
::= { lpsChannelInfoEntry 4 }
|
|
|
|
lpsGroupChannel2 OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..25))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The assigned group of LPS Channel 2."
|
|
::= { lpsChannelInfoEntry 5 }
|
|
|
|
lpsCustomText1Channel2 OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..50))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Custom Text 1 for LPS Channel 2."
|
|
::= { lpsChannelInfoEntry 6 }
|
|
|
|
lpsCustomText2Channel2 OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..50))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Custom Text 2 for LPS Channel 2."
|
|
::= { lpsChannelInfoEntry 7 }
|
|
|
|
lpsGroupChannel3 OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..25))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The assigned group of LPS Channel 3."
|
|
::= { lpsChannelInfoEntry 8 }
|
|
|
|
lpsCustomText1Channel3 OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..50))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Custom Text 1 for LPS Channel 3."
|
|
::= { lpsChannelInfoEntry 9 }
|
|
|
|
lpsCustomText2Channel3 OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..50))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Custom Text 2 for LPS Channel 3."
|
|
::= { lpsChannelInfoEntry 10 }
|
|
|
|
lpsGroupChannel4 OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..25))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The assigned group of LPS Channel 4."
|
|
::= { lpsChannelInfoEntry 11 }
|
|
|
|
lpsCustomText1Channel4 OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..50))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Custom Text 1 for LPS Channel 4."
|
|
::= { lpsChannelInfoEntry 12 }
|
|
|
|
lpsCustomText2Channel4 OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..50))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Custom Text 2 for LPS Channel 4."
|
|
::= { lpsChannelInfoEntry 13 }
|
|
|
|
--==========================================================================
|
|
-- The OBJECT IDENTIFIERs for the traps must be defined in this manner to
|
|
-- satisfy the NetSight MIB compiler; in particular, nodes cannot be defined
|
|
-- concatenated in a single line, but must be defined explicitly node by node
|
|
-- (hence, the dcPwrSysDevice.dcPwrSysTraps.dcPwrSysTrap definition)
|
|
-- In addition, forward references to extra system variables are needed for
|
|
-- dcPwrSysTrap by CastleRock SNMPc for event filter and match features.
|
|
--==========================================================================
|
|
dcPwrSysTrap OBJECT IDENTIFIER ::= { dcPwrSysTraps 0 }
|
|
|
|
--==========================================================================
|
|
-- Start of Traps
|
|
--==========================================================================
|
|
|
|
dcPwrSysAlarmActiveTrap NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
dcPwrSysRectAlrmStringValue,
|
|
dcPwrSysRectAlrmIndex,
|
|
dcPwrSysRectAlrmSeverity,
|
|
dcPwrSysSiteName,
|
|
dcPwrSysTimeStamp,
|
|
dcPwrSysAlarmTriggerValue
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "A trap issued when one of the alarms on the became active."
|
|
::= { dcPwrSysTrap 1 }
|
|
|
|
dcPwrSysAlarmClearedTrap NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
dcPwrSysRectAlrmStringValue,
|
|
dcPwrSysRectAlrmIndex,
|
|
dcPwrSysRectAlrmSeverity,
|
|
dcPwrSysSiteName,
|
|
dcPwrSysAlarmTriggerValue
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "A trap issued when one of the active alarms on the is cleared."
|
|
::= { dcPwrSysTrap 2 }
|
|
|
|
dcPwrSysRelayTrap NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
dcPwrSysRelayIntegerValue,
|
|
dcPwrSysRelayStringValue,
|
|
dcPwrSysRelayIndex,
|
|
dcPwrSysRelaySeverity,
|
|
dcPwrSysSiteName
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "A trap issued from a change in state in one of the relays on the DC power system controller."
|
|
::= { dcPwrSysTrap 3 }
|
|
|
|
dcPwrSysComOKTrap NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
dcPwrSysSiteName
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "A trap to indicate that communications with a DC power system controller has been established."
|
|
::= { dcPwrSysTrap 4 }
|
|
|
|
dcPwrSysComErrTrap NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
dcPwrSysSiteName
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "A trap to indicate that communications with a DC power system controller has been lost."
|
|
::= { dcPwrSysTrap 5 }
|
|
|
|
dcPwrSysAgentStartupTrap NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
dcPwrSysSiteName
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "A trap to indicate that the agent software has started up."
|
|
::= { dcPwrSysTrap 6 }
|
|
|
|
dcPwrSysAgentShutdownTrap NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
dcPwrSysSiteName
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "A trap to indicate that the agent software has shutdown."
|
|
::= { dcPwrSysTrap 7 }
|
|
|
|
dcPwrSysMajorAlarmActiveTrap NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
dcPwrSysRectAlrmStringValue,
|
|
dcPwrSysRectAlrmIndex,
|
|
dcPwrSysRectAlrmSeverity,
|
|
dcPwrSysSiteName
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "A trap issued as a summary of DC power system status. It is sent when the system goes into in Major Alarm"
|
|
::= { dcPwrSysTrap 8 }
|
|
|
|
dcPwrSysMajorAlarmClearedTrap NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
dcPwrSysRectAlrmStringValue,
|
|
dcPwrSysRectAlrmIndex,
|
|
dcPwrSysRectAlrmSeverity,
|
|
dcPwrSysSiteName
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "A trap issued as a summary of DC power system status. It is sent when the system comes out of Major Alarm"
|
|
::= { dcPwrSysTrap 9 }
|
|
|
|
dcPwrSysMinorAlarmActiveTrap NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
dcPwrSysRectAlrmStringValue,
|
|
dcPwrSysRectAlrmIndex,
|
|
dcPwrSysRectAlrmSeverity,
|
|
dcPwrSysSiteName
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "A trap issued as a summary of DC power system status. It is sent when the system goes into in Minor Alarm"
|
|
::= { dcPwrSysTrap 10 }
|
|
|
|
dcPwrSysMinorAlarmClearedTrap NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
dcPwrSysRectAlrmStringValue,
|
|
dcPwrSysRectAlrmIndex,
|
|
dcPwrSysRectAlrmSeverity,
|
|
dcPwrSysSiteName
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "A trap issued as a summary of DC power system status. It is sent when the system comes out of Minor Alarm"
|
|
::= { dcPwrSysTrap 11 }
|
|
|
|
|
|
--==========================================================================
|
|
-- Start of External Controls
|
|
--==========================================================================
|
|
|
|
dcPwrSysResyncAlarms OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Send/Resend all active alarms that were previously sent through SNMP notification."
|
|
::= { dcPwrExternalControls 1 }
|
|
|
|
--==========================================================================
|
|
-- Alarm Trigger
|
|
--==========================================================================
|
|
dcPwrSysAlarmTriggerValue OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION ""
|
|
::= { dcPwrVarbindNameReference 1 }
|
|
|
|
--==========================================================================
|
|
-- Time stamp
|
|
--==========================================================================
|
|
dcPwrSysTimeStamp OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION ""
|
|
::= { dcPwrVarbindNameReference 2 }
|
|
|
|
END
|